Ceiling Type
INSTALLATION
INSTRUCTION SHEET
(PART NO. 9374318216)
For authorized service personnel only.
DANGER
WARNING
CAUTION
Never touch electrical components immediately after the power supply has been turned off. Electrical shock may occur. After
turning off the power, always wait 5 minutes or more before touching electrical components.
The basic installation work procedures are the same as conventional refrigerant models.
However, pay careful attention to the following points:
1 Since the working pressure is 1.6 times higher than that of conventional refrigerant models, some of the piping and
installation and service tools are special. (See the table below.)
Especially, when replacing a conventional refrigerant model with a new refrigerant R410A model, always replace the
conventional piping and flare nuts with the R410A piping and flare nuts.
2 Models that use refrigerant R410A have a different charging port thread diameter to prevent erroneous charging with
conventional refrigerant and for safety. Therefore, check beforehand. [The charging port thread diameter for R410A is
1/2 UNF 20 threads per inch.]
3 Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with refrigerant models. Also, when
storing the piping, securely seal the openings by pinching, taping, etc.
4 When charging the refrigerant, take into account the slight change in the composition of the gas and liquid phases, and
always charge from the liquid phase side whose composition is stable.
Special tools for R410A
Tool name
Gauge manifold
Charge hose
Vacuum pump
Gas leakage detector
Copper pipes
It is necessary to use seamless copper pipes and it is desirable that the
amount of residual oil is less than 40 mg/10 m. Do not use copper pipes
having a collapsed, deformed or discolored portion (especially on the interior
surface). Otherwise, the expansion valve or capillary tube may become
blocked with contaminants.
As an air conditioner using R410A incurs pressure higher than when using
conventional refrigerant, it is necessary to choose adequate materials.
Thicknesses of copper pipes used with R410A are as shown in the table.
Never use copper pipes thinner than that in the table even when it is
available on the market.
This mark indicates procedures which, if improperly performed, are most likely to result in the death of or
serious injury to the user or service personnel.
This mark indicates procedures which, if improperly performed, might lead to the death or serious injury of
the user.
This mark indicates procedures which, if improperly performed, might possibly result in personal harm to
the user, or damage to property.
DANGER
This air conditioner uses new refrigerant HFC (R410A).
Pressure is high and cannot be measured with a conventional gauge. To prevent erroneous mixing of other
refrigerants, the diameter of each port has been changed.
It is recommended the gauge with seals –0.1 to 5.3 MPa (–76 cmHg to 53 kgf/cm
3.8 MPa (–76 cmHg to 38 kgf/cm
To increase pressure resistance, the hose material and base size were changed.
A conventional vacuum pump can be used by installing a vacuum pump adapter.
Special gas leakage detector for HFC refrigerant R410A.
2
) for low pressure.
Contents of change
2
) for high pressure. –0.1 to
Thicknesses of Annealed Copper Pipes (R410A)
Pipe outside diameter
6.35 mm (1/4 in.)
9.52 mm (3/8 in.)
12.70 mm (1/2 in.)
15.88 mm (5/8 in.)
19.05 mm (3/4 in.)
Thickness
0.80 mm
0.80 mm
0.80 mm
1.00 mm
1.20 mm
STANDARD PARTS
The following installation parts are furnished.
Use them as required.
INDOOR UNIT ACCESSORIES
Name and Shape
Drain hose insulation
VT wire
Coupler heat insulator (large)
Coupler heat insulator (small)
Nylon fastener
Special nut A
(large flange)
Special nut B
(small flange)
Installation
template
Auxiliary pipe assembly
Remote control unit
Battery (penlight)
Remote control unit holder
Tapping screw
(ø3 × 12)
Q’ty
1
1
2
1
Large
4
Small
4
4
4
1
1
1
2
1
2
Application
Adhesive type 70 × 230
For fixing the drain hose
L 280 mm
For indoor side pipe joint
(Gas pipe)
For indoor side pipe joint
(Liquid pipe)
For fixing the coupler heat
insulator
For installing indoor unit
For installing indoor unit
For positioning the indoor
unit
For connecting the piping
Use for air conditioner
operation
For remote control unit
Use as remote control unit
holder
For remote control unit
holder installation
OPTIONAL PARTS
The following options are available.
••
• DRAIN PUMP UNIT: UTR-DPB241 (P/N 9034087001)
••
••
• ROUND DUCT: UTD-RF204 (P/N 9093160004)
••
••
• WIRED REMOTE CONTROLLER: UTB–*UD
••
INSTALLATION PROCEDURE
1
REMOVE THE INTAKE GRILLE AND SIDE COVER
(1) Remove the two Air filters.
(2) Remove the two Intake grilles.
