Floor Console/Under Ceiling Dual Type
INSTALLATION
INSTRUCTION SHEET
(PART NO. 9374318346)
For authorized service personnel only.
DANGER
WARNING
CAUTION
Never touch electrical components immediately after the power supply has been turned off. Electrical shock may occur. After
turning off the power, always wait 5 minutes or more before touching electrical components.
The basic installation work procedures are the same as conventional refrigerant models.
However, pay careful attention to the following points:
1 Since the working pressure is 1.6 times higher than that of conventional refrigerant models, some of the piping and
installation and service tools are special. (See the table below.)
Especially, when replacing a conventional refrigerant model with a new refrigerant R410A model, always replace the
conventional piping and flare nuts with the R410A piping and flare nuts.
2 Models that use refrigerant R410A have a different charging port thread diameter to prevent erroneous charging with
conventional refrigerant and for safety. Therefore, check beforehand. [The charging port thread diameter for R410A is
1/2 UNF 20 threads per inch.]
3 Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with refrigerant models. Also, when
storing the piping, securely seal the openings by pinching, taping, etc.
4 When charging the refrigerant, take into account the slight change in the composition of the gas and liquid phases, and
always charge from the liquid phase side whose composition is stable.
Special tools for R410A
Tool name
Gauge manifold
Charge hose
Vacuum pump
Gas leakage detector
Copper pipes
It is necessary to use seamless copper pipes and it is desirable that the
amount of residual oil is less than 40 mg/10 m. Do not use copper pipes
having a collapsed, deformed or discolored portion (especially on the interior
surface). Otherwise, the expansion valve or capillary tube may become
blocked with contaminants.
As an air conditioner using R410A incurs pressure higher than when
using conventional refrigerant, it is necessary to choose adequate materials.
Thicknesses of copper pipes used with R410A are as shown in the table.
Never use copper pipes thinner than that in the table even when it is
available on the market.
This mark indicates procedures which, if improperly performed, are most likely to result in the death of or
serious injury to the user or service personnel.
This mark indicates procedures which, if improperly performed, might lead to the death or serious injury of
the user.
This mark indicates procedures which, if improperly performed, might possibly result in personal harm to
the user, or damage to property.
DANGER
This air conditioner uses new refrigerant HFC (R410A).
Pressure is high and cannot be measured with a conventional gauge. To prevent erroneous mixing of other
refrigerants, the diameter of each port has been changed.
It is recommended the gauge with seals –0.1 to 5.3 MPa (–76 cmHg to 53 kgf/cm
3.8 MPa (–76 cmHg to 38 kgf/cm
To increase pressure resistance, the hose material and base size were changed.
A conventional vacuum pump can be used by installing a vacuum pump adapter.
Special gas leakage detector for HFC refrigerant R410A.
2
) for low pressure.
Contents of change
2
) for high pressure. –0.1 to
Thicknesses of Annealed Copper Pipes (R410A)
Pipe outside diameter
6.35 mm (1/4 in.)
9.52 mm (3/8 in.)
12.70 mm (1/2 in.)
15.88 mm (5/8 in.)
19.05 mm (3/4 in.)
Thickness
0.80 mm
0.80 mm
0.80 mm
1.00 mm
1.20 mm
WARNING
1 For the air conditioner to operate satisfactorily, install it as outlined in this installation instruction sheet.
2 Connect the indoor unit and outdoor unit with the air conditioner piping and cords available from our standards parts. This instal-
lation instruction sheet describes the correct connections using the installation set available from our standard parts.
3 Installation work must be performed in accordance with national wiring standards by authorized personnel only.
4 Do not turn on the power until all installation work is complete.
CAUTION
This installation instruction sheet describes how to the indoor unit only.
To install the outdoor unit, refer to the installation instruction sheet included with the outdoor unit.
••
• Be careful not to scratch the air conditioner when handling it.
••
••
• After installation, explain correct operation to the customer, using the operating manual.
••
••
• Let the customer keep this installation instruction sheet because it is used when the air conditioner is serviced or moved.
••
CONNECTION PIPE REQUIREMENT
CAUTION
Refer to the installation instruction sheet of the outdoor unit for description of the length of connecting pipe or for difference of
its elevation.
MODEL
Diameter
••
• Use pipe with water-resistant heat insulation.
••
Liquid
Gas
14,000, 18,000 24,000
BTU/h model BTU/h model
6.35 mm (1/4 in.) 6.35 mm (1/4 in.)
12.70 mm (1/2 in.) 15.88 mm (5/8 in.)
CAUTION
Install heat insulation around both the gas and liquid pipes. Failure to do so may cause water leaks.
