MODELS :
AR 7FUAB / AO 7FSAJ
AR 9FUAB / AO 9FSAJ
AR 12FUAD / AO 12FSAJ
AR 14FUAD / AO 14FSDJ
AR 18FUAD / AO 18FNDK , AO 18FNDN
DUCT TYPE
AR7 - AR18K
AR 7UUAB / AO 7USAJL
AR 9UUAB / AO 9USAJL
AR 12UUAD / AO 12USAJL
AR 14UUAD / AO 14USDJL
AR 18UUAD / AO 18UNDKL , AO 18UNDNL
FEATURES
Universal design indoor unit
Since vertical and horizontal installation is possible, and the intake direction can also be selected
from two directions, flexible installation is possible.
DUCT TYPE
AR7 - AR18K
Ceiling concealedFloor concealed
Thin and compact indoor unit
- (02 - 01) -
2-2. REMOTE CONTROLLER
2-2-1. WIRED REMOTE CONTROLLER
FEATURES
Various timer setup (ON / OFF / WEEKLY) are possible.
Equipped with weekly timer as standard function.
(2 times Start / Stop per day for a week)
SUMOTUWETH FR SA
7
3126 9
15 18 21
DUCT TYPE
AR7 - AR18K
When setting up a timer, operation mode and a temperature
setup can be changed.
When a failure occurs,the error code is displayed. (Maximum of 16)
DUCT TYPE
AR7 - AR18K
Error indication.(A maximum of 16 error histories are memorizable.)
Up to 16 indoor units can be simultaneously controlled.
Anti freeze and energy saving operation are possible.
Easy installation with a slim shape with no boldge in the back.
The room temperature can be controlled by being detected the temperature
accurately with built-in thermo sensor.
High performance and compact size
Three functions are combined in
one unit.
Wired
remote
controller
Weekly
timer
Setback
timer
Built-in timers
Setback timerWeekly timer
Possible to set ON/OFF time to operate twice each day
of the week.
SUMOTUWETH FR SA
7
3126 9
15 18 21
Setup screen example
(Set to Wednesday: 8:00 to 20:00.)
0 3 6 9 12 15 18 21 Time
Easy-to-understand time bar display
24°C
SUMOTUWETH FR SA
7
3126 9
15 1821
Screen
after setup
Possible to set temperature for two time spans and
for each day of the week.
SUMOTUWETH FR SA
3126 9
Setup screen example
(Set from Sunday to Saturday: 12:00 to 15:00, 28 °C.)
0 3 6 9 12 15 18 21 Time
At "Weekly timer" + "Set back timer" setup
24°C
24°C 28°C 24°C
0 3 6 9 12 15 18 21 Time
28°C
Easy-to-understand operationSimple installation
Components are compatible with standard
switch boxes. Flat back construction allows
equipment to be installed wherever it is
Timer
area
Operation
area
needed.
15 18 21
28°C
[
Variable timer control
]
The operation/display sections are zoned according to time and operation, enabling variable programming to match application.
- (02 - 02) -
European
switch box
JIS box
FUNCTIONS
1
START/STOP button
Pressed to start and stop operation.
Display
SUMOTUWETH FR
SA
369
12 15 18 21
DUCT TYPE
AR7 - AR18K
10
2
7
8
9
CLOCK ADJUST
SET BACK
DELETESET
DAY
DAY OFF
ENERGY
SAVE
THERMO
SENSOR
13
1
3
4
6
2
Set temperature button
Selects the setting temperature.
3
Master control button
Selects the operating mode(AUTO, HEAT, FAN, COOL, DRY).
4
Fan control button
Selects the fan speed (AUTO, LOW, MED, HIGH).
5
Energy save button
DUCT TYPE
AR7 - AR18K
Turns the energy efficient mode on and off.
11
12
5
6
Thermo sensor
7
Timer mode (CLOCK ADJUST) button
Selects the timer mode (OFF TIMER, ON TIMER, WEEKLY TIMER)
Set the current time.
8
Day (DAY OFF) button
Display panel
Temporarily cancels of one day timer.
9
Set back button
pressed select the set back timer.
14
15
1617 18
10
Set time button
Pessed to select the set back timer.
SUMOTUWETH FR
SA
11
Delete button
The schedule of a weekly timer is deleted.
369
12 15 18 21
1920
12
Set button
Sets the date, hour, minute and on-off time.
13
Operation lamp
Lights during operation and when the timer is on.
