General ARG30A, ARG30ALC, AOG30AMBL Technical Manual

R22
3 . DUCT TYPE : ARG30ALC
D2D_AR012E/01
2005.09.15
3-1. FEATURE
MODELS : ARG30ALC / AOG30ABBDL
DUCT TYPE
AR30
FEATURES
Installation styles
Embedded in Ceiling
Hanging from Ceiling
DUCT TYPE
AR30
- (03 - 01) -
3-2. REMOTE CONTROLLER
3-2-1. WIRED REMOTE CONTROLLER WITH WEEKLY TIMER
FEATURES
Three kinds of timer setup (OFF/ON/WEEKLY) are possible.
REMOTE CONTROLLER WITH WEEKLY TIMER
1
DAY CODE
MON2TUE3WED4THU5FRI6SAT
DUCT TYPE
AR30
TEMP./DAY
SET TIME
TIMER MODE
CLOCK ADJUST
FUNCTIONS
Setting of different on-off time by day
Setting of set on-off time twice a day
Setting of time in 5 minute steps
Timer operation of a reserved day can be temporarily cancelled by pushing the DAY OFF button.
Time setting can be left until the next day.
11
Display
10
9
8
7
Display panel
NON STOP OFFON TIMER WEEKLY
2
1
REMOTE CONTROLLER WITH WEEKLY TIMER
1
DAY CODE
MON2TUE3WED4THU5FRI6SAT
SET TIME
TIMER MODE
CLOCK ADJUST
CLOCK
OFF
ON
TIMER
ON
NEXT DAY
OFF
TEMP./DAY
ZONE
SET
1615
TEMP.
DAY
DAY OFF
CONTROL
ENERGY SAVE
DAY OFF
C
FAN
MASTER
CONTROL
START/STOP
AUTO
HIGH MED LOW
ZONE
SET
FAN
CONTROL
MASTER
CONTROL
ENERGY SAVE
START/STOP
DAY OFF
17
HEAT FAN COOL
DEFROST TEST
12
13
14
1 START/STOP Button
Pressed to start and stop operation.
2 OPERATION Lamp
Lights during operation and when the timer is on.
3 DAY OFF Button
Temporary cancellation of one day timer
4 ENERGY SAVE Button
Turns energy save mode on and off.
5 ENERGY SAVE Button
Lights when the unit is in the energy save mode.
6 SET Button
1
2
3
4
5
6
Sets the date, hour, minute and on-off time.
7 ZONE Button
Use to turn zone control on and off.
8 ZONE Lamp
Lights when the unit is in the zone control mode.
9 CLOCK ADJUST Button
10 TIMER MODE Button
Changes the timer mode (NON STOP, OFF TIMER, ON TIMER, WEEKLY TIMER).
11 SET TIME Button
Sets the current time and on-off time.
12 TEMP./DAY Button
Sets the indoor temperature / day.
#
13 FAN CONTROL Button
14 MASTER CONTROL Button
Selects the operating mode (HEAT, FAN, COOL).
15 Clock Display 16 Set Temperature / Day Display (TEMP./DAY) 17 Operation Mode Display 18 Timer Mode Display
#
19 Fan Speed Display 20 DEFROST Display 21 TEST Display
DUCT TYPE
AR30
18
2019
21
#NOTE :
This model does not have a fan speed function.
