Generac Power Systems 5209, ULTRA SOURCE 005209 Owner's Manual

Owner’s Manual
• SAFETY
• ASSEMBLY
• OPERATION
• TROUBLESHOOTING
• ELECTRICAL DATA
• PARTS
• WARRANTY
ULTRA SOURCE
Semi-Automatic
Emergency Generator
COMMERCIAL • INDUSTRIAL • RESIDENTIAL
MODEL: 005209
1155,,000000 WWAATTTT GGEENNEERRAATTOORR
AANNDD 110000 AAMMPP TTRRAANNSSFFEERR SSWWIITTCCHH
WWIITTHH BBUUIILLTT--IINN LLOOAADD CCEENNTTEERR
AUTHORIZED DEALER SUPPORT:
Table of Contents
Residential Portable Generator System
Safety Rules ..............................................1-3
Section 1 – General Information ................4
1.1 Unpacking ....................................................................4
1.1.1 Accessory Box..................................................4
1.2 Assembly ......................................................................4
1.2.1 Assembling the Wheel Kit ................................4
1.2.2 Assembling the Handle ....................................5
1.2.3 Battery Connection ..........................................5
Section 2 – Operation ..................................6
2.1 Know The Generator ....................................................6
2.2 Cord Sets and Connector Plugs....................................7
2.2.1 120V AC, 20 A, Duplex Receptacle ..................7
2.2.2 120V AC, 20 A, GFCI Receptacle ......................7
2.2.3 120V AC, 30 A Receptacle ............................7-8
2.2.4 120/240V AC, 30 A, Receptacle........................8
2.2.5 12 VDC, 10 Amp Receptacle ............................8
2.2.6 120/240V AC, 50 A, Receptacle........................8
2.3 How To Use The Generator ..........................................9
2.3.1 Grounding The Generator ................................9
2.3.2 Connecting Electric Loads ................................9
2.4 Don’t Overload The Generator ......................................9
2.5 Wattage Reference Chart ............................................10
2.6 Before Starting The Generator ....................................10
2.6.1 Adding Engine Oil ..........................................10
2.6.2 Adding Gasoline ............................................11
2.7 To Start The Engine ....................................................11
2.8 Stopping The Engine ..................................................12
2.9 Automatic Idle Control ................................................12
2.10 Cold Weather Operation/De-Icer ................................12
2.11 Low Oil Pressure Shutdown........................................12
2.11.1 Initial Start-up ................................................12
2.11.2 Sensing Low Oil Pressure ..............................12
2.11.3 Restarting ......................................................12
2.12 Charging a Battery ......................................................13
Section 3 – Maintenance............................14
3.1 Maintenance Schedule ................................................14
3.2 Product Specifications ................................................14
3.2.1 Generator Specifications ................................14
3.2.2 Engine Specifications ....................................14
3.3 General Recommendations ........................................15
3.3.1 General Maintenance......................................15
3.3.2 To Clean The Generator..................................15
3.3.3 Engine Maintenance ......................................15
3.3.4 Checking Oil Level ..........................................15
3.3.5 Changing The Oil & Oil Filter ..........................15
3.3.6 Replacing The Spark Plug .............................16
3.4 Service Air Cleaner......................................................16
3.5 Clean Spark Arrestor Screen ......................................16
3.6 Adjusting Valve Clearance ..........................................17
3.7 General ......................................................................18
3.8 Long Term Storage ....................................................18
3.9 Other Storage Tips......................................................18
Section 4 – Troubleshooting ....................19
4.1 Troubleshooting Guide................................................19
Section 5 – Installation Guide For
Generator Ready Kit ........20-23
Section 6 – Operation Of Generator With
Generator Ready Kit ........24-26
Section 7 – Notes ......................................27
Section 8 – Electrical Data ..................28-29
Section 9 – Exploded Views and
Parts Lists..........................30-39
Section 108 – Warranty ........................40-42
INTRODUCTION
Thank you for purchasing this model of the GUARDIAN®product line by Generac Power Systems, Inc. This model is a compact, high performance, air-cooled, engine driven generator designed to supply electrical power to operate electrical loads when utility power is unavailable due to a power outage.
READ THIS MANUAL THOROUGHLY
If you do not understand any portion of this manual, contact your nearest GENERAC/GUARDIAN
®
Authorized Dealer for starting,
operating and servicing procedures.
Throughout this publication, and on tags and decals affixed to the generator, DANGER, WARNING, CAUTION and NOTE blocks are used to alert you to special instruction about a particular operation that may be hazardous if performed incorrectly or carelessly. Observe them carefully. Their definitions are as follows:
After this heading, you can read instructions that, if not strictly complied with, will result in personal injury or property damage.
After this heading, you can read instructions that, if not strictly complied with, may result in personal injury or property damage.
After this heading, you can read instructions that, if not strictly complied with, could result in damage to equipment and/or property.
NOTE: After this heading, you can read explanatory statements
that require special emphasis. These safety warnings cannot eliminate the hazards that they indicate. Common sense and strict compliance with the special instructions while performing the service are essential to preventing accidents.
Four commonly used safety symbols accompany the DANGER, WARNING and CAUTION blocks. The type of information each indicates follows:
This symbol points out important safety
information that, if not followed, could endanger personal safety and/or property of you and others.
This symbol points out potential explosion hazard.This symbol points out potential fire hazard.This symbol points out potential electrical shock
hazard.
The operator is responsible for proper and safe use of the equipment. We strongly recommend that the operator read this Owner’s Manual and thoroughly understand all instructions before using this equipment.
We also strongly recommend instructing other users to properly start and operate the unit. This prepares them if they need to operate the equipment in an emergency.
CAUTION! Always disconnect spark plug wire and place the
wire where it cannot contact the spark plug to prevent accidental starting when setting up, transporting, adjusting or making repairs to your generator.
• The generator produces dangerously high voltage that can cause extremely hazardous electrical shock. Avoid contact with bare wires, terminals, etc. Never permit any unqualified person to operate or service the generator.
• Never handle any kind of electrical cord or device while standing in water, while barefoot or while hands or feet are wet. Dangerous electrical shock will result.
• The National Electric Code requires the frame and external electrically conductive parts of the generator be properly connected to an approved earth ground. Local electrical codes may also require proper grounding of the generator. Consult with a local electrician for grounding requirements in your area.
• Use a ground fault circuit interrupter in any damp or highly conductive area (such as metal decking or steel work).
• Do not use worn, bare, frayed or otherwise damaged electrical cord sets with the generator.
• Operate generator only on level surfaces and where it will not be exposed to excessive moisture, dirt, dust or corrosive vapors.
• Gasoline is highly FLAMMABLE and its vapors are EXPLOSIVE. Do not permit smoking, open flames, sparks or heat in the vicinity while handling gasoline. Avoid spilling gasoline on a hot engine. Comply with all laws regulating storage and handling of gasoline.
• Never add fuel while unit is running.
• Do not overfill the fuel tank. Always allow room for fuel expansion. If tank is over-filled, fuel can overflow onto a hot engine and cause FIRE or an EXPLOSION.
• Never store generator with fuel in tank where gasoline vapors might reach an open flame, spark or pilot light (as on a furnace, water heater or clothes dryer). FIRE or EXPLOSION may result.
• Generator exhaust gases contain DEADLY carbon monoxide gas.This dangerous gas, if breathed in sufficient concentrations, can cause unconsciousness or even death. Operate this equipment only in the open air where adequate ventilation is available.
• Allow at least 2 feet of clearance on all sides of generator or you could damage the unit. Never operate the unit inside any
room or enclosure where the free flow of cooling air into and out of the unit might be obstructed. Review “Cold Weather
Operation” on page 12.
1
-------------
DANGER
-------------
-------------
WARNING
-------------
-------------
CAUTION
-------------
DANGER! NEVER operate your generator indoors,
in an attached garage or near an open window.
2
• Never start or stop the unit with electrical loads connected to receptacles AND with connected devices turned ON. Start the engine and let it stabilize before connecting electrical loads. Disconnect all electrical loads before shutting down the generator.
• Do not insert objects through unit's cooling slots.
Never operate generator: in rain; in any enclosed compartment; if connected electrical devices overheat; if electrical output is lost; if engine or generator sparks; if flames or smoke are observed while unit is running; if unit vibrates excessively.
Note: Your generator is equipped with a spark arrestor muffler. The spark arrestor must be maintained in effective working order by the owner/ operator. In the State of California, a spark arrestor is required by law (Section 4442 of the California Public Resources Code). Other states may have similar laws. Federal laws apply on federal lands.
Study these SAFETY RULES carefully before installing, operating or servicing this equipment. Become familiar with this Owner’s Manual and with the unit. The generator can operate safely, efficiently and reliably only if it is properly installed, operated and maintained. Many accidents are caused by failing to follow simple and fundamental rules or precautions.
GENERAC
®
cannot possibly anticipate every possible circumstance that might involve a hazard. The warnings in this manual, and on tags and decals affixed to the unit are, therefore, not all-inclusive. If you use a procedure, work method or operating technique GENERAC
®
does not specifically recommend, you must satisfy yourself that it is safe for you and others. You also must make sure the procedure, work method or operating technique that you choose does not render the generator unsafe.
Despite the safe design of this generator, operating
this equipment imprudently, neglecting its maintenance or being careless can cause possible injury or death. Permit only responsible and capable persons to operate or maintain this equipment.
Potentially lethal voltages are generated by these
machines. Ensure all steps are taken to render the machine safe before attempting to work on the generator.
Parts of the generator are rotating and/or hot during
operation. Exercise care near running generators.
GENERAL HAZARDS
• For safety reasons, GENERAC®recommends that the installation, initial start-up and maintenance of this equipment is carried out by a GENERAC®/GUARDIAN®Authorized Dealer.
• The engine exhaust fumes contain carbon monoxide, which can be DEADLY. This dangerous gas, if breathed in sufficient concentrations, can cause unconsciousness or even death. This exhaust system must be installed properly, in strict compliance with applicable codes and standards. Following installation, you must do nothing that might render the system unsafe or in noncompliance with such codes and standards.
• Keep hands, feet, clothing, etc., away from drive belts, fans, and other moving or hot parts. Never remove any drive belt or fan guard while the unit is operating.
• Adequate, unobstructed flow of cooling and ventilating air is critical to correct generator operation. Do not alter the installation or permit even partial blockage of ventilation provisions, as this can seriously affect safe operation of the generator. The generator MUST be operated outdoors.
• When working on this equipment, remain alert at all times. Never work on the equipment when you are physically or mentally fatigued.
• Inspect the generator regularly, and contact your nearest GENERAC
®
/GUARDIAN®Authorized Dealer for parts needing
repair or replacement.
• Before performing any maintenance on the generator, disconnect its battery cables to prevent accidental start up. Disconnect the cable from the battery post indicated by a NEGATIVE, NEG or (–) first. Reconnect that cable last.
• Never use the generator or any of its parts as a step. Stepping on the unit can stress and break parts, and may result in dangerous operating conditions from leaking exhaust gases, fuel leakage, oil leakage, etc.
IMPORTANT SAFETY INSTRUCTIONS
Residential Portable Generator System
SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe operation be copied and posted near the unit's installation site. Safety should be stressed to all operators and potential operators of this equipment.
The engine exhaust from this product
contains chemicals known to the state
of California to cause cancer, birth
defects or other reproductive harm.
WARNING:
This product contains or emits chemicals
known to the state of California to cause
cancer, birth defects or other reproductive harm.
WARNING:
-------------
DANGER
-------------
ELECTRICAL HAZARDS
• All generators covered by this manual produce dangerous electrical voltages and can cause fatal electrical shock. Utility power delivers extremely high and dangerous voltages as does the generator when it is in operation. Avoid contact with bare wires, terminals, connections, etc., while the unit is running. Ensure all appropriate covers, guards and barriers are in place before operating the generator. If you must work around an operating unit, stand on an insulated, dry surface to reduce shock hazard.
• Do not handle any kind of electrical device while standing in
water, while barefoot, or while hands or feet are wet.
DANGEROUS ELECTRICAL SHOCK MAY RESULT.
• The National Electrical Code (NEC) requires the frame and
external electrically conductive parts of the generator to be connected to an approved earth ground. Local electrical codes also may require proper grounding of the generator electrical system.
• In case of accident caused by electric shock, immediately shut
down the source of electrical power. If this is not possible, attempt to free the victim from the live conductor. AVOID DIRECT CONTACT WITH THE VICTIM. Use a non­conducting implement, such as a rope or board, to free the victim from the live conductor. If the victim is unconscious, apply first aid and get immediate medical help.
• Never wear jewelry when working on this equipment. Jewelry
can conduct electricity resulting in electric shock, or may get caught in moving components causing injury.
FIRE HAZARDS
• For fire safety, the generator must be operated and maintained
properly. Operation always must comply with applicable codes, standards, laws and regulations. Adhere strictly to local, state and national electrical and building codes. Comply with regulations the Occupational Safety and Health Administration (OSHA) has established. Also, ensure that the generator is operated in accordance with the manufacturer’s instructions and recommendations. Do not alter the construction of generator or change controls which might create an unsafe operating condition.
• Keep a fire extinguisher near the generator at all times.
