General ARG30A, ARG30ALC, ARG30R, ARG30RLC Installation Manual

SPLIT TYPE AIR CONDITIONER
Duct Type
INSTALLATION INSTRUCTION SHEET
(PART NO. 9361795037)
For authorized service personnel only.
WARNING!
CAUTION!
1 For the air conditioner to operate satisfactorily, install it as outlined in this installation instruction sheet.
2 Connect the indoor unit and outdoor unit with the room air conditioner piping and cords available from our standard
parts. This installation instruction sheet describes the correct connections using the installation set available from our standard parts.
3 Installation work must be performed in accordance with national wiring standards by authorized personnel only.
4 If refrigerant leaks while work is being carried out, ventilate the area.
If the refrigerant comes in contact with a flame, it produces a toxic gas.
5 Do not turn on the power until all installation work is complete.
Be careful not to scratch the air conditioner when handling it.
After installation, explain correct operation to the customer, using the operating manual.
Let the customer keep this installation instruction sheet because it is used when the air conditioner is serviced or moved.
The maximum length of the piping is shown in Table 1. If the units are further apart than this, correct operation cannot be guaranteed.
STANDARD PARTS
The following installation parts are furnished. Use them as required.
INDOOR UNIT ACCESSORIES
Name and Shape Q’ty Application
Installation template
Hanger
Special nut A (large flange)
Special nut B (small flange)
Coupler heat insulation (large)
Coupler heat insulation (small)
Nylon fastener For fixing the drain hose
Remote controller
Remote controller cord clamp
Tapping screw (flush heads)
Auxiliary pipe assembly
Drain hose insulation
OUTDOOR UNIT ACCESSORIES
Hexagon wrench
Cable clip
Tapping screw (painted)
Drain pipe
Drain cap
SELECTING THE MOUNTING POSITION
Install at a place that can withstand the weight of the indoor and outdoor units and install positively so that the units will not topple or fall.
This mark indicates procedures which, if improperly performed, might lead to the death or serious injury of the user.
This mark indicates procedures which, if improperly performed, might possibly result in personal harm to the user, or damage to property.
WARNING
CAUTION
Do not install where there is the danger of com-
1
bustible gas leakage.
2
Do not install the unit near heat source of heat, steam, or flammable gas.
If children under 10 years old may approach the unit,
For positioning the indoor unit
1
For suspending the indoor unit from ceiling
4
For suspending the indoor unit from ceiling
4
4
For indoor side pipe joint (large pipe)
2
For indoor side pipe joint (small pipe)
1
1
3
take preventive measures so that they cannot reach the unit.
Decide the mounting position together with the customer as follows:
INDOOR UNIT
(1)
Install the indoor unit on a place having a sufficient strength so that it withstands against the weight of the indoor unit.
(2)
The inlet and outlet parts should not be obstructed; the air should be able to blow all over the room.
(3)
Leave the space required to service the air conditioner (Fig. 1).
Fig. 1
Left side
300 mm (12”) or more
Install the unit where the drain pipe can be easily installed.
(4)
Providing as much space as possible between the indoor unit and
(5)
the ceiling will make work much easier.
Strong and durable ceiling
Indoor unit
OUTDOOR UNIT
WARNING
Install the unit where it will not be tilted by more than 5°.
1
When installing the outdoor unit where it may
1
2
exposed to strong wind, fasten it securely.
If possible, do not install the unit where it will exposed to direct sun-
For installing the remote controller cord
10
For installing the remote controller cord clamp
10
For wiring conduit (gas side) connection
1
Insulates the drain hose and vinyl hose connection
1
For opening the refrigerant valve on the outdoor unit
1
For power supply cord binding
2
(1)
light. (If necessary, install a blind that does not interfere with the air flow.) Install the outdoor unit in a place where it will be free from being
(2)
dirty or getting wet by rain as much as possible. Install the unit when connection to the indoor unit is easy.
(3)
During heating operation, drain water flows from the outdoor
(4)
unit. Therefore, install the outdoor unit in a place where the drain water flow will not be obstructed. (Heat & Cool model (Reverse cycle) only) Do not place animals and plants in the path of the warm air.