- (03 - 02) -
3-3. SPECIFICATIONS
DUCTED MODELS
COOLING TYPE
ARG30ALC
AOG30ABBDL
220-240V〜 50Hz
198-264V 〜 50Hz
kW 8.6 - 8.8
BTU/h
29300‑30000
kW -
BTU/h -
COOLING RATED 3.3 - 3.4
HEATING RATED -
COOLING RATED 15.8 - 16.3
HEATING RATED -
A 80
EER COOLING 2.61 - 2.59
COP HEATING -
l/h (pints/h) 4.0 (8.45)
High 1750 / -
Med 1650 / -
Low 1450 / -
Quiet -
High 3320 / -
Low -
High 1240 / -
Med 1140 / -
Low 1040 / -
Quiet -
High 730 / -
Low 450 / -
Pa 59 to 177
INDOOR 1
OUTDOOR 1
INDOOR 275
OUTDOOR 63
High 47.0 / -
Med 45.0 / -
Low 43.0 / -
55.0 / -
RECIPRO
OUTPUT W 2800
Permanent Starting Condenser
Copper tube
Alminum fin
Rows x Stages mm 2 x 12
Fin Pitch mm 1.50
Coil Dimensions mm
308x1000x38.1
Copper tube
Alminum fin
Rows x Stages mm 2 x 34
Fin Pitch mm 1.80
Coil Dimensions mm
864x840x38.1
TYPE
MODEL NAME
INDOOR
OUTDOOR
POWER SOURCE
AVAILABLE VOLTAGE RANGE
CAPACITY
COOLING
RATED
HEATING
RATED
INPUT POWER
kW
CURRENT
A
STARTING CURRENT
kW/kW
MOISTURE REMOVAL
AIR CIRCULATION COOL/HEAT (at 240V)
INDOOR
m3/h
OUTDOOR
FAN SPEED COOL/HEAT (at 240V)
INDOOR
r.p.m
OUTDOOR RECOMMENDED STATIC PRESSURE
FAN TYPE x Q'ty
FAN MOTOR OUTPUT
W
NOISE LEVEL (SOUND PRESSURE) COOL/HEAT (at 240V)
INDOOR
dB(A)
OUTDOOR
COMPRESSOR
TYPE
STARTING METHOD
HEAT EXCHANGER TYPE
INDOOR
Coil
Fin
OUTDOOR
Coil
Fin
DUCT TYPE
AR30
DUCT TYPE
AR30
CASING COLOR
INDOOR 270 x 1210 x 700
DIMENSIONS H ×W ×D
WEIGHT
PIPE
REFRIGERANT
REFRIGERANT OIL TYPE
OPERATION(OUTDOOR)
REMOTE CONTROLLER TYPE
DRAIN PIPE
Note: Specifications are based on the following conditions. Cooling: Indoor temperature of 27 °CDB / 19 °CWB,and outdoor temperature of 35 °CDB/24 °CWB.
Standard static pressure : 100 Pa. Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
OUTDOOR 900 x 900 x 350
INDOOR 330 x 1300 x 790
OUTDOOR 1045 x 1025 x 445
INDOOR 43 / 58 ( 95 / 128 )
OUTDOOR 84 / 96 ( 185 / 212 )
CONNECTION METHOD
SIZE mm
MAX LENGTH
MAX HEIGHT
MATERIAL SIZE
INDOOR Galvanized steel sheet
OUTDOOR Beige(10YR7.5/1.0NN)
NET
GROSS
NET / GROSS
LIQUID
GAS
TYPE
CHARGE kg 2.65
COOLING 0 to 52
HEATING -
mm
kg(lbs)
m 30(chargeless:7.5)
m 15
mm
Outer diameter 38.0mm / Inner diameter 36.0mm
FLARE
9.53 (3 / 8 inc.)
15.88 (5 / 8 inc.)
