Generac Power Systems iX Series Owner's Manual

Page 1
iX Series Digital Inverter
000721
(000209a)
WARNING
This product is not intended to be used in a critical life support application. Failure to adhere to this warning could result in death or serious injury.
Portable Generator
Owner’s Manual
MODEL:________________________ SERIAL:________________________ DATE PURCHASED:______________
Register your Generac product at:
WWW.GENERAC.COM
SAVE THIS MANUAL FOR FUTURE REFERENCE
Page 2

Table of Contents

Section 1 Introduction and Safety 1
Introduction ..................................... 1
Safety Rules .................................... 1
Safety Symbols and Meanings ........ 1
Exhaust and Location Hazards ....... 2
Electrical Hazards ...........................2
Fire Hazards .................................... 3
Standards Index ..............................3
Section 2 General Information and
Setup .............................................. 4
Know Your Generator ..................... 5
Emissions Information ..................... 5
Add Engine Oil ................................7
Fuel ................................................. 7
Section 3 Operation ......................8
Operation and Use Questions ......... 8
Before Starting Engine ....................8
Prepare Generator for Use .............. 8
Know Generator Limits .................... 8
Transporting/Tipping of the Unit ...... 9
Using the FlexPower™ Switch ........ 9
Starting Pull Start Engines .............. 9
Low Oil Level Shutdown System ... 10 Using the 12 VDC Battery Charger 10
Section 4 Maintenance and
Troubleshooting ..........................11
Maintenance Recommendations ...11
Maintenance Schedule ..................11
Preventive Maintenance ...............11
Engine Maintenance ......................11
Inspect Muffler and Spark Arrester 12
Replace Fuel Filter ........................13
Storage ..........................................13
Troubleshooting .............................15
Notes .............................................16
California Proposition 65. Engine exhaust and some of its constituents are known to the state of California to cause cancer, birth defects, and other reproductive harm.
California Proposition 65. This product contains or emits chemicals known to the state of California to cause cancer, birth defects, and other reproductive harm.
WARNING
(000004)
WARNING
(000005)
Page 3

Section 1 Introduction and Safety

(000100a)
WARNING
Consult Manual. Read and understand manual completely before using product. Failure to completely understand manual and product could result in death or serious injury.
(000001)
DANGER
Indicates a hazardous situation which, if not avoided, will result in death or serious injury.
(000002)
WARNING
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
(000003)
CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
000657
DANGER
Using a generator indoors CAN KILL YOU IN MINUTES. Generator exhaust contains carbon monoxide. This is
a poison you cannot see or smell.
NEVER use inside a home or garage, EVEN IF doors and windows are open.
Only use OUTSIDE and far away from windows, doors, and vents.
(000103)
DANGER
Asphyxiation. Running engines produce carbon monoxide, a colorless, odorless, poisonous gas. Carbon monoxide, if not avoided, will result in death or serious injury.

Introduction

Thank you for purchasing a Generac Power Systems Inc. product. This unit has been designed to provide high-performance, effi­cient operation, and years of use when main­tained properly.
If any section of the manual is not understood, contact your nearest Independent Authorized Service Dealer (IASD), or contact Generac Customer Service at 1-888-GENERAC (1­888-436-3722), or www.generac.com with any questions or concerns. The owner is responsible for proper mainte­nance and safe use of the equipment. Before operating, servicing or storing this generator:
• Study all warnings in this manual and on the product carefully.
• Become familiar with this manual and the unit before use.
• Refer to the Assembly section of the man­ual for instructions on final assembly proce­dures. Follow the instructions completely.
Save these instructions for future reference. ALWAYS supply this manual to any individual that will use this machine.
THE INFORMATION CONTAINED HEREIN WAS BASED ON MACHINES IN PRODUC­TION AT THE TIME OF PUBLICATION. GEN­ERAC RESERVES THE RIGHT TO MODIFY THIS MANUAL AT ANY TIME.
NOTE: Notes contain additional information important to a procedure and will be found within the regular text of this manual.
These safety warnings cannot eliminate the hazards that they indicate. Common sense and strict compliance with the special instruc­tions while performing the action or service are essential to preventing accidents.

