General AUG36A, AUG36ALC3W, AOG36APA3L, AUG36R, AUG36RLC3W Installation Manual

...
SPLIT TYPE AIR CONDITIONER
Cassette Type
INSTALLATION INSTRUCTION SHEET
(PART NO. 9363217018)
For authorized service personnel only.
WARNING!
CAUTION!
1 For the air conditioner to operate satisfactorily, install it as outlined in this installation instruction sheet.
2 Connect the indoor unit and outdoor unit with the room air conditioner piping and cords available from our
standard parts. This installation instruction sheet describes the correct connections using the installation set available from our standard parts.
3 Installation work must be performed in accordance with national wiring standards by authorized personnel only.
4 If refrigerant leaks while work is being carried out, ventilate the area. If the refrigerant comes in contact with a
flame, it produces a toxic gas.
5 Do not turn on the power until all installation work is complete.
Be careful not to scratch the air conditioner when handling it.
After installation, explain correct operation to the customer, using the operating manual.
Let the customer keep this installation instruction sheet because it is used when the air conditioner is serviced or moved.
The maximum length of the piping is shown in Table 1. If the units are further apart than this, correct operation cannot be guaranteed.
STANDARD PARTS
The following installation parts are furnished. Use them as required.
INDOOR UNIT ACCESSORIES
Name and Shape Q’ty Application
Coupler heat insulation
Remote controller cord clamp
Screw
Special nut A (large flange)
Special nut B (small flange)
Remote controller
Template For ceiling hole cutting
Binder For remote controller cord
Blower cover insulation For discharged air
Hook wire For installing intake grille
OUTDOOR UNIT ACCESSORIES
Power cap
Auxiliary pipe assembly
Edge cover
Tapping screw
Binder
Putty
Coupler heat insulation
Pipe (drain)
Flexible tube
Cap (drain)
This mark indicates procedures which, if improperly performed, might lead to the death of serious injury of the user.
This mark indicates procedures which, if improperly performed, might possibly result in personal harm to the user, or damage to property.
WARNING
SELECTING THE MOUNTING POSITION
Especially, the installation place is very important for the split type air conditioner because it is very difficult to move from place to place after the first installation. Decide the mounting position together with the customer as follows: The discharge direction can be selected as shown below.
Fig. 1
CAUTION
Since 2-way outlet as shown below causes performance problems, do not set it.
INDOOR UNIT
Install the indoor unit on a place having a sufficient strength so that
(1)
it withstands against the weight of the indoor unit. The inlet and outlet ports should not be obstructed; the air should
(2)
be able to blow all over the room. Leave the space required to service the air conditioner (Fig. 2).
(3)
The ceiling rear height as shown in Fig. 3.
(4)
A place from where the air can be distributed evenly throughout the
(5)
room by the unit. A place from where drainage can be extracted outdoors easily.
(6)
Install the unit where noise and vibrations are not amplified.
(7)
Fig. 2
Strong and durable ceiling
106” (2,700 mm) or more
Obstruction
This mechanism enables the cassette body to move 35 mm down­ward and realizes installation to the space of 250 mm. No special works and option is needed.
Fig. 3
You can select 2-way setting
(A) Standard setting (B) Slender setting
11-7/32” (285 mm)
or more
39” (1,000 mm) or more
OUTDOOR UNIT
WARNING
Install the unit where it will not be tilted by more than 5°.
1
When installing the outdoor unit where it may
2
exposed to strong wind, fasten it securely.
Leave the spaces indicated for good air flow (Fig. 4).
(1)
Fig. 4
12” (300 mm) or more
24” (600 mm) or more
2
10
10
2
4
4
1
1
2
(large)
1
(small)
2
2
1
1
1
2
1
1
1
2
2
2
For indoor side pipe joint
For installing the remote controller cord
For installing the remote controller cord clamp
For installing the remote controller
For installing indoor unit
For installing indoor unit
Installation to indoor unit
binding
For remote controller and remote controller cord binding
For power supply cord installation
For wiring conduit (gas side) connection (May not be supplied, depending on the model)
For wiring conduit installa­tion hole edge protection
For cabinet A and cabinet D mounting (1)
Spare (1)
For power supply cord binding
For sealing
For outdoor side pipe joint
For outdoor unit drain piping work (May not be supplied, depending on the model.)