R22
Mineral oil
WIRED
Steel
- (03 - 03) -
3-4. DIMENSIONS
3-4-1. OUTDOOR UNIT
MODELS : AOG30A
350
DUCT TYPE
AR30
900
900
930
Side view
(Unit : mm)
DUCT TYPE
AR30
Front view
804
Bottom view
MOUNTING POSITION
300 mm (12") or over
AIR
600 mm (24") or over
300 mm (12") or over
300 mm (12") or over
333
19
600 mm (24") or over
- (03 - 04) -
3-4-2. INDOOR UNIT
MODELS : ARG30A
(Unit : mm)
DUCT TYPE
AR30
26
197
200
141
117
139
46996
264
220
264 264
1,177
1,063
1,135
42
75
83
DUCT TYPE
AR30
270
96
58
26
196
126
243
700
382
4066 184
68
205
MOUNTING POSITION
Strong and durable ceiling
Left side
300 mm or more
Indoor unit
Right side
150 mm or more
- (03 - 05) -
3-5. REFRIGERANT SYSTEM DIAGRAM
MODELS : ARG30A / AOG30A
OUTDOOR UNITINDOOR UNIT
Refrigerant pipe
THPI
DUCT TYPE
THR
AR30
Evaporator
THRMISTOR(ROOM TEMP.)THR
THRMISTOR(PIPE TEMP.)THPI
ø 9.53mm(3/8")
Compressor
Refrigerant pipe
ø 15.88mm(5/8")
Charging valve
THRMOSTAT(OUTDOOR TEMP.)THO
Capillary tube
THO
Condenser
Dryer
Check joint
DUCT TYPE
AR30
- (03 - 06) -
3-6. WIRING DIAGRAM
3-6-1. OUTDOOR UNIT
MODELS : AOG30A
CR COMPOSITE
AR30
INTERNAL OVERLOAD PROTECTOR
RED
C
C
BLACK
RS
WHITE
OUTDOOR
BLACK
THERMOSTAT
1
4
H
BLUE
RED
L
5
6
WHITE
DUCT TYPE
COMPRESSOR
BLACK
CONNECTOR
THERMAL PROTECTOR
FAN MOTOR
DUCT TYPE
AR30
MAIN RELAY
FUSE
5A
WHITE
COMPRESSOR CAPACITOR
GREEN/YELLOW
TERMINAL
WHITE
BLACK
BLACK
LN 1
BLACK
WHITE
(N)
32
FAN MOTOR CAPACITOR
BROWN
BROWN
- (03 - 07) -
3-6-2. INDOOR UNIT
MODELS : ARG30A
DUCT TYPE
AR30
DUCT TYPE
AR30
- (03 - 08) -
3-7. CAPACITY TABLE
( °CDB) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
0
10.05 6.84 2.13 10.24 6.87 2.19 10.44 6.89 2.21 10.74 7.18 2.24 10.87 7.12 2.25 11.10 7.00 2.28 11.21 6.93 2.29 11.31 7.22 2.30
5
9.69 6.65 2.39 9.91 6.68 2.44 10.15 6.71 2.47 10.51 7.05 2.51 10.66 7.01 2.53 10.92 6.91 2.56 11.04 6.85 2.58 11.15 7.15 2.60
10
9.27 6.42 2.64 9.51 6.44 2.70 9.74 6.49 2.73 10.13 6.86 2.78 10.29 6.84 2.80 10.56 6.76 2.85 10.69 6.71 2.87 10.81 7.01 2.89
15
8.84 6.20 2.89 9.05 6.23 2.96 9.28 6.27 2.99 9.65 6.65 3.05 9.81 6.63 3.08 10.08 6.56 3.13 10.21 6.52 3.15 10.33 6.84 3.18
20
8.81 5.99 3.17 9.00 6.02 3.22 9.22 6.05 3.26 9.57 6.41 3.32 9.72 6.39 3.35 10.01 6.34 3.41 10.14 6.30 3.44 10.26 6.62 3.46
25
9.16 6.17 2.75 9.39 6.20 2.78 9.60 6.24 2.80 9.96 6.59 2.84 10.11 6.56 2.86 10.38 6.49 2.90 10.51 6.45 2.92 10.63 6.76 2.93
30
8.58 5.89 3.01 8.82 5.93 3.04 9.02 6.00 3.06 9.36 6.34 3.11 9.51 6.32 3.13 9.79 6.27 3.17 9.92 6.24 3.19 10.05 6.56 3.21
35
7.98 5.64 3.28 8.13 5.69 3.30 8.34 5.72 3.33 8.65 6.06 3.38 8.80 6.05 3.40 9.08 6.01 3.45 9.22 5.99 3.47 9.35 6.32 3.49
40
7.26 5.36 3.56 7.37 5.38 3.58 7.54 5.40 3.60 7.85 5.76 3.65 8.00 5.75 3.68 8.27 5.72 3.73 8.41 5.71 3.76 8.54 6.05 3.80