Safety Symbols and Meanings

Safety Rules

The manufacturer cannot anticipate every possible circumstance that might involve a hazard. The warnings in this manual, and on tags and decals affixed to the unit are, there­fore, not all inclusive. If using a procedure, work method or operating technique that the manufacturer does not specifically recom­mend, verify that it is safe for others. Also make sure the procedure, work method or operating technique utilized does not render the equipment unsafe.
Throughout this publication, and on tags and decals affixed to the generator, DANGER, WARNING, CAUTION and NOTE blocks are used to alert personnel to special instructions about a particular operation that may be haz­ardous if performed incorrectly or carelessly. Observe them carefully. Their definitions are as follows:
Owner’s Manual for Portable Generator 1
Electrocution. Water contact with a power source,
DANGER
if not avoided, will result in death or serious injury.
(000104)
Page 4
• For safety reasons, it is recommended that
(000116)
DANGER
Electrocution. Turn utility and emergency power supplies to OFF before connecting power source and load lines. Failure to do so will result in death or serious injury.
(000111)
WARNING
Moving Parts. Keep clothing, hair, and appendages away from moving parts. Failure to do so could result in death or serious injury.
(000146)
WARNING
Equipment and property damage. Do not alter construction of, installation, or block ventilation for generator. Failure to do so could result in unsafe operation or damage to the generator.
(000103)
DANGER
Asphyxiation. Running engines produce carbon monoxide, a colorless, odorless, poisonous gas. Carbon monoxide, if not avoided, will result in death or serious injury.
(000179a)
DANGER
The exhaust system must be properly maintained. Do not alter or modify the exhaust system as to render it unsafe or make it noncompliant with local codes and/or standards. Failure to do so will result in death or serious injury.
(000144)
DANGER
Electrocution. Contact with bare wires, terminals, and connections while generator is running will result in death or serious injury.
(000104)
DANGER
Electrocution. Water contact with a power source, if not avoided, will result in death or serious injury.
(000145)
DANGER
Electrocution. In the event of electrical accident, immediately shut power OFF. Use non-conductive implements to free victim from live conductor. Apply first aid and get medical help. Failure to do so will result in death or serious injury.
the maintenance of this equipment be per­formed by an IASD. Inspect the generator regularly, and contact the nearest IASD for parts needing repair or replacement.
• Operate generator only on level surfaces and where it will not be exposed to exces­sive moisture, dirt, dust or corrosive vapors.

Exhaust and Location Hazards

Equipment and property damage. Do not alter construction of, installation, or block ventilation for generator. Failure to do so could result in unsafe operation or damage to the generator.
WARNING
(000146)
Hot Surfaces. When operting machine, do not touch hot surfaces. Keep machine away from combustables during use. Hot surfaces could result in severe burns or fire.
(000108)
WARNING
Do not insert any object through the air cooling slots. Generator can start at any time and could result in
WARNING
death, serious injury, and unit damage.
• When working on this equipment, remain alert at all times.
• Never work on the equipment when physi­cally or mentally fatigued.
• Never use the generator or any of its parts as a step. Stepping on the unit can stress and break parts, and may result in danger­ous operating conditions from leaking exhaust gases, fuel leakage, oil leakage, etc.
(000142)
Asphyxiation. Always use a battery operated carbon monoxide alarm indoors and installed according to the manufacturer’s instructions. Failure to do so could result in death or serious injury.
• If you start to feel sick, dizzy, or weak after the generator has been running, move to fresh air IMMEDIATELY. Seek medical attention as you could have carbon monox­ide poisoning.
(000178a)

Electrical Hazards

• The National Electric Code (NEC) requires the frame and external electrically conduc­tive parts of the generator be properly con­nected to an approved earth ground. Local electrical codes may also require proper grounding of the generator. Consult with a local electrician for grounding requirements in the area.
• Use a ground fault circuit interrupter in any damp or highly conductive area (such as metal decking or steel work).
WARNING
000406
2 Owner’s Manual for Portable Generator
Page 5

Fire Hazards

(000130)
WARNING
Accidental Start-up. Disconnect the negative battery cable, then the positive battery cable when working on unit. Failure to do so could result in death or serious injury.
(000105)
DANGER
Explosion and Fire. Fuel and vapors are extremely flammable and explosive. Add fuel in a well ventilated area. Keep fire and spark away. Failure to do so will result in death or serious injury.
(000166)
DANGER
Do not overfill fuel tank. Fill to 1/2 in. of top of tank to allow for fuel expansion. Overfilling may cause fuel to spill onto engine causing fire or explosion, which will result in death or serious injury.
(000174)
DANGER
Risk of fire. Allow fuel spills to completely dry before starting engine. Failure to do so will result in death or serious injury.
(000142)
Do not insert any object through the air cooling slots. Generator can start at any time and could result in death, serious injury, and unit damage.
WARNING
• Do not operate the generator if connected electrical devices overheat, if electrical out­put is lost, if engine or generator sparks or if flames or smoke are observed while unit is running.
• Keep a fire extinguisher near the generator at all times.

