SPLIT TYPE ROOM AIR CONDITIONER
INSTALLATION MANUAL
(PART No. 9314989018-02)
This air conditioner uses new refrigerant HFC (R410A).
The basic installation work procedures are the same as conventional refrigerant (R22) models.
However, pay careful attention to the following points:
(1) Since the working pressure is 1.6 times higher than that of conventional refrigerant (R22) models,
some of the piping and installation and service tools are special.(See the table below.)
Especially, when replacing a conventional refrigerant (R22) model with a new refrigerant R410A
model, always replace the conventional piping and flare nuts with the R410A piping and flare nuts.
(2) Models that use refrigerant R410A have a different charging port thread diameter to prevent
erroneous charging with conventional refrigerant (R22) and for safety. Therefore, check
beforehand.[The charging port thread diameter for R410A is 1/2 threads per inch.]
(3) Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with refrigerant
(R22) models. Also, when storing the piping ,securely seal the opening by pinching ,taping, etc.
(4) When charging the refrigerant, take into account the slight change in the composition of the
gas and liquid phases, and always charge from the liquid phase side whose composition is
stable.
Special tools for R410A
Tool name
Pressure is high and cannot be measured with a conventional gauge. To prevent erroneous
Gauge manifold
Charge hose
Vacuum pump
Gas leakage detector
Copper pipes
It is necessary to use seamless copper pipes and it is desirable
that the amount of residual oil is less than 40 mg/10m. Do not
use copper pipes having a collapsed, deformed or discolored
portion (especially on the interior surface). Otherwise, the expansion value or capillary tube may become blocked with
contaminants.
As an air conditioner using R410A incurs pressure higher than
when using R22, it is necessary to choose adequate materials.
Thicknesses of copper pipes used with R410A are as shown in Table1.Never us copper pipes thinner than 0.8mm even
when it is available on the market.
mixing of other refrigerants, the diameter of each port has been changed.
It is recommended the gauge with seals-0.1 to 5.3 MPa (-1 to 53 bar) for high pressure.
-0.1 to 3.8 MPa (-1 to 38 bar) for low pressure.
To increase pressure resistance, the hose material and base size were changed.
A conventional vacuum pump can be used by installing a vacuum pump adapter.
Special gas leakage detector for HFC refrigerant R410A.
Contents of change
Table 1 Thicknesses of Annealed Copper Pipes
Nominal
diameter
1/4
3/8
Outer diameter
(B09LD/B12LD)
Thickness (mm)
(mm)
6.35
9.52
R410A
0.80
0.80
[ref.] R22
0.80
0.80
For authorized service personnel only.
WARNING
(1) For the room air conditioner to operate satisfactory, install it as outlined in this installation manual.
(2) Connect the indoor unit and outdoor unit with the air conditioner piping and cords available standards parts. This
installation manual describes the correct connections using the standard accessories and the parts specified in
this installation manual.
(3) Have installation work done by authorized service personnel only.
(4) Never cut the power cord, lengthen or shorten the cord, or change the plug.
(5) Also do not use an extension cord.
(6) Plug in the power cord plug firmly. If the receptacle is loose, repair it before using the room air conditioner.
(7) Do not turn on the power until all installation work is complete.
● Be careful not to scratch the air conditioner when handling it.
● After installation, explain correct operation to the customer, using the operating manual.
● Let the customer keep this installation manual because it is used when the air conditioner is serviced or moved.
● The maximum length of the piping is 20 m. The maximum height difference of the piping is 15 m,
if the units are further apart than these, correct operation can not be guaranteed.
STANDARD ACCESSORIES
The following installation accessories are supplied.
Use them as required.
Name and Shape Q’ty Name and Shape Q’ty
Wall hook bracket
Cloth tape
1
Remote
control
unit
Tapping screw (big)
1
Battery
Tapping screw (small)
2
1
8
2
One set of following parts are necessary in istallation of this product.
Name
Connection pipe assembly
Connection cord
Wall pipe
Decorative tape
Vinyl tape
Wall cap
Saddle
Drain hose
Tapping screws
Sealant
ELECTRICAL REQUIREMENT
Always make the air conditioner power supply a special branch circuit
and provide a special switch and receptacle. Do not extend the power
cord.
