General AUG25F, AUG25FUAR, AOG25FNAKT Technical Manual

Page 1
R410A
6 . CASSETTE TYPE :  AU 25FUAR (3 PHASE)
D2D_AU014E/01
2005.12.12
Page 2
6-1. FEATURE
FEATURES
Easy maintenance
The control box is easily accessible for maintenance work Wide opening for easy access.
Detachable,washable filter and intake grille.
Wide opening and long-life filter.
Long-life filter High efficiency, long-life filter extends the cleaning cycle.
Long-life filter
Slim intake grille
Slim type intake grille can fit the ceiling after installation.
CASSETTE TYPE
AU25F
20
(unit: mm)
CASSETTE TYPE
AU25F
Group controller
One remote controller can control up to 16 air conditioners. All of the air conditioners will be operated with the same settings.
Connectable quantity : Maximum 16 indoor units for 1 remote controller.
- (06 - 01) -
Page 3
Duct connection hole opening
Fresh air can be introduced through this opening.
Distribution duct
Fresh air
Distribution duct
Conditioned air can be distributed by means of a distribution duct.
One-way
CASSETTE TYPE
AU25F
Two-way
CASSETTE TYPE
AU25F
- (06 - 02) -
Page 4
6-2. REMOTE CONTROLLER
6-2-1. WIRED REMOTE CONTROLLER
FEATURES
Various timer setup (ON / OFF / WEEKLY) are possible.
SUMOTUWETH FR SA
7
3126 9
15 18 21
High performance and compact size
Equipped with weekly timer as standard function. (2 times Start / Stop per day for a week)
When setting up a timer, operation mode and a temperature setup can be changed.
When a failure occurs,the error code is displayed. (Maximum of 16)
Error indication.(A maximum of 16 error histories are memorizable.)
Up to 16 indoor units can be simultaneously controlled.
Anti freeze and energy saving operation are possible.
Easy installation with a slim shape with no boldge in the back.
The room temperature can be controlled by being detected the temperature accurately with built-in thermo sensor.
Three functions are combined in one unit.
Wired
remote
controller
Weekly
timer
Setback
timer
Built-in timers
Setback timerWeekly timer
Possible to set ON/OFF time to operate twice each day of the week.
SUMOTUWETH FR SA
7
3126 9
15 18 21
Setup screen example
CASSETTE TYPE
AU25F
(Set to Wednesday: 8:00 to 20:00.)
0 3 6 9 12 15 18 21 Time
Easy-to-understand time bar display
24°C
SUMOTUWETH FR SA
7
3126 9
15 18 21
Screen after setup
At "Weekly timer" + "Set back timer" setup
24°C 28°C 24°C
0 3 6 9 12 15 18 21 Time
Possible to set temperature for two time spans and for each day of the week.
SUMOTUWETH FR SA
3126 9
15 18 21
Setup screen example (Set from Sunday to Saturday: 12:00 to 15:00, 28 °C.)
28°C
0 3 6 9 12 15 18 21 Time
24°C
28°C
CASSETTE TYPE
AU25F
Easy-to-understand operation Simple installation
Components are compatible with standard switch boxes. Flat back construction allows equipment to be installed wherever it is needed.
Timer area
[
Variable timer control
]
The operation/display sections are zoned accord­ing to time and operation, enabling variable pro­gramming to match application.
Operation area
European switch box
- (06 - 03) -
JIS box
Page 5
FUNCTIONS
Display
2 7 8 9
10
11
12
Display panel
15
CLOCK ADJUST
SET BACK
SUMOTUWETH FR
369
12 15 18 21
DAY OFF
DELETE SET
1
START/STOP button
Pressed to start and stop operation.
2
Set Temperature button
SA
14
DAY
ENERGY
THERMO
SAVE
SENSOR
1 3
4
5
6
13
Selects the setting temperature.
3
Master control button
Selects the operating mode(AUTO, HEAT, FAN, COOL, DRY).
4
Fan control button
Selects the fan speed (AUTO, LOW, MED, HIGH).
5
Thermo sensor button
6
Energy save button
Turns the energy efficient mode on and off.
