General ARG14R, ARG14RLB, AOG14RGB Installation Manual

SPLIT TYPE AIR CONDITIONER
Duct Type
INSTALLATION INSTRUCTION SHEET
(PART NO. 9365623015)
For authorized service personnel only.
WARNING!
CAUTION!
1 For the air conditioner to operate satisfactorily, install it as outlined in this installation instruction sheet.
2 Connect the indoor unit and outdoor unit with the room air conditioner piping and cords available from our standard
parts. This installation instruction sheet describes the correct connections using the installation set available from our standard parts.
3 Installation work must be performed in accordance with national wiring standards by authorized personnel only.
4 If refrigerant leaks while work is being carried out, ventilate the area. If the refrigerant comes in contact with a flame, it
produces a toxic gas.
5 Do not turn on the power until all installation work is complete.
Be careful not to scratch the air conditioner when handling it.
After installation, explain correct operation to the customer, using the operating manual.
Let the customer keep this installation instruction sheet because it is used when the air conditioner is serviced or moved.
The maximum length of the piping is shown in Table 1. If the units are further apart than this, correct operation cannot be
guaranteed.
STANDARD PARTS
The following installation parts are furnished. Use them as required.
INDOOR UNIT ACCESSORIES
Name and Shape Q’ty Application
Installation template
Hanger
Tapping screw (ø4×10)
Special nut A (large flange)
Special nut B (small flange)
Coupler heat insulation (large)
Coupler heat insulation (small)
Binder For remote controller and
Remote controller
Remote controller cord clamp
Tapping screw (flush heads)
Filter
Drain hose insulation
OUTDOOR UNIT ACCESSORIES
Hexagon wrench
Drain pipe
Drain cap
This mark indicates procedures which, if improperly performed, might lead to the death or serious injury of the user.
This mark indicates procedures which, if improperly performed, might possibly result in personal harm to the user, or damage to property.
WARNING
SELECTING THE MOUNTING POSITION
WARNING
Install at a place that can withstand the weight of the indoor and outdoor units and install positively so that the units will not topple or fall.
For positioning the indoor unit
1
4
8
4
4
1
1
small
1
large
4
1
10
10
3
1
1
(1)
(2)
For suspending the indoor unit from ceiling
For installing the hanger
For suspending the indoor unit from ceiling
For indoor side pipe joint (large pipe)
For indoor side pipe joint (small pipe)
remote controller cord binding
For fixing the coupler heat insulation
For installing the remote controller cord
For installing the remote controller cord clamp
Insulates the drain hose and vinyl hose connection
For air purge
For outdoor unit drain piping work (Heat & Cool model only)
For outdoor unit drain piping work (Heat & Cool model only)
1
Do not install where there is the danger of com­bustible gas leakage.
2
Do not install near heat sources.
3
If children under 10 years old may approach the unit, take preventive measures so that they cannot reach the unit.
4
Take precautions to prevent the unit from falling.
Decide the mounting position with the customer as follows:
INDOOR UNIT
(1)
Install the indoor unit level on a strong wall, floor, ceiling which is not subject to vibration.
(2)
The inlet and outlet ports should not be obstructed : the air should be able to blow all over the room.
(3)
Install the unit near an electric outlet or special branch circuit.
(4)
Do not install the unit where it will be exposed to direct sunlight.
(5)
Install the unit where connection to the outdoor unit is easy.
(6)
Install the unit where the drain pipe can be easily installed.
(7)
Take servicing, etc. into consideration and leave the spaces shown in Fig.1. Also install the unit where the filter can be removed.
(8)
Install the indoor unit where vibrations and noise are not amplified.
(9)
When installing the unit on the floor, make sure that there is plen­ty of space around the inlet port.
Fig. 1
Strong and durable ceiling
Left side
4” (10 cm)
or more
Left side
Strong and durable floor
4” (10 cm)
or more
OUTDOOR UNIT
Install the unit where it will not be tilted by more than 5°.
1
When installing the outdoor unit where it may
2
exposed to strong wind, fasten it securely.
(1)
If possible, do not install the unit where it will exposed to direct sun­light. (If necessary, install a blind that does not interfere with the air flow.)
(2)
Install the outdoor unit in a place where it will be free from being dir­ty or getting wet by rain as much as possible.
(3)
Install the unit when connection to the indoor unit is easy.
(4)
During heating operation, drain water flows from the outdoor unit. Therefore, install the outdoor unit in a place where the drain water flow will not be obstructed. (Reverse cycle model only)
(5)
Do not place animals and plants in the path of the warm air.