45
6.75 5.11 3.73 6.86 5.17 3.74 7.02 5.20 3.76 7.33 5.56 3.81 7.48 5.55 3.84 7.75 5.54 3.90 7.90 5.54 3.92 8.05 5.88 3.95
50
6.35 4.63 3.75 6.52 4.68 3.84 6.68 5.06 3.87 6.98 5.43 3.92 7.13 5.42 3.95 7.40 5.42 4.01 7.55 5.42 4.04 7.69 5.77 4.07
52
6.17 4.56 3.80 6.35 4.61 3.89 6.51 4.99 3.92 6.81 5.36 3.97 6.96 5.36 4.00 7.23 5.36 4.07 7.38 5.36 4.09 7.53 5.71 4.12
Outdoor temperature
15 °CWB
18 °CDB
12 °CWB
29 °CWB
21 °CWB
16 °CWB
22 °CWB
Indoor temperature
32 °CWB
23 °CWB
27 °CWB
30 °CWB
18 °CWB
19 °CWB
26 °CWB
23 °CDB
21 °CDB
3-7-1. COOLING
COOLING CAPACITY
MODELS :
DUCT TYPE
AR30
AFR: Air flow rate (m3/min) TC : Total capacity (kW) SHC: Sensible Heat capacity (kW) PI : Power Input (kW)
ARG30A / AOG30A
DUCT TYPE
AR30
- (03 - 09) -
3-8. CAPACITY COMPENSATION FOR PIPE LENGTH
Pipe length (m)
Coefficient of compensation
COOLING
5 7.5 10 15 20 25 30
15 - - - 0.970 0.950 0.930 0.910
10 - - 0.990 0.970 0.950 0.930 0.910
7.5 - 1.000 0.990 0.970 0.950 0.930 0.910
5 1.010 1.000 0.990 0.970 0.950 0.930 0.910
0 1.010 1.000 0.990 0.970 0.950 0.930 0.910
-5 1.002 0.992 0.982 0.962 0.942 0.923 0.903
-7.5 - 0.988 0.978 0.958 0.939 0.919 0.899
-10 - - 0.974 0.954 0.935 0.915 0.895
-15 - - - 0.947 0.927 0.908 0.888
PIPE LENGTH (m)
COOLING
HEIGHT DIFFERENCE (m)
Outdoor unit
is
up-side
Outdoor unit is
bottom-side
AND HEIGHT DIFFERENCE
MODELS :
ARG30A / AOG30A
COEFFICIENT OF COMPENSATION FOR PIPE LENGTH
1.200
DUCT TYPE
AR30
1.150
1.100
1.050
1.000
0.950
0.900
0.850
0.800 0 5 10 15 20 25 30
DUCT TYPE
AR30
COEFFICIENT OF COMPENSATION FOR HEIGHT DIFFERENCE
- (03 - 10) -
3-9. ADDITIONAL CHARGE CALCULATION
REFRIGERANT AMOUNT g
REFRIGERANT TYPE
R22
2,650
PIPE LENGTH m
〜7.5 10
15 20 25 30 (MAX)
ADDITIONAL CHARGE g
0 (Charge less)
+50 +150 +250 +350 +450
20g/m
MODELS :
DUCT TYPE
AR30
REFRIGERANT CHARGE
ARG30A / AOG30A
DUCT TYPE
AR30
- (03 - 11) -
3-10. OPERATION RANGE
Indoor unit Outdoor unit Indoor temperature Indoor humidity Outdoor temperature
ARG30A AOG30A
Cooling
Dry
18 to 32
About 80% or less 0 to 52
Model
Mode
Operation Range
DUCT TYPE
AR30
DUCT TYPE
AR30
- (03 - 12) -
3-11. FAN PERFORMANCE CURVE
40 50 60 70 75 100 125 150 175
m3/h 2,060 2,000 1,940 1,870 1,840 1,650 1,430 1,170 830
l/s 572 556 539 519 511 458 397 325 231
CFM 1,212 1,177 1,142 1,101 1,083 971 842 689 488
m3/h 1,850 1,810 1,765 1,715 1,690 1,550 1,330 1,030 -
l/s 514 503 490 476 469 431 369 286 -
CFM 1,089 1,065 1,039 1,009 995 912 783 606 -
m3/h 1,650 1,610 1,560 1,510 1,490 1,350 1,170 - -
l/s 458 447 433 419 414 375 325 - -
CFM 971 948 918 889 877 794 689 - -
240V
STATIC PRESSRE (Pa)
FAN SPEED
Hi
Med
Low
MODELS :
DUCT TYPE