(3) Remove the Side cover A (Right side) and Side cover B (Right and
(4) This air conditioner can be set up to intake fresh air. For information
Tapping screw
2
You can use the accessory template to help you install the indoor unit.
The template helps you determine the appropriate locations for suspension bolts and pipe opening (drain pipe and connection cord).
1. LOCATION OF CEILING SUSPENSION BOLTS
PREPARING INDOOR UNIT
INSTALLATION
• For 4 Left rear drain and 5 Left drain: Remove air filters and intake
grilles at three places. (Refer to “2 INDOOR UNIT INSTALLATION”.)
Left side).
• For 5 Left drain: Remove both the Side cover A (Right and Left
side). (Refer to “2 INDOOR UNIT INSTALLATION”.)
about how to install for fresh-air intake, refer to “9 FRESH-AIR INTAKE”.
Air filter
Intake grille
INDOOR UNIT
Side cover B
(Left side)
Side cover A (Right side)
Side cover B (Right side)
INDOOR UNIT INSTALLATION
Drilling position for Suspension bolt
Ceiling
Wall
Template
30 mm Suspension bolt pitch 1600 mm
INDOOR UNIT (TOP VIEW)
INDOOR UNIT
Drilling position for piping
Suspension bolt should
extend outward 30 to 75 mm.
30 mm
Dimensions
(Space Required
for Installation)
10 mm
155 mm
300 mm
[For Half-Concealed Installation]
••
• Suspension-bolt pitch should be as shown in the figure.
••
40 mm Ceiling Opening: 1580 mm 40 mm
Ceiling panel
Ceiling Opening: 640 mm
INDOOR UNIT
15 mm
Ceiling panel
Suspension bolt should
extend outward 30 to 50 mm.
2. SELECT PIPING DIRECTION
Select connection piping and drain piping directions.
5 Left piping
(Drain pipe only)
4 Left rear piping
(Drain pipe only)
INDOOR UNIT (TOP VIEW)
2 Top piping
(Connection pipe only)
1 Right rear piping
Cut off the piping outlet cutting groove
with a hacksaw, etc.
[FOR 4 Left rear piping, 5 Left piping]
••
• Transfer the Drain cap and Drain cap seal.
••
Drain cap seal
Drain cap
Indoor unit
Drain pan
Push cap all the way on
(as far as it will go).
Drain cap seal
Drain cap
3. DRILLING THE HOLES AND ATTACHING THE
SUSPENSION BOLTS
(1) Drill ø25 mm holes at the suspension-bolt locations.
(2) Install the bolts, then temporarily attach Special nuts A and B and a
normal M10 nut to each bolt. (The two special nuts are provided with
the unit. The M10 nut must be obtained locally.) Refer to the figure.
Bolt Strength 980 to 1470 N (100 to 150 kgf)
Ceiling panel
10 to 15 mm
Special nut A (Included)
Special nut B (Included)
M10 Nut (Obtained locally)
3 Right
piping
4. INSTALLING THE INDOOR UNIT
(1) Lift unit so that suspension bolts pass through the suspension fittings
at the sides (four places), and slide the unit back.
Ceiling
Wall
Ceiling panel
Wall
INDOOR UNIT
(2) Fasten the indoor unit into place by tightening-up the special “B” bolts
and the M10 nuts. Make sure that unit is secure and will not shift back
and forth.
[For Half-Concealed Installation]
When installing the indoor unit in a semi-concealed orientation, make sure
to reinforce the insulation of the unit on all sides. Drops of water may fall
from the unit if it is not thoroughly insulated.
Glass wool insulate
(10 to 20 mm thick)
INDOOR UNIT
(Top view)
Wall
Ceiling panel
CAUTION
In order to check the drainage, be sure to use a level
during installation of the indoor unit. If the installation site
of the indoor unit is not level, water leakage may occur.
5. DRAIN PIPING
CAUTION
Install the drain pipe in accordance with the instructions
in this installation instruction sheet and keep the area
warm enough to prevent condensation. Problems with the
piping may lead to water leaks.
••
• Install the drain pipe with downward gradient (1/50 to 1/100) and so
••
there are no rises or traps in the pipe.
••
• Use general hard polyvinyl chloride pipe (VP25) [outside diameter
••
38 mm].
••
• During installation of the drain pipe, be careful to avoid applying
••
pressure to the drain port of the indoor unit.
••
• When the pipe is long, install supporters.
••
••
• Do not perform air bleeding.
••
••
• Always heat insulate (8 mm or over thick) the indoor side of the drain
••
pipe.
Drain pipe
Arrange the drain pipe
lower than this portion.
Lifted up
Wave
End in water
Supporter
(1) Install insulation for the drain pipe.
