Generac Power Systems NP-40G User Manual

Manual Part No. 94468-A
SERVICE
Manual
COMPUTER
CONTROLLED
VARIABLE
SPEED RV
GENERATORS
P. O. Box 8 PH ONE: (414) 544-4811
Printed In U.S.A.
Waukesha, Wisconsin 53187
_________
FA X: (414) 544-4851
REVISED: 05/16/96

SAFETY

Throughout this publication, ’DANGERl" and "CAUTiONI" blocks are used to alert the mechanic to special
Instructions concerning a particular service or operation that might be hazardous if performed Incorrectly or carelessly. PAY CLOSE ATTENTION TO THEM.
DANGER!
UNDER THIS HEADING WILL BE FOUND SPECIAL INSTRUCTIONS WHICH, IF NOT COMPLIED WITH, COULD RESULT IN PERSONAL INJURY OR DEATH.
CAUTION!
Under this heading will be found special instructions which, if not complied with, couid result in damage to equipment and/or property.
These ‘Safety Alerts” alone cannot eliminate the hazards that they signal. Strict compliance with these special
Instructions plus ‘common sense” are major accident prevention measures.

NOTICE TO USERS OF THIS MANUAL

This SERVICE MANUAL has been written and published by Generac to aid our dealers’ mechanics and company
service personnel when servicing the products described herein.
It Is assumed that these personnel are familiar with the servicing procedures for these products, or like or similar products manufactured and marketed by Generac. That they have been trained in the recommended servicing procedures for these products. Including the use of common hand tools and any special Generac tools or tools from other suppliers.
Generac could not possibly know of and advise the service trade of all conceivable procedures by which a service might be performed and of the possible hazards and/or results of each method. We have not undertaken any such wide evaluation. Therefore, anyone who uses a procedure or tool not recommended by Generac must
first satisfy himself that neither his nor the products safety will be endangered by the service procedure selected.
All information. Illustrations and specifications in this manual are based on the latest product information
available at the time of publication.
When working on these products, remember that the electrical system and engine Ignition system are capable
of violent and damaging short circuits or severe electrical shocks. If you intend to perform work where electrical terminals could be grounded or touched, the battery cables should be disconnected at the battery.
Any time the Intake or exhaust openings of the engine are exposed during service, they should be covered to
prevent accidental entry of foreign material. Entry of such materials will result In extensive damage when the engine Is started.
During any maintenance procedure, replacement fasteners must have the same measurements and strength as
the fasteners that were removed. Metric bolts and nuts have numbers that indicate their strength. Customary bolts use radial lines to indicate strength while most customary nuts do not have strength markings. Mismatched or Incorrect fasteners can cause damage, malfunction and possible injury.

REPLACEMENT PARTS

Components on Generac recreational vehicle generators are designed and manufactured to comply with
Recreational Vehicle Industry Association (RVIA) Rules and Regulations to minimize the risk of fire or explosion. The use of replacement parts that are not In compliance with such Rules and Regulations could result In a fire or explosion hazard. When servicing this equipment it is extremely important that all components be properly Installed and tightened. If improperly Installed and tightened, sparks could ignite fuel vapors from fuel system
leaks.
PART
TITLE

SERVICE

MANUAL

COMPUTER
CONTROLLED
VARIABLE
SPEED RV
GENERATORS
1 2 3
4
5 6 7 TROUBLESHOOTING
8
THE AC GENERATOR
ENGINE MECHANICAL
GASOLINE FUEL SYSTEM
GASEOUS FUEL SYSTEM
ENGINE OIL & COOLING SYSTEM
ENGINE ELECTRICAL SYSTEM
SPECIFICATIONS & CHARTS
Part 1
THE AC
GENERATOR
COMPUTER
CONTROLLED
VARIABLE
SPEED RV
GENERATORS
SECTION
1.2
1.3
1.4
1.5
1.6
1.7
TITLE
TaEnE!53tT5i?TOnï55mÇÏTRB"
GENERATOR MAJOR COMPONENTS
OPERATIONAL ANALYSIS
INSULATION RESISTANCE
COMPONENTS TESTING
CONTROL PANEL
SHEET METAL
Section 1.1- GENERATOR FUNDAMENTALS

Magnetism

Magnetism can be used to produce electricity and
electricity can be used to produce magnetism.
Much about magnetism cannot be explained by our present knowledge. However, there are certain patterns of behavior that are known. Application of these behavior patterns has led to the development of generators, mo tors and numerous other devices that utilize magnetism to produce and use electrical energy.
See Figure 1. The space surrounding a magnet Is permeated by magnetic lines offeree called "flux“. These lines offeree are concentrated at the magnet’s north and south poles. They are directed away from the magnet at Its north pole, travel In a loop and re-enter the magnet at Its south pole. The lines of force form definite patters which vary In Intensity depending on the strength of the magnet The lines of force never cross one another. The area surrounding a magnet In which Its lines offeree are effective Is called a "magnetic field".
Like poles of a magnet repel each other, while unlike poles attract each other.

Electromagnetic Fields

AM conductors through which an electric current Is flowing have a magnetic field surrounding them. This field Is always at right angles to the conductor. If a compass Is placed near the conductor, the compass needle will move to a right angle with the conductor. The following rules apply:
NOTE: The "right hand rule" Is based on the "current flow" theory which assumes that current flows from positive to negative. This Is opposite the "electron" theory, which states that current flows from negative to positive.

Electromagnetic induction

An electromotive force (EMF) or voltage can be pro duced In a conductor by moving the conductor so that it cuts across the lines of force of a magnetic field.
Similarly, if the magnetic lines of force are moved so that they cut across a conductor, an EMF (voltage) will be produced In the conductor. This Is the basic principal of the revolving field generator.
Figure 3, below. Illustrates a simple revolving field generator. The permanent magnet (Rotor) Is rotated so that its lines of magnetic force cut across a coll of wires called a Stator. A voltage Is then Induced into the Stator windings. If the Stator circuit Is completed by connecting a load (such as a light bulb), current will flow in the circuit and the bulb will light.
□ The greater the current flow through the conductor,
the stronger the magnetic field around the conduc tor.
□ The Increase In the number of lines of force Is di
rectly proportional to the Increase In current flow and the field Is distributed along the full length of the conductor.
D The direction of the lines of force around a conduc
tor can be determined by what Is called the "right hand rule". To apply this rule, place your right hand around the conductor with the thumb pointing In the direction of current flow. The fingers will then be pointing in the direction of the lines of force.

Alternating Current

A simple generator consists of a coil of wires called a Stator and a magnetic field called a Rotor. As the Rotor’s magnetic field cuts across the Stator coll, a voltage Is induced into the Stator windings. The amount of Induced voltage is equal to the strength of the magnetic field.
Page 1.1-1
Section 1.1- GENERATOR FUNDAMENTALS

Alternating Current (Continued)

See Figure 4. The current alternates according to the position of the Rotor’s poles in relation to the position of the Stator. At 0* and again at 180*, no current flow Is produced. At 90’ of Rotor rotation, current flow reaches a maximum positive value. Rotor rotation to 270’ brings another maximum flow of current. However, at 270’ the current flow has reversed In polarity and now flows in the opposite direction.

