In the event of a temporary power failure, the air conditioner
will automatically restart in the same operating mode as
before, once the power supply is restored.
The louver automatically swings to right and left. The
direction and the angle of the air flow can be easily
changed.
The optimum fan speed is available with the difference
between the indoor temperature and the setting
temperature.
The computer effectively dehumidifies the air.
(Air conditioner will operate with gentle cooling operation.)
When the timer reaches the set time, the air conditioner will
be turned off.
When the timer reaches the set time, the air conditioner will
be started.
The microcomputer gradually changes the room
temperature automatically to afford a comfortable night's
sleep.
Combines the OFF timer and the ON timer for one cycle.
(OFF
Æ ON or ON Æ OFF) Starts operation from the OFF
timer or ON timer, whichever is closer to the current time.
Combines the operation of the OFF timer and ON timer (the
cycle described in the PROGRAM timer above) so they
repeat the same cycle every day. Starts operation from the
OFF timer or ON timer, whichever is closer to the current
time.
When the ZONE CONTROL button is pressed while multiple
air conditioners are being centralized controlled, only the
preset air conditioners stop.
The energy conservation mode (ENERGY SAVE) raises the
set temperature slightly in the cooling mode and lowers the
set temperature in the heating mode, using a computer
program to economically control the operation of the unit.
One remote controller can control up to 16 air conditioners.
All the air conditioners can be operated with the same
setting.
Two remote controllers can be connected to one air
conditioner unit. The air conditioner operation contents are
the remote controller setting contents set later. (Both remote
controllers show the same display.)
In the auto mode, the air conditioner switches automatically
between cooling and heating, keeping the room at or around
the set temperature.
Cooling capacity is variable over a wide range, so the inside
environment stays comfortable with very little variation in
temperature or humidity.
NOTE: The parenthesis ( ) shows that the function is installed or not according to models.
13
BACK
NEXT
1.4 EASY OPERATION BY REMOTE CONTROLLER
1.4.1 WIRELESS REMOTE CONTROLLER
1
NON STOP CLOCK
2
1
Signal Transmitter
3
4
TIMERSET
AUTOAUTO
MASTER
CONTROL
THRTMOSTAT
Transmits control signals to the air conditioner.
2
SET TIME Buttons
/
( )
Use to make timer settings, to change the time, and to
set the clock to the current time.
3
TIMER Button
Use to select the various timer modes(OFF timer, ON
timer, PROGRAM timer, SLEEP timer, NON-STOP
operation).
4
MASTER CONTROL Switch
Use to select the various operating modes (AUTO,
COOL, DRY, FAN).
5
Remote Control Unit Display (LCD)
6
START
STOP Button
Press to start and stop operation.
7
ACL Button
5
6
7
8
9
10
11
LOW MED
26
28
START STOP
TIME ADJUST
TEST RUN
HIGH
LOUVER
30
ACL
TIME
COOL
DRY
FAN
FAN
CONTROL
18
20
22
24
19 21 23 25 27
12
8
TEST RUN Button
This button is used when installing the air conditioner,
and should not be used under normal conditions,
since it will cause the air conditioner's thermostat
function to stop operating properly.
If this button is pressed during normal operation, the
unit will switch to test operation mode, and the room
unit's operation lamp and timer lamp will begin to flash
simultaneously.
To stop the test operation mode, press the Operation
Stop button to stop the air conditioner.
9
TIME ADUST Button
10
LOUVER Button
Press it start and stop auto louver operation.
Press it to turn on and press again to turn off.
11
FAN CONTROL Switch
Use to select the fan speed (AUTO, LOW, MED,HIGH).
12
THERMOSTAT Control Switch
Use to set the desired room temperature.
Depending on the conditions in your room, the
displayed temperature may differ from the actual room
temperature.
14
BACK
TIMERSET
TIME
STARTSTOP
NON STOP CLOCK
SLEEP
TIMER
PROGRAM
OFF ON
1
2
3
NEXT
Remote Control Unit Display
Indicates the timer setting.
1
Transmit Indicator
This indicator is displayed when a signal is sent to the
air conditioner.
2
Time Display
Indicates either the current time or the timer setting (24hour display,from 0:00 to 23:59).
When the word "CLOCK" is shown, the display
indicates the current time.
When the word " TIMER " is shown, the display
indicates the timer setting.
2
Time Mode Display
Indicates the timer mode (OFF timer, ON timer,
PROGRAM timer, SLEEP timer, NON-STOP).
When the remote control unit's batteries run low, the
display (especially the transmit indicator) will become
faint. Use this as a guide to indicate when batteries
should be replaced.
To facilitate explanation, the accompanying illustration
has been drawn to show all possible indicators ; in actual
operation, however, the display will only show those
indicators appropriate to the current operation.
Signals will not be transmitted properly if a wall, curtain, or other
object is between the air conditioner and the remote control unit.
The air conditioner may fail to operate properly if strong direct
light is allowed to strike the signal receiver. Use a curtain to
shade strong sunlight from windows, and place strong lamps at
a distance away from the signal receiver.
If another electric appliance is operated by the remote control
unit move the appliance away or consult with authorized service
personnel.
Do not place the remote control unit in locations where it may be
subjected to heat from direct sunlight or from heating apparatus.
Do not subject the remote control unit to strong impacts, and do
not allow water or other liquids to splash on it.
When the remote control unit is used in rooms furnished with
instant-lighting type fluorescent lamps, the air conditioner may
fail to receive control signals correctly.Consult with authorized
service personnel when purchasing a new fluorescent lamp.
15
BACK
NEXT
PREPARATION
Prepare the Remote Control Unit
Load batteries in the remote control unit and set the clock to the current time.
Set the Current TimeLoad Batteries (R6P / LR6 x 4)
Pull the battery cover in the direction of the
1
arrow to open it.
Press the TIME ADJUST button.
1
(Use the tip of a pen, etc., to press the button.)
CLOCK
Insert batteries, taking care to align the and
2
-
polarities correctly.
Push the battery cover in the direction of the
3
arrow to close it.
CAUTION!
Take precautions to prevent infants from accidentally swallowing
batteries.
When not using the remote control unit for an extended period,
remove the batteries to avoid possible leakage and damage to
the unit.
If leaking battery fluid comes in contact with your skin, eyes, or
mouth, immediately wash with copious amounts of water, and
consult your physician.
Dead batteries should be removed quickly and disposed of
properly, either by placing in a public battery collection
receptacle, or by returning to a properly equipped dealer.
Do not attempt to recharge dry batteries.
NOTE:
Never mix new and used batteries, or batteries of different
types.
Batteries should last about one year under normal use. If the
remote control unit's operating range becomes appreciably
reduced, replace the batteries and press the ACL button with
the tip of a ballpoint pen or other small object.
+
TIMERSET
AUTOAUTO
COOL
DRY
VASTER
CONTROL
FAN
FAN
CONTROL
TIME
START STOP
TIME ADJUST
LOW MED
HIGH
TEST RUN
ACL
TIME ADJUST
button
<Remote Control Unit Display>
The current time display will flash.
CLOCK
Press the SET TIME buttons to set the display
2
to the current time.
button: Press to advance the time setting.
button: Press to reverse the time setting.
(The time setting will be changed by 1 minute each time
a button is pressed; the time setting will change
continuously in 10-minute increments when a button is
held depressed.)
<Remote Control Unit Display>
The current time display will flash.
CLOCK
TIMERSET
(Example: When the display is set to 21:53)
TIME
START STOP
BACK
NEXT
Press the TIME ADJUST button once again.
3
<Remote Control Unit Display>
The current time display will stop flashing.
CLOCK
To Use the Remote Control Unit
Install the remote control so that the front is facing the
photocell.
Install the remote control with a distance of 7 m
between the remote control and the grille photocell as
the criteria.
However, when installing the remote control, check that
it operates positively.
Photocell
Remote control unit
Remote Control Unit Holder
This holder allows the remote control unit to be
mounted on a post or wall.
If the holder is installed in a place that allows the
signals from the remote control unit to be properly
received by the main unit, the air conditioner can be
controlled without removing the remote control unit
from its holder.
1
Installing the holder.
2
Setting the remote control unit.
Remote
Screw
(
medium
)
control
unit
Machine screw
(
)
small
Hook
Battery
cover
THRTMOSTAT
MASTER
CONTROL
FAN
CONTROL
AUTOAUTO
COOL
18
1921 23 25 27
DRY
FAN
LOW MED
HIGH
TIME ADJUST
TEST RUN
ACL
LOUVER
TIMERSET
TIME
START STOP
NON STOP CLOCK
2022
24
26 28
30
1
2
THRTMOSTAT
MASTER
CONTROL
FAN
CONTROL
AUTOAUTO
COOL
18
19 21 23 25 27
DRY
FAN
LOW MED
HIGH
TIME ADJUST
TEST RUN
ACL
LOUVER
TIMERSET
TIME
START STOP
NON STOP CLOCK
20
22 24
26 28
30
THRTMOSTAT
MASTER
CONTROL
FAN
CONTROL
AUTOAUTO
COOL
18
19 21 23 25 27
DRY
FAN
LOW MED
HIGH
TIME ADJUST
TEST RUN
ACL
LOUVER
TIMERSET
TIME
START STOP
NON STOP CLOCK
20
22 24
26
28 30
BACK
NEXT
AUTOMATIC OPERATION
During AUTO operation, the operating mode (cooling, etc.) will be selected automatically in accordance with room temperature
conditions at the time operation is started.
To Select Mode Operation
Set the MASTER CONTROL switch to the AUTO position.
1
Press the START STOP button.
2
Operation will start (operation will not start if the ON timer has been set).
<Indoor Unit Display>
The OPERATION indicator lamp will light.
To Set the Thermostat
Set the THERMOSTAT control to the desired position.
Range of temperature settings:
19, 21, 23, 25, 27˚C
To Set the Fan Speed
Set the FAN CONTROL switch to the desired position.
When the FAN CONTROL switch is set to the AUTO position,
the optimum fan speed will be selected automatically in accordance with room
temperature and other conditions.
To Stop Operation
Press the START STOP button.
About Automatic Operation
When the room temperature is 2°C higher than the set
temperature, the mode will switch between cooling and dry.
Most effective cooling will be produced by setting the FAN
CONTROL to HIGH.
During dry mode operation, FAN setting is switched to LOW for
gentle cooling effect, and the room fan may stop rotating
temporarily.
Cooling Operation
Dry Operation
2
C
Setting temperature
Thermostat control
BACK
NEXT
MODE OPERATION (COOL, DRY)
Use the dry mode when you wish to eliminate room humidity without lowering the room temperature excessively.
To Select Mode Operation
NON STOP CLOCK
Set the MASTER CONTROL switch to the desired position (COOL,
1
TIMERSET
AUTOAUTO
MASTER
CONTROL
THRTMOSTAT
18
START STOP
TIME
TIME ADJUST
TEST RUN
COOL
DRY
FAN
2022
192123 25 27
1
FAN
CONTROL
24
26 28
LOW MED
30
ACL
HIGH
LOUVER
2
DRY).