Cut the included insulation material to an appropriate size and adhere
it to the pipe.
Indoor unit (drain port)
Indoor unit
(2) If “1 Right rear piping” : fasten the drain pipe with VT wire so that the
pipe slopes correctly within the indoor unit.
Indoor unit (rear view)
(3) If the drain hose will not be connected to the right rear piping, cut the
hole cover at the points indicated in Fig. (a), and attach it to the piping
hole as shown in Fig. (b).
(a)
Cut x 5
(b)
1.5 to 2 m
Insulation for drain pipe
(To be obtained locally. Length
should be at least 8 mm.)
Drain pipe insulation (accessories)
Drain pipe insulation
No gap
10 mm or over
VT wire
Drain pipe
Drain pipe
Drain hose
Hole cover
3
CONNECTING THE PIPE
CAUTION
1 Do not use mineral oil on flared part. Prevent mineral
oil from getting into the system as this would reduce
the lifetime of the units.
2 While welding the pipes, be sure to blow dry nitrogen
gas through them.
1. FLARING
(1) Cut the connection pipe to the necessary length with a pipe cutter.
(2) Hold the pipe downward so that cuttings will not enter the pipe and
remove the burrs.
(3) Insert the flare nut (always use the flare nut attached to the indoor
and outdoor units respectively) onto the pipe and perform the flare
processing with a flare tool.
Use the special R410A flare tool, or the conventional flare tool.
Check if [L] is flared uniformly
and is not cracked or scratched.
Die
A
Pipe
Pipe outside diameter
6.35 mm (1/4 in.)
9.52 mm (3/8 in.)
12.70 mm (1/2 in.)
15.88 mm (5/8 in.)
19.05 mm (3/4 in.)
Pipe outside diameter
6.35 mm (1/4 in.)
9.52 mm (3/8 in.)
12.70 mm (1/2 in.)
15.88 mm (5/8 in.)
19.05 mm (3/4 in.)
When using conventional flare tools to flare R410A pipes, the dimension
A should be approximately 0.5 mm more than indicated in the table (for
flaring with R410A flare tools) to achieve the specified flaring. Use a thickness gauge to measure the dimension A.
Width across flats
Pipe outside
diameter
6.35 mm (1/4 in.)
9.52 mm (3/8 in.)
12.70 mm (1/2 in.)
15.88 mm (5/8 in.)
19.05 mm (3/4 in.)
Dimension A
Flare tool for R410A, clutch type
0 to 0.5
Dimension B
9.1
13.2
16.6
19.7
24.0
Width across flats
of Flare nut
17 mm
22 mm
26 mm
29 mm
36 mm
(mm)
0
(mm)
-0.4
B
CONNECTION PIPE REQUIREMENT
CAUTION
The maximum/minimum lengths of this product, refer to the installation instruction sheet supplied with the outdoor unit. If
the units are further apart than this, correct operation can not be guaranteed.
Diameter
Liquid
9.52 mm (3/8 in.)
••
• Use pipe with water-resistant heat insulation.
••
Gas
15.88 mm (5/8 in.)
CAUTION
Install heat insulation around both the gas and liquid pipes. Failure to do so may cause water leaks.
Use heat insulation with heat resistance above 120 °C. (Reverse cycle model only)
In addition, if the humidity level at the installation location of the refrigerant piping is expected to exceed 70%, install heat
insulation around the refrigerant piping. If the expected humidity level is 70-80%, use heat insulation that is 15 mm or thicker
and if the expected humidity exceeds 80%, use heat insulation that is 20 mm or thicker.
If heat insulation is used that is not as thick as specified, condensation may form on the surface of the insulation.
In addition, use heat insulation with heat conductivity of 0.045 W/(m·K) or less (at 20 °C).
ELECTRICAL REQUIREMENT
••
• Electric wire size:
••
Connection cord (mm )
MAX.
2.5
••
• Use conformed cord with Type 245 IEC57.
••
••
• Install all electrical works in accordance to the standard.
••
••
• Install the disconnect device with a contact gap of at least 3 mm in all poles nearby the units. (Both indoor unit and outdoor unit)
••
2
MIN.
1.5
SELECTING THE MOUNTING POSITION
Decide the mounting position with the customer as follows:
WARNING
Select installation locations that can properly support the weight of the indoor and outdoor units. Install the units securely so
that they do not topple or fall.
CAUTION
1 Do not install where there is the danger of combustible gas leakage.
2 Do not install the unit near heat source of heat, steam, or flammable gas.
3 If children under 10 years old may approach the unit, take preventive measures so that they cannot reach the unit.
INDOOR UNIT
(1) Install the indoor unit level on a strong wall which is not subject to vibration.