Standards Index

1. National Fire Protection Association (NFPA) 70: The NATIONAL ELECTRIC CODE (NEC) available from www.nfpa.org
2. National Fire Protection Association (NFPA) 5000: BUILDING CONSTRUC­TION AND SAFETY CODE available from www.nfpa.org
3. International Building Code available from www.iccsafe.org
4. Agricultural Wiring Handbook available from www.rerc.org, Rural Electricity Resource Council P.O. Box 309 Wilming­ton, OH 45177-0309
5. ASAE EP-364.2 Installation and Mainte­nance of Farm Standby Electric Power available from www.asabe.org, American Society of Agricultural & Biological Engi­neers 2950 Niles Road, St. Joseph, MI 49085
6. C22.2 100-14 Electric motors and genera­tors for installation and use, in accordance with the Rules of the Canadian Electrical Code
This list is not all inclusive. Check with the Authority Having Jurisdiction (AHJ) for any local codes or standards which may be appli­cable to your jurisdiction.
Owner’s Manual for Portable Generator 3
Page 6

Section 2 General Information and Setup

000723
1
4
6
5
7
8
3
9
12
11
10
2
13
182019
17
16
14
15
000721
Figure 2-1. Features and Controls
TABLE 1. Generator Components
1 Carrying Handle 2 Spark Plug Cover 3 Primer Bulb 4 Fuel Tank Cap 5 Control Panel 6Air Intake Slats 7 Muffler 8 Choke 9 Left Side Service Cover 10 Vent Hoses 11 Fuel Shut Off 12 Recoil Starter 13 Low Oil Level LED (yellow) 14 Overload LED (red) 15 Ready LED (green) 16 12 VDC Plug 17 FlexPower™ Switch 18 12 VDC Circuit Breaker 19 Grounding Lug 20 120 VAC Receptacle
4 Owner’s Manual for Portable Generator
NOTE: Do not exceed the rated output of the generator.
Figure 2-2. Control Panel
Figure 2-3. Unit Identification Label
000724
000722
Page 7

Know Your Generator

(000100a)
WARNING
Consult Manual. Read and understand manual completely before using product. Failure to completely understand manual and product could result in death or serious injury.
• Ignition System –Spark Plug – Ignition Module
• Exhaust System – Exhaust Manifold – Muffler – Pulsed Air Valve
Replacement owner’s manuals are available at www.generac.com.
– Catalyst

Emissions Information

The Environmental Protection Agency (EPA) (and California Air Resource Board (CARB) for generators certified to CA standards) requires that this generator comply with exhaust and evaporative emission standards. Locate the emissions compliance decal on the engine to determine generator standards and warranty details. This generator is certified to operate on gasoline. The emission control system may include the following compo­nents:
• Air Induction System – Intake Manifold – Air Cleaner
• Fuel System – Carburetor – Fuel Tank –Fuel Cap – Fuel Lines – Evaporative Vent Lines – Carbon Canister
TABLE 2. Product Specifications
1600 Watt
Engine Type Single Cylinder, 4-Stroke Engine Size 99cc Starter Type Recoil
Fuel Capacity/Type
Oil Capacity 0.63 qt (0.6L) Run time at 25% Rated Load 5.7 Hours Spark Plug Type NGK BPR7HS Spark Plug Gap .030 in (0.762 mm) Dimensions L x W x H 22 x 12 x 18 in (55.8 x 30.4 x 45.7 cm) Weight Lb/kg 43.5/19.7 Maximum AC Output 1600 W Surge AC Output 1650 W AC Volts 120 VAC Rated AC Current 13.3 Amp Frequency 60 Hz THD 3.0% Insulation Class Class B Outlets 5-15R (2), 12 VDC (1) DC Volts 12 VDC Rated DC Current 5 Amp
0.69 gal (2.6L) Unleaded
Owner’s Manual for Portable Generator 5
Page 8
TABLE 2. Product Specifications
2000 Watt (49 State)
Engine Type Single Cylinder, 4-Stroke Engine Size 127cc Starter Type Recoil
Fuel Capacity/Type
Oil Capacity 0.63 qt (0.6L) Run time at 25% Rated Load 5.3 Hours Spark Plug Type NGK BPR6ES Spark Plug Gap .030 in (0.762 mm) Dimensions L x W x H 22 x 12 x 18 in (55.8 x 30.4 x 45.7 cm) Weight Lb/kg 49.6/22.5 Maximum AC Output 2000 W Surge AC Output 2200 W AC Volts 120 VAC Rated AC Current 16.7 Amp Frequency 60 Hz THD 3.0% Insulation Class Class B Outlets 5-20R (2), 12 VDC (1) DC Volts 12 VDC Rated DC Current 5 Amp
2000 Watt (50 State)
Engine Type Single Cylinder, 4-Stroke Engine Size 127cc Starter Type Recoil
Fuel Capacity/Type
Oil Capacity 0.63 qt (0.6L) Run time at 25% Rated Load 4.7 Hours Spark Plug Type NGK BPR6ES Spark Plug Gap .030 in (0.762 mm) Dimensions L x W x H 22 x 12 x 18 in (55.8 x 30.4 x 45.7 cm) Weight Lb/kg 49.6/22.5 Maximum AC Output 2000 W Surge AC Output 2200 W AC Volts 120 VAC Rated AC Current 16.7 Amp Frequency 60 Hz THD 3.0% Insulation Class Class B Outlets 5-20R (2), 12 VDC (1) DC Volts 12 VDC Rated DC Current 5 Amp
0.85 gal (3.2L) Unleaded
0.82 gal (3.1L) Unleaded
6 Owner’s Manual for Portable Generator
Page 9