9-27/32” (250 mm)
0.4” (10 mm) or more
or more
If possible, do not install the unit where it will exposed to direct sun-
(2)
light. (If necessary, install a blind that does not interfere with the air flow.) Do not install the unit near a source of heat, steam, of flammable gas.
(3)
During heating operation, drain water flows from the outdoor unit.
(4)
Therefore, install the outdoor unit in a place where the drain water flow will not be obstructed. (Reverse cycle model only.) Do not install the unit where a strong wind blows or where it is very
(5)
dusty. Do not install the unit where people pass.
(6)
Install the outdoor unit in a place where it will be free from being dirty
(7)
or getting wet by rain as much as possible. Install the unit when connection to the indoor unit is easy.
(8)
CONNECTION PIPE REQUIREMENT
Table 1
Diameter
Small Large
3/8”
(9.53 mm)
Use 0.7 mm to 1.2 mm thick pipe.
Use pipe with water-resistant heat insulation.
Use pipe that can withstand a pressure of 3,040 kPa.
3/4”
(19.05 mm)
Maximum length
164 ft (50 m) 99 ft (30 m)
Maximum height
(between indoor
and outdoor)
ELECTRICAL REQUIREMENT
Electric wire size and fuse/breaker capacity:
Table 2
Power
supply
cord
2
(mm
)
Connection
cord
2
(mm
)
Fuse/Breaker capacity (A)
Always use H07RN-F or equivalent as the cord. Install the disconnect device with a contact gap of at least 3 mm
nearby the units (both indoor unit and outdoor unit).
MAX
MIN
MAX
MIN
3.5
2.5
2.5
1.0
20
INSTALLATION PROCEDURE
Install the air conditioner as follows:
1
INDOOR UNIT INSTALLATION
WARNING
Install the air conditioner in a location which can with-
stand a load do at least five times the weight of the main unit and which will not amplify sound or vibration. If the installation location is not strong enough, the indoor unit may fall and cause injuries.
If the job is done with the panel frame only, there is a risk
that the unit will come loose. Please take care.
REMOVING THE INTAKE GRILLE
(1)
Push the intake grille pushbuttons (two places).
(2)
Open the intake grille.
Fig. 5
PUSH
Remove the grille hinge wire.
(3)
Fig. 6
Pull up while pressing the B section (Fig. 7).
Fig. 7 Part A detail view Fig. 8 Part A section view
(4)
Remove the intake grille.
OPEN
A
B
Grille hinge wire
REMOVING THE PANEL FRAME
Pull up the corner sections (A) of the panel frame as shown in
Fig. 9. (4 locations)
Fig. 9 Part A detail view
A
B
A
Pull up in the direction of the arrow while holding down the C
section of Fig. 10. (4 locations)
Fig. 10 Part B detail view
Fig. 11
Panel frame
Panel base
A
A
C
CAUTION
Always remove the panel frame after removing the intake grille.
1. POSITION THE CEILING HOLE AND HANGING BOLTS
Fig. 12
□37” (□940 mm)
(Grille measurement)
29-17/32” (750 mm)
(Hanging bolt position)
29-17/32” (750 mm)
(Hanging bolt position)
□35-3/64” (□890 mm)
(Ceiling opening measurement)
2. HANGING PREPARATIONS
Firmly fasten the hanging bolts as shown in Fig. 13 or by another method.
Install the hanging bolts at a place where they would be capable of holding a weight of at least 50 kgf per bolt.