(2) The inlet and outlet ports should not be obstructed : the air should be able to blow all over the room.
(3) Do not install the unit where it will be exposed to direct sunlight.
(4) Install the unit where connection to the outdoor unit is easy.
(5) Install the unit where the drain pipe can be easily installed.
(6) Take servicing, etc., into consideration and leave the spaces shown in the figure. Also install the unit where the filter can be removed.
[FOR HALF CONCEALED INSTALLATION]
Ceiling panel
INDOOR UNIT
80 or over 150 or over
Ceiling panel
2300 or over
10 or over
1000 or over
Obstruction
Floor
80 or over
Ceiling
INDOOR UNIT
Ceiling
2300 or over
Obstruction
Floor
(Unit : mm)
150 or over
10 or over
1000 or over
2. BENDING PIPES
The pipes are shaped by your hands. Be careful not to collapse them.
Do not bend the pipes in an angle more than 90°.
When pipes are repeatedly bend or stretched, the material will harden,
making it difficult to bend or stretch them any more. Do not bend or
stretch the pipes more than three times.
CAUTION
1 To prevent breaking of the pipe, avoid sharp bends.
Bend the pipe with a radius of curvature of 150 mm or
over.
2 If the pipe is bent repeatedly at the same place, it will
break.
3. CONNECTION PIPES
Indoor unit
(1) Detach the caps and plugs from the pipes.
CAUTION
1 Be sure to apply the pipe against the port on the in-
door unit correctly. If the centering is improper, the flare
nut cannot be tightened smoothly. If the flare nut is
forced to turn, the threads will be damaged.
2 Do not remove the flare nut from the indoor unit pipe
until immediately before connecting the connection
pipe.
(2) Centering the pipe against port on the indoor unit, turn the flare nut
with your hand.
To prevent gas leakage, coat the flare
surface with alkylbenzene oil (HAB).
Do not use mineral oil.
(3) Remove the filter guide.
Indoor unit
(4) Attach the connection pipe.
Indoor unit
Filter guide
Connection pipe (Gas)
Connection pipe (Liquid)
• For 2 Top piping and 3 Right piping connections, use the Auxi-
liary pipe (Gas pipe) provided.
2 Top piping
Connection pipe (Gas)
Indoor unit (rear)
Connection pipe (Gas)
3 Right piping
(5) When the flare nut is tightened properly by your hand, use a torque
wrench to finally tighten it.
Body side
Auxiliary pipe (Gas pipe)
Holding spanner
Torque wrench
CAUTION
Hold the torque wrench at its grip, keeping it in the right
angle with the pipe, in order to tighten the flare nut
correctly.
Flare nut Tightening torque
6.35 mm (1/4 in.) dia.
9.52 mm (3/8 in.) dia.
12.70 mm (1/2 in.) dia.
15.88 mm (5/8 in.) dia.
19.05 mm (3/4 in.) dia.
16 to 18 N·m (160 to 180 kgf·cm)
30 to 42 N·m (300 to 420 kgf·cm)
49 to 61 N·m (490 to 610 kgf·cm)
63 to 75 N·m (630 to 750 kgf·cm)
90 to 110 N·m (900 to 1100 kgf·cm)
4. HEAT INSULATION ON THE PIPE JOINTS
(INDOOR SIDE ONLY)
After checking for gas leaks, insulate by wrapping insulation around the
two parts (Gas and Liquid) of the indoor unit coupling, using the coupler
heat insulation.
After installing the coupler heat insulation, wrap both ends with vinyl tape
so that there is no gap.
Secure both ends of the heat insulation material using nylon fasteners.
And finally fix connection pipe (Liquid) to connection pipe (Gas) by rolling
vinyl tape over coupler heat insulation (Gas) and coupler heat insulation
(Liquid).
Coupler heat insulation (Large)
Indoor unit
Coupler heat insulation (Small)
Indoor unit
Indoor unit
• When using an auxiliary pipe, make sure that the fastener used is insulated in the same way.
There should be no gaps between the insulation and the
product.
Connection pipe (Gas)
Connection pipe (Liquid)
Nylon fastener (Large)
Nylon fastener (Small)
Connection pipe (Gas)
Connection pipe (Liquid)
Vinyl tape
CAUTION
No gap
Coupler heat
insulation
4
ELECTRICAL WIRING
WARNING
1 Before starting work, check that power is not being
supplied to the indoor unit and outdoor unit.
2 Match the terminal board numbers and connection
cord colors with those of the outdoor unit.
Erroneous wiring may cause burning of the electric
parts.
3 Connect the connection cords firmly to the terminal
board. Imperfect installation may cause a fire.
4 Always fasten the outside covering of the connection
cord with the cord clamp. (If the insulator is chafed,
electric leakage may occur.)