(5)
Take the air conditioner weight into account and select a place
(6)
where noise and vibration are small. Select a place so that the warm air and noise from the air condi-
(7)
tioner do not disturb neighbors. Provide the space shown in Fig. 2 so that the air flow is not blocked.
(8)
Also for efficient operation, leave open three of the four direc­tions front, rear, and both sides.
Fig. 2
300 mm (12”) or more
AIR
For fixing the valve cover
1
For outdoor unit drain piping work
1
[Heat & Cool (Reverse cycle) model only]
2
300 mm
(12”)
or more
600 mm (24”) or more
600 mm (24”) or more
300 mm
(12”)
or more
WARNING
Right side
150 mm (6”) or more
CONNECTION PIPE REQUIREMENT
CAUTION
The maximum lengths of this product are shown in table 1. If the units are further apart than this, correct operation can not be guaranteed.
Table 1
Small
9.53 mm (3/8”)
Diameter
Maximum length
Large Cooling
15.88 mm (5/8”)
(99 ft)
30 m
Reverse
cycle
25 m
(82 ft)
Maximum height
(between indoor
and outdoor)
(50 ft)
Use 0.7 mm to 1.2 mm thick pipe.
Use pipe with water-resistant heat insulation.
Use pipe that can withstand a pressure of 3,040 kPa.
ELECTRICAL REQUIREMENT
Electric wire size and fuse/breaker capacity:
Table 2
MAX
Power supply cord (mm2)
2
Connection cord (mm
Fuse/Breaker capacity (A)
Install the disconnect device with a contact gap of at least 3 mm
nearby the units. (Both indoor unit and outdoor unit)
)
MIN
MAX
MIN
4.0
3.5
2.5
1.0
30
INSTALLATION PROCEDURE
Install the air conditioner as follows:
1
1. PIPING CONNECTION DIRECTION AND
Fig. 3
2. DRILLING HOLES FOR BOLTS AND
Fig. 4
3. INSTALLING THE HANGERS
Installation method (1)
Fig. 5
Fig. 6
(Example)
INDOOR UNIT INSTALLATION
WARNING
Install the air conditioner in a location which can with-
stand a load of at least five times the weight of the main unit and which will not amplify sound or vibration. If the installation location is not strong enough, the in­door unit may fall and cause injuries.
If the job is done with the panel frame only, there is a risk
that the unit will come loose. Please take care.
PREPARATION
Select piping directions.(Fig. 3)
When bending the piping is difficult, use the auxiliary pipe assembly.
INSTALLING THE BOLTS
Using the installation template, drill holes for bolts (four holes). (Fig. 4)
Installation template
Drilling position for bolts
Fasten the hanging bolts to the ceiling and install special nuts A and B.
Bolt Strength 9.81 to 14.71 N·m(100 to 150 kgf·cm)
Hanging bolt
Special nut A
Special nut B
Install the hangers to the unit.
WARNING
When fastening the hangers, make the bolt positions uni­form.
15 m
Hang the unit.
(1) Pass the hanging bolts through the hangers. (Four places)
Fig. 7
(2) Slide the unit in the arrow direction and fasten it.
Fig. 8
WARNING
Fasten the unit securely with special nuts A and B.
Installation method (2)
Install the bolts to the ceiling at a place strong enough to hang the
unit. Mark the bolt positions from the installation template.
With a concrete drill for
12.7 mm (1/2”) dia. holes. (Fig. 9)
Insert the anchor bolts into the drilled holes, and drive the pins completely into the anchor bolts with a hammer.
Anchor-Bolt Strength
Fig. 10
Install the hangers to the unit.
Fig. 11
When fastening the hangers, make the bolt positions uni­form.
(Example)
Install the unit
Pass the unit hangers over the bolts installed to the ceiling and install the unit with the special nut B.
Fig. 12
4. LEVELING
Base horizontal direction leveling on top of the unit.
Fig. 13
Base vertical direction leveling on the unit (right and left).
Fig. 14
Fig. 9
12.7 mm (ø1/2”)
9.81 to 14.71 N·m(100 to 150 kgf·cm)
WARNING
60 to 70 mm
(2-3/8” to 2-3/4”)
5. SERVICE HOLE DIMENSIONS
It shall be possible to install and remove the control box metal.