Press the START STOP button.
The unit will start operating in the selected mode (operation will not start if the ON
timer has been set).
<Indoor Unit Display>
The OPERATION indicator lamp will light.
To Set the Thermostat
NON STOP CLOCK
TIMERSET
AUTOAUTO
MASTER
CONTROL
THRTMOSTAT
18
NON STOP CLOCK
TIMERSET
AUTOAUTO
MASTER
CONTROL
THRTMOSTAT
18
Set the THERMOSTAT control to the desired position.
2
START STOP
TIME
TIME ADJUST
TEST RUN
COOL
DRY
FAN
20
22 24
19 21 23 25 27
FAN
CONTROL
26 28
LOW MED
30
ACL
HIGH
LOUVER
Range of temperature settings: 18 to 30˚C
To Set the Fan Speed
Set the FAN CONTROL switch to the desired position.
START STOP
TIME
TIME ADJUST
TEST RUN
COOL
DRY
FAN
20
22 24
19 21 23 25 27
FAN
CONTROL
LOW MED
26
28 30
ACL
HIGH
LOUVER
When the FAN CONTROL switch is set to the AUTO position, the optimum fan
speed will be selected automatically in accordance with room temperature and
other conditions.
During the dry mode, fan speed is set automatically and cannot be changed.
To Stop Operation
Press the STARTSTOP button.
About Mode Operation
Cooling
When using the cooling mode, set the temperature to a value
lower than the actual current room temperature. If it is set higher
than the current room temperature, the unit will not enter the
cooling mode and only the fan will operate.
Drying
In the dry mode, since preference will be given to removing
humidity, the room temperature may not be lowered to the
selected value.
When using the dry mode, set the temperature to a value lower
than the actual current room temperature. If it is set higher than
the current room temperature, the unit will not enter the dry
mode.
In the dry mode, the optimum fan speed will be set automatically
and cannot be changed. The fan will emit a very weak stream of
air.
In the dry mode, the room fan may occasionally stop in order to
prevent room humidity from rising.
BACK
NEXT
MODE OPERATION (FAN)
Use this mode when you wish to recirculate the air in your room.
To Select Mode Operation
Set the MASTER CONTROL switch to the FAN position.
NON STOP CLOCK
1
TIMERSET
AUTOAUTO
COOL
MASTER
CONTROL
THRTMOSTAT
18
NON STOP CLOCK
TIMERSET
AUTOAUTO
MASTER
CONTROL
THRTMOSTAT
18
NON STOP CLOCK
START STOP
TIME
TIME ADJUST
TEST RUN
DRY
20
FAN
CONTROL
2224
1921232527
FAN
1
LOW MED
26
28 30
ACL
HIGH
LOUVER
2
Press the START STOP button.
2
Operation will start (operation will not start if the ON timer has been set).
<Indoor Unit Display>
The OPERATION indicator lamp will light.
To Set the Fan Speed
Set the FAN CONTROL switch to the desired position.
START STOP
TIME
TIME ADJUST
TEST RUN
COOL
DRY
FAN
20
22
19 21 23 25 27
FAN
CONTROL
24 26
LOW MED
28 30
ACL
HIGH
LOUVER
When the AUTO fan speed is selected in the FAN mode, the fan speed will
automatically be set on MED.
To Stop Operation
Press the START STOP button.
TIMERSET
AUTOAUTO
COOL
MASTER
CONTROL
THRTMOSTAT
18
DRY
20
FAN
CONTROL
22
19 21 23 25 27
FAN
24 26
TIME
START STOP
TIME ADJUST
LOW MED
HIGH
28 30
TEST RUN
LOUVER
ACL
NOTE:
Do not allow the air conditioner's air stream to directly strike a kerosene or other space heater.
Incomplete combustion or fires may result.
BACK
NEXT
TIMER OPERATION
Press the START•STOP button; after the unit starts operation perform the following procedure:
OFF Timer/ON Timer
TIMER
OFF
TIMERSET
TIME
START STOP
Example: To set for OFF timer
TIMER
ON
TIMERSET
TIME
START STOP
1
Press the TIMER button, so that the timer mode display shows only
OFF or ON.
The timer will start operating (if the ON timer has been set, the unit will stop
operating).
<Indoor Unit Display>
The TIMER indicator lamp will light.
Each time the button is pressed the timer function changes in the following order:
RESETSLEEPOFFON
PROGRAM (OFF ON, OFF ON)
Example: To set for ON timer
TIMER
OFF
TIMERSET
TIME
START
STOP
Example:To set the ON timer to turn
the air conditioner off at
00:00
To Confirm or Change Settings Before
Starting Operation
To confirm settings
Press the TIMER button once. (The timer
setting information will be displayed for 15
seconds after the TIMER button is
pressed.)
To change settings
Confirm the settings as noted above, then
press the SET TIME button and TIMER
button as necessary to change the
desired timer setting. (The timer settings
will be displayed for 15 seconds after the
button is pressed.)
After confirming or changing the settings,
press the START•STOP button to start
operation.
Press the SET TIME buttons to adjust the time (the accompanying
2
illustration shows the OFF timer).
Button: Press to advance the time setting.
Button: Press the reverse the time setting.
(Each time a button is pressed the time will change in 5-minute increments; when
held depressed the time will change continuously in 10-minute increments.)
To Change the Timer Setting During
Operation
Operate as noted in step 2.
To Change the Timer Mode During
Operation
Press the TIMER button and set the unit to
the desired mode.
To Cancel the Timer Mode During
Timer Operation
Press the TIMER button and set the display
to "NON STOP" (the unit will switch to nonstop operation).
To Stop Operation During Use of
Timer Mode
Press the START•STOP button.
During operation of the ON timer, the
indoor unit's OPERATION indicator lamp
will not light (the TIMER indicator lamp
will light instead).
When the time reaches the set value, the
unit will start operation and the
OPERATION indicator lamp will light.
BACK
NEXT
PROGRAM TIMER
Press the START•STOP button; after the unit starts operation perform the following procedure:
To Use the PROGRAM Timer
Press the TIMER button to select the "OFF" and "ON" timer modes
1
TIMER
OFF
TIMERSET
TIME
START STOP
To select OFF timer mode
and make the respective timer settings.
Press the TIMER button so that the display shows OFF ON
2
or OFF ON as desired.
TIMER
ON
TIMERSET
TIME
START STOP
To select ON timer mode
To Confirm or Change Settings Before
Starting Operation
See TIMER OPERATION
To Change Settings After Starting
Operation
<Remote Control Unit Display>
For 15 seconds, the display will switch between the "OFF timer" time and the "ON
timer" time. Then, it will switch to display the time setting for the timer operation
which will function first (the one closest to the current actual time).
<Indoor Unit Display>
The TIMER indicator lamp will light.
(Example: To set the OFF timer for 23:35 and the ON timer for 6:00)
Displayed
alternately
PROGRAM
TIMER
OFF
PROGRAM
TIMER
ON
After 15 seconds
TIMER
PROGRAM
OFF ON
To Change the Timer Mode During
Operation
Press the TIMER button and set the unit to
the desired mode.
To Stop Operation During Use of
Timer Mode
See TIMER OPERATION
1 Follow the instructions in step 1 of p.15 to
display the timer mode whose time
setting you wish to change.
2.Follow the instructions in step 2 to p.15 to
change the timer setting.
To change both the OFF timer and ON
timer settings, perform both of the above
steps 1,2 for each setting.
3.Press the TIMER button to display either
"OFF ON" or "OFF ON".
To Cancel the Timer Mode During
Timer Operation
Press the TIMER button and set the display
to "NON STOP" (the unit will switch to non
stop operation).
BACK
NEXT
SLEEP TIMER OPERATION
The SLEEP timer is different from other timer functions, in that it is used to set the amount of time the air conditioner operates
until it turns off (in the example shown, the air conditioner will turn off two hours after the current time).
Press the START•STOP button; after the unit starts operation perform the following procedure:
To Use the SELECT Timer
Press the TIMER button, so that the timer mode display shows only
1
SLEEP.
SLEEP
TIMER
OFF
TIMERSET
TIME
START STOP
<Indoor Unit Display>
The TIMER indicator lamp will light.
SLEEP
TIMER
OFF
TIMERSET
Example:To set the SLEEP timer
to turn the air conditioner
off after two hours.
TIME
START STOP
Press the SET TIMER buttons to adjust the time (the accom-
2
panying illustration shows the SLEEP timer).
Button: Press to advance the time setting
Button: Press to reverse the time setting
(Each time a button is pressed the time will change in 5-minute increments; when
held depressed the time will change continuously in 10-minute increments.)
To Confirm or Change Settings Before Starting Operation
See TIME OPERATION
To Change the Timer Setting During Operation
Operate as noted in step 2.
To Change the Timer Mode During Operation
Prese the TIMER button and set the unit to the desired mode.
To Cancel the Timer Mode During Timer Operation
Press the TIMER button and set the display to "NON STOP" (the unit will switch to
non-stop operation).
To Stop Operation During Use of Timer Mode
See TIME OPERATION
About the SLEEP Timer
This function changes the room thermostat setting over time, to
prevent excessive room cooling while you sleep. After the set time
has elapsed, the air conditioner operation turns off automatically.
During cooling and dry operation
When the sleep timer is set, the thermostat setting is raised 1°C
each hour. After the thermostat setting has been raised a total
of 2°C, that setting is maintained for the remainder of the set
time, and operation is then stopped.
SLEEP Timer setting
1 hour
Set time
1
c
Stop
2
c
BACK
NEXT
HOW TO CONTROL AIR DIRECTION
The power must be turned on in order to adjust the louver direction (attempting to move the
louvers by hand could result in damage).
CAUTION!
During cooling operation, if the louvers are adjusted to blow air directly downward for extended
periods of time, water may condense on the outlet port and louvers, and drip onto the floor.
Horizontal AUTO LOUVER
When the remote control unit's LOUVER button is pressed,
the automatic louver lamp lights and the direction of air flow
changes automatically between up and down.
Louver can be stopped at any position when the switch is
pressed to turn it off.
Horizontal louvers
CARE AND MAINTENANCE
Before cleaning the unit, be sure to stop the unit and disconnect the power supply.
CAUTION!
Cleaning the Air Filter
A clogged air filter reduces the airflow and weakens the
cooling effect. If the air filter remains clogged, it may cause
a defect.
How to remove the air filter
1. Push the intake grille pushbuttons two places until
you hear a "click".
Open the intake grille.
PUSH
Turn off the electrical breaker.
A fan operates at high speed inside the unit, and personal injury could result.
PUSH
How to clean the air filter
Clean the dust from the air filter by washing the filter with
water or blow it away with a vacuum cleaner. If the air filter
is very dirty, rinse the filter with warm or cool water mixed
with synthetic detergent and then wash the detergent
solution away with clean water and dry it.