5 Always connect the ground wire.
6 Install the remote controller wires so as not to be di-
rect touched with your hand.
HOW TO CONNECT WIRING TO THE
TERMINALS
For strand wiring
(1) Use crimp-type terminals with insulating sleeves as shown in the
figure below to connect to the terminal block.
(2) Securely crimp the crimp-type terminals to the wires using an ap-
propriate tool so that the wires do not come loose.
(3) Use the specified wires, connect them securely, and fasten them
so that there is no stress placed on the terminals.
(4) Use an appropriate screwdriver to tighten the terminal screws.
Do not use a screwdriver that is too small, otherwise, the screw
heads may be damaged and prevent the screws from being
properly tightened.
(5) Do not tighten the terminal screws too much, otherwise, the screws
may break.
(6) See the table below for the terminal screw tightening torques.
Crimp-type
terminal
Strip 10 mm
Sleeve
Screw with
special washer
Wire
Crimp-type terminal
Terminal board
Terminal block
M4 screw 1.2 to 1.8 N·m (12 to 18 kgf·cm)
Wire
Tighting torque
WARNING
Use crimp-type terminals and tighten the terminal
screws to the specified torques, otherwise, abnormal overheating may be produced and possibly
cause heavy damage inside the unit.
Screw with
special washer
Crimp-type
terminal
1. CONNECTION DIAGRAMS
Connection cord (to outdoor unit)
Control line
Power line
Indoor unit
side
Wired remote controller cord (option)
*
Black
White
Red
Indoor unit
side
Ground the remote controller ip it has a ground wire
*
2. CONNECTION CORD PREPARATION
Keep the earth wire longer than the other wires.
30 mm
Earth wire
40 mm or more
• Use a 4-core wire cord.
Power supply cord
or connection cord
3. INDOOR UNIT
CAUTION
Use care not to mistake the power supply cord and
connection wires when installing.
(1) Remove the two tapping screws and pull the control box downward.
Indoor unit
Control box
Tapping screw
(2) Remove the Cover A and install the Connection cord.
(3) Reattach Cover A. Then fasten the control box back into its original
position using the two tapping screws.
Control box
Cover A
(4) After wiring is complete, clamp the Connection cord with the Cord
clamp.
(5) Attach the connection cord and cable clips. Make sure that they are
positioned so that they will not interfere with opening and closing of
the intake grille or with removal and installation of the air filters.
Powe r
Remote
Connection cord
(To outdoor unit)
Wired remote controller cord
(Option)
Cable clip
Connection cord
Wired remote controller cord
- Continued on back -
5
REMOTE CONTROLLER
SETTING
1. LOAD BATTERIES (R03/LR03
1 Press and slide the battery compartment lid on the reverse side to
open it.
Slide in the direction of the arrow while pressing the
2 Insert batteries.
Be sure to align the battery polarities (
3 Close the battery compartment lid.
CAUTION
1 Take care to prevent infants from accidentally
swallowing batteries.
2 When not using the Remote Control Unit for an
extended period, remove the batteries to avoid
possible leakage and damage to the unit.
3 If leaking battery fluid comes in contact with your skin,
eyes, or mouth, immediately wash with copious
amounts of water, and consult your physician.
4 Dead batteries should be removed immediately and
disposed of properly, either in a battery collection
receptacle or to the appropriate authority.
5 Do not attempt to recharge dry batteries.
NOTES
• Never mix new and used batteries, or batteries of different types.
• Batteries should last about one year under normal use. If the Remote
Control Unit’s operating range becomes appreciably reduced, replace
the batteries and press the RESET button with the tip of a ballpoint pen
or other small object.
2. REMOTE CONTROL UNIT HOLDER INSTALLA-
TION
CAUTION
1 Check that the indoor unit correctly receives the sig-
nal from the remote control unit, then install the remote
control unit holder.
2 Select the remote control unit holder selection site by
paying careful attention to the following:
Avoid places in direct sunlight.
Select a place that will not be affected by the heat from
a stove, etc.
• Install the remote control unit with a distance of 7 m between the remote control unit and the photocell as the criteria. However, when installing the remote control unit, check that it operates positively.
• Install the remote control unit holder to a wall, pillar, etc. with the tapping screw.
××
× 2)
××
) correctly.
mark.
1 Mount the Holder.
Screws
2 Set the Remote Control Unit.
Insert
Press in
3 To remove the Remote Control Unit (when use at hand).
Slide up
Pull out
6
• This procedure changes to the function settings used to control the
indoor unit according to the installation conditions. Incorrect settings
can cause the indoor unit malfunction.
• After the power is turned on, perform the “FUNCTION SETTING”
according to the installation conditions using the remote controller.
