General ARG12F, ARG12FUAD, AOG12FSAJ, ARG12U, ARG12UUAD Installation Manual

...
Refrigerant
Duct Type
R410A
SPLIT TYPE AIR CONDITIONER
INSTALLATION INSTRUCTION SHEET
(PART NO. 9364658049)
WARNING
CAUTION
The basic installation work procedures are the same as conventional refrigerant (R22) models. However, pay careful attention to the following points:
(1) Since the working pressure is 1.6 times higher than that of conventional refrigerant (R22) models, some of the piping and
installation and service tools are special. (See the table below.) Especially, when replacing a conventional refrigerant (R22) model with a new refrigerant R410A model, always replace the conventional piping and flare nuts with the R410A piping and flare nuts.
(2) Models that use refrigerant R410A have a different charging port thread diameter to prevent erroneous charging with
conventional refrigerant (R22) and for safety. Therefore, check beforehand. [The charging port thread diameter for R410A is 1/2 UNF 20 threads per inch.]
(3) Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with refrigerant (R22) models. Also, when
storing the piping, securely seal the openings by pinching, taping, etc.
(4) When charging the refrigerant, take into account the slight change in the composition of the gas and liquid phases, and
always charge from the liquid phase side whose composition is stable.
Special tools for R410A
Tool name
Gauge manifold
Charge hose
Vacuum pump
Gas leakage detector
Copper pipes
It is necessary to use seamless copper pipes and it is desirable that the amount of residual oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed, deformed or discolored portion (especially on the interior surface). Otherwise, the expansion valve or capillary tube may become blocked with contaminants. As an air conditioner using R410A incurs pressure higher than when using R22, it is necessary to choose adequate materials. Thicknesses of copper pipes used with R410A are as shown in Table 1. Never use copper pipes thinner than 0.8 mm (Nominal diameter is 1/4 in., 3/8 in. 1/2 in.), 1.0 mm (Nominal diameter is 5/8 in.) even when it is available on the market.
This mark indicates procedures which, if improperly performed, might lead to the death or serious injury of the user.
This mark indicates procedures which, if improperly performed, might possibly result in personal harm to the user, or damage to property.
This air conditioner uses new refrigerant HFC (R410A).
Contents of change
Pressure is high and cannot be measured with a conventional gauge. To prevent erroneous mixing of other refrigerants, the diameter of each port has been changed. It is recommended the gauge with seals –0.1 to 5.3 MPa (–76 cmHg to 53 kgf/cm2) for high pressure. –0.1 to 3.8 MPa (–76 cmHg to 38 kgf/cm To increase pressure resistance, the hose material and base size were changed. A conventional vacuum pump can be used by installing a vacuum pump adapter. Special gas leakage detector for HFC refrigerant R410A.
2
) for low pressure.
Table 1 Thicknesses of Annealed Copper Pipes
Thickness (mm)
Nominal
diameter (inch)
1/4 3/8 1/2 5/8
Outer diameter
(mm)
6.35
9.52
12.70
15.88
R410A [ref.] R22
0.80 0.80
0.80 0.80
0.80 0.80
1.00 1.00
STANDARD PARTS
The following installation parts are furnished. Use them as required.
INDOOR UNIT ACCESSORIES
Name and Shape
Installation template
Hanger
Tapping screw (ø4 × 10)
Special nut A (large flange)
Special nut B (small flange)
Coupler heat insulation (large)
Coupler heat insulation (small)
Binder
Remote controller
Remote controller cord
Tapping screw (ø4 × 16)
Filter
Drain hose insulation
Q’ty
1
4
8
4
4
1
1
(Small)
1
(Large)
4
1
1
2
2
3
1
Application
For positioning the indoor unit
For suspending the indoor unit from ceiling
For installing the hanger
For suspending the indoor unit from ceiling
For indoor side pipe joint (large pipe)
For indoor side pipe joint (small pipe)
For remote controller and remote controller cord binding
For fixing the coupler heat insulation
For connecting the remote controller
For installing the remote controller
7000 and 9000 BTU/h models
12000, 14000, and 18000 BTU/h models
Insulates the drain hose and vinyl hose connection
OUTDOOR UNIT ACCESSORIES
Name and Shape
Drain pipe
Drain cap
7000, 9000, 12000 and 14000 BTU/h models
18000 BTU/h model
Q’ty
1
For outdoor unit drain piping work [Heat & Cool model (Reverse cycle) only]
2
1
Application
1
INDOOR UNIT INSTALLATION
A. CEILING CONCEALED TYPE
1. INSTALL THE FILTERS
• Install the filters to the unit (Fig. 3).
Fig. 3-(1)
[12000, 14000, and
18000 BTU/h models]
Filter
Fig. 3-(2)
Unit
This unit may also be installed with the air inlet facing down. See also Figs. 11 and 12 for such cases.
2. DRILLING HOLES FOR BOLTS AND INSTALL­ING THE BOLTS
• Using the installation template, drill holes for bolts (4 holes).(Fig. 4)
Fig. 4
3. INSTALLING THE HANGERS
• Fasten the hanging bolts to the ceiling and install special nuts A and B.
Fig. 5
[7000 and 9000 BTU/h models]
Filter
Installation template
Drilling position for bolts
M10 Hanging bolt
Special nut A
Special nut B
• Install the hangers to the unit (4 places).
Fig. 6
Hanger
Air
Hanger
Tapping screw
• Hang the unit. (1) Pass the hanging bolts through the hangers (4 places).