(6)
Take the air conditioner weight into account and select a place where noise and vibration are small.
(7)
Select a place so that the warm air and noise from the air condi­tioner do not disturb neighbors.
(8)
Provide the space shown in Fig. 2 so that the air flow is not blocked. Also for efficient operation, leave open three of the four direc­tions front, rear, and both sides.
CAUTION
Indoor unit
1’ (30 cm)
or more
WARNING
1’ (30 cm)
or more
Right side (PIPE side)
1” (3 cm)
or more
Right side
Inlet air
1” (3 cm)
or more
Fig. 2
4” (10 cm) or more
4” (10 cm) or more
2’ (60 cm) or more
2’ (60 cm) or more
2’ (60 cm)
or more
CONNECTION PIPE REQUIREMENT
Table 1
Diameter
Small Large
6.35 mm (1/4 in)
Use 0.7 mm to 1.2 mm thick pipe.
Use pipe with water-resistant heat insulation.
Use pipe that can withstand a pressure of 3,040 kPa.
12.7 mm (1/2 in)
Maximum
length
15 m
(49 ft)
Maximum height
(between indoor
and outdoor)
8 m
(26 ft)
ELECTRICAL REQUIREMENT
Electric wire size and fuse capacity:
Table 2
MAX
Power cord (mm2)
Connection cord (mm2)
Fuse capacity (A)
Always use H07RN-F or equivalent to the connection cord. Install the disconnect device with a contact gap of at least 3 mm
nearby the units. (Both indoor unit and outdoor unit)
MIN
MAX
MIN
2.0
1.5
2.0
1.5
15
INSTALLATION PROCEDURE
Install the air conditioner as follows:
1
INDOOR UNIT INSTALLATION
A. CEILING CONCEALED TYPE
1. INSTALL THE FILTERS
Install the filters to the unit (Fig. 3).
Fig. 3-(1)
Filter
Fig. 3-(2)
Unit
The inlet port can be installed at the bottom of this unit. For more details, refer to Fig. 11 and 12.
2. DRILLING HOLES FOR BOLTS AND INSTALLING THE BOLTS
Using the installation template, drill holes for bolts (4 holes). (Fig. 4)
Fig. 4
Installation template
Filter
Drilling position for bolts
3. INSTALLING THE HANGERS
Fasten the hanging bolts to the ceiling and install special nuts A
and B.
Fig. 5
M10 Hanging bolt
Special nut A
Special nut B
Install the hangers to the unit (4 places).
Fig. 6
Air
Tapping screw
Hang the unit.
(1) Pass the hanging bolts through the hangers (4 places).
Fig. 7
HangerHanger bolt
Hanger
Hanger
Unit
CAUTION
Fasten the unit securely with special nuts A and B.
4. LEVELING
Base horizontal direction leveling on top of the unit.
Fig. 8
Ceiling
Level
Drain side
10 mm
OK NO
Fig. 9
Air
OK
or less
Level
10 mm
or less
NO
5. SERVICE HOLE DIMENSIONS
Open a service hole with the dimensions shown below.
Fig. 10
Service hole
Unit
Control box
4” (10 cm)
or more
1’ (30 cm) or more
B. FLOOR STANDING CONCEALED TYPE
1. INSTALL THE FILTERS
Remove the 4 tapping screws, and then remove cover.
Install the cover with the 4 tapping screws as shown in the illus-
tration below.
Fig. 11
Tapping screw
Cover
Install the filters to the unit refer to Fig. 3-(2).
Fig. 12
Filter
2. INSTALLING THE HANGERS
Install the hangers to the unit (4 places).
Fig. 13
Hanger
3. DRILLING HOLES FOR BOLTS AND INSTALLING THE BOLTS
Drilling position for bolts.
Fig. 14
34-7/8’ (88.6 cm)
CAUTION
Mount using M10 anchor bolts or similar fasteners. If it is difficult to attach the unit to the floor, use a stand or some other frame.
Fig. 15
M10
30~50 mm
4. INSTALL THE UNIT
Fix the unit. Install the unit and fasten with special nut B.
Fig. 16
Special
Unit
nut B
6-3/4’
(17 cm)
5. LEVELING
Base horizontal and vertical direction leveling on top of the unit.
Fig. 17
Fig. 18
Level
10 mm
Drain side
or less
OK NO
CAUTION
In order to prevent water from leaking around the out­let port, make sure to insulate it (on both the CEILING CONCEALED type and the FLOOR STANDING CON­CEALED type).
