SPECIFICATIONS
TYPE COOLING
INDOOR UNIT
OUTDOOR UNIT
COOLING CAPACITY
AUG25FUAR
AOG25FNAKT
7.05 kW
ELECTRICAL DATA
POWER SOURCE
FREQUENCY
RUNNING CURRENT
INPUT WATTS
E.E.R.
STARTING CURRENT 27 A
MOISTURE REMOVAL
3N 400 V
50 Hz
4.9 A
2.40 kW
2.94 kW/kW
2.5 L/hr
COMPRESSOR
Hermetic type, 2 pole,
TYPE
DISCRIMINATION
Single phase,
Induction motor, Rotary
5JS290PCA01
REFRIGERANT R410A
HIGH
FAN SPEED
AIR FLOW
DIMENSIONS
H x W x D
WEIGHT
NET / GROSS
REMOTE CONTROLLER TYPE WIRED
INDOOR MED
LOW
OUTDOOR
INDOOR
OUTDOOR
INDOOR
GRILLE
OUTDOOR
INDOOR
OUTDOOR
1,550 g
490 r.p.m.
430 r.p.m.
360 r.p.m.
780 r.p.m.
1,100 m3/hr
3,200 m3/hr
246 x 830 x 830 mm
35 x 940 x 940 mm
650 x 830 x 320 mm
34 kg / 44 kg
56 kg / 60 kg
ADDITIONAL REFRIGERANT CHARGE (R410A)
PIPE LENGTH 7.5 m (24 ft.)
1,550 g (54.7 oz)
10 m (33 ft.)
FULL CHARGE AMOUNT
ADDITIONAL CHARGE
MAX PIPE LENGTH 25 m
MAX PIPE HEIGHT 15 m
15 m (49 ft.)
20 m (66 ft.)
25 m (82 ft.)
2006.05.24 1
1,600 g (56.4 oz)
1,700 g (60.0 oz)
1,800 g (63.5 oz)
1,900 g (67.0 oz)
20 g / m (0.7 oz / ft.)
OUTLINE AND DIMENSIONS
INDOOR UNIT Model : AUG25FUAR ( unit : mm )
30
Side view
940
940 830
Bottom view (panel) Bottom view
246
830
Drain inside Dia. ø32
outside Dia. ø37
298.5
60
(Drain pipe)
305.5
248.5 100
70
(Large pipe)
(Small pipe)
235
2006.05.24 2
298.5
305.5
60
(Drain pipe)
248.5 100
70
(Large pipe)
(Small pipe)
200
Side view (Slender setting)Side view (Standard setting)
OUTDOOR UNIT
Model : AOG25FNAKT
( unit : mm )
350
830
320
650
12
Air flow
Bottom
603
2006.05.24 3
343
REFRIGERANT SYSTEM DIAGRAM
Models : AUG25FUAR / AOG25FNAKT
OUTDOOR UNITINDOOR UNIT
Refrigerant pipe
Evaporator
Cooling
: Flare coupling
9.52 mm (3/8")
Refrigerant pipe
15.88 mm (5/8")
Charging valve
Capillary tube
Strainer
Condenser
Compressor
2006.05.24 4
CIRCUIT DIAGRAM
Models : AUG25FUAR / AOG25FNAKT
to remote control unit
Terminal
Filter board
Controller PCB
Thermistor (pipe temp.)
Thermistor (room temp.)
M
Stepping motor
Drain pump motor
INTERNAL OVERLOAD PROTECTOR
PURPLE
MAGNETIC RELAY
to outdoor unit
C. M.
U(S)
V(R)
WHITE
GRAY
4
2
1
6
53
COMPRESSOR
W(C)
BROWN
A1
22
14
21
13
A2
OUTDOOR THERMOSTAT
BROWN
Terminal
H L
C
WHITE
BLUE RED
1 3 6 4
BLACK
WHITE
Fan motor
FM
Fan motor capacitor
THERMAL
F. M.
PROTECTOR
FAN MOTOR
1 3 6 4
R
S
T
RED
TO POWER SUPPLY
WHITE
BLACK
RED
R(L1) S(L2)
BLACK
WHITE
T(L3) N
2006.05.24 5
RELAY
WHITE
3
2(N) 1
C
B
A
GRAY
WHITE
FAN MOTOR CAPACITOR
GRAY
BLACK
FUSE 250V-5A
TO INDOOR UNIT