Do not dry the air filter by exposing it to direct sunlight
or fire. This may damage the filter.
Avoid using hot water (40˚C or higher) to wash the
filter. This may damage the filter.
2. Pull the air filter once downward.
The air filter then comes out.
Cleaning the Indoor Unit
Wipe the cabinet with a dry soft cloth or clean with a cloth
dipped in hot water.
Use of a synthetic detergent is effective for cleaning.
Gasoline
Hot
Water
Polishing powder
Do not use gasoline, thinner, alcohol, benzine, chemicals,
polishing powder, etc. to clean the cabinet.
Benzine
BACK
NEXT
ERRORS AND SELF DIAGNOSIS
Operation can be checked by lighting and flashing of the grille display section OPERATION and TIMER lamps.
Perform judgment in accordance with the following:
MANUAL
OperationTimerLouver
OFF
POWER
ON
NORMAL
AUTO
RESTART
AUTO
Power ON
When the power is turned on, the grille display section
OPERATION and TIMER lamps flash quickly and
alternately.
When operation starts thereafter, flashing stops.
Test running
When the air conditioner is run by pressing the remote
control unit test running button, the OPERATION and
TIMER lamps flash slowly at the same time
Error
The OPERATION and TIMER lamps operate as follows
according to the error contents.
OPERATION
LAMP
TIMER
LAMP
OPERATION
LAMP
TIMER
LAMP
OPERATION
LAMP
TIMER
LAMP
Error displayError contents
0.5sec
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
0.1sec
0.1sec
0.5sec
0.1sec
5sec
0.1sec
0.5sec
5sec
0.1sec
0.5sec
5sec
0.1sec
0.5sec
Single quick
flash
repeated
0.1 sec ON/
OFF repeated
Two quick
flashes
repeated
0.1 sec ON/
OFF repeated
Six quick
flashes
repeated
0.1 sec ON/
OFF repeated
Room
temperature
thermistor
abnormal
temperature
detected
Piping
thermistor
abnormal
remperature
detected
Float switch
ON for 3
minutes or
longer
BACK
NON STOP
OFF ON
TIMER
PROGRAM
REPEAT
FAN AUTO
FAN HIGH
FAN MED
FAN LOW
AUTO
HEAT
FAN
COOL
CLOCK
TIMER
TEMP
SET
TIME
ENERGY
SAVE
ZONE
CONTROL
LOUVER
START
STOP
TIMER
MODE
CLOCK ADJUST
FAN
CONTROL
MASTER
CONTROL
DEFROSTTEST
OFF
ON
ON
OFF
SET
TEMP
1
2
3
4
5
6
7
89
10
11
12
13
14
Remote Controller
Display
NEXT
1.4.2 LIQUID CRYSTAL REMOTE CONTROLLER
START/STOP Button
1
Press to start and stop operation.
2
Operation Lamp
Lights up during operation and when the timer is on
3
LOUVER Button
Press it start and stop auto louver operation. Press it to
turn on and press again to turn off.
4
LOUVER Lamp
Lights up during auto louver operation.
For explanatory purposes, the figure showing
the remote controller display shows all
possible displays.
The actual display shows only that area that
is being adjusted or used.
5
ZONE CONTROL Button
Use to turn the zone control on and off.
6
ZONE CONTROL Lamp
Lights up when the unit is in the zone control mode.
ENERGY SAVE Button
7
Turns the energy efficient mode on and off.
8
ENERGY SAVE Lamp
Lights up when the unit is in the energy save mode.
9
CLOCK ADJUST Button
10
TIMER MODE Button
Use to change timer modes (NON STOP, OFF TIMER,
ON TIMER, PROGRAM TIMER, REPEAT TIMER).
11
SET TIME Button (/)
Use to change the timer settings,
and to set the current time.
12
SET TEMP. Button (/)
Use to change the temperature setting.
13
FAN CONTROL Button
Use to select the fan speed (AUTO, HIGH, MED, LOW).
116
14
MASTER CONTROL Button
Use to select the various operating modes (AUTO,
HEAT, FAN, COOL).
BACK
NON STOP
OFF ON
TIMER
PROGRAM
REPEAT
FAN AUTO
FAN HIGH
FAN MED
FAN LOW
AUTO
HEAT
FAN
COOL
CLOCK
TIMER
TEMP
DEFROSTTEST
OFF
ON
ON
OFF
45
6
7
321
NEXT
NAME AND FUNCTION OF PARTS
1
Remote Controller Display
* For explanatory purposes, the above figure shows all
possible displays. The actual display shows only that
area being adjusted or used.
Clock Display (CLOCK/TIMER)
Displays current or timer times (0:00 to 23:59).
2
Set Temperature Display (TEMP.)
Displays the set temperature.
Depending on the usage circumstances of the unit
(room width, outdoor temperature etc.)l, the displayed
temperature may differ from the actual room
temperature.
3
Operation Mode Display
Displays the operation mode (AUTO, HEAT, FAN,
COOL).
4
Timer Mode Display
Displays the timer mode (NON STOP, OFF TIMER, ON
TIMER, PROGRAM, REPEAT).
5
Fan Speed Display
Displays the current fan speed.
6
DEFROST Display
Displayed during defrosting.
7
TEST Display
Displayed during test operation.
PREPARATION
Set the Current Time
Press the CLOCK ADJUST button for more
1
than three seconds.
CLOCK
TIMER
SET
MODE
TIME
CLOCK ADJUST
ENERGY
SAVE
<Remote Controller Display>
The current time display will flash.
Press the SET TIME button and set the time.
SET
TEMP
ZONE
CONTROL
FAN
CONTROL
LOUVER
MASTER
CONTROL
START
STOP
2
: Use to advance the time forward.
: Use to turn the time back.
(Press once to move the time 1 minute; hold down and
the time will move 10 minutes at a time.)
CLOCK
TIMER
MODE
CLOCK ADJUST
SET
TIME
ENERGY
SAVE
CONTROL
SET
TEMP
ZONE
FAN
CONTROL
LOUVER
MASTER
CONTROL
START
STOP
<Remote Controller Display>
The current time display will flash.
Press the CLOCK ADJUST button again.
3
<Remote Controller Display>
The current time display will stop flashing.
CLOCK
Example: Set the time to 9:31.
117
BACK
NEXT
AUTO CHANGEOVER OPERATION
NON STOP
TIMER
MODE
CLOCK ADJUST
NON STOP
TIMER
MODE
CLOCK ADJUST
SET
TIME
ENERGY
SAVE
SET
TIME
ENERGY
SAVE
SET
TEMP
ZONE
CONTROL
SET
TEMP
ZONE
CONTROL
FAN HIGH
FAN
CONTROL
LOUVER
FAN HIGH
FAN
CONTROL
LOUVER
AUTOCLOCKTEMP
MASTER
CONTROL
START
STOP
AUTOCLOCKTEMP
MASTER
CONTROL
START
STOP
1
To Select AUTO CHANGEOVER Operation
Press the START/STOP button.
1
The unit will start and the operation lamp will light up.
Press the MASTER CONTROL button to select AUTO.
2
The operating mode "AUTO" will appear alone in the display.
2
To Set the Thermostat
Set the SET TEMP. button to the desired temperature.
: Use to raise the set temperature.
(Press the button once to raise the temperature 1°C).
: Use to lower the set temperature.
(Press the button once to lower the temperature 1°C).
The temperature can be set 18 to 30°C .
To Change the Fan Speed
NON STOP
TIMER
MODE
CLOCK ADJUST
SET
TIME
ENERGY
SAVE
SET
TEMP
ZONE
CONTROL
FAN HIGH
FAN
CONTROL
LOUVER
AUTOCLOCKTEMP
MASTER
CONTROL
START
STOP
Press the FAN CONTROL button to select the fan speed.
Every time you press the FAN CONTROL button, the speed changes as shown.
To Stop Operation
Press the START/STOP button.
<Remote Controller Display>
The display contents disappear and only the current time is displayed.
About AUTO CHANGEOVER Operation
When AUTO CHANGEOVER operation is selected, the air
conditioner selects the appropriate operating mode (Cooling or
Heating) in response to your room's temperature.
When AUTO CHANGEOVER operation first selected, the fan
will operate at very low speed for about one minute, during
which time the unit detects the room conditions and selects the
proper operating mode.
When the air conditioner has adjusted your room's temperature
to near the thermostat setting, it will begin monitor operation. In
AUTOHIGHMEDLOW
the monitor operation mode, the fan will operate at low speed. If
the room temperature subsequently changes, the air conditioner
will once again select the appropriate operation (Heating, Cooling)
to adjust the temperature to the value set in the thermostat.
(The monitor operation range is ±2°C relative to the thermostat
setting.)
If the mode automatically selected by the unit is not what you
wish, see MODE OPERATION and select one of the mode operation
(HEAT, COOL, FAN).
BACK
NEXT
MODE OPERATION (HEAT, COOL)
Steps are recorded by the unit, after entering in this information, you need only press the START/STOP button to control the unit.
NON STOP
CLOCKTEMP
TIMER
MODE
CLOCK ADJUST
NON STOP
CLOCKTEMP
TIMER
MODE
CLOCK ADJUST
SET
TIME
ENERGY
SAVE
SET
TIME
ENERGY
SAVE
SET
TEMP
ZONE
CONTROL
SET
TEMP
ZONE
CONTROL
FAN HIGH
FAN
CONTROL
LOUVER
FAN HIGH
FAN
CONTROL
LOUVER
COOL
MASTER
CONTROL
START
STOP
COOL
MASTER
CONTROL
START
STOP
1
To Select Mode Operation
Press the START/STOP button.
1
The unit will start and the operation lamp will light up.
Press the MASTER CONTROL button.
2
Select either HEAT or COOL.
2
To Set the Thermostat
Set the SET TEMP. button to the desired temperature.
: Use to raise the set temperature.
(Press the button once to raise the temperature 1°C ).
: Use to lower the set temperature.
(Press the button once to lower the temperature 1°C ).
Range of temperature setting:
For heating mode....................................................................... 16 to 30°C
For cooling mode........................................................................ 18 to 30°C
To Set the Fan Speed
NON STOP
CLOCKTEMP
TIMER
MODE
CLOCK ADJUST
SET
TIME
SET
TEMP
FAN HIGH
FAN
CONTROL
COOL
MASTER
CONTROL
Press the FAN CONTROL button to select the fan speed.
Every time you press the FAN CONTROL button, the speed changes as shown.
AUTOHIGHMEDLOW
When the AUTO fan speed is selected in the heating or cooling modes, the fan
speed will vary with room conditions.
ENERGY
SAVE
ZONE
CONTROL
LOUVER
START
STOP
To Stop Operation
Press the START/STOP button.
<Remote Controller Display>
The display contents disappear and only the current time is displayed.
About Mode Operation
Heating
Always set the temperature higher than the current room temperature. If it is set lower than the current room temperature, heating will not start.