Use heat insulation with heat resistance above 120 °C. (Reverse cycle model only)
In addition, if the humidity level at the installation location of the refrigerant piping is expected to exceed 70%, install heat
insulation around the refrigerant piping. If the expected humidity level is 70-80%, use heat insulation that is 15 mm or thicker and
if the expected humidity exceeds 80%, use heat insulation that is 20 mm or thicker.
If heat insulation is used that is not as thick as specified, condensation may form on the surface of the insulation.
In addition, use heat insulation with heat conductivity of 0.045 W/(m·K) or less (at 20 °C).
ELECTRICAL REQUIREMENT
Connection cord (mm2)
MAX.
2.5
••
• Use conformed cord with Type 245 IEC57.
••
••
• Install all electrical works in accordance to the standard.
••
••
• Install the disconnect device with a contact gap of at least 3 mm in all poles nearby the units. (Both indoor unit and outdoor unit)
••
MIN.
1.5
INSTALLATION PROCEDURE
Install the room air conditioner as follows:
1
1. REMOVE THE INTAKE GRILLE
Open the intake grille and remove the three screws.
Remark: The main unit can be wired before the indoor unit is in-
2
A. FLOOR CONSOLE TYPE
1. DRILLING FOR PIPING
Select piping and drain directions.
The piping and drain can be made in three directions as shown below.
For direction , bore the oval hole shown in the above figure.
The drain hose can be connected to either the left or right side.
When the directions are selected, drill a 10 cm (4") dia. hole on the wall so
that the hole is tilted downward toward the outdoor for smooth water flow.
When the pipe is led out from the rear, make a hole as shown in the figure,
at the position shown.
PREPARING INDOOR UNIT
INSTALLATION
Machine screw
Tapping screw
Intake grille
stalled. Select the most appropriate installation order.
Tapping screw
INDOOR UNIT INSTALLATION
VIEW
Drain hose
(Left side)
Wall
100 mm (4")
Indoor side
6 mm (1/4")
Outdoor side
Drain hose
(Right side)
Hole
When installing set to wall install the accessory wall bracket at the position as shown in the figure, and mount the set to it.
65.5 cm (26")
53 cm (21")
4.5 cm (1-3/4")
99 cm (39")
50 cm (20")
6.5 cm (2-1/2")
10 cm (4") hole
5 cm (2") hole
12.5 cm (5") 10 cm (4")
24.5 cm
9-5/8"
(
)
Wall bracket
Side of set
6.5 cm (2-1/2")
2. INSTALLING THE DRAIN HOSE
Select whether the drain hose will be connected to the left or right side.
Insert the drain hose into the drain pan, then secure the drain hose with a
nylon fastener.
Drain pan
Nylon fastener
Drain hose
Wrap the insulation (drain hose) around the drain hose connection.
Drain pan
Insulation (Drain hose)
Drain hose
Be sure to arrange the drain hose so that it is leveled lower than the drain
hose connecting port of the indoor unit.
Arrange the drain
hose lower than
this portion.
Do not install the unit so that the drain hose side is too
high. Height A should be less than 5 mm.
Drain hose
CAUTION
Drain hose
B. UNDER CEILING TYPE
Using the installation template, drill holes for piping and anchor bolts (for
holes).
900 mm (35-7/16")
Drilling position
200 mm
(7-7/8")
Installation
template
Drilling position
for piping
1. DRILLING FOR PIPING
Select piping and drain directions.
Top
Rear
(Install the drain hose in this direction.)
Right
Hole
For direction , bore the oval hole shown in the above figure.
CAUTION
Install the drain hose at the rear; it should not be installed
on the top or right side.
When the directions are selected, drill 80 mm (3-1/8") and 50 mm (2") or
150 mm (6") dia. hole on the wall so that the hole is tilted downward toward the outdoor for smooth water flow.
Wall
6 mm (1/4")
Indoor side Outdoor side
2. DRILLING HOLES FOR ANCHOR BOLTS AND
INSTALLING THE ANCHOR BOLTS
With a concrete drill, drill four 12.7 mm (1/2") dia. holes.
ø12.7 mm (1/2")
Insert the anchor bolts into the drilled holes, and drive the pins completely
into the anchor bolts with a hammer.
for anchor bolt
Ceiling
Wall
VIEW
60 to 70 mm
(2-3/8" to 2-3/4")
3. INSTALLING BRACKETS
Install the brackets with nuts, washers and spring washers.
Bracket (Left)
Spring
washer
Special nut
Bracket
Bracket (Right)
4. INSTALLING INDOOR UNIT
Reset the hex bolts as shown in the figure.
Hex bolt
Indoor unit
Apply the indoor unit to the brackets.
Bolt
Indoor unit
Now, securely tighten the hex bolts in both sides.
8 to 13 mm
(5/16" to 1/2")
Bracket
5. INSTALLING THE DRAIN HOSE
Select whether the drain hose will be connected to the left or right side.