Fig. 7
Hanger bolt Hanger
Unit
CAUTION
Fasten the unit securely with special nuts A and B.
4. LEVELING
Base horizontal direction leveling on top of the unit.
Fig. 8
Ceiling
Level
10 mm
OK
Fig. 9
Air
OK
or less
10 mm
or less
Level
NO
NO
Drain side
5. SERVICE HOLE DIMENSIONS
Open a service hole with the dimensions shown Fig. 10.
Fig. 10
Unit
10 cm (4”)
or more
Service hole
Control box
30 cm (1’) or more
B. FLOOR STANDING CONCEALED TYPE
1. INSTALL THE FILTERS
• Remove the 4 tapping screws, and then remove cover.
• Install the cover with the 4 tapping screws as shown in the illustration below.
Fig. 11
[12000, 14000, and
18000 BTU/h models]
Tapping screw
• Install the filters to the unit refer to Fig. 3-(2).
Fig. 12
[12000, 14000, and
18000 BTU/h models]
Filter
2. INSTALLING THE HANGERS
• Install the hangers to the unit (4 places).
Fig. 13
[7000 and 9000 BTU/h models]
Cover
[7000 and 9000 BTU/h models]
Hanger
Tapping screw
Cover
Filter
3. DRILLING HOLES FOR BOLTS AND INSTALL­ING THE BOLTS
• Drilling position for bolts.
Fig. 14
)
[7000 and 9000 BTU/h models]
59.6 cm (23-1/2’)
17 cm
(6-3/4
[12000, 14000, and 18000 BTU/h models]
88.6 cm (34-7/8’)
17 cm
CAUTION
Secure with an M10 anchor bolts. If securing the unit to the floor is difficult, first build a stand or platform.
Fig. 15
M10
30 to 50 mm (1-3/16” to 2-1/36”)
4. INSTALL THE UNIT
• Fix the unit.
Install the unit and fasten with special nut B.
Fig. 16
Unit
Special nut B
5. LEVELING
Base horizontal and vertical direction leveling on top of the unit.
Fig. 17
Fig. 18
OK
In order to prevent water from leaking around the outlet port, make sure insulate it (on both the CEILING CONCEALED type and the FLOOR STANDING CONCEALED type).
Level
10 mm
or less
CAUTION
Drain side
NO
)
(6-3/4
For authorized service personnel only.
WARNING
(1) For the room air conditioner to operate satisfactorily, install it as outlined in this installation instruction sheet.
(2) Connect the indoor unit and outdoor unit with the room air conditioner piping and cords available standards parts. This
installation instruction sheet describes the correct connections using the installation set available from our standard parts.
(3) Installation work must be performed in accordance with national wiring standards by authorized personnel only.
(4) If refrigerant leaks while work is being carried out, ventilate the area. If the refrigerant comes in contact with a flame, it
produces a toxic gas.
(5) Do not use an extension cord.
(6) Do not turn on the power until all installation work is complete.
••
Be careful not to scratch the room air conditioner when handling it.
••
••
After installation, explain correct operation to the customer, using the operating manual.
••
••
Let the customer keep this installation instruction sheet because it is used when the air conditioner is serviced or moved.
••
SELECTING THE MOUNTING POSITION
WARNING
Install at a place that can withstand the weight of the indoor and outdoor units and install positively so that the units will not topple or fall.
CAUTION
(1) Do not install where there is the danger of combustible gas leakage.
(2) Do not install near heat sources.
(3) If children under 10 years old may approach the unit, take preventive measures so that they cannot reach the unit.
(4) Take precautions to prevent the unit from falling.
Decide the mounting position with the customer as follows:
INDOOR UNIT
(1) Install the indoor unit level on a strong wall, floor, ceiling which is not sub-
ject to vibration.
(2) The inlet and outlet ports should not be obstructed : the air should be able
to blow all over the room. (3) Install the unit near an electric outlet or special branch circuit. (4) Do not install the unit where it will be exposed to direct sunlight. (5) Install the unit where connection to the outdoor unit is easy. (6) Install the unit where the drain pipe can be easily installed. (7) Take servicing, etc. into consideration and leave the spaces shown in Fig.1.
Also install the unit where the filter can be removed. (8) Install the indoor unit where vibrations and noise are not amplified. (9) When installing the unit on the floor, provide an opening that will allow
sufficient air to reach the air inlet panel.
Fig. 1
Strong and durable ceiling
Indoor unit
Left side
10 cm (4”) or more
Left side
Strong and durable floor
10 cm (4”) or more 30 cm (1’) or more
Right side (PIPE side)
30 cm (1’) or more
3 cm (1”)
or more
Right side
3 cm (1”)
or more
OUTDOOR UNIT
WARNING
(1) Install the unit where it will not be tilted by more than 5˚.
(2) When installing the outdoor unit where it may exposed to strong wind, fasten it securely.
(1) If possible, do not install the unit where it will exposed to direct sunlight. (If necessary, install a blind that does not interfere with the air flow.) (2) Install the outdoor unit in a place where it will be free from being dirty or getting wet by rain as much as possible. (3) Install the unit when connection to the indoor unit is easy. (4) During heating operation, drain water flows from the outdoor unit. Therefore, install the outdoor unit in a place where the drain water flow will not be
obstructed. (Reverse cycle model only) (5) Do not place animals and plants in the path of the warm air. (6) Take the air conditioner weight into account and select a place where noise and vibration are small. (7) Select a place so that the warm air and noise from the air conditioner do not disturb neighbors. (8) Provide the space shown in Fig. 2 so that the air flow is not blocked. Also for efficient operation, leave open three of the four directions front, rear, and both
sides.