For about 3 to 5 minutes after starting heating, the fan will operate very slowly, then switch to the selected fan setting.
This period allows the indoor unit's heat-exchanger to perform before emitting warm air.
During defrosting, the heating mode will be temporarily interrupted. DEFROST will be shown on the remote controller display.
Cooling
Always set the temperature lower than the current room temperature. If it is set higher than the current room temperature, the unit will not enter
the cooling mode and only the fan will operate.
BACK
NEXT
MODE OPERATION (FAN)
Steps are recorded by the unit, after entering in this information, you need only press the START/STOP button to control the unit
To Select MODE Operation
NON STOP
CLOCKTEMP
TIMER
MODE
CLOCK ADJUST
NON STOP
TIMER
MODE
CLOCK ADJUST
SET
SET
TIME
TEMP
ENERGY
ZONE
SAVE
CONTROL
CLOCKTEMP
SET
TIME
SET
TEMP
FAN HIGH
FAN
CONTROL
LOUVER
FAN HIGH
FAN
CONTROL
FAN
MASTER
CONTROL
START
STOP
FAN
MASTER
CONTROL
1
2
Press the START/STOP button.
1
The unit will start and the operation lamp will light up.
Press the MASTER CONTROL button to select FAN mode.
2
To Set the Fan Speed
Press the FAN CONTROL button to select the fan speed.
When the AUTO fan speed is selected in the FAN mode, the fan speed will
automatically be set on MED.
ENERGY
SAVE
ZONE
CONTROL
LOUVER
START
STOP
To Stop Operation
Press the START/STOP button.
<Remote Controller Display>
The display contents disappear and only the current time is displayed.
NOTE:
Do not allow the air conditioner's air stream to directly strike a kerosene or other space heater.
Incomplete combustion or fires may result.
About Mode Operation
The room temperature cannot be adjusted in the FAN mode. (The room temperature is not displayed on the remote controller.)
BACK
NEXT
TIMER OPERATION
Press the START/STOP button; after the unit starts operation perform the following procedure:
OFF Timer/ON Timer
CLOCK
OFF
TIMER
TIMER
TIMER
MODE
CLOCK ADJUST
1
ENERGY
SAVE
CLOCK
OFF
TIMER
TIMER
TIMERMODE
Example: Setting the OFF TIMER
CLOCK ADJUST
SET
TIME
SET
TIME
to
TEMP
OFF
ON
ON
OFF
SET
TEMP
ZONE
2
CONTROL
TEMP
OFF
ON
ON
OFF
SET
TEMP
23:35.
FAN HIGH
FAN
CONTROL
LOUVER
FAN HIGH
FAN
CONTROL
COOL
MASTER
CONTROL
START
STOP
COOL
MASTER
CONTROL
Press the TIMER MODE button and display
either OFF Timer or ON Timer.
1
The timer will start operating.
(If you set the ON timer, the air conditioner will stop operating).
Each time the button is pressed the timer function changes in the foollowing order:
RESETOFF ON
REPEATPROGRAM (OFF
Press the SET TIME button and set the timer time.
2
: Use to advance the time forward.
: Use to turn the time back.
(Press once to move the time 1 minute; hold down and the
time will move 10minutes at a time.)
ON,OFF ON)
1
ENERGY
SAVE
ZONE
2
CONTROL
LOUVER
START
STOP
To Confirm or Change Settings Before
Starting Operation
To confirm settings
Press the TIMER MODE button once.
(The timer setting information will be
displayed for 15 seconds after the TIMER
MODE button is pressed.)
To change settings
Confirm the settings as noted above, then
press the SET TIME button and TIMER
MODE button as necessary to change the
desired timer setting. (The timer settings
will be displayed for 15 seconds after the
button is pressed.)
After confirming or changing the settings,
press the START/STOP button to start
operation.
To Change the Timer Settings During
Operation
Operate as noted in step 2.
To Change the Timer Mode During
Operation
Press the TIMER MODE button and set the
unit to the desired mode.
To Cancel the Timer Mode During
Timer Operation
Press the TIMER MODE button and set the
display to "NON STOP" (the unit will switch
to non-stop operation).
To Stop Operation During Use of
Timer Mode
Press the START/STOP button.
BACK
NEXT
PROGRAM Timer/REPEAT Timer
CLOCK
TIMER
PROGRAM
TIMER
MODE
CLOCK ADJUST
ENERGY
SET
TIME
2
SAVE
TEMP
OFF
ON
SET
TEMP
ZONE
CONTROL
FAN HIGH
FAN
CONTROL
LOUVER
COOL
MASTER
CONTROL
START
STOP
Example:
If the OFF timer is set at 23:35 and the
ON timer at 6:00, and the unit is in the
PROGRAM timer mode.(Select the
REPEAT timer mode,
REPEAT" is
shown on the display.)
About Timer Operation
Setting the timer time.
1
Follow steps 1 and 2 See TIME OPERATION and set the times for the ON timer
and OFF timer modes.
Press the TIMER MODE button until the "PROGRAM" or "REPEAT"
2
mode display is shown.
PROGRAM Timer
Combines the OFF timer and the ON timer for one cycle.
(OFF
Starts operation from the OFF timer or the ON timer, whichever
is closer to the current time.
To Confirm or Change Settings Before
Starting Operation
See TIME OPERATION
To Change Settings After Starting
Operation
1
Follow the instructions in step 1 to display
the timer mode whose time setting
you wish to change.
2
Follow the instructions in step 2 to change
the timer setting.
To change both the OFF timer and ON
timer settings, perform both of the above
steps 1,2 for each setting.
Press the TIMER MODE button to display
3
either "OFF ON" or "OFF ON".
ON, or OFF ON)
To Change the Timer Mode During
Operation
Press the TIMER MODE button and set the
unit to the desired mode.
To Cancel the Timer Mode During
Timer Operation
Press the TIMER MODE button and set the
display to "NON STOP" (the unit will switch
to non stop operation).
REPEAT Timer
Combines the operation of the OFF timer and the ON timer (the
cycle described in the PROGRRAM timer above) so they repeat
the same cycle every day.
Starts operation from the OFF timer or the ON timer, whichever
is closer to the current time.
To Stop Operation During Use of
Timer Mode
Press the START/STOP button.
BACK
NEXT
ENERGY SAVE OPERATION
To Use the ENERGY SAVE
NON STOP
CLOCKTEMP
TIMER
SET
MODE
CLOCK ADJUST
About the ENERGY SAVE
TIME
ENERGY
SAVE
SET
TEMP
ZONE
CONTROL
FAN HIGH
FAN
CONTROL
LOUVER
COOL
MASTER
CONTROL
START
STOP
Press the ENERGY SAVE button.
The unit will run in the ENERGY SAVE mode.
To Stop the ENERGY SAVE
Press the ENERGY SAVE button one more time.
The ENERGY SAVE mode will be turned off.
<Remote Controller Display>
The ENERGY SAVE light goes off, and the unit will return to the former operating
conditions.
The energy conservation mode (ENERGY SAVE) raises the set temperature slightly in the cooling mode and lowers the set temperature in the
heating mode, using a computer program to economically control the operation of the unit.
If you press the ENERGY SAVE button while the air conditioner is on, it will change to the conservation mode. If you press the ENERGY SAVE
button while the unit is in the timer mode (ON timer, PROGRAM timer, or REPEAT timer), the unit will go into the conservation mode when the
unit starts with the timer.
If you turn off the air conditioner while in the conservation mode, the mode will be shut off.
The temperature set on the remote controller will not change if the energy save mode is used.
When Heating
After the ENERGY SAVE button is pressed, the set temperature
will be lowered about 1°C every 30 minutes. When it has lowered
a total of 2°C, then it will hold that temperature.
1
c
30 min.
2
c
When Cooling
After the ENERGY SAVE button is pressed, the set temperature
will be raised about 0.5°C every 30 minutes. When it has gone up
a total of 1°C, then it will hold that temperature.
Set to the ENERGY SAVE mode.
30 min.
1
0.5
c
c
Set to the ENERGY SAVE mode.
BACK
NEXT
HOW TO CONTROL AIR DIRECTION
The power must be turned on in order to adjust the louver direction (attempting to move the
CAUTION!
louvers by hand could result in damage).
During cooling operation, if the louvers are adjusted to blow air directly downward for extended
periods of time, water may condense on the outlet port and louvers, and drip onto the floor.
Horizontal AUTO LOUVER
When the remote control unit's AUTO LOUVER button is
pressed, the automatic louver lamp lights and the direction
of air flow changes automatically between up and down.
Louver can be stopped at any position when the switch is
pressed to turn it off.
Horizontal louvers
During heating, point the louvers down so that warn air
reaches the floor.
CARE AND MAINTENANCE
Before cleaning the unit, be sure to stop the unit and disconnect the power supply.
CAUTION!
Cleaning the Air Filter
A clogged air filter reduces the airflow and weakens the
cooling effect. If the air filter remains clogged, it may cause
a defect.
How to remove the air filter
1. Push the intake grille pushbuttons two places until
you hear a "click".
Open the intake grille.
PUSH
Turn off the electrical breaker.
A fan operates at high speed inside the unit, and personal injury could result.
PUSH
How to clean the air filter
Clean the dust from the air filter by washing the filter with
water or blow it away with a vacuum cleaner. If the air filter
is very dirty, rinse the filter with warm or cool water mixed
with synthetic detergent and then wash the detergent
solution away with clean water and dry it.
Do not dry the air filter by exposing it to direct sunlight
or fire. This may damage the filter.
Avoid using hot water (40˚C or higher) to wash the
filter. This may damage the filter.
2. Pull the air filter once downward.
The air filter then comes out.
124
Cleaning the Indoor Unit
Wipe the cabinet with a dry soft cloth or clean with a cloth
dipped in hot water.
Use of a synthetic detergent is effective for cleaning.
Gasoline
Hot
Water
Polishing powder
Do not use gasoline, thinner, alcohol, benzine, chemicals,
polishing powder, etc. to clean the cabinet.
Benzine
100 to 120
Hook shaft
Hook
BACK
NEXT
CARE AND MAINTENANCE
REMOVING / INSTALLING THE INTAKE GRILLE
Removing the intake grille
1. Push the intake grille pushbuttons (two places)
until you hear a "click".
Open the intake grille.
PUSH
PUSH
2. Remove the wire (hanger).
Removing the intake grille by opening it 100° to 120°.
Installing the intake grille
1. Tilt the intake grille 100
° to 120° and hook the
three hooks to the intake grille hook shaft.
2. Install the wire (hanger).
100 to 120
Wire
(
hanger
)
Wire
(
hanger
)
Wire
(
hanger
)
3. Push the intake grille pushbuttons (two places)
until you hear a "click".
Intake grille hooks
PUSH
PUSH
4. Hook the intake grille hooks to the grille
assembly.