7
Timer mode (CLOCK ADJUST) button
Selects the timer mode (OFF TIMER, ON TIMER, WEEKLY TIMER) Set the current time.
8
Day (DAY OFF) button
Temporarily cancels of one day timer.
9
16
1718 19
Set back button
pressed select the set back timer.
10
SUMOTUWETH FR
SA
Set time button
Pessed to select the set back timer.
11
369
12 15 18 21
202122
Delete button
The schedule of a weekly timer is deleted.
12
Set button
Sets the date, hour, minute and on-off time.
13
Vertical air flow direction and swing button
DIMENSION
120
CASSETTE TYPE
AU25F
SUMOTUWETH FR
CLOCK ADJUST
SET BACK
DELETE SET
369
12 15 18 21
DAY
DAY OFF
SA
ENERGY
THERMO
SAVE
SENSOR
[ Unit : mm ]
17
120
Push for two seconds to change the swing mode
14
Operation lamp
Lights during operation and when the timer is on.
15
Timer and clock display
16
Operation mode display
17
Fan speed display
18
Central control display
19
Temperature display
20
Stand by display
CASSETTE TYPE
AU25F
Indicates during the oil recovery and defrosting operation.
21
Front View
Vertical swing display
22
Energy save display
SPECIFICATION
SIZE (H x W x D mm) 120 x 120 x 17
WEIGHT ( g ) 160
CABLE LENGTH ( m )
POWER ( V )
10
12
- (06 - 04) -
Page 6
6-3. SPECIFICATIONS
AU 25FUAR
AO 25FNAKT
3N 400V 50Hz
3N 342-457V 50Hz
Fin Pitch
1.3
Fin Pitch
1.45
9.52 (3/8 inc)
15.88 (5/8 inc)
RATED
EER
INPUT POWER
kW
CURRENT STARTING CURRENT
kW/kW
A
COP
REMOTE CONTROLLER
TYPEmmMAX LENGTH
REFRIGERANT TYPE
MAX HEIGHT
kg(lbs)
OPERATION(OUTDOOR)
°C
REFRIGERANT OIL
CONNECTION METHOD
CASING COLOR
PIPE
SIZE
mm
WEIGHT
NET
GROSS
NET / GROSS
INDOOR
OUTDOOR
HEAT EXCHANGER TYPE
INDOOR
OUTDOOR
Coil
Fin
Rows x Stages
mm
STARTING METHOD
OUTPUT
Rows x Stages
mm
DIMENSIONS H × W × D
INDOOR
TYPE
COOLING
HEATING
CAPACITY
RATED
Fin
Coil
COMPRESSOR
NOISE LEVEL (SOUND PRESSURE)
COOL/HEAT
FAN SPEED
COOL/HEAT
MODEL NAME
INDOOR
OUTDOOR
TYPE POWER SOURCE
AVAILABLE VOLTAGE RANGE
EUROPEAN ENERGY LABEL
FAN MOTOR OUTPUT
m3/h
AIR CIRCULATION
COOL/HEAT
INDOOR
OUTDOOR
FAN TYPE x Q'ty
DRAIN PIPE MATERIAL
SIZE
MOISTURE REMOVAL
OUTDOOR
INDOOR
OUTDOOR
r.p.m
W
dB(A)
CASSETTE MODELS
COOLING
kW 7.05
BTU/h 24100
kW -
COOLING RATED 2.40
HEATING RATED -
COOLING RATED 4.9
HEATING RATED -
COOLING 2.94
HEATING -
High 1100/-
Med 940/-
Low 780/-
Quiet -
High 3200/-
Low 1600/-
High 490/-
Med 430/-
Low 360/-
Quiet -
High 780/-
Low 400/-
INDOOR Turbo × 1
OUTDOOR Propeller × 1
INDOOR 40
OUTDOOR 65
High 44/-
Med 42/-
Low 39/-
CASSETTE TYPE
AU25F
BTU/h -
A 27
l/h(pints/h) 2.5(5.3)
W 1900
C
53/-
ROTARY
