General ARG30F, ARG30FUAN, AOG30FNBWL, ARG30U, ARG30UUAN Service Manual

...
SPLIT TYPE AIR CONDITIONER (50Hz)
DUCT
Models Indoor unit Outdoor unit
ARG30FUAN AOG30FNBWL ARG30UUAN AOG30UNBWL
type
2005.07.29
CONTENTS
SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
REFRIGERANT SYSTEM DIAGRAM . . . . . . . . . . . . . .4
CIRCUIT DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
ERROR CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
INDOOR P. C. BOARD CIRCUIT DIAGRAM . . . . . . . .8
SPECIFICATIONS
TYPE COOLING COOLING & HEATING
INDOOR UNIT
OUTDOOR UNIT
COOLING CAPACITY (kW) 8.40 8.40
HEATING CAPACITY (kW) ------- 9.50
ELECTRICAL DATA
POWER SOURCE (V) 230
FREQUENCY (Hz) 50
RUNNING CURRENT
INPUT WATTS (kW)
E.E.R. (kW/kW)
MOISTURE REMOVAL ( /hr) 3.0
AIR CIRCULATION (m3/hr) 1,400
COOLING 14.0 14.0
(A)
HEATING ------- 12.4
COOLING 2.99 2.99
HEATING ------- 2.63
COOLING 2.81 2.81
HEATING ------- 3.61
ARG30FUAN ARG30UUAN
AOG30FNBWL AOG30UNBWL
COMPRESSOR
TYPE Hermetic type, 2 poles, Induced by condenser, Rotary
DISCRIMINATION 5JS330DAE01
FAN MOTOR
POWER SOURCE (V) 230
DISCRIMINATION MFA-30PTT
INDOOR UNIT
OUTDOOR UNIT
HI-SPEED (r.p.m.) 990
MED-SPEED (r.p.m.) 920
LO-SPEED (r.p.m.) 850
DISCRIMINATION MFB-30PTT
HI-SPEED (r.p.m.) 780
LO-SPEED (r.p.m.) 400
DIMENSIONS
INDOOR UNIT
OUTDOOR UNIT 830 x 900 x 330
H x W x D(mm)
270 x 1,135 x 700
WEIGHT
INDOOR UNIT
OUTDOOR UNIT 74 / 68 75 / 69
GROSS / NET (kg)
50 / 43
ADDITIONAL REFRIGERANT CHARGE (R410A)
PIPE LENGTH 7.5 m 2,300 g 2,300 g
FULL CHARGE AMOUNT
ADDITIONAL CHARGE 20 g / m 40 g / m
10.0 m 2,350 g 2,400 g
20.0 m 2,550 g 2,800 g
30.0 m 2,750 g 3,200 g
- 1 -
2005.07.29
DIMENSIONS
INDOOR UNIT
Models :
ARG30FUAN ARG30UUAN
(Unit : mm)
2005.07.29
- 2 -
OUTDOOR UNIT
(Unit : mm)
Models :
AOG30FNBWL AOG30UNBWL
3003177900
12
830
21
9
400
650
Air Flow
370
196
99
147
- 3 -
170
2005.07.29
REFRIGERANT SYSTEM DIAGRAM
Models :
ARG30FUAN / AOG30FNBWL
OUTDOOR UNIT
Condenser
Pressure Check Valve
Compressor
Capillary Tube
Accumulator
INDOOR UNIT
Refrigerant pipe
15.88mm(5/8")
Charging Valve
Evaporator
Models :
ARG30UUAN / AOG30UNBWL
OUTDOOR UNIT
Condenser
Strainer
Muffler
Pressure Check Valve
4-Way Valve
Compressor
Capillary Tube
Refrigerant pipe
9.52mm(3/8")
INDOOR UNIT
Refrigerant pipe
15.88mm(5/8")
Charging Valve
Accumulator
Evaporator
2005.07.29
: Cool : Heat
Strainer
Strainer
Refrigerant pipe
9.52mm(3/8")
- 4 -
CIRCUIT DIAGRAM
Models :
ARG30FUAN / AOG30FNBWL
INDOOR UNIT
OUTDOOR UNIT
COMPRESSOR
COMPRESSOR CAPACITOR
FUSE
TO POWER SUPPLY
C
C M
SR
RED
BLACK
GRAY
BLACK
INTERNAL OVERLOAD PROTECTOR
RELAY
WHITE
WHITE
WHITE
WHITE
1NL23
PURPLE
15
46
BROWN
BLACK
BROWN
C
OUTDOOR THERMOSTAT
TERMINAL
TO INDDR UNIT
H
L
BLUE RED WHITE BLACK
FAN MOTOR CAPACITOR
1364
FAN MOTOR
1364
THERMAL PROTECTOR
F M
- 5 -
2005.07.29
Models :
ARG30UUAN / AOG30UNBWL
INDOOR UNIT
OUTDOOR UNIT
COMPRESSOR
COMPRESSOR CAPACITOR
FUSE
C
C M
SR
RED
BLACK
GRAY
WHITE
1NL23
BLACK
INTERNAL OVERLOAD PROTECTOR
WHITE
WHITE
THERMAL PROTECTOR
15
RELAY
46
RED
BLACK
TERMINAL
F M
FAN MOTOR
FAN MOTOR CAPACITOR
RED
RED WHITE BLACK
1364
BLUE
1364
RED WHITE BLACK
YELLOW
YELLOW
GRAY
GRAY
21
21
4321
7531
21
21
GRAY
BLACK
21
21
BLACK
BROWN
21
21
BROWN
BLACK
13
21
BLACK
THERMISTOR (PIPE TEMP.)
