Nots : Based on AMCA standard 300-96 in which the test setups are designed according
to the ANS/AMCA standsrd 210 & ANSI/ASHRAE standard.
DUCT TYPE
AR30
- (03 - 14) -
SOUND LEVEL CHECK POINT
DUCT TYPE
AR30
DUCT TYPE
AR30
- (03 - 15) -
3-13. ELECTRIC CHARACTERISTICS
VoltageV
FrequencyHz
CurrentA
InputkW
Max Operating Current A
A
Main Fuse (Circuit
breaker) Current
A
Power Cable
mm2
*2)Limited wiring lengthm
InputkW
Full Load Amp.A
InputkW
Full Load Amp.A
Indoor unit
Outdoor unit
Model Name
Starting Current
ARG30A
AOG30A
Power Supply
220-240 〜50
Rated Value
Mode
*1) Wiring Spec
30
21
Cooling
3.30-3.40
80
15.8-16.3
20.5
Outdoor Fan Motor
0.14
4.0
Indoor Fan Motor
0.15
0.67
0.60
MODELS :
DUCT TYPE
AR30
ARG30A / AOG30A
DUCT TYPE
AR30
* Wiring Spec :
(Selected based on Japan Electrotechnical Standard and Codes Committee E0005)
*2 Limited Wiring length : This is the wiring length in case voltage descent is less than 2%.
When the wiring length becomes long, please select the wiring of a more larger diameter.
Selected Sample
- (03 - 16) -
3-14. SAFETY DEVICES
PROTECTION FORMAOG30AMBL
FUSE
(SIDE OF POWER SUPPLY
TERMINAL)
-5A 250V
FAN MOTOR PROTECTORTHERMAL PROTECTOR
150
℃±5℃OFF
COMPRESSOR THERMAL PROTECTOR
OFF:25℃(65A) to 120℃(23.4A)
ON:80±10
℃
PROTECTION FORMARG30ALC
PCB FUSE-3.15A 250V
FAN MOTOR PROTECTORTHERMAL PROTECTOR
150
℃±5℃OFF
INDOOR UNIT
DUCT TYPE
AR30
OUTDOOR UNIT
DUCT TYPE
AR30
- (03 - 17) -
3-15.
EXTERNAL INPUT & OUTPUT
EXTERNAL
ELECTRICAL HEA
TER OUTPUT SETTING
You can control Electrical heater (Booster) by sychronization with heating operation.
When temperature is -10 to -3 degrees from Setpoint,External electrical heater is ON.
When temperature is -1 degrees from Setpoint,External electrical heater Stops.
Jumper wire (Indoor Unit)
DUCT TYPE
AR30
This is used to continue indoor unit fan operation for 1 minute after thermo OFF in heating mode.
1 minute delay control set by cutting JM3 on PCB.
[Example]
Fuse
Indoor
unit
+
1
2
-
CN15
(ORANGE)
Field supplied
Power
External Heater, other.
DUCT TYPE
AR30
Indoor
Operation
unit
Heating
Indoor
Stop
1min
Operation
unit fan
Stop
14V
CN15
(Output)
Please locate external a heater between the indoor unit and the ductwork.
Please be sure to use delay control of a fan.
0V
Supply air
CAUTION!
!
External
Heater
Indoor unit
Return air
- (03 - 18) -
3-16. FUNCTION SETTING
1Zone control setting
2Room temperature correct coefficient of heating
3Room temperature correct coefficient of heating
1Forbidden
2Forbidden
3Fan delay setting
Rotary SWSW 2Indoor unit number setting
JM1 Forbidden
JM2 Forbidden
JM3 Forbidden
Jumper wire
INDOOR UNIT
SW 1
SW 4
DIP SW
3-16-1. INDOOR UNIT
DUCT TYPE
AR30
SWITCH POSITION
DUCT TYPE
AR30
Indoor unit control circuit board
JM1
JM3
JM2
- (03 - 19) -
3-16-2.SWITCH FUNCTION (INDOOR UNIT)
DIP SWITCH SETTING
1-1.Zone control setting
Zone control function can be selected by turning this switch ON/OFF.
Zonecontrol SETTING
DUCT TYPE
AR30
SW 1-1SW state
DUCT TYPE
AR30
OFFInvalidity
ONValidity
1-2.Room temperature correct coefficient of heating.
Decide the heating temperature correct coefficient vale of heating.
HEAT TEMPERATURE CORRECTION
( Factory setting)
( Factory setting)
SW 1-2SW state
OFF
ON
SW 1-3
OFF
OFF
+2 deg
-2 deg
OFFON0 deg (Floor setting)
ONON+4 deg (Ceiling setting)
4-1.Dip SW 4-1setting forbidden
( Factory setting)
OFFSW 4-1
4-2.Dip SW 4-2 setting forbidden
( Factory setting)
SW 4-2OFF
4-3.Fan delay setting
This setting can be used when the auxiliary heater is mounted.
When the fan operation is stopped when the indoor unit is operating with an auxiliary heater,
the fan operation continues one minutes.
( Factory setting)
SW 4-3SW state
OFFInvalidity
ValidityON
- (03 - 20) -
ROTARY SWITCH SETTING
This switch can be used when group control system.
Set the indoor unit address in the 1,2,-,15 order.
( Factory setting)
SW 2SW state
0Single
1 - 15Indoor unit address
DUCT TYPE
AR30
DUCT TYPE
AR30
JUMPER WIRE SETTING
1-1.JM 1, 2, 3 setting forbidden
( Factory setting)
JM stateJM 1
Connect
Disconnect
( Factory setting)
JM 2,3
Connect
Disconnect
Forbidden
JM state
Forbidden
EXTERNAL INPUT AND OUTPUT
ConnectorINPUTOUTPUTREMARKS
CN10-ELECTRICAL HEATER
See external input/output
settings for details.
- (03 - 21) -
6Memory backup switch
JM6Forbidden
Jumper Wire
Wired remote controller
DIP SW
SW1
Group control setting
(Unit address NO. setting)
SW2
3-16-3. WIRED REMOTE CONTROLLER
1
2
3
4
5Forbidden
6Indoor unit connection(Single/Multiple)