Generac Power Systems RXGW20SHA3 Owner's Manual

Page 1
003722
Owner’s Manual
For
Automatic Transfer Switch
200 Amp, Single Phase, 240 VAC, Service Rated, 20–40 Circuit Load Center With Pass-Through Lugs
Model Number
RXGW20SHA3
SERIAL NUMBER: _________________________
DATE PURCHASED:________________________
888-436-3722
Para español , visita: Pour le français, visiter : http://www.generac.com/service-support/product-support-lookup
http://www.generac.com/service-support/product-support-lookup
SAVE THIS MANUAL FOR FUTURE REFERENCE
Page 2
(000393a)
WARNING
CANCER AND REPRODUCTIVE HARM
www.P65Warnings.ca.gov.
ii Automatic Transfer Switch Owner’s Manual
Page 3
Table of Contents
Section 1: Safety Rules & General
Information
Introduction ..........................................................1
Read This Manual Thoroughly ....................................1
Safety Rules .........................................................1
General Hazards ..................................................1
Electrical Hazards ................................................2
Section 2: Installation
Introduction to Installation .................................5
Mounting the Enclosure ......................................5
Opening the Enclosure .......................................5
Installing Breakers ...............................................6
Installing Branch Circuit Conductors ................6
Connecting Power Source and Generator
Power Supply .......................................................6
Connecting Start Circuit Wires ...........................7
Section 4: Drawings and Diagrams
Installation Drawing .......................................... 15
No. 10000047450 ...................................................... 15
Interconnection Drawing .................................. 16
No. 10000047283—Page 1 of 4
(Liquid-Cooled Engine Generator) ............................16
No. 10000047283—Page 2 of 4
(Liquid-Cooled Engine Generator) ............................17
No. 10000047283—Page 3 of 4
(Air-Cooled Engine Generator) ..................................18
No. 10000047283—Page 4 of 4
(Air-Cooled Engine Generator) ..................................19
Connecting SACM ...............................................8
Control of Air Conditioner Load ...................................8
Auxiliary Contact .................................................9
Fault Current Identification Label ......................9
Section 3: Operation
Functional Tests and Adjustments ..................11
Manual Operation ..............................................11
Close to Utility Source Side .......................................11
Close to Generator Source Side ...............................12
Return to Utility Source Side .....................................12
Voltage Checks ..................................................12
Utility Voltage Checks ...............................................12
Generator Voltage Checks ........................................12
Generator Tests Under Load ............................12
Checking Automatic Operation ........................13
Installation Summary ........................................13
Shutting Generator Down While
Under Load .........................................................13
Shutting Generator Down To Perform
Maintenance .......................................................14
Testing the SACM ..............................................14
Testing The SMM ...............................................14
Fuse Removal and Installation .........................14
Automatic Transfer Switch Owner’s Manual iii
Page 4
This page intentionally left blank.
iv Automatic Transfer Switch Owner’s Manual
Page 5
Safety Rules & General Information
(000100a)
WARNING
Consult Manual. Read and understand manual completely before using product. Failure to completely understand manual and product could result in death or serious injury.
(000001)
DANGER
Indicates a hazardous situation which, if not avoided, will result in death or serious injury.
(000002)
WARNING
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
(000003)
CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
(000237)
DANGER
Electrical backfeed. Use only approved switchgear to isolate generator from the normal power source. Failure to do so will result in death, serious injury, and equipment damage.
(000188)
DANGER
Electrocution. Do not wear jewelry while working on this equipment. Doing so will result in death or serious injury.
(000213)
DANGER
Electrocution. Only authorized personnel should access transfer switch interior. Transfer switch doors should be kept closed and locked. Failure to do so will result in death or serious injury.

Section 1: Safety Rules & General Information

Introduction

Thank you for purchasing a Generac Power Systems Inc. product. This unit has been designed to provide high performance, efficient operation, and years of use when maintained correctly.
The information in this manual is accurate based on products produced at the time of publication. The manu facturer reserves the right to make technical updates, corrections, and product revisions at any time without notice.