Fig. 13
Fig. 14 (A) Standard setting
2-3/8”
(60 mm)
(B) Slender setting
2-3/8”
(60 mm)
Hole-in anchor Hole-in plug
Hanging bolt M10
Drain pipe (I.D. 32 mm)
12” (305.5 mm)
Drain pipe (I.D. 32 mm)
12” (305.5 mm)
InsertConcrete
11-3/4” (298.5 mm)
9-25/32”
(248.5 mm)
11-3/4” (298.5 mm)
9-25/32”
(248.5 mm)
(120 mm)
(150 mm)
4-23/32”
5-29/32”
(127 mm)
5”
(120 mm)
(150 mm)
4-23/32”
5-29/32”
(92 mm)
3-5/8”
2
11-7/32” (285 mm)
9-27/32” (250 mm)
3. BODY INSTALLATION
[The ceiling rear height is 11-7/32” (285 mm) or more.] [Standard setting]
[The ceiling rear height is 9-27/32” (250 mm) or more.] [Slender setting]
(1)
Install special nut A, then special nut B onto the hanging bolt (Fig. 15).
(2)
Raise the body and mount its hooks onto the hanging bolt bet­ween the special nuts (Fig. 15).
(3)
Turn special nut B to adjust the height of the body (Fig. 15).
(4)
Leveling Using a level, or vinyl hose filled with water, fine adjust so that the body is level.
WARNING
Perform final tightening by tightening the double nut firmly.
Fig. 15
Special nut B
Hanging bolt
Fig. 16
Allowable space between
*
the unit and the ceiling 5 mm or less
Special nut A
Hook
30 mm
or more
After installing the body, tighten the nuts.
Ceiling
* Must fit tightly against
ceiling without any gap.
Vinyl hose
INSTALLING THE PANEL FRAME
Fig. 17
Panel base
*90° Turn
Panel frame
* With slender setting, turn the panel frame 90° as shown in the
diagram above.
Grille setting method has been changed at the marked posi­tions on the panel frame and panel base.
Fig. 18
(A) Standard setting (B) Slender setting
Mark
Fig. 19
(Example)
* Appearance of slender setting
Panel frame
No mark
INSTALLING DRAIN PIPE
CAUTION
Install the drain pipe in accordance with the instructions in this installation instruction sheet and keep the area warm enough to prevent condensation. Problems with the piping may lead to water leaks.
NOTE: Install the drain pipe.
Install the drain pipe with downward gradient (1/50 to 1/100) and so there are no rises or traps in the pipe.
Use general hard polyvinyl chloride pipe (VP25) [outside diameter 1-1/4” (32 mm)] and connect it with adhesive (polyvinyl chloride) so that there is no leakage.
When the pipe is long, install supporters.
Do not perform air bleeding.
Always heat insulate the indoor side of the drain pipe.
When desiring a high drain pipe height, raise it up to 31” (800 mm) or less from the ceiling within a range of 6” (150 mm) from the body. A rise dimension over this range will cause leakage.
Fig. 20
Air bleeding
Rise
Trap
6” (150 mm) or less
Supporter
Max 31”
5 to 6.5 ft (1.5 to 2 m)
(800 mm)
3
OUTDOOR UNIT INSTALLATION
1. OUTDOOR UNIT PROCESSING
(1)
When the outdoor unit will be exposed to strong wind, fasten it with bolts or wire at the four places indicated by the arrows (Fig. 21).
(2)
Since the drain water flows out of the outdoor unit during heating operation, install the drain pipe and connect it to an commercial 16 mm hose. (When heating when the outdoor temperature is 0 °C or less, construct so that the drain water drained from the outdoor unit will not freeze in the drain pipe.)
(3)
When installing the drain pipe, plug all the holes other than the drain pipe mounting hole in the bottom of the outdoor unit with put­ty so there is no water leakage (Fig. 21).
Fig. 21
(4)
Always use a drain pipe at two places.
2. OUTDOOR UNIT CONNECTION CORD AND PIPE CONNECTION PREPARATIONS
Piping and connection cord mounting direction (4-way mounting
(1)
possible).
Fig. 22
(2) Remove outdoor unit cabinet A and cabinet D.
Fig. 23
(3)
Open the piping and connection cord knockout holes of the desired direction with nippers, etc. After opening the knockout holes, install the accessory edge cover and power cap to protect the opened places.
