This product is not intended to be used in
a critical life support application. Failure to
adhere to this warning could result in
death or serious injury.
Portable Generator
Owner’s Manual
MODEL:________________________
SERIAL:________________________
DATE PURCHASED:______________
California Proposition 65. Engine exhaust and some
of its constituents are known to the state of California
to cause cancer, birth defects, and other reproductive
harm.
California Proposition 65. This product contains or
emits chemicals known to the state of California to
cause cancer, birth defects, and other reproductive
harm.
WARNING
(000004)
WARNING
(000005)
Page 3
Section 1 Introduction and Safety
(000100a)
WARNING
Consult Manual. Read and understand manual
completely before using product. Failure to
completely understand manual and product
could result in death or serious injury.
(000001)
DANGER
Indicates a hazardous situation which, if not avoided,
will result in death or serious injury.
(000002)
WARNING
Indicates a hazardous situation which, if not avoided,
could result in death or serious injury.
(000003)
CAUTION
Indicates a hazardous situation which, if not avoided,
could result in minor or moderate injury.
000657
DANGER
Using a generator indoors CAN KILL YOU IN MINUTES.
Generator exhaust contains carbon monoxide. This is
a poison you cannot see or smell.
NEVER use inside a home
or garage, EVEN IF doors
and windows are open.
Only use OUTSIDE and
far away from windows,
doors, and vents.
(000103)
DANGER
Asphyxiation. Running engines produce carbon
monoxide, a colorless, odorless, poisonous gas.
Carbon monoxide, if not avoided,
will result in death or serious injury.
Introduction
Thank you for purchasing a Generac Power
Systems Inc. product. This unit has been
designed to provide high-performance, efficient operation, and years of use when maintained properly.
If any section of the manual is not understood,
contact your nearest Independent Authorized
Service Dealer (IASD), or contact Generac
Customer Service at 1-888-GENERAC (1888-436-3722), or www.generac.com with any
questions or concerns.
The owner is responsible for proper maintenance and safe use of the equipment. Before
operating, servicing or storing this generator:
• Study all warnings in this manual and on
the product carefully.
• Become familiar with this manual and the
unit before use.
• Refer to the Assembly section of the manual for instructions on final assembly procedures. Follow the instructions completely.
Save these instructions for future reference.
ALWAYS supply this manual to any individual
that will use this machine.
THE INFORMATION CONTAINED HEREIN
WAS BASED ON MACHINES IN PRODUCTION AT THE TIME OF PUBLICATION. GENERAC RESERVES THE RIGHT TO MODIFY
THIS MANUAL AT ANY TIME.
NOTE: Notes contain additional information
important to a procedure and will be found
within the regular text of this manual.
These safety warnings cannot eliminate the
hazards that they indicate. Common sense
and strict compliance with the special instructions while performing the action or service
are essential to preventing accidents.
Safety Symbols and Meanings
Safety Rules
The manufacturer cannot anticipate every
possible circumstance that might involve a
hazard. The warnings in this manual, and on
tags and decals affixed to the unit are, therefore, not all inclusive. If using a procedure,
work method or operating technique that the
manufacturer does not specifically recommend, verify that it is safe for others. Also
make sure the procedure, work method or
operating technique utilized does not render
the equipment unsafe.
Throughout this publication, and on tags and
decals affixed to the generator, DANGER,
WARNING, CAUTION and NOTE blocks are
used to alert personnel to special instructions
about a particular operation that may be hazardous if performed incorrectly or carelessly.
Observe them carefully. Their definitions are
as follows:
Owner’s Manual for Portable Generator1
Electrocution. Water contact with a power source,
DANGER
if not avoided, will result in death or serious injury.
(000104)
Page 4
• For safety reasons, it is recommended that
(000116)
DANGER
Electrocution. Turn utility and emergency
power supplies to OFF before connecting power
source and load lines. Failure to do so will result
in death or serious injury.
(000111)
WARNING
Moving Parts. Keep clothing, hair, and appendages
away from moving parts. Failure to do so could
result in death or serious injury.
(000146)
WARNING
Equipment and property damage. Do not alter
construction of, installation, or block ventilation for
generator. Failure to do so could result in unsafe
operation or damage to the generator.
(000103)
DANGER
Asphyxiation. Running engines produce carbon
monoxide, a colorless, odorless, poisonous gas.