Electrical Units

AMPERE;
The rate of electron flow in a circuit is represented by the AMPERE. The ampere is the number of electrons flowing past a given point at a given time. One AMPERE Is equal to Just slightly more than six thousand million billion electrons per second.
With alternating current (AC), the electrons flow first In one direction, then reverse and move In the opposite direction. They will repeat this cycle at regular intervals. A wave diagram, called a “sine wave“ shows that current goes from zero to maximum positive value, then reverses and goes from zero to maximum negative value. Two reversals of current flow Is called a cycle. The number of cycles per second Is called frequency and is usually stated in "Hettz".
Page 1.1-2
VOLT:
The VOLT is the unit used to measure electrical PRES­SURE, or the difference In electrical potential that causes electrons to flow. Very few electrons will flow when voltage is weak. More electrons will flow as voltage becomes stronger. VOLTAGE may be consdiered to be a state of unbalance and current flow as an attempt to regain balance. One volt is the amount of EMF that will cause a current of 1 ampere to flow through 1 ohm of resistance.
Figure 6. Electrical Units
Conductor of a Circuit
AMPERE - Unit measuring rate of
L.
OHM - Unit measuring resistance
or opposition to flow
current flow (nunfcer of elec trons past a given point)
■ VOLT - Unit measuring force or _____
difference in potential
causing current flow
Section 1.1- GENERATOR FUNDAMENTALS
OHM:
The OHM Is the unit of RESISTANCE. In every circuit there Is s natural resistance or opposition to the flow of electrons. When an EMF Is applied to a complete circuit, the electrons are forced to flow In a single direction rather than their free or orbiting pattern. The resistance of a conductor depends on (a) Its physical makeup, (b) Its cross-sectional area, (c) Its length, and (d) Its temper ature. As the conductor’s temperature Increases, Its re sistance Increases In direct proportion. One (1) ohm of resistance will permit one (1) ampere of current to flow when one (1) volt of electromotive force (EMF) Is applied.

Ohm’s Law

A definite and exact rela tionship exists between VOLTS, OHMS and AMPERES. The value of one can be calcu lated when the value of the other two are known. Ohm’s
Law states that In any circuit
the current will Increase when voltage Increases but resis tance remains the same, and current will decrease when re
sistance Increases and volt
age remains the same.
If AMPERES Is unknown while VOLTS and OHMS are
known, use the following formula:
i AMPS
\(l)
OHMS j
(R)y
The magnetic field around the conductor Induces elec
tromotive forces that cause current to keep on flowing while voltage drops. The result Is a condition In which voltage leads current When a conductor Is formed Into a coll, the magnetic lines of force are concentrated In the center of the coll. This Increased density causes an Increase In magnetically Induced EMF without Increas ing current Thus, colls cause Inductive reactance.
Inductive reactance can also be caused by placing an
Inductlonmotoronthe circuit which utilizes the current’s magnetic field for excitation.
AMPERESs VOLTS
■ÖHMS"
If VOLTS is unknown while AMPERES and OHMS are
known, use the following formula:
VOLTS 3 AMPERES X OHMS If OHMS Is unknown but VOLTS and
AMPERES are unknown, use the following:
OHMS: VOLTS
AMPERES

Reactance in AC Circuits

GENERAL:
When direct current (DC) Is flowing, the only opposi
tion to current flow that must be considered is resistance (ohms). This Is also true of alternating current (AC) when only resistance type loads such as heating and lamp elements are on the circuit In such a case, current will be In phase with voltage- that Is, the current sine wave will coincide In time with the voltage sine wave.
However, two factors In AC circuits called INDUCTIVE
and CAPACITIVE REACTANCE will prevent the voltage and current sine waves from being In phase.
INDUCTIVE REACTANCE:
This condition exists when current lags behind volt
age (Figure 8). As current flows In a circuit, magnetic
lines offeree are created at right angles to the conductor. The continuous changes In current value (from positive to negative) cause these magnetic lines to collapse and
build up continuously.
CAPACITIVE REACTANCE:
This condition occurs when current leads voltage (Fig
ure 9). It might be thought of as the ability to oppose change In voltage. Capacitance exists In a circuit when certain devices are (a) capable of storing electrical
charges as voltage Increases and (b) discharging these
stored charges when the voltage decreases.
Section 1.1- GENERATOR FUNDAMENTALS
introduction to CCG’s
WHAT IS A "CCG"?:
The initials “CCG” stand for “computer con
trolled generator“. Such units are different from conventional generators in that the performance of the engine and AC generator are more accurately matched over a wide range of power needs. The CCG’s provide greater efficiency of both the engine and the generator while maintaining electrical out put within an acceptable voltage and frequency band.
CCG units have the ability to operate the engine over a wide range of speeds, while conventional generators will deliver correct AC frequency and voltage only at a fixed rpm. The unit’s electrical output is fed through an AC-AC converter which reconstructs electrical waveforms to the correct output frequency.
Unlike conventional AC generators, the CCG can match engine speed to load requirements. This provides several advantages, as follows:
П Smaller engines can be used to produce more
power than on a conventional generator, since it can be allowed to run at a higher speed.
When the load is reduced, the engine can run
at slower than the usual speeds. This improves fuel economy and reduces engine noise.
The CCG unit can be operated closer to its peak
power point at all times, because output volt
age and current are functions of engine speed. This allows fora much more compact generator design.
CCG SYSTEM OVERVIEW:
Figure 10 is a block diagram of the CCG system.
The major elements of the system are represented
in the diagram. Operation of the system may be described briefly as follows:
1. The engine is directly coupled to a permanent magnet type Rotor, so the Rotor runs at the same speed as the engine.
2. As the Rotor turns. Its magnetic field cuts across
the Stator windings to induce a voltage into the Stator.
a. The Stator is a 2-phase type with center tap. b. Stator AC output frequency Is between 336 and
540 Hertz. This corresponds to engine speeds of 2520 to 4050 rpm.
c. The load requires a nominal AC frequency of 60 Hertz. Thus, the generated frequency Is six to nine times the desired range.
3. A Frequency Converter changes the high fre quency output to a useful frequency, I.e., one that is compatible with load requirements of about 60 Hertz.
4. A Voltage Detector circuit senses load voltage and signals a System Control circuit.
5. The System Control circuit establishes the RE
QUIRED ENGINE SPEED for correct voltage and
delivers an output to an Engine Controller.
6. The Engine Controller adjusts the engine’s Throttle to change engine speed and establish the correct AC output voltage.
7. The following facts should be apparent:
LOAD FREQUENCY IS CONTROLLED BY THE
“FREQUENCY CONVERTER“ DEVICE.
VOLTAGE IS CONTROLLED BY A “SYSTEM
CONTROL“ CIRCUIT WHICH CHANGES EN GINE SPEED TO MAINTAIN A CONSTANT
VOLTAGE AT VARYING ELECTRICAL LOADS.
Page 1.1-4
Section 1.1- GENERATOR FUNDAMENTALS

Why Variable

Most electrical loads will operate satisfactorily only within a relatively small voltage band. In order to provide useful voltage at larger load currents, It is necessary to increase engine speed.
In conventional AC generators, some form of voltage regulation Is needed to provide correct voltage in the full range of load current. This Is often accomplished by regulating excitation cur rent to the Rotor (fíelo) which then regulates the strength of the Rotor’s magnetic field. The voltage
Induced Into the Stator windings Is proportional to
the strength of the Rotor’s magnetic field.