Fig. 24
(4)
Connect the piping and power supply cord from the mounting holes.
Fig. 25
(Example)
4
CONNECTING THE PIPING
1. FLARE PROCESSING
(1)
Cut the connection pipe with pipe cutters so that the pipe is not deformed.
(2)
Holding the pipe downward so that cuttings cannot enter the pipe, remove the burrs.
(3)
Remove the flare nut from the indoor unit pipe and outdoor unit and assemble as shown in (Table 3) and insert the flare nut onto the pipe, and flare with a flaring tool.
(4)
Check if the flared part “L” (Fig. 26) is spread uniformly and that there are no cracks.
After removing the screws, remove
*
cabinet A by pushing it down.
When pipe bending work is
*
difficult inside the outdoor unit, use the accessory auxiliary pipe assembly.
Table 3
Flare nut
L dimension Small pipe (9.53 mm dia.)
1.8 to 2.0 mm Large pipe (19.05 mm dia.)
2.6 to 3.0 mm
Small pipe
Large pipe
Fig. 26
Pipe
Small (width across flats 22 mm)
Large (width across flats 36 mm)
2. BENDING PIPES
The pipes are snapped by your hands. Be careful not to collapse them.
Fig. 27
Do not bend the pipes in an angle more than 90°. When pipes are repeatedly bent or stretched, the material will harden, making it difficult to bend or stretch them any more. Do not bend or stretch the pipes more than three times.
When bending the pipe, do not bend it as is. The pipe will be collapsed. In this case, cut the heat insulating pipe with a sharp cutter as shown in Fig. 28, and bend it after exposing the pipe. After bending the pipe as you want, be sure to put the heat insulat­ing pipe back on the pipe, and secure it with tape.
Fig. 28
CAUTION
To prevent breaking of the pipe, avoid sharp bends.
1
Bend the pipe with a radius of curvature of 150 mm or over.
If the pipe is bent repeatedly at the same place, it will
2
break.
3. CONNECTION PIPES
(1) Indoor unit side
Fig. 29
Indoor unit
Large pipe
Small pipe
CAUTION
1
Be sure to apply the pipe against the port on the indoor unit correctly. If the centering is improper, the flare nut cannot be tightened smoothly. If the flare nut is forced to turn, the threads will be damaged.
2
Do not remove the flare nut from the indoor unit pipe until immediately before connecting the connection pipe.
When the flare nut is tightened properly by your hand, hold the body side coupling with a separate spanner, then tighten with a torque wrench (Fig. 30).
Fig. 30
CAUTION
Hold the torque wrench at its grip, keeping it in the right angle with the pipe as shown in Fig. 30, in order to tighten the flare nut correctly.
Table 4: Flare nut tightening torque
Pipe
Small pipe
Large pipe
310 to 350 kgf
800 to 1,000 kgf
Tightening torque
cm (30.4 to 34.3 N
cm (78.4 to 98 N
m)
m)
CAUTION
Be sure to connect the large pipe after connecting the small pipe completely.
(2) Outdoor unit side
1)
Tighten the flare nut of the connection pipe at the outdoor unit valve connector. The tightening method is the same as that as at the indoor side.
2)
Seal with the accessory putty so that water does not enter at the top of the pipe insulation installed to the connection pipe (large pipe and small pipe).
Fig. 31
Valve A (small)
Putty
(Small pipe)
(Large pipe)
Valve B (large)
Flare nut
Connection pipe
- Continued on back -
5 10 12
VACUUM PROCESS
Fig. 34
1. VACUUM
Vacuum inside the indoor unit and the piping to a pressure of
(1)
1.5 mmHg abs or less from the charging valve with a vacuum pump. After vacuuming inside the indoor unit and the piping, remove the
(2)
cap of the two valves. Open the handle of the two valves from the closed state (Table 6).
(3)
Tighten the cap of the two valves to the specified torque.