Read This Manual Thoroughly

-
If any section of this manual is not understood, contact the nearest Independent Authorized Service Dealer (IASD) or Generac Customer Service at 1-888-436-3722 (1-888-GENERAC), or visit ing, operating, and servicing procedures. The owner is responsible for correct maintenance and safe use of the unit.
This manual must be used in conjunction with all other supporting product documentation supplied with the product.
SAVE THESE INSTRUCTIONS for future reference. This manual contains important instructions that must be fol lowed during placement, operation, and maintenance of the unit and its components. Always supply this manual to any individual that will use this unit, and instruct them on how to correctly start, operate, and stop the unit in case of emergency.
www.generac.com for start-

Safety Rules

The manufacturer cannot anticipate every possible cir­cumstance that might involve a hazard. The alerts in this manual, and on tags and decals affixed to the unit, are not all inclusive. If using a procedure, work method, or operating technique that the manufacturer does not spe cifically recommend, verify that it is safe for others and does not render the equipment unsafe.
Throughout this publication, and on tags and decals affixed to the unit, DANGER, WARNING, CAUTION, and NOTE blocks are used to alert personnel to special instructions about a particular operation that may be hazardous if performed incorrectly or carelessly. Observe them carefully. Alert definitions are as follows:
Automatic Transfer Switch Owner’s Manual 1
NOTE: Notes contain additional information important to a procedure and will be found within the regular text of this manual.
These safety alerts cannot eliminate the hazards that they indicate. Common sense and strict compliance with the special instructions while performing the action or service are essential to preventing accidents.

General Hazards

-
-
Page 6
Safety Rules & General Information
Automatic start-up. Disconnect utility power and render unit inoperable before working on unit. Failure to do so will result in death or serious injury.
(000191)
DANGER
(000145)
DANGER
Electrocution. In the event of electrical accident, immediately shut power OFF. Use non-conductive implements to free victim from live conductor. Apply first aid and get medical help. Failure to do so will result in death or serious injury.
(000209b)
WARNING
Loss of life. This product is not intended to be used in a critical life support application. Failure to adhere to this warning could result in death or serious injury.
WARNING
Equipment damage. This unit is not intended for use as a prime power source. It is intended for use as an intermediate power supply in the event of temporary power outage only. Doing so could result in death, serious injury, and equipment damage.
(000247a)
(000129)
DANGER
Electrocution. High voltage is present at transfer switch and terminals. Contact with live terminals will result in death or serious injury.
(000104)
DANGER
Electrocution. Water contact with a power source, if not avoided, will result in death or serious injury.
(000145)
DANGER
Electrocution. In the event of electrical accident, immediately shut power OFF. Use non-conductive implements to free victim from live conductor. Apply first aid and get medical help. Failure to do so will result in death or serious injury.
(000237)
DANGER
Electrical backfeed. Use only approved switchgear to isolate generator from the normal power source. Failure to do so will result in death, serious injury, and equipment damage.
(000195)
DANGER
Electrocution, equipment and property damage. Handle transfer switches carefully when installing. Never install a damaged transfer switch. Doing so could result in death or serious injury, equipment and property damage.
(000123)
DANGER
Electrocution. Turn utility supply OFF before working on utility connections of the transfer switch. Failure to do so will result in death or serious injury.
(000157)
DANGER
Electrocution. Do not disable or modify the connection box door safety switch. Doing so will result in death or serious injury.
Automatic start-up. Disconnect utility power and render unit inoperable before working on unit. Failure to do so will result in death or serious injury.
(000191)
DANGER

