Generac Power Systems MB375 Features

MB375
BI-FUEL DIESEL
Standby Power Rating
375KW 60 Hz
FEATURES
INNOVATIVE DESIGN & PROTOTYPE TESTING are key components of GENERAC'S success in "IMPROVING POWER BY DESIGN." But it doesn't stop there. Total commitment to component testing, reliability testing, environmental testing, destruction and life testing, plus testing to applicable CSA, NEMA, EGSA, and other standards, allows you to choose GENERAC POWER SYSTEMS with the confidence that these systems will provide superior performance.
PARALLELING SYSTEM FEATURES
AUTO SYNCHRONIZATION
ISOCHRONOUS LOAD SHARING REVERSE POWER PROTECTION MAXIMUM POWER PROTECTION ELECTRICALLY OPERATED MECHANICAL HELD CONTACTORS UL2200 LISTED
POWERMANAGER® DIGITAL CONTROL PLATFORM. The PowerManager® Digital Control Platform (PM-DCP) is a powerful control system built around a 32 bit industrial microprocessor. Standard factory programming controls the entire engine generator system while allowing the PM-DCP, with its onboard PLC, to be customized to meet any application requirement. The system is available on single unit gas, diesel or bi-fuel installations as well as Modular Paralleling Systems (MPS) from 200 kW - 3000 kW.
277/480, 345/600 Volt
12.0DTA ENGINE
Turbocharged, Aftercooled
REMOTELY PROGRAMMABLE VIA GENLINK communications software which is provided with each system sold.
SOLID STATE DIGITAL VOLTAGE REGULATOR senses all 3 phases, electronically matches surge loads to the torque curve of the engine.
ECONOMICAL POWER. Microprocessor controlled bi-fuel diesel/ natural gas engine provides long, low cost, reliable life.
SINGLE SOURCE SERVICE RESPONSE from Generac's dealer network provides parts and service know-how for the entire unit, from the engine to the smallest electronic component. You are never on your own when you own a GENERAC POWER SYSTEM.
GENERAC TRANSFER SWITCHE S, SWITCHGEAR AND ACCESSORIES. Long life and reliability is synonymous with
GENERAC POWER SYSTEMS. One reason for this confidence is that the GENERAC product line includes its own transfer systems, accessories, switchgear and controls for total system compatibility.
WEATHER PROTECTIVE SOUND ATTENUATED ENCLOSURE
is available utilizing Generac's advance sound technology.
APPLICATION & ENGINEERING DATA
GENERATOR SPECIFICATIONS
TYPE ................................................................ Four-pole, revolving field
ROTOR INSULATION ................................................................. Class H
STATOR INSULATION ................................................................ Class H
ADDITIONAL INSULATION ....................................... Antifungal Coating
TOTAL HARMONIC DISTORTION ...................................................<5%
TELEPHONE INTERFERENCE FACTOR (TIF) ................................<50
BEARINGS ............................................................ Prelubed and Sealed
COUPLING ..................................................................Direct Connected
LOAD CAPACITY(Standby Rating) ................................................100%
TEMPERATURE RISE .................................................................125° C
WINDING PITCH ................................................................................2/3
ROTOR ................................................................ Dynamically Balanced
VOLTAGE REGULATOR
Regulation ...................................................Digitally Controlled ± 0.25%
Sensing ....................................................................... Single or 3 Phase
Paralleling Capability ......................................................................... Yes
CONTROL PANEL
Type ....................................... PowerManager Digital Control Platform
DISPLAY
AC Volts ............................................ Line to Line and Line to Neutral
AC Amps ................................................................................Per line
Frequency ........................................................................10-99 Hertz
Oil Pressure ................................................ Digital Touchscreen LCD
Coolant Temperature .................................. Digital Touchscreen LCD
Fuel Level ................................................... Digital Touchscreen LCD
DC Battery Voltage ..................................... Digital Touchscreen LCD
Hour Meter - Run Time Hours .................... Digital Touchscreen LCD
Engine Speed in RPM ................................ Digital Touchscreen LCD
Generator Power kW .................................. Digital Touchscreen LCD