Speed Control?

The CCG uses a Rotor having a fixed and perma
nent magnetic field. The strength of this magnetic
field Is fixed and cannot be regulated.
The output voltage on CCG generators tends to
droop with Increasing electrical loads. The SYS TEM CONTROLLER maintains a constant AC out
put voltage by Increasing engine and Rotor speed
as the load current increases, to offset this Inherent voltage droop.
The SYSTEM CONTROLLER also selects the cor rect number of generator pulses which are com bined to form each 60 Hertz "half-cycle“.
Section 1.1- GENERATOR FUNDAMENTALS
Page 1.1-6
Section 1.2- MAJOR GENERATOR COMPONENTS

Introduction

Major components of the generator proper are shown in Figure 1, beiow. Externai sheet metal and other unrelated components are omitted from the drawing for clarity. These parts are:
ITEM
1 2 3 4 5 6 7 8 9
10
NOMENCLATURE

Upper Fan Housing

Upper Cooling Fan

Permanent Magnet Rotor

Rotor Hub
Stator Retaining Ring
Stator Assembly
Stator Adapter
Engine
Lower Fan & Flywheel
Stepper Motor
Upper Fan Housing
As its name implies, this component houses and
shields the upper cooling fan. See Figure 1, Item
1.
Upper Cooling Fan
The Cooling Fan draws air Into the generator
through slots in the Upper Fan Housing. It Is fas tened to and rotates with the Permanent Magnet
Rotor.
Permanent Magnet Rotor
Sixteen permanent magnets have been affixed to
the Rotor. A starter ring gear is welded to the Rotor. The Rotor and Hub are balanced at the fac tory as an assembly and must be replaced as an assembly.
NOTE: The hub MUST be properly aligned during
reassembiy. The mounting bolt, housing opening and magnet must be properly aligned. In addition, match marks between the Hub and Rotor must be' aiigned as indicated by an “ALIGN MARKS FOR BALANCE” decal. During assembiy, use care to avoid damage to the Ignition Sensor.______________
DANGERI
THE PERMANENT MAGNET ROTOR PRODUCES AN EXTREMELY STRONG MAGNETIC FORCE.
USE CARE DURING INSTALLATION TO AVOID PINCHED FINGERS.
Page 1.2-1
Section 1.2- MAJOR GENERATOR COMPONENTS

Rotor Hub

See Figure 2. The Rotor Hub Is balanced with the Rotor and must be replaced with the Rotor as an assembly. Part of the engine ignition system is pressed onto the Hub and can be replaced only as part of the Rotor and Hub assembly.

Stator Retaining Ring

The Stator Retaining Ring is made of dIe-cast aluminum. Four hex head capscrews with lockwashers pass through holes in the Retaining Ring, to retain the Stator Assembly to the Stator
Adapter (Item 7, Figure 1).

Stator Assembly

The 2-phase Stator is made up of eight (8) wind ings, with leads brought out as shown in figure 3. Figure 4 is a schematic representation of each sta
tor winding. Note that there are four (4) power
phase windings (Leads AC2, AC1, SI2, SI1 and 11);
a timing winding (Leads TIM1 and TIM2); a power supply winding (Leads PS1, PS2); and a dual bat tery charge winding (Leads 55, 66, 77). The Stator produces a frequency of 336 to 540 Hertz, which corresponds to engine speeds between 2520 and 4050 rpm. This means the gen erated frequency is between six and nine times
the desired frequency of about 60 Hertz.

Stator Adapter

The Adapter Is retained to the engine by means of four hex head capscrews. The Stator Is retained to the Stator Adapter and Is “sandwiched'' between the Adapter and the Stator Retaining Ring.

Lower Fan & Flywheel

The Lower Fan and Flywheel are retained to the engine PTO shaft by means of a conical washer and an Ml 6-1.50 hex nut. When assembling, tighten the flywheel nut to 75 foot-pounds.

Engine

The engine is a single cyclinder, overhead valve type manufactured by Generac Corporation. De pending on the specific generator Model Number, either a GN-190 or a GN-220 engine is used on NP-30 and NP-40 RV generators.
sponse to changes In AC output voltage. Thus, In response to decreasing AC output voltages, the Motor will increase the throttle setting and engine speed will Increase. Conversely, Increasing AC output voltages will cause the Motor to decrease
throttle setting and engine speed will decrease.
Figure 3. Stator Pictorial View
-66 (BROWN)-
—77 (BROWN) T1M1 (ORANGE)
—TM2 (GRAY)
-PS1 (BROWN)-
-AC2 (YELLOW)
-AC1 (GRAY)—
-SL1 (ORANGE)—
-----
SL2 (BROWN)-------------
Figure 4. Schematic- Stator Windings
POWER PHASE 1
POWER PHASE 2
AC1 aC2
I ! I
POWER I TIMING
SUPPLY I I
PS1 PS2
C «r ® ®
-55 (BLACK)
--------
»<§)
H T1M1 (
PS2 (YELLOW)
■11 (BLUE)
---------
AC2
I (7»CT«r|
II è
b
SL2
è

Stepper Motor

The Stepper Motor (Figure 5, next page) consists of a stepper motor along with a gear and cam arrangement which allows motor movement to change the engine carburetor throttle setting. The Motor Is controlled by output signals from the Com puter Control Circuit Board, which calculates the number of steps the stepper needs to take and generates the required signals to the Motor. The circuit board signals the Motor to actuate in re
Page 1.2-2
BATTERY CHARGE
Section 1.2- MAJOR GENERATOR COMPONENTS

The Genistor

GENERAL:
See Figure 6. The GENISTOR is often called a “frequency converter“ (also see "Introduction to CCG’s“ on Page 1.1-4). its function is to change the high frequency AC output of the Stator (336-540 Hertz) to a useful frequency (about 56-60 Hertz).
The Genistor has no intelligence of Its own. It is simply a high speed switcning device which is controlled by the CCG circuit board.
Switching signals from the CCG circuit board are
also delivered to the Genistor. These signals switch the Genistor on and off as required, result
ing In a sine wave output to the load as shown in
Figure 8.
Figure 6. The dtenhtor
GENISTOR THEORY:
The purpose of a “frequency converter“ is to
divide the Stator AC output frequency by an inte gral factor to provide a useful output frequency. Each of the four half-phases of the center-tapped Stator Is Genistor-controlled.
Figure 7 shows the sine wave output from the
2-phase Stator windings. This output Is delivered to the Genistor switching module.

