R22
3 . CASSETTE TYPE :
AU 25ALD-W, AU 25RLD-W
AU 30ALD-W, AU 30RLD-W
D2D_AU022E/02
2007.07.26
3-1. FEATURE
MODELS :
AU 25ALD-W/ AO 25ANAL
AU 25RLD-W/ AO 25RNAL
AU 30ALD-W / AO 30AMBL
AU 30RLD-W / AO 30RMBL
CASSETTE TYPE
AU25-AU30A,R
FEATURES
Easy maintenance
The control box is easily accessible for maintenance work
Wide opening for easy access.
CASSETTE TYPE
AU25-AU30A,R
Detachable,washable filter and intake grille.
Wide opening and long-life filter.
Long-life filter
High efficiency, long-life filter extends the cleaning cycle.
Slim intake grille
Slim type intake grille can fit the ceiling after installation.
20
(unit: mm)
Group controller
Long-life filter
One remote controller can control up to 16 air conditioners.
All of the air conditioners will be operated with the same settings.
Connectable quantity : Maximum 16 indoor units for 1 remote controller.
CLOCK
TEMP.
NON STOP
AUTO
AUTO
OFF
OFFON
HEAT
HIGH
ON
TIMER
TIMER
FAN
MED
DAY
ON
WEEKLY
COOL
LOW
DAY OFF
OFF
2
1
DEFROST TEST
NEXT DAY
TEMP./DAY
SET TIME
FAN
TIMER
CONTROL
MODE
MASTER
CONTROL
CLOCK ADJUST
ZONE
ENERGY SAVE
START/STOP
SET
DAY OFF
- (03 - 01) -
Duct connection hole opening
Fresh air can be introduced through this opening.
Distribution
duct
CASSETTE TYPE
AU25-AU30A,R
Fresh air
CASSETTE TYPE
AU25-AU30A,R
Distribution
duct
Conditioned air can be distributed by means of a distribution duct.
Two-way
One-way
- (03 - 02) -
3-2. REMOTE CONTROLLER
3-2-1. WIRED REMOTE CONTROLLER
FEATURES
Three kinds of timer setup (OFF/ON/WEEKLY) are possible.
CLOCK
TIMER
2
NEXT DAY
SET TIME
14
Display
13
12
11
10
9
8
7
2
1
21
TEMP.
OFF
ON
DAY
ON
DAY OFF
OFF
TEMP./DAY
ZONE
SET
NEXT DAY
AUTO
HIGH
MED
LOW
DEFROST TEST
FAN
CONTROL
MASTER
CONTROL
ENERGY SAVE
START/STOP
DAY OFF
CLOCK
TIMER
AUTO
HEAT
FAN
COOL
NON STOP
OFFON
TIMER
WEEKLY
1
TIMER
MODE
CLOCK ADJUST
2
OFF
ON
ON
OFF
Function of weekly timer
Setting of different on-off time by day.
Setting of set on-off time twice a day.
Setting of time in 5 minute steps.
Timer operation of a reserved day can be temporarily cancelled
by pushing the "DAY OFF" button.
Time setting can be left until the next day.
15
16
CLOCK
TIMER
NEXT DAY
SET TIME
TEMP.
OFF
ON
DAY
ON
DAY OFF
OFF
TEMP./DAY
ZONE
SET
1918
TEMP.
DAY
DAY OFF
CONTROL
ENERGY SAVE
DAY OFF
C
AUTO
HIGH
MED
LOW
FAN
AUTO
HEAT
FAN
COOL
DEFROST TEST
MASTER
CONTROL
START/STOP
AUTO
HIGH
MED
LOW
20
AUTO
HEAT
FAN
COOL
DEFROST TEST
2322
17
1
2
3
4
5
6
24
NON STOP
OFFON
TIMER
WEEKLY
1
TIMER
MODE
CLOCK ADJUST
CASSETTE TYPE
AU25-AU30A,R
Display panel
NON STOP
OFFON
TIMER
WEEKLY
1STAR T/STOP Button
Pressed to start and stop operation.