Fig. 15
Reference B
2
200 mm
(8”)
500 mm (20”)
500 mm (20”)
OUTDOOR UNIT INSTALLATION
Service hole
Control box metal
(2”)
50 mm
Vertical dimension 500 mm from 50 mm below reference A
Horizontal dimension 500 mm from 200 mm from the left from reference B
1. OUTDOOR UNIT PROCESSING
When the outdor unit will be exposed to strong wind, fasten it with bolts at the places indicated by the arrows. (Fig. 16)
Fig. 16
Bottom
Drain pipe mounting hole
Set the unit on a strong stand, such as one model of concrete blocks to
minimize shock and vibration. Do not set the unit directly on the ground because it will cause trouble.
Air frow
804 mm (31-21/32”)
Drain pipe
Drain cap
Bottom plate
333 mm
(13-7/64”)
19 mm (3/4”)
CAUTION
If this product is used in an area where the temperature falls below freezing for long periods of time, do not con­nect the drain pipe. Instead, allow the water to drain into a drain pan.
2. OUTDOOR UNIT CONNECTION CORD AND PIPE CONNECTION PREPARATIONS
(1)
Remove outdoor unit valve cover.
3
Fig. 17
Connect the piping, connection cord and power supply cord.
(2)
Fig. 18
Power supply cord
Connection cord
CONNECTING THE PIPING
* After removing the screws, remove valve cover
Valve cover take off direction
Valve cover
Valve
Pipe
1. FLARE PROCESSING
Cut the connection pipe with pipe cutters so that the pipe is not
(1)
deformed. Holding the pipe downward so that cuttings cannot enter the pipe
(2)
and remove the burrs. Remove the flare nut from the indoor unit pipe and outdoor unit
(3)
and assemble as shown in (Table 3) and insert the flare nut onto the pipe, and flare with a flaring tool. Check if the flared part “L” (Fig. 19) is spread uniformly and that
(4)
there are no cracks.
Table 3
Flare nut
L dimension Small pipe (9.53 mm dia)
1.8 to 2.0 mm Large pipe (15.88 mm dia)
2.2 to 2.4 mm
Small pipe
Large pipe
Fig. 19
Pipe
Small (width across flats 22 mm)
Large (width across flats 27 mm)
2. BENDING PIPES
The pipes are shaped by your hands. Be careful not to collapse them.
Fig. 20
Reference A
Do not bend the pipes in an angle more than 90°. When pipes are repeatedly bent or stretched, the material will harden, making it difficult to bend or stretch them any more. Do not bend or stretch the pipes more than three times.
When bending the pipe, do not bend it as is. The pipe will be collapsed. In this case, cut the heat insulating pipe with a sharp cutter as shown in Fig. 21, and bend it after exposing the pipe. After bending the pipe as you want, be sure to put the heat insulating pipe back on the pipe, and secure it with tape.
Fig. 21
CAUTION
To prevent breaking of the pipe, avoid sharp bends.
1
Bend the pipe with a radius of curvature of 150 mm or over.
If the pipe is bent repeatedly at the same place, it will
2
break.
3. CONNECTION PIPES
(1)
Indoor unit side
Detach the caps and plugs from the pipes.
CAUTION
Be sure to apply the pipe against the port on the in-
1
door unit correctly. If the centering is improper, the flare nut cannot be tightened smoothly. If the flare nut is forced to turn, the threads will be damaged.
Do not remove the flare nut from the indoor unit pipe
2
until immediately before connecting the connection pipe.
Centering the pipe against port on the indoor unit, turn the flare nut with your hand.
CAUTION
Hold the torque wrench at its grip, keeping it in the right angle with the pipe as shown in Fig. 23, in order to tighten the flare nut correctly.
When the flare nut is tightened properly by your hand, use a tor­que wrench to finally tighten it.
Fig. 22
Holding spanner
Pipe
Small pipe
Large pipe
Torque wrench
Table 4 : Flare nut tightening torque
30.4 to 34.3 N
73.5 to 78.4 N
Fig. 23
Unit side
Tightening torque
·
m (310 to 350 kgf·cm)
·
m (750 to 800 kgf·cm)
90°
CAUTION
Be sure to connect the large pipe after connecting the small pipe completely.