Insert the drain hose into the drain pan, then secure the drain hose with a
nylon fastener.
Wrap the insulation (drain hose) around the drain hose connection.
Be sure to arrange the drain hose so that it is leveled lower than the drain
hose connecting port of the indoor unit.
Remove the hole cover.
Arrange the drain hose
lower than this portion.
When drain hose is arranged backward.
Secure the drain hose with the VT wire.
VT wire
hole
Pass the drain hose
through here.
Cut the grille
Drain hose
Base (Bottom)
Intake grille
VT wire
Drain hose
STANDARD PARTS
The following installation parts are furnished. Use them as required.
INDOOR UNIT ACCESSORIES
Name and Shape
Cover plate (left)
Cover plate (right)
Tapping screw (ø4 × 10)
Installation template
Bracket (left)
Bracket (right)
Anchor bolt (M12)
Spring washer
Special nut
Wall bracket
Tapping screw (ø4 × 20)
Coupler heat insulator
(large)
Coupler heat insulator
(small)
Q’ty
1
1
2
1
1
1
4
4
4
2
6
1
1
Application
For positioning the indoor
unit
For under ceiling type
For suspending the indoor
unit from ceiling
For suspending the indoor
unit on the wall
For fixing the wall bracket
For indoor side pipe joint
(Large pipe)
For indoor side pipe joint
(Small pipe)
Name and Shape
Drain hose
Insulation (drain hose)
VT wire
Remote control unit
Battery (penlight)
Remote control unit holder
Tapping screw
(ø3 × 12)
Q’ty
1
Adhesive type 70 × 230
1
For fixing the drain hose
1
L 280 mm
Use for air conditioner
operation
1
For remote control unit
2
Use as remote control unit
holder
1
For remote control unit
holder installation
2
OPTIONAL PARTS
The following options are available.
• WIRED REMOTE CONTROLLER: UTB–*UD
Application
SELECTING THE MOUNTING POSITION
WARNING
Install at a place that can withstand the weight of the indoor and outdoor units and install positively so that the units will not
topple or fall.
CAUTION
1 Do not install where there is the danger of combustible gas leakage.
2 Do not install near heat sources.
3 If children under 10 years old may approach the unit, take preventive measures so that they cannot reach the unit.
Decide the mounting position with the customer as follows:
INDOOR UNIT
(1) Install the indoor unit level on a strong wall, floor, ceiling which is not subject to vibration.
(2) The inlet and outlet ports should not be obstructed : the air should be able to blow all over the room.
(3) Install the unit near an electric outlet or special branch circuit.
(4) Do not install the unit where it will be exposed to direct sunlight.
(5) Install the unit where connection to the outdoor unit is easy.
(6) Install the unit where the drain pipe can be easily installed.
(7) Take servicing, etc., into consideration and leave the spaces as shown in the figure. Also install the unit where the filter can be removed.
••
• Floor console
••
30 cm (12") or more 30 cm (12") or more
Floor console
Indoor unit
Left
Right
To outdoor unit
••
• Under ceiling
••
Left
15 cm (6") or more 30 cm (12") or more
Ceiling
Indoor unit
Ceiling
230 cm (90-1/2")
or more
Floor
2 cm (3/4")
or more
Under ceiling
Indoor unit
Right
3
CONNECTING THE PIPE
CAUTION
1 Do not use mineral oil on flared part. Prevent mineral
oil from getting into the system as this would reduce
the lifetime of the units.
2 While welding the pipes, be sure to blow dry nitrogen
gas through them.
3 The maximum lengths of this product are shown in the
table. If the units are further apart than this, correct
operation can not be guaranteed.
1. FLARING
(1) Cut the connection pipe to the necessary length with a pipe cutter.
(2) Hold the pipe downward so that cuttings will not enter the pipe and
remove the burrs.
(3) Insert the flare nut (always use the flare nut attached to the indoor
and outdoor units respectively) onto the pipe and perform the flare
processing with a flare tool.
Use the special R410A flare tool, or the conventional flare tool.
Check if [L] is flared uniformly
and is not cracked or scratched.
Die
A
Pipe
Pipe outside diameter
6.35 mm (1/4 in.)
9.52 mm (3/8 in.)
12.70 mm (1/2 in.)
15.88 mm (5/8 in.)
19.05 mm (3/4 in.)
Pipe outside diameter
6.35 mm (1/4 in.)
9.52 mm (3/8 in.)
12.70 mm (1/2 in.)
15.88 mm (5/8 in.)
19.05 mm (3/4 in.)
When using conventional flare tools to flare R410A pipes, the dimension
A should be approximately 0.5 mm more than indicated in the table (for
flaring with R410A flare tools) to achieve the specified flaring. Use a thickness gauge to measure the dimension A.