2
OUTDOOR UNIT INSTALLATION
(1)
When the outdoor unit will be exposed to strong wind, fasten it with bolts at the places indicated by the arrows (Fig. 19).
(2)
Since the drain water flows out of the outdoor unit during heating operation, install the drain pipe and connect it to an commercial 16 mm hose (Reverse cycle model only).
(3)
When installing the drain pipe, plug all the holes ( two places) other than the drain pipe mounting hole in the bottom of the outdoor unit with putty so there is no water leakage (Fig. 19). (Reverse cycle model only)
Fig. 19
21-1/4” (540 mm)
Bottom
Drain pipe mounting hole
11-7/32” (285 mm)
Plug the holes
holes at
Bottom plate
Drain pipe
3
CONNECTING THE PIPING
1. FLARE PROCESSING
(1)
Cut the connection pipe with pipe cutters so that the pipe is not deformed.
(2)
Holding the pipe downward so that cuttings cannot enter the pipe and remove the burrs.
(3)
Remove the flare nut from the indoor unit pipe and outdoor unit and assemble as shown in (Table 3) and insert the flare nut onto the pipe, and flare with a flaring tool.
(4)
Check if the flared part “L” (Fig. 20) is spread uniformly and that there are no cracks.
Table 3
Pipe
Small pipe
Large pipe
Fig. 20
Small (width across flats 17 mm)
Large (width across flats 24 mm)
2. BENDING PIPES
The pipes are shaped by your hands. Be careful not to collapse them.
Fig. 21
Do not bend the pipes in an angle more than 90°. When pipes are repeatedly bent or stretched, the material will harden, making it difficult to bend or stretch them any more. Do not bend or stretch the pipes more than three times.
When bending the pipe, do not bend it as is. The pipe will be collapsed. In this case, cut the heat insulating pipe with a sharp cutter as shown in Fig. 22, and bend it after exposing the pipe. After bending the pipe as you want, be sure to put the heat insulat­ing pipe back on the pipe, and secure it with tape.
CAUTION
To prevent breaking of the pipe, avoid sharp bends.
1
Bend the pipe with a radius of curvature of 150 mm or over.
If the pipe is bent repeatedly at the same place, it will
2
break.
Flare nut
1.4 to 1.7 mm (6.35 mm dia) Large pipe
1.9 to 2.2 mm (12.7 mm dia)
Fig. 22
3. CONNECTION PIPES
Indoor unit side
(1)
Detach the caps and plugs from the pipes.
CAUTION
Be sure to apply the pipe against the port on the
1
indoor unit correctly. If the centering is improper, the flare nut cannot be tightened smoothly. If the flare nut is forced to turn, the threads will be damaged.
Do not remove the flare nut from the indoor unit pipe
2
until immediately before connecting the connection pipe.
Centering the pipe against port on the indoor unit, turn the flare
nut with your hand. When the flare nut is tightened properly by your hand, hold the body side coupling with a separate spanner, than tighten with a torque wrench (Fig. 23).
Fig. 23
Fig. 24
CAUTION
Hold the torque wrench at its grip, keeping it in the right angle with the pipe as shown in Fig. 24, in order to tighten the flare nut correctly.
Table 4 Flare nut tightening torque
Pipe
Small pipe
Large pipe
Tightening torque
150 to 200 kgf (14.7 to 19.6 N
500 to 550 kgf (49.0 to 53.9 N
cm
cm
m)
m)
CAUTION
Be sure to connect the large pipe after connecting the small pipe completely.
Lay the piping.
A. CEILING CONCEALED TYPE
Fig. 25
Control box cover
Pipe
OK NO
B. FLOOR STANDING CONCEALED TYPE
Fig. 26
OK OK NO
CAUTION
Connect the piping so that the control box cover can
1
easily be removed for servicing when necessary.
In order to prevent water from leaking into the con-
2
trol box, make sure that the piping is well insulated.
(2) Outdoor unit side
Tighten the flare nut of the connection pipe at the outdoor unit valve connector. The tightening method is the same as that as at the indoor side.
Fig. 27
Connection pipe
(Large pipe)
(Small pipe)
Flare nut
3-way valve
Pipe coupling
2-way valve
4. CHECKING THE PIPE CONNECTIONS FOR GAS LEAKING
For both indoor and outdoor unit side, check the joints for gas leaking by the use of a gas leakage detector without fail when the pipes are connected.