WARNING
(1) Do not use the existing (for R22) piping and flare nuts.
• If the existing materials are used, the pressure inside the refrigerant cycle will rise and cause breakage, injury,
etc.(Use the special R410A materials.)
(2) When installing and relocating the air conditioner, do not mix gases other than the specified refrigerant(R410A)
to enter the refrigerant cycle.
• If air or other gas enters the refrigerant cycle, the pressure inside the cycle will rise to an abnormally high value
and cause breakage, injury, etc.
CAUTION
When installing pipes shorter than 3m, sound of the outdoor unit will be transferred to the indoor unit, which will
cause large operating sound or some abnormal sound.
SELECTING THE MOUNTING
POSITION
Decide the mounting position with the customer as follows:
1. INDOOR UNIT
(1) Install the indoor unit level on a strong wall which is not subject to
vibration.
(2) The inlet and outlet ports should not be obstructed : the air should
be able to blow all over the room.
(3) Install the unit near an electric outlet or special branch circuit.
(4) Do not install the unit where it will be exposed to direct sunlight.
(5) Install the unit where connection to the outdoor unit is easy.
(6) Install the unit where the drain pipe can be easily installed.
(7) Take servicing, etc. into consideration and leave the spaces shown
in (Fig. 2). Also install the unit where the filter can be removed.
2. OUTDOOR UNIT
(1) If possible, do not install the unit where it will be exposed to direct
sunlight. (If necessary, install a blind that does not interfere with
the air flow.)
(2) Do not install the unit where a strong wind blows or where it is very
dusty.
(3) Do not install the unit where people pass.
(4) Take your neighbors into consideration so that they are not dis-
turbed by air blowing into their windows or by noise.
(5) Provide the space shown in Fig. 2 so that the air flow is not blocked.
Also for efficient operation, leave open three of the four directions
front, rear, and both sides.
WARNING
Install at a place that can withstand the weight of the
indoor and outdoor units and install positively so that
the units will not topple or fall.
INSTALLATION DIAGRAM OF
INDOOR AND OUTDOOR UNITS
Fig. 2
[INDOOR UNIT]
5 cm or over
6 cm or over
150 cm or over
230 cm or over
Dust collection unit
Air-cheaning and
Deodorizing filter
Air filter
Remote
control unit
Connection Cord
Conform to Type245 IEC57
[OUTDOOR UNIT]
60 cm or over
Wall hook bracket
9 cm or over
(Wall cap)
Remote
control unit
holder
Tapping
screw
(small)
10 cm or over
CAUTION
(1) Do not install where there is the danger of com-
bustible gas leakage.
10 cm or over
(2) Do not install near heat sources.
(3) If children under 10 years old may approach the
20 cm or over
25 cm or
over
unit, take preventive measures so that they cannot reach the unit.
(4) Install the indoor unit on the wall where the height
from the floors more than 230 cm.
• Do not directly install it on
the ground, otherwise it
will cause failure.
5 cm or over
[Indoor unit piping direction]
The piping can be connected in the five directions indicated by 1,
2, 3, 4, and 5 in (Fig. 1). When the piping is connected in
direction 2 or 5, cut along the piping groove in the side of the
front cover with a hacksaw.
When connecting the piping in direction 3, cut a notch in the thin
wall at the front bottom of the front cover.
Fig. 1
(Rear)
5 Left
outlet
2 Right
outlet
3 Bottom outlet
1 Rear outlet
4 Left rear
outlet
Fig. 3
54 cm
Drain hose
NOTE:
In places where the outdoor temperature drops to 0˚C or
lower, the drain water may freeze and may stop up the
drain or cause other outdoor unit trouble. Therefore take
measures so that the drain water will not freeze and clog
the drain.
Outdoor unit bottom
32 cm
Remote control
unit holder
Drain pipe
Air-cleaning and
Deodorizing filter
1
1
1
FRONT PANEL REMOVAL AND INSTALLATION
AIR CLEANING UNIT REMOVAL
(1) Open the intake grille, and then remove the right air filter.
(2) Pull the air cleaning unit grip in the direction of the arrow and remove
the unit.