Electrical Hazards

IMPORTANT NOTE: See individual unit specifica­tions for required maintenance and run times per­taining to use.
Competent, qualified personnel should install,
operate, and service this equipment. Strictly com ply to local, state, and national electrical and build­ing codes. When using this equipment, comply with regulations established by the National Electrical Code (NEC), CSA Standard; the Occupational Safety and Health Administration (OSHA), or the local agency for workplace health and safety.
If working on this equipment while standing on
metal or concrete, place insulative mats over a dry wood platform. Work on this equipment only while standing on such insulative mats.
Never work on this equipment while physically or
mentally fatigued.
Any voltage measurements should be performed
with a meter that meets UL3111 safety standards, and meets or exceeds overvoltage class CAT III.
-
2 Automatic Transfer Switch Owner’s Manual
Page 7
Safety Rules & General Information
(000119)
Equipment malfunction. Installing a dirty or damaged transfer switch will cause equipment malfunction and will result in death or serious injury.
DANGER
(000155a)
WARNING
Electric shock. Only a trained and licensed electrician should perform wiring and connections to unit. Failure to follow proper installation requirements could result in death, serious injury, and equipment or property damage.
(000120)
CAUTION
Equipment damage. Verify all conductors are tightened to the factory specified torque value. Failure to do so could result in damage to the switch base.
(000121)
CAUTION
Equipment damage. Perform functional tests in the exact order they are presented in the manual. Failure to do so could result in equipment damage.
(000134a)
CAUTION
Equipment damage. Exceeding rated voltage and current will damage the auxiliary contacts. Verify that voltage and current are within specification before energizing this equipment.
Automatic Transfer Switch Owner’s Manual 3
Page 8
Safety Rules & General Information
This page intentionally left blank.
4 Automatic Transfer Switch Owner’s Manual
Page 9

Section 2: Installation

(000119)
Equipment malfunction. Installing a dirty or damaged transfer switch will cause equipment malfunction and will result in death or serious injury.
DANGER
004086a
A
B
C
D
E
F
H
G
J
Installation

Introduction to Installation

This equipment has been wired and tested at the factory. Installing the transfer switch includes the following proce dures:
Mounting the enclosure.
Connecting power source and load leads.
Connecting generator start and sensing circuit.
Connecting any auxiliary contact (if needed).
Testing functions.

Mounting the Enclosure

Mounting dimensions for the transfer switch enclosure are in this manual. Enclosures are typically wall­mounted. See
This transfer switch is mounted in a UL type 3R enclo­sure. It can be mounted outside or inside and should be based on the layout of installation, convenience, and proximity to the utility supply and load center.
Drawings and Diagrams.
Install transfer switch as close as possible to electrical loads that will be connected to it. Mount transfer switch vertically to a rigid supporting structure. Level all mount
­ing points to prevent transfer switch distortion. Use wash-
ers behind mounting holes to level the unit if necessary.

Opening the Enclosure

See Figure 2-1. First, remove outer cover (A):
1. Remove two thumb screws (B).
2. Slide slot (C) over retention tab.
3. Lower cover until clear of top flange (D), and pull
away from enclosure.
Then, remove inner panel (E):
4. Loosen nut (F).
5. Grasp inner panel at two cutouts (G—left and
right). Tilt inner panel as shown, passing nut through t-slot (H) in inner panel.
6. Lower inner panel until clear of two retention slots (J—left and right sides), and pull away from enclo sure.
-
-
Automatic Transfer Switch Owner’s Manual 5
Figure 2-1. Open Enclosure
Page 10
Installation
000362
B
A
Electrocution. Turn utility and emergency power supplies to OFF before connecting power source and load lines. Failure to do so
will result in death or serious injury.
(000116)
DANGER
(000120)
CAUTION
Equipment damage. Verify all conductors are tightened to the factory specified torque value. Failure to do so could result in damage to the switch base.

Installing Breakers

See Figure 2-2. Insert tab on each breaker (A) into the hook on the bus (B). Push breaker into bus until it snaps into place.
Figure 2-2. Install Breakers
NOTE: The following 1 in circuit breaker manufacturers are permitted to be installed: Siemens, Murray, Eaton BR, and Square D Homeline.

Installing Branch Circuit Conductors

1. Install correctly sized branch circuit conductors into
transfer switch. Knockouts can be made in the field as needed.
2. Connect ungrounded branch circuit conductors (hot conductors) to a correctly sized circuit breaker approved for use with the transfer switch.
3. Terminate neutral conductor and equipment grounding conductor of the branch circuit at neu tral/equipment ground terminal bars.
4. Size all conductors, raceways, conduits, and junc­tion boxes, if required, to the applicable NEC code articles and follow NEC installation requirements for wiring method(s) selected.
NOTE: Multi-wire branch circuits must be installed in accordance with NEC Article 210.4.