Permanent Split Capacitor
Copper tube
Aluminium
2 × 10
CASSETTE TYPE
AU25F
Note: Specifications are based on the following conditions. Cooling: Indoor temperature of 27 °CDB / 19 °CWB,and outdoor temperature of 35 °CDB/24 °CWB. Heating: Indoor temperature of 20 °CDB / 15 °CW B,and outdoor temperature of 7 °CDB/6 °CW B. Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
Coil Dimensions
Coil Dimensions
Beige(10YR7.5/1.0NN)
INDOOR 246 × 830 × 830
OUTDOOR 650 × 830 × 320
INDOOR 355 × 1060 × 1025
OUTDOOR 768 × 984 × 413
INDOOR 34/44 (75/97)
OUTDOOR 56/60 (123/132)
LIQUID
GAS
CHARGE g 1550
COOLING 0 to 43
HEATING -
m 25(Chaegeless 7.5)
m 15
mm Outer diameter 37.0 / Inner diameter 32.0
210 × 970 × 26.6
Copper tube
Aluminium
2 × 30
630 × 901 × 36.38
White(5Y9/0.5NN)
FLARE
R410A
POE
WIRED
ABS
- (06 - 05) -
Page 7
6-4. DIMENSIONS
6-4-1. OUTDOOR UNIT
MODEL : AO 25F
650
12
Bottom
Top view
830
Front view
Air flow
(Unit : mm)
350
320
Side view
154
101
58
90
343
CASSETTE TYPE
AU25F
603
CASSETTE TYPE
AU25F
Bottom view
MOUNTING POSITION
When there are obstacles at the back or front sides.
100 mm or more
100 mm
600 mm
or more
or more
When there are obstacles at the back, side(s), and top.
600 mm or more
300 mm
25
(
S
0 mm o
er
v
i
c
r
more
e s
p
ac
e)
or more
When there are obstacles at the back, side with the installation of more than one unit.
250 mm or more
250 mm or more
300 mm or more
- (06 - 06) -
Page 8
6-4-2. INDOOR UNIT
750
830
750
830
Bottom view
MODEL : AU 25F
940
(Unit : mm)
246
30
Side view
940
Bottom view (Panel)
Drain inside Dia. 32
outside Dia. 37
298.5
60
(Drain pipe)
CASSETTE TYPE
AU25F
235
200
305.5
248.5
100
70
(Small pipe)
(Large pipe)
CASSETTE TYPE
AU25F
Side view (Standard setting)
Side view (Slender setting)
- (06 - 07) -
Page 9
MOUNTING POSITION
Floor
Strong and durable ceiling
2,300 mm or more
1,200 mm or more
1,000 mm or more
Obstruction
You can select 2-way setting
(A) Standard setting (B) Slender setting
215 mm
250 mm
or more
CASSETTE TYPE
AU25F
100 or more 100 or more
or more
100 or more
CASSETTE TYPE
AU25F
(4 directions) (3 directions)
Piping position
(2 directions) (2 directions)
100 or more
- (06 - 08) -
Page 10
6-5. REFRIGERANT CIRCUIT
MODELS : AU 25F / AO 25F
CASSETTE TYPE
AU25F
CASSETTE TYPE
AU25F
- (06 - 09) -
Page 11
6-6. WIRING DIAGRAMS
6-6-1. OUTDOOR UNIT
MODEL : AO 25F
CASSETTE TYPE
AU25F
CASSETTE TYPE
AU25F
- (06 - 10) -
Page 12
6-6-2. INDOOR UNIT
MODEL : AU 25F
to remote control unit
Terminal
Thermistor (pipe temp.)
Thermistor (room temp.)