BACK
NEXT
ERRORS AND SELF DIAGNOSIS
CLOCK
OFF
ON
TIMER
MODE
CLOCK ADJUST
SET
TIME
ENERGY
SAVE
TEMP
ZONE
CONTROL
SET
FAN
CONTROL
LOUVER
MASTER
CONTROL
START
STOP
If there is a problem with the air conditioner, it will stop
running and "EE:EE"will be displayed instead of the clock.
1. If the operation lamp is on then press the
START/STOP button to turn it off.
2. Press the ENERGY SAVE and the ZONE
CONTROL buttons at the same time for more
than three seconds to start the self diagnosis
check.
An error code will be displayed in the clock
display area.
3. Press the ENERGY SAVE and the ZONE
CONTROL buttons again for more than three
seconds to end the self diagnosis check.
Error codeError
Communication error
(
indoor unit remote controller
Communication error
(
indoor unit outdoor unit
Room temperature sensor open.
Room temperature sensor shorted.
Indoor heat exchanger temperature
sensor open.
Indoor heat exchanger temperature
sensor shorted.
Outdoor heat exchanger temperature
sensor open.
Outdoor heat exchanger temperature
sensor shorted.
Float switch operated.
Outdoor temperature sensor open.
Outdoor temperature sensor shorted.
Discharge pipe temperature
sensor open.
Discharge pipe temperature
sensor shorted.
High pressure abnormal.
Discharge pipe temperature abno
rmal.
)
)
OPERATION DETAILS
Please read and understand the following details regarding this air conditioner.
Operation and Performance
Heating Performance
This air conditioner uses a heat pump which absorbs
heat from outside air and brings it indoors. As a result,
its heating performance is reduced as the temperature
of outside air drops. If you find that insufficient room
heat is produced, we recommend that you use the air
conditioner together with other heating appliances.
Heat-pump type air conditioners use warm-air
recirculation to warm your entire room. As a result,
some time will be required after starting operation until
your entire room becomes warm.
Microcomputer-controlled Automatic Defrosting
When the outside temperature is low and the humidity high,
frost will collect on the outside unit, reducing heater
efficiency. When this happens, the computer will
automatically start the defrost cycle. During the defrost
cycle, the indoor fan will shutdown and DEFROST will be
displayed on the remote controller. It will take anywhere
from 4 to 15 minutes before the air conditioner starts up
again.
When both indoor and outdoor temperatures are high during
use of the heating mode, the outdoor unit's fan may stop at
times.
When the outdoor temperature drops, the outdoor unit's fans
may switch to Low Speed, or one of the fans may stop
intermittently.
When Indoor and Outdoor Temperatures are High
Low Ambient Cooling
126
BACK
NEXT
SYSTEM OPERATION
There are different ways the unit can be controlled.
<Spare Remote Controller>
Two remote controllers can be connected to one air
conditioner unit. The air conditioner operation contents
are the remote controller setting contents set later.
(Both remote controllers show the same display.)
To Use the ZONE CONTROL
NON STOP
CLOCK
TIMER
TIMER
MODE
CLOCK ADJUST
SET
TIME
ENERGY
SAVE
TEMP
OFF
ON
ON
OFF
SET
TEMP
ZONE
CONTROL
FAN HIGH
FAN
CONTROL
LOUVER
COOL
MASTER
CONTROL
START
STOP
When the ZONE CONTROL button is pressed while multiple air conditioners
are being centralized controlled, only the preset air conditioners stop.
Press the ZONE CONTROL button.
Preset units will stop.
To Stop the ZONE CONTROL
Press the ZONE CONTROL button one more time.
Those units that were stopped will start again.
<Control Several Units with just one Remote
Controller>
One remote controller can control up to 16 air conditioners.
All the air conditioners can be operated with the same
setting.
Unit No. 1Unit No. 2Unit No. 16
Auto Restart
When the air conditioner power was temporarily turned off by a power failure, etc., it will
restart automatically after the power recovers. (Operated by settings before the power failure.)
BACK
NEXT
2. SPECIFICATIONS
2.1 AU18, 18R, 25, 25R, 30, 30R, 1-PHASE 50Hz
MODEL
Capacity
Power supply1 ~ 220-240V 50Hz
Total
input
Total
current
EER
Starting currentA
Indoor
unit
Grille
Outdoor
unit
Refrigerant
circuit
Condition
Piping
Cooling
Heating
Cooling
Heating
Cooling
Heating
Cooling
Heating
Fan speedHiMed
Air
circulation
Noise level
(Sound
pressure)
Heat exchanger
Fan type x Q' ty
Fan motor outputkW
Operation control
Dimensions
Weight kg Net/Gross
Dimensions
Weight kg Net/Gross
Fan speed
Air circulation Hi
Noise leveldB
Heat exchanger
Fan type x Q 'ty
Fan motor outputkW
Compressor type
Protection
Dimensions
Weight kg Net/Gross
Disch. pressure kg/cm
Suct. pressure kg/cm
For the room air conditioner to operate satisfactorily, install it as outlined in this
installation manual.
2
Connect the indoor unit and outdoor unit with the room air conditioner piping
cords available from our standard parts. This installation manual describes the
correct connections using the installation set available from our standard parts.
3
Installation work must be performed in accordance with national wiring standards
by authorized personnel only.
4
Do not turn on the power until all installation work is complete.
Be careful not to scratch the air conditioner when handling it.
After installation, explain correct operation to the customer, using the operating manual.
Let the customer keep this installation manual because it is used when the air conditioner is serviced
or moved.
The maximum length of the piping is shown in Table 1. If the units are further apart than this, correct
operation cannot be guaranteed.
81
BACK
NEXT
STANDARD PARTS
The following installation parts are furnished. Use them as required.
INDOOR UNIT ACCESSORIES
Name and Shape Q'ty Application
Coupler heat
insulation
Special nut A
(large flange)
Special nut B
(small flange)
Template
Remote controller
Machine screw
(small)
Remote controller holder
2 For indoor side
pipe joint
4 For installing
indoor unit
4 For installing
indoor unit
1 For ceiling hole
cutting
1
1 For installing
the remote con troller
1 For mounting
the remote con troller
OUTDOOR UNIT ACCESSORIES
Name and Shape Q'ty Application
Hexagon wrench
GRILLE ACCESSORIES
Name and Shape Q'ty Application
Bolt
Washer
Spring washer
1 For air purge
4 For mounting
grille
4 For mounting
grille
4 For mounting
grille
Screw (medium)
Battery
(R6P/LR6)
2 For installing
the remote con troller holder
4 For remote con troller
Blower cover
insulation
2 For discharged
air
BACK
NEXT
SELECTING THE MOUNTING POSITION
Especially, the installation place is very important for the split type air conditioner because it is very difficult to move from place to place after the
first installation. Decide the mounting position together with the customer as follows: The discharge direction can be selected as shown below.
Fig. 1
4" (100 mm) or more
(4 directions)(3 directions)
Piping positon4" (100 mm)
4" (100 mm) or more
(2 directions)(2 directions)
or more
39" (1,000 mm)
or more
CAUTION
Since 2-way outlet as shown below
causes performance problems, do not
set it.
PipePipe
Indoor unit
(1) Install the indoor unit on a place having a sufficient strent strength
so that it withstands against the weight of the indoor unit.
(2) The inlet and outlet ports should not be obstructed; the air
should be able to blow all over the room.
(3) Leave the space required to service the air conditioner.
(Fig.2)
(4) The ceiling rear height is 11-13/16 inches (300mm) or more.
(5) A place from where the air can be distributed evenly through-
out the room by the unit.
(6) A place from where drainage can be extracted outdoors easi ly.
Fig. 2
Outdoor unit
WARNING
1
Install the unit where it will not be
tilted by more than 5˚
2
When installing the outdoor unit
where it may exposed to strong
wind, fasten it securely.
(1) If possible, do not install the unit where it will be exposed
todirect sunlight.(If necessary, install a blind that does not
interfere with the air flow.)
(2) Install the outdoor unit in a place where it will be free
from being dirty or getting wet by rain as much as possi ble.
(3) Install the unit when connection to the indoor unit is easy.
(4) Do not place animals and plants in the path of the warm
air.
(5) Take the air conditioner weight into account and select a
place where noise and vibration are small.
(6) Select a place so that the warm air and noise from the air
conditioner do not disturb neighbors.
(7) Provide the space shown in Fig. 3 so that the air flow is
not blocked. Also for efficient operation, leave open three
of the four directions front, rear, and both sides.
Fig. 3
1'
(30 cm)
or more
1'4" (40 cm) or more
1' (30 cm)
or more
2' (60 cm)
or more
Strong and durable ceiling
11-13/16" (300 mm)
or more
39" (1,000 mm)
or more
Obstruction
39" (1,000 mm)
or more
2' (60 cm)
or more
BACK
NEXT
CONNECTION PIPE REQUIREMENT
Table 1
Diameter
Small Large
18,000 BTU/h class
25,000 BTU/h (1ø ) class
25,000 BTU/h(3ø ) class
Use 0.7 mm to 1.2 mm thick pipe.
Use pipe with water-resistant heat insulation.
Use pipe that can withstand a pressure of 3,040 kPa.
9.53 mm
(3/8 in)
9.53 mm
(3/8 in)
15.88 mm
(5/8 in)
15.88 mm
(5/8 in)
Maximum
height
25 m
(82 ft)
35 m
(115 ft)
Maximum height
(between indoor
and outdoor)
15 m
(49 ft)
30 m
(98 ft)
ELECTRICAL REQUIREMENT
Electric wire size and fuse capacity.
Table 2
18,000
BTU/h
class
Power
cable
(mm2)
Connection
cord (mm2)
Fuse capacity (A)
Always use H07RN-F or equivalent as the connection
cord.
Install the circuit breaker nearby the units. (Both indoor
unit and outdoor unit)
MAX
MIN
MAX
MIN
3.0
2.5
3.0
2.5
303010
25,000
BTU/h(1ø)
class
3.0
2.51.5
3.0
25,000
BTU/h (3ø)
class
2.0
1.5
1.01.0
INSTALLATION PROCEDURE
Install the room sir conditioner as follows:
35-3/64" ( 890 mm) (Ceiling opening measurement)
1
INDOOR UNIT INSTALLATION
18" (457 mm)
2. Hanging preparations
Firmly fasten the hanging bolts as shown in Fig. 5 or by
another method.
(hanging bolt position)
28-25/32" (731 mm)
(hanging bolt position)
37-13/32" ( 950 mm)
(grille measurement)
Fig. 5
Hole-in anchor
Hole-in plug Concrete Insert
Hanging bolt
M10
Length (H) = h – 9-21/32"
(shown in Fig.6)
BACK
NEXT
4
CONNECTING THE PIPING
1. Flare processing
(1) Cut the connection pipe with pipe cutters so that the pipe
is not deformed.
(2) Holding the pipe downward so that cuttings cannot enter
the pipe, remove the burrs.
(3) Remove the flare nut from the indoor unit pipe and out door unit and assemble as shown in (Table 3) and insert
the flare nut onto the pipe, and flare with a flaring tool.