Carbon monoxide, if not avoided,
will result in death or serious injury.
(000179a)
DANGER
The exhaust system must be properly maintained. Do
not alter or modify the exhaust system as to render it
unsafe or make it noncompliant with local codes and/or
standards. Failure to do so will result in death
or serious injury.
(000144)
DANGER
Electrocution. Contact with bare wires,
terminals, and connections while generator
is running will result in death or serious injury.
(000104)
DANGER
Electrocution. Water contact with a power source,
if not avoided, will result in death or serious injury.
(000145)
DANGER
Electrocution. In the event of electrical accident,
immediately shut power OFF. Use non-conductive
implements to free victim from live conductor. Apply
first aid and get medical help. Failure to do so will
result in death or serious injury.
the maintenance of this equipment be performed by an IASD. Inspect the generator
regularly, and contact the nearest IASD for
parts needing repair or replacement.
• Operate generator only on level surfaces
and where it will not be exposed to excessive moisture, dirt, dust or corrosive vapors.
Exhaust and Location Hazards
Equipment and property damage. Do not alter
construction of, installation, or block ventilation for
generator. Failure to do so could result in unsafe
operation or damage to the generator.
WARNING
(000146)
Hot Surfaces. When operting machine, do not
touch hot surfaces. Keep machine away from
combustables during use. Hot surfaces
could result in severe burns or fire.
(000108)
WARNING
Do not insert any object through the air cooling slots.
Generator can start at any time and could result in
WARNING
death, serious injury, and unit damage.
• When working on this equipment, remain
alert at all times.
• Never work on the equipment when physically or mentally fatigued.
• Never use the generator or any of its parts
as a step. Stepping on the unit can stress
and break parts, and may result in dangerous operating conditions from leaking
exhaust gases, fuel leakage, oil leakage,
etc.
(000142)
Asphyxiation. Always use a battery operated carbon
monoxide alarm indoors and installed according to
the manufacturer’s instructions. Failure to do so
could result in death or serious injury.
• If you start to feel sick, dizzy, or weak after
the generator has been running, move to
fresh air IMMEDIATELY. Seek medical
attention as you could have carbon monoxide poisoning.
(000178a)
Electrical Hazards
• The National Electric Code (NEC) requires
the frame and external electrically conductive parts of the generator be properly connected to an approved earth ground. Local
electrical codes may also require proper
grounding of the generator. Consult with a
local electrician for grounding requirements
in the area.
• Use a ground fault circuit interrupter in any
damp or highly conductive area (such as
metal decking or steel work).
WARNING
000406
2Owner’s Manual for Portable Generator
Page 5
Fire Hazards
(000130)
WARNING
Accidental Start-up. Disconnect the negative battery
cable, then the positive battery cable when working
on unit. Failure to do so could result in death
or serious injury.
(000105)
DANGER
Explosion and Fire. Fuel and vapors are extremely
flammable and explosive. Add fuel in a well
ventilated area. Keep fire and spark away. Failure to
do so will result in death or serious injury.
(000166)
DANGER
Do not overfill fuel tank. Fill to 1/2 in. of top of tank to
allow for fuel expansion. Overfilling may cause fuel to
spill onto engine causing fire or explosion, which will
result in death or serious injury.
(000174)
DANGER
Risk of fire. Allow fuel spills to completely dry
before starting engine. Failure to do so will
result in death or serious injury.
(000142)
Do not insert any object through the air cooling slots.
Generator can start at any time and could result in
death, serious injury, and unit damage.
WARNING
• Do not operate the generator if connected
electrical devices overheat, if electrical output is lost, if engine or generator sparks or if
flames or smoke are observed while unit is
running.
• Keep a fire extinguisher near the generator
at all times.
Standards Index
1. National Fire Protection Association
(NFPA) 70: The NATIONAL ELECTRIC
CODE (NEC) available from www.nfpa.org
2. National Fire Protection Association
(NFPA) 5000: BUILDING CONSTRUCTION AND SAFETY CODE available from
www.nfpa.org
3. International Building Code available from
www.iccsafe.org
4. Agricultural Wiring Handbook available
from www.rerc.org, Rural Electricity
Resource Council P.O. Box 309 Wilmington, OH 45177-0309
5. ASAE EP-364.2 Installation and Maintenance of Farm Standby Electric Power
available from www.asabe.org, American
Society of Agricultural & Biological Engineers 2950 Niles Road, St. Joseph, MI
49085
6. C22.2 100-14 Electric motors and generators for installation and use, in accordance
with the Rules of the Canadian Electrical
Code
This list is not all inclusive. Check with the
Authority Having Jurisdiction (AHJ) for any
local codes or standards which may be applicable to your jurisdiction.