(4)
Table 5
Tightening torque
Large valve Small valve
Handle
Cap
cm (1.47 N
150 to 200 kgf
m) or less
cm (14.7 to 19.6 N
m)
15 kgf
Table 6
Open valve state Closed valve state
HOW TO FIXED CONNECTION CORD AND POWER SUPPLY CORD AT THE CORD CLAMP
After passing the connection cord and power supply cord through the insulation tube, fasten it with the cord clamp.
Fig. 35
Insulation tube
Insulation tube
Cord clamp
Fig. 32
Valve A
(Small)
* If the handle is not fully open, performance will drop and an abnormal sound will be generated.
Gauge mainfold
Valve B
(Large)
Use VW-1, 0.5 to 1.0 mm thick, PVC tube as the insulation tube.
Vacuum
Small pipe
Handle
pump
Large pipe
cap
Service hose
1. INDOOR UNIT SIDE
WARNING
1
Before starting work, check that power is not being supplied to the indoor unit.
2
Match the terminal board numbers and connection cord colors with those of the outdoor unit. Erroneous wiring may cause burning of the electric parts.
3
Charging valve
Connect the connection cord firmly to the terminal board. Imperfect installation may cause a fire.
4
Always fasten the outside covering of the connection cord with the cord clamp. (If the insulator is chafed,
2. ADDITIONAL CHARGE
Refrigerant suitable for a piping length 20 m for other model is charged in the outdoor unit at the factory. When the piping is longer than 20 m, additional charging is necessary. For the additional amount, see the table below.
Table 7
Pipe length
Model type
36,000 BTU 45,000 BTU
class
54,000 BTU
class
66 ft
(20 m)
None
None
99 ft
(30 m)
14.1 oz (400 g)
17.6 oz (500 g)
132 ft
(40 m)
28.2 oz (800 g)
35.2 oz
(1000 g)
164 ft
(50 m)
42.3 oz
(1200 g)
52.8 oz
(1500 g)
oz/ft
(g/m)
1.41 oz/3.3 ft (40 g/m)
1.76 oz/3.3 ft (50 g/m)
electric leakage may occur.)
5
Always connect the ground wire.
(1)
Remove the cotrol box cover and cover (wire) B and install the connection cord.
Fig. 36
Cover (wire) B
Control box cover
CAUTION
When charging the refrigerant, always use a measur-
1
ing cylinder.
Add refrigerant from the charging valve after the com-
2
pletion of the work.
(2)
After wiring is complete, clamp the remote controller cord and connection cord with the cord clamp.
(3)
Install the control box cover and cover (wire) B.
Fig. 37
6
INSTALLING THE COUPLER
HEAT INSULATION
After checking for gas leaks, insulate by wrapping insulation around the two parts (large and small) of the indoor unit coupling, using the coupler heat insulation. After installing the coupler heat insulation, wrap both ends with vinyl tape so that there is no gap.
Fig. 33
CAUTION
Must fit tightly against body without any gap.
7
ELECTRICAL WIRING
HOW TO CONNECT WIRING TO THE TERMINALS
A. For solid core wiring (or F-cable)
(1)
Cut the wire end with a wire cutter or wire-cutting pliers, then strip the insulation to about 15/16 (25 mm) of expose the solid wire.
(2)
Using a screwdriver, remove the terminal screw(s) on the terminal board.
(3)
Using pliers, bend the solid wire to form a loop suitable for the terminal screw.
(4)
Shape the loop wire properly, place it on the terminal board and tighten securely with the terminal screw using a screwdriver.
B. For strand wiring
(1)
Cut the wire end with a wire cutter or wire-cutting pliers, then strip the insulation to about 3/8 (10 mm) of expose the strand wiring.
(2)
Using a screwdriver, remove the terminal screw(s) on the terminal board.
(3)
Using a round terminal fastener or pliers, securely clamp a round terminal to each stripped wire end.
(4)
Position the round terminal wire, and replace and tighten the terminal screw using a screwdriver.
Connection cord (To the outdoor unit)
Fig. 38
Connection cord
OUTDOOR UNIT
Ceiling height setting
Set the DIP switch for the ceiling height according to the table below.