Width across
flats
Pipe outside
diameter
6.35 mm (1/4 in.)
9.52 mm (3/8 in.)
12.70 mm (1/2 in.)
15.88 mm (5/8 in.)
19.05 mm (3/4 in.)
Dimension A
Flare tool for R410A, clutch type
Dimension B
Width across flats
(mm)
0 to 0.5
0
(mm)
-0.4
9.1
13.2
16.6
19.7
24.0
of Flare nut
17 mm
22 mm
26 mm
29 mm
36 mm
2. BENDING PIPES
The pipes are shaped by your hands. Be careful not to collapse them.
Do not bend the pipes in an angle more than 90°.
When pipes are repeatedly bend or stretched, the material will harden,
making it difficult to bend or stretch them any more. Do not bend or stretch
the pipes more than three times.
CAUTION
1 To prevent breaking of the pipe, avoid sharp bends.
Bend the pipe with a radius of curvature of 150 mm or
over.
2 If the pipe is bent repeatedly at the same place, it will
break.
6.35 mm (1/4 in.) dia.
9.52 mm (3/8 in.) dia.
12.70 mm (1/2 in.) dia.
15.88 mm (5/8 in.) dia.
19.05 mm (3/4 in.) dia.
Do not remove the cap from the connection pipe before connecting
the pipe.
Be sure to connect the gas pipe after connecting the
Flare nut tightening torque
Flare nut Tightening torque
16 to 18 N·m (160 to 180 kgf·cm)
30 to 42 N·m (300 to 420 kgf·cm)
49 to 61 N·m (490 to 610 kgf·cm)
63 to 75 N·m (630 to 750 kgf·cm)
90 to 110 N·m (900 to 1100 kgf·cm)
CAUTION
4
BARRIER AND RFM BASE
REMOVAL
BARRIER AND RFM BASE REMOVAL
AND INSTALLATION
(1) Remove the barriers by removing the 4 fixing screws (2 screws each).
(2) Remove the RFM base by removing the 2 fixing screws and unhooking
the 1 hook.
(3) After completing the work, install the barriers and RFM base as they
were originally.
liquid pipe completely.
3. CONNECTION PIPES
(1) Centering the pipe against port on the indoor unit, turn the flare nut
with your hand.
Be sure that the small pipe is completely installed before connecting
the large the pipe.
CAUTION
Be sure to apply the pipe against the port on the indoor
B
unit correctly. If the centering is improper, the flare nut
cannot be tightened smoothly. If the flare nut is forced to
turn, the threads will be damaged.
(2) Install the outdoor unit wall cap (supplied with the optional installation
set or procured at the site) to the wall hole pipe.
(3) Connect the outdoor unit and indoor unit piping.
(4) After matching the center of the flare surface and tightening the nut
hand tight, tighten the nut to the specified tightening torque with a
torque wrench.
Tighten with two wrenches.
Wrench (fixed)
Torque wrench
Indoor unit
pipe
Flare nut
Connection pipe
To prevent gas leakage,
coat the flare surface with
alkylbenzene oil (HAB).
Do not use mineral oil.
4. HEAT INSULATION ON THE PIPE JOINTS
(INDOOR SIDE ONLY)
Put coupler heat insulator on the joints (indoor side only).
Indoor unit
No gap
Coupler heat
insulator
(large)
Gas pipe Liquid pipe
No gap
Coupler heat
insulation
Coupler heat
insulator (small)
Be sure to overlap
the insulation
Fixing screw
(2 positions)
Install the barriers in the correct direction.
Barrier
Fixing screw
(2 positions)
Hook
RFM base
Nylon fastener
For fixing the drain hose
1
To outdoor unit
(Continued to the next page)
45
ELECTRICAL WIRING
WARNING
1 Before starting work, check that power is not being
supplied to the indoor unit and outdoor unit.
2 Match the terminal board numbers and connection
cord colors with those of the outdoor unit.
Erroneous wiring may cause burning of the electric
parts.
3 Connect the connection cords firmly to the terminal
board. Imperfect installation may cause a fire.
4 Always fasten the outside covering of the connection
cord with the cord clamp. (If the insulator is chafed,
electric leakage may occur.)
5 Always connect the ground wire.
6 Install the remote controller wires so as not to be di-
rect touched with your hand.
HOW TO CONNECT WIRING TO THE
TERMINALS
For strand wiring
(1) Use crimp-type terminals with insulating sleeves as shown in the
figure below to connect to the terminal block.
(2) Securely crimp the crimp-type terminals to the wires using an ap-
propriate tool so that the wires do not come loose.
(3) Use the specified wires, connect them securely, and fasten them
so that there is no stress placed on the terminals.
(4) Use an appropriate screwdriver to tighten the terminal screws.