The CCG Circuit Board

GENERAL:
The CCG circuit board has several functions as
follows:
1. It controls the operation of the “frequency con
verter“ (Genistor).
2. It controls AC output voltage under all load requirements by controlling engine speed.
3. It protects the system against various faults.
FREQUENCY CONTROL:
The CCG board will adjust the number of alterna
tor cycles In one output cycle to control AC output frequency. The number of cycles is based on en gine rpm and the output frequency will be main tained in the 55-65 Hertz band.
The board uses a "zero crossing" detector to synchronize an internal clock. The frequency of the Stator’s waveform is measured and, with referencve to the required output frequency, a “fre­guency divisor" is calculated. The circuit board then signals the Genistor (frequency converter) to switch on and off at the proper times so that fre quency Is maintained in the 55-65 Hertz band.
Page 1.2-3
Section 1.2- MAJOR GENERATOR COMPONENTS

The CCG

VOLTAGE CONTROL:
The CCG circuit board utilizes a closed-loop,
proportional-derivative controller which regulates RMS voltage by changing engine speed. The sys tem maintains output voltage at about 115 volts at the lowest rpm and 120 volts up to the maximum rpm.
The board controls a Stepper Motor (Figure 5),
which moves the throttle. The board calculates the number of steps the Motor needs to take and sig nals the Motor to move. Motor movement changes
throttle position and changes In engine speed re
sult.
FAULT PROTECTION:
The CCG board has the ability to detect several
fault conditions and shut the engine down, as fol
lows:
1. Overvoltage:- If the output voltage exceeds 127
VAC for longer than 15 seconds, the board will turn AC output power off and shut the engine down.
2. Undervoitage:- If output remains below about 96 VAC longer than 15 seconds, an overload condition probably exists. The board will then turn AC output off and shut the engine down.
3. Overspeed:- if engine speed exceeds 4500 rpm, shutdown will occur.
4. Failure of the Genistor (frequency converter) will result in engine shutdown.
5. Loss of output to any circuit connected to the board will result in engine shutdown.
Circuit Board (Continued)
CIRCUIT BOARD CONI
The board Is equipped with eight (8) connection points (receptacles). These are identified as
"CONNr through "CONNS". See Figure 9.
CONNECTOR CONNI
CONNECTIONS:
FUNCTION
Six-pin connector Interconnects
with speed control Stepper Motor.
CONN2
12-pin connector is NOT used on RV units. An orange jumper wire is connected across Pins 5 & 11.
CONN3
7-pin connector interconnects with
the Genistor.
CONN4
4-pln receptacle for connection of
the Stator power supply leads
(PS1, PS2) and the Stator timing
leads (TIM1, TIM2).
CONNS Single point connection for Stator
lead No. 11 (blue).
CONN6 Interconnects with the Genistor. CONN7 Single point connector Is NOT
used on RV units.
CONNS Single point connector for Wire 18B.
Interconnects with Engine Cont
roller circuit board, allows the
CCG board to shut the engine down.
-O
Figure 9. the CÔà Circuit Board
0 0 ^
C0NN4
CDNN8 CDNN7
CDNN5
a
u
JSl
_______________
Ì i
o
o
CGNN3 CDNN6
lij Itl lil Ui lli'ururuu umuuiuiuniniimui Ui'Ul uul
mfamfsifsifiifgifaifgimfiimfsimmisifCTm ijunj
■~L0r'
Page 1.2-4
Section 1.3- OPERATIONAL ANALYSIS
General
Figure 1, below, is a block diagram of the com puter controlled RV generator. The diagram la In tended only for the purpose of Illustrating genera tor operation. Refer to the actual wiring diagram for wiring interconnections.
Operational Description
1. The PERMANENT MAGNET ROTOR Is directly
coupled to the ENGINE and rotates at the same speed as the engine.
2. As the ROTOR turns, its magnetic field cuts across a number of STATOR windings, to Induce a voltage Into those windings. A voltage Is induced
Into the following STATOR windings:
a. Phase 1 and 2 of the STATOR POWER WIND
INGS (output leads AC1-AC2 and SL1-SL2).
b. The STATOR POWER SUPPLY WINDING with
output leads PS1-PS2.
c. The STATOR TIMING WINDING (output leads
TIM1-TIM2).
d. STATOR BATTERY CHARGE WINDING with
output leads 55,66 and 77.
Figure 1. Block Diagram- AC Generator System
3. STATOR BATTERY CHARGE WINDING o^ut Is delivered to the unit battery via a BATTERY CHARGE RECTIFIER (BCR) and a 1 OHM, 50 WATT RESISTOR. The circuit Is completed through the battery to frame ground and back to the BATTERY CHARGE WINDING via Wire 55.
4. STATOR TIMING WINDING output is delivered to
the CCG CIRCUIT BOARD. The circuit board mea sures the frequency of the waveform and calcu
lates a "frequency divisor" to maintain a useable
frequency to the CUSTOMER CONNECTION re
gardless of rpm.
5. The STATOR POWER SUPPLY WINDING output Is delivered to the CCG CIRCUIT BOARD. This is
the power supply for operation of the circuit board and GENISTOR.
6. STATOR POWER WINDING OUTPUT (Phase 1
and 2) Is delivered to a GENISTOR. The GENISTOR
is a nIgh-speed switching device which is con
trolled by the CCG board.
7. The CCG CIRCUIT BOARD senses voltage and
frequency and then acts to control voltage and frequency as follows:
STATOR POWER WINDING AC1-AC2
WÀ‘§Ê2
STATOR
POWER
WINDING
SL1-SL2
STATOR
POWER
SUPPLY
WINDING
PS1-PS2
STATOR
TIMING
WINDING
TIM1-TIM2
WIRE18B
.(ENGINE
SHUTDOWN)
STATOR
BATTERY
CHARGE
WINDING
66-77
MAGNETIC FIELD
PERMANENT
MAGNET
ROTOR
ENGINE
Page 1.3-1
Section 1.3- OPERATIONAL ANALYSIS
Operational Description (Continued)
a. The circuit board senses actual voltage and b. The CCG board < "compares“ it to a pre-set “reference“ voltage of about 115-120 volts AC.
0) If voltage Is low, the board will signal a STEPPER MOTOR to change engine throttle setting and In crease speed until the desired voltage level Is reached.
If voltage goes high, the board will signal the
STEPPER MOTOR to reduce engine throttle setting until the desired voltage level Is obtained.
(3) Engine speed Is variable and Is used to control output voltage and may range from about 2520 to 4050 rpm.
acting on the GENISTOR. (1) The GENISTOR is a high speed switching
device. (2) The CCG board signals the Genistor to switch
generator waveforms on and off at the proper times. In order to maintain a frequency In the 55-65 Hertz band.
8. The CCG circuit board can protect the system against some faults by shutting the engine down, wire 18B is the “engine shutdown“ lead that con­nectcts this system to the Engine Controller circuit board. See “FAULT PROTECTION“, Page 1.2-4.
controls AC frequency by
Page 1.3-2
Section 1.4- INSULATION RESISTANCE

Dirt and Moisture

If moisture Is permitted to remain In contact with the generator Stator windings, some of It will be retained In voids and cracks of the winding Insulation. This can eventually cause a reduction In Insulation resistance and generator output may be affected.
Winding Insulation In Generac generators Is moisture resistant. However, prolonged exposure to water, high humidity, salt air, etc., will gradually reduce the resis tance of winding Insulation.
Dirt can make the problem even worse, since It tends to hold moisture Into contact with the windings. Salt, as from sea air, can also worsen the problem, since salt tends to absorb moisture from the air. When salt and moisture combine, they make a good electrical conduc tor.
Because of the detrimental effects of water, dirt and salt, the generator should be kept as dry and as clean as possible. Stator windings should be tested periodically using a Hi-Pot tester or a Megohmmeter. If insulation resistance is low, drying of the unit may be necessary. If resistance is still low after drying, the defective Stator should be replaced.