Stepping motor
Filter board
to outdoor unit
230V 50Hz
CASSETTE TYPE
AU25F
Controller PCB
Terminal
Fan motor
FM
Drain pump
M
motor
Fan motor capacitor
CASSETTE TYPE
AU25F
- (06 - 11) -
Page 13
6-7. CAPACITY TABLE
(°CDB)
30 °CDB
18 °CWB
Outdoor temperature
18 °CDB
12 °CWB
21 °CWB
16 °CWB
27 °CDB
19 °CWB
26 °CDB
22 °CWB
29 °CDB
23 °CDB
21 °CDB
15 °CWB
Indoor temperature
32 °CDB
23 °CWB
MODELS : AU 25F / AO 25F
COOLING
AFR 18.3
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
0 8.05 6.02 1.50 8.21 6.05 1.54 8.37 6.07 1.56 8.61 6.33 1.58 8.71 6.28 1.59 8.89 6.17 1.61 8.98 6.11 1.62 9.06 6.36 1.63
5 7.76 5.86 1.69 7.94 5.89 1.72 8.13 5.91 1.74 8.42 6.21 1.77 8.54 6.18 1.79 8.75 6.09 1.81 8.84 6.04 1.82 8.93 6.30 1.83
10 7.43 5.66 1.86 7.62 5.68 1.90 7.80 5.72 1.93 8.12 6.05 1.96 8.24 6.02 1.98 8.46 5.95 2.01 8.56 5.91 2.03 8.66 6.18 2.04
15 7.08 5.46 2.04 7.25 5.49 2.09 7.44 5.53 2.11 7.73 5.86 2.15 7.86 5.84 2.17 8.08 5.78 2.21 8.18 5.75 2.23 8.28 6.02 2.24
20 7.06 5.28 2.24 7.21 5.30 2.28 7.38 5.33 2.30 7.67 5.65 2.35 7.79 5.63 2.37 8.02 5.58 2.41 8.12 5.56 2.43 8.22 5.84 2.44
25 7.34 5.44 1.94 7.52 5.46 1.96 7.69 5.50 1.98 7.98 5.80 2.01 8.10 5.78 2.02 8.32 5.72 2.05 8.42 5.68 2.06 8.52 5.96 2.07
30 6.87 5.19 2.13 7.07 5.22 2.14 7.23 5.28 2.16 7.50 5.59 2.19 7.62 5.57 2.21 7.84 5.52 2.24 7.95 5.50 2.25 8.05 5.78 2.27
35 6.39 4.97 2.32 6.51 5.01 2.33 6.68 5.04 2.35 6.93 5.34 2.38 7.05 5.33 2.40 7.28 5.30 2.43 7.38 5.28 2.45 7.49 5.57 2.46
40 5.82 4.72 2.52 5.90 4.74 2.52 6.04 4.76 2.54 6.29 5.07 2.58 6.41 5.07 2.59 6.63 5.04 2.63 6.74 5.03 2.65 6.84 5.33 2.69
43 5.41 4.51 2.63 5.50 4.56 2.64 5.63 4.58 2.65 5.87 4.90 2.69 5.99 4.89 2.71 6.21 4.88 2.75 6.33 4.88 2.77 6.45 5.19 2.79
AFR: Air flow rate (m3/min)
TC : Total capacity (kW)
SHC: Sensible Heat capacity (kW)
PI : Power Input (kW)
CASSETTE TYPE
AU25F
CASSETTE TYPE
AU25F
- (06 - 12) -
Page 14
6-8. CAPACITY COMPENSATION FOR PIPE LENGTH
PIPE LENGTH (m)
COOLING
HEIGHT DIFFERENCE (m)
Outdoor unit
is up-side
Outdoor unit
is bottom-side
AND HEIGHT DIFFERENCE
MODELS : AU 25F / AO 25F
5 7.5 10 15 20 25
15 - - - 0.952 0.919 0.888
10 - - 0.985 0.952 0.919 0.888
7.5 - 1.000 0.985 0.952 0.919 0.888
5 1.010 1.000 0.985 0.952 0.919 0.888
0 1.010 1.000 0.985 0.952 0.919 0.888
-5 1.002 0.992 0.977 0.944 0.912 0.881
-7.5 - 0.988 0.973 0.941 0.908 0.877
-10 - - 0.969 0.937 0.904 0.874
-15 - - - 0.929 0.897 0.867
CASSETTE TYPE
AU25F
CASSETTE TYPE
AU25F
- (06 - 13) -
Page 15
6-9. ADDITIONAL CHARGE CALCULATION
R410A
1550
PIPE LENGTH m
7.5 10 15 20 25(MAX)
ADDITIONAL CHARGE g
0 (Charge less)
+50 +150 +250 +350