Extinguishers rated “ABC” by the National Fire Protection Association are appropriate for use on the standby electric system. Keep the extinguisher properly charged and be familiar with its use. If you have any question pertaining to fire extinguishers, consult your local fire department.
EXPLOSION HAZARDS
• Do not smoke around the generator. Wipe up any fuel or oil spills immediately. Ensure that no combustible materials are left on or near the generator, as FIRE or EXPLOSION may result. Keep the area surrounding the generator clean and free from debris.
• Gasoline is extremely EXPLOSIVE.
STANDARDS INDEX
In the absence of pertinent standards, codes, regulations and laws, the published information listed below may be used as a guideline for operation of this equipment.
1. NFPA No. 70, NFPA HANDBOOK OF NATIONAL ELECTRIC CODE.
2. Article X, NATIONAL BUILDING CODE, available from the American Insurance Association, 85 John Street, New York, N.Y. 10038.
3. AGRICULTURAL WIRING HANDBOOK, available from the Food and Energy Council, 909 University Avenue, Columbia, MO
65201.
4. ASAE EP-3634, INSTALLATION AND MAINTENANCE OF FARM STANDBY ELECTRICAL SYSTEMS, available from the American Society of Agricultural Engineers, 2950 Niles Road, St. Joseph, MI 49085.
5. NFPA No. 30, FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE.
3
IMPORTANT SAFETY INSTRUCTIONS
Residential Portable Generator System
1.1 UNPACKING
• Set the palleted carton on a rigid flat surface.
• Remove staples along bottom of carton that fasten carton to pallet. Open carton from top.
• Remove all packaging material.
• Remove separate accessory box.
• Lift carton off the generator.
• Remove generator from shipping pallet by removing bolts through the shipping brackets.
Figure 1 - Bracket Removal
1.1.1 ACCESSORY BOX
Check all contents. If any parts are missing or damaged locate an authorized dealer at 1-800-333-1322.
Contents include:
• Owner’s Manual
• Bolt-on tubular handle
• Wheel Axle
• 2 – Pneumatic Wheels
• 2 – Axle Bracket Assemblies
• 2 – Washers
• 2 – Wheel Spacers
• 2 – Cotter Pins
• Bolt-on Foot
• 6 – Carriage Bolts, Washers, Nuts
• Battery Charge Cable
• Spark Plug Wrench
• 2 Spark Plugs.
• Air Filter
• Pre-cleaner
1.2 ASSEMBLY
The generator requires some assembly prior to using it. If problems arise when assembling the generator, please call the Generator Helpline at 1-800-333-1322.
1.2.1 ASSEMBLING THE WHEEL KIT
The wheel kit is designed to greatly improve the portability of the generator. A socket wrench with a 9/16” socket, a 1/2” socket, a 1/2” wrench and a pair of pliers are the tools that will be needed for assembly of the wheel kit.
Note:The wheel kit is not intended for over-the-road use.
• Refer to Figure 2 shown on opposite page and install the wheel kit as follows:
• Place the generator on a hard flat surface.
• Stand at the engine end of the unit and gently tilt the generator forward, high enough to place wooden blocks beneath the cradle. This will allow space to install the wheel assemblies.
• Attach an axle bracket assembly with attached sleeve to either side of the frame. Ensure the sleeve faces outward.
• Slide the axle through the sleeves on the axle brackets.
• Slide one wheel with flat washer to the outside and a spacer to the inside onto each end of the axle. Make sure the air inflation valve on the wheel is facing outward.
• Insert retaining pins and using pliers, bend out the ends to prevent the pins from falling out of the axle. Remove the wooden blocks.
1.2.2 ASSEMBLING THE HANDLE
• Attach the handle by aligning one side of the handle on the cradle, then spread the handle around the cradle and let it spring into place. Secure the handle to the frame using the 5/16’ hex head bolts provided. Check each fastener to ensure that it is secure.
• Using the handle, lift the unit high enough to place wooden blocks under the unit. Attach the front support foot to the underside of the cradle using the 3/8” carriage bolts provided.
• Remove the shipping brackets from the cradle, if you have not already done so.
4
Section 1 – General Information
Residential Portable Generator System
Shipping
Bracket
(x4)
5
1.2.3 BATTERY CONNECTION
• The battery shipped with the generator has been provided fully charged. Caution must be taken when connecting the battery.
• Cut the tie wrap cable holding the RED and BLACK battery cables to the stator.
• Connect the RED battery cable to the battery Positive terminal (+). After making sure that the connection is tight, slip the rubber boot over the terminal connection.
• Connect the BLACK battery cable to the battery Negative terminal (–). Make sure the connection is tight.
• Double check all connections to ensure they are in the correct location and secure. See Figure 3 at right.
Figure 3 - Battery Connections
Section 1 - General Information
Residential Portable Generator System
Negative
Cable
Positive
Cable
Figure 2 - Handle Assembly
6
Section 2 – Operation
Residential Portable Generator System
OPERATION
2.1 KNOW THE GENERATOR
Read the Owner’s Manual and Safety Rules before operating this generator.
Compare the generator to this illustration to become familiarized with the locations of various controls and adjustments. Save this manual for future reference.
1) 12 Volt DC, 10 Amp Receptacle – This receptacle allows the capability to recharge a 12 volt DC storage battery with provided battery charge cables.
2) 120 Volt AC, 20 Amp, Duplex Receptacle – Supplies electrical power for the operation of 120 Volt AC, 20 Amp, single-phase, 60 Hz electrical lighting, appliance, tool and motor loads.
3) 120 Volt AC, 20A Duplex GFCI Receptacle –
Supplies ground fault protected electrical power for operation of 120 volt AC 20 amp, single-phase, 60 Hz electric lighting, appliances, tools and motor loads.
4) 120 Volt AC, 30 Amp Locking Receptacle – Supplies electrical power for the operation of 120 Volt AC, 30 Amp, single-phase, 60 Hz electrical lighting, appliance, tool and motor loads.
5) 120/240 Volt AC, 30 Amp Locking Receptacle –
Supplies electrical power for the operation of 120 and/or 240 Volt AC, 30 Amp, single-phase, 60 Hz, electrical lighting, appliance, tool and motor loads.
6) 120/240 Volt AC, 50 Amp Receptacle – Supplies electrical power for the operation of 120/240 Volt AC, 50 Amp, single-phase, 60 Hz, welder or motor loads.
7) Air Cleaner – Filters intake air as it is drawn into the engine.
8) Choke Knob – Used when starting a cold engine.
9) Winter / Summer Valve – See “Cold Weather Operation.”
(Section 2, page 12.)
10) Circuit Breakers (AC) – Each receptacle is provided with a push-to-reset circuit breaker to protect the generator against electrical overload. (50 amp uses toggle reset)
11) Fuel Tank – Tank holds 16 U.S. gallons of fuel.
12) Grounding Lug – Ground the generator to an approved
earth ground here. See page 9 for details.
13) Idle Control Switch – The idle control runs the engine at normal (high) speeds when there is an electrical load present and runs the engine at idle (low) speeds when a load is not present.
7
11
12
15
9
8
14
Figure 5 - Generator Controls
Figure 6 - Engine Control Panel
Figure 4 - Control Panel
14) Start/Run/Stop Switch – Controls the operation of the generator.
15) Oil Fill – Use this point to add oil to engine.
16) Fuse - 10 Amp – Protects the DC control circuit from
overload. If this fuse element has melted open the engine will not be able to crank and start.
2.2 CORD SETS AND CONNECTION
PLUGS
2.2.1 AC, 20 AMP, DUPLEX RECEPTACLE
This is a 120 Volt outlet protected against overload by a 20 Amp push-to-reset circuit breaker. Use each socket to power 120 Volt AC, single phase, 60 Hz electrical loads requiring up to a combined 2400 watts (2.4 kW) or 20 Amps of current. Use only high quality, well­insulated, 3-wire grounded cord sets rated for 125 Volts at 20 Amps (or greater).
Keep extension cords as short as possible, preferably less than 15 feet long, to prevent voltage drop and possible overheating of wires.
Figure 7 - 120 Volt AC, 20 Amp, Duplex Receptacle
2.2.2 120V AC, 20 AMP, GFCI RECEPTACLE
This unit is equipped with a ground fault circuit interrupter (GFCI). This device meets applicable federal, state and local codes.
A GFCI receptacle is different from conventional receptacles. In the event of a ground fault, a GFCI will trip and quickly stop the flow of electricity to prevent serious injury.
Definition: Instead of following its normal safe path, electricity passes through a persons body to reach the ground. For example, a defective appliance can cause a ground fault.
A GFCI receptacle does NOT
protect against circuit overloads, short circuits, or shocks. For example, electric shock can still occur if a person touches charged electrical wires while standing on a non-conducting surface, such as a wood floor.
Figure 8 - 120 VAC, 20 Amp GFCI Receptacle
Testing the GFCI: Test the GFCI outlet every month as follows:
• Plug a test lamp into the receptacle.
• Start the generator, the test lamp should be on.
• Press the “Test” button located on the front of the receptacle
to trip the device.
• This should stop the flow of electricity making the lamp shut
off. The yellow trip indicator should now be on.
• To restore the flow of electricity, press the “Reset” button on
the front of the receptacle. If the GFCI does not perform in this manner, do not use the receptacle. Contact a local service dealer.
• This outlet is protected against overload by a 20A push-to-
reset circuit breaker. Use the outlet to power 120V AC, single­phase, 60 Hz, electrical loads requiring up to a combined 2400 watts (2.4 kW) or 20 amps of current.
2.2.3 120V AC, 30 AMP RECEPTACLE
Use a NEMA L5-30 plug with this receptacle. Connect a 3-wire cord set rated for 125 Volts AC at 30 Amps (or greater) to the plug.
7
Section 2 – Operation
Residential Portable Generator System
Figure 9 - 120 VAC, 30 Amp Receptacle
Use this receptacle to operate 120 Volt AC, 60 Hz, single phase loads requiring up to 3600 watts (3.6 kW) of power at 30 Amps. The outlet is protected by a 30 Amp push-to-reset circuit breaker.
2.2.4 120/240V AC, 30 AMP RECEPTACLE
Use a NEMA L14-30 plug with this receptacle. Connect a suitable 4-wire grounded cord set to the plug and to the desired load. The cord set should be rated for 250 Volts AC at 30 Amps (or greater).
Figure 10 - 120/240 VAC, 30 Amp Receptacle
Use this receptacle to operate 120 Volt AC, 60 Hz, single phase loads requiring up to 3600 watts (3.6 kW) of power at 30 Amps or 240 Volt AC, 60 Hz, single phase loads requiring up to 7200 watts (7.2 kW) of power at 30 Amps. The outlet is protected by two 30 Amp push-to-reset circuit breakers.
2.2.5 12 VOLT DC, 10 AMP RECEPTACLE
This receptacle allows you to recharge a 12 Volt automotive or utility style storage battery with the battery charge cables provided. This receptacle can not recharge 6 Volt batteries and can not be used to crank an engine having a discharged battery. See the section "Charging a Battery" (page 12) before attempting to recharge a battery.
Figure 11 - 12 Volt DC, 10 Amp Receptacle
2.2.6 120/240 VOLT AC, 50 AMP RECEPTACLE
Use a NEMA 14-50 plug with this receptacle. Connect a 4-wire cord set rated for 250 Volts AC at 50 Amps to the plug.
Figure 12 - 120/240 VAC, 50 Amp Receptacle
Use this receptacle to operate 120/240 Volt AC, 60 Hz electrical loads requiring up to 12,000 watts (12.0 kW) of power. This receptacle is protected by a 50 Amp 2-pole circuit breaker.
8
Section 2 – Operation
Residential Portable Generator System
2.3 HOW TO USE THE GENERATOR
If you have any problems operating your generator, please call the generator helpline at 1-800-333-1322.
2.3.1 GROUNDING THE GENERATOR
The National Electrical Code requires that the frame and external electrically conductive parts of this generator be properly connected to an approved earth ground. Local electrical codes may also require proper
grounding of the unit. For that purpose, generally, connecting a No. 10 AWG (American Wire Gauge) stranded copper wire to the grounding wing nut and to an earth-driven copper or brass grounding rod (electrode) provides adequate protection against electrical shock. However, local codes may vary widely. Consult
with a local electrician for grounding requirements in your area.
Figure 13 - Grounding the Generator
Proper grounding of the generator will help prevent electrical shock in the event of a ground fault condition in the
generator or in connected electrical devices. Proper grounding also helps dissipate static electricity, which often builds up in ungrounded devices.
2.3.2 CONNECTING ELECTRICAL LOADS
DO NOT connect 240 Volt loads to 120 Volt receptacles. DO NOT connect 3-phase loads to the generator. DO NOT connect
50 Hz loads to the generator.
• Let engine stabilize and warm up for a few minutes after
starting.
• Plug in and turn on the desired 120 or 240 Volt AC, single
phase, 60 Hz electrical loads.
• Add up the rated watts (or amps) of all loads to be connected
at one time. This total should not be greater than (a) the rated wattage/amperage capacity of the generator or (b) circuit breaker rating of the receptacle supplying the power. See "Don't Overload the Generator" below.