Connecting Power Source and Generator Power Supply

Installation and interconnection diagrams are provided in this manual.
NOTE: All installations must comply with national, state, and local codes. It is the responsibility of the installer to perform an installation that will pass final electrical inspection.
1. Connect utility supply at utility service disconnect circuit breaker terminals N1 and N2. Utility supply lugs are equipped with the 2017/2020 NEC required finger safe barriers. These barriers must remain in place after installation.
2. Connect utility neutral conductor to grounded ter­minal bar. Neutral/grounding conductor terminal bars are bonded together and to the transfer switch
-
enclosure through the use of a green main bonding jumper screw.
3. Connect loads to integrated load center with cus­tomer-supplied circuit breakers.
4. See Figure 2-1 and Figure 2-3. Connect generator to generator terminals (E1 and E2) on the transfer mechanism.
6 Automatic Transfer Switch Owner’s Manual
Page 11
Installation
N2
004982a
N1
E1
E2
A
T1
T2
All power cables can enter enclosure through provided knockouts. Additional knockouts into transfer switch can be made in the field as needed. Conduit entry shall main tain correct wire bending spaces required by Tables
312.6 (A) and (B) in the NEC. Conduits should be arranged to provide separation between utility and gener ator supply conductors inside the enclosure.
NOTE: If aluminum conductors are used, apply corrosion inhibitor to conductors. After tightening terminal lugs, carefully wipe away any excess corrosion inhibitor.
Tighten terminal lugs to required torque values as noted on decal located on the inside of the door. After tighten ing terminal lugs, carefully wipe away any excess corro­sion inhibitor.

Connecting Start Circuit Wires

Control system interconnections consist of N1, N2, and T1, and leads 23, 194, and 9 (ground). The connections are color coded on the load shed to match connections in the Generac genset. Generac Type TC-ER-JP tray cable includes power cables with all necessary color-coded control wiring. It is suitable for direct burial, overhead, and indoor wiring.
-
-
-
Figure 2-3. Wiring Connections
5. Connect generator neutral wire to top neutral lug or side lugs on the panel board.
6. Connect neutral conductors to the lugs and termi­nals along the neutral/ground bars in panel board section of transfer switch.
7. Connect a maximum 200A subpanel feeder to lower T1 and T2 connections. Connect feeder neu tral and equipment grounding conductors to the neutral/grounding terminal bar in the transfer switch.
8. Connect grounding electrode conductors to neu­tral/ground terminal bars in panel board portion of transfer switch.
NOTE: A neutral to equipment ground main bonding screw (A) is provided for use where transfer switch is installed as service equipment.
NOTE: See Article 336 in the 2017 and 2020 editions of the NEC for more information on the installation require­ments for Type TC-ER-JP cable.
The generator control wiring is a Class 1 signaling circuit. See instruction manual of specific engine generator for wiring connection details. Recommended wire gauge sizes for this wiring depends on wire length, as recom mended in the following chart:
Maximum Wire Length Recommended Wire Size
1–115 ft (1–35 m) No. 18 AWG
116–185 ft (36–56 m) No. 16 AWG
186–295 ft (57–89 m) No. 14 AWG
296–460 ft (90–140 m) No. 12 AWG
­Exception: Conductors of AC and DC circuits, rated
1000 volts nominal or less, shall be permitted to occupy the same equipment, cable, or conduit. All conductors shall have an insulation rating equal to at least the maxi mum circuit voltage applied to any conductor within the equipment, cable, or conduit. See NEC 300.3(C)(1).
-
-
Conductor sizes must be adequate to handle maximum current they will be subjected to, based on the 75 °C col
-
umn of tables, charts, etc. used to size conductors. Installation must fully comply with all applicable codes, standards, and regulations.
Automatic Transfer Switch Owner’s Manual 7
Page 12
Installation
A
B
G
H
C
D
E
F
T1N1N2
0 GROUND
194 +12V
N1
N2
T1
Replace with Littlefuse 021606.3MXHP Generac 10000005117 250 vac, 6.3A
23 TRANSFER
1
1
1
1
2
2
2
2
®
J
T1
N2
0
194
23A
N1
004435

Connecting SACM

See Figure 2-4. The SACM can control an air conditioner (24 VAC) directly.