Fig. 2
[18000 BTU/h model]
30 cm (1’) or over
30 cm (1’) or over
Air
60 cm (2’) or over
60 cm (2’) or over
30 cm (1’) or over
[7000, 9000, 12000 and 14000 BTU/h models]
10 cm (4”) or over
60 cm (2’) or
over
60 cm (2’) or over
60 cm (2’) or over
10 cm (4”) or over
CONNECTION PIPE REQUIREMENT
Table 2
MODEL
Diameter
Maximum length
Maximum Height (between indoor and outdoor)
••
Use pipe with water-resistant heat insulation.
••
Small Large
7000, 9000 and
12000 BTU/h models
6.35 mm (1/4 in.) 6.35 mm (1/4 in.) 6.35 mm (1/4 in.)
9.52 mm (3/8 in.) 12.70 mm (1/2 in.) 15.88 mm (5/8 in.)
15 m (49 ft) 15 m (49 ft) 20 m (66 ft)
8 m (26 ft) 8 m (26 ft) 8 m (26 ft)
14000 BTU/h 18000 BTU/h
model model
ELECTRICAL REQUIREMENT
••
Electric wire size and fuse capacity:
••
Table 3
MODEL
Power supply cord (mm2)
Connection cord (mm2)
Fuse capacity (A)
••
Always use H07RN-F or equivalent to the connection cord.
••
••
Install the disconnect device with a contact gap of at least 3 mm nearby the units. (Both
••
indoor unit and outdoor unit)
7000 BTU/h model
9000 BTU/h model
MAX.
MIN.
MAX.
MIN.
3.0 3.0 3.0
1.5 2.0 2.5
2.5 2.5 2.5
1.5 1.5 1.5 10 15 20
12000 BTU/h model
14000 BTU/h model
18000 BTU/h model
2
OUTDOOR UNIT INSTALLATION
WARNING
(1) Install the unit where it will not be tilted by more than 5˚.
(2) When installing the outdoor unit where it may exposed
to strong wind, fasten it securely.
Set the unit on a strong stand, such as one made of concrete blocks to minimize shock and vibration.
Do not set the unit directly on the ground because it will cause trouble.
Since the drain water flows out of the outdoor unit during heating op-
eration, install the drain pipe and connect it to an commercial 16 mm hose. (Heat & Cool model (Reverse cycle) only)
When installing the drain pipe, plug all the holes (• hole at one place) other than the drain pipe mounting hole in the bottom of the outdoor unit with putty so there is no water leakage. (Fig. 19) (Heat & Cool model (Reverse cycle) only)
CAUTION
Installation in cold regions. Do not use the accessory drain pipe and drain cap. (If the drain pipe and drain cap are used, the drain water in the pipe may freeze in extremely cold weather.)
Fig. 19
[7000, 9000, 12000 and 14000 BTU/h models]
Bottom
Drain cap
Drain pipe mounting hole
[18000 BTU/h model]
Bottom
Drain cap
Drain pipe mounting hole
Air flow
285 mm (11-7/32”)
504 mm (21-1/4”)
Bottom plate
Drain pipe
Air flow
343 mm (13-1/2”)
603 mm (23-23/32”)
Bottom plate
Drain pipe
3
CONNECTING THE PIPING
WARNING
Do not use the existing (for R22) piping and flare nuts.
If the existing materials are used, the pressure inside the refrigerant cycle will rise and cause breakage, injury, etc. (Use the special R410A materials.)
CAUTION
(1) Do not use mineral oil on flared part.
Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
(2) While welding the pipes, be sure to blow dry nitrogen
gas through them.
(3) The maximum lengths of this product are shown in ta-
ble 2. If the units are further apart than this, correct operation can not be guaranteed.
CAUTION
Install heat insulation around both the gas and liquid pipes. Failure to do so may cause water leaks. Use heat insulation with heat resistance above 120 °C. (Reverse cycle model only) In addition, if the humidity level at the installation location of the refrigerant piping is expected to exceed 70%, install heat insulation around the refrigerant piping. If the ex­pected humidity level is 70-80%, use heat insulation that is 15 mm or thicker and if the expected humidity exceeds 80%, use heat insulation that is 20 mm or thicker. If heat insulation is used that is not as thick as specified, condensation may form on the surface of the insulation. In addition, use heat insulation with heat conductivity of
0.045 W/(m·K) or less (at 20 °C).
1. FLARING
(1) Cut the connection pipe to the necessary length with a pipe cutter. (2) Hold the pipe downward so that cuttings will not enter the pipe and
remove the burrs.
(3) Insert the flare nut (always use the flare nut attached to the indoor
and outdoor units respectively) onto the pipe and perform the flare processing with a flare tool. Use the special R410A flare tool, or the conventional (for R22) flare tool. When using the conventional flare tool, always use an allowance ad­justment gauge and secure the A dimension shown in table 4.
Fig. 20
Check if [L] is flared uniformly and is not cracked or scratched.
Die
A
L
Pipe outside
diameter
6.35 mm (1/4 in.)
9.52 mm (3/8 in.)
12.70 mm (1/2 in.)
15.88 mm (5/8 in.)