2.4 DON’T OVERLOAD THE
GENERATOR
Overloading a generator in excess of its rated wattage capacity can result in damage to the generator and to connected electrical devices. Observe the following to prevent overloading the unit:
• Add up the total wattage of all electrical devices to be
connected at one time. This total should NOT be greater than the generator's wattage capacity.
• The rated wattage of lights can be taken from light bulbs. The
rated wattage of tools, appliances and motors can usually be found on a data plate or decal affixed to the device.
• If the appliance, tool or motor does not give wattage, multiply
volts times ampere rating to determine watts (volts x amps = watts).
• Some electric motors, such as induction types, require about
three times more watts of power for starting than for running. This surge of power lasts only a few seconds when starting such motors. Make sure you allow for this high starting wattage when selecting electrical devices to connect to your generator:
1. Figure the watts needed to start the largest motor.
2. Add to that figure the running watts of all other connected
loads.
The Wattage Reference Guide on page 10 is provided to assist you in determining how many items your generator can operate at one time. (Note: All figures are approximate. See data plate on appliance for wattage requirements.)
Generator Ground Lug
9
Section 2 – Operation
Residential Portable Generator System
2.5 WATTAGE REFERENCE GUIDE
Device . . . . . . . . . . . . . . . . . . . . . . .Running Watts
*Air Conditioner (12,000 Btu) . . . . . . . . . . . . . . . . .1700
*Air Conditioner (24,000 Btu) . . . . . . . . . . . . . . . . .3800
*Air Conditioner (40,000 Btu) . . . . . . . . . . . . . . . . .6000
Battery Charger (20 Amp) . . . . . . . . . . . . . . . . . . . . .500
Belt Sander (3") . . . . . . . . . . . . . . . . . . . . . . . . . . . .1000
Chain Saw . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1200
Circular Saw (6-1/2") . . . . . . . . . . . . . . . . . . .800 to 1000
*Clothes Dryer (Electric) . . . . . . . . . . . . . . . . . . . . .5750
*Clothes Dryer (Gas) . . . . . . . . . . . . . . . . . . . . . . . . .700
*Clothes Washer . . . . . . . . . . . . . . . . . . . . . . . . . . .1150
Coffee Maker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1750
*Compressor (1 HP) . . . . . . . . . . . . . . . . . . . . . . . .2000
*Compressor (3/4 HP) . . . . . . . . . . . . . . . . . . . . . . .1800
*Compressor (1/2 HP) . . . . . . . . . . . . . . . . . . . . . . .1400
Curling Iron . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .700
*Dehumidifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .650
Disc Sander (9") . . . . . . . . . . . . . . . . . . . . . . . . . . . .1200
Edge Trimmer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .500
Electric Blanket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .400
Electric Nail Gun . . . . . . . . . . . . . . . . . . . . . . . . . . . .1200
Electric Range (per element) . . . . . . . . . . . . . . . . . .1500
Electric Skillet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1250
*Freezer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .700
*Furnace Fan (3/5 HP) . . . . . . . . . . . . . . . . . . . . . . . .875
*Garage Door Opener . . . . . . . . . . . . . . . . . . .500 to 750
Hair Dryer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1200
Hand Drill . . . . . . . . . . . . . . . . . . . . . . . . . . .250 to 1100
Device . . . . . . . . . . . . . . . . . . . . . . .Running Watts
Hedge Trimmer . . . . . . . . . . . . . . . . . . . . . . . . . . . . .450
Impact Wrench . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .500
Iron . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1200
*Jet Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .800
Lawn Mower . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1200
Light Bulb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .100
Microwave Oven . . . . . . . . . . . . . . . . . . . . . .700 to 1000
*Milk Cooler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1100
Oil Burner on Furnace . . . . . . . . . . . . . . . . . . . . . . . .300
Oil Fired Space Heater (140,000 Btu) . . . . . . . . . . . . .400
Oil Fired Space Heater (85,000 Btu) . . . . . . . . . . . . . .225
Oil Fired Space Heater (30,000 Btu) . . . . . . . . . . . . . .150
*Paint Sprayer, Airless (1/3 HP) . . . . . . . . . . . . . . . .600
Paint Sprayer, Airless (handheld) . . . . . . . . . . . . . . . .150
Radio . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50 to 200
*Refrigerator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .700
Slow Cooker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .200
*Submersible Pump (1-1/2 HP) . . . . . . . . . . . . . . . .2800
*Submersible Pump (1 HP) . . . . . . . . . . . . . . . . . . .2000
*Submersible Pump (1/2 HP) . . . . . . . . . . . . . . . . .1500
*Sump Pump . . . . . . . . . . . . . . . . . . . . . . . .800 to 1050
*Table Saw (10") . . . . . . . . . . . . . . . . . . . . .1750 to 2000
Television . . . . . . . . . . . . . . . . . . . . . . . . . . . .200 to 500
Toaster . . . . . . . . . . . . . . . . . . . . . . . . . . . .1000 to 1650
Weed Trimmer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .500
*Allow 3 times the listed watts for starting these devices.
10
Section 2 – Operation
Residential Portable Generator System
2.6 BEFORE STARTING THE GENERATOR
Prior to operating the generator, engine oil and gasoline will need to be added, as follows:
2.6.1 ADDING ENGINE OIL
NOTE: When adding oil to the engine crankcase in the future, use only high quality detergent oil rated with API service classification SF or SG SAE 30 weight. Use no special additives.
Select the oil’s viscosity grade according to the expected operating temperature. Do not use SAE 10W-40.
Above 40°F, use SAE 10W-30 or SAE 30.
Below 40°F, use synthetic 5W-20 or 5W-30.
Although multi-viscosity oils (5W-30, 10W-30, etc.) improve starting in cold weather, these multi-viscosity oils will result in increased oil consumption when used above 32°F. Check your engine oil level more frequently to avoid possible damage from running low on oil.
• Place generator on a level surface.
• Clean area around oil fill and remove oil fill cap and dipstick.
Wipe dipstick clean.
Slowly fill engine with oil through the oil fill opening until it reaches the full mark on the dipstick. Stop filling occasionally to check oil level. DO NOT OVERFILL.
• Install dipstick. Install oil fill cap and finger tighten securely.
• Check engine oil level before starting each time thereafter.
2.6.2 ADDING GASOLINE
WARNING: Never fill fuel tank indoors. Never fill
fuel tank when engine is running or hot. DO NOT
light a cigarette or smoke when filling the fuel
tank.
Caution: Do not overfill the fuel tank. Always
leave room for fuel expansion.
• Use regular UNLEADED gasoline with the generator engine. Do not use premium gasoline. Do not mix oil with gasoline.
• Clean area around fuel fill cap, remove cap.
• Slowly add unleaded regular gasoline to fuel tank. Be careful not to overfill. Allow about 1/2" of tank space for fuel expansion, as shown here.
• Install fuel cap and wipe up any spilled gasoline.
Figure 14 - Fuel Tank
IMPORTANT: It is important to prevent gum deposits from forming in fuel system parts such as the carburetor, fuel hose or tank during storage. Alcohol-blended fuels (called gasohol, ethanol or methanol) can attract moisture, which leads to separation and formation of acids during storage. Acidic gas can damage the fuel system of an engine while in storage. To avoid engine problems, the fuel system should be emptied before storage of 30 days or longer. See "Storage" on page 18. Never use engine or carburetor cleaner products in the fuel tank as permanent damage may occur.
2.7 TO START THE ENGINE
WARNING! Never start or stop engine with electrical
devices plugged into the receptacles AND devices turned on.
• Unplug all electrical loads from the unit's receptacles before starting the engine.
• Make sure the unit is in a level position.
• Open the fuel shut-off valve.
Figure 15 - Fuel Shut-off Valve
• Locate the Idle Control ON/OFF switch on the control panel and set it to the “OFF” position.
Figure 16 - Idle Control Switch
Section 2 – Operation
Residential Portable Generator System
11
-------------
WARNING
-------------
• Move engine CHOKE knob to “Full Choke” position.
Figure 17 - Full Choke Position
• To start engine, press and hold the Start/Run/Stop switch in the “Start” position. The engine will crank and attempt to start. When the engine starts, release the switch to the run position.
• When the engine starts, move choke knob to “1/2 Choke” position until the engine runs smoothly and then to “Run” position. If engine falters, move choke knob to “1/2 Choke” position until the engine runs smoothly and then to “Run” position.
Note: If engine fires, but does not continue to run, move choke lever to “Full Choke” and repeat starting instructions.
2.8 STOPPING THE ENGINE
• Shut off all loads, then unplug the electrical loads from generator panel receptacles. Never start or stop the engine with electrical devices plugged in and turned on.
• Turn “Off” the Idle Control switch (if on).
• Let engine run at no-load for several minutes to stabilize the internal temperatures of engine and generator.
• Move Start/Run/Stop switch to “Off” position.
• Close fuel valve.
IMPORTANT: Do not overload the generator. Also, do not overload individual panel receptacles. These outlets are protected against overload with push-to-reset-type circuit breakers. If amperage rating of any circuit breaker is exceeded, that breaker opens and electrical output to that receptacle is lost. Read “Don’t Overload the Generator” on page 9 carefully.
2.9 AUTOMATIC IDLE CONTROL
This feature is designed to greatly improve fuel economy. When this switch is turned On,” the engine will only run at its normal fast governed engine speed when electrical load is connected. When the load is removed, the engine will run at a reduced speed of 2100 RPM. With the switch Off,” the engine runs at the normal fast engine speed all the time. Always have the switch
OFF when starting and stopping the engine.
2.10 COLD WEATHER OPERATION/ DE-ICER
Under certain weather conditions (temperatures below 40° F (4° C) and a high dew point), the engine may experience icing of the carburetor and/or the crankcase breather system. To eliminate this problem, this generator engine is fitted with a winter/summer valve. this directs hot air into the carburetor during cold weather operation. Always make sure the winter/summer valve is in the correct location relative to the weather conditions.
2.11 LOW OIL PRESSURE SHUTDOWN
SYSTEM
The engine is equipped with a low oil pressure sensor that shuts down the engine automatically when the oil pressure drops below 10 psi. If the engine shuts down by itself and the fuel tank has enough gasoline, check engine oil level.
2.11.1 INITIAL START-UP
A delay built into the low oil shutdown system allows oil pressure to build during starting. The delay allows the engine to run for about 10 seconds before sensing oil pressure.
2.11.2 SENSING LOW OIL PRESSURE
If the system senses low oil pressure during operation, the engine shuts down.
2.11.3 RESTARTING
If you try to restart the engine within 10 seconds after it shuts down, the engine may NOT start. The system needs 5 to 10 seconds to reset.
If you do restart the engine after such a shutdown and have not corrected the low oil pressure, the engine runs for about 10 seconds as described above and then stops.
Section 2 – Operation
Residential Portable Generator System
12
2.12 CHARGING A BATTERY
DANGER! Storage batteries give off explosive hydrogen
gas while recharging. An explosive mixture will remain around the battery for a long time after it has been charged. The slightest spark can ignite the hydrogen and cause an explosion. Such an explosion can shatter the battery and cause blindness or other serious injury.
DANGER! Do not permit smoking, open flame, sparks or
any other source of heat around a battery. Wear protective goggles, rubber apron and rubber gloves when working around a battery. Battery electrolyte fluid is an extremely caustic sulfuric acid solution that can cause severe burns. If spill occurs flush area with clear water immediately.
Your generator has the capability of recharging a discharged 12 Volt automotive or utility style storage battery. Do not use the
unit to charge any 6 Volt batteries. Do not use the unit to crank an engine having a discharged battery.
To recharge 12 Volt batteries, proceed as follows:
• Check fluid level in all battery cells. If necessary, add ONLY distilled water to cover separators in battery cells. Do not use
tap water.
• If the battery is equipped with vent caps, make sure they are installed and are tight.
• If necessary, clean battery terminals.
• Connect battery charge cable connector plug to panel receptacle identified by the words "12-VOLT D.C."
• Connect battery charge cable clamp with red handle to the positive (+) battery terminal.
• Connect battery charge cable clamp with black handle to the negative (-) battery terminal.
• Start engine. Let the engine run while battery recharges. Engine idle control switch must
be in off position for battery
charging.
• When battery has charged, shut down engine.
Note: Use an automotive hydrometer to test battery state of charge and condition. Follow the hydrometer manufacturer's instructions carefully. Generally, a battery is considered to be at 100% state of charge when specific gravity of its fluid (as measured by hydrometer) is 1.260 or higher.