Insuiation Resistance Testers

One kind of Insulation resistance tester Is shown in Figure 1, below. Other types are commerlally available. The type shown has a "Breakdown” lamp which turns on to indicate an Insulation breakdown during the test.
One common type of tester is the "Megohmmeter" which measures resistance in "Megohms".
NO. COLOR CONNECTS TO
U 77
66 55 SL2 SL1 AC2 AC1 PS1 TIM1 PS2 TIM2
Blue Brown Brown
Black
Brown
Orange
Yellow
Gray
Brown
Orange
Yellow
Gray
Main Circuit Breaker CB1 Battery Charge Rectifier BCR Battery Charge Rectifier BCR
Grounding Terminal
Genistor fG) Genistor (G) Genistor (G) Genistor (G)
CCG Circuit Board (CCB)
CCG Circuit Board i CCB)
CCG Circuit Board l CCB)
CCG Circuit Board (CCB)
Figure 2. Stator Leads
— 55 (BLACK)-*^)
-66 (BROWN)
— 77 (BROWN) —(ORANGE)
PS2 (YELLOW)
—TM2 (GRAY) -
-PS1 (BROWN)­I (BLUE) —«0)
-AC2 (YELLOW)
-AC1 (GRAY)—
-SL1 (ORANGE)^—
CAUTION!
When using a Megohmmeter or any other tester, be sure to follow the manufacturer’s instructions carefully. All Stator leads must be isolated from other components, especially circuit boards, be fore performina tests. The high voltages used In testing Insuiation resistance will damage elec tronic components.

Stator Leads

The following leads are brought out of the Stator and
connected to various components in the unit:
-----
SL2 (BROWN)
-------------
■^0

Preparation for Tests

See Stator leads CHART above. Disconnect and Iso
late all Stator leads. ALL STATOR LEADS MUST BE DISCONNECTED AND ISOLATED BEFORE STARTING
THE TESTS.

Test Aii Stator Windings to Ground

Connect the ends of all Stator leads together. Make
sure none of the leads are touching any terminal or any
part of the generator.
Connect one Tester probe to the Junction of all Stator
leads; the other Tester probe to a clean frame ground on
the Stator. Apply a voltage of 1000 volts for about 1 second.
Follow the tester manufacturer’s Instructions care
fully. Some "Hl-Pot" testers are equipped with a "Break down" light which will turn ON to indicate an Insulation
breakdown.
A
"Megger" (Megohmmeter) will Indicate the "meg
s’’ of resistance. Normal Stator winding Insulation
ohms"
resistance is on the order of "millions of ohms" or "meg
ohms". The MINIMUM acceptable Insulation resistance
reading for Stators can be calculated using the following
formula.
MINIMUM INSULATION RESISTANCE (In “megohniis")
GENERATOR RATED VOLTS
-
------------------------------------------ +1 1000
Page 1.4-1
Section 1.4- INSULATION RESISTANCE
Test All Stator Windings to
Ground (Continued)
EXAMPLE: Generator rated voltage Is "120 VAC". Divide obtain the unit Is "1.12 megohms".
120 by 1000 to obtain "0.12". Add “1" to "1.12 . Minimum Insulation resistance for
.
..............................................■

Test for Shorts Between Windings

Figure 2 on the previous page shows the Stator leads that are brought out of the Stator. Figure 3 is a schematic representation of the eight (8) Stator windings. To test for shorts between windings, proceed as follows:
1. Make sure all Stator output leads are isolated from each other and from the frame.
2. POWER PHASE TO TIMING WINDINGS:- Connect one tester probe to Stator lead No. 11, the other test probe to Stator lead TIM1. Apply a voltage of 1000 volts. The Tester will Indicate a breakdown if the windings are shorted together.
3. POWER PASE TO POWER SUPPLY WINDINGS: Con nect one tester probe to Stator lead No. 11, the other tester probe to Stator lead PS1. Apply 1000 volts. If a breakdown Is Indicated, the windings are shorted to gether.
4. POWER PHASE TO BATTERY CHARGE WINDINGS:­Connect one tester probe to Stator Lead No. 11, the other probe to Stator lead No. 55. Apply 1000 volts. If break down Is Indicated, the windings are shorted together.
5. TIMING TO POWER SUPPLY WINDING:- Connect one tester probe to Stator lead No. TM1, the other test probe to Stator lead No. PS1. Apply 1000 volts. If breakdown is Indicated, the windings are shorted together.
6. TIMING TO BATTERY CHARGE WINDING:- Connect one test probe to Stator lead No. TIM1, the other test probe to Stator lead No. 55. Apply 1000 volts. If break down is Indicated the windings are shorted together.
7. POWER SUPPLY TO BATTERY CHARGE WINDING:­Connect one test probe to Stator lead No. PS1, the other probe to Stator lead No. 55. Apply 1000 volts. If break down is indicated, the windings are shorted together.

Results of Tests

1. If testing Indicates that Stator windings are shorted to ground, the Stator should be cleaned and dried. The Insulation resistance tests should then be repeated. If, after cleaning and drying, the Stator again fails the test, replace the Stator assembly.
2. If testing Indicates that a short between windings exists, clean and dry the Stator. Then, repeat the tests. If Stator fails a second test (after cleaning and drying), replace the Stator assembly.

Cleaning the Generator

GENERAL:
If testing indicates that the insulation resistance is below a safe value, the winding should be cleaned. Proper cleaning can be accomplished only while the generator is disassembled. The cleaning method used should be determined by the type of dirt to be removed. Be sure to dry the unit after it has been cleaned. An electric motor repair shop may be able to assist with cleaning. Such shops are often experienced in special problems (sea coast, marine, wetland applications, etc.).
Figure 3. Schematic- Stator Windings
pravm ппушт|
POWER PHASE 1
POWER ^ PHASE 2
BATTERY CHARGE
AC1
I
SL1
à
POWER
f
SUPPLY
PS1 PS2 .
О ^ О
11
AC2
h
SL2
h
TIMING
TIMI T1M2
USING SOLVENTS FOR CLEANING:
A solvent is generally required when dirt contains oil or grease. Only petroleum distillates should be used to clean electrical components. Recommended are safety
type petroleum solvents having a flash point greater than
100’ F. (38* C.).
Use a soft brush or cloth to apply the solvent. Use care
to avoid damaging magnet wire or winding Insulation. After cleaning, dry all components thoroughly with mois ture-free, low pressure compressed air.
DANGER!
DO NOT WORK WITH SOLVENTS IN ANY EN CLOSED AREA. ALWAYS PROVIDE ADEQUATE VENTILATION. FIRE, EXPLOSION OR OTHER HEALTH HAZARDS MAY EXIST UNLESS ADE QUATE VENTILATION IS PROVIDED. WEAR EYE PROTECTION. WEAR RUBBER GLOVES TO PRO TECT THE HANDS.
CAUTIONI
Some generators use epoxy or polyester base winding varnishes. Use solvents that do not at tack such materials.
Page 1.4-2
Section 1.4- INSULATION RESISTANCE

Drying the Generator

GENERAL:
If testing Indicates that the insulation resistance of a winding Is below a safe value, the winding should be dried before operating the unit Some recommended drying methods include (a) heating units and (b) forced air.
HEATING UNITS:
If drying Is needed, the generator can be enclosed In
a covering. Heating units can then be Installed to raise the temperature about 15’-18* F. (8*-10* C.) above ambi ent.
FORCED AIR:
Portable forced air heaters can be used to dry the
generator. Direct the heated air Into the generator’s air
intake openings. Run the unit at no-load. Air temperature
at the point of entry Into the generator should not exceed
150* F. (66* C.).
Section 1.4- INSULATION RESISTANCE
Page 1.4-4
Section 1.5- COMPONENTS TESTING

Introduction

Problems that occur In the computer-controlled
RV generator generally Involve the following sys
tems or components:
1. The engine.
2. The Speed Control System.
3. The AC Generator.
4. The Genistor.
5. Battery Charge Circuit. 6{ CCG Circuit Board.
7. Wiring Harness and Front Panel.
This Section will discuss test procedures for the
following components. Also see Part 8 of this
Manual, “TROUBLESHOOTING".
1. The AC Generator (Stator).
2. The Genistor.
3. Battery Charge Circuit.
4. CCG Circuit Board.