(2) Outdoor unit side
Tighten the flare nut of the connection pipe at the outdoor unit valve connector. The tightening method is the same as that as at the indoor side.
Fig. 24
(Small pipe)
Cnnection pipe
(Large pipe)
2-way valve
Flare nut
3-way valve
4. HEAT INSULATION ON THE PIPE JOINTS (INDOOR SIDE ONLY)
Stick coupler heat insulation (large and small) to the place where
connecting pipes. When using auxiliary piping with large pipe, stick coupler heat insu-
lation (large) to the pipe at the two places shown below.
Fig. 25
Reference A
Coupler heat insulation (large) on the pipe.
Front outlet
Coupler heat insulation (small) on the pipe
Small pipe
Cover this portion with heat insulating material also without fail.
Large pipe
Heat insulating pipe
CAUTION
No gap should remain.
4
VACUUM PROCESS
CAUTION
Do not purge the air with refrigerants but use a vacuum pump to vacuum the installation! There is no extra refriger­ant in the outdoor unit for air purging!
VACUUM
1.
(1)
Remove the cap, and connect the gauge manifold and the vacuum pump to the charging valve by the service hoses.
(2)
Vacuum the indoor unit and the connecting pipes until the pressure in them lowers to below 0.2 kPa (1.5 mmHg.)
(3)
Disconnect the service hoses and fit the cap to the charging valve (Tightening torque : 6.87 to 8.83 N
(4)
Remove the blank caps, and fully open the spindles of the 2-way and 3-way valves with a hexagon wrench (Torque : 2-way valve: 6.87 to
8.83 N
·m (70 to 90 kgf·cm), 3-way valve: 9.81 to 11.77 N·m (100 to
120 kgf
·cm)).
(5)
Tighten the blank caps of the 2-way valve and 3-way valve to the specified torque (19.62 to 24.53 N
Fig. 26
Outdoor unit
Service hose with valve core
Fig. 27
·m (70 to 90 kgf·cm).
·m (200 to 250 kgf·cm)).
Refrigerant pipe
3-way valve
Blank cap
Charging valve
Cap
Gauge manifold
L
O
H
I
Vacuum pump
Service hose
2. ADDITIONAL CHARGE
Refrigerant suitable for a piping length of 7.5 m is charged in the outdoor unit at the factory. When the piping is longer than 7.5 m, additional charging is necessary. For the additional amount, see the table below.
Table 5
Pipe length
Heat & Cool
Additional refrigerant
Between 7.5 m and 25 m or 30 m, when using a connection pipe other than that in the table, charge additional refrigerant with 50 g (1.8 oz)/1 m (3.3 ft) (Reverse cycle model), 20 g (0.7 oz)/1 m (3.3 ft) (Cooling model) as the criteria.
(Reverse cycle)
Cooling
model
7.5 m (25 ft)
None
None
10 m
(33 ft)
125 g
(4.4 oz)
50 g
(1.8 oz)
15 m
(49 ft)
375 g
(13.2oz)
150 g
(5.3 oz)
20 m
(66 ft)
625 g
(22.0 oz)
250 g
(8.9 oz)
25 m
(82 ft)
875 g
(30.9 oz)
350 g
(12.3 oz)
CAUTION
When moving and installing the air conditioner, do not
1
mix gas other than the specified refrigerant (R22) inside the refrigerant cycle.
When adding refrigerant, add the refrigerant from the
2
charging valve at the completion of work.
If the units are further apart than the maximum pipe
3
length, correct operation can not be guaranteed.
5
GAS LEAKAGE INSPECTION
CAUTION
After connecting the piping, check the joints for gas leakage with gas leak detector.
6
INSTALLING DRAIN HOSE
CAUTION
Install the drain hose in accordance with the instructions in this installation instruction sheet and keep the area warm enough to prevent condensation. Problems with the piping may lead to water leaks.
NOTE : INSTALL THE DRAIN HOSE
Install the drain hose with downward gradient (1/50 to 1/100) and so
there are no rises or traps in the hose. Use general hard polyvinyl chloride pipe (VP25) [outside diameter
38 mm] and connect it with adhesive (polyvinyl chloride) so that there is no leakage. When the hose is long, install supporters.
Do not perform air bleeding.
Always heat insulate the indoor side of the drain hose.