2 OPERATION Lamp
Lights during operation and when the timer is on.
3DAY OFF Button
Temporary cancellation of one day timer.
4 ENERGY SAVE Button
Turns energy efficient mode on and off.
5 ENERGY SAVE Lamp
Lights up when the unit is in the energy save mode.
6 SET Button
Sets the date, hour minute and on-off time.
7 ZONE Button
Use to turn the zone control on and off.
8 ZONE Lamp
Lights up when the units is in the zone control mode.
9 VERTICAL SWING Button
10 VERTICAL SWING Lamp
11 VERTICAL AIR FLOW DIRECTION Button
12 CLOCK ADJUST Button
13 TIMER MODE Button
Changes the timer mode (NON STOP, OFF TIMER,
ON TIMER, WEEKLY TIMER).
14 SET TIME Button
Sets the current time and on-off time.
15 TEMP./DAY Button
Sets the indoor temperature / days.
16 FAN CONTROL Button
Selects the fan speed (AUTO, HIGH, MED, LOW).
17 MASTER CONTROL Button
Selects the operating mode
(AUTO, HEAT, FAN, COOL).
18 Clock Display
19 Set Temperature / Day Display (TEMP./DAY)
20 Operation Mode Display
21 Timer Mode Display
22 Fan Speed Display
23 DEFROST Display
24 TEST Display
CASSETTE TYPE
AU25-AU30A,R
- (03 - 03) -
3-3. SPECIFICATIONS
AU 25ALD-W AU 30ALD-W AU 25RLD-W AU 30RLD-W
AO 25ANAL AO 30AMBL AO 25RNAL AO 30RMBL
Fin Pitch
1.8 1.8 1.8 1.8
AIR
CIRCULATION
COOL/HEAT
NOISE LEVEL
(SOUND
PRESSURE)
COOL/HEAT
Outer diameter 37.0 / Inner diameter 32.0
Permanent Starting Condenser
COOLING RATED 2.66 - 2.75 3.20 - 3.30 2.60 - 2.70 3.25 - 3.35
HEATING RATED - - 2.38 - 2.53 3.15 - 3.30
COOLING RATED 13.0 - 12.7 14.7 - 14.5 12.3 - 12.3 15.0 - 14.8
HEATING RATED - - 11.3 - 11.7 14.5 - 14.5
COOLING 2.63 - 2.58 2.69 - 2.67 2.67 - 2.61 2.55 - 2.57
HEATING - - 3.26 - 3.16 2.95 - 2.88
CASSETTE TYPE
AU25-AU30A,R
High 1100/- 1200/- 1100/970 1200/1100
Med 940/- 1050/- 940/820 1050/940
Low 780/- 840/- 780/700 840/740
Quiet - - - -
High 3000/- 3320/- 3000/3000 3450/3450
Low 1900/- 2050/- 1900/1900 2100/2100
High 490/- 540/- 490/440 540/490
Med 430/- 480/- 430/380 480/430
Low 360/- 390/- 360/330 390/340
Quiet - - - -
High 720/- 730/- 720/720 760/760
Low 450/- 450/- 450/450 470/470
INDOOR
OUTDOOR
INDOOR 40 40 40 40
OUTDOOR 63 63 63 63
High 44/- 46/- 44/41 46/44
Med 42/- 44/- 42/37 44/40
Low 39/- 41/- 39/34 41/36
kW 7.00 - 7.10 8.60 - 8.80 6.95 - 7.05 8.30 - 8.60
BTU/h 23900 - 24200 29400 - 30000 23700 - 24100 28300 - 29400
kW - - 7.75 - 8.00 9.30 - 9.50
BTU/h - - 26500 - 27300 31800 - 32400
A 61 90 61 90
l/h(pints/h) 2.5(5.3) 4.0(8.5) 2.5(5.3) 4.0(8.5)
52/- 53/- 52/53 53/54
CASSETTE TYPE
AU25-AU30A,R
W 2000 2500 2000 2500
Coil Dimensions
2 × 26 2 × 34 2 × 26 2 × 34
Coil Dimensions
INDOOR
OUTDOOR 700 × 900 × 350 900 × 900 × 350 700 × 900 × 350 900 × 900 × 350
INDOOR
OUTDOOR 783 × 1025 × 445 1045 × 1025 × 445 783 × 1025 × 445 1045 × 1025 × 445
INDOOR
OUTDOOR 67(147) 79(174) 70(154) 80(176)
INDOOR
OUTDOOR 79(174) 91(201) 82(181) 92(203)
LIQUID
GAS
m 25 (Chaegeless:7.5) 30 (Chaegeless:7.5) 25 (Chaegeless:7.5) 25 (Chaegeless:7.5)
m 15 15 15 15
CHARGE g 2050 2400 2100 2700
COOLING 0 to 43 0 to 43 0 to 43 0 to 43
HEATING
660 × 840 × 38.1 864 × 840 × 38.1 660 × 840 × 38.1 864 × 840 × 38.1
MINERAL MINERAL MINERAL MINERAL
- -
WIRED WIRED W IRED WIRED
-5 to 21 -5 to 21
Note: Specifications are based on the following conditions.