DIMENSION
[ Unit : mm ]
17
120
SUMOTUWETH FR
369
12 15 18 21
DAY
CLOCK ADJUST
DAY OFF
SET BACK
DELETESET
Front View
120
SA
ENERGY
THERMO
SAVE
SENSOR
SPECIFICATION
SIZE (H x W x D mm)120 x 120 x 17
WEIGHT( g )160
CABLE LENGTH ( m )
POWER( V )
10
12
14
Timer and clock display
15
Operation mode display
16
Fan speed display
17
Central control display
18
Temperature display
19
Stand by display
Indicates during the oil recovery and defrosting operation.
20
Energy save display
- (02 - 03) -
2-3. SPECIFICATIONS
TYPE
MODEL NAME
POWER SOURCE
EUROPEAN ENERGY LABEL
CAPACITY
INPUT POWER
DUCT TYPE
AR7 - AR18K
CURRENTA
STARTING CURRENT
EER
COP
MOISTURE REMOVAL
AIR
CIRCULATION
RECOMMENDED STATIC PRESSURE
FAN TYPE x Q'ty
FAN MOTOR OUTPUTW
NOISE LEVEL
(SOUND
PRESSURE)
COOL/HEAT
COMPRESSOR
COOLING
HEATING
COOLINGRATED0.760.991.241.392.03
HEATINGRATED-----
COOLINGRATED3.74.65.56.39.0
HEATINGRATED-----
INDOOR
OUTDOOR
INDOOR
OUTDOOR
TYPE
OUTPUT
STARTING METHOD
Coil
INDOOR
HEAT
EXCHANGER
TYPE
OUTDOOR
SAFETY DEVICES
CASING COLOR
INDOOR217 x 663 x 595217 x 663 x 595217 x 953 x 595217 x 953 x 595217 x 953 x 595
DIMENSIONS
H ×W ×D
WEIGHT
PIPE
REFRIGERANT
REFRIGERANT OIL
OPERATION(OUTDOOR)
REMOTE CONTROLLER
OUTDOOR530 × 750 × 250530 x 750 x 250530 x 750 x 250530 x 750 x 250650 x 830 x 320
INDOOR324 × 785 × 686324 x 785 x 686324 x 785 x 686324 x 785 x 686324 x 785 x 686
OUTDOOR609 × 882 × 339609 x 882 x 339609 x 882 x 339609 x 882 x 339743 x 984 x 413
INDOOR18/2218/2225/2925/2925/29
OUTDOOR27/2927/2934/3635/3752/56
CONNECTION METHOD
SIZE
MAX LENGTH
MAX HEIGHT
fin
Rows x Stages x
Fin Pitch
Coil Dimensionsmm
Coil
fin
Rows x Stages x
Fin Pitch
Coil Dimensionsmm
INDOOR
OUTDOOR
INDOOR
OUTDOOR
NET
GROSS
NET /
GROSS
LIQUID
GAS
TYPE
CHARGEkg0.550.600.800.900.90
TYPE
COOLING
HEATING
MATERIAL
DRAIN PIPE
SIZE
INDOOR
OUTDOOR
RATED
RATED
COOLING2.832.832.823.022.66
HEATING-----
High3404205006401000
Med320390450560900
Low300360400480760
INDOORSirocco x 1Sirocco x 1Sirocco x 2Sirocco x 2Sirocco x 2
OUTDOORPropeller x 1Propeller x 1Propeller x 1Propeller x 1Propeller x 1
Note:Specifications are based on the following conditions.
Cooling:Indoor temperature of 27°CDB / 19°CWB,and outdoor temperature of 35°CDB/24°CWB.
Heating:Indoor temperature of 20°CDB / 15°CWB,and outdoor temperature of 7°CDB/6°CWB.
Standard static pressure : 0 Pa.
Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
Coil Dimensionsmm294 x 410 x 26.6294 x 410 x 26.6294 x 700 x 26.6294 x 700 x 26.6294 x 700 x 26.6
mm
mm
Coil Dimensionsmm504 x 770 x 18.19504 x 658 x 36.38504 x 658 x 36.38504 x 658 x 36.38630 x 901 x 36.38
INDOOR
OUTDOOR
INDOOR
OUTDOOR
INDOOR217 x 663 x 595217 x 663 x 595217 x 953 x 595217 x 953 x 595217 x 953 x 595
OUTDOOR530 x 750 x 250530 x 750 x 250530 x 750 x 250530 x 750 x 250650 x 830 x 320
INDOOR324 x 785 x 686324 x 785 x 686324 x 1075 x 686324 x 1075 x 686324 x 1075 x 686
OUTDOOR609 x 882 x 339609 x 882 x 339609 x 882 x 339609 x 882 x 339743 x 984 x 413
INDOOR18/2218/2225/2925/2925/29
OUTDOOR28/3030/3234/3635/3752/56
LIQUID
GAS
CHARGEkg0.650.750.851.001.40
COOLING
HEATING
m1515151520
m88888
mm
Note:Specifications are based on the following conditions.