- Continued on back -
5. HEAT INSULATION ON THE PIPE JOINTS (INDOOR SIDE ONLY)
After checking for gas leaks, insulate by wrapping insulation
around the two parts (large and small) or the indoor unit cou­pling, using the coupler heat insulation. After installing the coupler heat insulation, wrap both ends
with vinyl tape so that there is no gap. After affixing the coupler heat insulation, secure it with two
binders (large), one on each end of the insulation. Make sure that the binders overlap the heat insulating pipe.
Fig. 28
Coupler heat insulation
Indoor unit
Binder (Large)
Fig. 29
Cover this portion with heat insulating material also without fail.
Heat insulating pipe
4
VACUUM PROCESS
1. VACUUM
Remove the cap, and connect the gauge manifold and the
(1)
vacuum pump to the charging valve by the service hoses. Vacuum the indoor unit and the connecting pipes until the pres-
(2)
sure in them lowers to below 1.5 mmHg. Disconnect the service hoses and fit the cap to the charging
(3)
valve (Tightening torque : 70 to 90 kgf cm). Remove the blank caps, and fully open the spindles of the
(4)
2-way and 3-way valves with a hexagon wrench (Torque : 2-way valve: 70 to 90 kgf cm, 3-way valve: 100 to 120 kgf cm). Tighten the blank caps of the 2-way valve and 3-way valve to
(5)
the specified torque (200 to 250 kgf cm).
This model is not supplied with refrigerant for air purging.
Fig. 30
Refrigerant pipe
Blank cap
Outdoor unit
Service hose with valve core
Cap
Charging valve
3-way valve
Service hose
2. ADDITIONAL CHARGE
Refrigerant suitable for a piping length of 7.5 m is charged in the outdoor unit at the factory. When the piping is longer than 7.5 m, additional charging is nec­essary. For the additional amount, see the table below.
Table 5
Pipe length
12R Additional refrigerant
14R
Between 7.5 m and 15 m, when using a connection pipe other than that in the table, charge additional refrigerant with 0.7 oz (20 g)/3.3 ft (1 m) (14R model) as the criteria.
25 ft
(7.5 m)
None
CAUTION
1
When moving and installing the air conditioner, do not mix gas other than the specified refrigerant (R22) inside the refrigerant cycle.
2
When adding refrigerant, add the refrigerant from the charging valve at the completion of work.
3
If the units are further apart than the maximum pipe length, correct operation can not be guaranteed.
Hexagon wrench
Gaurge manifold
33 ft
(10 m)
None
1.7 oz (50 g)
Vacuum pump
(15 m)
5.3 oz
(150 g)
5
INSTALLING DRAIN HOSE
INSTALL THE DRAIN HOSE
Install the drain hose with downward gradient (1/50 to 2/50) and so
••
there are no rises or traps in the hose. Use general hard polyvinyl chloride pipe and connect it with
adhesive (polyvinyl chloride) so that there is no leakage. When the hose is long, install supporters.
Do not perform air bleeding.
Always heat insulate the indoor side of the drain hose.
49 ft
A. CEILING CONCEALED TYPE
Fig. 31
Outlet air flow
OK NO
Arrange the drain hose lower than this portion
B. FLOOR CONSOLE TYPE
Fig. 32
OK NO NO
Drain hose
Rise
5 to 6.5 ft (1.5 to 2 m)
Air bleeding
CAUTION
Connect the drain hose so that the control box cover
1
can easily be removed for servicing when necessary.
In order to prevent water from leaking into the con-
2
trol box, make sure that the piping is well insulated.
After finishing the piping, the drain hose installation
3
and the wiring, seal the holes in the wall.
The out side diameter of drain port is 26 mm, use a suitable drain hose.
Fig. 33
Drain hose insulation
Unit
Unit
Drain hose
0 mm
6
ELECTRICAL WIRING
HOW TO CONNECT WIRING TO THE TERMINALS
A. For solid core wiring (or F-cable)
(1)
Cut the wire end with a wire cutter or wire-cutting pliers, then strip the insulation to about 15/16 (25 mm) to expose the solid wire.
(2)
Using a screwdriver, remove the terminal screw(s) on the terminal board.
(3)
Using pliers, bend the solid wire to form a loop suitable for the terminal screw.
(4)
Shape the loop wire properly, place it on the terminal board and tighten securely with the terminal screw using a screwdriver.