Ceiling height
(m)
2.5 ~ 3.0
3.0 ~ 3.5
More than 3.5
Less than 2.5
Fig. 39
Dip switch (SW4)
If the setting for a low ceiling is selected, the capaci-
1
ty of the air conditioner decreases slightly.
Do not set any switches other than those specified
2
in this sheet or the remote controller installation instruction sheet. The air conditioner may not oper­ate correctly if any switches other than those speci­fied are changed.
High ceiling 1
High ceiling 2
Cord clamp
Terminal board (Indoor unit)
Table 8
Normal
Low ceiling
Indoor unit PC board
CAUTION
Remote controller cord
Black
White
Terminal board
Red
Remote controller
DIP-SW4
123
SW 1
123
O
OFF
ON
OFF
ON
F
F
Indoor unit PC board
SW 4
123
F
O
OFF
OFF
ON
ON
F
2. OUTDOOR UNIT SIDE
WARNING
1
Before starting work, check that power is not being supplied to the outdoor unit.
2
Match the terminal board numbers and connection cord colors with those of the indoor unit side. Erroneous wiring may cause burning of the electric parts.
3
Connect the connection cords and the power supply cord firmly to the terminal board. Imperfect installa­tion may cause a fire.
4
Always fasten the outside covering of the connection cord and the power supply cord with cord clamps. (If the insulator is chafed, electric leakage may occur.)
5
Always connect the ground wire.
(1)
Remove outdoor unit cabinet A and connect the power supply cord and the outdoor unit connection cord wired at the indoor unit.
(2)
Fasten the power supply cord and connection cord with cable clip and binders as shown in (Fig. 42).
Fig. 40
Electric box
Terminal board
Power supply cord
Cord clamp
Power supply cord
Fig. 41
Remote controller
Black
White
Red
3 2 1
Ground
Connection cord (indoor unit and outdoor unit connection cord)
Power supply
Power line
R S T
N
3
2
(N)
1
Control line
Indoor unit side terminal
Fig. 42
Cable clip
Coupler holder
Binder
Compressor
8
GRILLE INSTALLATION
BLOWER COVER INSULATION
Install the blower cover insulation only when the outlet direction is not specified. Two blower cover insulations are packed with the indoor unit. Install the blower cover insulation at the diffuser position shown in Fig. 43. At this time, use the piping position as the criteria.
Fig. 43
2 direction example
A
(Piping direction)
INSTALLING THE INTAKE GRILLE
Mount the grille hinge wire to the hook shaft as shown in
(1)
Fig. 44.
Fig. 44
Power supply cord and connection cord (indoor unit and outdoor unit connection cord)
Outdoor unit
4 (100 mm) or less
Cabinet D
A
Blower cover insulation
A
3
2
(N)
1
EARTH
Outdoor unit side terminal
A-A Section view
Panel base
Drain pan
9
Latch the grille hinge wire to the hook shaft, and fasten.
Fig. 45 Part A detail view Fig. 46 Part A section view
Hook shaft
Grille hinge wire
(2)
Install the hook wire.
Pass the hook wire through the panel base from the rear
side as shown in Fig. 47, and fasten to the reinforced metal fitting of the intake grille using a screw.
Fig. 47
Hook wire
RFM (grille)
Fig. 48 Section view
Hook wire
Screw
(3) Loosen the screw, put the loop of the hook wire over it,
and tighten the screw again.
CAUTION
Install the intake grille hook wire to the grille assem­bly. If it falls, it may cause injuries.
(4)
Bring up the intake grille by pushing it up at an angle as shown in Figs. 49, 50, and fasten.
Fig. 49
Fig. 50
POWER
WARNING
The rated voltage of this product is 380-415 V 3ø 50 Hz.
1
Before turning on verify that the voltage is within the
2
342 to 457 V range.
Always use a special branch circuit and install a special
3
receptacle to supply power to the air conditioner.
Use a special branch circuit breaker and receptacle
4
matched to the capacity of the air conditioner. (Install in accordance with standard.)