• The settings may be selected between the following two: Function
Number or Setting Value.
• Settings will not be changed if invalid numbers or setting values are
selected.
FUNCTION SETTING
Entering the Function Setting Mode
• While pressing the FAN button and SET TEMP. ( ) simultaneously,
press the RESET button to enter the function setting mode.
STEP 1
Selecting the Remote Control Unit Signal Code
Use the following steps to select the signal code of the remote control unit.
(Note that the air conditioner cannot receive a signal code if the air conditioner has not been set for the signal code.)
The signal codes that are set through this process are applicable only to
the signals in the FUNCTION SETTING. For details on how to set the
signal codes through the normal process, refer to SELECTING THE
REMOTE CONTROL UNIT SIGNAL CODE.
1 Press the SET TEMP. (
between .
Match the code on the display to the air conditioner signal code. (initially set to )
(If the signal code does not need to be selected, press the MODE
button and proceed to STEP 2.)
2 Press the TIMER MODE button and check that the indoor unit can
receive signals at the displayed signal code.
3 Press the MODE button to accept the signal code, and proceed to
STEP 2.
) ( ) button to change the signal code
The air conditioner signal code is set to A prior to shipment.
Contact your retailer to change the signal code.
The remote control unit resets to signal code A when the batteries in
the remote control unit are replaced. If you use a signal code other
than signal code A, reset the signal code after replacing the
batteries.
If you do not know the air conditioner signal code setting, try each
of the signal codes (
operates the air conditioner.
) until you find the code which
STEP 2
Selecting the Function Number and Setting Value
1 Press the SET TEMP. ( ) ( ) buttons to select the function number.
(Press the MODE button to switch between the left and right digits.)
2 Press the FAN button to proceed to setting the value.
(Press the FAN button again to return to the function number selection.)
3 Press the SET TEMP. (
(Press the MODE button to switch between the left and right digits.)
4 Press the TIMER MODE button, and START/STOP button, in the
order listed to confirm the settings.
5 Press the RESET button to cancel the function setting mode.
6 After completing the FUNCTION SETTING, be sure to turn off the
power and turn it on again.
Function number
After turning off the power, wait 10 seconds or more
before turning on it again.
The FUNCTION SETTING doesn’t become effective if it
doesn’t do so.
) ( ) buttons to select the setting value.
Setting value
CAUTION
Setting the Ceiling Height
• Select the setting values in the table below according to the height of
the ceiling. (The unit is factory-set to “00”.)
Setting Description
Standard
(2.3 m to 3.0 m)
High ceiling
(3.0 m or more)
Function Number
20
Setting Value
00
01
Setting the Filter Sign
• The indoor unit has a sign to inform the user that it is time to clean the
filter.
• Select the time setting for the filter sign display interval in the table
below according to the amount of dust or debris in the room. (The unit
is factory-set to “00”.)
• If you do not wish the filter sign to be displayed, select the setting value
for “No indication”.
Setting Description
Standard
(2,500 hours)
Long interval
(4,400 hours)
Short interval
(1,250 hours)
No indication
Function Number
11
Setting Value
00
01
02
03
Setting the Cooler Room Temperature Correction
• Depending on the installed environment, the room temperature sensor
may require a correction. The settings may be selected as shown in the
table below. (The unit is factory-set to “00”.)
Setting Description
Standard
Lower control
Function Number
30
Setting Value
00
01
Setting the Heater Room Temperature Correction
• Depending on the installed environment, the room temperature sensor
may require a correction. The settings may be changed as shown in the
table below. (The unit is factory-set to “00”.)
Setting Description
Standard
Lower control
Slightly warmer control
Warmer control
Function Number
31
Setting Value
00
01
02
03
Setting Other Functions
• The following settings are also possible, depending on the operating
conditions. (The unit is factory-set to “00”.)
Auto Restart
Setting Description
Ye s
No
Indoor Room Temperature Sensor Switching Function (Wired remote controller only)
Setting Description
No
Ye s
• If setting value is “00”, room temperature is controlled by the indoor unit
temperature sensor.
• If setting value is “01”, room temperature is controlled by either indoor
unit temperature sensor or remote control unit sensor.
Function Number
40
Function Number
42
Setting Value
00
01
Setting Value
00
01
Setting record
• Record any changes to the settings in the following table.
Setting
Ceiling height
Filter sign
Cooler room temperature
correction
Heater room temperature
correction
Auto restart
Indoor room temperature
sensor switching function
After completing the FUNCTION SETTING, be sure to turn off the power
and turn it on again.