Cooling: Indoor temperature of 27°CDB / 19°CWB, and outdoor temperature of 35°CDB/24°CWB.
Heating: Indoor temperature of 20°CDB / 15°CWB, and outdoor temperature of 7°CDB/6°CWB.
Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
mm
- (03 - 04) -
3-4. DIMENSIONS
3-4-1. OUTDOOR UNIT
MODELS : AO 25A, AO 25R
700
CASSETTE TYPE
AU25-AU30A,R
15
900
930
(Unit : mm)
350
Side view
CASSETTE TYPE
AU25-AU30A,R
Front view
Bottom view
MOUNTING POSITION
When there are obstacles at the
back or front sides.
100 mm
or more
600 mm
or more
100 mm
or more
333
804
When there are obstacles at the
back, side(s), and top.
600 mm or more
300 mm
250 m
(
Servic
m
or
e space)
mor
or more
e
19
When there are obstacles at the
back, side with the installation of
more than one unit.
250 mm
or more
250 mm
or more
300 mm
or more
- (03 - 05) -
MODELS : AO 30A, AO 30R
(Unit : mm)
350
CASSETTE TYPE
AU25-AU30A,R
900
Side view
CASSETTE TYPE
AU25-AU30A,R
930
Front view
900
333
19
804
Bottom view
MOUNTING POSITION
When there are obstacles at the
back or front sides.
100 mm
or more
600 mm
or more
100 mm
or more
When there are obstacles at the
back, side(s), and top.
600 mm or more
300 mm
250 mm
(
Ser
v
or
i
c
e s
m
o
pace
- (03 - 06) -
or more
r
e
)
When there are obstacles at the
back, side with the installation of
more than one unit.
250 mm
or more
250 mm
or more
300 mm
or more
3-4-2. INDOOR UNIT
750
830
750
830
Bottom view
MODELS : AU 25A, AU 25R, AU 30A, AU 30R
CASSETTE TYPE
AU25-AU30A,R
940
(Unit : mm)
246
30
Side view
CASSETTE TYPE
AU25-AU30A,R
940
Bottom view (Panel)
Drain inside Dia. 32
outside Dia. 37
235
Side view (Standard setting)
60
(Drain pipe)
200
305.5
Side view (Slender setting)
298.5
248.5
100
70
(Small pipe)
(Large pipe)
- (03 - 07) -
MOUNTING POSITION
Strong and durable ceiling
CASSETTE TYPE
AU25-AU30A,R
2,300 mm
or more
1,200 mm
or more
1,000 mm
or more
CASSETTE TYPE
AU25-AU30A,R
Obstruction
You can select 2-way setting
(A) Standard setting (B) Slender setting
215 mm
250 mm
or more
100 or more 100 or more
or more
100 or more
(4 directions) (3 directions)
Piping position
(2 directions) (2 directions)
100 or more
- (03 - 08) -