20g/m
MODELS : AU 25F / AO 25F
REFRIGERANT TYPE
REFRIGERANT AMOUNT g
REFRIGERANT CHARGE
CASSETTE TYPE
AU25F
CASSETTE TYPE
AU25F
- (06 - 14) -
Page 16
6-10. OPERATION RANGE
AU*25F AO*25F
Cooling
Dry
Model
Mode
Operation Range
Indoor unit Outdoor unit Indoor temperature Indoor humidity Outdoor temperature
18 to 32 °C About 80% or less 0 to 43 °C
CASSETTE TYPE
AU25F
CASSETTE TYPE
AU25F
- (06 - 15) -
Page 17
6-11. FAN PERFORMANCE AND AIR FLOW
6-11-1. AIR VELOCITY DISTRIBUTION
MODEL : AU 25F
4-WAY AIR OUTLET
(m)
3
2
1
0.5
1
2
0.25
UNIT : m/s
Note :
Condition
Fan speed : High Operation mode :FAN
0
0.25 2 1 0.5 0.25
210.5
1
2
2
3
1
0.25
0.5
8765432
(m)
2
1
1012345678
UNIT : m/s
2
2
1
1
0
87
(m)
2
CASSETTE TYPE
AU25F
1
0
21012
0.25
654321012345678
2
1
0.5
0.25
0.5
2
1
0.5
0.25
UNIT : m/s
SIDE VIEW HORIZONTAL LOUVER  : Downward
(m)
0.5
0.25
TOP VIEW HORIZONTAL LOUVER  : Upward
(m)
SIDE VIEW HORIZONTAL LOUVER  : Upward
(m)
CASSETTE TYPE
AU25F
2-WAY AIR OUTLET
(m)
1
0
1
87654321012345678
(m)
2
1
0
87654321012345678
0.25
0.5
210.50.25 2 1 0.5 0.25
2
1
2
1
0.5
- (06 - 16) -
0.25
UNIT : m/s
TOP VIEW HORIZONTAL LOUVER  : Upward
(m)
UNIT : m/s
SIDE VIEW HORIZONTAL LOUVER  : Upward
(m)
Page 18
6-11-2. AIR FLOW
m3/h
1100
m3/h
940
m3/h
780
m3/h
3200
m3/h
1600
780
400
Outdoor unit
HIGH
MED
LOW
HIGH
LOW
AIR FLOW
FAN SPEED
NUMBER OF
ROTATIONS
(r.p.m)
Indoor unit
490
430
360
MODELS : AU 25F / AO 25F
l/s 306
CFM 647
l/s 261
CFM 553
l/s 217
CFM 459
l/s 889
CFM 1883
l/s 444
CFM 942
CASSETTE TYPE
AU25F
CASSETTE TYPE
AU25F
- (06 - 17) -
Page 19
6-11-3. DUCT CONNECTION
MODEL : AU 25F
OUTLET AIR
Duct (Inside Dia. ø100mm)
L
Duct (Inside Dia. ø100mm)
L
DUCT STATIC PRESSURE
DUCT STATIC PRESSURE
(Pa)
(Pa)
98
49
L=5m
AU25
L=3m
L=1m
0
01234
98
49
AU25
(m
3
/min)
L=5m
(mmAq)
10
8
6
4
2
0
5
(mmAq)
10
L=3m
8
L=1m
6
4
2
0
0 1234
0
5
(m3/min)
CASSETTE TYPE
AU25F
FRESH AIR
Duct (Inside Dia. ø70mm)
P
Static pressure required to take in fresh air
Duct Fan
(Pa)
DUCT STATIC PRESSURE
58.8
39.2
19.6
(mmAq)
7
6
5
4
3
2
1
0
0
0.1 0.2 0.3 0.4 0.5 0.6
0
CASSETTE TYPE
AU25F
(m3/min)
- (06 - 18) -
Page 20
6-12. NOISE LEVEL CURVE
6-12-1. OUTDOOR UNIT
COOLING
MODEL : AO 25F
80
70
60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002µbar)
10
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
0
63 125 250 500 1,000 2,000 4,000 8,00 0
Octave band center frequency,Hz
CASSETTE TYPE
AU25F
CASSETTE TYPE
AU25F
- (06 - 19) -
Page 21
SOUND LEVEL CHECK POINT
CASSETTE TYPE
AU25F
CASSETTE TYPE
AU25F
- (06 - 20) -
Page 22
6-12-2. INDOOR UNIT
HIGH
LOW
COOLING
MODEL : AU 25F
80
70
60
NC-65