Setting Value
7
SELECTING THE REMOTE
CONTROL UNIT SIGNAL CODE
When two or more air conditioners are installed in a room and the remote
control unit is operating an air conditioner other than the one you wish to
set, change the signal code of the remote control unit to operate only the
air conditioner you wish to set (four selections possible).
When two or more air conditioners are installed in a room, please contact
your retailer to set the individual air conditioner signal codes.
• Confirm the setting of the remote control unit signal code and the printed
circuit board setting.
If these are not confirmed, the remote control unit cannot be used to
operate for the air conditioner.
Selecting the Remote Control Unit Signal Code
Use the following steps to select the signal code of the remote control unit.
(Note that the air conditioner cannot receive a signal code if the air conditioner has not been set for the signal code.)
1 Press the START/STOP button until only the clock is displayed on the
remote control unit display.
2 Press the MODE button for at least five seconds to display the current
signal code (initially set to
3 Press the SET TEMP. (
between .
Match the code on the display to the air conditioner signal code.
4 Press the MODE button again to return to the clock display. The signal
code will be changed.
If no buttons are pressed within 30 seconds after the signal code is
displayed, the system returns to the original clock display. In this
case, start again from step 1.
The air conditioner signal code is set to A prior to shipment.
Contact your retailer to change the signal code.
The remote control unit resets to signal code A when the batteries in
the remote control unit are replaced. If you use a signal code other
than signal code A, reset the signal code after replacing the
batteries.
If you do not know the air conditioner signal code setting, try each
of the signal codes (
operates the air conditioner.
).
) ( ) button to change the signal code
) until you find the code which
Indoor unit setting
Jumper wire
JM1
Connect
Disconnect
Connect
Disconnect
Connect
Connect
Disconnect
Disconnect
JM2
Remote control unit
signal code
A (Primary setting)
B
C
D
Indoor unit
Printed circuit board
8
TEST RUN
CHECK ITEMS
(1) Is operation of each button on the remote control unit normal?
(2) Does each lamp light normally?
(3) Do not air flow direction louvers operate normally?
(4) Is the drain normal?
(5) Is there any abnormal noise and vibration during operation?
• Do not operate the air conditioner in the running state for a long time.
• Test running
When the air conditioner is run by pressing the remote control unit test
run button, the OPERATION and TIMER lamps flash slowly at the same
time.
[OPERATION METHOD]
• For the operation method, refer to the operating manual.
• The outdoor unit may not operate depending on the room temperature.
In this case, press the test run button on the remote control unit while
the air conditioner is running. (Point the transmitter section of the
remote control unit toward the air conditioner and press the test run
button with the tip of a ball-point pen, etc.)
Transmitter section
Test run button
•
To end test operation, press the remote control unit START/STOP button.
(When the air conditioner is run by pressing the test run button, the
OPERATION indicator lamp and TIMER indicator lamp will simultaneously flash slowly.)
[Using the wired remote control] (Option)
• For the operation method, refer to the operating manual.
(1) Stop the air conditioner operation.
(2) Press the master control button and the fan control button simulta-
neously for 2 seconds or more to start the test run.
Test run display
(3) Press the start/stop button to stop the test run.
Troubleshooting
(Troubleshooting with the indoor display)
Troubleshooting at the display is possible either on the wired or wireless
remote control.
FILTER lamp (Orange)
TIMER lamp (Green)
OPERATION lamp (Red)
The OPERATION, TIMER and FILTER lamp operate as follows table according to the error contents.
Error contents
Indoor signal error
Wired remote controller abnormal
Indoor room temperature sensor error
Indoor heat exchanger temperature
sensor (middle) error
Indoor heat exchanger temperature
sensor (inlet) error
Float switch operated
Outdoor discharge pipe temperature
sensor error
Outdoor heat exchanger temperature
sensor (outlet) error
Outdoor temperature sensor error
Heatsink thermistor error
Compressor temperature sensor error
2-way valve temperature sensor error
3-way valve temperature sensor error
Outdoor heat exchanger temperature
sensor (middle) error
Indoor manual auto switch abnormal
Power supply frequency detection
error
IPM protection
CT error
Compressor location error
Outdoor fan error
Connected indoor unit abnormal
Outdoor unit computer communication
error
Indoor fan abnormal
Discharge temperature error
Excessive high pressure protection on
cooling
4-way valve abnormal
Pressure switch abnormal
Compressor temperature error
Active filter abnormal
PFC circuit error
: 0.5s ON/0.5s OFF (Flash) : OFF
OPERATION
lamp (RED)
(2 times)
(2 times)
(2 times)
(2 times)
(3 times)
(3 times)
(3 times)
(3 times)
(3 times)
(3 times)
(3 times)
(3 times)
(4 times)
(4 times)
(5 times)
(5 times)
(5 times)
(5 times)
(5 times)
(5 times)
(6 times)
(7 times)
(7 times)
(7 times)
(7 times)
(7 times)
(8 times)
(8 times)
TIMER lamp
(8 times)
(2 times)
(3 times)
(4 times)
(6 times)
(2 times)
(3 times)
(4 times)
(7 times)
(8 times)
(2 times)
(4 times)
(2 times)
(3 times)
(5 times)
(6 times)
(7 times)
(8 times)
(2 or 3 times)
(2 times)
(3 times)
(4 times)
(5 times)
(6 times)
(2 or 3 times)
(4 times)
(GREEN)
FILTER lamp
(ORANGE)
(2 times)
(3 times)
(4 times)
[Troubleshooting at the remote control LCD]
This possible only on the wired remote control. (Option)
[SELF-DIAGNOSIS]
This possible only on the wired remote control. (Option)
If an error occurs, the following display will be shown.