Do not use a screwdriver that is too small, otherwise, the screw
heads may be damaged and prevent the screws from being
properly tightened.
(5) Do not tighten the terminal screws too much, otherwise, the screws
may break.
(6) See the table below for the terminal screw tightening torques.
Crimp-type
Strip 10 mm
Screw with
special washer
Wire
Crimp-type terminal
Terminal board
Terminal block
M4 screw 1.2 to 1.8 N·m (12 to 18 kgf·cm)
Wire
Tighting torque
WARNING
Use crimp-type terminals and tighten the terminal
screws to the specified torques, otherwise, abnormal overheating may be produced and possibly
cause heavy damage inside the unit.
terminal
Sleeve
Screw with
special washer
Crimp-type
terminal
1. CONNECTION DIAGRAMS
Connection cord (to outdoor unit)
Control line
Power line
Indoor unit
side
Wired remote controller cord (option)
*
Black
White
Red
Indoor unit
side
Ground the remote controller ip it has a ground wire
*
2. CONNECTION CORD PREPARATION
Keep the earth wire longer than the other wires.
30 mm
Earth wire
60 mm or more
• Use a 4-core wire cord.
Power supply cord
or connection cord
3. CONNECTION OF WIRING
INDOOR UNIT SIDE
(1) Remove the electric component box.
Electric component box
Electric component box
RFM
Remove the four
tapping screws.
CAUTION
1 Do not remove the screws. If the stays
are removed, the electric component
box will fall.
2 If you use as “Floor console”, you must
remove screws and RFMs (2 positions).
Wires
Remove the clamp. Install the clamp.
(1) When removing the electric component box, remove the clamp from
the cables.
(2) After completing the work, fasten the cables as they were originally by
installing the clamp.
Clamp
(2) Pull out the electric component box.
Electric component box
(3) Remove the electric component box cover.
Base
Electric component box cover
Remove the three tapping screws.
CAUTION
Be careful not to pinch the lead wires between the electric
component box and base.
(4) Wiring
1 Remove the cord clamp.
2 Process the end of the connection cords to the dimensions as shown
in the figure.
3 Connect the end of the connection cord fully into the terminal block.
Wired remote
Cord clamp
4 Fasten the connection cord with a cord clamp.
5 Fasten the end of the connection cord with the screw.
controller cord
(option)
Cord clamp
Connection cord
(to outdoor unit)
CAUTION
Do not bundle the remote controller cord, or wire the remote controller cord in parallel, with the indoor unit connection wire (to the outdoor unit) and the power supply
cord. It may cause erroneous operation.
(5) Floor console/Under celing select switch
1 This unit was set for use as a ceiling type at the factory.
2 When using the unit as a floor type, perform the following settings in
FUNCTION SETTING. (Refer to 8 FUNCTION SETTING.)
Setting the Cooler Room Temperature Correction
Setting the Heater Room Temperature Correction
6
MOUNT THE COVER PLATE
→Setting Value “01”
→Setting Value “01”
AND THE INTAKE GRILLE
1. MOUNT THE COVER PLATE (RIGHT)
(1) Cut a pipe exit hole in the right plate. This is only when the pipe exits
from the right side. (This operation is not required when the protrusion
is on the top or rear.)
(2) Join the cover plates (right) and mount with the screw (ø4 × 10).
Cover plate (Right)
2. MOUNT THE COVER PLATE (LEFT)
Join the cover plates (left) and mount with the screw (ø4 × 10).
Cover plate (Left)
3. MOUNT THE INTAKE GRILLE
(1) Cut the right side of the intake grille. This is only when the pipe exits
from the right side.
(2) Insert the hinges on the bottom of the intake grille into the holes in the
base assembly. Then mount the arms to the three areas on the top of
the intake grille.
7
REMOTE CONTROLLER
SETTING
1. LOAD BATTERIES (R03/LR03
1 Press and slide the battery compartment lid on the reverse side to
open it.
Slide in the direction of the arrow while pressing the
2 Insert batteries.
Be sure to align the battery polarities (
3 Close the battery compartment lid.
××
× 2)
××
) correctly.
mark.
CAUTION
1 Take care to prevent infants from accidentally
swallowing batteries.
2 When not using the Remote Control Unit for an
extended period, remove the batteries to avoid
possible leakage and damage to the unit.
3 If leaking battery fluid comes in contact with your skin,
eyes, or mouth, immediately wash with copious
amounts of water, and consult your physician.
4 Dead batteries should be removed immediately and
disposed of properly, either in a battery collection
receptacle or to the appropriate authority.
5 Do not attempt to recharge dry batteries.
NOTES
• Never mix new and used batteries, or batteries of different types.
• Batteries should last about one year under normal use. If the Remote
Control Unit’s operating range becomes appreciably reduced, replace
the batteries and press the RESET button with the tip of a ballpoint pen
or other small object.