Section 2 – Operation
Residential Portable Generator System
13
3.2.1 GENERATOR SPECIFICATIONS
MODEL GPS 15000
Model # 004582-1 Rated Max. Power 15.0 kW Surge Power 22.5 kW Rated AC Voltage 120/240 Rated Max AC Load Current @ 240V 62.5 Amps Current @ 120V 125.0 Amps Rated Frequency 60 Hz @ 3600 RPM Phase Single Phase Rated DC Voltage 12 Volts Rated Max DC Load Current @ 12 Volts 10 Amperes
3.2.2 ENGINE SPECIFICATIONS
Rated Horsepower @ 3600 RPM 30 Displacement 992cc Spark Plug Type Champion RC14YC or Equivalent Spark Plug Gap 0.030 inch or (0.76 mm) Gasoline Capacity 16 U.S. gallons Oil Type Summer – SAE 30 or 10W-30 Winter – Synthetic 5W-20 or 5W-30 Oil Capacity w/ Filter Change = 1.5 Qts. w/o Filter Change = 1.2 Qts. Run Time/Fuel 10 Hours / 1.6 gallons per hour
Consumption-1/2 Load
Check Oil Level Service Air Pre-Cleaner ** Change Oil and Oil Filter‡ *
Clean Spark Arrestor Screen Adjust Valve Clearance Service Air Cleaner **
Replace Spark Plugs
Change oil after first 8 hours of operation then every season. * Change oil and oil filter every month when operating under heavy load or in high temperatures. ** Clean more often under dirty or dusty operating conditions. Replace air cleaner parts if very dirty..
14
Section 3 — Maintenance
Residential Portable Generator System
3.1 MAINTENANCE SCHEDULE
Follow the calendar intervals. More frequent service is required when operating in adverse conditions noted below.
Operation Maintenance Daily Every Season Every Season Every Season
PRODUCT SPECIFICATIONS
15
3.3 GENERAL RECOMMENDATIONS
The warranty of the generator does not cover items that have been subjected to operator abuse or negligence. To receive full value from the warranty, the operator must maintain the generator as instructed in this manual.
Some adjustments will need to be made periodically to properly maintain the generator.
All adjustments in the Maintenance section (3) of this manual should be made at least once each season. Follow the requirements in the "Maintenance Schedule" chart on page 14.
NOTE: Once a year you should replace the spark plug and replace the air filter. A new spark plug and clean air filter assure proper fuel-air mixture and help your engine run better and last longer.
3.3.1 GENERATOR MAINTENANCE
Generator maintenance consists of keeping the unit clean and dry. Operate and store the unit in a clean dry environment where it will not be exposed to excessive dust, dirt, moisture or any corrosive vapors. Cooling air slots in the generator must not become clogged with snow, leaves, or any other foreign material.
Check the cleanliness of the generator frequently and clean when dust, dirt, oil, moisture or other foreign substances are visible on its exterior surface.
CAUTION! Never insert any object or tool through the air
cooling slots, even if the engine is not running.
Note: DO NOT use a garden hose to clean generator. Water can enter the engine fuel system and cause problems. In addition, if water enters the generator through cooling air slots, some water will be retained in voids and crevices of the rotor and stator winding insulation. Water and dirt buildup on the generator internal windings will eventually decrease the insulation resistance of these windings.
3.3.2 TO CLEAN THE GENERATOR
• Use a damp cloth to wipe exterior surfaces clean.
• A soft, bristle brush may be used to loosen caked on dirt, oil, etc.
• A vacuum cleaner may be used to pick up loose dirt and debris.
• Low pressure air (not to exceed 25 psi) may be used to blow away dirt. Inspect cooling air slots and openings on the generator. These openings must be kept clean and unobstructed.
3.3.3 ENGINE MAINTENANCE
DANGER! When working on the generator, always disconnect negative cable from battery. Also disconnect spark plug wires from spark plug and keep wire away from spark plug.
3.3.4 CHECKING OIL LEVEL
See the “BEFORE STARTING THE GENERATOR” section on page 10 for information on checking the oil level. The oil level should be checked before each use, or at least every eight hours of operation. Keep the oil level maintained.
3.3.5 CHANGING THE OIL AND OIL FILTER
Change the oil and filter after the first eight hours of operation. Change the oil every 100 hours thereafter. If you are running this unit under dirty or dusty conditions, or in extremely hot weather, change the oil more often.
Use the following instructions to change the oil while the engine is still warm:
• Clean area around oil drain hose and plug.
• Remove oil drain plug from end of hose and oil fill plug to drain oil completely into a suitable container.
• When oil has completely drained, install oil drain plug and tighten securely.
• Place a suitable container beneath the oil filter and turn filter counterclockwise to remove. Discard according to local regulations.
• Coat gasket of new filter with clean engine oil. Turn filter clockwise until gasket contacts lightly with filter adapter. Then tighten an additional 3/4 turn.
• Fill oil sump with recommended oil. (See “Before Starting the Generator” on page 10 for oil recommendations).
• Wipe up any spilled oil.
Section 3 — Maintenance
Residential Portable Generator System
3.3.6 REPLACING THE SPARK PLUG
Use Champion RC14YC spark plug or equivalent. The correct air gap is 0.76 mm (0.030 in.). Replace the plug once each year. This will help your engine start easier and run better.
1. Stop the engine and pull the spark plug wire off of the spark plug.
2. Clean the area around the spark plug and remove it from the cylinder head.
3. Set the spark plug's gap to 0.76 mm (0.030 in.). Install the correctly gapped spark plug into the cylinder head.
Figure 18 - Spark Plug Gap
3.4 SERVICE AIR CLEANER
Your engine will not run properly and may be damaged if you run it using a dirty air cleaner. Clean or replace the air cleaner paper filter once a year. Clean or replace more often if operating under dusty conditions. Clean foam pre-cleaner every month or more often under dusty conditions.
Figure 20 - Air Cleaner
To clean or replace foam pre-cleaner:
• Remove air cleaner cover, then foam pre-filter.
Wash pre-cleaner in soapy water. Squeeze pre-filter dry in clean cloth (DO NOT TWIST).
• Clean air cleaner cover before re-installing it.
To clean or replace paper air filter:
• Remove air cleaner cover; then remove foam pre-filter (service
if necessary) and remove paper filter.
• Clean paper filter by tapping it gently on a solid surface. If the
filter is too dirty, replace it with a new one. Dispose of the old filter properly.
• Clean air cleaner cover then slip pre-cleaner over filter. Next
insert new paper filter into the base of the air cleaner. Re­install air cleaner cover.
Note: To order a new air filter, please contact the nearest authorized service center at 1-800-333-1322.
3.5 CLEAN SPARK ARRESTOR
SCREEN
The engine exhaust muffler has a spark arrestor screen. Inspect and clean the screen at least once each year. If unit is used regularly, inspect and clean more often.
NOTE: If you use your generator on any forest­covered, brush-covered or grass-covered unimproved land, it must equipped with a spark arrestor. The spark arrestor must be maintained in good condition by the owner/operator.
Clean and inspect the spark arrestor as follows:
• Remove the screen retaining bracket by removing the screw.
• Slide the spark arrestor screen out from the tail pipe.
• Inspect screen and replace if torn, perforated or otherwise
damaged. DO NOT USE a defective screen. If screen is not damaged, clean it with commercial solvent.
• Replace the screen and the retaining bracket.
Section 3 — Maintenance
Residential Portable Generator System
16
Cover
Pre-Cleaner
Base
Filter
Figure 21 - Spark Arrestor
3.6 ADJUSTING VALVE CLEARANCE
After the first 50 hours of operation, you should adjust the valve clearance in the engine.
Important: If you feel uncomfortable about doing this procedure
or you don't have the proper tools, please take your generator in to the nearest service center to have the valve clearance adjusted. This is a very important step to insure longest life for your engine.
To adjust valve clearance:
• Make sure the engine is at room temperature.
• Make sure that the spark plug wire is removed from the spark plug and out of the way.
• Remove the four screws attaching the valve cover with a #2 or #3 phillips screwdriver.
• Make sure the piston is at Top Dead Center (TDC) of its compression stroke (both valves closed). To get the piston at TDC, remove the intake screen at the front of the engine to gain access to the flywheel nut. Use a large socket and socket wrench to rotate the nut and hence the engine. While watching the piston through the spark plug hole. The piston should move up and down. The piston is at TDC when it is up as high as it can go.
• Loosen the rocker jam nut. Use an 10mm allen wrench to turn the pivot ball stud while checking clearance between the rocker arm and the valve stem with a feeler gauge. Correct clearance is 0.002-0.004 inch (0.05-0.1 mm).
NOTE: You must hold the rocker arm jam nut in place as you turn the pivot ball stud.
When valve clearance is correct, hold the pivot ball stud in place with the allen wrench and tighten the rocker arm jam nut. Tighten the jam nut to 174 in/lbs. torque. After tightening the jam nut, recheck valve clearance to make sure it did not change.
Figure 22 - Valve Clearance Adjustment
• Install new valve cover gasket.
• Re-attach the valve cover.
NOTE: Start all four screws before tightening or you will not be able to get all the screws in place. Make sure the valve cover gasket is in place.
• Re-attach the spark plug wire to the spark plug.
• Repeat the process for the other cylinder.
Section 3 — Maintenance
Residential Portable Generator System
17
3.7 GENERAL
The generator should be started at least once every seven days and be allowed to run at least 30 minutes. If this cannot be done and you must store the unit for more than 30 days, use the following information as a guide to prepare it for storage.
 DANGER! NEVER store engine with fuel in
tank indoors or in enclosed, poorly ventilated areas where fumes may reach an open flame, spark or pilot light as on a furnace, water heater, clothes dryer or other gas appliance.
3.8 LONG TERM STORAGE
It is important to prevent gum deposits from forming in essential fuel system parts such as the carburetor, fuel hose or tank during storage. Also, experience indicates that alcohol-blended fuels (called gasohol, ethanol or methanol) can attract moisture, which leads to separation and formation of acids during storage. Acidic gas can damage the fuel system of an engine while in storage.
To avoid engine problems, the fuel system should be emptied before storage of 30 days or longer, as follows:
• Remove all gasoline from the fuel tank.
DANGER! Drain fuel into approved container
outdoors, away from open flame. Be sure engine is
cool. Do not smoke.
• Start and run engine until engine stops from lack of fuel.
• While engine is still warm, drain oil from crankcase. Refill with recommended grade.
• Remove spark plugs and pour about 1/2 ounce (15 ml) of engine oil into the cylinders. Cover spark plug hole with rag. Press the “Start” button and allow engine to crank for 2 seconds. Then press the “Stop” button.
CAUTION! Avoid spray from spark plug holes
when cranking engine.
• Install and tighten spark plugs. Do not connect spark plug wires.
• Clean the generator outer surfaces. Check that cooling air slots and openings on generator are open and unobstructed.
• Store the unit in a clean, dry place.
3.9 OTHER STORAGE TIPS:
• Do not store gasoline from one season to another.
• Replace your gasoline can if your can starts to rust. Rust and/or dirt in your gasoline will cause problems with the carburetor and fuel system.
• If possible, store your unit indoors and cover it to give protection from dust and dirt. BE SURE TO EMPTY THE
FUEL TANK.
• If it is not practical to empty the fuel tank and the unit is to be stored for some time, use a commercially available fuel stabilizer added to the gasoline to increase the life of the gasoline.
• Cover your unit with a suitable protective cover that does not retain moisture.
DANGER! NEVER cover your generator while
engine and exhaust area are warm.
Section 3 — Maintenance
Residential Portable Generator System
18
19
4.1 TROUBLESHOOTING
Engine is running, but no AC 1. Circuit breaker is open. 1. Reset circuit breaker. output is available. 2. Poor connection or defective cord set. 2. Check and repair.
3. Connected device is bad. 3. Connect another device that is in good condition.
4. Fault in generator. 4. Contact Authorized Service Facility.
Engine runs good but bogs 1. Short circuit in a connected load. 1. Disconnect shorted electrical load. down when loads are connected. 2. Generator is overloaded. 2. See
“Don’t Overload the Generator” on page 9.
3. Engine speed is too slow. 3. Contact Authorized Service Facility.
4. Shorted generator circuit. 4. Contact Authorized Service Facility.
Engine will not crank. 10 amp fuse at rear of generator Replace fuse with only an identical
control panel has melted open. 10-amp replacement fuse.
Engine will not start; or starts 1. Dirty air cleaner. 1. Clean or replace air cleaner. and runs rough. 2. Out of gasoline. 2. Fill fuel tank.
3. Stale gasoline. 3. Drain fuel tank and fill with fresh fuel.
4. Spark plug wire not connected to 4. Connect wire to spark plug.
spark plug.
5. Bad spark plug. 5. Replace spark plug.
6. Water in gasoline. 6. Drain fuel tank; fill with fresh fuel.
7. Overchoking. 7. Put choke knob to No Choke position.
8. Low oil level. 8. Fill crankcase to proper level.
9. Excessive rich fuel mixture. 9. Contact Authorized Service Facility.
10. Intake valve stuck open or closed. 10. Contact Authorized Service Facility.
11. Engine has lost compression. 11. Contact Authorized Service Facility.
Engine shuts down during 1. Out of gasoline. 1. Fill fuel tank. operation. 2. Low oil level. 2. Fill crankcase to proper level.
3. Fault in engine. 3. Contact Authorized Service Facility.
Engine lacks power. 1. Load is too high. 1. See
“Don’t Overload the Generator” on page 9.
2. Dirty air filter. 2. Replace air filter.
3. Engine needs to be serviced. 3. Contact Authorized Service Facility.
Engine “hunts” or falters. 1. Choke is opened too soon. 1. Move choke to halfway position until
engine runs smoothly.
2. Carburetor is running too rich or too 2. Contact Authorized Service Facility.
lean.
