MODELS :
AU 12FBAB / AO 12FSAJ
AU 12UBAB / AO 12USAJL
AU 14FBAB / AO 14FSDJ
AU 14UBAB / AO 14USDJL
AU 18FBAB / AO 18FNCKL
CASSETTE TYPE
AU12-18
AU 18UBAB / AO 18UNCKL
AO 18UNCNL
FEATURES
Compact size
Compact grille fits European ceiling panel (650 x 650 mm).
Punch Hall grille
CASSETTE TYPE
AU12-18
650
650
(unit: mm)
Slim intake grille
Slim type intake grille can fit the ceiling after installation.
20
(unit: mm)
Detachable,washable filter and intake grille.
Intake grille and air filter can be removed easily and cleaned.
Long-life filter
- (02 - 01) -
Duct connection hole opening
Fresh air can be introduced through this opening.
Fresh air
CASSETTE TYPE
AU12-18
CASSETTE TYPE
AU12-18
Distribution
duct
Distribution
duct
Conditioned air can be distributed by means of a distribution duct.
One-way
Two-way
- (02 - 02) -
2-2.
REMOTE CONTROLLER
2-2-1. WIRELESS REMOTE CONTROLLER
FEATURES
Four kinds of timer setup (ON / OFF / PROGRAM / SLEEP) are possible.
Four kinds of timers. Easy operation.
CASSETTE TYPE
AU12-18
CASSETTE TYPE
AU12-18
Built-in timers
Easy to change transmission code (4 patterns) by button operation.
Select from four different timer programs (On/Off/Program/Sleep).
Program timer
The program timer operates the ON and OFF timer once within a 24 hour period.
Sleep timer
The sleep timer function automatically corrects the temperature thermostat setting according to the
time setting to prevent excessive cooling and heating while sleeping.
Cooling operation/dry operation
When the sleep timer is set, the set temperature
automatically rises 1 °C every hour. The set
temperature can rise up to a maximum of 2 °C.
Heating operation
When the sleep timer is set, the set temperature
automatically drops 1 °C every 30 minutes. The
set temperature can drop to a maximum of 4 °C.
Timer setting
60min.
1 °C
Simultaneously operation
After code change
Mixed-up
• Code selector switch eliminates unit
being wrongly switched.
(Up to 4 codes can be set.)
ABCD
AB
C
2 °C
D
•Wide and precise
transmitting range.
1 °C
2 °C
3 °C
4 °C
30min.
60min.
90min.
Timer setting
1. Press the MASTER CONTROL
button for more than five seconds
to start the code change.
2. Press the (+) or (-) button to
select the desired code.
A B C D
3. Press the MASTER CONTROL
button again to end the code
change.
- (02 - 03) -
FUNCTIONS
1
5
START/STOP button
Pressed to start and stop operation
64
Display
2
Set temp./Set time/
Set remote controller custom code buttons
Sets the indoor temp./ Sets the current time and on-off time.
/Sets R.C. custom code.
CASSETTE TYPE
AU12-18
3
2
9
10
1
7
11
12
8
3
Master control / Code change buttons
Selects the operating mode (AUTO, HEAT, FAN, COOL, DRY).
/Start / end R.C. custom code change. (Max 4 types)
4
Sleep timer button
Pressed to select sleep timer.
5
Signal transmitter
6
Timer button
CASSETTE TYPE
AU12-18
Pressed to select the timer mode. (OFF TIMER, ON TIMER,
PROGRAM TIMER, TIMER RESET)
7
Fan control button
Selects the fan speed (AUTO, LOW, MED, HIGH).
8
Battery compartment lid
9
Air flow direction set button
TEST
RUN
13
10
Time adjust button
Sets the current time.
Display panel
14
15
16
17
18
19
20
21
11
Air flow direction swing button
12
ACL button
Used when replacing batteries or change the code.
13
Test run button
Used when testing the air conditioner after installation.
14
Transmit indicator
15
Clock display
16
Master control display
17
Timer mode display
18
Fan speed display
19
Set temperature display
20
Timer set indicator
21
Temperature set indicator
SPECIFICATION
SIZE (H x W x D mm)160 x 56 x 20
WEIGHT ( g )120
ACCESSORYHolder
- (02 - 04) -
2-3. SPECIFICATIONS
AU 12FBABAU 14FBABAU 18FBABAU 12UBA B AU 14UBABAU 18UBAB
AO 12FSAJAO 14FSDJAO 18FNCKLAO 12USAJL AO 14USDJLAO 18UNCKL
Note:S pecifications are based on the following conditions.
Cooling:Indoor temperature of 27 °CDB / 19 °CWB,and outdoor temperature of 35 °CDB/24 °CWB.
Heating:Indoor temperature of 20 °CDB / 15 °CWB ,and outdoor temperature of 7 °CDB/6 °CWB.
Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
COOLING0 to 43
HEATING
mm
- (02 - 05) -
2-4. DIMENSIONS
2-4-1. OUTDOOR UNIT
MODELS : AO 12F, AO 12U, AO 14F, AO 14U
250
250
250
250
CASSETTE TYPE
AU12-18
100
100
100
100
60
60
60
60
95
95
95
95
(Unit : mm)
750
750
750
750
530
530
530
530
13
13
13
13
CASSETTE TYPE
AU12-18
285
285
285
285
Side viewFront view
MOUNTING POSITION
10 cm
or more
60 cm
or
more
60 cm
or more
60 cm
or more
10 cm
or more
540
540
540
540
- (02 - 06) -
MODELS : AO 18F, AO 18U
(Unit : mm)
CASSETTE TYPE
AU12-18
Top view
CASSETTE TYPE
AU12-18
830
650
12
Front view
Bottom
Air flow
343
350
320
Side view
154
101
58
90
MOUNTING POSITION
When there are obstacles at the
back or front sides.
100 mm
or more
600 mm
or more
Bottom view
100 mm
or more
603
When there are obstacles at the
back, side(s), and top.
600 mm or more
300 mm
25
(
S
0 mm o
er
v
i
c
r
more
e s
p
ac
e)
or more
When there are obstacles at the
back, side with the installation of
more than one unit.
250 mm
or more
250 mm
or more
300 mm
or more
- (02 - 07) -
2-4-2. INDOOR UNIT
MODELS : AU 12F, AU 12U, AU 14F, AU 14U, AU 18F, AU 18U
(Unit : mm)
20
35
CASSETTE TYPE
AU12-18
440
650
650
Bottom view (Panel)
580
Bottom view
235
CASSETTE TYPE
AU12-18
66
580
245
Side view
(Grille measurement)
( 650)
650
(Hanging bolt position)
400
60
47
111
131
440
606
(Hanging bolt position)
Top view
66
46
86
(Ceiling opening measurement)
Drain pipe(I.D. 32)
600
245
54
- (02 - 08) -
MOUNTING POSITION
Floor
Strong and durable ceiling
250 mm
CASSETTE TYPE
AU12-18
or more
CASSETTE TYPE
AU12-18
1,000 mm
2,300 mm
or more
(4 directions)(3 directions)
Piping position
or more
Obstruction
100 or more100 or more
1,000 mm
or more
100 or more
(2 directions)(2 directions)
100 or more
- (02 - 09) -
2-5. REFRIGERANT CIRCUIT
MODELS : AU 12F / AO 12F
Refrigerant pipe
OUTDOOR UNITINDOOR UNIT
6.35mm(1/4")
CASSETTE TYPE
AU12-18
Evaporator
Capillary tube
Strainer
Condenser
CASSETTE TYPE
AU12-18
Refrigerant pipe
9.52mm(3/8")
Charging valve
Compressor
MODELS : AU 12U / AO 12U
INDOOR UNIT
Refrigerant pipe
6.35mm(1/4")
Evaporator
Refrigerant pipe
9.52mm(3/8")
OUTDOOR UNIT
Strainer
Capillary
tube
Compressor
Strainer
Condenser
Muffler
4-Way
valve
Cooling
Heating
: Flare coupling
Charging valve
- (02 - 10) -
MODELS : AU 14F / AO 14F
Refrigerant pipe
OUTDOOR UNITINDOOR UNIT
6.35mm(1/4")
CASSETTE TYPE
AU12-18
Capillary tube
Strainer
CASSETTE TYPE
AU12-18
Evaporator
Condenser
Refrigerant pipe
12.7mm(1/2")
Charging valve
Compressor
MODELS : AU 14U / AO 14U
INDOOR UNIT
Refrigerant pipe
6.35mm(1/4")
Evaporator
Refrigerant pipe
12.7mm(1/2")
OUTDOOR UNIT
Strainer
Muffler
4-Way
valve
CapillAR
tube
Compressor
Strainer
Condenser
Strainer
Cooling
Heating
: Flare coupling
Charging valve
- (02 - 11) -
MODELS : AU 18F / AO 18F
Refrigerant pipe
OUTDOOR UNITINDOOR UNIT
6.35mm(1/4")
CASSETTE TYPE
AU12-18
Capillary tube
Strainer
CASSETTE TYPE
AU12-18
Condenser
Evaporator
Refrigerant pipe
12.7mm(1/2")
Charging valve
Compressor
MODELS : AU 18U / AO 18U
INDOOR UNIT
Refrigerant pipe
6.35mm(1/4")
Evaporator
Evaporator
Refrigerant pipe
12.7mm(1/2")
Charging valve
OUTDOOR UNIT
Strainer
Compressor
4-Way
valve
Capillary tube
Strainer
Distributor
Condenser
Muffler
Cooling
Heating
- (02 - 12) -