2. REMOTE CONTROL UNIT HOLDER INSTALLA-
TION
CAUTION
1 Check that the indoor unit correctly receives the sig-
nal from the remote control unit, then install the remote
control unit holder.
2 Select the remote control unit holder selection site by
paying careful attention to the following:
Avoid places in direct sunlight.
Select a place that will not be affected by the heat from
a stove, etc.
• Install the remote control unit with a distance of 7 m between the remote control unit and the photocell as the criteria. However, when installing the remote control unit, check that it operates positively.
• Install the remote control unit holder to a wall, pillar, etc. with the tapping screw.
1 Mount the Holder.
Screws
2 Set the Remote Control Unit.
Insert
Press in
3 To remove the Remote Control Unit (when use at hand).
Slide up
Pull out
8
• This procedure changes to the function settings used to control the
indoor unit according to the installation conditions. Incorrect settings
can cause the indoor unit malfunction.
• After the power is turned on, perform the “FUNCTION SETTING”
according to the installation conditions using the remote controller.
• The settings may be selected between the following two: Function
Number or Setting Value.
• Settings will not be changed if invalid numbers or setting values are
selected.
FUNCTION SETTING
Entering the Function Setting Mode
• While pressing the FAN button and SET TEMP. ( ) simultaneously,
press the RESET button to enter the function setting mode.
STEP 1
Selecting the Remote Control Unit Signal Code
Use the following steps to select the signal code of the remote control unit.
(Note that the air conditioner cannot receive a signal code if the air conditioner has not been set for the signal code.)
The signal codes that are set through this process are applicable only to
the signals in the FUNCTION SETTING. For details on how to set the
signal codes through the normal process, refer to SELECTING THE
REMOTE CONTROL UNIT SIGNAL CODE.
1 Press the SET TEMP. (
between .
Match the code on the display to the air conditioner signal code. (initially set to )
(If the signal code does not need to be selected, press the MODE
button and proceed to STEP 2.)
2 Press the TIMER MODE button and check that the indoor unit can
receive signals at the displayed signal code.
3 Press the MODE button to accept the signal code, and proceed to
STEP 2.
The air conditioner signal code is set to A prior to shipment.
Contact your retailer to change the signal code.
The remote control unit resets to signal code A when the batteries in
the remote control unit are replaced. If you use a signal code other
than signal code A, reset the signal code after replacing the
batteries.
If you do not know the air conditioner signal code setting, try each
of the signal codes (
operates the air conditioner.
) ( ) button to change the signal code
) until you find the code which
STEP 2
Selecting the Function Number and Setting Value
1 Press the SET TEMP. ( ) ( ) buttons to select the function number.
(Press the MODE button to switch between the left and right digits.)
2 Press the FAN button to proceed to setting the value.
(Press the FAN button again to return to the function number selection.)
3 Press the SET TEMP. (
(Press the MODE button to switch between the left and right digits.)
4 Press the TIMER MODE button, and START/STOP button, in the
order listed to confirm the settings.
5 Press the RESET button to cancel the function setting mode.
6 After completing the Function Setting, be sure to turn off the power
and turn it on again.
Function number
) ( ) buttons to select the setting value.
Setting value
CAUTION
After turning off the power, wait 10 seconds or more
before turning on it again.
The FUNCTION SETTING doesn’t become effective if it
doesn’t do so.
Setting the Ceiling Height
• Select the setting values in the table below according to the height of
the ceiling. (The unit is factory-set to “00”.)
Setting Description
Standard
High ceiling
When using floor console installation, don't need to change the setting value.
Function Number
20
Setting Value
00
01
Setting the Filter Sign
• The indoor unit has a sign to inform the user that it is time to clean the
filter.
• Select the time setting for the filter sign display interval in the table
below according to the amount of dust or debris in the room. (The unit
is factory-set to “00”.)
• If you do not wish the filter sign to be displayed, select the setting value
for “No indication”.
Setting Description
Standard
(400 hours)
Long interval
(1,000 hours)
Short interval
(200 hours)
No indication
Function Number
11
Setting Value
00
01
02
03
Setting the Cooler Room Temperature Correction
• Depending on the installed environment, the room temperature sensor
may require a correction. The settings may be selected as shown in the
table below. (The unit is factory-set to “00”.)
Setting Description
Standard
Lower control
When using floor console installation, change the setting value to “01”.
Function Number
30
Setting Value
Setting the Heater Room Temperature Correction
• Depending on the installed environment, the room temperature sensor
may require a correction. The settings may be changed as shown in the
table below. (The unit is factory-set to “00”.)
Setting Description
Standard
Lower control
Slightly warmer control
Warmer control
When using floor console installation, change the setting value to “01”.