(4) Check if the flared part “ L” (Fig. 11) is spread uniformly
and that there are no cracks.
Table 3
PipeFlare nut
Small pipe Small (width across flats 22 mm)
Large pipe Large (width across flats 24 mm)
Fig. 11
Width across flats
L dimension
Small pipe
1.8 to 2.0 mm (9.53 mm dia)
L
2. Bending pipes
The pipes are snapped by your hands. Be careful not to
collapse them.
Large pipe
2.2 to 2.4 mm (15.88 mm dia)
When bending the pipe, do not bend it as is. The pipe
will be collapsed. In this case, cut the heat insulating
pipe with a sharp cutter as shown in Fig. 13 and bend it
after exposing the pipe. After bending the pipe as you
want, be sure to put the heat insulating pipe back on the
pipe, and secure it with tape.
Fig. 13
Heat insulating
pipe
Cutter
Cut line
Pipe
CAUTION
1
To prevent breaking of the pipe,
avoid sharp bends. Bend the pipe
with a radius of curvature of 150 mm
or over.
2
If the pipe is bent repeatedly at the
same place, it will break.
3. Connection pipes
(1) Indoor unit side
Fig. 14
Indoor unit
Large pipe
Fig. 12
OKNO
Do not bend the pipes in an angle less than 90˚. When
the pipes are bent and stretched repeatedly, the material
will be hardened, causing the pipes no longer be sent or
stretched. Be sure to limit number of bending and
stretching to three times.
Extend the pipe
by unwinding it.
CAUTION
1
Be sure to apply the pipe against the
port on the indoor unit correctly. If
the centering is improper, the flare
nut cannot be tightened smoothly. If
the flare nut is forced to turn, the
threads will be damaged.
2
Do not remove the flare nut from the
indoor unit pipe until immediately
before connecting the connection pipe.
Small pipe
BACK
NEXT
When the flare nut is tightened properly by your hand,
hold the body side coupling with a separate spanner,
then tighten with a torque wrench. (Fig. 15)
Holding spanner
Fig.15
Body side
Holding spanner
90
Torque wrench
CAUTION
1
[Hold] the torque wrench at its grip,
keeping it in the right angle with the
pipe as shown in Fig. 15, in order to
tighten the flare nut correctly.
Table 4: Flare nut tightening torque
Pipe Tightening torque
Small pipe 310 to 350 kgf • cm
Large pipe 750 to 800 kgf • cm
CAUTION
5
AIR PURGE
1. Air purge
(1) Remove the cap, and connect the gauge manifold and
the vacuum pump to the charging valve by the service
hoses.
(2) Vacuum the indoor unit and the connecting pipes until
the pressure in them lowers to below 1.5 mmHg.
(3) Disconnect the service hoses and fit the cap to the
charging valve (Tightening torque: 70 to 90 kgf•cm).
(4) Remove the blank caps, and fully open the spindles of
the 2-way and 3-way valves with a hexagon wrench
(Torque: 2-way valve: 70 to 90 kgf•cm, 3-way valve: 100
to 120 kgf•cm).
(5) Tighten the blank caps of the 2-way valve and 3-way
valve to the specified torque (200 to 250 kgf•cm).
Fig. 17
Outdoor
unit
Service
hose with
valve core
Refrigerant pipe
Blank cap
Hexagon wrench
3-way valve
Charging
valve
Be sure to connect the large pipe after
connecting the small pipe completely.
(2) Outdoor unit side
Tighten the flare nut of the connection pipe at the outdoor unit valve connector. The tightening method is the
same as that as at the indoor side.
Fig. 16
(Large pipe)
Connection pipe
(Small pipe)
Flare nut
Pipe coupling
2-way valve3-way valve
Cap
Gauge manifold
Lo
Hi
Vacuum pump
Service hose
2. Additional charge
Refrigerant suitable for a piping length of 5 m is charged
in the outdoor unit at the factory. When the piping is
longer than 5 m, additional charging is necessary. For
he additional amount, see the table below.
BACK
NEXT
Table 5
Pipe length
18,000 BTU/h
class
Addi-
25,000 BTU/h
tional
(1 ) class
refrigerant
[18,000 BTU/h class • 25,000 BTU/h (1ø) class]
Between 5 m and 25 m, when using a connection pipe
other than that in the table, charge additional refrigerant
with 0.42 oz (12 g)/3.3 ft(1 m) as the criteria.
[25,000 BTU/h (3ø) class]
Between 5 m and 35 m, when using a connection pipe
other than that in the table, charge additional refrigerant
with 0.42 oz (12 g)/3.3 ft(1 m) as the criteria.
6
ø
25,000 BTU/h
(3 ) class
ø
INSTALLING THE COUPLER
Table 4: Flare nut tightening torque
16 ft 33 ft 49 ft 66 ft 82 ft 98ft 115 ft
(5 m) (10 m) (15 m) (20 m) (25 m) (30 m) (35 m)
2.1 oz4.2 oz6.3 oz8.5 oz
None
(60 g)(120 g)(180 g)(240 g)
2.1 oz4.2 oz6.3 oz8.5 oz10.6 oz1.8 oz
None
(60 g)(120 g)(180 g)(240 g)(300 g)(360 g)
— —
HEAT INSULATION
CAUTION
When moving and installing the air
1
conditioner, do not mix gas other
than the specified refrigerant (R22)
inside the refrigerant cycle.
2
When adding refrigerant, add the
refrigerant from the charging valve
at the completion of work.
The maximum length of the piping is
25m[18,000 BTU/h class•25,000
BTU/h(1 ) class], 35m [25,000
BTU/h (3 ) class]. If the units are
ø
ø
further apart than this, correct opertion can not be guaranteed..
7
ELECTRICAL WIRING
After checking for gas leaks, insulate by wrapping insulation
around the two parts (large and small) of the indoor unit coupling, using the coupler heat insulation.
Fig. 18
Coupler heat
insulation
Body
}
Be sure to overlap
the insulation
CAUTION
Must fit tightly against body without
any gap.
No gap
HOW TO CONNECT WIRING TO THE TERMINALS
A. For solid core wiring (or F-cable)
(1) Cut the wire end with a wire cutter or wire-cutting
pliers, then strip the insulation to about 15/16” (25
mm) to expose the solid wire.
(2) Using a screwdriver, remove the terminal
screw(s) on the terminal board.
(3) Using pliers, bend the solid wire to form a loop
suitable for the terminal screw.
(4) Shape the loop wire properly, place it on the terminal board and tighten securely with the terminal
screw using a screw-driver.
B. For strand wiring
(1) Cut the wire end with a wire cutter or wire-cutting
pliers, then strip the insulation to about 3/8” (10
mm) to expose the strand wiring.
(2) Using a screwdriver, remove the terminal
screw(s) on the terminal board.
(3) Using a round terminal fastener or pliers, securely clamp a round terminal to each stripped wire
end.
(4) Position the round terminal wire, and replace and
tighten the terminal screw using a screwdriver.
Coupler heat insulation
BACK
NEXT
2. Outdoor unit side
(1) Remove the terminal cover of the outdoor unit, and insert
the end of the connection cord and the power cable
[25,000 BTU/h (3ø) class] into the terminal board.
(2) Fasten the connection cord with the cord clamps, and
install the terminal cover.
[18,000 BTU/h class • 25,000 BTU/h (1ø) class]
Fig.23
Terminal
cover
Insulation tube
After passing the connection
cord through the insulation
tube, fasten it with the cord
clamp.
2
1
(N)
N
L
Indoor unit
side terminal
Connection cord
Connection
cord
Connection cord
Green/Yellow
Terminal board
Cord clamp
Insulation tube
Connection cord
Cord
clamp
Insulation tube
(Use VW-1, 0.5 to 1.0 mm thick,
PVC tube as the insulation tube)
2
1
(N)
Outdoor unit
side terminal
1
2
(N)
Green/Yellow
Connection cord
[25,000 BTU/h (3ø) class]
Fig.24
Terminal board
Green/
Yellow
Terminal
cover
Power cable
Insulation tube
Connection
cord
After passing the connection
cord through the insulation
tube, fasten it with the cord
clamp.
Indoor unit
side terminal
Power supply
3
22
1
Green/Yellow
123NTSR
Green/
Yellow
Green/
Yellow
Power
cable
Connection
cord
Cord clamp
Insulation tube
Connection cord
Insulation tube
(Use VW-1, 0.5 to 1.0 mm thick,
PVC tube as the insulation tube)
Connection
Cord clamp
R
S
T
N
3
1
cord
EARTH
EARTH
Outdoor unit
side terminal
BACK
NEXT
8
GRILLE INSTALLATION
1. Blower cover insulation
Install the blower cover insulation only when the outlet
direction is not specified.
Two blower cover insulations are packed with the grille
assembly. Install the blower cover insulation at the diffuser position shown in Fig. 25. At this time, use the piping position as the criteria.
Fig. 25
2 direction example
Fit the blower cover insulation
tightly at the air diffuser section.
A
(Piping
direction)
A
Blower cover
insulation
2. Installing grille assembly to body
Hook the grille assembly to the hook of the body and
temporarily fasten it. Do this that bottom of control box of
the body becomes the display section of the grille
assembly.
Air diffuser
A-A Section view
Fig. 27
Washer
Spring washer
Bolt
No gap between ceiling and
grille around entire periphery.
Wireless unit connection wire wiring
Connect the connector in accordance with part A detail view.
Then clamp the lead wire with clamp so that it does not
touch the rotating parts .
Fig. 28
Fig. 26
Hook of the
body
Hook of the
body
Hook
Control box
Hook of the
body
Hook
Hook
Grille assembly
Bolting the grille assembly to the body
Install the grille assembly to the body with the four bolts,
spring washers and washers.
A
Fig. 29 Part A detail view
Wire (louver)
Joint wire (louver)
Install the cover C. (Fig. 20)
Install the intake grille.
BACK
NEXT
REMOVING/INSTALLING THE INTAKE GRILLE
1. Removing the intake grille
(1) Push the intake grille pushbuttons (two places) until you
hear a “click”.
(2) Open the intake grille.
Fig. 30
PUSH
(3) Remove the wire (hanger). (Fig. 31)
(4) Remove the intake grille by opening it 100˚ to 120˚.
Fig. 31
PUSH
Wire
(
hanger
(2) Install the wire (hanger).
Fig. 33
Wire
(
hanger
)
Wire
(
hanger
)
(3) Hook the intake grille hooks to the grille assembly.
Fig. 34
Intaje grille hooks
)
PUSH
PUSH
100 to 120
2. Installing the intake grille
(1) Tilt the intake grille 100˚ to 120˚ and hook the three
hooks to the intake grille hook shaft.
Hook shaft
Fig. 32
Hook
100 to 120
(4) Push the intake grille pushbuttons (two places) until you
hear a “click”.
CAUTION
1
The louver angle cannot be changed
if the power is not on, (If moved by
hand, it may be damaged.)
2
The grille assembly is directional relative to the air conditioner body.