AR30
ARG30A / AOG30A
DUCT TYPE
AR30
Q-h Characteris tic curve
200
180
160
140
120
100
80
60
40
20
STATIC PRESSURE(Pa)
0
800 900 1000 1100 1 20 0 1300 1400 1500 160 0 17 00 180 0 19 00 2 000 2100
Hi Med Lo
AIR FLOW (m3/h)
Test condition : No filter and Fan mode
- (03 - 13) -
3-12. NOISE LEVEL CURVE
2000 HI 65.7 63.4 66.3 65.7 61.9 54.5 46.5
1810 MED 65.1 62.4 64.4 63.7 59.1 51.9 44.1
1611 LO 64.3 59.9 62.8 61.5 56.6 47.4 41.8
4000
250
500
1000
2000
Octave Band Center Frequency (Hz)
ARG30A
Model name
Condition
50
Air flow
(m3/h)
External Static
Pressre(Pa)
Blower
speed
63
125
INDOOR UNIT
SOUND POWER LEVEL (dB)
DUCT TYPE
AR30
Nots : Based on AMCA standard 300-96 in which the test setups are designed according to the ANS/AMCA standsrd 210 & ANSI/ASHRAE standard.
DUCT TYPE
AR30
- (03 - 14) -
SOUND LEVEL CHECK POINT
DUCT TYPE
AR30
DUCT TYPE
AR30
- (03 - 15) -
3-13. ELECTRIC CHARACTERISTICS
Voltage V
Frequency Hz
Current A
Input kW
Max Operating Current A
A
Main Fuse (Circuit breaker) Current
A
Power Cable
mm2
*2)Limited wiring length m
Input kW
Full Load Amp. A
Input kW
Full Load Amp. A
Indoor unit
Outdoor unit
Model Name Starting Current
ARG30A
AOG30A
Power Supply
220-240 〜50
Rated Value
Mode
*1) Wiring Spec
30 21
Cooling
3.30-3.40
80
15.8-16.3
20.5
Outdoor Fan Motor
0.14
4.0
Indoor Fan Motor
0.15
0.67
0.60
MODELS :
DUCT TYPE
AR30
ARG30A / AOG30A
DUCT TYPE
AR30
* Wiring Spec : (Selected based on Japan Electrotechnical Standard and Codes Committee E0005)
*2 Limited Wiring length : This is the wiring length in case voltage descent is less than 2%. When the wiring length becomes long, please select the wiring of a more larger diameter.
Selected Sample
- (03 - 16) -
3-14. SAFETY DEVICES
PROTECTION FORM AOG30AMBL
FUSE (SIDE OF POWER SUPPLY TERMINAL)
- 5A 250V
FAN MOTOR PROTECTOR THERMAL PROTECTOR
150
℃±5℃OFF
COMPRESSOR THERMAL PROTECTOR
OFF:25℃(65A) to 120℃(23.4A)
ON:80±10
PROTECTION FORM ARG30ALC
PCB FUSE - 3.15A 250V
FAN MOTOR PROTECTOR THERMAL PROTECTOR
150
℃±5℃OFF
INDOOR UNIT
DUCT TYPE
AR30
OUTDOOR UNIT
DUCT TYPE
AR30
- (03 - 17) -
3-15.
EXTERNAL INPUT & OUTPUT
EXTERNAL
ELECTRICAL HEA
TER OUTPUT SETTING
You can control Electrical heater (Booster) by sychronization with heating operation. When temperature is -10 to -3 degrees from Setpoint,External electrical heater is ON. When temperature is -1 degrees from Setpoint,External electrical heater Stops.
Jumper wire (Indoor Unit)
DUCT TYPE
AR30
This is used to continue indoor unit fan operation for 1 minute after thermo OFF in heating mode. 1 minute delay control set by cutting JM3 on PCB.
[Example]
Fuse
Indoor unit
+
1
2
-
CN15
(ORANGE)
Field supplied
Power
External Heater, other.