Function Number
31
Setting Value
Setting Other Functions
• The following settings are also possible, depending on the operating
conditions. (The unit is factory-set to “00”.)
Auto Restart
Setting Description
Yes
No
Indoor Room Temperature Sensor Switching Function (Wired remote controller only)
Setting Description
No
Yes
• If setting value is “00”, room temperature is controlled by the indoor unit
temperature sensor.
• If setting value is “01”, room temperature is controlled by either indoor
unit temperature sensor or remote control unit sensor.
Function Number
40
Function Number
42
Setting Value
Setting Value
Setting record
• Record any changes to the settings in the following table.
Setting
Ceiling height
Filter sign
Cooler room temperature
correction
Heater room temperature
correction
Auto restart
Indoor room temperature
sensor switching function
After completing the FUNCTION SETTING, be sure to turn off the power
and turn it on again.
Setting Value
9
SELECTING THE REMOTE
CONTROL UNIT SIGNAL CODE
When two or more air conditioners are installed in a room and the remote
control unit is operating an air conditioner other than the one you wish to
00
01
00
01
02
03
00
01
00
01
set, change the signal code of the remote control unit to operate only the
air conditioner you wish to set (four selections possible).
When two or more air conditioners are installed in a room, please contact
your retailer to set the individual air conditioner signal codes.
• Confirm the setting of the remote control unit signal code and the printed
circuit board setting.
If these are not confirmed, the remote control unit cannot be used to
operate for the air conditioner.
Selecting the Remote Control Unit Signal Code
Use the following steps to select the signal code of the remote control unit.
(Note that the air conditioner cannot receive a signal code if the air conditioner has not been set for the signal code.)
1 Press the START/STOP button until only the clock is displayed on the
remote control unit display.
2 Press the MODE button for at least five seconds to display the current
signal code (initially set to
3 Press the SET TEMP. (
between .
Match the code on the display to the air conditioner signal code.
4 Press the MODE button again to return to the clock display. The signal
code will be changed.
If no buttons are pressed within 30 seconds after the signal code is
displayed, the system returns to the original clock display. In this
case, start again from step 1.
The air conditioner signal code is set to A prior to shipment.
Contact your retailer to change the signal code.
The remote control unit resets to signal code A when the batteries in
the remote control unit are replaced. If you use a signal code other
than signal code A, reset the signal code after replacing the
batteries.
If you do not know the air conditioner signal code setting, try each
of the signal codes (
operates the air conditioner.
).
) ( ) button to change the signal code
) until you find the code which
Indoor unit setting
Jumper wire
JM1
Connect
Disconnect
Connect
Disconnect
Connect
Connect
Disconnect
Disconnect
JM2
Remote control unit
signal code
A (Primary setting)
B
C
D
Indoor unit
Printed circuit board
10
CHECK ITEMS
(1) Is operation of each button on the remote control unit normal?
(2) Does each lamp light normally?
(3) Do not air flow direction louvers operate normally?
(4) Is the drain normal?
(5) Is there any abnormal noise and vibration during operation?
• Do not operate the air conditioner in the running state for a long time.
• Test running
When the air conditioner is run by pressing the remote control unit test
run button, the OPERATION and TIMER lamps flash slowly at the same
time.
[OPERATION METHOD]
• For the operation method, refer to the operating manual.
• The outdoor unit may not operate depending on the room temperature.
In this case, press the test run button on the remote control unit while
the air conditioner is running. (Point the transmitter section of the remote control unit toward the air conditioner and press the test run button with the tip of a ball-point pen, etc.)
Transmitter section
•
To end test operation, press the remote control unit START/STOP button.
(When the air conditioner is run by pressing the test run button, the
OPERATION indicator lamp and TIMER indicator lamp will simultaneously flash slowly.)
[Using the wired remote control] (Option)
• For the operation method, refer to the operating manual.
(1) Stop the air conditioner operation.
(2) Press the master control button and the fan control button simulta-
neously for 2 seconds or more to start the test run.
(3) Press the start/stop button to stop the test run.
TEST RUN
Test run button
Test run display
Troubleshooting
(Troubleshooting with the indoor display)
Troubleshooting at the display is possible either on the wired or wireless
remote control.
OPERATION lamp (Green)
TIMER lamp (Orange)
FILTER lamp (Red)
The OPERATION, TIMER and FILTER lamp operate as follows table according to the error contents.