B. For strand wiring
Cut the wire end with a wire cutter or wire-cutting pliers,
(1)
then strip the insulation to about 3/8 (10 mm) to expose the strand wiring. Using a screwdriver, remove the terminal screw(s) on the
(2)
terminal board. Using a round terminal fastener or pliers, securely clamp
(3)
a round terminal to each stripped wire end. Position the round terminal wire, and replace and tighten
(4)
the terminal screw with a screwdriver.
Fig. 34
Supporter
Drain hose insulation
Drain hose
Trap
Rise
HOW TO FIXED CONNECTION CORD AND POWER CORD AT THE CORD CLAMP
After passing the connection cord and power cord through the insulation tube, fasten it with the cord clamp.
Fig. 35
Use VW-1, 0.5 to 1.0 mm thick, PVC tube as the insulation tube.
1. INDOOR UNIT SIDE
(1)
Remove the control box cover from the control box.
Fig. 36
Control box
Screw
Control box cover
Remove the 4 screws and remove the con­trol box cover from the control box.
(2) Connection cord connection.
Clamp the connection cord with the cable clamp.
Connect the connection cord to the terminals.
Fig. 37
Cord clamp
(3) Remote controller cord connection.
Clamp and the remote controller cord with the nylon clamp.
Connect the remote controller cord to the PCB with the black
connecter. Remove the Nylon clamp and pass the remote controller cord,
and then fix the Nylon clamp to the control box.
Fig. 38
PCB
<
BLACK
REMOCON
25~35 mm
Fig. 39
CAUTION
1
Tighten the indoor unit connection cord (to the out­door unit) and power supply indoor and outdoor unit terminal board connections firmly with the terminal board screws. Faulty connection may cause a fire.
2
If the indoor unit connection cord (to the outdoor unit) and power supply are wired incorrectly, the air conditioner may be damaged.
3
Wire the indoor unit connection cord (to the outdoor unit) by matching the numbers of the outdoor and indoor units terminal board numbers as shown in ter­minal label.
4
Ground both the indoor and outdoor units by attach­ing a ground wire.
5
Unit shall be grounded in compliance with the appli­cable local and national codes.
Nylon clamp
Remote controller cord
>
(4) Control box cover installation
Fasten control box cover with the 4 screws.
Fig. 40
Connection cord
2. OUTDOOR UNIT SIDE
(1)
Remove the terminal cover of the outdoor unit, and insert the end of the connection cord and the power cable into the terminal board.
(2)
Fasten the connection cord with the cord clamps, and install the terminal cover.
Fig. 41
Terminal board
Terminal
Power line
3
2
(N)
1
Indoor unit side terminal
cover
Power cord
Power supply
Control line
Green/Yellow
Green/ Yellow
Cord clamps
Connection cord
EARTH
L
N
3
2
(N)
1
EARTH
Outdoor unit side terminal
Power cord
7
REMOTE CONTROLLER
INSTALLATION
Insert the end of a flat blade screwdriver at the arrow parts of
the groove at the side of the remote controller case and remove the remote controller case top by turning the screwdriver. Disconnect the remote controller cord from the remote
controller terminal board.
Fig. 42
(1)
When remote controller exposed
1)
Make a notch in the thin part ( part of Fig. 42) at the rem­ote controller case top and bottom with nippers, file, etc.
2)
Connect the remote controller cord to the remote con­troller terminal board specified in (Fig. 43).
3)
Clamp the remote controller cord sheath with the binder (small) as shown in Fig. 43.
4)
Cut off the excess binder.
5)
Clamp the remote controller cord to a wall, etc. with the remote controller cord clamp furnished (Fig. 44).
Fig. 43
Fig. 44
Tapping screw (flush heads)
(2)
When remote controller cord embedded
1)
Embed the remote controller cord and box.
2)
Pass the remote controller cord through the hole at the rem­ote controller case bottom and install the cord to the box (Fig. 45).
3)
Connect the remote controller cord to the remote con­troller terminal board specified in (Fig. 43).
Remote controller cord
Binder (small)
Remote controller cord
Red
White
Black
Remote controller terminal board
Remote controller cord clamp
Remote controller cord
Connection cord
Fig. 45 [Example]
Remote controller case top
Remote controller case bottom
After wiring work is complete, return the remote controller
case top to its original state.
CAUTION
Do not bundle the remote controller cord, or wire the
1
remote controller cord in parallel, with the indoor unit connection wire (to the outdoor unit) and the power supply cord. It may cause erroneous operation.
When installing the remote controller and cord near
2
a source of electromagnetic waves, separate the rem­ote controller from the source of the electromagnetic waves and use shielded cord.