DUCT TYPE
AR30
Indoor
Operation
unit
Heating
Indoor
Stop
1min
Operation
unit fan
Stop
14V
CN15 (Output)
Please locate external a heater between the indoor unit and the ductwork. Please be sure to use delay control of a fan.
0V
Supply air
CAUTION!
!
External Heater
Indoor unit
Return air
- (03 - 18) -
3-16. FUNCTION SETTING
1 Zone control setting
2 Room temperature correct coefficient of heating
3 Room temperature correct coefficient of heating
1 Forbidden
2 Forbidden
3 Fan delay setting
Rotary SW SW 2 Indoor unit number setting
JM1 Forbidden
JM2 Forbidden
JM3 Forbidden
Jumper wire
INDOOR UNIT
SW 1
SW 4
DIP SW
3-16-1. INDOOR UNIT
DUCT TYPE
AR30
SWITCH POSITION
DUCT TYPE
AR30
Indoor unit control circuit board
JM1
JM3
JM2
- (03 - 19) -
3-16-2.SWITCH FUNCTION (INDOOR UNIT)
DIP SWITCH SETTING
1-1.Zone control setting
Zone control function can be selected by turning this switch ON/OFF.
Zonecontrol SETTING
DUCT TYPE
AR30
SW 1-1 SW state
DUCT TYPE
AR30
OFF Invalidity
ON Validity
1-2.Room temperature correct coefficient of heating.
Decide the heating temperature correct coefficient vale of heating.
HEAT TEMPERATURE CORRECTION
( Factory setting)
( Factory setting)
SW 1-2 SW state
OFF
ON
SW 1-3
OFF OFF
+2 deg
-2 deg
OFF ON 0 deg (Floor setting)
ON ON +4 deg (Ceiling setting)
4-1.Dip SW 4-1setting forbidden
( Factory setting)
OFFSW 4-1
4-2.Dip SW 4-2 setting forbidden
( Factory setting)
SW 4-2 OFF
4-3.Fan delay setting
This setting can be used when the auxiliary heater is mounted. When the fan operation is stopped when the indoor unit is operating with an auxiliary heater, the fan operation continues one minutes.
( Factory setting)
SW 4-3 SW state
OFF Invalidity
ValidityON
- (03 - 20) -
ROTARY SWITCH SETTING
This switch can be used when group control system. Set the indoor unit address in the 1,2,-,15 order.
( Factory setting)
SW 2 SW state
0 Single
1 - 15 Indoor unit address
DUCT TYPE
AR30
DUCT TYPE
AR30
JUMPER WIRE SETTING
1-1.JM 1, 2, 3 setting forbidden
( Factory setting)
JM stateJM 1
Connect
Disconnect
( Factory setting)
JM 2,3
Connect
Disconnect
Forbidden
JM state
Forbidden
EXTERNAL INPUT AND OUTPUT
Connector INPUT OUTPUT REMARKS
CN10 - ELECTRICAL HEATER
See external input/output
settings for details.
- (03 - 21) -
6 Memory backup switch
JM6 Forbidden
Jumper Wire
Wired remote controller
DIP SW
SW1
Group control setting (Unit address NO. setting)
SW2
3-16-3. WIRED REMOTE CONTROLLER
1 2 3 4 5 Forbidden 6 Indoor unit connection(Single/Multiple)
DUCT TYPE
AR30
1 Cooling / Heat pump 2 Auto restart validity / invalidity 3 Forbidden 4 Defrost display 5 Forbidden
JM1 Forbidden JM2 Forbidden JM3 Forbidden JM4 Auto change over validity / invalidity JM5 Forbidden
DUCT TYPE
AR30
SWITCH POSITION
Wired remote controller
N
N
O
O
2
2
345
1
Dip switch 1 Dip switch 2
4
5
3
6
1
6
- (03 - 22) -
3-16-4. SW FUNCTION (WIRED REMOTE CONTRLLER)
DIP SWITCH SETTING
(1) SW1 setting
1-1 Unit address No. setting
Set remoto controller the SW1-6 toON. Set the address number of additional indoor unit with remote controller SW1-(1-4).
DUCT TYPE
AR30
For the address number of additional connected units, see the table below.