Control of Air Conditioner Load

1. Route thermostat cable (from furnace/thermostat to
outdoor air conditioner unit) to transfer switch.
2. Con
nect wire to the terminal strip terminals (A/C 1) on SACM as shown in Figure 2-4. These are nor­mally closed contacts which open upon load shed
ditions. Route thermostat wire away from high
con voltage wires.
required, connect additional air conditioners to
3. If the terminal strip terminals (A/C 2-4).
Contact Ratings
A/C 1-4 24 VAC, 1.0 amp max
NOTE: These instructions are for a typical air conditioner installation. Control of certain heat pumps and 2-stage air conditioners may require special connections or the use of SMMs to control the loads.
A—Thermostat 1
B—Air conditioner 1
C—Thermostat 2
D—Air conditioner 2
E—Thermostat 3
F—Air conditioner 3
G—Thermostat 4
H—Air conditioner 4
T1 (fused)—Battery Charge
(blue background, white letters)
N1 (fused)—Utility Sense
(yellow background, black letters)
N2 (fused)—Utility Sense
(yellow background with black
stripe, black letters)
0—Ground
(black background, white
letters)
194+12 VDC
(red background, white letters)
23—Transfer Control
(white background, black
letters)
J—240 VAC, 6.3A Fuses
Figure 2-4. Typical SACM Connections
8 Automatic Transfer Switch Owner’s Manual
Page 13
Installation
(000134a)
CAUTION
Equipment damage. Exceeding rated voltage and current will damage the auxiliary contacts. Verify that voltage and current are within specification before energizing this equipment.
A
004496

Auxiliary Contact

See Figure 2-5. If desired, there is one normally-closed auxiliary contact (A) on the transfer switch to operate customer accessories, remote advisory lights, or remote annunciator devices. A suitable power source must be connected to common terminal. If needed, an extra auxil iary contact can be added.
The auxiliary contact is normally closed when transfer switch is in utility mode. Contacts will open when transfer switch is in standby mode.
NOTE: Auxiliary contact is rated 10 amps at 125 or 250 volts AC, and 0.6 amps at 125 volts DC.

Fault Current Identification Label

See Figure 2-6. A Fault Current Identification Label is provided in the bag containing the unit owner’s manual and transfer switch manual operating handle. The 2017 NEC requires the short-circuit current rating of the trans fer equipment, based on type of overcurrent protective device protecting transfer equipment, be field marked on the exterior of the transfer equipment. For NEC compli ance, verify required short-circuit current rating of trans­fer switch before installation. The completed label provides the local Authority Having Jurisdiction (AHJ) with information they may require during inspection.
Apply label to the exterior of the transfer switch enclo-
­sure. Use a pen to fill in required information, and then
cover label with the clear protective decal.
-
-
Figure 2-5. Auxiliary Contact
003626
Figure 2-6. Fault Current Identification Label
NOTE: The 2020 NEC code change omits this field labeling requirement for one- and two-family dwelling units.
Automatic Transfer Switch Owner’s Manual 9
Page 14
Installation
This page intentionally left blank.
10 Automatic Transfer Switch Owner’s Manual
Page 15

Section 3: Operation

(000121)
CAUTION
Equipment damage. Perform functional tests in the exact order they are presented in the manual. Failure to do so could result in equipment damage.
(000132)
DANGER
Electrocution. Do not manually transfer under load. Disconnect transfer switch from all power sources prior to manual transfer. Failure to do so will result in death or serious injury, and equipment damage.
(000122)
CAUTION
Equipment damage. Do not use excessive force while manually operating the transfer switch. Doing so could result in equipment damage.
B
009339
A
Operation

Functional Tests and Adjustments

Following transfer switch installation and interconnection, inspect entire installation carefully. A competent, qualified electrician should inspect it. The installation should strictly comply with all applicable codes, standards, and regulations. When absolutely certain installation is cor rect, complete a functional test of the system.
IMPORTANT NOTE: Before proceeding with func­tional tests, read and verify all instructions and infor­mation in this section is understood. Also read information and instructions of labels and decals affixed to transfer switch. Note any options or acces­sories that might be installed and review their opera­tion.