Fig. 28
Outlet air flow
OK
Arrange the drain hose lower than this portion.
The outside diameter of the drain port is 38 mm. Use a suitable
drain hose. There is a drain port on both the left and right sides. Select the drain
port to match the local conditions.
Drain hose
NO
Rise
Supporter
1.5 to 2 m (5 to 6.5 ft)
Air bleeding
30 m
(99 ft)
450 g
(15.9 oz)
Trap
- Continued on back -
Fig. 29
When the unit is shipped from the factory, the drain port is on
the left side (control box side). When using the drain port on the right side of the unit, reinstall
the drain cap to the left side drain port.
Fig. 30
CAUTION
1. INDOOR UNIT SIDE
(1)
Remove the control box metal-B from the control box metal assy.
Fig. 34
(2) Connection cord and remote controller cord connections.
Clamp the connection cord with the cable clamp and the remote
controller cord with the nylon clamp. Connect the connection cord to the terminals with the white
characters on the terminal nameplate. Connect the remote controller cord to the terminals with the
black characters on the terminal nameplate.
Fig. 35
Remote controller Power supply
Black
White Red
(N)
3 2 1
3
2
Power line
1
Indoor unit side terminal
Fig. 38
Control line
EARTH
L N 3
2
(N)
1
EARTH
Outdoor unit side terminal
Cable clip
Cable clip
Fig. 42
Remote controller cord
Tapping screw (flush heads)
(2) When remote controller cord embedded
1)
Embed the remote controller cord and box.
2)
Pass the remote controller cord through the hole at the remote controller case bottom and install the cord to the box. (Fig. 43)
3)
Connect the remote controller cord to the remote controller terminal board specified in (Fig. 41).
Fig. 43 [Example]
Remote controller case top
Remote controller cord clamp
Remote controller cord
When EE : EE blinks at the current time display, there is an error
inside the air conditioner. If the SET TIME button ( ) and TEMP./DAY button ( ) are pressed simultaneously for more than three seconds, the self diagnosis check will start and the error contents will be displayed at the current time display (Fig. 45). When the operation lamp lights, press the START/STOP button and after operation lamp goes off, perform the same operation (Fig. 45). Process the error contents by referring to (Table 6).
Fig. 45
CLOCK
NON STOP
21
TIMER MODE
CLOCK ADJUST
Stop Operation.
TEMP
SET TIME TEMP./DAY FAN
ZONE
SET
AUTO
°C
HIGH
COOL
DEFROST
CONTROL
MASTER
CONTROL
START/STOP
ENERGY SAVE ENERGY SAVE
DAY OFF
21
TIMER
SET TIME TEMP./DAY FAN
MODE
CLOCK ADJUST
CONTROL
SET
DAY OFF
AUTO
START/STOP
Table 6
Error code
Error contents
Communication error (indoor unit remote controller)
Communication error (indoor unit outdoor unit)
Room temperature sensor open
MASTER
CONTROL
OUTLET DUCT CONNECTION
1. DUCT INSTALLATION PATTERN (CUT PART)
Fig. 47
(1) Square duct
(2) Round duct outlet × 4 (This is the factory setting.)
2. WHEN USING AS A SQUARE DUCT
Cut the slit seam with a cutter.
(1)
Fig. 48
1312
14
INTAKE PORT REAR COVER
DIMENSIONS
Fig. 52
1,078 mm (42-7/16)
102 mm
10 mm
(13/32)
10 mm
(13/32)
348 mm
(13-11/16)
1,063 mm (41-27/32)
348 mm
(13-11/16)
INTAKE PORT
The square flange (rear side) and panel (intake panel) are instal-
(1)
led at the factory at the places shown in Fig. 53. When taking in air from the bottom side, reinstall the square
(2)
flange (rear side) and panel (intake panel).
(4-1/32)
204 mm
(8-1/32)
Always check that the drain cap is installed to the un­used drain port and is fastened with the nylon fastener. If the drain cap is not installed, or is not sufficiently fas­tened by the nylon fastener, water may drip during the cooling operation.