Stator Assembly

GENERAL:
For additional information on the Stator, refer to
the following:
1. “ Stator Assembly“ on Page 1.2-2.
2. Section 1.4, “INSULATION RESISTANCE“.
SYMPTOMS OF STATOR FAILURE:
A. If the engine starts but the Stepper Motor does
not move, and shutdown occurs after several sec
onds, look for the following:
1. Broken or shorted Power Supply winding
(Wires PS1 and PS2).
2. Broken or shorted Timing winding (Wires TIM1 and TIM2).
NOTE: If the Power Supply windina Is shorted to
ground, a burned area on the CCG circuit board
mircult board ground track) may be visible. If the
Timing winding Is shorted to ground, the circuit will
probably be damaged but bum-up may not be vls-
A short circuit between windings.
NOTE: The resistance of Stator windings Is very
low. Some meters will not read such alow resis
tance and will simply Indicate “continuity". Recom
mended Is a high quality, digital type meter capable
of reading very low resistances.
TESTING POWER PHASE WINDINGS: A. Refer to Figures 1 and 2. To test the Power
Phase windings for an open circuit condition, pro ceed as follows:
1. Disconnect the following wires:
a. Lead “AC1" (Gray) at the Genistor. b. Lead “AC2” (Yellow) at the Genistor. c. Lead “SL1" (Orange) at the Genistor. d. Lead “SL2" (Brown) at the Genistor. e. Lead No. 11 (Blue) at the Main Circuit Breaker
(CB1).
2. Make sure all of the disconnected leads are isolated from each other and are not touching the
frame during the test.
3. Set a VOM to its "Rxl" scale and zero the
meter.
4. Connect one VOM test lead to Lead No. 11
. Then, connect the remaining test lead as
K
s:
a. To Lead AC1 and note the resistance reading, b. To Lead AC2 and note the resistance reading, c. To lead SL1 and note the resistance reading, d. To lead SL2 and note the resistance reading.
NOMINAL RESISTANCE- POWER PHASE WINDINGS
Figure 1. Schematic- Stator Windings
POWER PHASE 1
POWER PHASE 2
0.30 to 0.42 ohm
B. If the engine shuts down but speed did NOT exceed 4500 rpm, look for the following:
1. One of the main windings (Power Phase 1 or
2) is open.
2. One of the main windings (Power Phase 1 or
2) is shorted to ground.
TESTING THE STATOR WITH A VOM:
A Volt-Ohm-Milliammeter (VOM) can be used to
test the Stator windings for tne following faults:
An open circuit condition. □ A "short-to-ground“ condition.
BATTERY CHARGE
nSGfiSIPr
PS1
c
POWER SUPPLY
TIMING
TIMI T1M2
Page 1.5-1
Section 1.5- COMPONENTS TESTING
Stator Assembly (Continued)
TESTING POWER PHASE WINDINGS
B. To test the Power Phase windings for a "short-to­ground* condition, proceed as follows:
1. Make sure all leads are Isolated from each other and
are not touching the frame.
2. Set a VOM to its *Rx10,000" or "RxlK* scale and zero the meter.
3. Connect one VOM test lead to the terminal end of Lead" AC1", the other test lead to a clean frame ground on the Stator.
a. The meter should read "infinity". b. Any reading other than "infinity" indicates a
"short-to-ground* condition.
TESTING POWER SUPPLY WINDINGS:
A. To test the Power Supply winding for an open circuit condition, proceed as follows:
1. Disconnect the 4-pin connector from "CONN4" of the CCG circuit board. See Rgure 3.
a. Stator lead "PS1* (Brown) connects to Pin 1 of
the connector.
b. Stator lead "PS2* (Yellow) connects to Pin 3 of
the connector.
2. Set a VOM to its *Rx1* scale and zero the meter.
3. Connect one VOM test lead to Pin 1 (Lead PS1­Brown), the othet test lead to Pin 3 (Lead PS2-Yellow). The meter should indicate the resistance of the Power Supply winding.
NGS (CONT’D): NOTE: Any reading other than "Infinity'' Indicates
the winding Is shorted to ground. If winding Is open or shorted, the Stator should be replaced.
TESTING THE TIMING WINDING:
A. To test the Stator Timing winding for an open circuit condition, proceed as follows:
1. Disconnect the 4-pin connector from "CONN4" of
the CCG circuit board. See Rgure 3.
a. Stator lead TIM1 (Orange) connects to Pin 2 of the 4-pin connector.
b. Stator lead TIM2 (Gray) connects to Pin 4 of the 4-pin connector.
2. Set a VOM to its *Rx1 * scale and zero the meter.
3. Connect one VOM test lead to Pin 2 (Lead TIM1­Orang^; connect the other test lead to Pin 4 (Lead
TIM2- Gray). The meter should Indicate the Stator Timing winding resistance.
B. To test the Timing winding for a "short-to-ground" condition, proceed as follows:
1. Set the VOM to its "Rx10,000* or "Rx1K" scale and
zero the meter.
2. Connect one VOM test lead to Pin 2 of the 4-pin
connector (Lead TIMI-Orange).
3. Connect the other test lead to a clean frame ground on the Stator. The meter should read "Infinity". Any reading other than "Infinity" Indicates the Timing winding is shorted to ground.
Figures. "CONN4“4-Pin Connector
NOMINAL RESISTANCE
STATOR TIMING WINDING
0.35-0.44 ohm
NOMINAL RESISTANCE
POWER SUPPLY WINDING
0.35-0.44 ohm
B. To test the Power Supply winding for a “short-to­ground" condition, proceed as follows:
1. Set the VOM to its “Rx10,000" or "RxlK" scale and
zero the meter.
2. Connect one VOM test lead to Pin 1 (Lead PS1­Brown). Connect the other test lead to a clean frame ground on the Stator. The meter should read "infinity".
Page 1.5-2
SHORT CIRCUIT BETWEEN WINDINGS:
To test for a short circuit between windings, proceed
as follows:
1. Set a VOM to its "Rx10,000" or "RxlK" scale and zero the meter.
2. Connect one meter test lead to Stator lead PS1 (Brown).
3. Connect the remaining test lead to Stator lead AC1 (Gray). The meter should read "Infinity*. Any reading other than "infinity" indicates a shorted condition and the Stator should be replaced.
Section 1.5- COMPONENTS TESTING
4. Connect one VOM test lead to Stator lead AC1, the other test lead to Stator lead 77. The VOM should read "Infinity“.
5. Connect one VOM test lead to Stator lead AC1, the other test lead to Stator lead TIM1. The meter should read “Infinity”.
6. Connect one test lead to Stator lead PS1, the other to Stator lead TIM1. “Infinity" should be Indicated.
7. Connect one test lead to Stator lead PS1, the other to Stator lead 77. The VOM should read "Infinity".
8. Connect one VOM test lead to Stator lead TIMI, the other test lead to Stator lead 77. “Infinity" should be Indicated.

