General AUG25F, AUG25FUAR, AOG25FNAKT Technical Manual

R410A
6 . CASSETTE TYPE :  AU 25FUAR (3 PHASE)
D2D_AU014E/01
2005.12.12
6-1. FEATURE
FEATURES
Easy maintenance
The control box is easily accessible for maintenance work Wide opening for easy access.
Detachable,washable filter and intake grille.
Wide opening and long-life filter.
Long-life filter High efficiency, long-life filter extends the cleaning cycle.
Long-life filter
Slim intake grille
Slim type intake grille can fit the ceiling after installation.
CASSETTE TYPE
AU25F
20
(unit: mm)
CASSETTE TYPE
AU25F
Group controller
One remote controller can control up to 16 air conditioners. All of the air conditioners will be operated with the same settings.
Connectable quantity : Maximum 16 indoor units for 1 remote controller.
- (06 - 01) -
Duct connection hole opening
Fresh air can be introduced through this opening.
Distribution duct
Fresh air
Distribution duct
Conditioned air can be distributed by means of a distribution duct.
One-way
CASSETTE TYPE
AU25F
Two-way
CASSETTE TYPE
AU25F
- (06 - 02) -
6-2. REMOTE CONTROLLER
6-2-1. WIRED REMOTE CONTROLLER
FEATURES
Various timer setup (ON / OFF / WEEKLY) are possible.
SUMOTUWETH FR SA
7
3126 9
15 18 21
High performance and compact size
Equipped with weekly timer as standard function. (2 times Start / Stop per day for a week)
When setting up a timer, operation mode and a temperature setup can be changed.
When a failure occurs,the error code is displayed. (Maximum of 16)
Error indication.(A maximum of 16 error histories are memorizable.)
Up to 16 indoor units can be simultaneously controlled.
Anti freeze and energy saving operation are possible.
Easy installation with a slim shape with no boldge in the back.
The room temperature can be controlled by being detected the temperature accurately with built-in thermo sensor.
Three functions are combined in one unit.
Wired
remote
controller
Weekly
timer
Setback
timer
Built-in timers
Setback timerWeekly timer
Possible to set ON/OFF time to operate twice each day of the week.
SUMOTUWETH FR SA
7
3126 9
15 18 21
Setup screen example
CASSETTE TYPE
AU25F
(Set to Wednesday: 8:00 to 20:00.)
0 3 6 9 12 15 18 21 Time
Easy-to-understand time bar display
24°C
SUMOTUWETH FR SA
7
3126 9
15 18 21
Screen after setup
At "Weekly timer" + "Set back timer" setup
24°C 28°C 24°C
0 3 6 9 12 15 18 21 Time
Possible to set temperature for two time spans and for each day of the week.
SUMOTUWETH FR SA
3126 9
15 18 21
Setup screen example (Set from Sunday to Saturday: 12:00 to 15:00, 28 °C.)
28°C
0 3 6 9 12 15 18 21 Time
24°C
28°C
CASSETTE TYPE
AU25F
Easy-to-understand operation Simple installation
Components are compatible with standard switch boxes. Flat back construction allows equipment to be installed wherever it is needed.
Timer area
[
Variable timer control
]
The operation/display sections are zoned accord­ing to time and operation, enabling variable pro­gramming to match application.
Operation area
European switch box
- (06 - 03) -
JIS box
FUNCTIONS
Display
2 7 8 9
10
11
12
Display panel
15
CLOCK ADJUST
SET BACK
SUMOTUWETH FR
369
12 15 18 21
DAY OFF
DELETE SET
1
START/STOP button
Pressed to start and stop operation.
2
Set Temperature button
SA
14
DAY
ENERGY
THERMO
SAVE
SENSOR
1 3
4
5
6
13
Selects the setting temperature.
3
Master control button
Selects the operating mode(AUTO, HEAT, FAN, COOL, DRY).
4
Fan control button
Selects the fan speed (AUTO, LOW, MED, HIGH).
5
Thermo sensor button
6
Energy save button
Turns the energy efficient mode on and off.
7
Timer mode (CLOCK ADJUST) button
Selects the timer mode (OFF TIMER, ON TIMER, WEEKLY TIMER) Set the current time.
8
Day (DAY OFF) button
Temporarily cancels of one day timer.
9
16
1718 19
Set back button
pressed select the set back timer.
10
SUMOTUWETH FR
SA
Set time button
Pessed to select the set back timer.
11
369
12 15 18 21
202122
Delete button
The schedule of a weekly timer is deleted.
12
Set button
Sets the date, hour, minute and on-off time.
13
Vertical air flow direction and swing button
DIMENSION
120
CASSETTE TYPE
AU25F
SUMOTUWETH FR
CLOCK ADJUST
SET BACK
DELETE SET
369
12 15 18 21
DAY
DAY OFF
SA
ENERGY
THERMO
SAVE
SENSOR
[ Unit : mm ]
17
120
Push for two seconds to change the swing mode
14
Operation lamp
Lights during operation and when the timer is on.
15
Timer and clock display
16
Operation mode display
17
Fan speed display
18
Central control display
19
Temperature display
20
Stand by display
CASSETTE TYPE
AU25F
Indicates during the oil recovery and defrosting operation.