Do not touch the remote controller PC board and PC
3
board parts directly with your hands.
8
TEST RUNNING
1. REMOTE CONTROLLER
For test running, when the remote controller FAN CONTROL
button and MASTER CONTROL button are pressed simultane­ously for more than three seconds when the air conditioner is not running, the air conditioner starts and TEST is displayed on the remote controller display. However, the SET TEMP. setting button does not function, but all other buttons, displays, and protection functions operate (Fig. 46).
Fig. 46
When blinks at the current time display, there is an error
inside the air conditioner. If the ZONE CONTROL button and ENERGY SAVE button are pressed simultaneously for more than three seconds, the self diagnosis check will start and the error contents will be displayed at the current time display (Fig.
47). When the operation lamp lights, press the START/STOP but­ton and after operation lamp goes off, perform the same opera­tion (Fig. 47). Process the error contents by referring to (Table 6).
Fig. 47
Stop operation
Table 6
Error cord
Communication error (indoor unit remote controller)
Communication error (indoor unit outdoor unit)
Room temperature sensor open
Room temperature sensor shortcircuited
Indoor heat exchanger temperature sensor open
Indoor heat exchanger temperature sensor short­circuited
Outdoor heat exchanger temperature sensor open
Outdoor heat exchanger temperature sensor shortcircuited
Outdoor temperature sensor open
Outdoor temperature sensor shortcircuited
Discharge pipe temperature sensor open
Discharge pipe temperature sensor shortcir­cuited
High pressure abnormal
Discharge pipe temperature abnormal
To stop test running, press the START/STOP button.
For the operation method, refer to the operating manual and
perform operation check. Check that there are no abnormal sounds or vibration sounds
during the test running.
2. OUTDOOR UNIT
When the outdoor temperature drops, the outdoor unit's fans may switch to low speed, or one of the fans may stop intermittently.
ERROR
The LED lamps operate as follows (Table 7) according to the error contents. The LED lamps are on the outdoor unit board.
Error contents
Remote controller cord
Table 7
Error display Error contents
ON
OFF
0.5 sec
ON
OFF
LED
No. 1
Lamp
LED No. 2 Lamp
When the fault is cleared, the LED lamp goes off. However, for discharge pipe temperature abnormal and high pres­sure abnormal, the LED lamp lights continuously for 24 hours, as long as the power is not turned off.
ON
OFF
ON
OFF
ON
OFF
5 sec
0.5 sec 0.5 sec
5 sec
0.5 sec 0.5 sec
5 sec
Lighting continued
Single quick flashes repeated
Two quick flashes repeated
Three quick flashes repeated
Lighting continue
Discharge pipe temperature abnormal
Outdoor heat exchanger tem­perature sensor abnormal
Outdoor tem­perature sensor abnormal
Discharge pipe temperature sensor abnormal
High pressure abnormal
9
STATIC PRESSURE
CHARACTERISTIC
Fig. 48
14,000 BTU class
EXTERNAL
STATIC
PRESSURE
12,000 BTU class
EXTERNAL
STATIC
PRESSURE
10
1
2
3
4
5
6
7
1
2
FAN PERFORMANCE AND AIR FLOW
EXTERNAL STATIC PRESSURE
Recommended range
83 111 139 167
(Pa)
50
40
30
20
10
0
300
Recommended range
83 111 139 167
(Pa)
50
40
30
20
10
0
300
400 500 600
AIR FLOW
HIGH
400 500 600
AIR FLOW
HIGH
POWER
WARNING
The rated voltage of this product is 220-240 V A.C. 50Hz.
Before turning on the verify that the voltage is within the 198 V to 264 V range.
Always use a special branch circuit and install a special receptacle to supply power to the room air conditioner.
Use a circuit breaker and receptacle matched to the capacity of the room air conditioner.
The circuit breaker is installed in the permanent wiring. Always use a circuit that can trip all the poles of the wiring and has an isolation distance of at least 3 mm between the contacts of each pole.
Perform wiring work in accordance with standards so that the room air conditioner can be operated safely and positively.
Install a leakage circuit breaker in accordance with the related laws and regulations and electric compa­ny standards.
CAUTION
The power source capacity must be the sum of the room air conditioner current and the current of other electrical appliances. When the current contracted capacity is insufficient, change the contracted capacity.
When the voltage is low and the air conditioner is dif­ficult to start, contact the power company the voltage raised.
(l/sec)
194
700
(m3/h)
(l/sec)
194
700
(m3/h)
PART NO. 9365623015    
Loading...