Perform wiring work in accordance with standards so
5
that the air conditioner can be operated safely and positively.
Install a leakage special branch circuit breaker in
6
accordance with the related laws and regulations and electric company standards.
CAUTION
When the voltage is low and the air conditioner is difficult to start, contact the power company the voltage raised.
11
REMOTE CONTROLLER
INSTALLATION
Insert the end of a flat blade screwdriver at the arrow parts of the
groove at the side of the remote controller case and remove the remote controller case top by turning the screwdriver. Disconnect the remote controller cord from the remote controller
terminal board.
Fig. 51
CLOCK
21
SET TIME TEMP./DAY FAN
TEMP
ZONE
SET
°C
AUTO
HIGH
CONTROL
ENERGY SAVE
DAY OFF
COOL
DEFROST
MASTER
CONTROL
START/STOP
NON STOP
TIMER
MODE
CLOCK ADJUST
When remote controller exposed
(1)
1)
Make a notch in the thin part ( part of Fig. 51) at the rem­ote controller case top and bottom with nippers, file, etc.
2)
Connect the remote controller cord to the remote controller terminal board specified in (Fig. 52).
3)
Clamp the remote controller cord sheath with the binder (small) as shown in Fig. 52.
4)
Cut off the excess binder.
5)
Clamp the remote controller cord to a wall, etc. with the rem­ote controller cord clamp furnished (Fig. 53).
Fig. 52
Remote controller cord
White
Binder (small)
Red
Black
Remote controller terminal board
Fig. 53
Remote controller cord
Tapping screw (flush heads)
(2)
When remote controller cord embedded
1)
Embed the remote controller cord and box.
2)
Pass the remote controller cord through the hole at the remote
Remote controller cord clamp
controller case bottom and install the cord to the box (Fig. 54).
3)
Connect the remote controller cord to the remote controller terminal board specified in (Fig. 52).
Fig. 54 [Example]
Remote controller case top
Remote controller cord
Remote controller case bottom
After wiring work is complete, return the remote controller case
top to its original state.
CAUTION
Do not bundle the remote controller cord, or wire
1
the remote controller cord in parallel, with the indoor unit connection wire (to the outdoor unit) and the power supply cord. It may cause erroneous operation.
When installing the remote controller and cord near
2
a source of electromagnetic waves, separate the rem­ote controller from the source of the electromagnet­ic waves and use shielded cord.
Do not touch the remote controller PC board and PC
3
board parts directly with your hands.
TEST RUNNING
1. REMOTE CONTROLLER
Supply power to the crankcase heater 12 hours before the start
of operation in the winter. For test running, when the remote controller FAN CONTROL but-
ton and MASTER CONTROL button are pressed simultaneously for more than three seconds when the air conditioner is not run­ning, the air conditioner starts and TEST is displayed on the rem­ote controller display. However, the SET TEMP./DAY setting button does not function, but all other buttons, displays, and protection functions operate (Fig. 55).
Fig. 55
CLOCK
NON STOP
21
TIMER
SET TIME TEMP./DAY FAN
MODE
CLOCK ADJUST
TEMP
ZONE
SET
°C
CONTROL
ENERGY SAVE
DAY OFF
AUTO
HIGH
COOL
DEFROST TEST
MASTER
CONTROL
START/STOP
When EE:EE blinks at the current time display, there is an error
inside the air conditioner. If the SET TIME button ( ) and SET TEMP./DAY button ( ) are pressed simultaneously for more than three seconds, the self diagnosis check will start and the error contents will be displayed at the current time display (Fig. 56). When the operation lamp lights, press the START/STOP button and after operation lamp goes off, perform the same operation (Fig. 56). Process the error contents by referring to (Table 9).
Fig. 56
CLOCK
NON STOP
21
TIMER MODE
CLOCK ADJUST
TEMP
°C
HIGH
SET TIME TEMP./DAY FAN
ZONE
SET
CONTROL
ENERGY SAVE
DAY OFF
AUTO
COOL
DEFROST
MASTER
CONTROL
START/STOP
21
TIMER
SET TIME TEMP./DAY FAN
MODE
CLOCK ADJUST
ZONE
SET
AUTO
CONTROL
ENERGY SAVE
DAY OFF
MASTER
CONTROL
START/STOP
Stop operation.