Table 4 Pipe outside diameter
A (mm)
Flare tool for
R410A, clutch type
0 to 0.5 0 to 0.5 0 to 0.5 0 to 0.5
Conventional (R22) flare tool Clutch type Wing nut type
1.0 to 1.5 1.5 to 2.0
1.0 to 1.5 1.5 to 2.0
1.0 to 1.5 2.0 to 2.5
1.0 to 1.5 2.0 to 2.5
Pipe
2. BENDING PIPES
(1) When bending the pipe, be careful not to crush it. (2) To prevent crushing of the pipe, do not bend the pipe at a radius cur-
vature of 100 mm or over.
(3) If the copper pipe is bend the pipe or pulled to often, it will become
stiff. Do not bend the pipes more than three times at one place.
3. CONNECTION
(1) Install the outdoor unit wall cap (supplied with the optional installation
set or procured at the site) to the wall hole pipe. (2) Connect the outdoor unit and indoor unit piping. (3) After matching the center of the flare surface and tightening the nut
hand tight, tighten the nut to the specified tightening torque with a
torque wrench.
Fig. 21
Tighten with two wrenches.
Wrench (fixed)
Flare nut
Torque wrench
Indoor unit pipe
Connection pipe
To prevent gas leakage, coat the flare surface with alkylbenzene oil (HAB). Do not use mineral oil.
Table 5 Flare nut tightening torque
Flare nut
6.35 mm (1/4 in.) dia.
9.52 mm (3/8 in.) dia.
12.70 mm (1/2 in.) dia.
15.88 mm (5/8 in.) dia.
Do not remove the cap from the connection pipe before connecting the pipe.
Tightening torque
14 to 18 N · m (140 to 180 kgf · cm)
33 to 42 N · m (330 to 420 kgf · cm)
50 to 62 N · m (500 to 620 kgf · cm)
63 to 77 N · m (630 to 770 kgf · cm)
CAUTION
Be sure to connect the large pipe after connecting the small pipe completely.
• Lay the piping.
A. CEILING CONCEALED TYPE
Fig. 22
Control box cover
Pipe
OK NO
B. FLOOR STANDING CONCEALED TYPE
Fig. 23
OK
OK
NO
CAUTION
(1) Install the piping so that the control box cover can be
removed for servicing.
(2) In order to prevent water from leaking into the control
box, make sure that the piping is well insulated.
4. HEAT INSULATION ON THE PIPE JOINTS (INDOOR SIDE ONLY)
After checking for gas leaks, insulate by wrapping insulation around the
two parts (large and small) of the indoor unit coupling, using the cou­pler heat insulation.
After installing the coupler heat insulation, wrap both ends with vinyl
tape so that there is no gap.
After wrapping tape around the ends of the coupler heat insulation,
secure the heat insulation pipe and the taped portion with large binders in two places, as shown in Fig. 24.
Fig. 24
Coupler heat insulation
Indoor unit
Binder (Large) Heat insulating pipe
Fig. 25
Cover this portion with heat insulating material also without fail.
No gap
Coupler heat insulation
- Continued on back -
4
High static pressure mode
HIGH
Normal mode
HIGH
High static pressure mode
HIGH
Normal mode
HIGH
High static pressure mode
HIGH
Normal mode
HIGH
Normal mode
HIGH
High static pressure mode
HIGH
278
VACUUM PROCESS
CAUTION
(1) Do not purge the air with refrigerants but use a vacuum
pump to vacuum the installation! There is no extra re­frigerant in the outdoor unit for air purging!
(2) Use a vacuum pump for R410A exclusively. Using the
same vacuum pump for different refrigerants may dam­age the vacuum pump or the unit.
1. VACUUM
(1) Remove the cap, and connect the gauge manifold and the vacuum
pump to the charging valve by the service hoses.
(2) Vacuum the indoor unit and the connecting pipes until the pressure
gauge indicates –0.1 MPa (–76 cmHg).
(3) When –0.1 MPa (–76 cmHg) is reached, operate the vacuum pump
for at least 15 minutes.
(4) Disconnect the service hoses and fit the cap to the charging valve to
the specified torque.
(5) Remove the blank caps, and fully open the spindles of the 2-way and
3-way valves with a hexagon wrench (Torque : 6 to 7 N · m (60 to 70 kgf · cm).
(6) Tighten the blank caps of the 2-way valve and 3-way valve to the
specified torque.
Table 6
Tightening torque
Blank cap (2-way valve)
9.52 mm (3/8 in.)
Blank cap
(3-way valve)
12.70 mm (1/2 in.)
15.88 mm (5/8 in.)
Charging port cap
Outdoor unit
Service hose with valve core
Cap
Gauge manifold
Service hose
[18000 BTU/h model]
[7000, 9000, 12000 and 14000 BTU/h models]
20 to 25 N · m (200 to 250 kgf · cm)
20 to 25 N · m (200 to 250 kgf · cm)
25 to 30 N · m (250 to 300 kgf · cm)
30 to 35 N · m (300 to 350 kgf · cm)
10 to 12 N · m (100 to 120 kgf · cm)
Connecting pipe
Blank cap
Hexagon wrench
3-way valve
Charging port
Use a clean gauge manifold and charging hose for
t
L O
H
I
Vacuum pump
Gauge manifold
R410A exclusively.
Use a 4 mm hexagon wrench.
CAUTION
t
Vacuum pump
Service hose
2. ADDITIONAL CHARGE
Refrigerant suitable for a piping length of 7.5 m is charged in the outdoor unit at the factory. When the piping is longer than 7.5 m, additional charging is necessary. For the additional amount, see the table below.
