MODELS :
AU 12FBAB / AO 12FSAJ
AU 12UBAB / AO 12USAJL
AU 14FBAB / AO 14FSDJ
AU 14UBAB / AO 14USDJL
AU 18FBAB / AO 18FNCKL
CASSETTE TYPE
AU12-18
AU 18UBAB / AO 18UNCKL
AO 18UNCNL
FEATURES
Compact size
Compact grille fits European ceiling panel (650 x 650 mm).
Punch Hall grille
CASSETTE TYPE
AU12-18
650
650
(unit: mm)
Slim intake grille
Slim type intake grille can fit the ceiling after installation.
20
(unit: mm)
Detachable,washable filter and intake grille.
Intake grille and air filter can be removed easily and cleaned.
Long-life filter
- (02 - 01) -
Duct connection hole opening
Fresh air can be introduced through this opening.
Fresh air
CASSETTE TYPE
AU12-18
CASSETTE TYPE
AU12-18
Distribution
duct
Distribution
duct
Conditioned air can be distributed by means of a distribution duct.
One-way
Two-way
- (02 - 02) -
2-2.
REMOTE CONTROLLER
2-2-1. WIRELESS REMOTE CONTROLLER
FEATURES
Four kinds of timer setup (ON / OFF / PROGRAM / SLEEP) are possible.
Four kinds of timers. Easy operation.
CASSETTE TYPE
AU12-18
CASSETTE TYPE
AU12-18
Built-in timers
Easy to change transmission code (4 patterns) by button operation.
Select from four different timer programs (On/Off/Program/Sleep).
Program timer
The program timer operates the ON and OFF timer once within a 24 hour period.
Sleep timer
The sleep timer function automatically corrects the temperature thermostat setting according to the
time setting to prevent excessive cooling and heating while sleeping.
Cooling operation/dry operation
When the sleep timer is set, the set temperature
automatically rises 1 °C every hour. The set
temperature can rise up to a maximum of 2 °C.
Heating operation
When the sleep timer is set, the set temperature
automatically drops 1 °C every 30 minutes. The
set temperature can drop to a maximum of 4 °C.
Timer setting
60min.
1 °C
Simultaneously operation
After code change
Mixed-up
• Code selector switch eliminates unit
being wrongly switched.
(Up to 4 codes can be set.)
ABCD
AB
C
2 °C
D
•Wide and precise
transmitting range.
1 °C
2 °C
3 °C
4 °C
30min.
60min.
90min.
Timer setting
1. Press the MASTER CONTROL
button for more than five seconds
to start the code change.
2. Press the (+) or (-) button to
select the desired code.
A B C D
3. Press the MASTER CONTROL
button again to end the code
change.
- (02 - 03) -
FUNCTIONS
1
5
START/STOP button
Pressed to start and stop operation
64
Display
2
Set temp./Set time/
Set remote controller custom code buttons
Sets the indoor temp./ Sets the current time and on-off time.
/Sets R.C. custom code.
CASSETTE TYPE
AU12-18
3
2
9
10
1
7
11
12
8
3
Master control / Code change buttons
Selects the operating mode (AUTO, HEAT, FAN, COOL, DRY).
/Start / end R.C. custom code change. (Max 4 types)
4
Sleep timer button
Pressed to select sleep timer.
5
Signal transmitter
6
Timer button
CASSETTE TYPE
AU12-18
Pressed to select the timer mode. (OFF TIMER, ON TIMER,
PROGRAM TIMER, TIMER RESET)
7
Fan control button
Selects the fan speed (AUTO, LOW, MED, HIGH).
8
Battery compartment lid
9
Air flow direction set button
TEST
RUN
13
10
Time adjust button
Sets the current time.
Display panel
14
15
16
17
18
19
20
21
11
Air flow direction swing button
12
ACL button
Used when replacing batteries or change the code.
13
Test run button
Used when testing the air conditioner after installation.
14
Transmit indicator
15
Clock display
16
Master control display
17
Timer mode display
18
Fan speed display
19
Set temperature display
20
Timer set indicator
21
Temperature set indicator
SPECIFICATION
SIZE (H x W x D mm)160 x 56 x 20
WEIGHT ( g )120
ACCESSORYHolder
- (02 - 04) -
2-3. SPECIFICATIONS
AU 12FBABAU 14FBABAU 18FBABAU 12UBA B AU 14UBABAU 18UBAB
AO 12FSAJAO 14FSDJAO 18FNCKLAO 12USAJL AO 14USDJLAO 18UNCKL
Note:S pecifications are based on the following conditions.
Cooling:Indoor temperature of 27 °CDB / 19 °CWB,and outdoor temperature of 35 °CDB/24 °CWB.
Heating:Indoor temperature of 20 °CDB / 15 °CWB ,and outdoor temperature of 7 °CDB/6 °CWB.
Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
COOLING0 to 43
HEATING
mm
- (02 - 05) -
2-4. DIMENSIONS
2-4-1. OUTDOOR UNIT
MODELS : AO 12F, AO 12U, AO 14F, AO 14U
250
250
250
250
CASSETTE TYPE
AU12-18
100
100
100
100
60
60
60
60
95
95
95
95
(Unit : mm)
750
750
750
750
530
530
530
530
13
13
13
13
CASSETTE TYPE
AU12-18
285
285
285
285
Side viewFront view
MOUNTING POSITION
10 cm
or more
60 cm
or
more
60 cm
or more
60 cm
or more
10 cm
or more
540
540
540
540
- (02 - 06) -
MODELS : AO 18F, AO 18U
(Unit : mm)
CASSETTE TYPE
AU12-18
Top view
CASSETTE TYPE
AU12-18
830
650
12
Front view
Bottom
Air flow
343
350
320
Side view
154
101
58
90
MOUNTING POSITION
When there are obstacles at the
back or front sides.