NC-60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002µbar)
10
0
63 125 250 500 1,000 2,000 4,000 8,00 0
Octave band center frequency,Hz
CASSETTE TYPE
AU25F
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
CASSETTE TYPE
AU25F
- (06 - 21) -
Page 23
SOUND LEVEL CHECK POINT
// //
CENTER
MIC
1.5m
MIC
// //
CENTER
CASSETTE TYPE
AU25F
CASSETTE TYPE
AU25F
- (06 - 22) -
Page 24
6-13. ELECTRIC CHARACTERISTICS
Main Fuse (Circuit breaker) Current A
mm
2
Model Name
Outdoor Fan Motor
0.15
0.73
Indoor Fan Motor
0.153
0.64
1.5
Rated Value
Mode
*1) Wiring Spec.
10
48
27
Power Supply
3N 400V
50
AU 25F
AO 25F
MODELS : AU 25F / AO 25F
Indoor unit
Outdoor unit
Voltage V
Frequency Hz
Current A 4.9 -
Input kW 2.40 -
Max Operating Current A 6.4 -
Starting Current A
Power Cable
*2)Limited wiring length m
Input kW
Cooling Heating
Full Load Amp. A
Input kW
Full Load Amp. A
*1) Wiring Spec : Selected Sample
(Selected based on Japan Electrotechnical Standard and Codes Committee E0005)
*2) Limited Wiring length : This is the wiring length in case voltage descent is less than 2%.
When the wiring length becomes long, please select the wiring of a more larger diameter.
CASSETTE TYPE
AU25F
CASSETTE TYPE
AU25F
- (06 - 23) -
Page 25
6-14. SAFETY DEVICE
AO 25F
FUSE (SIDE OF POWER SUPPLY TERMINAL)
OFF 70°C(10A) 155°C(0A)
ON 80±10°C
AU 25F
OUTDOOR UNIT
FAN MOTOR PROTECTOR THERMAL PROTECTOR 150±5°C OFF
COMPRESSOR THERMAL PROTECTOR
INDOOR UNIT
PCB FUSE - 3.15A 250V
FAN MOTOR PROTECTOR THERMAL PROTECTOR 150±5°C OFF
TERMINAL FUSE - 102±2°C
PROTECTION FORM
- 25A 250V
PROTECTION FORM
CASSETTE TYPE
AU25F
CASSETTE TYPE
AU25F
- (06 - 24) -
Page 26
6-15. FUNCTION SETTING
Auto restart validity/invalidity
Room temperature correct coefficient
Room temperature correct coefficient
Forbidden
Indoor unit number setting
Forbidden
Forbidden
Forbidden
Ceiling height setting
INDOOR UNIT
DIP SW
3
1
JM3
Jumper Wire
2
3
JM1
JM2
Rotary SW
SW 2
SW 1
SW 4
1
2
6-15-1. INDOOR UNIT
SWITCH POSITION
Indoor unit control circuit board
CASSETTE TYPE
AU25F
CASSETTE TYPE
AU25F
- (06 - 25) -
Page 27
6-15-2. SWITCH FUNCTION (INDOOR UNIT)
SW 1-1
SW state
OFF
Invalidity
ON
Validity
0 deg
0 deg
0 deg
cooling
-2 deg
SW 1-2
SW 1-3
0 deg
heating
dry
-2 deg
-2 degONONONOFF
OFF
+2 deg
-2 deg
OFF
SW state
-2 deg
OFF
ON
0 deg
+4 deg
SW 4-1
OFF
3
OFF
-
ON
Less than 2.5
Normal
High ceiling 1
High ceiling 2
Low ceiling
-ONON
3.0-3.5
More than 3.5
-
OFF-ON
OFF
2.5-3.0
OFF
Ceiling height(m)
DIP - SW4
1
2
DIP SWITCH SETTING
SW1-1. Auto restart setting
Auto restart function can be selected by turning this switch ON/OFF.