(“EE” will appear in the set room temperature display.)
Unit number
Error code
Ex. Self-diagnosis
Error code Error contents
01
13
26
27
00
02
04
28
09
0C
06
0A
0E
15
1d
1E
29
20
2A
17
18
1A
1b
1F
1c
12
0F
24
2c
16
2b
19
25
If “CO” appears in the unit number display, there is a remote controller
error.
Unit number
Indoor signal error
Wired remote controller abnormal
Indoor room temperature sensor error
Indoor heat exchanger temperature sensor (middle)
error
Indoor heat exchanger temperature sensor (inlet)
error
Float switch operated
Outdoor discharge pipe temperature sensor error
Outdoor heat exchanger temperature sensor (outlet)
error
Outdoor temperature sensor error
Heatsink thermistor error
Compressor temperature sensor error
2-way valve temperature sensor error
3-way valve temperature sensor error
Outdoor heat exchanger temperature sensor (middle)
error
Indoor manual auto switch abnormal
Power supply frequency detection error
IPM protection
CT error
Compressor location error
Outdoor fan error
Connected indoor unit abnormal
Outdoor unit computer communication error
Indoor fan abnormal
Discharge temperature error
Excessive high pressure protection on cooling
4-way valve abnormal
Pressure switch abnormal
Compressor temperature error
Active filter abnormal
PFC circuit error
Error code
C0
C0
1d
1c
Incompatible indoor unit is
connected
Indoor unit ↔ remote controller
communication error
Content
9
(1) Open up the knockout hole for the fresh-air intake, as shown in the
figure. (If using half-concealed installation, open up the top knockout
hole instead.)
FRESH-AIR INTAKE
For half concealed
installation
Indoor unit
CAUTION
1 When removing the cabinet (iron plate), be careful
not to damage the indoor unit internal parts and
surrounding area (outer case).
2 When processing the cabinet (iron plate), be careful
not to injure yourself with burrs, etc.
(2) Fasten the round flange (optional) to the fresh-air intake, as shown in
the figure. (If using half-concealed installation, attach to the top.)
Round duct (option parts)
[After completing “2 INDOOR UNIT INSTALLATION”...]
(3) Connect the duct to the round flange.
(4) Seal with a band and vinyl tape, etc. so that air does not leak from the
connection.
Duct
10
SPECIAL INSTALLATION
METHODS
CAUTION
1 When setting DIP switches, do not touch any other parts
on the circuit board directly with your bare hands.
2 Be sure to turn off the main power.
1. GROUP CONTROL SYSTEM
A number of indoor units can be operated at the same time using a
single remote controller.
(1) Wiring method (indoor unit to remote controller)
Indoor unit 2Indoor unit 1Indoor unit 0 Indoor unit 3
Remote
controller cord
Remote controller
When ground wire is necessary
(2) DIP switch setting (indoor unit)
Set the unit number of each indoor unit using DIP switch on the indoor
unit circuit board. (See following table and figure.)
DIP switch is normally set to make unit number No. 0.
Indoor unit
Unit number DIP SWITCH No.
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Example : No. 3
1
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
2
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
Bus wire
3
OFF
OFF
OFF
OFF
ON
ON
ON
ON
OFF
OFF
OFF
OFF
ON
ON
ON
ON
4
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
11
Explain the following to the customer in accordance with the operating
manual:
(1) Starting and stopping method, operation switching, temperature
adjustment, timer, air flow switching, and other remote control unit
operations.
(2) Air filter removal and cleaning, and how to use the air louvers.
(3) Give the operating and installation manuals to the customer.
(4) If the signal code is changed, explain to the customer how it changed
(the system returns to signal code A when the batteries in the remote
control unit are replaced).
*(4) is applicable to using wireless remote control.
CUSTOMER GUIDANCE
PART NO. 9374318216