Pipe length
Additional refrigerant
7000, 9000 12000 and
14000 BTU/h models
18000 BTU/h model
7.5 m
(25 ft)
None
None
10 m
(33 ft)
37.5 g
(1.3 oz)
50 g
(1.8 oz)
15 m
(49 ft)
112.5 g (4.0 oz)
150 g
(5.3 oz)
20 m
(66 ft)
250 g
(8.8 oz)
g/m
(oz/ft)
15 g/m
(0.53 oz/3.3 ft)
20 g/m
(0.71 oz/3.3 ft)
CAUTION
(1) When moving and installing the air conditioner, do not
mix gas other than the specified refrigerant (R410A) inside the refrigerant cycle.
(2) When charging the refrigerant R410A, always use an
electronic balance for refrigerant charging (to meas­ure the refrigerant by weight).
(3) When charging the refrigerant, take
into account the slight change in the composition of the gas and liquid phases, and always charge from the liquid phase side whose composi­tion is stable.
(4) Add refrigerant from the charging valve after the com-
pletion of the work.
(5) If the units are further apart than the maximum pipe
length, correct operation can not be guaranteed.
Gas
R410A
Liquid
3. GAS LEAKAGE INSPECTION
CAUTION
After connecting the piping, check the joints for gas leak­age with gas leak detector.
5
INSTALLING DRAIN HOSE
INSTALL THE DRAIN HOSE
Install the drain hose with downward gradient (1/50 to 2/50) and so there are no rises or traps in the hose.
Use general hard polyvinyl chloride pipe and connect it with adhesive (polyvinyl chloride) so that there is no leakage.
When the hose is long, install supporters.
Do not perform air bleeding.
Always heat insulate the indoor side of the drain hose.
A. CEILING CONCEALED TYPE
Drain
Outlet air flow
OK
Arrange the drain hose lower than this portion
hose
NO
Rise
1.5 to 2 m (5 to 6.5 ft)
Air bleeding
Trap
Supporter
B. FLOOR STANDING CONCEALED TYPE
Rise
OK
(1) Install the drain hose so that the control box cover can
be removed for servicing.
(2) In order to prevent water from leaking into the control
box, make sure that the drain hose is well insulated.
(3) After the wiring is connected and installation of the pip-
ing and drain hose is complete, make a seal around the opening in the wall.
The out side diameter of drain port is 26 mm, use a suitable drain hose.
Drain hose insulation
Unit
Drain hose
NO NO
CAUTION
Unit
Drain hose insulation
0 mm
Drain hose
6
ELECTRICAL WIRING
HOW TO CONNECT WIRING TO THE TERMINALS
A. For solid core wiring (or F-cable)
(1) Cut the wire end with a wire cutter or wire-cutting pliers, then strip
the insulation to about 25 mm (15/16”) of expose the solid wire.
(2) Using a screwdriver, remove the terminal screw(s) on the terminal
board.
(3) Using pliers, bend the solid wire to form a loop suitable for the
terminal screw.
(4) Shape the loop wire properly, place it on the terminal board and
tighten securely with the terminal screw using a screwdriver.
B. For strand wiring
(1) Cut the wire end with a wire cutter or wire-cutting pliers, then strip
the insulation to about 10 mm (3/8”) of expose the strand wiring.
(2) Using a screwdriver, remove the terminal screw(s) on the terminal
board.
(3) Using a round terminal fastener or pliers, securely clamp a round
terminal to each stripped wire end.
(4) Position the round terminal wire, and replace and tighten the ter-
minal screw using a screwdriver.
A. Solid wire
)
Insulation
Strip 25 mm (15/16
Wire
Loop
Screw with special washer
Round terminal
Terminal board
Wire
B. Strand wire
)
Strip 10 mm (3/8
Screw with special washer
Round terminal
HOW TO FIXED CONNECTION CORD AND POWER CABLE AT THE CORD CLAMP
After passing the connection cord and power cable through the insula­tion tube, fasten it with the cord clamp.
Insulation tube
Insulation tube Cord clamp
Use VW-1, 0.5 to 1.0 mm thick, PVC tube as the insulation tube.
1. CONNECTION DIAGRAM
[18000 BTU/h model Cooling, Heat&Cool model (Reverse cycle)]
Remote controller
Black White Red
3 2 1
6 5 4 3
2(N)
1
Indoor unit side terminal
Power supply
Power Line
EARTH
L
N
3
2(N)
1
EARTH
Outdoor unit side terminal
Round terminal
[7000, 9000, 12000 and 14000 BTU/h models Cooling model]
Remote controller
Red White Black
1 2 3
1
2(N)
3
Power supply
Power Line
EARTH
L
N
1(L)
2(N)
3 4 5 6
EARTH
Indoor unit side terminal
Outdoor unit side terminal
[7000, 9000, 12000 and 14000 BTU/h models Heat&Cool model (Reverse cycle)]
Remote controller
Red White Black
1 2 3
1
2(N)
3 4 5 6
Power supply
Power Line
EARTH
L
N
1(L)
2(N)
3
4
5
6
EARTH
Indoor unit side terminal
Outdoor unit side terminal
2. INDOOR UNIT SIDE
(1) Remove the control box cover from the control box.
Control box
(2) Cord connection.
Clamp the connection cord with the cord clamp.
Connect the connection cord to the terminal board.
Clamp the remote control cord with nylon clamp.
Connect the remote control cord to the terminal board.
[18000 BTU/h model Cooling, Heat&Cool model (Reverse cycle)] [7000, 9000, 12000 and 14000 BTU/h models Cooling model]
1
2(N)
3456 123
Terminal board
Connection cord
Cord clamp
Screw
Control box cover
Remove the 4 screws and remove the control box cover from the control box.