THERMISTOR (OUTDOOR TEMP.)
THERMISTOR (DISCHARGE TEMP.)
4WV
SOLENOID COIL
BLACK
13
21
21
21
3
51
21
3
BLACK
RED
21
21
RED
21
21
BELT HEATER
PRINTED CIRCUIT BOARD
PURPLE
31
21
PURPLE
TRANSFORMER
2005.07.29
TO POWER SUPPLY
TO INDDR UNIT
FUSE
- 6 -
ERROR CONTENTS
(1) Stop the air conditioner operation. (2) Press the master control button and the fan control button simultane-
ously for 2 seconds or more to start the test run.
Test run display
(3) Press the start/stop button to stop the test run.
[SELF-DIAGNOSIS]
When the error indication E:EE is displayed, follow the following items to perform the self-diagnosis. E:EE indicates an error has occurred.
1. REMOTE CONTROLLER DISPLAY
1) Stop the air conditioner operation.
2) Press the set temperature buttons simultaneously for 5 sec­onds or more to start the self-diagnosis. Refer to the following tables for the description of each error code.
Unit number (usually 0)
Error code
SUMOTUWETH FR
SA
Ex. Self-diagnosis
(3) Press the set temperature buttons simultaneously for 5 sec-
onds or more to stop the self-diagnosis.
Error code Error contents
00 01
02
03 04 05 06
07 08 09
0A
0b 0c
0d 0E 0F
11
12
13
14
Communication error (indoor unit remote controller)
Communication error (indoor unit outdoor unit)
Room temperature sensor open
Room temperature sensor short-circuited
Indoor heat exchanger temperature sensor open
Indoor heat exchanger temperature sensor short­circuited
Outdoor heat exchanger temperature sensor open
Outdoor heat exchanger temperature sensor short­circuited
Power source connection error
Float switch operated
Outdoor temperature sensor open
Outdoor temperature sensor short-circuited
Discharge pipe temperature sensor open
Discharge pipe temperature sensor short-circuited
Outdoor high pressure abnormal
Discharge pipe temperature abnormal
Model abnormal
Indoor fan abnormal
Outdoor signal abnormal
Outdoor EEPROM abnormal
2. OUTDOOR UNIT
ERROR : Heat & Cool model (Reverse cycle) only
When a malfunction occurs in the outdoor unit, the LEDs on the circuit board light to indicate the error. Refer to the following table for the de­scription of each error according to the LEDs.
Error display
LED1 LED2
0.1 sec.
ON
OFF
Quick flash continued Quick flash continued
0.5 sec.
ON
OFF
1 quick flash repeated Lighting continued
ON
OFF
2 quick flash repeated Lighting continued
ON
OFF
3 quick flash repeated Lighting continued
4 quick flash repeated Lighting continued
5 quick flash repeated Lighting continued
6 quick flash repeated Lighting continued
7 quick flash repeated Lighting continued
8 quick flash repeated Lighting continued
5 quick flash repeated Dislighting continued Discharge temperature
6 quick flash repeated Dislighting continued
2 sec.
0.5 sec.
2 sec.
0.5 sec.
2 sec.
ON
OFF
ON
OFF
ON
OFF
ON
OFF
0.1 sec.
When the fault is cleared, the LED lamp goes off. However, for discharge pipe temperature abnormal and high pressure abnormal, the LED lamp lights continuously for 24 hours, as long as the power is not turned off.
Error contents
Model abnormal or EEPROM abnormal
Power source connection error
Discharge temperature sensor error
Outdoor heat exchanger temperature sensor error
Outdoor temperature sensor error
Communication signal error
Indoor unit error
Discharge temperature abnormal
High pressure abnormal
abnormal (24h)
High pressure abnormal (24h)
– 7 –
2005.07.29
Loading...
+ 16 hidden pages