Add Engine Oil

10W-30
SAE 30
Synthetic 5W-30
000729
000730
A
B
(000105)
DANGER
Explosion and Fire. Fuel and vapors are extremely flammable and explosive. Add fuel in a well ventilated area. Keep fire and spark away. Failure to do so will result in death or serious injury.
000728
A
B
CAUTION
Engine damage. Verify proper type and quantity of engine oil prior to starting engine. Failure to do so could result in engine damage.
Add recommended engine oil as shown in the following chart.
NOTE: Use petroleum based oil (supplied) for engine break-in before using synthetic oil.
.
1. Place generator on a level surface.
2. Remove the Left Side Service Cover.
3. Remove oil fill cap (A) located on bottom of engine crankcase. See Figure 2-4.
4. Add recommended engine oil. The full level is the base of the threads in the filler neck (B). DO NOT OVERFILL!
5. Replace oil fill cap and hand-tighten.
(000135)
DANGER
Do not overfill fuel tank. Fill to 1/2 in. of top of tank to allow for fuel expansion. Overfilling may cause fuel to spill onto engine causing fire or explosion, which will result in death or serious injury.
(000166)
Fuel requirements are as follows:
• Clean, fresh, unleaded gasoline.
• Minimum rating of 87 octane/87 AKI (91 RON).
• Up to 10% ethanol (gasohol) is acceptable (where available; non-ethanol-premium fuel is recommended).
• DO NOT use E85.
• DO NOT use a gas oil mix.
• DO NOT modify engine to run on alternate fuels. Stabilize fuel prior to storage.
1. Verify unit is OFF and cooled for a mini-
mum of two minutes prior to fueling.
2. Place unit on level ground in a well venti-
lated area.
3. Clean area around fuel cap and remove
cap slowly (A). See Figure 2-5.
4. Add recommended fuel to 2 inches below
top (B). Do not overfill. See Figure 2-5.
5. Install fuel cap.
Figure 2-5. Add Recommended Fuel
NOTE: Allow spilled fuel to evaporate before starting unit.
IMPORTANT NOTE: It is important to pre­vent gum deposits from forming in fuel system parts such as the carburetor, fuel hose or tank during storage. Alcohol­blended fuels (called gasohol, ethanol or methanol) can attract moisture, which leads to separation and formation of acids during storage. Acidic gas can damage the fuel system of an engine while in storage. To avoid engine problems, the fuel system
Figure 2-4. Add Engine Oil

Fuel

should be emptied before storage of 30 days or longer. See the Storage section. Never use engine or carburetor cleaner products in the fuel tank as permanent damage may occur.
Owner’s Manual for Portable Generator 7
Page 10

Section 3 Operation

(000179a)
DANGER
The exhaust system must be properly maintained. Do not alter or modify the exhaust system as to render it unsafe or make it noncompliant with local codes and/or standards. Failure to do so will result in death or serious injury.
(000118)
DANGER
Risk of fire. Do not use generator without spark arrestor installed. Failure to do so could result in death or serious injury.
(000178a)
Asphyxiation. Always use a battery operated carbon monoxide alarm indoors and installed according to the manufacturer’s instructions. Failure to do so could result in death or serious injury.
WARNING
(000110)
WARNING
Risk of Fire. Hot surfaces could ignite combustibles, resulting in fire. Fire could result in death or serious injury.
(000108)
WARNING
Hot Surfaces. When operating machine, do not touch hot surfaces. Keep machine away from combustibles during use. Hot surfaces could result in severe burns or fire.
(000136)
CAUTION
Equipment and property damage. Disconnect electrical loads prior to starting or stopping unit. Failure to do so could result in equipment and property damage.

Operation and Use Questions

Call Generac customer service at 1-888-GEN­ERAC (1-888-436-3722) with questions or concerns about equipment operation and maintenance.

Before Starting Engine

1. Verify engine oil level is correct.
2. Verify fuel level is correct.
3. Verify unit is secure on level ground, with proper clearance and is in a well ventilated area.