Power Factor ............................................... Digital Touchscreen LCD
Turbo Pressure ........................................... Digital Touchscreen LCD
Gas Pressure.............................................. Digital Touchscreen LCD
Gas Flow (CFM) ......................................... Digital Touchscreen LCD
Air Temperature (Incoming) ........................ Digital Touchscreen LCD
Gas Temperature ........................................ Digital Touchscreen LCD
Charge Air Cooler Valve Position ................ Digital Touchscreen LCD
Not in Auto ................................................................................... LED
Common Alarm ...........................................................................LED
ALARMS
High/Low Generator Voltage ....................... Digital Touchscreen LCD
High/Low Battery Voltage ........................... Digital Touchscreen LCD
High/Low Frequency ................................... Digital Touchscreen LCD
Low Oil Pressure & Prealarm ..................... Digital Touchscreen LCD
High, Low, Critical Low Fuel Level .............. Digital Touchscreen LCD
Overcrank ................................................... Digital Touchscreen LCD
Sensor Failure ............................................ Digital Touchscreen LCD
COMMUNICATION
Serial Communication RS232 and RS485 GenLink Software for PowerManager® Digital Control Platform
ENGINE SPECIFICATIONS
MAKE ......................................................................Generac / Mitsubshi
MODEL ...................................................................................... 12.0DTA
CYLINDERS ............................................................................... 6 in-line
DISPLACEMENT .............................................. 11.945 Liter (729 cu. in.)
BORE .......................................................................................... 5.11 in.
STROKE ...................................................................................... 5.91 in.
COMPRESSION RATIO ................................................................16.5:1
INTAKE AIR ...................................................Turbocharged, Aftercooled
NUMBER OF MAIN BEARINGS ...........................................................7
CONNECTING RODS .....................................................6-Carbon Steel
CYLINDER HEAD ............(6) 1-Cylinder Cast Iron with Overhead Valve
PISTONS ................................................Heat Resistant Aluminum Alloy
CRANKSHAFT .................... Case Hardened, Die Forged, Carbon Steel
Rating definitions - Standby: Applicable for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. (All
ratings in accordance with BS5514, ISO3046 and DIN6271).
MB375
ENGINE SPECIFICATIONS Cont.
VALVE TRAIN
LIFTER TYPE .................................................................................. Solid
INTAKE VALVE MATERIAL .............. Stellite Faced Heat Resistant Steel
EXHAUST VALVE MATERIAL ......... Stellite Faced Heat Resistant Steel
HARDENED VALVE SEATS ................................................Replaceable
ENGINE GOVERNOR
ELECTRONIC ...................................................................... Standard
FREQUENCY REGULATION, NO-LOAD TO FULL LOAD .........0.5%
STEADY STATE REGULATION ...............................................+0.25%
LUBRICATION SYSTEM
TYPE OF OIL PUMP .......................................................................Gear
OIL FILTER ............................................. Bypass and Full flow, cartridge
CRANKCASE CAPACITY ................................... 31 Liters (8.2 U.S. gal.)
ENGINE FEATURES
ECONOMICAL POWER Microprocessor controlled bi- fuel diesel engine starts
on diesel fuel and provides power from an air/natural gas mixture ignited by diesel injection and continuously monitored by the on board control.
LONGER ENGINE LIFE Generac heavy duty bi-fuel diesels provide long and reliable operating life along with low emissions.
GENERAC GEAR DRIVE Generac's Gear Drive technology drives the engine at the most economical operating point. The engine runs at 2280 rpm, which is well below the maximum design speed. The Generac Gear Drive transmission is constructed with heavy duty helical gears and ball bearings for quiet operation and long life. It has been in the Generac product line for over 20 years and several thousand units are installed and in operation today.
EMISSIONS Capable of low particulate and NOx emission levels. Unit is registered with SCAQMD permitting program (CEP No. 414037)
HOW DOES A BI-FUEL ENGINE WORK?