( Factory setting)
SW1-1 SW1-2 SW1-3 SW1-4 SW1-5 SW1-6 Indoor unit address
OFF OFF OFF OFF OFF OFF Single OFF OFF OFF ON OFF ON 1 OFF OFF ON OFF OFF ON 2 OFF OFF ON ON OFF ON 3 OFF ON OFF OFF OFF ON 4 OFF ON OFF ON OFF ON 5 OFF ON ON OFF OFF ON 6 OFF ON ON ON OFF ON 7
ON OFF OFF OFF OFF ON 8 ON OFF OFF ON OFF ON 9 ON OFF ON OFF OFF ON 10 ON OFF ON ON OFF ON 11 ON ON OFF OFF OFF ON 12 ON ON OFF ON OFF ON 13 ON ON ON OFF OFF ON 14
OFF OFF OFF OFF OFF ON 15
DUCT TYPE
AR30
SELF DIAGNOSIS
If [EE : EE] flashes at the remote controller current time displey, per-form[Self Diagnosis]
For the [Self Diagnosis] method, refer to the test operetion section of the installation instruction sheet.
The faulty air conditioner is also displayed.
Example [ 22 : 03 ] : Unit 03 room temperature sensor open
Faulty unit
Error cord
DIP SW 1-5 setting forbidden.
( Factory setting)
DIP SW 1-5 OFF
Number of indoor unit conneection(Single/Multiple)
This is switchsd according to the number of connected indoor units.
NUMBER OF INDOOR UNIT CONNECTION
( Factory setting)
SW 1-6
OFF
ON
Number of indoor unit
One unit connection
Multiple unit connection
- (03 - 23) -
(2) SW2 setting
2-1 Cooling only heat pump
Switching cooling only / heat pump
COOLING ONLY / HEAT PUMP SWITCH
( Factory setting, in case of Heat pomp Model)
( Factory setting in case of cooling only Model)
DUCT TYPE
AR30
SW2-2
OFF
ON
Operation system
Heat pump/Heat recovery
Cooling only
2-2 Auto restart validity/invalidity
Selecting auto restart invalidity/validity
In the case of it is ON, to set the SW2-6 ON.
AUTO RESTART
( Factory setting)
SW2-2
OFF
ON
Auto restart
Invalidity
Validity
DUCT TYPE
AR30
2-3 DIP SW 2-3 setting forbidden
( Factory setting)
DIP SW2-5 OFF
2-4 Defrost display invalidity/validity
mark is displayed.
DEFROST
( Factory setting, in case of Heat pomp Model) ( Factory setting in case of cooling only Model)
SW2-4
OFF
ON
Defrost display
Invalidity
Validity
2-5 DIP SW 2-5 setting forbidden
( Factory setting)
DIP SW 2-5 OFF
2-6 Memory backup switch (wired remote controller only)
When installing, turn the SW2-6 ON.
MEMORY BACKUP SWITCH
( Factory setting)
DIP SW2-6
OFF
ON
Battery backup
Invalidity
Validity
- (03 - 24) -
JUMPER WIRE SETTING
1 JM1 setting forbiden
( Factory setting)
JM1
Connect
Disconnect
DUCT TYPE
2 JM2 setting forbiden
AR30
JM state
Forbidden
DUCT TYPE
AR30
( Factory setting)
JM2
Connect
Disconnect
JM state
Forbidden
3 JM3 setting forbiden
( Factory setting)
JM3
Connect
Disconnect
JM state
Forbidden
4 Auto change over setting
selecting auto change over validity / invalidity
( Factory setting)
JM4
Connect
Disconnect
5 JM5 setting forbiden
( Factory setting)
JM5
Connect
Disconnect
6 JM6 setting forbiden
( Factory setting)
JM6
Connect
Disconnect
Auto change over
validity
invalidity
JM state
Forbidden
JM state
Forbidden
- (03 - 25) -
3-17. OPTIONAL PARTS
SQUARE FLANGE (UTD - SF045T)
DUCT TYPE
AR30
ROUND FLANGE (UTD - RF204)
Round flange is used when the fresh air duct is installed.
DUCT TYPE
AR30
Air intake hole
Round flange
- (03 - 26) -