Prepare Generator for Use

Asphyxiation. Running engines produce carbon monoxide, a colorless, odorless, poisonous gas. Carbon monoxide, if not avoided, will result in death or serious injury.
DANGER
(000103)

Know Generator Limits

Overloading a generator can result in damage to the generator and connected electrical devices. Observe the following to prevent overload:
• Add up the total wattage of all electrical devices to be connected at one time. This total should NOT be greater than the gener­ator's wattage capacity.
• The rated wattage of lights can be taken from light bulbs. The rated wattage of tools, appliances, and motors can be found on a data label or decal affixed to the device.
• If the appliance, tool, or motor does not give wattage, multiply volts times ampere rating to determine watts (volts x amps = watts).
• Some electric motors, such as induction types, require about three times more watts of power for starting than for running. This surge of power lasts only a few seconds when starting such motors. Make sure to allow for high starting wattage when select­ing electrical devices to connect to the gen­erator:
1. Figure the watts needed to start the largest
motor.
2. Add to that figure the running watts of all
other connected loads. The Wattage Reference Guide is provided to assist in determining how many items the gen­erator can operate at one time.
NOTE: All figures are approximate. See data label on appliance for wattage requirements.
Table 3. Wattage Reference Guide
Device Running
*Air Conditioner (12,000 Btu) 1700 *Air Conditioner (24,000 Btu) 3800 *Air Conditioner (40,000 Btu) 6000 Battery Charger (20 Amp) 500 Belt Sander (3") 1000 Chain Saw 1200 Circular Saw (6-1/2") 800 to 1000 *Clothes Dryer (Electric) 5750 *Clothes Dryer (Gas) 700 *Clothes Washer 1150 Coffee Maker 1750 *Compressor (1 HP) 2000 *Compressor (3/4 HP) 1800 *Compressor (1/2 HP) 1400 Curling Iron 700 *Dehumidifier 650
8 Owner’s Manual for Portable Generator
Watts
Page 11
Disc Sander (9") 1200
(000183)
WARNING
Recoil Hazard. Recoil could retract unexpectedly. Kickback could result in death or serious injury.
(000136)
CAUTION
Equipment and property damage. Disconnect electrical loads prior to starting or stopping unit. Failure to do so could result in equipment and property damage.
000725
Edge Trimmer 500 Electric Blanket 400 Electric Nail Gun 1200 Electric Range (per element) 1500 Electric Skillet 1250 *Freezer 700 *Furnace Fan (3/5 HP) 875 *Garage Door Opener 500 to 750 Hair Dryer 1200 Hand Drill 250 to 1100 Hedge Trimmer 450 Impact Wrench 500 Iron 1200 *Jet Pump 800 Lawn Mower 1200 Light Bulb 100 Microwave Oven 700 to 1000 *Milk Cooler 1100 Oil Burner on Furnace 300 Oil Fired Space Heater (140,000
Btu) Oil Fired Space Heater (85,000 Btu) 225 Oil Fired Space Heater (30,000 Btu) 150 *Paint Sprayer, Airless (1/3 HP) 600 Paint Sprayer, Airless (hand-held) 150 Radio 50 to 200 *Refrigerator 700 Slow Cooker 200 *Submersible Pump (1-1/2 HP) 2800 *Submersible Pump (1 HP) 2000 *Submersible Pump (1/2 HP) 1500 *Sump Pump 800 to 1050 *Table Saw (10") 1750 to 2000 Television 200 to 500 Toaster 1000 to 1650 Weed Trimmer 500 * Allow 3 times the listed watts for starting these
devices.
400

Transporting/Tipping of the Unit

Do not operate, store or transport the unit at an angle greater than 15 degrees.

Using the FlexPower™ Switch

When the accessories connected to the gen­erator are going to be used intermittently (such as a hand drill), the FlexPower™ switch can be pushed to the ON (I) position. This will lower generator engine speed when loads are not being applied, saving fuel, reducing engine wear and extending runtime.