Nylon clamp
Remote control cord
[7000, 9000, 12000 and 14000 BTU/h models Heat&Cool model (Reverse cycle)]
1
2(N)
3456 123
Terminal board
Connection cord
Cord clamp
Connection cord
Nylon clamp
Remote control cord
CAUTION
(1) Tighten the indoor unit connection cord (to the out-
door unit) and power supply indoor and outdoor unit terminal board connections firmly with the terminal board screws. Faulty connection may cause a fire.
(2) If the indoor unit connection cord (to the outdoor unit)
and power supply are wired incorrectly, the air condi­tioner may be damaged.
(3) Wire the indoor unit connection cord (to the outdoor
unit) by matching the numbers of the outdoor and in­door units terminal board numbers as shown in termi­nal label.
(4) Ground both the indoor and outdoor units by attach-
ing a ground wire.
(5) Unit shall be grounded in compliance with the applica-
ble local and national codes.
3. Floor standing concealed/ceiling concealed select switch
(1) The DIP switches were set for use as a ceiling concealed type at the
factory.
(2) The following changes must be made to the settings if the unit is to be
used as a floor standing concealed type.
(3) Changing the settings for the electrical circuits.
DIP Switch 1 (SW1) on the printed circuit board inside the electric component box must be set as follows.
Rotary switch
DIP switch [SW1]
SW1
Ceiling concealed type
Indoor unit PC board
SW1
Floor standing
concealed type
4. OUTDOOR UNIT SIDE
(1) Remove the terminal cover of the outdoor unit, and insert the end of
the connection cord and the power cable into the terminal board.
(2) Fasten the connection cord with the cord clamp, and install the termi-
nal cover.
Insulation tube (Use VW-1, 0.5 to 1.0 mm thick,
Insulation tube
Connection cord
After passing the connection cord through the insulation tube, fasten it with the cord clamp.
[18000 BTU/h model Cooling, Heat&Cool model (Reverse cycle)]
Terminal cover
Power cable
Ground wire length 60 mm or more
Terminal board
[7000, 9000, 12000 and 14000 BTU/h models Cooling model]
Terminal block
Ground wire length 80 mm or more
Cord clamp
Power supply cord
PVC tube as the insulation tube)
Cord clamp
Cord clamp
Insulation tube
Connection cord
Power cable
Terminal cover
Power cable
NL1
(L)2(N)
3
Insulation tube
Connection cord
Connection cord
Ground wire length 60 mm or more
NL32
(N)
1
Connection cord
Cord clamp
Insulation tube
Connection cord
Control box
Ground wire length 65 mm or more
Cord clamp
Insulation tube
[7000, 9000, 12000 and 14000 BTU/h models Heat & Cool model (Reverse cycle)]
NL1
(L)2(N)
Terminal block
Ground wire length 45 mm or more
Cord clamp
Power supply cord
3456
Ground wire length 65 mm or more
Control box
Insulation tube
Connection cord
CAUTION
When routing the ground wires, leave slack as shown in the illustrations.
7
POWER
WARNING
(1) The rated voltage of this product is 230 V A.C. 50 Hz.
(2) Before turning on the verify that the voltage is within
the 198 V to 264 V range.
(3) Always use a special branch circuit and install a spe-
cial breaker to supply power to the room air conditioner.
(4) Use a circuit breaker matched to the capacity of the
room air conditioner. (Install in accordance with stand­ard)
(5) The circuit breaker is installed in the permanent wir-
ing. Always use a circuit that can trip all the poles of the wiring and has an isolation distance of at least 3 mm between the contacts of each pole.
(6) Perform wiring work in accordance with standards so
that the room air conditioner can be operated safely and positively.
(7) Install a leakage circuit breaker in accordance with the
related laws and regulations and electric company standards.
CAUTION
(1) The power source capacity must be the sum of the room
air conditioner current and the current of other electri­cal appliances. When the current contracted capacity is insufficient, change the contracted capacity.
(2) When the voltage is low and the air conditioner is diffi-
cult to start, contact the power company the voltage raised.
8
REMOTE CONTROLLER
SETTING
CAUTION
(1) In order to detect the room temperature
correctly when using the temperature sensor of the remote controller, do not install the remote controller in a place where it will be exposed to direct sun­light or directly below the air outlet of the indoor unit.
(2) When installing the remote controller and cord near a
source of electromagnetic waves, separate the remote controller from the source of the electromagnetic waves and use shielded cord.
(3) Do not touch the remote controller PC board and PC
board parts directly with your hands.
1. INSTALLING THE REMOTE CONTROLLER
(1) Open the operation panel on the front of the remote controller, re-
move the two screws indicated in the following figure, and then re­move the front case of the remote controller.
Front case (back side)
DAY
CLOCK ADJUST
DAY OFF
ENERGY
SET BACK
DELETE SET
Screws
THERMO
SAVE
SENSOR
Connector
When installing the remote controller, remove the connector from the front case. The wires may break if the connector is not removed and the front case hangs down. When installing the front case, connect the connector to the front case.
(2) Install the rear case to the wall, etc. with the two tapping screws.
Refer to the following information to install the remote controller wires.
Front case
Connector
2. ROUTING THE REMOTE CONTROLLER WIRES
(1) Install the remote controller wires to the terminals on the top of the
rear case as shown in the following figure. (2) Fasten the wires with the binder. (3) If the remote controller wires run through the room, use a tool to cut
away the thin area on the upper center of the front case.