BACK
NEXT
9
REMOTE CONTROLLER INSTALLATION
Install the remote controller so that the front is facing the
photocell. (Fig. 35)
Fig. 35
Photocell
Remote control unit
Install the remote controller with a distance of 7 m
between the remote controller and the grille photocell as
the criteria. However, when installing the remote controller, check that it operates positively.
Install the remote controller holder to a wall, pillar, etc.
with the two screws (medium).
Hook the remote controller to the hook of the remote
controller holder. (Fig. 36)
Fig. 36
Hook
Remote
controller
Remote
holder
control
Screw (medium)
Fasten the remote controller to the remote controller
holder with the machine screw (small). (Fig. 37)
Fig. 37
Machine screw
(small)
Battery cover
Remote controller code switching
Fig. 38
123
F
F
O
DIP switch
Indoor unit
control panel
Fig. 39
AB
Remote controller
signal selector switch
Remote controller
Controll panel DIP switch [3] and the remote controller
signal selector switch can be switched and signals
received as follows:
DIP SW [3]Remote controller
signal selector SW
ONA
OFFB
When DIP SW [3] was set to ON — remote controller
signal selector SW was set to B and DIP SW [3] was
set to OFF — remote controller selector SW was set
to A, signals cannot be received.
<Example>
When two air conditioners installed in a room
When you want to run the two conditioners the same
Set DIP SW [3] of both air conditioners to ON and the
remote controller signal selector SW to A.
When you can run the two air conditioners individually
Set DIP SW [3] of one air conditioner to ON and the
remote controller signal selector SW to A. Set DIS
AB
DI PSW
BACK
NEXT
10
TEST RUNNING
Press the remote controller test running button while the
air conditioner is running.
At the end of test running, press the remote controller
start-stop button. (F ig. 40)
Fig. 40
Test running
button
Run the air conditioner in accordance with the operating
manual.
Fig. 41
LOUVER
TIMER
OPERATION
OFFON
LOUVER LAMP
(Orange)
TIMER LAMP
(Green)
OPERATION LAMP
(Red)
Operation can be checked by lighting and flashing of the
grille display section (Fig.41) OPERATION andTIMER
lamps.
Perform judgement in accordance with the following:
Power ON
POWER
NORMALAUTO
RESTART
MANUAL
AUTO
Error
The OPERATION and TIMER lamps operate as fol-
When the power is turned on, the grille display section OPERATION and TIMER lamps flash quickly and
alternately. When operation starts thereafter, flashing
stops.
Test running
When the air conditioner is run by pressing the
remote controller test running button, the OPERATION and TIMER lamps flash slowly at the same
time.
To stop test running, press the START/STOP button.
Do not operate the air conditioner in the test running
state for a long time.
For the operation method, refer to the operating manual
and perform operation check
Check that there are to abnormal sounds or vibration
sounds during test running.
BACK
NEXT
8.1.2 AU18R, 25R
SPLIT TYPE AIR CONDITIONER
Cassette Type[Reverse Cycle Model]
INSTALLATION MANUAL
(PART NO.
9356966015
)
For authorized service personnel only.
WARNING
1
For the room air conditioner to operate satisfactorily, install it as outlined in this
installation manual.
2
Connect the indoor unit and outdoor unit with the room air conditioner piping and
cords available from our standard parts. This installation manual describes the
correct connections using the installation set available from our standard parts.
3
Installation work must be performed in accordance with national wiring standards
by authorized personnel only.
4
Do not turn on the power until all installation work is complete.
Be careful not to scratch the air conditioner when handling it.
After installation, explain correct operation to the customer, using the operating manual.
Let the customer keep this installation manual because it is used when the air conditioner is serviced
or moved.
The maximum length of the piping is shown in Table 1. If the units are further apart than this, correct
operation cannot be guaranteed.
BACK
NEXT
STANDARD PARTS
The following installation parts are furnished. Use them as required.
INDOOR UNIT ACCESSORIESOUTDOOR UNIT ACCESSORIES
Name and ShapeQ'tyApplicationName and ShapeQ'tyApplication
Coupler heat
insulation
Remote
controller cord
clamp
Screw
Special nut A
(large flange)
Special nut B
(small flange)
Remote
controller
Template
2 For indoor side
pipe joint
10 For installing the
remote controller
cord
10
For installing the
remote controller
cord clamp
2 For installing the
remote controller
4 For installing
indoor unit
4 For installing
indoor unit
1 Installation to
indoor unit
1 For ceiling hole
cutting
Hexagon wrench
Pipe (drain)
Flexible tube
Cap (drain)
GRILLE ACCESSORIES
Name and ShapeQ'tyApplication
Bolt
1 For air purge
1
1 For outdoor
unit drain
piping work
2
4 For mounting
grille
Binder
2 For remote
(large)
controller cord
binding
2 For remote con-
(small)
troller cord binding
Washer
Spring washer
Blower cover
insulation
4 For mounting
grille
4 For mounting
grille
2 For discharged
air
4" (100 mm) or more
(4 directions)(3 directions)
Piping positon4" (100 mm)
or more
(2 directions)(2 directions)
4" (100 mm) or more
39" (1,000 mm)
or more
PipePipe
Strong and durable ceiling
11-13/16" (300 mm)
or more
39" (1,000 mm)
or more
39" (1,000 mm)
or more
Obstruction
BACK
NEXT
SELECTING THE MOUNTING POSITION
Especially, the installation place is very important for the split type air conditioner because it is very difficult to move from place to place after the
first installation.
Decide the mounting position together with the customer as follows:
The discharge direction can be selected as shown below.
Fig. 1
CONNECTION PIPE REQUIREMENT
Table 1
CAUTION
Since 2-way outlet as shown below
causes performance problems, do not
set it.
Indoor unit
(1) Install the indoor unit on a place having a sufficient strength
so that it withstands against the weight of the indoor unit.
(2) The inlet and outlet ports should not be obstructed; the air
should be able to blow all over the room.
(3) Leave the space required to service the air conditioner.
(Fig. 2)
(4) The ceiling rear height is 11-13/16 inches (300 mm) or more.
(5) A place from where the air can be distributed evenly through-
out the room by the unit.
(6) A place from where drainage can be extracted outdoors easi-
ly.
Fig. 2
Diameter
Maximum
length
SmallLarge
9.53 mm 15.88 mm
(3/8 in)(5/8 in)
Use 0.7 mm to 1.2 mm thick pipe.
Use pipe with water-resistant heat insulation.
Use pipe that can withstand a pressure of 3,040 kPa.
25 m
(82 ft)
Maximum height
(between indoor and
outdoor)
15 m
(49 ft)
ELECTRICAL REQUIREMENT
Electric wire size and fuse capacity:
Table 2
18,000 BTU/h class25,000 BTU/h class
Power
cable
(mm2)
Connection
cord (mm2)
Fuse capacity (A)
Always use H07RN-F or equivalent as the connection
cord.
Install the circuit breaker nearby the units. (Both indoor
unit and outdoor unit)
MAX
MIN
MAX
MIN
3.03.0
2.52.5
3.03.0
2.52.5
2030
35-3/64" ( 890 mm)
(Ceiling opening measurement)
18" (457 mm)
(hanging bolt position)
37-13/32" ( 950 mm)
(grille measurement)
28-25/32" (731 mm)
(hanging bolt position)
Hole-in anchor
Hole-in plug Concrete Insert
Hanging bolt
M10
Length (H) = h–9-21/32"
(shown in Fig.6)
1'
(30 cm)
or more
2' (60 cm)
or more
1'4" (40 cm) or more
1' (30 cm)
or more
2' (60 cm)
or more
BACK
NEXT
Outdoor unit
WARNING
Install the unit where it will not be
tilted by more than 5 ˚
When installing the outdoor unit
where it may exposed to strong
wind, fasten it securely.
(1) If possible, do not install the unit where it will exposed to
direct sunlight. (If necessary, install a blind that does not
interfere with the air flow.)
(2) Install the outdoor unit in a place where it will be free from
being dirty or getting wet by rain as much as possible.
(3) Install the unit when connection to the indoor unit is easy.
(4) During heating operation, drain water flows from the out-
door unit.
Therefore, install the outdoor unit in a place where the
drain water flow will not be obstructed.
(5) Do not place animals and plants in the path of the warm air.
(6) Take the air conditioner weight into account and select a
place where noise and vibration are small.
(7) Select a place so that the warm air and noise from the air
conditioner do not disturb neighbors.
(8) Provide the space shown in Fig. 3 so that the air flow is
not blocked. Also for efficient operation, leave open three
of the four directions front, rear, and both sides.
Fig. 3
INSTALLATION PROCEDURE
Install the room air conditioner as follows:
1
INDOOR UNIT INSTALLATION
1. Position the ceiling hole and hanging bolts as shown in
Fig. 4.
Fig. 4
2. Hanging preparations
Firmly fasten the hanging bolts as shown in Fig. 5 or by
another method.
Fig. 5
Trap
Rise
Air bleeding
Supporter
5 to 6.5 ft (1.5 to 2 m)
6" (150 mm)
or less
Max 6"
(150 mm)
Plug the holes.Drain pipe mounting hole
Drain pipe mounting hole
Drain pipe
Bottom
Special nut A
Special nut B
Hanging bolt length
Hanging bolt
Bottom of ceiling
10-15/16"
(278 mm)
Fine adjust to
that the body
is level.
Vinyl hoseGrille supporter
9-21/32" to 10"
(245 to 255 mm)
11-1/32" to 11-7/32"
(280 to 285 mm)
Special nut A
Special nut B
25/64" to 19/32"
(10 to 15 mm)
BACK
NEXT
3. Body installation
(1) Install special nut A (large flange) to the hanging bolts at
a position 11-1 /32” to 11-7/32” (280 to 285 mm) from the
bottom of the ceiling. (Fig. 7)
(2) Next, install special nut B (small flange) to the hanging
bolts. Provide a space of 25/64” to 19/32” (10 to 15 mm)
between special nut B and special nut A (large flange).
(3) Align the end of the hanging bolts with the larger of the
four long body mounting plate holes and lift the body until
it touches special nut A.
Then slide the body in the rotation direction so that it is
supported by special nut B. (Fig. 8)
(4) Adjust special nut B so that the bottom of the ceiling and
the four grille supporters are on the same plane. (Fig. 6)
(5) Leveling
Using a level, or vinyl hose filled with water, fine adjust
so that the body is level.
WARNING
Perform final tightening by tightening
the double nut firmly.
Fig. 6
2
INSTALLING DRAIN PIPE
Note: Install the drain pipe.
Install the drain pipe with downward gradient (1/50 to
1/100) and so there are no rises or traps in the pipe.
Use general hard polyvinyl chloride pipe (VP25) [outside
diameter 1-1/4” (32 mm)] and connect it with adhesive
(polyvinyl chloride) so that there is no leakage.
When the pipe is long, install supporters.
Do not perform air bleeding.