No Battery Charge DC output. 1. Battery posts are corroded. 1. Clean battery posts.
2. Battery cable is bad. 2. Replace cable.
3. Battery is defective. 3. Check battery condition; replace if defective.
4. Receptacle is bad. 4. Contact Authorized Service Facility.
Section 4 — Troubleshooting
Commercial-Industrial-Residential Portable Generator System
SYMPTOM CAUSE SOLUTION
MAKES A HOME GENERATOR READY!
1.
3.
4.
5.
6.
7.
2.
GENERATOR READY KIT
SECTION 5 - INSTALLATION GUIDE FOR GENERATOR READY KIT
20
KIT INCLUDES:
1. 50 AMP PLUG ON 5FT. POWER CORD
Use with ULTRA SOURCE portable generator to supply power to load center.
2. THE EXTERNAL CONNECTION BOX
Located outside the home where the generator will be operated.
3. 30’ FLEXIBLE CONDUIT
Pre-wired from the automatic transfer switch with built­in 12 circuit load center for connection to the external connection box.
4. PRE-WIRED AUTOMATIC TRANSFER SWITCH* AND
5. EMERGENCY LOAD CENTER WITH 12 CIRCUITS
Installed within 1 foot of the home’s main distribution panel. This transfer switch will provide smooth and safe transition between utility and generator power. Eliminates the need to run extension cords.*When used
with a portable generator the transfer from utility to generator power will require that some manual connections are performed by the user. (See page 25)
6. 2’ PRE-WIRED CONDUIT FOR EASY CONNECTION TO THE HOME’S MAIN DISTRIBUTION PANEL
8. 5’ DC SIGNAL HARNESS
Provides signal from the ULTRA SOURCE portable generator to the transfer switch.
9. 12 UL LISTED WIRE NUTS (not shown)
TOOLS REQUIRED:
Drill, drill bits, hole saw (type and length will be determined by the materials you will be drilling and cutting), open-end wrenches or adjustable wrenches, socket wrenches or nut drivers, standard and Phillips screwdrivers, sledge hammer, level, pencil, channel-lock pliers and safety goggles.
ITEMS YOUR MUST PURCHASE:
70 AMP double pole circuit breaker (must be the same type as in your main electrical distribution panel)
Ground rod (8 foot) with grounding strap (No. 10 AWG stranded copper)
Silicone caulk
Fasteners - to mount connection box and automatic transfer switch
Power cord clamp - to secure power cord at the entrance point to the external connection box
1. PLAN THE LOCATION OF YOUR GENERATOR.
NOTE: Do not place the generator directly under a window.
Select an area outside of your home where you can easily transport the portable generator to and from. Keep in mind that the generator must have free air flow for proper operation and to ensure there is no possibility for exhaust gases to build up.
2. Drive an 8-foot grounding rod into the ground to grade (so that no part is exposed above ground).
3. Determine where the flexible conduit will pass through the house from inside to outside. When you are certain you have clearance on each side of the wall, drill a small pilot hole through the wall to mark the location. . Drill a 1-3/4” diameter hole through the sheathing and siding with hole saw.
4. While adhering to all local electrical codes, route the 30 foot conduit along ceiling/floor joists and wall studs to the location where the conduit will pass through the wall to the exterior of the house.
5. From the inside of the house, feed the end of the 30­foot conduit (INCLUDED and pre-wired from transfer switch) through the wall to outside.
1-3/4”
Diameter Hole
1-3/4”
Diameter Hole
1
3
Drill Hole Through House
3
Portable Generator Placement
Drill Pass Through Hole
3
Illustration at left shows the Guardian Ultra Source 15,000 watt portable generator placed outside the home and connected to the weather protective external box. The ground rod and ground strap show a suggested location only. When fully installed the ground rod will not protrude above ground level.
2
Silicone
Caulk
The outer diameter of the
conduit connector is 1-11/16”
Feed Conduit and Wires
5
21
SECTION 5 - INSTALLATION GUIDE
FOR GENERATOR READY KIT
6. Remove the threaded lock nut from the conduit coupling.
7. Remove the knock out
in the lower right corner of the external connection box. From the rear of the connection box, feed wires & 4 pin plug into box. Slip the lock nut over wires and plug and tighten securely onto conduit coupling. Connect the black, red, and white wires to separate threaded lugs and tighten securely. Fasten the green ground wire securely beneath the hex nut on the grounding stud at the bottom of the box. Tighten securely to ensure good contact with metal box.
NOTE: THE 4-PIN PLUG WILL not be connected to any mating plug or other wires at this time.
8. Using appropriate
fasteners, mount external connection box over pre-drilled hole to fully conceal the hole. (Seal around the hole and conduit with insulating material and/or silicone caulk from both outside and inside of house.)
The external connection box must be locked to ensure
safety and to discourage tampering.
9. Locate automatic transfer switch with built-in
emergency load center within one foot of main distribution panel. The automatic transfer switch can be located to the left or right of main distribution panel. Hold transfer switch against the mounting surface. Level the transfer switch and mark the mounting holes. Drill the appropriate size pilot holes. Mount the automatic transfer switch to mounting surface with appropriate fasteners.
The outer diameter of the threaded end is 15/16 inches.
Knockout
Threaded Lock Nut
6
Connect Wires
7
--- WARNING ---
Mount External Connection Box
11b
1ft.
Mounting Automatic Transfer Switch
9
DANGER: Although you may choose to perform electrical connections yourself, Generac Power Systems, Inc. recommends that a licensed electrician or individual with complete knowledge of electricity perform the procedures in sections 10a and 10b.
DANGER: Switch service main circuit breaker to “off” or open position prior to removal of cover or removal of any wiring of the main electrical distribution panel. The wires connected to the service main circuit breaker remain live or “hot”. Avoid contact with these wires and the service main circuit breaker connection lugs.
SECTION 5 - INSTALLATION GUIDE FOR GENERATOR READY KIT
22
NOTE: Balance must be maintained when moving circuit locations from main electrical distribution panel to emergency load center. Circuit breaker positions alternate buss bars vertically. Circuits sharing a neutral wire should either be moved together to adjacent positions in emergency load center or not moved. If you are unsure of proper procedure or if your installation differs from that described in this guide, consult a licensed professional at this time.
10a. Remove the main electrical distribution panel cover.
Remove appropriate size knockout from the bottom or side of the main panel. (A 2-foot flexible conduit is pre-wired from the transfer switch with built-in load center). Remove threaded lock nut from conduit coupling. Feed all wires through knockout into main panel. Slip lock nut over wires and tighten securely onto conduit coupling.
NOTE: Circuits to be moved must be protected by same size breaker. For example, a 15 amp 120V circuit in emergency load center will replace a 15 amp 120V circuit in main panel.
10b. In your main panel, remove the black (hot) wire from
a circuit breaker that protects a circuit you want to have powered in the event of a power failure. Wire nut the black wire to the matching circuit lead wire from the emergency circuit breaker from load center in the transfer switch. (All circuit wires are color coded and labeled for easy identification). Repeat this process with remaining circuits to be powered by the generator. White wires (neutral) in your main distribution panel should remain connected to neutral bar. It is not necessary to move them. The emergency load center in the transfer switch supplies the following circuits: (5) 15A/120V, (3) 20A/120V, (1) 20A/240V and (1) 30A/240V.
11. Install the 70 Amp double pole circuit breaker that
you have purchased into main electrical distribution panel. This circuit breaker must be compatible with your main electrical distribution panel. It may be necessary to reposition remaining circuit breakers or remove circuit breakers that have been disconnected to accommodate the insertion of the 70 Amp double pole circuit breaker. Connect white wire to the main distribution panel neutral bar. Connect solid green wire to main electrical panel ground bar. Connect the black and red wires to the 70 Amp double pole circuit breaker. Replace electrical distribution panel cover.
YOUR GUARDIAN
®
GENERATOR READY KIT
IS NOW INSTALLED!
Install 70 AMP Circuit Breaker
11
70
70
UL approved wire nuts are included with installation kit.
Connection of Emergency Circuits
10b
Connection of Emergency Circuits
10a
23
SECTION 5 - INSTALLATION GUIDE FOR GENERATOR READY KIT
The GUARDIAN® Generator Ready Kit gives you the ability to hook up a GUARDIAN
®
ULTRA SOURCE portable generator to provide power safely and conveniently to vital items in your home including hard wired items. Included in the kit is a 5 foot electrical power cord and a 5 foot DC signal harness. The power cord contains 4 wires (black & red), neutral (white) and ground (green) wires. At one end are the terminal connectors. At the other end is the male connector (NEMA 14-50) which plugs into the GUARDIAN
®
ULTRA SOURCE portable generator’s control panel. To install this option, insert the terminal wire end of the power cord into the bottom of the external connection box through the conduit clamp (not included) from the outside. Allow about an inch of the power cord insulation to enter beyond the clamp to the inside of the box. TIghten clamp securely. Attach ground wire (green) to the bottom of the box using the supplied ground screw and pre-drilled hole. Connect red, black and white wires each to separate lug posts. Make sure hold down nuts are tightened securely. The 5 foot DC signal harness allows semi­automatic transfer switch operation. You simply attach the four-pin plug to its mating plug within the external connection box. At the other end is a V-type connector that plugs into the 12-volt DC receptacle on the portable generator control panel. Instructions for these items are detailed on the following page (Page 25).
USING THE GENERATOR READY KIT WITH ULTRA SOURCE PORTABLE GENERATOR
CAUTION: If you are connecting the 5 foot power cord after the 30 foot conduit has been connected inside of the external
connection box you must match the black, red and white wires to the lugs of the wires previously placed. (For example: black to black; red to red, etc.) Failure to match wires may result in damage to generator and house wiring.
EXTERNAL
CONNECTION BOX
Lug Posts
Bring power cord through here
NEMA 14-50 Receptacle
ULTRA SOURCE PORTABLE GENERATOR CONTROL PANEL
5 FOOT POWER CORD
WITH PLUG
50 AMP POWER PLUG
NEMA 14-50 Plug
Ground
Lug
12 Volt DC Receptacle
5 FOOT DC SIGNAL HARNESS
SECTION 6 - OPERATION OF GENERATOR WITH GENERATOR READY KIT
24
GENERATOR READY KIT
TRANSFER TO GENERATOR POWER SOURCE WHEN UTILITY POWER FAILS
1. Connect ground strap to generator’s grounding lug
and to grounding rod.
2. Set the generator’s 50 amp circuit breaker to its OFF
(or open) position.
3. Insert the NEMA 14-50 plug (from the power cord that
you have installed) into the mating receptacle on the generator control panel.
4. Start the generator.
5. Let the engine stabilize and warm up for a few minutes.
6. Insert the V-type plug (on the DC signal harness
you have connected within the external connection box) into the 12 volt DC receptacle on the generator control panel. The insertion of this plug will send a signal to the transfer switch to shift the contactor to the standby position.
7. Set the generator’s 50 amp circuit breaker to its’ ON
(or closed) position to send the generator power to the load center in the transfer switch.
TRANSFER BACK TO UTILITY POWER SOURCE
When utility power has been restored, you will want to transfer back to that source and shut down the generator. This can be accomplished as follows:
1. Set the generator’s 50 amp circuit breaker to its OFF (or open) position.
2. Remove the V-type plug (on the DC signal harness that was connected within the external connection box) from the 12 volt DC receptacle on the generator control panel. The removal of this plug will send a signal to the transfer switch to shift the contactor back to the utility position and allow the circuits of the home to again be powered by the incoming utility.
3. Let the engine run for a minute or two at no-load to stabilize the internal temperatures.
4. Turn off the generator.
After utilizing the 5 ft. electrical power cord, 5 ft. DC signal harness and ground strap for operation with the GUARDIAN
®
ULTRA SOURCE portable generator you must disconnect and remove them. Open the external connection box. Remove the fasteners holding the Black, Red, White, and Green wires in place. Remove wires from threaded lugs and from under ground screw. Replace fasteners and ground screw. Loosen the cable clamp and slide the power cord out of the external connection box. Disconnect the 4-pin plug from its mating half within the external connection box. Remove ground strap from the generator’s ground lug and from the grounding rod. Store the power cord, the DC signal harness and the ground strap with your GUARDIAN
®
ULTRA SOURCE portable
generator for future use.
Choose a lamp or light fixture located in a frequently occupied area of the house as a signal light to tell you when utility power has returned. This light should be on a utility powered circuit only so it operates independent of the generator.
SEMI-AUTOMATIC TRANSFER OPERATION USING GUARDIAN®PORTABLE GENERATOR
25
SECTION 6 - OPERATION OF GENERATOR WITH GENERATOR READY KIT
TO HOUSE BRANCH CIRCUITS SPLICED USING WIRE NUTS
11
3
9
7
5
1
12
4
10
8
6
2
XTERNAL CUSTOMER
CONNECTION PANEL
4 POSITION DEUTSCH CONNECTOR
100A OR 200A
HOUSE MAIN
SERVICE
NEUTRAL
BAR
GENERAC UL LISTED PANEL BOARD
GROUND
70A 2-POLE
CIRCUIT BREAKER
KIT - 12 CIRCUITS
GENERATOR READY
INTERCONNECTION DRAWING
SEMI-AUTOMATIC TRANSFER SWITCH CONNECTED TO THE EXTERNAL CONNECTION BOX
AND HOME’S MAIN ELECTRICAL DISTRIBUTION PANEL.