(Example)
Binder
1. Red
Temperature sensor
Rear case
Remote controller wires
Rear case
2. White
3. Black
3. SETTING THE DIP SWITCHES
When using a battery (memory backup)
OFF
ON
1 2 3 4 5 6
ON
DIP Switch
Change the DIP switch setting to use batteries. (The DIP switch is not set to use batteries at the factory.) Change DIP switch No. 6 from OFF to ON. If batteries are not used, all of the settings stored in memory will be de­leted if there is a power failure.
4. SETTING THE ROOM TEMPERATURE DETEC­TION LOCATION
The detection location of the room temperature can be selected from the following three examples. Choose the detection location that is best for the installation location.
A. Indoor unit setting (factory setting)
The room temperature is detected by the indoor unit temperature sensor.
A
Indoor unit
(1) When the THERMO SENSOR button is pressed, the lock display
flashes because the function is locked at the factory.
B. Remote controller setting
The room temperature is detected by the remote controller temperature sensor.
B
Indoor unit
(1) Press the THERMO SENSOR button for 5 seconds or more to unlock
the function. The thermo sensor display flashes and then disappears when the function is unlocked.
(2) Press the THERMO SENSOR button.
The thermo sensor display appears.
(3) Press the THERMO SENSOR button again for 5 seconds or more to
lock the function. The thermo sensor display flashes and then remains on when the function is locked.
(4) Make sure that the function is locked.
C.
Indoor unit/remote controller setting (room temperature sensor selection)
The temperature sensor of the indoor unit or the remote controller can be used to detect the room temperature.
C
Indoor unit
(1) Press the THERMO SENSOR button for 5 seconds or more to unlock
the function. The thermo sensor display flashes and then disappears when the function is unlocked.
(2) Press the THERMO SENSOR button to select the temperature sen-
sor of the indoor unit or the remote controller.
NOTES
If the function to change the temperature sensor is used as shown in examples A and B (other than example C), be sure to lock the detection location. If the function is locked, the lock display the THERMO SENSOR button is pressed.
9
TEST RUN
(1) Stop the air conditioner operation. (2) Press the master control button and the fan control button simultane-
ously for 2 seconds or more to start the test run.
Test run display
(3) Press the start/stop button to stop the test run.
[SELF-DIAGNOSIS]
When the error indication “E:EE” is displayed, follow the following items to perform the self-diagnosis. “E:EE” indicates an error has occurred.
1. REMOTE CONTROLLER DISPLAY
1) Stop the air conditioner operation.
2) Press the set temperature buttons simultaneously for 5 sec­onds or more to start the self-diagnosis. Refer to the following tables for the description of each error code.
Unit number (usually 0)
SUMOTUWETH FR
SA
Ex. Self-diagnosis
(3) Press the set temperature buttons simultaneously for 5 sec-
onds or more to stop the self-diagnosis.
Error code Error contents
00 01
Communication error (indoor unit
remote controller)
Communication error (indoor unit outdoor unit)
will flash when
Error code
Error code Error contents
02
03 04 05 06
07 08 09
0A
0b 0c 0d
0E
0F 11 12 13 14
Room temperature sensor open
Room temperature sensor short-circuited
Indoor heat exchanger temperature sensor open
Indoor heat exchanger temperature sensor short­circuited
Outdoor heat exchanger temperature sensor open
Outdoor heat exchanger temperature sensor short­circuited
Power source connection error
Float switch operated
Outdoor temperature sensor open
Outdoor temperature sensor short-circuited
Discharge pipe temperature sensor open
Discharge pipe temperature sensor short-circuited
Outdoor high pressure abnormal
Discharge pipe temperature abnormal
Model abnormal
Indoor fan abnormal
Outdoor signal abnormal
Outdoor EEPROM abnormal
2. OUTDOOR UNIT LEDS
When the outdoor temperature drops, the outdoor unit’s fans may switch to low speed.
ERROR : 18000 BTU/h model HEAT & COOL MODEL (REVERSE CYCLE) ONLY
The LED lamps operate as follows according to the error contents.
Error display
LED1 LED2 Error contents
0.1 sec.
ON
OFF
Quick flash continued Quick flash continued
0.5 sec.
ON
OFF
2 sec.
1 quick flash repeated Lighting continued
0.5 sec.
ON
OFF
2 sec.
2 quick flash repeated Lighting continued
0.5 sec.
ON
OFF
2 sec.
3 quick flash repeated Lighting continued
4 quick flash repeated Lighting continued Outdoor temperature
5 quick flash repeated Lighting continued 6 quick flash repeated Lighting continued Indoor unit error 7 quick flash repeated Lighting continued Discharge temperature
8 quick flash repeated Lighting continued
When the fault is cleared, the LED lamp goes off. However, for discharge pipe temperature abnormal and high pressure abnormal, the LED lamp lights continuously for 24 hours, as long as the power is not turned off.
ON
OFF
ON
OFF
ON
OFF
ON
OFF
0.1 sec.