Manual Operation

Manual operation handle in UP position—
LOAD terminals (T1, T2) are connected to util­ity terminals (N1, N2).
Manual operation handle in DOWN position–
LOAD terminals (T1, T2) are connected to EMERGENCY terminals (E1, E2).

Close to Utility Source Side

Before proceeding, verify position of transfer switch by observing position of manual operation handle in
3-1. If manual operation handle is UP, contacts are
closed in utility (normal) position. No further action is required. If manual operation handle is DOWN, proceed
­with Step 1.
1. With manual operation handle inserted into mov­able contact carrier arm, move handle UP. Hold on to manual operation handle as it will move quickly after the center of travel.
2. Remove manual operating handle from movable contact carrier arm. Return manual operation han dle to storage bracket.
Figure
-
See Figure 3-1. A manual handle (B) is shipped with the transfer switch manual. Manual operation must be veri­fied BEFORE transfer switch is operated electrically. Pro­ceed as follows to verify manual operation:
1. Verify generator is in OFF mode.
2. Turn off both utility (service disconnect circuit
breaker) and emergency (generator main line cir cuit breaker) power supplies to transfer switch.
3. Note position of transfer mechanism main contacts (A) by observing the movable contact carrier arm. This can be viewed through the long narrow slot in the inside cover. The top of the movable contact carrier arm is yellow to be easily identified.
Automatic Transfer Switch Owner’s Manual 11
Figure 3-1. Manual Operation
-
Page 16
Operation
(000129)
DANGER
Electrocution. High voltage is present at transfer switch and terminals. Contact with live terminals will result in death or serious injury.
(000123)
DANGER
Electrocution. Turn utility supply OFF before working on utility connections of the transfer switch. Failure to do so will result in death or serious injury.
(000129)
DANGER
Electrocution. High voltage is present at transfer switch and terminals. Contact with live terminals will result in death or serious injury.

Close to Generator Source Side

Before proceeding, verify position of transfer switch by observing the position of the manual operation handle in
Figure 3-1. If manual operation handle is DOWN, con-
tacts are closed in generator (standby) position. No fur­ther action is required. If manual operation handle is UP,
oceed with Step 1.
pr
1. With
2. Rem
manual operation handle inserted into mov-
able contact carrier arm, move manual operation
andle DOWN. Hold on to manual operation han-
h dle as it will move quickly after the center of travel.
ove manual operating handle from movable contact carrier arm. Return manual operation han­dle to storage bracket.

Return to Utility Source Side

Proceed as follows to return to utility source side:
1. Ma
2. Rem
nually actuate transfer switch to return manual
operating handle to the UP position.
ove manual operating handle from movable contact carrier arm. Return manual operation han­dle to storage bracket.

Voltage Checks

Generator Voltage Checks

Proceed as follows to check generator voltage:
1. Se
2. Allow
3. Set
4. V
lect MANUAL mode on generator panel. Gener-
ator will crank and start.
generator to stabilize and warm up at no-load
for at least five minutes.
generator's main circuit breaker (CB1) to ON
(CLOSED).
erify no-load, voltage, and frequency with an accurate AC voltmeter and frequency meter. Mea­sure across ATS terminal lugs E1 to E2; E1 to
EUTRAL and E2 to NEUTRAL.
N
Frequency 60–62 Hz
Terminals E1 to E2 240–246 VAC
Terminals E1 to NEUTRAL 120–123 VAC
Terminals E2 to NEUTRAL 120–123 VAC
NOTE: Use the Digital Multimeter (DMM) LowZ low input impedance setting to collect accurate voltage measure­ments. LowZ eliminates the possibility of inaccurate ghost voltage readings, also known as phantom voltage or stray voltage readings. See DMM manufacturer’s liter­ature for additional information.
5. Turn off generator supply to transfer switch when generator supply voltage is correct and compatible with transfer switch ratings.
6. Set
7. Pre
generator main circuit breaker (CB1) to OFF
(OPEN).
ss OFF on generator panel to shut down gener-
ator.

Utility Voltage Checks

IMPORTANT NOTE: DO NOT proceed until generator AC
output voltage and frequency are correct and within stated limits. If no-load voltage is correct but no-load frequency is incorrect, engine governed speed may require adjustment. If no-load frequency is correct but voltage is not, voltage regulator may require adjustment.