SECTION 6 - OPERATION OF GENERATOR WITH GENERATOR READY KIT
26
GENERAC UL LISTED PANEL BOARD
TO HOUSE BRANCH CIRCUITS SPLICED USING WIRE NUTS
GENERATOR READY KIT - 12 CIRCUITS
12
GENERATOR READY KIT
70A 2-POLE
CIRCUIT BREAKER
100A OR 200A
HOUSE MAIN
SERVICE
EEXTERNAL CUSTOMER
CONNECTION PANEL
NEUTRAL
BAR
3 4
312 45
N
A
TYPE HOM 120/240v
CBHOM-F
1
TYPE HOM 120/240v
CBHOM-F
3
TYPE HOM 120/240v
CBHOM-F
5
TYPE HOM 120/240v
CBHOM-F
7
TYPE HOM 120/240v
CBHOM-F
9
TYPE HOM 120/240v
CBHOM-F
11
B
CBHOM-F
120/240v TYPE HOM
2
CBHOM-F
120/240v TYPE HOM
4
CBHOM-F
120/240v TYPE HOM
6
CBHOM-F
120/240v TYPE HOM
8
CBHOM-F
120/240v TYPE HOM
10
CBHOM-F
120/240v TYPE HOM
12
GROUND
4 POSITION DEUTSCH CONNECTOR
27
Section 7 - Notes
Residential Portable Generator System
28
Section 8 — Electrical Data
Commercial-Industrial-Residential Portable Generator System
Wiring Diagram – Drawing No. 0E0228
29
Section 8 — Electrical Data
Commercial-Industrial-Residential Portable Generator System
Schematic – Drawing No. 0E0229-A
30
Section 9 — Exploded Views and Parts Lists
Commercial-Industrial-Residential Portable Generator System
GT-990 & GT-760 Engine (Page 1) – Drawing No. 0E8589-J
0
4
4, 5, 6
8, 11, 12, 13
3, 30, 35, 65
2, 5, 17, 18, 34, 35, 40, 57, 139, 153
61
60
62
59
25, 26, 27
7, 41, 42, 43, 44, 45, 46, 47, 49, 50, 51, 52, 53, 54, 57, 58
41, 42, 43, 44, 45, 46, 47, 49, 50, 51, 52, 53, 54, 56, 57, 58
63
65
64
20
16
5
9
6
7
16
2
15
10
1
12
11
8
13
14
18
58
17
56
57
55
54
19
53
32
31
160
3
34
30
35
51
52
23
28
21
47
49
50
22
48
25
24
41
42
43
3
3
29
46
45
44
26
27
38
40
39
36
37
31
ITEM PART NO. QTY. DESCRIPTION
1 0C5729 1 ASSEMBLY, CRANKCASE HOUSING
WITH SLEEVE 2 0E9843 1 SEAL, 38 I.D. CRANKSHAFT 3 090388 3 SCREW, TAPTITE M6-1.0 X 12 BP 4 0C5372 1 ASSEMBLY, BREATHER 5 0C3005 1 GASKET, BREATHER COVER 6 0E3372B 1 SEPARATOR, OIL BREATHER 7 0D8067A 1 ASSEMBLY, HEAD #1 8 071983 4 RETAINER, PISTON PIN 20 9 0D5269 1 ROCKER, COVER 10 043790 1 BARBED EL 90 3/8NPT X 3/8 11 0E2950 2 PISTON, LC (GT-990)
0E2985 2 PISTON, HC (GT-760) 12 021533 2 SET, PISTON RING 90MM 13 0E1466 2 PIN PISTON 14 0D4041 1 ASSEMBLY, CAMSHAFT & GEAR 15 0D4788 2 PLUG STD PIPE 3/8 STEEL SQ HD 16 093064 1 ASSEMBLY, OIL FILL CAP 17 0C2977 1 GASKET, CRANK CASE 18 0C5943 1 SEAL, OIL PASSAGE 19 0E4357E 1 ASSEMBLY, CRANKSHAFT
HORIZONTAL DIRECT DRIVE (GT-990)
0E4356E 1 ASSEMBLY, CRANKSHAFT
HORIZONTAL DIRECT DRIVE (GT-760)
20 0E3223 2 ASSEMBLY, CONNECTING ROD
(GT-990)
0E3222 2 ASSEMBLY, CONNECTING ROD
(GT-760) 21 0D2157 2 SCREW SHC M6-1.0 X 50 G8.8 22 0E6098 1 SCREEN, OIL PICKUP 23 0D4123A 1 ASSEMBLY, OIL PUMP 24 078699E 2 SLEEVE, SEAMED DOWEL 10 DIA. 25 0C3011 2 COVER, OIL RELIEF 26 0C3009 2 SPRING, OIL RELIEF 27 0C3010 2 BALL, 1/2D OIL RELIEF 28 093873 2 WASHER, LOCK RIB M6 29 0C5315 1 GEROTOR, OUTER 30 0C5998 1 CLAMP, OIL TUBE 31 0D4497 1 PLUG-CRANKCASE GOVERNOR
BORE 32 0C3971E 1 ASSEMBLY, DIPSTICK WITH
HANDLE 33 0D3745 1 TUBE, DIPSTICK 34 0C3027 3 O-RING, OIL CLR 35 0E9842 1 SEAL, 42 I.D. CRANKSHAFT
ITEM PART NO. QTY. DESCRIPTION
36 0C5731 1 ASSEMBLY, HOUSING COVER
WITH SLEEVE 37 0C3006 11 SCREW, HHFC M10-1.5 X 55 38 080318 8 SCREW HHFC M6-1.0 X 25 39 0C8808 2 HOOK, LIFTING 40 0C2981C 1 ROCKER, COVER 41 0C2979 2 GASKET, VALVE COVER 42 086515 8 KEEPER, VALVE SPRING 43 0D2274 4 RETAINER, VALVE SPRING 44 0D3867 4 SPRING, VALVE 45 078672 2 SEAL, VALVE STEM D7 46 0C5371 4 WASHER, VALVE SPRING 47 072694 4 STUD, ROCKER ARM PIVOT 48 0C3027 2 O-RING, 3/8" X 1/2" 49 0D5313 4 ROCKER ARM 50 0D3998 4 NUT, HEX M8-1.0 GB YELLOW
CHROME 51 0D6024 2 PLATE, PUSH ROD GUIDE 52 0C2976 12 SCREW HHFC M8-1.25 X 65 53 086516 2 VALVE, EXHAUST 54 0C2229 2 VALVE, INTAKE 55 083897 4 TAPPET, SOLID 56 0D8067B 1 ASSEMBLY, HEAD #2 57 0D9853D 4 PUSHROD 147 58 0C2978 2 GASKET, HEAD 59 0D6008 1 KIT GEAR COVER 60 0D4010 1 KIT GASKET 61 0D6007 1 KIT PISTON & RINGS 62 0D4012 1 KIT BREATHER ASSEMBLY 63 0D8675A 1 KIT HEAD ASSEMBLY CYLINDER 1 64 0D8675B 1 KIT HEAD ASSEMBLY CYLINDER 2 65 0D4015 1 KIT OIL RELIEF
Section 9 — Exploded Views and Parts Lists
Commercial-Industrial-Residential Portable Generator System
GT-990 & GT-760 Engine (Page 1) – Drawing No. 0E8589-J
Item 59 (Kit) includes items 3, 30, 35, 65 Item 60 (Kit) includes items 2, 5, 17, 18, 34, 35, 40, 57, 139, 153. Item 61 (Kit) includes items 8, 11, 12, 13 Item 62 (Kit) includes items 4, 5, 6 Item 63 (Kit) includes items 7, 41, 42, 43, 44, 45, 46, 47, 49, 50, 51, 52,
53, 54, 57, 58
Item 64 (Kit) includes items 41, 42, 43, 44, 45, 46, 47, 49, 50, 51, 52, 53,
54, 56, 57, 58
Item 65 (Kit) includes items 25, 26, 27
32
Section 9 — Exploded Views and Parts Lists
Commercial-Industrial-Residential Portable Generator System
GT-990 & GT-760 Engine (Page 2) – Drawing No. 0E8589-J
79
111
78
118
117
80
160
81
116
82
119
77
83
76
93
96
66
95
67
93
68
92
125
84
124
120
110
92
91
70 69
71
94
72
73
98
122
97
102
99
123
75
105
74
121
147
90
85
114
113
112
155
104
103
101
100
DETAIL "A"
115, 161
108
107
160
151
150
37
86
114
109
87
113
89
106
153
152
157
157
108
139
158
149
147
159
154
137
138
155
DETAIL "A"
133
132
131
134
140
146
127
145
136
143
144
135
143
108
130
142
126
128
108
129
141
ITEM PART # QTY. DESCRIPTION
66 0D6592 1 WINGNUT, AIRBOX 67 0D4511 1 PRECLEANER, AIR 68 0D9723 1 ELEMENT, AIR CLEANER 69 0E5302 1 STUD M6-1.0 X 73 70 0D4183 1 ADAPTOR, SPIT BACK 71 0D6327 1 GASKET, SPITBACK 72 0D2774B 1 BASE, AIRBOX 73 0D5125 1 SPRING, WINTER/SUMMER VALVE 74 0D2930 1 VALVE, SUMMER / WINTER 75 0D4612A 1 SNORKEL, AIR INTAKE 76 0D6143 1 TUBE, HEAT RISER 50.8 I.D. 77 0D2775 1 COVER, AIRBOX 78 0D5014A 1 KNOB, AIRBOX 17mm 79 0D5014B 1 KNOB, AIRBOX 95MM 80 049721 1 SCREW HHC M6-1.0 X 35 81 022097 1 WASHER LOCK M6-1/4 82 022473 1 WASHER FLAT 1/4 83 0E8388 4 NUT HEX FLANGE WHIZ M6-1.0 84 0D6021 4 STUD, METRIC 85 0C9093A 1 HOSE, BREATHER 86 0D4522 1 CONTROLLER ASSEMBLY 87 074908 2 SCREW HHTT M5-0.8 X 10 89 0E3398 1 ASSEMBLY, WIRE 90 0E2548 1 CARBURETOR (GT-990)
0E5077 1 CARBURETOR (GT-760)
91 0D4026 1 GASKET, CARB TO SPACER
(GT-990)
0D4024 1 GASKET, CARB/AIRBOX (GT-760) 92 048031C 4 CLAMP HOSE BAND 1/4 93 030340 12" HOSE ¼ ID 94 0D4023 1 GASKET, MANIFOLD TO CARB
(GT-990)
0D5282 1 GASKET, MANIFOLD TO CARB
(GT-760) 95 086061G 1 SLEEVING 1/2" I.D. 96 0D6313 1 FILTER, FUEL 97 070008 4 WASHER FLAT M8 98 070006 4 WASHER LOCK M8 99 049821 4 SCREW SHC M8-1.25 X 30 100 0C9911 1 MANIFOLD, INTAKE 101 051714 1 NUT HEX M3-0.5 102 0D5411 1 ROD, SUMMER / WINTER VALVE 103 0D5445 1 BUSHING, MINI CONTROL PANEL 104 0D5416A 1 KNOB, CONTROL SUMMER /
WINTER 105 0D5398 1 CHOKE ASSEMBLY 106 0E6043 2 SCREW TAPTITE M5-0.8 X 8 ZP 107 0D3432 1 PANEL, CONTROL FACE PLATE 108 045756 24 SCREW TAPTITE M6-1.0X 10
YELLOW CHROME 109 0D4767 1 SWITCH ROCKER 110 0D1142A 1 WRAPPER, LOWER CYLINDER 2 111 0D1143 1 WRAPPER, UPPER CYLINDER 2 112 0F1177 1 ASSEMBLY, GROUND WIRE 113 022097 4 WASHER LOCK M6-1/4
ITEM PART NO#.QTY. DESCRIPTION
114 092079 4 SCREW TAPTITE M6-1.0 X 25 BP 115 0F1338B 1 ASSY, IGN COIL W/DIODE NO ADV 116 0C4147 1 PUMP, IMPULSE 117 022264 2 WASHER LOCK M4 118 0D6142 2 SCREW PPHM M4-0.7 X 40 119 0D5399A 1 ELBOW, RUBBER 90 DEG. 120 0E7585 2 SPARKPLUG, CHAMPION RC14YC 121 0E4271 1 STARTER, DELCO REMY SD80 122 022129 3 WASHER LOCK M8-5/16 123 061906 2 SCREW HHC M8-1.25 X 85 G8.8 124 022145 1 WASHER, FLAT M8 125 045771 1 NUT, HEX M8-1.25 YELLOW ZINC 126 0D1131 1 GUARD,FAN 127 0F1169J 1 HOUSING, BLOWER REPOWER
L&G 128 0C9763 4 NUT, GROMMET 1/4 PLUG 129 0C3034 1 NUT,HEX M24 130 0C3033 1 WASHER, M24 131 0C3032 1 PLATE, FAN 132 0A5992 2 WASHER SHAKEPROOF INT M8 SS 133 051754 2 SCREW HHC M8-1.25 X 12 G8.8 134 0C3031 1 FAN, NYLON 135 0E4997 1 ASSY,GROUND WIRE CONNECTOR 136 045756 4 SCREW TAPTITE M6-1X10 YELLOW
CHROME 137 0C3725A 1 FLYWHEEL ASSEMBLY 138 0F1170C 1 PLATE, BACKING GT990 WITH REG.