Starting Pull Start Engines

1. Unplug all electrical loads from the unit's
receptacles before starting engine.
2. Place generator on a level surface.
3. Turn the FlexPower Switch OFF (O).
4. Turn fuel valve to the ON. See Figure 3-6.
Figure 3-6.Fuel Valve ON
5. Press primer bulb (up to six (6) times). See
Figure 3-7.
000726
Figure 3-7.Primer Bulb
6. Slide engine choke to Full Choke position
(right). See Figure 3-8.
Owner’s Manual for Portable Generator 9
Page 12
Figure 3-8.Choke Position
000727
(000136)
CAUTION
Equipment and property damage. Disconnect electrical loads prior to starting or stopping unit. Failure to do so could result in equipment and property damage.
000725
7. Firmly grasp recoil handle and pull slowly until increased resistance is felt. Pull rap­idly up and away.
8. When engine starts, move choke knob to 1/2-choke position until engine runs smoothly, then to OFF position. If engine falters, move choke back to 1/2-choke position until engine runs smoothly, then to OFF position.
NOTE: If engine fires, but does not continue to run, move choke lever to Full Choke and repeat starting instructions.
IMPORTANT NOTE: Do not overload the generator. Also, do not overload individual panel receptacles. If the Overload LED (red) is lit attached devices stop operating, stop engine. Reduce loads before restart­ing engine. Read “Know Generator Limits” carefully.
Generator Shut Down
1. Shut off all loads and unplug electrical loads from generator panel receptacles.
2. Let engine run at no-load for several min­utes to stabilize internal temperatures of engine and generator.
3. Turn fuel valve to the OFF. See Figure 3-9.
.

Low Oil Level Shutdown System

The engine is equipped with a low oil level sensor that shuts down the engine automati­cally when the oil level drops below a speci­fied level. The engine will not run until the oil has been filled to the proper level. If the engine shuts down and there is sufficient fuel, check engine oil level.
Using the 12 VDC Battery
.
Charger
WARNING
Risk of burn. Battery contains electrolyte solution which can cause burns and blindness. If electrolyte contacts skin or eyes, flush with water and seek immediate medical attention.
The 12 VDC receptacle may be used to recharge 12 VDC automotive batteries only. The DC charging output is not regulated. The circuit protector does not prevent over­charging a battery.
1. Connect the charging cable to the genera­tor first, then the battery. ALWAYS connect the red lead to positive (+), and the black to negative (-).
2. Keep the FlexPower™ switch in the OFF (O) position.
3. Start generator and use as normal. Charging time will vary with battery size and condition. Check voltage at battery terminals once the charging cable has been unplugged, or generator has been shut down.
NOTE: This receptacle cannot recharge 6 Volt batteries and cannot be used to crank an engine having a discharged battery.
WARNING
WARNING
CAUTION
Do not make battery connections in reverse. Doing so will result in equipment damage.
(000137a)
(000163)
(000138a)
(000167)
Figure 3-9.Fuel Valve OFF
10 Owner’s Manual for Portable Generator
Page 13

Section 4 Maintenance and Troubleshooting

10W-30
SAE 30
Synthetic 5W-30
000729

Maintenance Recommendations

Regular maintenance will improve perfor­mance and extend generator life. See a quali­fied dealer for service. Generator warranty does not cover items sub­jected to operator abuse or negligence. To receive full warranty value, operator must maintain generator as instructed in this man­ual, including proper storage as detailed in Winter Storage and Long Term Storage.
NOTE: Call 1-888-GENERAC (1-888-436-
3722) with questions about component replacement.

Maintenance Schedule

Follow maintenance schedule intervals, whichever occurs first according to use.
NOTE: Adverse conditions will require more frequent service.
NOTE: All required service and adjustments should be each season as detailed in the fol­lowing chart.
At Each Use
Check engine oil level
Every 100 Hours or Every Season* Change oil ǂ Clean air filter**
Every 6 Months Check spark plug Check muffler
Every Season Replace spark plug Replace fuel filter Inspect/clean spark arrestor ǂ Change oil after first 5 hours of operation,
then every season.
* Change oil and oil filter every month when
operating under heavy load or in high tem­peratures.
** Clean more often under dirty or dusty oper-
ating conditions. Replace air filter parts if they cannot be adequately cleaned.
WARNING
Do not insert any object through the air cooling slots. Generator can start at any time and could result in death, serious injury, and unit damage.
• Use a damp cloth to wipe exterior surfaces clean.
• Use a soft bristle brush to loosen caked on dirt, oil, etc.
• Use a vacuum to pick up loose dirt and debris.
• Low pressure air (not to exceed 25 psi) may be used to blow away dirt. Inspect cooling air slots and openings on generator. These openings must be kept clean and unobstructed.
NOTE: DO NOT use a garden hose to clean generator. Water can enter engine fuel system and cause problems. If water enters generator through cooling air slots, some water will be retained in voids and crevices of rotor and sta­tor winding insulation. Water and dirt buildup on generator internal windings will decrease insulation resistance of windings.
(000142)

Engine Maintenance

WARNING
Accidental start-up. Disconnect spark plug wires when working on unit. Failure to do so could result in death or serious injury.
Engine Oil Recommendations
Add recommended engine oil as shown in the following chart.
NOTE: Use petroleum based oil (supplied) for engine break-in before using synthetic oil.
.
(000141)