Generator Tests Under Load

Proceed as follows to perform generator tests under load:
1. Set
Proceed as follows to check utility voltage:
1. T
urn on utility power supply to transfer switch using
utility service disconnect circuit breaker.
2. With
12 Automatic Transfer Switch Owner’s Manual
an accurate AC voltmeter, check for correct voltage. Measure across ATS terminal lugs N1 and N2; N1 to NEUTRAL and N2 to NEUTRAL.
2. Set
3. Ma
4. Sele
generator main line circuit breaker (MLCB) to
OFF (OPEN).
utility service disconnect circuit breaker of the transfer switch to OFF (OPEN), and turn OFF (OPEN) all load circuit breakers.
nually actuate transfer switch main contacts to
emergency (STANDBY) position. See Manual
Operation.
ct MANUAL mode to start the generator. Allow
engine to stabilize for a few minutes, and close lid.
Page 17
Operation
5. Set generator MLCB to ON (CLOSED). Generator now powers all LOAD circuits. Verify generator operation under load as follows:
Turn on electrical loads to the full rated watt-
age/amperage capacity of generator. DO NOT OVERLOAD.
With maximum rated load applied, check volt-
age and frequency across transfer switch ter­minals E1 and E2. Voltage should be greater than 230 VAC (240 VAC system); frequency should be greater than 59 Hz.
Verify fuel pressure remains within acceptable
parameters (see generator installation man­ual).
Allow generator to run under rated load for at
least 30 minutes. With unit running, inspect for unusual noises, vibration, or overheating that might indicate a problem.
6. Set generator MLCB to OFF (OPEN) when test under load is complete.
7. Allow generator to run at no-load for several min­utes. Then, shut down generator by pressing OFF.
8. Set main switch contacts to utility.
NOTE: See Manual Operation. Handle and operating
lever of transfer switch should be in down position.
9. Set utility service disconnect circuit breaker of transfer switch to ON (CLOSED).
System is now set for fully automatic operation.

Checking Automatic Operation

Proceed as follows to check system for correct automatic operation:
1. Verify generator is in OFF mode.
2. Set utility service disconnect circuit breaker of the
transfer switch to OFF (OPEN).
3. Verify switch is de-energized.
4. Install front cover of transfer switch.
5. Set transfer switch utility service disconnect circuit
breaker to ON (CLOSED).
6. Set generator MLCB to ON.
7. Select AUTO on generator control panel. System is
now ready for automatic operation.
8. Set transfer switch utility service disconnect circuit breaker to OFF (OPEN).
With generator ready for automatic operation, engine should crank and start when utility source power is turned off after a five second delay (factory default setting). After starting, transfer switch should connect load circuits to standby side after a five second delay. Allow system to operate through entire automatic sequence of operation.
With generator running and loads powered by generator AC output, set transfer switch utility service disconnect circuit breaker to ON (CLOSED). The following will occur:
After approximately 15 seconds, transfer switch will
transfer loads to utility power source.
Approximately one minute after transfer, generator
should shut down.
With generator in AUTOMATIC mode, system is now set for fully automatic operation.

Installation Summary

1. Verify installation has been performed correctly as
outlined by the manufacturer and that it meets all applicable laws and codes.
2. Test and verify correct operation of the system as outlined in the appropriate installation and owner’s manuals.
3. Educate end-user on correct operation, mainte­nance, and service call procedures.
NOTE: The utility power circuit breaker in transfer switch must be turned OFF to simulate a utility outage. Shutting off main disconnect in a subpanel connected to transfer switch will NOT simulate an outage.