Always heat insulate the indoor side of the drain pipe.
When desiring a high drain pipe height raise it up to 6”
(150 mm) within a range of 6” (150 mm) from the body.
A rise dimension over this range will cause leakage.
Fig. 9
Fig. 7
Fig.8
3
OUTDOOR UNIT INSTALLATION
(1) When the outdoor unit will be exposed to strong wind, fasten
it with bolts at the places indicated by the arrows. (Fig. 10)
(2) Since the drain water flows out of the outdoor unit during
heating operation, install the drain pipe and connect it to
an commercial 16 mm hose.
(3) When installing the drain pipe, plug all the holes ( • holes
at two places) other than the drain pipe mounting hole in
the bottom of the outdoor unit with putty so there is no
water leakage. (Fig. 10)
Fig. 10
BACK
NEXT
4
CONNECTING THE PIPING
1. Flare processing
(1) Cut the connection pipe with pipe cutters so that the pipe
is not deformed.
(2) Holding the pipe downward so that cuttings cannot enter
the pipe, remove the burrs.
(3) Remove the flare nut from the indoor unit pipe and out-
door unit and assemble as shown in (Table 3) and insert
the flare nut onto the pipe, and flare with a flaring tool.
(4) Check if the flared part “ L” (Fig. 11) is spread uniformly
and that there are no cracks.
Table 3
Pipe
Small pipe Small (width across flats 22 mm)
Large pipeLarge (width across flats 24 mm)
Fig. 11
Width across flats
L
2. Bending pipes
The pipes are snapped by your hands. Be careful not to
collapse them.
Flare nut
L dimension
Small pipe
1.8 to 2.0 mm (9.53 mm dia.)
Large pipe
2.2 to 2.4 mm (15.88 mm dia.)
When bending the pipe, do not bend it as is. The pipe
will be collapsed. In this case, cut the heat insulating
pipe with a sharp cutter as shown in Fig. 13 and bend it
after exposing the pipe. After bending the pipe as you
want, be sure to put the heat insulating pipe back on the
pipe, and secure it with tape.
Fig. 13
Heat insulating
pipe
Cutter
Cut line
Pipe
CAUTION
1
To prevent breaking of the pipe,
avoid sharp bends. Bend the pipe
with a radius of curvature of 150 mm
or over.
2
If the pipe is bent repeatedly at the
same place, it will break.
3. Connection pipes
(1) Indoor unit side
Fig. 14
Indoor unit
Large pipe
Fig. 12
OKNO
Do not bend the pipes in an angle less than 90°. When
the pipes are bent and stretched repeatedly, the material
will be hardened, causing the pipes no longer be sent or
stretched. Be sure to limit number of bending and
stretching to three times.
Extend the pipe
by unwinding it.
CAUTION
Be sure to apply the pipe against the
1
port on the indoor unit correctly. If
the centering is improper, the flare
nut cannot be tightened smoothly. If
the flare nut is forced to turn, the
threads will be damaged.
2
Do not remove the flare nut from the
indoor unit pipe until immediately
before connecting the connection
pipe.
Small pipe
Lo
Hi
Refrigerant pipe
Outdoor
unit
Blank cap
3-way valve
Charging
valve
Service
hose with
valve core
Cap
Service hose
Vacuum pump
Gauge manifold
Hexagon wrench
BACK
NEXT
When the flare nut is tightened properly by your hand,
hold the body side coupling with a separate spanner,
then tighten with a torque wrench. (Fig. 15)
Fig. 15
Body side
Holding spanner
90
Torque wrench
CAUTION
1
Hold the torque wrench at its grip,
keeping it in the right angle with the
pipe as shown in Fig. 15, in order to
tighten the flare nut correctly.
Table 4: Flare nut tightening torque
5
AIR PURGE
1. Air purge
(1) Remove the cap, and connect the gauge manifold and
the vacuum pump to the charging valve by the service
hoses.
(2) Vacuum the indoor unit and the connecting pipes until
the pressure in them lowers to below 1.5 mmHg.
(3) Disconnect the service hoses and fit the cap to the
charging valve (Tightening torque: 70 to 90 kgf
(4) Remove the blank caps, and fully open the spindles of
the 2-way and 3-way valves with a hexagon wrench
(Torque: 2-way valve: 70 to 90 kgf
to 120 kgf
•cm).
•cm, 3-way valve: 100
(5) Tighten the blank caps of the 2-way valve and 3-way
valve to the specified torque (200 to 250 kgf
Fig. 17
•cm).
•cm).
PipeTightening torque
Small pipe310 to 350 kgf · cm
Large pipe750 to 800 kgf · cm
CAUTION
Be sure to connect the large pipe after
connecting the small pipe completely.
(2) Outdoor unit side
Tighten the flare nut of the connection pipe at the outdoor unit valve connector. The tightening method is the
same as that as at the indoor side.
Fig. 16
(Large pipe)
Connection pipe
(Small pipe)
Flare nut
Pipe coupling
2. Additional charge
Refrigerant suitable for a piping length of 5 m is charged
in the outdoor unit at the factory. When the piping is
longer than 5 m, additional charging is necessary. For
the additional amount, see the table below.
3-way valve2-way valve
}
Coupler heat
insulation
Body
Be sure to overlap
the insulation
BACK
NEXT
Table 5
Pipe length
18,000 BTU/h
Additional
refrigerant
[18,000 BTU/h class]
Between 5 m and 25 m, when using a connection pipe
other than that in the table, charge additional refrigerant
with 1.69 oz (48 g)/3.3 ft(1 m) as the criteria.
[25,000 BTU/h class]
Between 5 m and 25 m, when using a connection pipe
other than that in the table, charge additional refrigerant
with 1.20 oz (34 g)/3.3 ft(1 m) as the criteria.
6
class
25,000 BTU/h
class
INSTALLING THE COUPLER
16 ft 33 ft49 ft66 ft82 ft
(5 m)(10 m)(15 m)(20 m)(25 m)
8.5 oz 16.9 oz25.4 oz33.9 oz
None
(240 g)(480 g) (720 g)(960 g)
6.0 oz 12.0 oz18.0 oz 24.0 oz
None
(170 g)(340 g) (510 g)(680 g)
HEAT INSULATION
CAUTION
1
When moving and installing the air
conditioner, do not mix gas other
than the specified refrigerant (R22)
inside the refrigerant cycle.
2
When adding refrigerant, add the
refrigerant from the charging valve
at the completion of work.
3
The maximum length of the piping is
25m. If the units are further apart
than this, correct operation can not
be guaranteed.
7
ELECTRICAL WIRING
After checking for gas leaks, insulate by wrapping insulation
around the two parts (large and small) of the indoor unit coupling, using the coupler heat insulation.
Fig. 18
CAUTION
Must fit tightly against body without
any gap.
No gap
Coupler heat insulation
HOW TO CONNECT WIRING TO THE TERMINALS
A. For solid core wiring (or F-cable)
(1) Cut the wire end with a wire cutter or wire-cutting
pliers, then strip the insulation to about 15/16” (25
mm) to expose the solid wire.
(2) Using a screwdriver, remove the terminal
screw(s) on the terminal board.
(3) Using pliers, bend the solid wire to form a loop
suitable for the terminal screw.
(4) Shape the loop wire properly, place it on the ter-
minal board and tighten securely with the terminal
screw using a screw-driver.
B. For strand wiring
(1) Cut the wire end with a wire cutter or wire-cutting
pliers, then strip the insulation to about 3/8” (10
mm) to expose the strand wiring.
(2) Using a screwdriver, remove the terminal
screw(s) on the terminal board.
(3) Using a round terminal fastener or pliers, secure-
ly clamp a round terminal to each stripped wire
end.
(4) Position the round terminal wire, and replace and
tighten the terminal screw using a screwdriver.
Cover
(wire)
Cover B
Cover C
Binder (large)
Cord
clamp
Connection cord
(To the outdoor unit)
Remote controller cord
1
2
(N)
3
123
OUTDOOR
UNIT
Black
White
Red
Connection
cord
Terminal board
(Indoor unit)
Remote
controller
BACK
NEXT
Fig. 19
A. Solid wireB. Strand wire
Round terminal
Screw with
special
washer
Round
terminal
Wire
Strip 15/16" (25 mm)
Wire
Insulation
Loop
Strip 3/8" ((10 mm)
Screw with
special washer
Round terminal
Terminal
board
1. Indoor unit side
(1) Remove the cover B,C and cover (wire) and install the
connection cord. (Figs. 20, 21 and 22)
Fig. 21
Fig. 22
Fig. 20
(2) After wiring is complete, clamp the remote controller
(3) Install the cover B and cover (wire).
cord and connection cord with the cord clamp and binder
(large).
CAUTION
1
Tighten the indoor unit connection
cord (to the outdoor unit) and power
supply indoor and outdoor unit terminal board connections firmly with
the terminal board screws. Faulty
connection may cause a fire.
2
If the indoor unit connection cord (to
the outdoor unit) and power supply
are wired incorrectly, the air conditioner may be damaged.
3
Wire the indoor unit connection cord
(to the outdoor unit) by matching the
numbers of the outdoor and indoor
units terminal board numbers as
shown in (Fig. 22)
4
Ground both the indoor and outdoor
units by attaching a ground wire.
5
Unit shall be grounded in compliance with the applicable local and
national codes.
L N 3
2
(N)
1
3
Black
2
White
1
3
1
Red
EARTH
2
(N)
3
N
L
1
2
(N)
EARTH
Terminal board
Green/
Yellow
Terminal
cover
Power cable
Insulation tube
Cord
clamp
Connection
cord
Insulation tube
(Use VW-1, 0.5 to 1.0 mm thick,
PVC tube as the insulation tube)
Connection cord
Remote controllerPower supply
Power line
Control Line
Indoor unit
side terminal
Outdoor unit
side terminal
Cord clamp
Insulation tube
Connection cord
Power
cable
Connection
cord
Green/
Yellow
After passing the connection cord through the
insulation tube, fasten it
with the cord clamp.
BACK
NEXT
2. Outdoor unit side
(1) Remove the terminal cover of the outdoor unit, and insert
the end of the connection cord and the power cable into
the terminal board.
(2) Fasten the connection cord with the cord clamps, and
install the terminal cover.
Fig. 23
8
GRILLE INSTALLATION
1. Blower cover insulation
Install the blower cover insulation only when the outlet
direction is not specified.
Two blower cover insulations are packed with the grille
assembly. Install the blower cover insulation at the diffuser position shown in Fig. 24. At this time, use the piping position as the criteria.
Fig. 24
2 direction example
Fit the blower cover insulation
tightly at the air diffuser section.
A
(Piping
direction)
A
Blower cover
insulation
2 Installing grille assembly to body
Hook the grille assembly to the hook of the body and
temporarily fasten it.
Fig. 25
Air diffuser
A-A Section view
Hook of the
body
Hook
Control box
Hook of the
body
Hook of the
body
Hook
Hook
Grille assembly
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.