Table 9
Error cord
Error contents
Communication error (indoor unit remote controller)
Communication error (indoor unit outdoor unit)
Room temperature sensor open
Room temperature sensor shorted
Indoor heat exchanger temperature sensor open
Indoor heat exchanger temperature sensor shorted
Outdoor heat exchanger temperature sensor open
Outdoor heat exchanger temperature sensor shorted
Power source connection error
Float switch operated
Outdoor temperature sensor open
Outdoor temperature sensor shorted
Discharge pipe temperature sensor open
Discharge pipe temperature sensor shorted
Outdoor high pressure abnormal
Discharge pipe temperature abnormal
Model abnormal
Indoor fan abnormal
Outdoor signal abnormal
Outdoor EEPROM abnormal
2. OUTDOOR UNIT
When the outdoor temperature drops, the outdoor unit's fans may switch to low speed, or one of the fans may stop intermittently.
ERROR
The LED lamps operate as follows (Table 10) according to the error contents.
Table 10
Error contents LED1 LED2 LED3 LED4 LED5 LED6
Signal abnormal
Indoor unit abnormal
Discharge pipe temperature abnormal
Outdoor heat exchanger temperature abnormal
Outdoor temperature abnormal
Power sorce connection error
EEPROM abnormal
− − × ○ × ×
− − × × ○ ×
− − × × × ○
− − × × ○ ○
− − × ○ × ○
− − ○ × × ×
− − ○ ○ ○ ○
◎ ◎ ◎ ◎ ◎ ◎
Outdoor high pressure abnormal
Discharge pipe temperature abnormal
: 0.5s ON/0.5s OFF (flash) ×: OFF: 0.1s ON/0.1s OFF (flash) : Indefinite
When the fault is cleared, the LED lamp goes off. However, for discharge pipe temperature abnormal and high pres­sure abnormal, the LED lamp lights continuously for 24 hours, as long as the power is not turned off.
3. CHECKING DRAINAGE
To check the drain, remove the water cover and fill with 2 to 3rof water as shown in Fig. 57. The drain pump operates when operating in the cooling mode.
Fig. 57
Drain pipe
Watering pot
○ − − − − −
− ○ − − − −
Water cover
OPENING THE DUCT
CONNECTION HOLE
Fig. 58
Distribution duct Fresh air
Distribution duct
CAUTION
1
When performing hole opening work, be careful not to damage the drain pan.
2
When connecting the distribution duct, to make the air flow easily, block the outlet port with the blower cover insulation as shown by the hatched lines in Fig. 58. For the blocking direction, refer to Fig. 43.
1. DIMENSION
Screw position and connection hole which are fresh air duct and dis­tribution duct.
Fig. 59
97
45
P. D 120
°
ø100
160
12-ø3.3 self tapping screw holes (for 4 mm)
45°
P. D 88
ø70
334.2
2. DISTRIBUTION DUCT AND FRESH AIR DUCT HOLE PROCESSING
Use the distribution duct hole and fresh air duct hole by removing the insulation material as shown below.
Fig. 60
Cut
Cabinet
Cut
Cut off the part (Cabinet) indicated by the arrow in the Fig. 60 with
nippers, needle nose pliers, etc.
Fig. 61
Knife
Insulation (Inner box)
Open the holes and cut the insulation with a knife.
Be careful not to damage the internal parts.
*
Be careful not to cut yourself on the cutout in the metal plate.
*
Please remove the insulation (inner box) left over after cutting.
* Connect the distribution duct.
When mounting the duct, block the gap so that there is no cold
*
Cabinet
air leakage. Insulate the duct and cut connection.
*
CAUTION
The air conditioner cannot take in fresh air by itself. When connecting a fresh air duct, always use a duct fan.
Unit: mm
113
PART NO. 9363217018
Loading...