21
Front View
Vertical swing display
22
Energy save display
SPECIFICATION
SIZE (H x W x D mm) 120 x 120 x 17
WEIGHT ( g ) 160
CABLE LENGTH ( m )
POWER ( V )
10
12
- (06 - 04) -
6-3. SPECIFICATIONS
AU 25FUAR
AO 25FNAKT
3N 400V 50Hz
3N 342-457V 50Hz
Fin Pitch
1.3
Fin Pitch
1.45
9.52 (3/8 inc)
15.88 (5/8 inc)
RATED
EER
INPUT POWER
kW
CURRENT STARTING CURRENT
kW/kW
A
COP
REMOTE CONTROLLER
TYPEmmMAX LENGTH
REFRIGERANT TYPE
MAX HEIGHT
kg(lbs)
OPERATION(OUTDOOR)
°C
REFRIGERANT OIL
CONNECTION METHOD
CASING COLOR
PIPE
SIZE
mm
WEIGHT
NET
GROSS
NET / GROSS
INDOOR
OUTDOOR
HEAT EXCHANGER TYPE
INDOOR
OUTDOOR
Coil
Fin
Rows x Stages
mm
STARTING METHOD
OUTPUT
Rows x Stages
mm
DIMENSIONS H × W × D
INDOOR
TYPE
COOLING
HEATING
CAPACITY
RATED
Fin
Coil
COMPRESSOR
NOISE LEVEL (SOUND PRESSURE)
COOL/HEAT
FAN SPEED
COOL/HEAT
MODEL NAME
INDOOR
OUTDOOR
TYPE POWER SOURCE
AVAILABLE VOLTAGE RANGE
EUROPEAN ENERGY LABEL
FAN MOTOR OUTPUT
m3/h
AIR CIRCULATION
COOL/HEAT
INDOOR
OUTDOOR
FAN TYPE x Q'ty
DRAIN PIPE MATERIAL
SIZE
MOISTURE REMOVAL
OUTDOOR
INDOOR
OUTDOOR
r.p.m
W
dB(A)
CASSETTE MODELS
COOLING
kW 7.05
BTU/h 24100
kW -
COOLING RATED 2.40
HEATING RATED -
COOLING RATED 4.9
HEATING RATED -
COOLING 2.94
HEATING -
High 1100/-
Med 940/-
Low 780/-
Quiet -
High 3200/-
Low 1600/-
High 490/-
Med 430/-
Low 360/-
Quiet -
High 780/-
Low 400/-
INDOOR Turbo × 1
OUTDOOR Propeller × 1
INDOOR 40
OUTDOOR 65
High 44/-
Med 42/-
Low 39/-
CASSETTE TYPE
AU25F
BTU/h -
A 27
l/h(pints/h) 2.5(5.3)
W 1900
C
53/-
ROTARY
Permanent Split Capacitor
Copper tube
Aluminium
2 × 10
CASSETTE TYPE
AU25F
Note: Specifications are based on the following conditions. Cooling: Indoor temperature of 27 °CDB / 19 °CWB,and outdoor temperature of 35 °CDB/24 °CWB. Heating: Indoor temperature of 20 °CDB / 15 °CW B,and outdoor temperature of 7 °CDB/6 °CW B. Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
Coil Dimensions
Coil Dimensions
Beige(10YR7.5/1.0NN)
INDOOR 246 × 830 × 830
OUTDOOR 650 × 830 × 320
INDOOR 355 × 1060 × 1025
OUTDOOR 768 × 984 × 413
INDOOR 34/44 (75/97)
OUTDOOR 56/60 (123/132)
LIQUID
GAS
CHARGE g 1550
COOLING 0 to 43
HEATING -
m 25(Chaegeless 7.5)
m 15
mm Outer diameter 37.0 / Inner diameter 32.0
210 × 970 × 26.6
Copper tube
Aluminium
2 × 30
630 × 901 × 36.38
White(5Y9/0.5NN)
FLARE
R410A
POE
WIRED
ABS
- (06 - 05) -
6-4. DIMENSIONS
6-4-1. OUTDOOR UNIT
MODEL : AO 25F
650
12
Bottom
Top view
830
Front view
Air flow
(Unit : mm)
350
320
Side view
154
101
58
90
343
CASSETTE TYPE
AU25F
603
CASSETTE TYPE
AU25F
Bottom view
MOUNTING POSITION
When there are obstacles at the back or front sides.
100 mm or more
100 mm
600 mm
or more
or more
When there are obstacles at the back, side(s), and top.
600 mm or more
300 mm
25
(
S
0 mm o
er
v
i
c
r
more
e s
p
ac
e)
or more
When there are obstacles at the back, side with the installation of more than one unit.
250 mm or more
250 mm or more
300 mm or more
- (06 - 06) -
6-4-2. INDOOR UNIT
750
830
750
830
Bottom view
MODEL : AU 25F
940
(Unit : mm)
246
30
Side view
940
Bottom view (Panel)
Drain inside Dia. 32
outside Dia. 37
298.5
60
(Drain pipe)
CASSETTE TYPE
AU25F
235
200
305.5
248.5
100
70
(Small pipe)
(Large pipe)
CASSETTE TYPE
AU25F
Side view (Standard setting)
Side view (Slender setting)
- (06 - 07) -
MOUNTING POSITION
Floor
Strong and durable ceiling
2,300 mm or more
1,200 mm or more
1,000 mm or more
Obstruction
You can select 2-way setting
(A) Standard setting (B) Slender setting
215 mm
250 mm
or more
CASSETTE TYPE
AU25F
100 or more 100 or more
or more
100 or more
CASSETTE TYPE
AU25F
(4 directions) (3 directions)
Piping position
(2 directions) (2 directions)
100 or more
- (06 - 08) -
6-5. REFRIGERANT CIRCUIT
MODELS : AU 25F / AO 25F
CASSETTE TYPE
AU25F
CASSETTE TYPE
AU25F
- (06 - 09) -