AIR CLEANING UNIT INSTALLATION
(1) Open the intake grille, and then insert the dust collection unit into the
indoor unit.
(2) Install the right air filter, and then close the intake grille.
THE INTAKE GRILLE REMOVAL
(1) Open the intake grille.
(2) Pull down the knob.
(3) Lift the intake grille upward, until the axle at the top of the intake
grille is removed.
THE INTAKE GRILLE INSTALLATION
(1) The fixing axle of the intake grille is installed on the Panel.
(2) Lay down the intake grille.
THE FRONT PANEL REMOVAL
(1) Remove intake grille (Reference the intake grille removal.)
(2) Remove four screws.
(3) The thumb is hung on the lower part as shown in the figure,
and it pulls to the front, pushing [ ] mark , and bottom hooks
(two position) is removed from wall hook bracket.
(4) The front panel bottom is pulled to the front, and bottom hooks
is removed indoor unit.
(5) The front panel is pulled to the front, raising the upper surface,
and a front panel is removed.
THE FRONT PANEL INSTALLATION
(1) Firstly, fit the lower part of the front panel, and insert top and
bottom hooks. (Three top sides, six bottom sides)
(2) Four screws is attached.
(3) The intake grille is attached.
CAUTION
Install the front panel and
INTAKE GRILLE securely. If installation is imperfect, the
front panel or INTAKE GRILLE
may fall off and cause injury.
Be sure that the top hole of the
front panel is hooked securely to
the hook of the base.
CUSTOMER GUIDANCE
Explain the following to the
customer in accordance with the operating manual:
(1) Starting and stopping method,
operation switching, temperature adjustment, timer, air flow
switching, and other remote
control unit operations.
(2) Air filter removal and cleaning,
and how to use the air louvers.
(3) Give the operating and installat-
ion manuals to the customer.
PUMP DOWN OPERATION (FORCED COOLING OPERATION)
To avoid discharging refrigerant into the atmosphere at the time of relocation or disposal, recover
refrigerant by doing the cooling operation or forced cooling operation according to the following
procedure. (When the cooling operation cannot start in winter, and so on, start the forced cooling
operation.).
(1) Do the air purging of the charge hose by connecting the charging hose of gauge manifold to the charging
port of 3 way valve and opening the low-pressure valve slightly.
(2) Close the valve stem of 2 way valve completely.
(3) Start the cooling operation or following forced cooling operation.
When using the remote control unit
Press the TEST RUN button after starting the cooling operation by the remote control unit.
The operation indicator lamp and timer indicator lamp will begin to flash simultaneously during test run.
When using the MANUAL AUTO button of the indoor unit (The remote control unit is lost, and so on.)
Keep on pressing the MANUAL AUTO button of the indoor unit for more than 10 seconds.
(The forced cooling operation cannot start if the MANUAL AUTO button is not kept on pressing for more
than 10 seconds.)
(4) Close the valve stem of 3 way valve when the reading on the compound pressure gage becomes 0.05~0 Mpa
(0.5~0 kg/cm2).
(5) Stop the operation.
• Press the START/STOP button of the remote control unit to stop the operation.
• Press the MANUAL AUTO button when stopping the operation from indoor unit side.
(It is not necessary to press on keeping for more than 10 seconds.)
During the pump-down operation, make sure that the compressor is turned off before you remove the refrigerant
piping.
Do not remove the connection pipe while the compressor is in operation with 2 way or 3 way valve open. This
may cause abnormal pressure in the refrigeration cycle that leads to breakage and even injury.
Fig. 4
Screws
(4 position)
Top hole
(center)
Indoor unit
INSERT
Intake grille
Mounting shaft
Bearing
Front panel
[ ] mark
Push
Top holes
(two sides)
Bottom hole
(six position)
CAUTION
PULL
Push
Grip
Front panel
Bottom hooks
(six position)
Intake grille
Knob
Front panel
Wall hook bracket
Top hook (two sides)
Top hook
(center)
Front panel
POWER
WARNING
(1) The rated voltage of this product is 230 V AC 50 Hz.
(2) Before turning on the power, check if the voltage is within the
220 V -10 % to 240 V +10 % range.
(3) Always use a special branch circuit and install a special
receptacle to supply power to the room air conditioner.