Cooling:Indoor temperature of 27°CDB / 19°CW B,and outdoor temperature of 35°CDB/24°CWB.
Heating:Indoor temperature of 20°CDB / 15°CWB,and outdoor temperature of 7°CDB/6°CW B.
Standard static pressure : 0 Pa.
Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
- (02 - 05) -
2-4. DIMENSIONS
2-4-1. OUTDOOR UNIT
MODELS :
AO 7F , AO 9F , AO 12F , AO 14F
AO 7U , AO 9U , AO 12U , AO 14U
250
250
250
250
750
750
750
750
DUCT TYPE
AR7 - AR18K
100
100
100
100
60
60
60
60
13
13
13
95
95
95
95
285
285
285
285
13
540
540
540
540
(Unit : mm)
530
530
530
530
DUCT TYPE
AR7 - AR18K
Side viewFront view
MOUNTING POSITION
When there are obstacles at
the back or front sides.
AIR
600 mm
or more
100 mm
or more
When there are obstacles at
the back, side(s), and top.
600 mm
(
Ser
v
or
i
c
mor
e
s
pac
e)
AIR
e
100 mm
or
mor
e
600 mm or more
300 mm
or more
When there are obstacles at the
back, side with the installation of
more than one unit.
AIR
600 mm
or more
600 mm
or more
300 mm
or more
- (02 - 06) -
MODELS : AO 18F , AO 18U
AR7 - AR18K
830
650
12
Front view
Bottom
Air flow
343
350
320
Side view
154
101
58
90
DUCT TYPE
AR7 - AR18K
DUCT TYPE
Top view
MOUNTING POSITION
When there are obstacles at the
back or front sides.
AIR
600 mm
or more
100 mm
or more
603
Bottom view
When there are obstacles at the
back, side(s), and top.
600 mm or more
100 mm
or more
AIR
250 mm
(
Ser
300 mm
or more
v
o
i
c
r
m
e
s
o
pace)
r
e
When there are obstacles at the
back, side with the installation of
more than one unit.
AIR
250 mm
or more
250 mm
or more
300 mm
or more
- (02 - 07) -
2-4-2. INDOOR UNIT
MODELS :
AR 7F , AR 9F , AR 12F , AR 14F , AR 18F
AR 7U , AR 9U , AR 12U , AR 14U , AR 18U
FAN MOTOR PROTECTORTHERMAL PROTECTOR 150°C±5°C OFF 150°C±5°C OFF 150°C±5°C OFF 150°C±5°C OFF 150°C±5°C OFF
- (02 - 52) -
2-15. EXTERNAL INPUT & OUTPUT
FRESH
AIR OUTPUT SETTING
You can control sub fan by synchronizaton with fan operation of indoor unit.
[Example]
+
DUCT TYPE
AR7 - AR18K
Indoor
unit
1
2
Fuse
DUCT TYPE
AR7 - AR18K
-
CN11
(RED)
Indoor
unit fan
CN11
(Output)
Field supplied
Operation
Stop
14V
0V
Power
Fan, other
- (02 - 53) -
EXTERNAL
ELECTRICAL HEA
TER OUTPUT SETTING
You can control Electrical heater (Booster) by sychronization with heating operation.
When temperature is -10 to -3 degrees from Setpoint,External electrical heater is ON.
When temperature is -1 degrees from Setpoint,External electrical heater Stops.
Jumper wire (Indoor Unit)
This is used to continue indoor unit fan operation for 1 minute after thermo OFF in heating mode.
1 minute delay control set by turning switch 4-3 on PCB.
DUCT TYPE
AR7 - AR18K
[Example]
DUCT TYPE
AR7 - AR18K
+
Indoor
unit
1
2
-
CN10
(GREEN)
Indoor
Operation
unit
Heating
Indoor
Stop
Operation
unit fan
Stop
14V
CN10
(Output)
0V
<Operation condition>
All conditions shall be met.
Under heating operation.
Fan mode : Either Hi, Med, Low, Quiet.
Field supplied
Fuse
Power
External Heater, other.
1min
Cold air prevention function not working (Heat exchanger temperature over 27 C ).
Temperature subtracted set temperature from room temperature is between -10 C to -3 C.
-10 C < *T < -3 C *T=Room temperature
Compressor 3 minutes stop mode is released.
Defrosting mode is released.
<Release condition>
Do not meet above condition , or room temperature is 1 C below from set temperature.
CAUTION!
!
Please locate external a heater between the indoor unit and the ductwork.
Please be sure to use delay control of a fan.