The diesel engine is equipped with a metering system that feeds natural gas into the incoming air supply. The standard diesel injection pump is used and the injector sprays diesel fuel into the cylinder at the correct time. The diesel fuel ignites and thus ignites the natural gas charge. Total power is derived from a combination of natural gas and diesel as shown in the chart below. The ratio of natural gas to diesel fuel is a function of several factors, including load and intake air temperature. The system is programmed to avoid pre­ignition, but should it occur due to a transient event such as sudden loading or fuel variation, knock sensors will signal the controller to reduce the flow of natural gas and the diesel injectors will take over to maintain engine speed and required power level. The higher thermal efficiency of diesel engines and the lower cost of natural gas, along with low emission levels, combine to make the bi-fuel engine a very economical choice.
FUEL PRESSURE - NAT. GAS 2 psi MINIMUM FUEL CONSUMPTION*
NG ft3/hr. Diesel NG ft3/hr. Diesel kW @2 psi gal./hr. kw @ 2 psi gal.hr.
225 2355 1.8 325 3402 2.62 275 2880 2.22 375 3358 6.95
Fuel Pressure NG line 2 psi @ full load BTU Content (Min) 920 BTU/ft3 LHV
*Note: Percentages and consumption can vary depending on air temperature and heat content of fuel
MB375
OPERATING DATA
STANDBY
MB375
GENERATOR OUTPUT VOLTAGE/KW-60Hz kW Rated AMP
277/480V, 3-phase, 0.8 pf 375 564 600V, 3-phase, 0.8 pf 375 450
GENERATOR PARAMETERS Subtransient Reactance pu. 0.12
Transient Reactance pu. 0.13 Synchronous Reactance pu. 2.98
LOCKED ROTOR kVA % INSTANTANEOUS DIP 10% 400
20% 750
Note: Available kVA values are based on instantaneous voltage values and not sustained values. Thus a load that
30% 1210
requires 750 kVA will create a 20% instantaneous voltage dip
35% 1410
from the nominal voltage value.
COOLING
Coolant capacity US gal. 22 Coolant flow/min. 60 Hz - US gal. 70 Heat rejection to coolant BTU/hr. 1,265,000 Radiator air flow 60 Hz - cfm 34,000 Maximum external pressure drop after radiator "H2O 0.5 Maximum operating air temperature onto radiator °F 140 * Maximum operating ambient temperature °F 120 *
COMBUSTION AIR REQUIREMENTS
Flow at rated power 60 Hz - cfm
EXHAUST
Exhaust flow at rated output 60 Hz - cfm
Max recommended back pressure "Hg Exhaust temperature at rated output (pre-turbo) °F 1350 Exhaust outlet size 5" ANSI Flange
ENGINE
Rated RPM 60 Hz 2280 HP at rated kWe (gross) 60 Hz 555 Piston speed 60 Hz - ft./min. 2249 BMEP 60 Hz psi 264
1257
4237
1.5
SYSTEM DESCRIPTION
Multiple generators are paralleled to a common generator bus through a unit-mounted switching mechanism to provide the total power output. The control system consists of the PowerManager® Digital Control Platform (PM-DCP) along with a PowerManager® Parallel Controller (PM-PC) for each 375 kW genset. The PowerManager System Controller (PM­SC) is provided in a separate NEMA 1 wall mount enclosure. It interfaces with the generator controllers to provide start­stop commands based on utility power, proportional load sharing and provides safe paralleling of each unit to the common generator bus.
The PowerManager Digital Control System, including generator controllers, can be locally or remotely viewed and programmed via Generac GenLink® Communications software. PowerManager also offers upstream digital communications via RS485/Modbus to other supervisory control systems.
TYPICAL OPERATIONAL SEQUENCE
1. A transfer switch detects a utility failure and issues a start command. The command goes to the PM-SC which then issues a start command to the Generator Controller (PM-DC).
2. Each individual generator will start on it's own.
3. The first generator that attains rated frequency and voltage is connected to the common generator bus via the switching mechanism.
4. The second generator will synchronize and close into the bus via its switching mechanism.
5. When all gensets are paralleled to the bus, the PM-SC will signal the transfer switch or switches to transfer to the load. There is a maximum of 3 programmed steps available for connection of multiple transfer switches.