Preventive Maintenance

Dirt or debris can cause improper operation and equipment damage. Clean generator daily or before each use. Keep area around and behind muffler free from combustible debris. Inspect all cooling air openings on generator.
Owner’s Manual for Portable Generator 11
Page 14
Change Engine Oil
000730
A
B
B
C
A
D
000733
A
B
WARNING
Accidental start-up. Disconnect spark plug wires when working on unit. Failure to do so could result in death or serious injury.
When using generator under extreme, dirty, dusty conditions, or in extremely hot weather, change oil more frequently.
NOTE: Don’t pollute. Conserve resources. Return used oil to collection centers.
Change oil while engine is still warm from run­ning, as follows:
1. Place generator on a level surface.
2. Remove the Left Side Service Cover.
3. Remove oil fill cap (A) located on bottom of engine crankcase. See Figure 4-1.
4. Tip unit and drain oil completely into a suit­able container.
5. Add recommended engine oil. The full level is the base of the threads in the filler neck (B). DO NOT OVERFILL!
6. Install oil fill cap, and finger tighten.
7. Wipe up any spilled oil.
8. Properly dispose of oil in accordance with all applicable regulations.
(000141)
4. Clean air filter cover before installing. NOTE: To order a new air filter, contact the
nearest IASD at 1-888-GENERAC (1-888­436-3722).
000731
Figure 4-2. Air Filter Assembly
Service Spark Plug
To service spark plug:
1. Remove spark plug cover (A). See Figure
4-3.
2. Pull spark plug lead from spark plug (B).
3. Use a socket wrench and remove spark plug.
4. Install new spark plug into cylinder head and tighten to 15 ft/lb (20.3 Nm).
5. Replace the spark plug lead, making sure it is fully seated.
6. Replace spark plug cover.
Figure 4-3. Spark Plug
Inspect Muffler and Spark
Figure 4-1. Add Engine Oil
Air Filter
Engine will not run properly and may be dam­aged if run with a dirty air filter. Service air fil­ter more frequently in dirty or dusty conditions. To service air filter:
1. See Figure 4-2. Remove the Left Side Ser­vice Cover screw (A) and remove cover (B).
2. Remove filter housing cover (C).
3. Remove air filter (D) and wash in soapy water. Squeeze filter dry in clean cloth (DO NOT TWIST).
12 Owner’s Manual for Portable Generator
Arrester
NOTE: It is a violation of California Public
Resource Code, Section 4442, to use or oper­ate the engine on any forest-covered, brush­covered, or grass-covered land unless the exhaust system is equipped with a spark arrester, as defined in Section 4442, main­tained in effective working order. Other states or federal jurisdictions may have similar laws.
Contact original equipment manufacturer, retailer, or dealer to obtain a spark arrester designed for exhaust system installed on this engine.
NOTE: Use ONLY original equipment replace­ment parts.
Page 15
Inspect muffler for cracks, corrosion, or other
(000108)
WARNING
Hot Surfaces. When operating machine, do not touch hot surfaces. Keep machine away from combustibles during use. Hot surfaces could result in severe burns or fire.
000735
A
B
C
D
(000168)
DANGER
Explosion and Fire. Fuel and vapors are extremely flammable and explosive. Keep fire and spark away. Failure to do so will result in death or serious injury.
000732
A
damage. Remove spark arrester, if equipped, inspect for damage or carbon blockage. Replace parts as required.
Inspect Spark Arrester Screen (50 State)
Figure 4-5. Replace Fuel Filter
1. Remove clamp (A) and screen retainer (B). See Figure 4-4.
2. Slide spark arrestor screens (C) out from muffler outlet (D).
3. Inspect screens and replace if torn, perfo­rated or otherwise damaged. Do NOT use a defective screen. If screens are not dam­aged, clean with commercial solvent.
4. Replace screens (C) and retainer (B) and secure with clamp (A).
Figure 4-4. Spark Arrestor Screen

Replace Fuel Filter

Locate fuel filter just below engine intake housing. See Figure 4-5. Make sure fuel shut­off is OFF (O).
1. Remove the pinch clamps from fuel filter (A) and pull hoses free.
2. Replace used filter.
3. Push fuel hoses onto barbed filter fittings until they seat completely.
4. Replace clamps making sure they are seated on the fittings.