Genistor

GENERAL:
The “Genistor" or "Triac Module" is the FRE
QUENCY CONVERTER for the generator. For addi tional Information on the Genistor, refer to "The
Genistor" on Pages 1.2-3 and 1.2-4.
SYMPTOMS OF GENISTOR FAILURE:
If the engine shuts down but speed did not ex
ceed 4500 rpm, the following problems may exist:
1. Loss of the "Gate" connection (G1 through G4) between the CCG circuit board and the Genistor.
2. Although the correct “Gate" signal Is received from the CCG board, one or more switches are not gating.
3. The Genistor is not gating properly, I.e., one or more switches are permanently turned on.
4. Open circuit or loss of connection(s) between Stator and Genistor (Leads AC1, aC2, SLI, SL2,
22).
5. Open circuit or loss of connection between Genistor and CCG circuit board (Leads AC1, AC2, SL1,SL2).
TESTING THE GENISTOR:
Disconnect ail wires from the Genistor before
attempting to test it.
RESISTANCE READING "COM" to G1 s 20-60 Ohms "COM" to G2 > 20-60 Ohms "COM" to G3 o 20-60 Ohms "COM" to G4 B 20-60 Ohms
3. Set the VOM to its “Rx1” scale and zero the meter. Then connect the VOM test leads across
the “COM" terminal and the center screw. The VOM should read “continuity”.
4. Now, connect the VOM test leads across the fol lowing terminals and screws:
a. Across AC1 screw to AC1 terminal should read “continuity”.
b. Across AC2 screw to AC2 terminal should read “continuity”.
c. Across SLI screw to SLI terminal should read “continuity”.
d. Across SL2 screw to SL2 terminal should read “continuity”.
5. Set the VOM to its “Rxl 0,000” or “RxlK” scale
and zero the meter. Then, connect the VOM test
leads across each of the screws. There should be
no continuity between any of the screws (“infini
ty”).
NOTE: The resistance reading between any two of the screws on the Genistor is in the neighborhood of about 1 megohm (about 1 million amps). If the Genistor failed any of the proceeding tests, it
should be replaced.
f^lgure 4. Genistor Test Points
CAUTIONI
DO NOT attempt to test the Genistor until ALL leads have been disconnected. The genistor MUST be completely disconnected from the cir
cuit If testing is accomplished with any leads connected, alftest results are Invalid.
See Figure 4. To test the Genistor, proceed as
follows:
1. Set a VOM to a resistance scale that will allow a range of about 20-60 ohms to be read. Zero the meter.
2. Connect one VOM test leads to the "COM" termi nal and the other test lead to Terminals G1, G2, G3 and G4 one at a time. Read the resistance as the meter is connected to G1, to G2, to G3, and to G4.

Testing the Battery Charge Circuit

GENERAL:
The Stator Is equipped with
dual battery charge windings.
These windings deliver an AC output to a Battery Charge Rec tifier (BCR) which rectifies it
changes It to direct current or
É
C). The direct current Is deliv
ered to the unit battery, to main tain the battery in a charged state while the unit Is running.
figure 5,
BATTERY CHARGE
WINDING
Page 1.5-3
BCR
Section 1.5- COMPONENTS TESTING
Testing the Battery Charge Circuit
(Continued)
SYMPTOMS OF CIRCUIT FAILURE:
It is difficult to determine if the battery charm
circuit is operating without testing for correct volt age. If you suspect the battwery charge circuit Is defective, the following symptoms will usually point to a cause of the problem. See Figure 6.
1. If no AC voltage can be measured across Stator connections at the Battery Charge Rectifier (BCR), an open circuit condition probably exists in Wire 66 (Brown), or Wire 77 (Brown).
2. If AC voltage is available to the Wire 66 and 77 terminals at the battery Charge Rectifier, but no voltage or a low voltage Is measured between the
BCR’s Wire 55 terminal and ground, the Battery
Charge Rectifier (BCR) Is defective.
TESTING THE BATTERY CHARGE CIRCUIT: Test the Battery Charge winding as follows:
1. Disconnect Wire 77 at the Battery Charge Recti
fier (BCR).
2. Disconnect Stator output Wire 66 at the Battery Charge Rectifier (BCR).
3. Disconnect Wire 55.
4. Set a VOM to its ”Rx1" scale and zero the meter.
5. Connect the VOM test leads across Wires 77 and 55, then across Wires 66 and 55. Note the resis tance reading in both cases. Replace Stator As sembly, If defective.
BATTERY CHARGE WINDING RESISTANCE
ACROSS WIRES 66 TO 55 s 0.037-0.042 Ohm ACROSS WIRES 77 TO 55 s 0.037-0.042 Ohm
6. Use a VOM to measure AC voltage at the Wires 66 and 77 terminals of the Battery Charge
Rectifier, with the unit running. If no AC voltage is
measured, an open circuit exists in the wire 66 or
77 circuit.
7. With engine running, use a VOM to check for DC
voltage between the Battery Charge Rectifiers Wire 55 and frame ground. If AC voltage was pre
sent in step 6, but DC voltage is NOT present in
this stem, the Battery Charge Rectifier (BCR) is
d6f6CtiVG.