100 mm
or more
600 mm
or more
Bottom view
100 mm
or more
603
When there are obstacles at the
back, side(s), and top.
600 mm or more
300 mm
25
(
S
0 mm o
er
v
i
c
r
more
e s
p
ac
e)
or more
When there are obstacles at the
back, side with the installation of
more than one unit.
250 mm
or more
250 mm
or more
300 mm
or more
- (02 - 07) -
2-4-2. INDOOR UNIT
MODELS : AU 12F, AU 12U, AU 14F, AU 14U, AU 18F, AU 18U
*1) Wiring Spec : Selected Sample (Selected based on Japan Electrotechnical Standard and Codes Committee E0005)
*2) Limited Wiring length : This is the wiring length in case voltage descent is less than 2%.
W hen the wiring length becomes long, please select the wiring of a more larger diameter.
CurrentA5.56.38.55.55.46.36.38.29.2
InputkW1.241.391.901.241.211.401.421.852.00
A7.08.010.07.06.58.07.510.011.0
A303139303031313939
A151520
Power Cable
*2) Limited wiring length
InputkW0.0400.0400.050
Full Load Amp.A0.170.170.20
InputkW0.0570.0570.148
Full Load Amp.A0.240.240.73
CASSETTE TYPE
AU12-18
- (02 - 38) -
2-14. SAFETY DEVICE
PROTECTION FORM
AO 12FAO 14FAO 18FAO 12UAO 14UAO 18U
FUSE
(SIDE OF INDOOR UNIT)
-
FAN MOTOR PROTECTORTHERMAL PROTECTOR140±5°C OFF140±5°C OFF150±5°C OFF140±5°C OFF140±5°C OFF150±5°C OFF
COMPRESSOR THERMAL PROTECTOR
OFF 150±5°C
(23.5A/25°C)
(9.6A/80°C)
ON 69±11°C
OFF 160±5°C
(25.5A/25°C)
(10.7A/80°C)
ON 69±11°C
OFF 150±5°C
(30A/25°C)
(13A/80°C)
ON 69±11°C
OFF 150±5°C
(23.5A/25°C)
(9.6A/80°C)
ON 69±11°C
OFF 160±5°C
(25.5A/25°C)
(10.7A/80°C)
ON 69±11°C
OFF 150±5°C
(30A/25°C)
(13A/80°C)
ON 69±11°C
5A 250V
PROTECTION FORM
AU 12FAU 14FAU 18FAU 12UAU 14UAU 18U
PCB FUSE-
FAN MOTOR PROTECTORTHERMAL PROTECTOR
3.15A 250V
140±5°C OFF
OUTDOOR UNIT
CASSETTE TYPE
AU12-18
INDOOR UNIT
CASSETTE TYPE
AU12-18
- (02 - 39) -
2-15. FUNCTION SETTING
Auto restart validity/invalidity
Room temperature correct coefficient
Room temperature correct coefficient
Forbidden
Remote control unit single code
Remote control unit single code
INDOOR UNIT
DIP SW
3
JM3
SW 1
Jumper Wire
JM1
JM212
2-15-1. INDOOR UNIT
CASSETTE TYPE
AU12-18
SWITCH POSITION
Indoor unit control circuit board
CASSETTE TYPE
AU12-18
JM1
JM3
JM2
CN10
- (02 - 40) -
SW 1-1
SW state
OFF
Invalidity
ON
Validity
Jumper wire
JM3
Remote control unit signal code
connect
connect
A
JM2
Disconnect
Disconnect
Disconnect
connect
connectBC
D
Disconnect
2-15-2. SWITCH FUNCTION (INDOOR UNIT)
0 deg
0 deg
0 deg
cooling
-2 deg
SW 1-2
SW 1-3
0 deg
heating
dry
-2 deg
-2 degONONONOFF
OFF
+2 deg
-2 deg
OFF
SW state
-2 deg
OFF
ON
0 deg
+4 deg
DIP SWITCH SETTING
SW1-1. Auto restart setting
Auto restart function can be selected by turning this switch ON/OFF.
AUTO RESTART SETTING
CASSETTE TYPE
AU12-18
SW1-2, 1-3. Room temperature correct coefficient of heating.
Decide the heating temperature correct coefficient vale of heating.
TEMPERATURE CORRECTION
(Factory setting)
(Factory setting)
CASSETTE TYPE
AU12-18
JUMPER WIRE SETTING
JM 1, 2, 3 setting
(Factory setting)
- (02 - 41) -
2-16. OPTIONAL PARTS
ADDITIONAL GRILLE
UTG-AGDA-W
The additional grille hides the gap between the ceiling hole
and the outlet grille.
Additional grille (optional parts)
CASSETTE TYPE
AU12-18
Additonal grille
The ceiling hole
CASSETTE TYPE
AU12-18
Indoor Unit(grille)
- (02 - 42) -