Cut the drain hose insulation at a position approximately 30 mm
from the end with cutters, etc. (Fig. 31-(1)) Stick the large drain hose insulation at the drain hose installation
side. (Fig. 31-(2)) Stick the small drain hose insulation at the drain cap side (Fig. 31-(3))
Fig. 31-(1)
450 mm (17-23/32)
170 mm
(6-11/16)
Fig. 31-(2)
Drain hose insulation (large)
Unit
Drain hose
Cut line
30 mm (1-3/16)
420 mm (16-17/32)
170 mm
(6-11/16)
Unit
Drain hose insulation (large)
0 mm (0)
170 mm ( 6-11/16)
Drain hose
30 mm (1-3/16)
CAUTION
1
Tighten the indoor unit connection cord (to the out­door unit) indoor and outdoor unit terminal board connections firmly with the terminal board screws. Faulty connection may cause a fire.
2
If the indoor unit connection cord (to the outdoor unit) are wired incorrectly, the air conditioner may be damaged.
3
Wire the indoor unit connection cord (to the outdoor unit) by matching the numbers of the outdoor and indoor units terminal board numbers as shown in (Fig. 35).
4
Ground both the indoor and outdoor units by attach­ing a ground wire.
(3)
Install the valve cover.
Fig. 39
2
Valve cover
1
Attach the four fasteners.
3
Reinstall the removed screws.
Accessory part
Remote controller case bottom
After wiring work is complete, return the remote controller case
top to its original state.
CAUTION
Do not bundle the remote controller cord, or wire
1
the remote controller cord in parallel, with the in­door unit connection wire (to the outdoor unit) and the power supply cord. It may cause erroneous oper­ation.
When installing the remote controller and cord near
2
a source of electromagnetic waves, separate the re­mote controller from the source of the electromag­netic waves and use shielded cord.
Do not touch the remote controller PC board and PC
3
board parts directly with your hands.
Room temperature sensor shortcircuited
Indoor heat exchanger temperature sensor open
Indoor heat exchanger temperature sensor shortcircuited
Outdoor heat exchanger temperature sensor open
Outdoor heat exchanger temperature sensor shortcircuited
Power source connection error
Float switch operated
Outdoor temperature sensor open
Outdoor temperature sensor shortcircuited
Discharge pipe temperature sensor open
Discharge pipe temperature sensor shortcircuited
Outdoor high pressure abnormal
Discharge pipe temperature abnormal
Model abnormal
Indoor fan abnormal
Outdoor signal abnormal
Outdoor EEPROM abnormal
(2)
Turn up the insulation around the points to be cut according to the outlet port shape working points so that the insulation does not stick out at the part.
Fig. 49
Cut with nippers and remove the sheet metal.
(3)
Since there is a slit in the insulation, use radio pliers, tweezers, etc.
(4)
to stretch tight the screw hole part used when installing the round flange and square flange when connecting the duct.
Fig. 50
15
CAUTION
When air is taken in from the bottom side, the operating sound of the product will easily enter the room. Install the product and intake grilles where the affect of the operating sound is small.
Fig. 53
FRESH AIR IN TAKE
(Processing before use)
When taking in fresh air, cut a slit shaped cabinet in the left side
(1)
of the outer case as shown in Fig. 54 with nippers.
7
Fig. 31-(3)
Drain hose insulation (small)
0 mm (0)
Unit
Drain hose insulation (small)
Unit
Drain cap
ELECTRICAL WIRING
HOW TO CONNECT WIRING TO THE TERMINALS A. For solid core wiring (or F-cable)
Cut the wire end with a wire cutter or wire-cutting pliers,
(1)
then strip the insulation to about 25 mm (15/16) to ex­pose the solid wire. Using a screwdriver, remove the terminal screw(s) on the
(2)
terminal board. Using pliers, bend the solid wire to form a loop suitable
(3)
for the terminal screw. Shape the loop wire properly, place it on the terminal
(4)
board and tighten securely with the terminal screw using a screwdriver.
B. For strand wiring
(1)
Cut the wire end with a wire cutter or wire-cutting pliers, then strip the insulation to about 10 mm (3/8) to expose the strand wiring.
(2)
Using a screwdriver, remove the terminal screw(s) on the terminal board.
(3)
Using a round terminal fastener or pliers, securely clamp a round terminal to each stripped wire end.
(4)
Position the round terminal wire, and replace and tighten the terminal screw with a screwdriver.