6. If an NFPA requirement for 10 second start exists, the first unit up will connect to the bus. This causes the controller in a separate emergency transfer switch to immediately transfer to the NFPA load.
7. If a single generator fails, load shed contacts are available to disconnect selected noncritical loads.
8. If load conditions are reduced (night time operation) one generator can be programmed off-line (optional).
9. When utility supply returns, the PM-SC will issue commands to transfer loads back to the utility. It then issues commands to the individual PM-PC to disconnect from the bus. Each PM-PC will operate its generator for the cool-down period and then issue a shutdown command.
POWER ADJUSTMENT FOR AMBIENT CONDITIONS
Temperature °C 25 30 40 50
-2.5% for every 10oF above - °F 77 86 104 122 Rating kW 375 375 375 324 Altitude
-2.5% for every 1000 m. above - m. 1066
-2.5% for every 1000 ft. above - ft. 3500
*Note: Values given are maximum temperatures to which power adjustment
factors can be applied. Consult your Generac representative if operating conditions exceed these maximums.
STANDARD ENGINE & SAFETY FEATURES
MB375
12 Liter 2300 RPM Diesel Engines
12 Lead 400 kW 60 Hz Generators
PM-PC Generator Controllers
High Coolant Temperature Automatic Shutdown w/Pre Alarms
Low Coolant Level Automatic Shutdown w/Pre Alarms
Low Oil Pressure Automatic Shutdown w/Pre Alarms
Overspeed Automatic Shutdown (Solid-state)
Crank Limiter (Solid-state Programmable)
Emergency Stop Button
Serial RS232 and RS485 Output
Isochronous Governors
1% Digital Voltage Regulator
Fuel Shut-Off Solenoid
Factory Installed Cool-Flow Radiator
2000 Watt Coolant Heater
Rubber-Booted Engine Electrical Connections
35 Amp DC Engine Driven Alternator
Air Cleaner (dry type)
Dual Oil Filters
Vibration Isolators
Oil and Antifreeze
Critical Mufflers
10 Amp Battery Charger per Engine
Stainless Steel Flex Exhaust Connections
Flex Fuel Lines
3 Sets of Owners Manuals
Mainline Circuit Breaker
Two Year Warranty
Critical Grade Muffler (2)
GenLink® Communications Software
POWERMANAGER® DIGITAL CONTROL PLATFORM
The PowerManager® Paralleling Controller (PM-DC) is a fully programmable, integrated digital generator control console, using a 32-bit industrial microprocessor to handle all the control, monitoring, input and output genset functions. The open architecture used allows customizing the control to meet any customer requirement, yet maintaining the simplicity of operating 'as is' with the factory default programming. (see Generac bulletin #0168840SBY)
OPTIONS
OPTIONAL FUEL ACCESSORIES ❍ UL Listed Base Tank
Base Tank Low Fuel Alarm Secondary Diesel Fuel Filters and Heaters
OPTIONAL ELECTRICAL ACCESSORIES Battery Warmer
Batteries
OPTIONAL ALTERNATOR ACCESSORIES ❍ Alternator Heater Alternator Tropicalization
ADDITIONAL OPTIONAL EQUIPMENT
❍ Automatic Transfer Switch 3 Light Remote Annunciator
ADDITIONAL OPTIONAL EQUIPMENT
21 Light Remote Annunciator Remote Relay Panel 2 and 5 Year Extended Warranties
POWERMANAGER SYSTEM CONTROLLER Controls Up To 3 Distinct Transfer Switches
Unlimited Number of Slave Switches 3 Programmable Load Permissive Relays NEMA 1 Wall Mount Enclosure Touch Screen Display Of All Parameters
Distributed by:
Design and specifications subject to change without notice. Dimensions shown are approximate. Contact your Generac dealer for certified drawings. DO NOT USE THESE DIMENSIONS FOR INSTALLATION PURPOSES.
mm [in]
Generac Power Systems, Inc. • S45 W29290 HWY. 59, Waukesha, WI 53189 • generac.com
©2008 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Bulletin 0169180SBY/Printed in U.S.A. 11.03, rev: 05.09