Note:Specifications are based on the following conditions.
Cooling:Indoor temperature of 27 °CDB / 19 °CWB,and outdoor temperature of 35 °CDB/24 °CWB.
Heating:Indoor temperature of 20 °CDB / 15 °CW B,and outdoor temperature of 7 °CDB/6 °CW B.
Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
mm
- (04 - 05) -
Page 7
4-4. DIMENSIONS
4-4-1. OUTDOOR UNIT
MODELS : AO 36F, AO 36U
(Unit : mm)
Top view
317790033012
1165
CASSETTE TYPE
CASSETTE TYPE
AU36
21
AU36
Front view
MOUNTING POSITION
When there are
obstacles at the
back or front side.
When there are obstacles
at the back and front sides.
9
Bottom view
400
Side view
When there are obstacles at
the back, side(s), and top.
When there are obstacles
at the back side with the
installation of more than
one unit.
100 mm
or more
600 mm
or more
100 mm
or more
100 to 300 mm *
- (04 - 06) -
600 to 1000 mm
250 mm
or more
250
(
mm
Ser
v
ic
e
* If the space is larger than that is stated, the
condition will be the same as that there are no
obstacles.
*1) Wiring Spec :Selected Sample (Selected based on Japan Electrotechnical Standard and Codes
Committee E0005)
*2 Limited Wiring length : This is the wiring length in case voltage descent is less than 2%.
When the wiring length becomes long, please select the wiring of a more larger
diameter.
- (04 - 25) -
Page 27
4-14. SAFETY DEVICE
PROTECTION FORMAO36FAO36U
FUSE
(SIDE OF INDOOR UNIT)
-
FUSE ON PCB--6.3A 250V
FAN MOTOR PROTECTIONTHERMAL PROTECTOR
COMPRESSOR PROTECTION THERMAL PROTECTOR
HIGH PRESSURE PROTECTION PRESSURE SWITCH
DISCHARGE THERMOSTATTHERMAL PROTECTOR
OFF:130±5°C
ON:100±15°C
-
5A 250V
OFF:4.2±0.1MPa
ON:3.2±0.15MPa
150°C±5°C OFF
OFF : 25°C(28A)120°C(8.1A)
ON : 80±10°C
PROTECTION FORMAU36FAU 36U
PCB FUSE-
FAN MOTOR PROTECTIONTHERMAL PROTECTOR
TERMINAL FUSETHERMAL FUSE
130°C±5°C OFF
102°C±2°C OFF
3.15A 250V
OUTDOOR UNIT
INDOOR UNIT
CASSETTE TYPE
AU36
CASSETTE TYPE
AU36
- (04 - 26) -
Page 28
4-15. FUNCTION SETTING
Auto restart validity/invalidity
Room temperature correct coefficient
Room temperature correct coefficient
Forbidden
Indoor unit number setting
Forbidden
Forbidden
Forbidden
SW 1
SW 4
1
2
Jumper Wire
2
3
JM1
JM2
Rotary SW
SW 2
INDOOR UNIT
DIP SW
31JM3
Ceiling height setting
4-15-1. INDOOR UNIT
SWITCH POSITION
CASSETTE TYPE
AU36
Indoor unit control circuit board
CASSETTE TYPE
AU36
- (04 - 27) -
Page 29
4-15-2. SWITCH FUNCTION (INDOOR UNIT)
SW 1-1
SW state
OFF
Invalidity
ON
Validity
0 deg
0 deg
0 deg
cooling
-2 deg
SW 1-2
SW 1-3
0 deg
heating
dry
-2 deg
-2 degONONONOFF
OFF
+2 deg
-2 deg
OFF
SW state
-2 deg
OFF
ON
0 deg
+4 deg
SW 4-1
OFF
3
OFF
-
ON
Less than 2.5
Normal
High ceiling 1
High ceiling 2
Low ceiling
-ONON
3.0-3.5
More than 3.5
-
OFF-ON
OFF
2.5-3.0
OFF
Ceiling height(m)
DIP - SW4
1
2
DIP SWITCH SETTING
SW1-1. Auto restart setting
Auto restart function can be selected by turning this switch ON/OFF.
AUTO RESTART SETTING
(Factory setting)
SW1-2, 1-3. Room temperature correct coefficient of heating.
Decide the heating temperature correct coefficient vale of heating.
TEMPERATURE CORRECTION
(Factory setting)
CASSETTE TYPE
AU36
CASSETTE TYPE
AU36
SW4-1. Dip SW 4-1setting forbidden
(Factory setting)
SW4-2, 4-3. Ceiling height setting
(Factory setting)
If the setting for a low ceiling is selected, the capacity of the air
conditioner decreases slightly.
- (04 - 28) -
Page 30
ROTARY SWITCH SETTING (SW2)
0
Single
1 - 15
Indoor unit address
SW 2
SW state
SW state
JM 1, 2, 3
Connect
Disconnect
Forbidden
This switch can be used when group control system.
Set the indoor unit address in the 0,1,-,15 order.
(Factory setting)
JUMPER WIRE SETTING
JM 1, 2, 3 setting forbidden
(Factory setting)
CASSETTE TYPE
CASSETTE TYPE
AU36
AU36
- (04 - 29) -
Page 31
4-15-3. WIRED REMOTE CONTROLLER CIRCUIT BOARD
Wired remote controller
1
Dual remote controller setting
2
Group control setting
DIP SW
SWITCH POSITION
Wired remote controller
Front case (back side)
CASSETTE TYPE
AU36
3
4
Model setting
Auto changeover setting
5
6
Memory backup setting
CASSETTE TYPE
AU36
DIP Switch
OFF
ON
1
2
3
4
5
6
ON
- (04 - 30) -
Page 32
4-15-4. WIRED REMOTE CONTROLLER
DIP SWITCH SETTING
1. SW setting
1-1 Dual remote controller setting
Set the remote controller DIP switch No.1 and 2 according to the following table.
(Factory setting)
Number of
remote
controller
1 (Normal)
2 (Dual)
1-2 Group control setting
Number of indoor unit connection (One/Multiple)
This is switched according to the number of connected indoor units.
CASSETTE TYPE
AU36
DIP-SW
No.3
OFF
Master unitSlave unit
DIP-SW
No.1
DIP-SW
No.2
ON
OFF
(Factory setting)
Number of indoor unit
One unit connection
OFF
OFF
DIP-SW
No.1
ONON
DIP-SW
No.2
CASSETTE TYPE
AU36
ONMultiple unit connection
1-3 Model setting
The system type of the outdoor unit can be selected by setting up DIP switch No.4 as follows.
( )
( )
(
DIP-SW
No.4
OFF
ONCooling only model
Heat Pump model
Factory setting)
Model
1-4 Auto changeover setting
Selecting auto changeover validity / invalidity.
(Factory setting)
DIP-SW
No.5
OFF
ONValidity
Auto changeover
Invalidity
1-5 Memory backup setting
Set to ON to use batteries for the memory backup.if batteries are not used,
all of the settings stored in memory will be deleted if there is a power failure.
This function is wired remotecontroll only.
(Factory setting)
DIP-SW
No.6
OFF
ONValidity
Memory backup
Invalidity
- (04 - 31) -
Page 33
4-16. OPTIONAL PARTS
ADDITIONAL GRILLE
UTG-AGEA-W
The additional grille hides the gap between the ceiling hole
and the outlet grille.
Additional grille (optional parts)
Additonal grille
CASSETTE TYPE
AU36
The ceiling hole
Indoor Unit(grille)
CASSETTE TYPE
AU36
- (04 - 32) -