CUTOUT 139 082774 1 KEY, WOODRUFF 4 X 19D 140 0C3043 2 GASKET, MANIFOLD / PORT 141 0C9764 4 PLASTITE,1/4-15 X 3/4 142 0C3026 1 COOLER, OIL 143 0F6301 4 CLAMP, HOSE OETIKER 16.5mm 144 0C9806 2 HOSE, 3/8" I.D. X 6" LONG 145 035461 2 BARBED STR 1/4NPT X 3/8 146 070185B 1 OIL FILTER 147 0C7292 1 NIPPLE, 3/4"-16 UNF 148 0D3083 1 ASSEMBLY, OIL DRAIN HOSE 149 0C3025 1 SWITCH, OIL PRESS 150 0D4550 1 BRACKET, AIRBOX SUPPORT 151 0C3018 1 WRAPPER, UPPER CYLINDER 1 152 0C3019 1 WRAPPER, LOWER CYLINDER 1 153 046964 1 BRASS ST ELBOW 1/4 NPT 154 0E0409 1 ASSY, ROD, GOV. STEPPER
MOTOR 155 0C8563 6 SCREW HHHC M6-1.0 X12 157 0D9784 2 NUT, LOCK HEX M3-0.5 (GT-990)
0E4869 2 NUT, HEX W/TOOTH WASHER M3-
0.5 (GT-760)
158 031879 1 WASHER FLAT #4 (GT-990)
0E4868 1 WASHER FLAT #4 (GT-760) 159 0D6098 1 SPACER, ROD (GT-760 ONLY) 160 0D6147 7 SCREW HHFC M6-1.0 X 10mm 161 0F1338A 1 ASSY, IGN COIL W/DIODE NO ADV
33
Section 9 — Exploded Views and Parts Lists
Commercial-Industrial-Residential Portable Generator System
GT-990 & GT-760 Engine (Page 2) – Drawing No. 0E8589-J
34
Section 9 — Exploded Views and Parts Lists
Commercial-Industrial-Residential Portable Generator System
Generator – Drawing No. 0D4488-D
35
ITEM PART NO. QTY. DESCRIPTION
1 0C6934 1 ADAPTOR, ENGINE 2 0D2123 1 STATOR 12.5KW
0D2134 STATOR 15KW 0D2136 STATOR 18KW
3 0D21320SRV 1 ASSEMBLY, ROTOR WITH FAN
12.5KW
0D21330SRV ASSEMBLY, ROTOR WITH FAN
15KW
0D2135 ROTOR 18KW 4 0C6043B 1 CARRIER, REAR BEARING 5 0D2492 1 EXHAUST MANIFOLD 6 0D2726 1 MUFFLER 7 0C4138 2 GASKET, EXHAUST 8 0D3547 1 COVER, ALTERNATOR AIR IN 9 031971 1 BEARING 10 0C3168 3 5/16 SPECIAL LOCK WASHER 11 0D1838 1 SCREW IHHC 3/8-24 X 15.50 G5 12 0D3549 4 SCREW IHHC M8-1.25 X 400 G8.8 13 0C7038E 1 BRACKET, ALT MOUNTING 14 032712 4 SCREW HHTT #10-32 X 1.75 15 0D4662 1 SCREW HHTT M8-1.2 X 20 16 0C7038D 1 ENGINE MOUNTING PLATE 17 0C7758 6 RUBBER MOUNT 18 0388050AF0 1 BATTERY CABLE, BLACK 19 0C2417A 1 EARTH STRAP 3/8X 3/8 20 082121C 1 CLIP-J VINYL COAT .625 ID 21 066386 1 ASSEMBLY, BRUSH HOLDER 22 0C2824 1 SCREW TAP-R #10-32 X 9/16
ITEM PART NO. QTY. DESCRIPTION
23 0A2038 1 WASHER FLAT 3/8 ZINC 24 022237 5 WASHER LOCK 3/8 25 022511 4 SCREW HHC 3/8-16 X 1-1/4 G5 26 022131 4 WASHER FLAT 3/8-M10 ZINC 27 051731 4 SCREW HHC M8-1.25 X 50 G8.8 28 022145 21 WASHER FLAT 5/16 ZINC 29 049820 4 NUT LOCK HEX M8-1.25 NYLON
INSERT
30 079246 5 SCREW HHC M6-1.0 X 16 WITH
LOCK WASHER 31 022129 18 WASHER LOCK M8-5/16 32 022259 12 NUT HEX 5/16-18 STEEL 33 059637 2 SCREW TAPTITE 3/8-16 X 3/4 BP 34 0D5100 1 SHIELD, MUFFLER HEAT 35 0D5823 1 U-BOLT & SADDLE 36 0C8565 4 SCREW SHC M8-1.25 X 18 37 0D5833 1 PANEL, MUFFLER BOX BACK 38 0D5834 1 PANEL, MUFFLER BOX END 39 090388 3 SCREW HHTT M6-1.0 X 12 40 022473 5 WASHER FLAT 1/4 41 N/A - NOT USED 42 0D5133 1 SPARK ARRESTOR SCREEN 43 0D5133A 1 RETAINER, SPARK ARREST
SCREEN 44 045764 1 SCREW HHTT M4-0.7 X 8 45 0D6214 1 SHIELD, RUBBER MOUNT 46 066849 2 SCREW HHTT M5-0.8 X 16
Section 9 — Exploded Views and Parts Lists
Commercial-Industrial-Residential Portable Generator System
Generator – Drawing No. 0D4488-D
36
Section 9 — Exploded Views and Parts Lists
Commercial-Industrial-Residential Portable Generator System
Control Panel – Drawing No. 0E0227-C
2
33
62
7
5
61
58
24
47,48
4
51
52
54
4
45
53
50
17
18
25
22
37
36
35
34
29
30
49
7
42
18
41
17
31
38
32
18
17
55
19
20
18
17
16
27
8
26
39
40
23
64
8
9
63
42
43
21
9
8
44
3
41
28
8
9
41
42
41
42
59
59
46
41
13
15
42
59
12
6
14
10
11
56
60
5
1
ITEM PART NO. QTY. DESCRIPTION
1 087968 1 SWITCH, ROCKER -/0 2 090418 1 OUTLET, 12VDC SNAP 3 0D6640 1 COVER, GOVERNOR CONTROL 4 090987 6 SCREW PPHM M3-0.5 X 12 5 0D8740 1 PANEL, SHEET METAL 6 068868 2 OUTLET 30A 120V RECEPT 7 022985 2 WASHER FLAT #6 8 043182 10 WASHER LOCK M3 9 051714 6 NUT HEX M3-0.5 G8 10 075207A 4 CIRCUIT BREAKER 30A 11 075207 2 CIRCUIT BREAKER 20A 12 0D4969 1 OUTLET 50A 125/250V 13 043437 1 OUTLET 30A 125/250V 14 0D4968 1 OUTLET 20A 120V DPLX 15 0D4966 1 OUTLET 20A 120V GFCI 16 0D1004E 1 CIRCUIT BREAKER 50A 400V
2POLE 17 051716 8 NUT HEX M5-0.8 G8 18 022152 8 WASHER LOCK #10 19 0D5045 1 DIN RAIL 59.5mm LONG 20 067680 1 ASSEMBLY VOLTAGE REGULATOR
60HZ 21 0D4409 1 ELECTRONIC GOVERNOR / IDLE
CONTROLLER 22 052844 1 RELAY PNL 12VDC SPST 30A 23 0F3100 1 RELAY 3PDT 12VDC 24 0D2691 1 CONTROL PANEL BOX 25 023484L 1 BUSHING SNAP 26 0A1661 2 RIVET POP .156 X .160-.164 / #20 27 048766 1 BLOCK TERMINAL 20A 2 X 6 X
1100V 28 0D3550 1 BLOCK DOUBLE ROW TERMINAL 8
POSITION 29 049939 1 RECTIFIER MSC 12A 600V 30 070370 1 WASHER MICA .203 31 030468 1 WASHER STEP NYLON .20
ITEM PART NO. QTY. DESCRIPTION
32 022158 1 NUT HEX #10-32 33 023897 1 WASHER FLAT #10 34 057405 1 RESISTOR 25R 5% 25W 35 022473 1 WASHER FLAT 1/4 36 022097 1 WASHER LOCK M6-1/4 37 049813 1 NUT HEX M6-1.0 G8 38 065795 2 RECTIFIER-BATTERY CHARGER 39 0D4804 2 TRANSFORMER, IDLE CURRENT 40 0C1085 4 SCREW PPHM M3-0.5 X 8 41 051715 18 NUT HEX M4-0.7 G8 42 022264 18 WASHER LOCK M4 43 048505 1 CIRCUIT BREAKER 6 X 1 44 087962 1 CIRCUIT BREAKER 10 X 1 12VDC
1/4"QC 45 036261 2 RIVET POP .125 X .129-.133 / #30 46 0A2769 1 LUG GRND 8 TABS 47 032300 1 HOLDER FUSE 48 028578 1 FUSE 10A X AGC10 49 055444 1 HEATSINK 50 075475 2 SCREW PPHM M4-0.7 X 10 51 049815 4 SCREW HHC M5-0.8 X 16 G8.8 52 0A2053 1 SCREW HHC M6-1.0 X 65 G8.8 53 055440 2 SCREW HHC M5-0.8 X 25 G8.8 54 045770 1 SCREW HHC M5-0.8 X 10 G8.8 55 0D5734 2 SPACER .25 X .50 X 1.5 56 074908 18 SCREW HHTT M5-0.8 X 10 57 075235 1 SCREW PPHM M5-0.8 X 30 58 080823 2 SCREW PPHM M5-0.8 X 50 59 038150 14 WASHER FLAT #8 60 0D6140 1 GASKET, PORTABLE CONTROL
PANEL 61 075476 2 SCREW PPHM M4-0.7 X 16 62 027565 A/R TAPE ELEC UL PERMACEL 63 058000K 2 NUT TRIC M5-0.8 64 0F3101 1 RELAY BASE 3PDT 12VDC
37
Section 9 — Exploded Views and Parts Lists
Commercial-Industrial-Residential Portable Generator System
Control Panel – Drawing No. 0E0227-C
Section 9 — Exploded Views and Parts Lists
Commercial-Industrial-Residential Portable Generator System
Frame, Handle & Wheel Kit – Drawing No. 0E0695-A
38
39
ITEM PART NO. QTY. DESCRIPTION
1 057058 4 SCREW HHC M6-1.0 X 55 2 0D5315 4 RUBBER TANK MOUNT 3 0D4570 1 CAP, FUEL WITH GAUGE & VENT 4 0D22850SRV 1 KIT, FUEL TANK 5 045771 4 NUT HEX M8-1.25 6 022129 10 WASHER LOCK M8-5/16 7 022145 14 WASHER FLAT 5/16 8 0D4565 1 BRACKET BATTERY 9 0D3545 2 BOLT,BATTERY J-BOLT 10 022287 2 SCREW HHC 1/4-20 X 3/4 G5 11 022473 2 WASHER FLAT 1/4 12 022097 2 WASHER LOCK M6-1/4 13 022127 2 NUT HEX 1/4-20 14 0388040AK0 1 BATTERY CABLE, RED 15 0D4575 1 BATTERY U1 16 0D5202 1 NUT WING 5/16-18 BRASS 17 0D5199 4 WASHER FLAT 5/16 BRASS 18 029809 1 NUT HEX 5/16-18 BRASS 19 0C3168 1 5/16 SPECIAL L/WASH 20 0D5198 1 SCREW HHC 5/16-18 X 1.5 BRASS 21 0E0317 1 BRACKET FRONT FOOT (15 kW)
0D2498 1 BRACKET FRONT FOOT (12.5 kW) 22 027007 2 VIB MOUNT 23 0D5303 4 WASHER FLAT .25ID X 1"OD 24 042909 2 SCREW HHC M8-1.25 X 30 25 090388 4 SCREW HHTT M6-1.0 X 12 26 064101 6 NUT LOCK FL 3/8-16 27 039214 6 BOLT CARR 3/8-16 X 1 28 0D9165 1 AXLE, 3/4"DIA X 30" (15 kW)
0D2496 1 AXLE, 3/4"DIA X 27.25" (12.5 kW)
ITEM PART NO. QTY. DESCRIPTION
29 045900 2 WASHER FLAT 3/4" (15 kW)
045900 4 WASHER FLAT 3/4" (12.5 kW)
30 0D7668 2 12.3" PNEUM WHEEL 3/4" AXLE
(15 kW)
0D2495 2 10" PNEUM WHEEL 3/4" AXLE
(12.5 kW) 31 0D4999 2 PIN COTTER 1/8 X 1-1/4 32 0D4044 2 BRACKET, WHEEL SPACER 33 0D3700 4 NUT FLANGE M6-1.0 NYLOK 34 0D2497 1 HANDLE 35 022532 4 SCREW HHC 5/16-18 X 2-1/2 G5 36 027028 6 NUT LOCK HEX 5/16-18 NYLON
INSERT 37 0D2271 1 FRAME 38 052762 4 SCREW HHC M5-0.8 X 45 G8.8 39 051713 8 WASHER FLAT M5 40 049226 4 WASHER LOCK M5 41 051716 4 NUT HEX M5-0.8 42 050190 2 WASHER FLAT 1" 43 078299 1 BUSHING TANK DEXTOR 44 080270 1 VALVE, PLASTIC TANK 45 0D5142 1 AIR DEFLECTOR 46 096021 2 GROMMET .75 X .06 X .50 47 048031C 2 CLAMP HOSE BAND ¼ 48 030340 18" HOSE ¼ ID 49 075763 1 BOOT BATTERY CABLE 50 075763A 1 BOOT STARTER CABLE 51 0E0318 2 SPACER, AXLE (15 kW) 52 030795 2 SCREW HHC 5/16"-18 X 1"
Section 9 — Exploded Views and Parts Lists
Commercial-Industrial-Residential Portable Generator System
Frame, Handle & Wheel Kit – Drawing No. 0E0695-A
40
CALIFORNIA EMISSION CONTROL WARRANTY STATEMENT
YOUR WARRANTY RIGHTS AND OBLIGATIONS
The California Air Resources Board (CARB) and Generac Power Systems, Inc. (Generac) are pleased to explain the Emission Control System warranty on your new engine. In California, new off-road Large Spark-Ignition (LSI) engines must be designed, built and equipped to meet the state's stringent anti-smog standards. Generac will warrant the emission control. system on your engine one for the periods of time listed below provided there has been no abuse, neglect, unapproved modification or improper maintenance of your engine.