Fig. 32
A. Solid wire B. Strand wire
Loop
Insulation
Strip 25 mm (15/16)
Wire
Screw with special washer
Round terminal
Wire
HOW TO FIXED CONNECTION CORD AND POWER SUPPLY CORD AT THE CORD CLAMP
After passing the connection cord and power supply cord through the insulation tube, fasten it with the cord clamp.
Fig.33
Use VW-1, 12 mm diameter, 0.5 to 1.0 mm thick, PVC tube as the insulation tube.
Strip 10 mm (3/8)
Screw with special washer
Round terminal
Round terminal
5
Unit shall be grounded in compliance with the appli­cable local and national codes.
(3)
Control box matel-B installation Fasten control box metal-B with the two screws. For the connection cord outlet port see Fig. 36.
Fig. 36
2. OUTDOOR UNIT SIDE
WARNING
Before starting work, check that power is not being
1
supplied to the indoor unit and outdoor unit.
Match the terminal board numbers and connection
2
cord colors with those of the indoor unit side. Erroneous wiring may cause burning of the electric parts.
Connect the connection cord and the power supply
3
cord firmly to the terminal board. Imperfect installa­tion may cause a fire.
Always fasten the outside covering of the connec-
4
tion cord and the power supply cord with the cord clamp. (If the insulator is chafed, electric leakage may occur.)
Always connect the ground wire.
5
(1)
Remove outdoor unit valve cover and connect the power supply cord and the outdoor unit connection cord wired at the indoor unit.
(2)
Fasten the power supply cord and connection cord with cable clip and binders as shown in (Fig. 38).
Fig. 37
Control box
Cord clamp
Power cord
Terminal board
LN3
Power cord
Ground
Connection cord (indoor unit and outdoor unit connection cord)
(N)
2
1
Make longer than the other wires.
8
REMOTE CONTROLLER
INSTALLATION
When mounting the remote controller, refer to the en­closed REMOTE CONTROLLER INSTALLATION INSTRUC­TION SHEET. Then, make the necessary settings on both the remote controller and the main unit.
Insert the end of a flat blade screwdriver at the arrow parts of the
groove at the side of the remote controller case and remove the remote controller case top by turning the screwdriver. Disconnect the remote controller cord from the remote controller
terminal board.
Fig. 40
CLOCK
TEMP
NON STOP
21
TIMER
SET TIME TEMP./DAY FAN
MODE
CLOCK ADJUST
When remote controller exposed
(1)
Make a notch in the thin part ( part of Fig. 40) at the remote
1) controller case top and bottom with nippers, file, etc. Connect the remote controller cord to the remote controller
2) terminal board specified in (Fig. 41). Clamp the remote controller cord sheath with the binder
3) (small) as shown in Fig. 41. Cut off the excess binder.
4) Clamp the remote controller cord to a wall, etc. with the re-
5) mote controller cord clamp furnished (Fig. 42).
Fig. 41
Remote controller cord
Binder (small)
Red
ZONE
SET
AUTO
°C
HIGH
CONTROL
ENERGY SAVE
DAY OFF
White
COOL
DEFROST
MASTER
CONTROL
START/STOP
Black
Remote controller terminal board
9
10
POWER
WARNING
1
The rated voltage of this product is 1ø 220-240 V 50 Hz.
2
Before turning on the verify that the voltage is within the 198 V to 264 V range.
3
Always use a special branch circuit and install a special re­ceptacle to supply power to the air conditioner.
4
Use a circuit breaker and receptacle matched to the ca­pacity of the air conditioner. (Install in accordance with standard.) When connecting the power supply to the outdoor unit, always install a circuit breaker between the outdoor unit and the power supply. Use the circuit breaker has an iso­lation distance of at least 3 mm between the contacts of each pole.
5
Perform wiring work in accordance with standards so that the air conditioner can be operated safely and posi­tively.
6
Install a leakage circuit breaker in accordance with the re­lated laws and regulations and electric company stan­dards.
CAUTION
The power source capacity must be the sum of the
1
air conditioner current and the current of other elec­trical appliances. When the current contracted ca­pacity is insufficient, change the contracted capacity.
When the voltage is low and the air conditioner is
2
difficult to start, contact the power company the vol­tage raised.