(4) Use a circuit breaker and receptacle matched to the capacity of
the air conditioner.
(1) The power source capacity must be the sum of the air conditioner current and the current of other electrical appliances. When the
current contracted capacity is insufficient, change the contracted capacity.
(2) When the voltage is low and the air conditioner is difficult to start, contact the power company the voltage raised.
(5) Do not extend the power cord.
(6) Perform wiring work in accordance with standards so that the
air conditioner can be operated safely and positively.
(7) Install a leakage circuit breaker in accordance with the related
laws and regulations and electric company standards.
CAUTION
Installation instruction on the back.
INDOOR UNIT
CUTTING THE HOLE IN THE WALL FOR THE CONNECTING PIPING
(1) Cut a 65 mm diameter hole in the wall at the position shown in (Fig. 5).
(2) When cutting the wall hole at the inside of the wall hook bracket, cut
the hole within the range of the left and right center marks 40 mm
below the wall hook bracket.
When cutting the wall hole at the outside of the wall hook bracket, cut
the hole at least 10 mm below over.
(3) Cut the hole so that the outside end is lower (5 to 10 mm) than the
inside end.
(4) Always align the center of the wall hole. If misaligned, water leakage
will occur.
(5) Cut the wall pipe to match the wall thickness, stick it into the wall cap,
fasten the cap with vinyl tape, and stick the pipe through the hole.
(The connection pipe is supplied in the installation set.) (Fig. 5)
(6) For left piping and right piping, cut the hole a little lower so that drain
water will flow freely. (Fig. 5)
INSTALLING THE WALL HOOK BRACKET
(1) Install the wall hook bracket so that it is correctly positioned horizon-
tally and vertically. If the wall hook bracket is tiled, water will drip to
the floor.
(2) Install the wall hook bracket so that it is strong enough to withstand
the weight of an adult.
● Fasten the wall hook bracket to the wall with 6 or more screws through
the holes near the outer edge of the bracket.
● Check that there is no rattle at the wall hook bracket.
WARNING
If the wall pipe is not used, the cord interconnecting
the indoor and outdoor units may touch metal and
cause electric leakage.
FORMING THE DRAIN HOSE AND PIPE
[Rear piping, Right piping, Bottom piping]
● Install the indoor unit piping in the direction of the wall hole and bind
the drain hose and pipe together with vinyl tape. (Fig. 7)
● Install the piping so that the drain hose is at the bottom.
● Wrap the pipes of the indoor unit that are visible from the outside
with decorative tape.
[For Left rear piping, Left piping]
Interchange the drain cap and the drain hose.
CAUTION
(1) In order to align the drain hose and drain cap, be
sure to insert securely and vertically. Incline
insertion will cause water leakage.
(2) When inserting, be sure not to attach any material
besides water. If any other material is attached, it
will cause deterioration and water leakage.
(3) After removing drain hose, be sure not to forget
mounting drain cap.
(4) Be sure to fix the drain hose with tape to the bottom
of piping.
(5) Prevent drain water frozen under low temperature
environment.
When installing indoor unit's drain hose outdoors, necessary
measure for frost protection should be taken to prevent drain
water frozen.
• Under low temperature environment (when outdoor
temperature under 0 °C), after cooling operation is executed,
water in the drain hose could be frozen.
Once drain water is frozen, the drain hose will be blocked
and water leakage may be resulted for indoor unit.
Fig. 5
Fasten with
vinyl tape
(Wall cap)
Fig. 6
Install the wall hook bracket horizontally and
perpendicularly.
Fig. 7
Right piping
Bottom piping
Removal method of drain
hose
● Remove the screw at the left of
drain hose and pull out drain
hose.
Screw Drain hose
Drain fixture
(blue)
● Be sure to install around the drain hose connector.
● As the screw is inside, be sure to use screwdriver treated with
magnet.
Wall hook bracket
Lower
65 mm dia. hole
(Wall pipe)
(Inside)
Wall hook bracket
Indoor unit drain hose (bottom)
Indoor unit
drain hose
Wall (Outside)
CAUTION
Bind with vinyl tape
Pipe (top)
Rear piping
Drain cap
Center mark
Lower
5 to 10
mm low
Tapping screw
Wall hook bracket
For left outlet piping, cut off the
piping outlet cutting groove
with a hacksaw.