Storage

General
Explosion and Fire. Fuel and vapors are extremely flammable and explosive. Store fuel in a well ventilated area. Keep fire and spark away. Failure to do so will result in death or serious injury.
Risk of Fire. Verify machine has properly cooled before installing cover and storing machine. Hot surfaces could result in fire.
It is recommended to start and run the genera­tor for 30 minutes, every 30 days. If this is not possible, refer to the following list to prepare unit for storage.
• DO NOT place a storage cover on a hot generator. Allow unit to cool to room tem­perature before storage.
• DO NOT store fuel from one season to another unless properly treated.
• Replace fuel container if rust is present. Rust in fuel will cause fuel system prob­lems.
• Cover unit with a suitable protective, mois­ture resistant cover.
• Store unit in a clean and dry area.
• Always store generator and fuel away from heat and ignition sources.
DANGER
(000143)
WARNING
(000109)
Owner’s Manual for Portable Generator 13
Page 16
Prepare Fuel System for Storage
A
(000181)
WARNING
Vision Loss. Eye protection is required to avoid spray from spark plug hole when cranking engine. Failure to do so could result in vision loss.
Fuel stored over 30 days can go bad and damage fuel system components. Keep fuel fresh, use fuel stabilizer.
If fuel stabilizer is added to fuel system, pre­pare and run engine for long term storage. Run engine for 10-15 minutes to circulate sta­bilizer throughout fuel system. Adequately prepared fuel can be stored up to 24 months.
NOTE: If fuel has not been treated with fuel stabilizer, it must be drained into an approved container. See Figure 4-6. Run engine until it stops from lack of fuel. Use of fuel stabilizer in fuel storage container is recommended to keep fuel fresh.
000734
Figure 4-6. Carburetor Drain Valve
1. Change engine oil.
2. Remove spark plug.
3. Pour tablespoon (5-10cc) of clean engine oil or spray a suitable fogging agent into cylinder.
4. Pull starter recoil several times to distrib­ute oil in cylinder.
5. Install spark plug.
6. Pull recoil slowly until resistance is felt. This will close valves so moisture cannot enter engine cylinder. Gently release recoil.
Change Oil
Change engine oil before storage. See
Change Engine Oil.
14 Owner’s Manual for Portable Generator
Page 17

Troubleshooting

PROBLEM CAUSE CORRECTION
Engine won't start. 1. No fuel in tank.
2. Fuel valve turned off.
3. Defective spark plug.
4. Plugged fuel filter.
5. Defective or stuck engine stop switch.
1. Add fuel to tank.
2. Turn fuel valve on.
3. Replace spark plug.
4. Replace fuel filter.
5. Replace engine start switch.
Engine starts, then shuts down.
Engine starts, then runs rough.*
No AC output. 1. Generator overloaded (Over-
1. Low fuel level.
2. Fuel tank vent closed.
3. Incorrect engine oil level.
4. Contaminated fuel.
5. Defective low oil level switch.
6. Defective ignition coil.
1. Choke is stuck or left on.
2. Dirty or clogged air filter.
3. Defective or dirty spark plug.
4. Dirty fuel filter.
5. Defective EcoMode switch.
load LED is on and Ready LED is flashing. See
Figure 2-
2).
2. AC voltage is low (Overload LED is on and Ready LED is flashing. See
3. Inverter module overheated (Overload LED is on and Ready LED is flashing. See
Figure 2-2).
Figure 2-2).
4. Short circuit in electrical device (Overload LED is on and Ready LED is flashing.
Figure 2-2).
See
5. Defective inverter assembly.
No DC output. ** 1. DC circuit breaker is open.
2. Defective DC circuit breaker.
3. Defective rectifier.
1. Add fuel to tank.
2. Open fuel tank vent.
3. Check engine oil level. Add or drain as needed.
4. Replace fuel filter.
5. Replace low oil level switch.
6. Replace ignition coil.
1. Turn choke off.
2. Clean or replace the air filter element.
3. Replace spark plug.
4. Replace fuel and fuel filter.
5. Replace EcoMode switch.
1. Shut down generator to reset module. Reduce loads and restart generator.
2. Verify the choke is OFF.
3. Verify service door is ON. Let cool for 15 minutes and start generator.
4. Check condition of extension cords and items being pow­ered.
5. Replace inverter assembly.
1. Reset DC circuit breaker.
2. Replace DC circuit breaker.
3. Replace rectifier.
Fuel leaks from drain hoses.
* Engine speed increases and decreases — This is normal as the generator starts up and as loads
vary.
** Verify EcoMode Switch is OFF.
Owner’s Manual for Portable Generator 15
1. Fuel system over primed (flooded).
2. Carburetor drain in bowl is not closed.
1. Let generator sit 15 minutes before starting.
2. Turn valve clockwise to close.
Page 18

Notes

16 Owner’s Manual for Portable Generator
Page 19
Owner’s Manual for Portable Generator 17
Page 20

Part No. 0J9694 Rev. G 08/20/15 Printed in USA ©2015 Generac Power Systems, Inc. All rights reserved Specifications are subject to change without notice. No reproduction allowed in any form without prior written consent from Generac Power Systems, Inc.

Generac Power Systems, Inc.
S45 W29290 Hwy. 59
1-888-GENERAC (1-888-436-3722)
Waukesha, WI 53189
generac.com
Loading...