TEST RUNNING
1. REMOTE CONTROLLER
Supply power to the crankcase heater 12 hours before the start
of operation in the winter. For test running, when the remote controller FAN CONTROL
button and MASTER CONTROL button are pressed simultane­ously for more than three seconds when the air conditioner is not running, the air conditioner starts and TEST is displayed on the remote controller display. However, the TEMP./DAY setting button does not function, but all other buttons, displays, and protection functions operate (Fig. 44).
Fig. 44
CLOCK
NON STOP
21
TIMER
SET TIME TEMP./DAY FAN
MODE
CLOCK ADJUST
TEMP
ZONE
SET
°C
AUTO
HIGH
CONTROL
DAY OFF
COOL
DEFROST TEST
MASTER
CONTROL
START/STOP
To stop test running, press the START/STOP button.
For the operation method, refer to the operating manual and per-
form operation check. Check that there are no abnormal sounds or vibration sounds
during the test running.
2. OUTDOOR UNIT
When the outdoor temperature drops, the outdoor unit's fans may switch to low speed, or one of the fans may stop intermittently.
ERROR: HEAT & COOL (REVERSE CYCLE) MODEL ONLY
The LED lamps operate as follows (Table 7) according to the error contents. The LED lamps are on the outdoor unit board.
ON
OFF
ON
OFF
ON
OFF
ON
OFF
4 quick flash repeated
5 quick flash repeated
6 quick flash repeated
7 quick flash repeated
8 quick flash repeated
When the fault is cleared, the LED lamp goes off. However, for discharge pipe temperature abnormal and high pres­sure abnormal, the LED lamp lights continuously for 24 hours, as long as the power is not turned off.
11
Fig. 46 FAN PERFORMANCE AND AIR FLOW
EXTERNAL STATIC PRESSURE (mmAq)
Table 7
Error display
Error contentsLED2LED1
0.1 sec.
0.5 sec.
2 sec.
0.5 sec.
2 sec.
0.5 sec.
2 sec.
0.1 sec.
ON
OFF
Quick flash continuedQuick flash continued
ON
OFF
Lighting continued1 quick flash repeated
ON
OFF
Lighting continued2 quick flash repeated
ON
OFF
Lighting continued3 quick flash repeated
Lighting continued
Lighting continued
Lighting continued
Lighting continued
Lighting continued
Model abnormal or EEPROM abnormal
Power source connection error
Discharge temperature sensor error
Outdoor heat exchanger temperature sensor error
Outdoor temperature sensor error
Communication signal error
Indoor unit error
Discharge temperature abnormal
High pressure abnormal
STATIC PRESSURE
CHARACTERISTIC
EXTERNAL STATIC PRESSURE
RECOMMENDED RANGE
20 196
18
16
14
12
10 98
8
6
4
2
0 0
400 600 800 1,000 1,200 1,400 1,600 1,800 2,000 2,200 2,400
LOW
HIGH
AIR FLOW (m
3
/H)
(Pa)
3. SPECIAL ITEMS
When connecting the square duct and round duct, use the optional square flange or round flange and flexible duct.
Fig. 51
Square flange
Model name : UTD-SF045 (P/N 9054229009) (P/N 9098180007)
Square flange dimensions
40 mm
(1-19/32)
204 mm
(8-5/16)
1,065 mm (41-15/16)
Round flange
Model name : UTD-RF204 (P/M 9093160004)
Round flange dimensions
ø225 mm
(8-7/8
”)
ø205
ø195
85
Flexible duct
Model name : UTD-RD202 (P/N 9074165004)
ø235 mm
”)
(9-1/4
ø200 mm (7-7/8) L 2 m (78-3/4)
Fig. 54
CAUTION
When removing the cabinet (iron plate), be careful not
1
to damage the indoor unit internal parts and sur­rounding area (outer case).
When processing the cabinet (iron plate), be careful
2
not to injure yourself with burrs, etc.
(2)
Install the round flange (optional parts) to the fresh air intake.
Fig. 55
(3)
Connect the duct to the round flange.
(4)
Seal with a band and vinyl tape, etc. so that air does not leak from the connection.
Fig. 56
Duct
PART NO. 9361795037
Loading...