Remove the drain cap by pulling
at the projection at the end of
the cap with pliers, etc.
10 mm
or over
65 mm dia. hole
Center notch
Hook
String
Installation method of
drain hose
● Vertically insert the drain hose
toward the inside, so that the
drain fixture (blue) can
accurately align with the screw
hole around the drain cock.
After inserting and before
replacing, please reinstall and
fix the removed screws.
Drain fixture (blue)
Screw hole
Screw
Drain hose
Drain cock
●
For left piping and left rear piping, align the marks on the wall hook
bracket and shape the connection pipe.
● Bend the connection piping at the bend radius of 70 mm or more and
install no more than 35 mm from the wall.
● After passing the indoor piping and drain hose through the wall hole,
hang the indoor unit on the hooks at the top and bottom of the wall
hook bracket.
[Installing the indoor unit]
● Hang the indoor unit from the hooks at the top of the wall hook bracket.
● Insert the spacer, etc. between the indoor unit and the wall hook
bracket and separate the bottom of the indoor unit from the wall.
Indoor unit
(Spacer)
Wall hook bracket
CONNECTING THE PIPING
CONNECTION
(1) Install the outdoor unit wall cap (supplied with the optional installation set
or procured at the site) to the wall pipe.
(2) Connect the outdoor unit and indoor unit piping.
(3) After matching the center of the flare surface and tightening the nut hand
tight, tighten the nut to the specified tightening torque with a torque wrench.
(Table 2)
FLARING
(1) Cut the connection pipe to the necessary
length with a pipe cutter.
(2) Hold the pipe downward so that cuttings
will not enter the pipe and remove the
burrs.
(3) Insert the flare nut onto the pipe and flare
the pipe with a flaring tool.
Insert the flare nut (always use the flare nut
attached to the indoor and outdoor units
respectively) onto the pipe and perform the
flare processing with a flare tool.
Use the special R410A flare tool, or the conventional (for R22) flare tool.
When using the conventional flare tool, always
use an allowance adjustment gauge and secure
the A dimension shown in table 3 .
Check if [L] is flared uniformly
and is not cracked or scratched.
Die
A
Pipe
INDOOR UNIT WIRING
(1) Remove the cord clamp.
(2) Bend the end of the connection cord as shown in the figure.
Fig. 10
Cord clamp
(There is a
terminal block
inside.)
Screw
(1) Match the terminal block numbers and connection
cord colors with those of the outdoor unit.
Erroneous wiring may cause burning of the electric parts.
(2) Connect the connection cords firmly to the terminal
block. Imperfect installation may cause a fire.
Connection cord
Connection cord
CAUTION
Fig. 8
Connection pipe
(6.35 mm dia.)
Bend (R70) with
a pipe bender
Connection pipe
(9.52 mm dia.)
After hooking the indoor unit to the top hook, hook the fittings of the
indoor unit to the two bottom hooks while lowering the unit and
pushing it against the wall.
Fig. 9
Tighten with two wrenches.
Torque
wrench
Indoor unit pipe
Align the marks.
Top hooks
Indoor unit (Fitting) Bottom hooks
Wrench (fixed)
Flare nut
Connection pipe
To prevent gas leakage, coat the flare
surface with refrigerator oil.
Wall hook
bracket
Table 2 Flare nut tightening torque
Flare nut
6.35 mm dia.
9.52 mm dia.
Tightening torque
15.7 to 17.6 N
(160 to 180 kgf
29.4 to 41.1 N
(300 to 420 kgf
• m
• cm)
• m
• cm)
Tightening torque standard
(using a 20 cm wrench)
Wrist strength
Arm strength
Table 3 Pipe outside diameter
Pipe outside
diameter
ø 6.35 mm (1/4”)
ø 9.52 mm (3/8”)
Flash tool for
R410A, clutch type
0 to 0.5
0 to 0.5
A (mm)
Conventional (R22) flare tool
Clutch type
1.0 to 1.5
1.0 to 1.5
Wing nut type
1.5 to 2.0
1.5 to 2.0
CAUTION
(1) Fasten a flare nut with a torque wrench as instructed in this manual. If
fastened too tight, the flare nut may be broken after a long period of time
and cause a leakage of refrigerant.