Error contents
Indoor signal error
Wired remote controller abnormal
Indoor room temperature sensor error
Indoor heat exchanger temperature
sensor (middle) error
Indoor heat exchanger temperature
sensor (inlet) error
Float switch operated
Outdoor discharge pipe temperature
sensor error
Outdoor heat exchanger temperature
sensor (outlet) error
Outdoor temperature sensor error
Compressor temperature sensor error
2-way valve temperature sensor error
3-way valve temperature sensor error
Outdoor heat exchanger temperature
sensor (middle) error
Indoor manual auto switch abnormal
Power supply frequency detection
error
IPM protection
CT error
Compressor location error
Outdoor fan error
Connected indoor unit abnormal
Outdoor unit computer communication
error
Indoor fan abnormal
Discharge temperature error
Exessive high pressure protection on
cooling
4-way valve abnormal
Pressure switch abnormal
Compressor temperature error
Active filter abnormal
PFC circuit error
: 0.5s ON/0.5s OFF (Flash) : OFF
OPERATION
lamp (Green)
(2 times)
(2 times)
(2 times)
(2 times)
(3 times)
(3 times)
(3 times)
(3 times)
(3 times)
(3 times)
(3 times)
(4 times)
(4 times)
(5 times)
(5 times)
(5 times)
(5 times)
(5 times)
(5 times)
(6 times)
(7 times)
(7 times)
(7 times)
(7 times)
(7 times)
(8 times)
(8 times)
TIMER lamp
(8 times)
(2 times)
(3 times)
(4 times)
(6 times)
(2 times)
(3 times)
(4 times)
(8 times)
(2 times)
(4 times)
(2 times)
(3 times)
(5 times)
(6 times)
(7 times)
(8 times)
(2 or 3 times)
(2 times)
(3 times)
(4 times)
(5 times)
(6 times)
(2 or 3 times)
(4 times)
FILTER lamp
(Orange)
(2 times)
(3 times)
(4 times)
(Red)
[Troubleshooting at the remote control LCD]
This is possible only on the wired remote control. (Option)
[SELF-DIAGNOSIS]
This possible only on the wired remote control. (Option)
If an error occurs, the following display will be shown.
(“EE” will appear in the set room temperature display.)
Unit number
Error code
Ex. Self-diagnosis
Error code Error contents
01
13
26
27
00
02
04
28
09
0C
06
0A
15
1d
1E
29
20
2A
17
18
1A
1b
1F
1c
12
0F
24
2c
16
2b
19
25
If “CO” appears in the unit number display, there is a remote controller
error.
Unit number
Indoor signal error
Wired remote controller abnormal
Indoor room temperature sensor error
Indoor heat exchanger temperature sensor (middle)
error
Indoor heat exchanger temperature sensor (inlet)
error
Float switch operated
Outdoor discharge pipe temperature sensor error
Outdoor heat exchanger temperature sensor (outlet)
error
Outdoor temperature sensor error
Compressor temperature sensor error
2-way valve temperature sensor error
3-way valve temperature sensor error
Outdoor heat exchanger temperature sensor (middle)
error
Indoor manual auto switch abnormal
Power supply frequency detection error
IPM protection
CT error
Compressor location error
Outdoor fan error
Connected indoor unit abnormal
Outdoor unit computer communication error
Indoor fan abnormal
Discharge temperature error
Exessive high pressure protection on cooling
4-way valve abnormal
Pressure switch abnormal
Compressor temperature error
Active filter abnormal
PFC circuit error
Error code
C0
C0
1d
1c
Incompatible indoor unit is
connected
Indoor unit ↔ remote controller
communication error
Content
11
SPECIAL INSTALLATION
METHODS
This possible only on the wired remote control. (Option)
CAUTION
1 When setting DIP switches, do not touch any other parts
on the circuit board directly with your bare hands.
2 Be sure to turn off the main power.
1. GROUP CONTROL SYSTEM
A number of indoor units can be operated at the same time using a
single remote controller.
(1) Wiring method (indoor unit to remote controller)
Indoor unit 2Indoor unit 1Indoor unit 0 Indoor unit 3
Remote
controller cord
Remote controller
When ground wire is necessary
(2) DIP switch setting (indoor unit)
Set the unit number of each indoor unit using DIP switch on the indoor
unit circuit board. (See following table and figure.)
DIP switch is normally set to make unit number No. 0.
Indoor unit
Unit number DIP SWITCH No.
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Example : No. 3
1
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
2
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
Bus wire
3
OFF
OFF
OFF
OFF
ON
ON
ON
ON
OFF
OFF
OFF
OFF
ON
ON
ON
ON
4
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
12
Explain the following to the customer in accordance with the operating
manual:
(1) Starting and stopping method, operation switching, temperature
adjustment, timer, air flow switching, and other remote control unit
operations.
(2) Air filter removal and cleaning, and how to use the air louvers.
(3) Give the operating and installation manuals to the customer.
(4) If the signal code is changed, explain to the customer how it changed
(the system returns to signal code A when the batteries in the remote
control unit are replaced).
*(4) is applicable to using wireless remote control.
CUSTOMER GUIDANCE
PART NO. 9374318346