AUTO RESTART SETTING
( Factory setting)
SW1-2, 1-3. Room temperature correct coefficient of heating.
Decide the heating temperature correct coefficient vale of heating.
TEMPERATURE CORRECTION
( Factory setting)
SW4-1. Dip SW 4-1setting forbidden
( Factory setting)
CASSETTE TYPE
AU25F
SW4-2, 4-3. Ceiling height setting
( Factory setting)
If the setting for a low ceiling is selected, the capacity of the air conditioner decreases slightly.
CASSETTE TYPE
AU25F
- (06 - 26) -
Page 28
ROTARY SWITCH SETTING (SW2)
0
Single
1 - 15
Indoor unit address
SW 2
SW state
SW state
JM 1, 2, 3
Connect
Disconnect
Forbidden
This switch can be used when group control system. Set the indoor unit address in the 0,1,-,15 order.
( Factory setting)
JUMPER WIRE SETTING
JM 1, 2, 3 setting forbidden
( Factory setting)
CASSETTE TYPE
AU25F
CASSETTE TYPE
AU25F
- (06 - 27) -
Page 29
6-15-3. WIRED REMOTE CONTROLLER CIRCUIT BOARD
Wired remote controller
1
Dual remote controller setting
2
Group control setting
DIP SW
SWITCH POSITION
Wired remote controller
Front case (back side)
3
4
Model setting
Auto changeover setting
5
6
Memory backup setting
OFF
1 2 3 4 5 6
ON
ON
DIP Switch
CASSETTE TYPE
AU25F
CASSETTE TYPE
AU25F
- (06 - 28) -
Page 30
6-15-4. WIRED REMOTE CONTROLLER
DIP SWITCH SETTING
1. SW setting
1-1 Dual remote controller setting
Set the remote controller DIP switch No.1 and 2 according to the following table.
( Factory setting)
Number of remote controller
1 (Normal)
2 (Dual)
1-2 Group control setting
Number of indoor unit connection (One/Multiple) This is switched according to the number of connected indoor units.
DIP-SW No.3
OFF
Master unit Slave unit
DIP-SW No.1
DIP-SW No.2
ON
OFF
( Factory setting)
Number of indoor unit
One unit connection
OFF
OFF
DIP-SW No.1
ON ON
DIP-SW No.2
ON Multiple unit connection
1-3 Model setting
The system type of the outdoor unit can be selected by setting up DIP switch No.4 as follows.
( Factory setting)
DIP-SW No.4
OFF
CASSETTE TYPE
AU25F
ON Cooling only model
Heat Pump model
Model
CASSETTE TYPE
AU25F
1-4 Auto changeover setting
Selecting auto changeover validity / invalidity.
( Factory setting)
DIP-SW No.5
OFF
ON Validity
Auto changeover
Invalidity
1-5 Memory backup setting
Set to ON to use batteries for the memory backup.if batteries are not used, all of the settings stored in memory will be deleted if there is a power failure.
This function is wired remotecontroll only.
( Factory setting)
DIP-SW No.6
OFF
ON Validity
Memory backup
Invalidity
- (06 - 29) -
Page 31
6-16. OPTIONAL PARTS
ADDITIONAL GRILLE UTG-AGEA-W
The additional grille hides the gap between the ceiling hole and the outlet grille.
Additional grille (optional parts)
Additonal grille
The ceiling hole
Indoor Unit(grille)
CASSETTE TYPE
AU25F
CASSETTE TYPE
AU25F
- (06 - 30) -