(2) During installation, make sure that the refrigerant pipe is attached firmly
before you run the compressor. Do not operate the compressor under the
condition of refrigerant piping not attached properly with 2-way or 3-way
valve open. This may cause abnormal pressure in the refrigeration cycle
that leads to breakage and even injury.
(3) Connect the end of the connection cord fully into the terminal block.
(4) Fasten the connection cord with a cord clamp.
Cord clamp
5 mm
12 mm
50 mm
5 mm
12 mm
40 mm
(3) Always fasten the outside covering of the connec-
tion cord with the cord clamp. (If the insulator is
chafed, electric leakage may occur.)
(4) Securely earth the power cord plug.
(5) Do not use the earth screw for an external connector.
Only use for interconnection between two units.
Tab
Square hole
Screw
Insert the tab into the square hole of the
indoor unit and fasten with a screw.
OUTDOOR UNIT
OUTDOOR UNIT INSTALLATION
● Set the unit on a strong stand, such as one made of concrete blocks
to minimize shock and vibration.
● Do not set the unit directly on the ground because it will cause trou-
ble.
Connector cover removal
● Remove the tapping screws.
Installing the connector cover
(1) After inserting the two front hooks, then insert the rear hook.
(2) Tighten the tapping screws.
WARNING
(1) Install the unit where it will not be tilted by more
than 5°.
(2) When installing the outdoor unit where it may ex-
posed to strong wind, fasten it securely.
AIR PURGE
Always use a vacuum pump to purge the air.
Refrigerant for purging the air is not charged in the
outdoor unit at the factory.
Close the high pressure side valve of the gauge manifold fully and do
not operate it during the following work.
1. Check if the piping connections are secure.
2. Check that the stems of 2-way valve and 3-way valve are closed
fully.
3. Connect the gauge manifold charge hose to the charging port
of the 3-way valve (side with the projection for pushing in the
valve core).
4. Open the low pressure side valve of the gauge manifold fully.
5. Operate the vacuum pump and start pump down.
6. Slowly loosen the flare nut of the 3-way valve and check if air
enters, then retighten the flare nut.
(When the flare nut is loosened the operating sound of the
vacuum pump changes and the reading of the compound
pressure gauge goes from minus to zero.)
7. Pump down the system for at least 15 minutes, then check if the
compound pressure gauge reads -0.1 MPa (-76 cmHg, -1 bar).
8. At the end of pump down, close the low pressure side gauge of
the gauge manifold fully and stop the vacuum pump.
9. Slowly loosen the valve stem of the 3-way valve. When the
compound pressure gauge reading reaches 0.1-0.2 MPa,
retighten the valve stem and disconnect the charge hose
from the 3-way valve charging port.
(If the stem of the 3-way valve is opened fully before the
charge hose is disconnected, it may be difficult to disconnect
the charge hose.)
Additional charge
Refrigerant suitable for a piping length of 15 m is charged in the outdoor
unit at the factory.
When the piping is longer than 15 m, additional charging is necessary.
For the additional amount, see the table below.
Table 5
Pipe length
Additional refrigerant
15 m
None
20 m
100 g
Fig. 11
Tapping screw
Rear hooks
Front hooks
Connector cover
CAUTION
(1) Refrigerant must not be discharged into
atmosphere.
(2) After connecting the piping , check the joints for
gas leakage with gas leak detector.
10. Fully open the valve stems of the 2-way valve and 3-way valve
using a hexagon wrench. (After the valve stem begins to turn,
turn it with a torque of less than 2.9 N
stops turning.)
11. Firmly tighten the 2-way valve and 3-way valve blank cap and
the charging port cap.
Fig. 12
Table 4
Blank cap 19.6 to 24.5 N
Charging port cap 12.3 to 15.7 N
• m (30 kgf • cm) until it
Tightening torque
• m (200 to 250 kgf • cm)
• m (125 to 160 kgf • cm)
CAUTION
(1)
When adding refrigerant, add the refrigerant from
the charging port at the completion of work.
(2) The maximum length of the piping is 20 m. If
the units are further apart than this, correct
operation can not be guaranteed.