Your emission control system may include parts such as the carburetor, ignition system and exhaust system. Generac will repair your engine at no cost to you for diagnosis, replacement parts arid labor, should a warrantable condition occur.
MANUFACTURER’S EMISSION CONTROL SYSTEM WARRANTY COVERAGE:
Emissions control systems on 2001 and later model year LSI engines are warranted for two years as hereinafter noted- If, during such warranty period, any emission-related component or system on your engine is found to be defective in materials or workmanship, repairs or replacement will be performed by a Generac Authorized Warranty Service Facility.
PURCHASER'S/OWNER'S WARRANTY RESPONSIBILITIES:
As the engine owner, you are responsible for the completion of all required maintenance as listed in your factory supplied Owner's Manual. For warranty purposes, Generac recommends that you retain all receipts covering maintenance on your engine. However, Generac cannot deny warranty solely due to the lack of receipts or for your failure to ensure the completion of all scheduled maintenance.
As the engine purchaser/owner, you should, however, be aware that Generac may deny any and/or all warranty coverage or responsibility if your engine, or a part/component thereof, has failed due to abuse, neglect , improper maintenance or unapproved modifications, or the use of counterfeit and/ox "grey market" parts not made, supplied or approved by Generac.
You are responsible for contacting a. Generac Authorized Warranty Facility as soon as a problem occurs. The warranty repairs should be completed in a reasonable amount of time, not to exceed 30 days.
Warranty service can be arranged by contacting either your selling dealer or a Generac Authorized Warranty Service Facility. To locate the Generac Authorized Warranty Service Facility nearest you, call our toll free number:
1-800-333-1322
IMPORTANT NOTE: This warranty statement explains your rights and obligations under the Emission Control System Warranty (ECS
Warranty), which is provided to you by Generac pursuant to California law. See also the "Generac Limited Warranties for Generac Power Systems, Inc.," which is enclosed herewith on a separate sheet, also provided to you by Generac. The ECS Warranty applies only to the emission control system of your new engine. If there is any conflict in terms between the ECS Warranty and the Generac Warranty, the ECS warranty shall apply except in circumstances where the Generac Warranty may provide a longer warranty period. Both the ECS Warranty and the Generac Warranty describe important rights and obligations with respect to your new engine.
Warranty service can be performed only by a Generac Authorized Warranty Service Facility. When requesting warranty service, evidence must be presented showing the date of the sale to the original purchaser/owner.
If you have any questions regarding your warranty rights and responsibilities, you should contact Generac at one of the following addresses:
ATTENTION WARRANTY DEPARTMENT
GENERAC POWER SYSTEMS, INC.
P.O. BOX 297 • WHITEWATER, WI 53190
Part 1
Section 10 – Warranty
Commercial-Industrial-Residential Portable Generator System
41
EMISSION CONTROL SYSTEM WARRANTY
Emission Control System Warranty (ECS warranty) for 2001 and later model year LSI engines:
(a) Applicability: This warranty shall apply to 1995 and later model year engines. The ECS Warranty period shall begin on the date the new engine or
equipment is purchased by/delivered to its original, end-use purchaser/owner and shall continue for 24 consecutive months thereafter.
(b) General Emissions Warranty Coverage: Generac warrants to the original, end-use purchaser/owner of the new engine or equipment and to each
subsequent purchaser/owner that each of its engines is...
(1) Designed, built and equipped so as to conform with all applicable regulations adopted by the CARB pursuant to its authority, and
(2) Free from defects in materials and workmanship which, at any time during the ECS Warranty Period, may cause a warranted emissions-related part
to fail to be identical in all material respects to the part as described in the engine manufacturer's application for certification.
The ECS Warranty pertains only to emissions-related parts on your engine, as follows:
(1) Any warranted, emissions-related parts that are not scheduled for replacement as required maintenance in the Owner's Manual shall be warranted
for the ECS Warranty Period. If any such part fails during the ECS Warranty Period, it shall be repaired or replaced by Generac according to Subsection (4) below. Any such part repaired or replaced under the ECS Warranty shall be warranted for the remainder of the ECS Warranty Period.
(2) Any warranted, emissions-related part that is scheduled only for regular inspection as specified in the Owner's Manual shall be warranted for the ECS
Warranty Period. A statement in such written instructions to the effect of "repair or replace as necessary" shall not reduce the ECS Warranty Period. Any such part repaired or replaced under the ECS Warranty shall be warranted for the remainder of the ECS Warranty Period.
(3) Any warranted, emissions-related part that is scheduled for replacement as required maintenance in the Owner's Manual shall be warranted for the
period of time prior to first scheduled replacement point for that part. If the part fails prior to the first scheduled replacement, the part shall be repaired or replaced by Generac according to Subsection (4) below. Any such emissions-related part repaired or replaced under the ECS warranty shall be warranted for the remainder of the ECS Warranty Period prior to the first scheduled replacement point for such emissions-related part.
(4) Repair or replacement of any warranted, emissions-related part under this ECS Warranty shall be performed at no charge to the owner at a Generac
Authorized Warranty Service Facility.
(5) When the engine is inspected by a Generac Authorized Warranty Service Facility, the purchaser/owner shall not be held responsible for diagnostic
costs if the repair is deemed warrantable.
(6) Generac shall be liable for damages to other original engine components or approved modifications caused by a failure under warranty of any
emission-related part covered by the ECS Warranty.
(7) Throughout the ECS Warranty Period, Generac shall maintain a supply of warranted emission-related parts sufficient to meet the expected demand
for such emission-related parts.
(8) Any Generac authorized and approved emission-related replacement part may be used in the performance of any ECS warranty maintenance or repairs
and will be provided without charge to the purchaser/owner. Such use shall not reduce Generac RCS Warranty obligations.
(9) Unapproved, add-on, modified, counterfeit and/or "grey market" parts nay not be used to modify or repair a Generac engine. Such use voids this ECS
Warranty and shall be sufficient grounds for disallowing an ECS Warranty claim. Generac shall not be held liable hereunder for failures of any warranted parts of a Generac engine caused by the use of such an unapproved, add-on, modified, counterfeit and/or "grey market" part.
EMISSION RELATED PARTS INCLUDE THE FOLLOWING:
* Generac engine types covered by this warranty statement include the following:
1) Prepackaged Standby Generator
2) Auxiliary Power Unit (APU) Generator
3) Standby Generator
Part 2
Section 10 – Warranty
Commercial-Industrial-Residential Portable Generator System
1) Fuel Metering System:
1.2) LPG/Natural Gas carburetion assembly and its internal components.
a) Fuel controller (if so equipped) b) Mixer and its gaskets (if so equipped) c) Carburetor and its gaskets (if so equipped) d) Primary gas regulator (if so equipped) e) LP liquid vaporizer (if so equipped)
2) Air Induction System including: a) Intake pipe/manifold b) Air cleaner
3) Ignition System including: a) Spark plug b) Ignition module
4) Catalytic Muffler Assembly (if so equipped) including: a) Muffler gasket b) Exhaust manifold
5) Crankcase Breather Assembly including: a) Breather connection tube
GENERAC POWER SYSTEMS "TWO YEAR" LIMITED WARRANTY FOR GUARDIAN
®
"ULTRA SOURCE 15,000 WATT GENERATOR WITH GENERATOR READY KIT"
For a period of two years from the date of original sale, Generac Power Systems, Inc. (Generac) warrants that its Guardian generator and accompanying transfer switch will be free from defects in material and workmanship for the items and period set forth below. Generac will, at its option, repair or replace any part which, upon examination, inspection and testing by Generac or a Guardian Authorized Warranty Service Dealer, is found to be defective. Any equipment that the purchaser/owner claims to be defective must be examined by the nearest Guardian Authorized Warranty Service Dealer. All transportation costs under the warranty, including return to the factory, are to be borne and prepaid by the purchaser/owner. This warranty applies only to Generac Guardian Ultra Source portable generator prepackaged with transfer switch sold and rated for use in "Standby" applications.
WARRANTY SCHEDULE
YEARS ONE and TWO - 100% (one hundred percent) transferable coverage on Labor and Part(s) listed (proof of purchase and maintenance is required): Engine - All Components Alternator - All Components Transfer System - All Components
All warranty expense allowances are subject to the conditions defined in Guardian's Warranty Policies, Procedures and Flat Rate Manual.
THIS WARRANTY SHALL NOT APPLY TO THE FOLLOWING:
• Guardian Ultra Source generators that utilize non-Guardian/Generac replacement parts.
• Guardian Ultra Source generators utilizing non-Guardian/Generac automatic transfer switches.
• Guardian Ultra Source generators used in commercial or rental applications.
• Repairs or diagnostics performed by individuals other than Guardian/Generac authorized dealers not authorized in writing by Generac Power Systems.
• Any Guardian Ultra Source generators used as rental or trailer mounted applications.
• Units used for prime power in place of existing utility power where utility power is present or in place of utility power where utility power service does not normally exist.
• Costs of normal maintenance, adjustments, installation and start-up.
• Steel components that are rusting due to the improper use, location in a harsh or saltwater environment or scratched where integrity of paint applied is compromised.
• Failures caused by any contaminated fuels, oils, coolants or lack of proper fluid amounts.
• Failures due, but not limited, to normal wear and tear, accident, misuse, abuse, negligence or improper installation. As with all mechanical devices, the Generac engines need periodic part(s) service and replacement to perform well. This warranty will not cover repair when normal use has exhausted the life of a part(s) or engine.
• Failures caused by any external cause or act of God, such as collision, theft, vandalism, riot or wars, nuclear holocaust, fire, freezing, lightning, earthquake, windstorm, hail, volcanic eruption, water or flood, tornado or hurricane.
• Damage related to rodent and/or insect infestation.
• Products that are modified or altered in a manner not authorized by Generac in writing.
• Any incidental, consequential or indirect damages caused by defects in materials or workmanship, or any delay in repair or replacement of the defective part(s).
• Failure due to misapplication.
• Telephone, cellular phone, facsimile, internet access or other communication expenses.
• Living or travel expenses of person(s) performing service, except as specifically included within the terms of a specific unit warranty period.
• Expenses related to "customer instruction" or troubleshooting where no manufacturing defect is found.
• Rental equipment used while warranty repairs are being performed.
• Costs incurred for equipment used for removal and/or reinstallation of generator, (i.e.; cranes, hoists, lifts, etc.)
• Overnight freight costs for replacement part(s).
• Overtime labor.
• Starting batteries, fuses, light bulbs and engine fluids.
THIS WARRANTY IS IN PLACE OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED. SPECIFICALLY, GENERAC MAKES NO OTHER WARRANTIES AS TO THE MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you. GENERAC'S ONLY LIABILITY SHALL BE THE REPAIR OR REPLACEMENT OF PART(S) AS STATED ABOVE. IN NO EVENT SHALL GENERAC BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES, EVEN IF SUCH DAMAGES ARE A DIRECT RESULT OF GENERAC'S NEGLIGENCE. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation may not apply to you. This warranty gives you specific legal rights. You also have other rights from state to state.
GENERAC®POWER SYSTEMS, INC.
P.O. BOX 297
WHITEWATER, WI 53190
Section 8 – Warranty
Commercial-Industrial-Residential Portable Generator System
Part No. 0F7573 Rev.* Printed in U.S.A. 07.05