Model abnormal or EEPROM abnormal
Power source connection error
Discharge tempera­ture sensor error
Outdoor heat exchanger tempera­ture sensor error
sensor error Communication signal error
abnormal High pressure abnormal
10
STATIC PRESSURE
CHARACTERISTIC
1. FAN PERFORMANCE AND AIR FLOW
EXTERNAL STATIC PRESSURE
7000 BTU model
Recommended range
56 83 111
(Pa)
50
40
High static pressure mode
30
20
10
EXTERNAL STATIC PRESSURE
0
200
9000 BTU model
56 83 111
(Pa)
50
40
30
20
10
EXTERNAL STATIC PRESSURE
0
200
12000 BTU model
83 111
(Pa)
50
40
30
20
10
EXTERNAL STATIC PRESSURE
0
300
14000 BTU model
83 111 139
(Pa)
50
40
30
20
10
EXTERNAL STATIC PRESSURE
0
300
High static pressure mode
High static pressure mode
Recommended range
400 500
High static pressure mode
High static pressure mode
400 500
High static pressure mode
Normal mode
Normal mode
300 400
AIR FLOW
Recommended range
HIGH
HIGH
Normal mode
Normal mode
HIGH
HIGH
300 400
AIR FLOW
139
High static pressure mode
High static pressure mode
Normal mode
Normal mode
AIR FLOW
Recommended range
HIGH
HIGH
Normal mode
Normal mode
HIGH
HIGH
AIR FLOW
HIGH
HIGH
HIGH
HIGH
167
600
167
600
HIGH
HIGH
HIGH
HIGH
(
r
/sec)
139
500
3
(m
/h)
(r/sec)
139
500
3
(m
/h)
(r/sec)
194
700
3
(m
/h)
(r/sec)
194
700
3
(m
/h)
18000 BTU model
139 194 222 250 306
80
(Pa)
70
60
50
40
30
20
EXTERNAL STATIC PRESSURE
10
0
Recommended range
167 278
Normal mode
Normal mode
HIGH
HIGH
*
Quiet mode
Quiet mode
HIGH
HIGH
600 800
AIR FLOW
(
r
/sec)
278
1000 1100500 700 900
3
/h)
(m
2. AIR FLOW SETTING
The air flow is set according to the DIP switch settings in the following tables.
[7000, 9000, 12000, and 14000 BTU/h models]
Fan mode
Normal mode (0 Pa 20)
High static pressure mode (20 < Pa 40)
[18000 BTU/h model]
Fan mode
Normal mode (0 Pa 70)
Quiet mode (*0 Pa 40)
* When the PC board of the indoor unit is set for the quiet mode, air flow
and cooling and heating performance will be reduced slightly. The quiet mode can only be used when the external static pressure is 40 Pa or less.
Indoor unit PC board
Dip switch (SW4)
Indoor unit PC board
CAUTION
Do not set any switches other than those specified in this sheet. The air conditioner may not operate correctly if any switches other than those specified are changed.
DIP-SW4
123
OFF OFF
ON OFF
DIP-SW4
123
OFF OFF
ON OFF
SW 1
123
O
SW 4
123
F
F
F
F
O
11
SPECIAL INSTALLATION
METHODS
CAUTION
(1) When setting the rotary switch and DIP switches, do
not touch any other parts on the circuit board directly with your bare hands.
(2) Be sure to turn off the main power.
1. GROUP CONTROL SYSTEM
A number of indoor units can be operated at the same time using a single remote controller.
(1) Wiring method (indoor unit to remote controller)
Indoor unit No. 0 Indoor unit No. 1 Indoor unit No. 2 Indoor unit No. 3
1 2 3
Remote controller wire
1 2 3
Remote controller
(2) Rotary switch setting (indoor unit)
Set the unit number of each indoor unit using the rotary switch on the indoor unit circuit board. The rotary switch is normally set to 0.
(3) DIP switch setting (remote controller)
Change DIP switch No. 3 on the remote controller from OFF to ON.
Indoor unit
Rotary Switch
2. DUAL REMOTE CONTROLLERS (OPTIONAL)
Two separate remote controllers can be used to operate the indoor units.
(1) Wiring method (indoor unit to remote controller)
Remote controller wire
(2) DIP switch setting (remote controller)
Set the remote controller DIP switch Nos. 1 and 2 according to the following table.
Number of remote controllers
1 (Normal)
2 (Dual)
Number of remote controllers
1 (Normal)
2 (Dual)
DIP-SW No. 1
DIP-SW No. 1 DIP-SW No. 2
1 2 3 1 2 3 1 2 3
Remote controller
1 2 3 4 5 6
DIP Switch
Indoor unit
1 2 3
1 2 3
Master unit
Master unit
ON
OFF
Slave unit
ON
Remote controller
DIP-SW No. 2
OFF
OFF
ON
ONOFF
ON
1 2 3
Slave unit
Remote controller
1 2 3 4 5 6
DIP Switch
3. AUTO RESTART
When the air conditioner power was temporarily turned off by a power failure etc., it restarts automatically after the power recovers. (Operated by setting before the power failure)
The auto restart function can be canceled.
(1) DIP switch setting (indoor unit)
Change the DIP switch (SW1-1) on the indoor unit circuit board from ON to OFF. The auto restart function will be canceled.
Indoor unit
123
OFF
OFF
SW1
DIP Switch
123
OFF
SW4
[DIP-SWITCH SETTING]
Indoor unit
NO.
1 Invalidity Validity ✽ Auto restart setting
DIP-Switch 1
2 ——✽ Temperature correction
3 ——✽ setting for heating
1 ——Remote controller setting
DIP-Switch 4
2
3
Remote controller
NO.
1 Dual remote controller
2 setting
DIP-Switch
ONOFF
3
4
5 Invalidity Validity ✽ Auto changeover setting
6 Invalidity Validity Memory backup setting
SW state
OFF ON
Air flow setting
SW state
OFF ON
One unit
Multiple unit Group control setting
Heat & Cool model
Cooling only model
Model setting
PART NO. 9364658049
Detail
Detail
: Factory setting
Loading...