Between 15 m and 20 m, when using a connection pipe other than
that in the table, charge additional refrigerant with 20g/1 m as the
criteria.
OUTDOOR UNIT WIRING
(1) Remove the outdoor unit connector cover.
(2) Bend the end of the cord as shown in the figure.
(3) Connect the end of the connection cord fully into the terminal block.
5mm
12mm
5mm
12mm
(4) Fasten the sheath with a cord clamp.
(5) Install the connector cover.
Fig. 13
Control box
Control box cover
Cord clamp
Connection cord
Connection cord wiring
Run the connection cord to the rear of the outdoor unit within the A
range of the arrows shown in the figure.
Earth screw
Cord clamp
Earth screw
Sheath
Connection cord
45mm
Outdoor unit terminal blockIndoor unit terminal block
30mm
Earth screw
(The connector cover becomes difficult to install.)
Fig. 14
Connection cord
CAUTION
(1) Match the terminal block numbers and connection
cord colors with those of the indoor unit.
Erroneous wiring may cause burning of the electric
parts.
(2) Connect the connection cords firmly to the terminal
block. Imperfect installation may cause a fire.
FINISHING
(1) Insulate between pipes.
● For rear, right, and bottom piping, overlap the connection pipe heat insulation and
indoor unit pipe heat insulation and bind them with vinyl tape so that there is no gap.
● For left and left rear piping, butt the connection pipe heat insulation and indoor unit
pipe heat insulation together and bind them with and vinyl tape so that there is no gap.
● For left and left rear piping, wrap the area which accommodates the rear piping housing
section with cloth tape.
● For left and left rear piping, bind the connection cord to the top of the pipe with vinyl
tape.
● For left and left rear piping, bundle the piping and drain hose together by wrapping
them with cloth tape over the range within which they fit into the rear piping housing
section.
(2) Temporarily fasten the connection cord along the connection pipe with vinyl tape. (Wrap
to about 1/3 the width of the tape from the bottom of the pipe so that water does not
enter.)
(3) Fasten the connection pipe to the outside wall with saddles, etc.
(4) Fill the gap between the outside wall pipe hole and the pipe with sealer so that rain
water and wind cannot blow in.
(5) Fasten the drain hose to the outside wall, etc.
Wall
(Outside wall cap)
(Sealer putty)
(Outdoors)
Fig. 15
(Saddle)
Pipe
(3) Always fasten the outside covering of the connec-
tion cord with the cord clamp. (If the insulator is
chafed, electric leakage may occur.)
(4) Securely earth the power cord plug.
(5) Do not use the earth screw for an external connector.
Only use for interconnection between two units.
Fig. 16
Connection pipe
(heat insulation)
Bind the pipes together so
that there is no gap.
Left piping
Connection cord
Pipe
Check the following:
GOOD
Drain hose
Overlap the insulation
Pipe
Drain hose
Drain hose
Saddle
Indoor unit pipe
(heat insullation)
Vinyl tape
Wrap with cloth tape
Cloth tape
For connection from the left rear
Wall pipe
Drain hose
BAD
Lifted up
Connection cord
Connection
pipe
BAD BAD
Wave End in water
TEST RUNNING
● Perform test operation and check items 1 and 2 below.
● For the test operation method, refer to the operating manual.
● The outdoor unit, may not operate, depending on the room temperature. In this case, press the test run button on the remote control unit while
the air conditioner is running, (Point the transmitter section of the remote control unit toward the air conditioner and press the test run button
with the tip of a ball-point pen, etc.)
● To end test operation, press the remote control unit START/STOP button.
(When the air conditioner is run by pressing the test run button, the OPERATION indicator lamp and TIMER indicator lamp will simultaneously
flash slowly.)
1. INDOOR UNIT
(1) Is operation of each button on the remote control unit normal?
(2) Does each lamp light normally?
(3) Do the air flow-direction louver operate normally?
(4) Is the drain normal?
2. OUTDOOR UNIT
(1) Is there any abnormal noise and vibration during operation?
(2) Will noise, wind, or drain water from the unit disturb the neighbors?
(3) Is there any gas leakage?
Transmitter section
Test run button
Fig. 17
P/N 9314989018-02