Testing the CCG Circuit Board

GENERAL:
It is difficult if not impossible to test the CCG circuit board in the field. Generally, if the other components in the AC generator system have
tested good, you may assume that any problem is
In the CCG circuit board.
NOTE: Also refer to “CCG Circuit Board" on Pages
Ï.2-4, 1^-5, and 1^-6.
SYMPTOMS OF CIRCUIT BOARD FAILURE:
1. If the engine starts, but the Stepper Motor does not move, and engine shuts down after several
seconds, the CCG circuit board’s micro-controiler may not be operating.
2. A failure of the circuit board’s Stepper Motor drive can result in the following:
a. Engine starts, but Stepper Motor does not
move. The engine accelerates uncontrollably
and shuts down when engine speed exceeds 4500 rpm.
b. Engine starts, but Stepper Motor does not move. The following symptoms occur:
(1) Engine appears to operate too slowly. (2) Engine is not able to handle the load and unit
operates at low AC output voltage. (3) After several seconds under load, AC output
voltage is turned off (overload condition).
3. If the engine can be started, but shuts down after several seconds, a timing detection faiiure may have occured (Timing winding. Wires TIM1, T1M2).
4. if the engine speed and output voltage are erratic under constant load, but the AC output does not turn off intermittently, erratic timing detection may have occured (Timing winding. Wires TIM1, TIM2).
NOTE: Timing detection Involves the circuit board’s ability to detect "zero crosslrws" of the sine wave (see “Alternating Current", Pages 1.1-1 and 1.1-2). The CCG clrculfboard must detect both
zero VOLTAGE and zero CURRENT crossings If the
system Is to operate properly. This “zero crossing“ detector Is used to synchronize an Internal clock on the circuit board. The frequency of the Input
waveform la measured by the circuit board and checked against a "reference“ frequency. The board then calculates a frequency divisor. By counting “zero voltage crossings“, an Internal ret­erence output polarity Is generated. The Genistor switch with the maximum potential In the direction of the Internal reference Is gated.
Page 1.5-4
Section 1.5- COMPONENTS TESTING
TESTING THE CIRCUIT BOARD;
There Is no practical way of testing the CCG
circuit board In the field. Read "SYMPTOMS OF CIRCUIT BOARD FAILURE" carefully. Test the Sta tor, the Genistor, and the Battery Charge circuit as outlined In this Section. Also perform a resistance test of the Stepper Motor (see Part 7, "THE VARI ABLE SPEED SYSTEM") and observe Its operation
If possible.
Inspect wiring and wiring connections between
the CCG circuit board and the Genistor as follows (refer to appropriate wiring diagram):
1. Check wires G1 through G4 (and Wire 22) for proper connections at circuit board and at the
Genistor.
2. Use a VOM to check Wires G1 through G4 (and Wire 22) for continuity.
3. Check Wires AC1, AC2, SL1 and SL2 (between circuit board and Genistor) for proper connections.
4. Use a VOM to check Wires AC1, AC2, SL1, SL2 (between circuit board and Genistor) for condlnu-
Ity.
If all tests are completed and no problem Is found
on other components of the system, replace the
CCG circuit board and check unit operation.
Page 1.5-5
Section 1.5- COMPONENTS TESTING
Page 1.5-6
Section 1.6- CONTROL PANEL

Construction

The panel Is constructed of sheet metal and Includes a panel box, a panel back cover and a front control panel. The panel box Is retained to an enolne-generator divider plate by five MS screws. Removal of these screws will permit the panel to be removed from the divider plate and set out of the way with connecting wires still attached. This will allow access to components housed In the control panel.
Figurer 1. Exploded View of Control Panel

Components

A heat sink bracket Is attached to the engine-generator
divider plate, for attachment of a heat sink to which a CCG circuit board and Genistor are mounted. See Items 26,31,32 and 38 In the Exploded View of Control Panel. Other components are also shown In the Exploded View.
Many of tnese components are part of the "ENGINE ELECTRICAL SYSTEM" (Part 6 of this manual).
ITEM
1
2
3 4
5 6 7
8
9
10
11
12
13 8
14 15 16
17 18 20 21 22 23 24 25
QTY
6 1
1
2 5
8 1 1 1 1
2
1
2
2 M6 Hex Nut
1
2
4
1
2
1
1
1
1
M5 Pan Head Machine Screw
Engine Controller Circuit Board
DESCRIPTION
Back Panel Cover
Control Panel Box
No. 10-32 Pan Head Screw
M4 Pan Head Screw
M5 Screw Snap Bushing 90’ Connector
25 amp circuit breaker
M6 Lockwasher Ignition Module 38 M5 Lockwasher
M4 Hex Nut
Ignition Coll Assembly
Ignition Coll Spacer
No. 8 Flatwasher 44 1 Ground Wire
Front Control Panel 45 1
Snap Bushing 46
Start-Stop Switch
Fuel Primer Switch
15 amp Fuse
Fuse Holder
ITEM
26 1 27 1 28 9
29 2
31 1 32 1 CCG Printed Circuit Board 33 4 M3 Pan Head Screw 34 4 M3 Lockwasher 35
36 1 500 ohm Power Resistor
37 4 M6 Screw 39 4
40 2
41 1 Terminal Block 42 43 1 Genistor Harness
47 48 2 Wiring Harness Clamp
49 1 Panel Harness (Not Shown)
QTY
1 1 ohm Power Resistor
1 Heat Sink Bracket
1 12-pln Connector
1 Remote Panel Harness 1
DESCRIPTION
Heat Sink
Battery Charge Rectifier
M4 Lockwasher
No. 10-32 Hex Nut
Genistor
M4 Pan Head Screw
M5 Hex Nut
Customer Wiring Harness
Snap Bushing
Page 1.6-1
Section 1.6- CONTROL PANEL
Page 1.6-2
Section 1.7- SHEET METAL
See ‘Exploded View of Sheet Metal" on next page. A

General

DIVIDER PLATE (Item 1 )separate8 the AC generator com ponents from the engine. The engine Itself Is enclosed by a BASE HOUSING WRAPPER (ftem 4), a FRAME (Item
24), and a BELLY PAN (Item 23). These components are sealed by means of rubber SEALS (Items 3), to prevent the escape of gases.
NP-30/NP-40 Generator
CONTROL PANEL BOX
DIVIDER PLATE
The LOWER FAN attaches to the engine shaft and Is
enclosed In a LOWER FAN HOUSING (Item 19). Air Is
drawn Into the enclosed area around the engine and
forced out of the LOWER FAN HOUSING.
Removal of sheet metal will be necessary for many
repairs and for replacement of most parts.
ROCKER COVER
COVER
OIL FILTER buy il
AIR CLEANER
/
I ...r
OIL FILL TAG
ionoanjiiJ
Page 1.7-1
Section 1.7- SHEET METAL

Parts List for Exploded View of Sheet Metal

ITEM 1 1
2 3 4 5 26 6 7 8 9 5 10 12 1 13 14 1 3/8"-16 Capscrew 38 1 Snap Bushing 15 16 17 18 19 20 21 1 22 1
23
24 25
QTY
Engine-Generator Divider Plate 1 Engine Upper Wrapper 1 Rubber Seal
1
2 Customer Mounting Ralls 4 M8 Lockwasher 32 1 Starter Contactor Insulator Boot 4
7 M6 Lockwasher 35 4 1 1 3/8” Lockwasher 39
1 3/8” Hex NHut 40 1 Air Outlet Deflector 41 1 1 Exhaust Muffler 1 1 45 1 Grounding Strap
1 Belly Pan 49 1 Muffler Lower Insulation 1 1
DESCRIPTION ITEM QTY DESCRIPTION
Grounding Strap
1/4” Lockwasher
Seal Retainer
M8 Flatwasher
No. 8 Hex Nut
M6-1.00 Capscrew
Lockwasher
Muffler Heat Shield
Base Housing Wrapper
M5 Screw 30
M8-1.25 Capscrew M8-1.25 Capscrew
Spark Arrestor Exhaust Clamp
Lower Fan Housing
Carburetor Baffle SKlrt
Rocker Cover Cover
Spark Plug Side Skirt 48
Frame
Grounding Strap
26 1 27 1 Fuel Pump 28 2 Barbed 90* Fitting 29
31 33 1 Oil Filter Opening Seal
34 1 36 1 Fuel Line
37
42 44
47
50 1 Muffler Upper Insulation
3 1/4”-20 Hex Nut 3 1 Starter Contactor
2 Hose Clamp 7 Lockwasher
1 No. 8 Hex Nut 2
1 1
1 Muffler Hanger Bracket
Page 1.7-2
Loading...
+ 96 hidden pages