Shutting Generator Down While Under Load

IMPORTANT NOTE: To avoid equipment damage, fol­low these steps, in order, when shutting the genera­tor down during utility outages. Shutdowns may be required during outages to perform routine mainte­nance or to conserve fuel.
To turn generator OFF (while running in AUTO and online):
1. Turn main utility disconnect off.
2. Turn generator MLCB (generator disconnect) to
OFF (OPEN).
3. Run generator for approximately one minute to cool down.
4. Turn generator OFF.
To turn generator back ON:
1. Put generator into AUTO mode. Start generator
and warm-up for a few minutes.
2. Set MLCB (generator disconnect) to ON (CLOSED).
The system now operates in AUTO mode. The main util­ity disconnect can be turned ON (CLOSED). To shut unit off, repeat this complete process.
Automatic Transfer Switch Owner’s Manual 13
Page 18
Operation
10000004183
Rev. A M1704
A
005450

Shutting Generator Down To Perform Maintenance

Proceed as follows to shut down generator for mainte­nance:
1. Press OFF button on controller.
2. Turn main utility disconnect OFF (OPEN).
3. Turn MLCB (generator disconnect) on generator to
OFF (OPEN) and follow maintenance proce dure(s).
To turn generator back ON:
1. Turn main utility disconnect ON (CLOSED).
2. Put generator into AUTO mode.
3. Set MLCB (generator disconnect) on generator to
ON (CLOSED).
The system is now in AUTO mode.

Testing the SACM

A TEST pushbutton is provided on top of the SACM to test operation of load shed functions. The TEST button will work when ATS is in utility or generator position. Pro ceed as follows to test the SACM:
1. Turn on utility supply to ATS.
2. Verify managed loads are powered and all LEDs
illuminate on SACM.
3. Press TEST button on the SACM.
4. Verify all of the connected loads to be “shed” are
disabled.
5. After five minutes, verify A/C 1 is energized and Status LED A/C 1 is ON.
6. After another 15 seconds, verify A/C 2 is energized and Status LED A/C 2 is ON.
7. After another 15 seconds, verify Load A/C 3 is energized and Status LED Load A/C 3 is ON.
8. After another 15 seconds, verify A/C 4 is energized and Status LED A/C 4 is ON.

Testing The SMM

See SMM owner’s/installation manual for testing proce­dure.

Fuse Removal and Installation

See Figure 3-2. A fuse removal and installation tool (A) is included in the control housing.
-
-
Figure 3-2. Fuse Removal and Installation Tool
If a fuse requires replacement, snap tool free with an appropriate tool such as diagonal pliers, and use it to replace fuse. The tool can be stored in the control hous ing retainer directly above the fuses, with the large thumb tab facing out.
Use only Generac replacement fuses—part number 100000005117, rated 240 VAC, 6.3 Amps, 10,000 AIC.
Alternative fuses are Littelfuse® 021606.3MXHP or Opti­fuse® FCD-6.3.
-
14 Automatic Transfer Switch Owner’s Manual
Page 19

Section 4: Drawings and Diagrams

Installation Drawing

No. 10000047450

Drawings and Diagrams
Automatic Transfer Switch Owner’s Manual 15
Page 20
Drawings and Diagrams

Interconnection Drawing

No. 10000047283—Page 1 of 4 (Liquid-Cooled Engine Generator)

16 Automatic Transfer Switch Owner’s Manual
Page 21

No. 10000047283—Page 2 of 4 (Liquid-Cooled Engine Generator)

Drawings and Diagrams
Automatic Transfer Switch Owner’s Manual 17
Page 22
Drawings and Diagrams

No. 10000047283—Page 3 of 4 (Air-Cooled Engine Generator)

18 Automatic Transfer Switch Owner’s Manual
Page 23

No. 10000047283—Page 4 of 4 (Air-Cooled Engine Generator)

Drawings and Diagrams
Automatic Transfer Switch Owner’s Manual 19
Page 24
Drawings and Diagrams
This page intentionally left blank.
20 Automatic Transfer Switch Owner’s Manual
Page 25
Drawings and Diagrams
This page intentionally left blank.
Automatic Transfer Switch Owner’s Manual 21
Page 26
Drawings and Diagrams
This page intentionally left blank.
22 Automatic Transfer Switch Owner’s Manual
Page 27
Page 28
Part No. A0000023930 Rev B 06/27/19 ©2019 Generac Power Systems, Inc. All rights reserved. Specifications are subject to change without notice. No reproduction allowed in any form without prior written consent from Generac Power Systems, Inc.
®
Generac Power Systems, Inc.
S45 W29290 Hwy. 59 Waukesha, WI 53189
1-888-GENERAC (1-888-436-3722)
www.generac.com
Loading...