External
Heater
Supply air
Indoor unit
Return air
- (02 - 54) -
2-16. FUNCTION SETTING
Auto restart validity/invalidity
Room temperature correct coefficient of heating
Room temperature correct coefficient of heating
Forbidden
High(Low) static pressure function setting
Fan delay setting
Indoor unit number setting
Forbidden
Forbidden
Forbidden
INDOOR UNIT
DIP SW
Rotary SW
SW 2
3
1
JM3
SW 1
SW 4
Jumper Wire
23JM1
JM2
1
2
2-16-1. INDOOR UNIT
DUCT TYPE
AR7 - AR18K
SWITCH POSITION
DUCT TYPE
AR7 - AR18K
Indoor unit control circuit board
ON
OFF
3
2
1
ON OFF
3
2
1
JM1
JM2
JM3
- (02 - 55) -
2-16-2. SWITCH FUNCTION (INDOOR UNIT)
the fan operation continues one minutes.
SW 4-3
SW state
OFF
Invalidity
Validity
ON
OFFON0 deg (Floor setting)
ONON+4 deg (Ceiling setting)
SW state
+2 deg
-2 deg
SW 1-3
OFF
OFF
ON
Low static pressure
SW 1-1
SW state
OFF
Invalidity
ON
Validity
SW 1-2
SW 4-1
SW 4-2
SW state
OFF
Normal
SW 4-2
OFFONSW state
Normal
High static pressure
OFF
ON
ON
DIP SWITCH SETTING
1-1.Auto restart setting
Auto restart function can be selected by turning this switch ON/OFF.
AUTO RESTART SETTING
DUCT TYPE
AR7 - AR18K
(Factory setting)
DUCT TYPE
AR7 - AR18K
◆
1-2.Room temperature correct coefficient of heating.
Decide the heating temperature correct coefficient vale of heating.
HEAT TEMPERATURE CORRECTION
(Factory setting)
◆
4-1.Dip SW 4-1setting forbidden
(Factory setting)
◆
4-2.High(Low) static pressure function setting
In case of installing in high(low) static, you can maximize(minimize) air flow and noise.
Model:AR*7 to 14
(Factory setting)
◆
Model:AR*18
(Factory setting)
◆
4-3.Fan delay setting
This setting can be used when the auxiliary heater is mounted.
When the fan operation is stopped when the indoor unit is operating with an auxiliary heater,
(Factory setting)
◆
- (02 - 56) -
G
CN11-FRESH AIR
See external input/output
settings for details.
CN10
-
ELECTRICAL HEATER
Connector
INPUT
OUTPUT
REMARKS
JM state
JM 1, 2, 3
Connect
Disconnect
Forbidden
0
Single
1 - 15
Indoor unit address
SW 2
SW state
N
I
T
T
SE
H
C
T
WI
S
Y
R
A
OT
R
This switch can be used when group control system.
Set the indoor unit address in the 1,2,-,15 order.
Set the remote controller DIP switch No.1 and 2 according to the following table.
(Factory setting)
DUCT TYPE
AR7 - AR18K
Number of
remote
controller
1 (Normal)
2 (Dual)
1-2 Group control setting
Number of indoor unit connection (One/Multiple)
This is switched according to the number of connected indoor units.
DIP-SW
No.3
OFF
Master unitSlave unit
DIP-SW
No.1
DIP-SW
No.2
ON
OFF
(Factory setting)
Number of indoor unit
One unit connection
OFF
OFF
DIP-SW
No.1
ONON
DIP-SW
No.2
DUCT TYPE
AR7 - AR18K
ONMultiple unit connection
1-3 Model setting
The system type of the outdoor unit can be selected by setting up DIP switch No.4 as follows.
(Factory setting)
DIP-SW
No.4
OFF
ONCooling only model
Heat Pump model
Model
1-4 Auto changeover setting
Selecting auto changeover validity / invalidity.
(Factory setting)
DIP-SW
No.5
OFF
ONValidity
Auto changeover
Invalidity
1-5 Memory backup setting
Set to ON to use batteries for the memory backup.if batteries are not used,
all of the settings stored in memory will be deleted if there is a power failure.
Remote controller which gives priority to ease-of-use and allows operation
of the necessary functions only.
DUCT TYPE
AR7 - AR18K
Remote sensor unit
UTD - RS100
Accurate and Comfortable
New amenity space can be offered by installing the thermo sensor in the remote controller.
Because the remote controller has the switching function, the user can select the position of the
sensor. (Room temperature sensor selection)
Example of room temperature
sensor selection
Sensor part
Simple remote
controllers
Remote Sensor
in the bed room (effective at night)
DUCT TYPE
AR7 - AR18K
Wired Remote Controller
THERMO
Day
The detecting point can be freely changed.
SENSOR
Night
Remote Controller
in the living room (effective during the day)
Remote Sensor (Optional Parts)
- (02 - 60) -
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.