Owner’s Manual for Portable Generator3
Page 6
Section 2 General Information and Setup
000723
1
4
6
5
7
8
3
9
12
11
10
2
13
182019
17
16
14
15
000721
Figure 2-1. Features and Controls
TABLE 1. Generator Components
1Carrying Handle
2Spark Plug Cover
3Primer Bulb
4Fuel Tank Cap
5Control Panel
6Air Intake Slats
7Muffler
8Choke
9Left Side Service Cover
10Vent Hoses
11Fuel Shut Off
12Recoil Starter
13Low Oil Level LED (yellow)
14Overload LED (red)
15Ready LED (green)
1612 VDC Plug
17FlexPower™ Switch
1812 VDC Circuit Breaker
19Grounding Lug
20120 VAC Receptacle
4Owner’s Manual for Portable Generator
NOTE: Do not exceed the rated output of the
generator.
Figure 2-2. Control Panel
Figure 2-3. Unit Identification Label
000724
000722
Page 7
Know Your Generator
(000100a)
WARNING
Consult Manual. Read and understand manual
completely before using product. Failure to
completely understand manual and product
could result in death or serious injury.
• Ignition System
–Spark Plug
– Ignition Module
• Exhaust System
– Exhaust Manifold
– Muffler
– Pulsed Air Valve
Replacement owner’s manuals are available
at www.generac.com.
– Catalyst
Emissions Information
The Environmental Protection Agency (EPA)
(and California Air Resource Board (CARB)
for generators certified to CA standards)
requires that this generator comply with
exhaust and evaporative emission standards.
Locate the emissions compliance decal on the
engine to determine generator standards and
warranty details. This generator is certified to
operate on gasoline. The emission control
system may include the following components:
• Air Induction System
– Intake Manifold
– Air Cleaner
• Fuel System
– Carburetor
– Fuel Tank
–Fuel Cap
– Fuel Lines
– Evaporative Vent Lines
– Carbon Canister
Oil Capacity0.63 qt (0.6L)
Run time at 25% Rated Load5.7 Hours
Spark Plug TypeNGK BPR7HS
Spark Plug Gap.030 in (0.762 mm)
Dimensions L x W x H22 x 12 x 18 in (55.8 x 30.4 x 45.7 cm)
Weight Lb/kg43.5/19.7
Maximum AC Output1600 W
Surge AC Output1650 W
AC Volts120 VAC
Rated AC Current13.3 Amp
Frequency60 Hz
THD3.0%
Insulation ClassClass B
Outlets5-15R (2), 12 VDC (1)
DC Volts12 VDC
Rated DC Current5 Amp
Oil Capacity0.63 qt (0.6L)
Run time at 25% Rated Load5.3 Hours
Spark Plug TypeNGK BPR6ES
Spark Plug Gap.030 in (0.762 mm)
Dimensions L x W x H22 x 12 x 18 in (55.8 x 30.4 x 45.7 cm)
Weight Lb/kg49.6/22.5
Maximum AC Output2000 W
Surge AC Output2200 W
AC Volts120 VAC
Rated AC Current16.7 Amp
Frequency60 Hz
THD3.0%
Insulation ClassClass B
Outlets5-20R (2), 12 VDC (1)
DC Volts12 VDC
Rated DC Current5 Amp
Oil Capacity0.63 qt (0.6L)
Run time at 25% Rated Load4.7 Hours
Spark Plug TypeNGK BPR6ES
Spark Plug Gap.030 in (0.762 mm)
Dimensions L x W x H22 x 12 x 18 in (55.8 x 30.4 x 45.7 cm)
Weight Lb/kg49.6/22.5
Maximum AC Output2000 W
Surge AC Output2200 W
AC Volts120 VAC
Rated AC Current16.7 Amp
Frequency60 Hz
THD3.0%
Insulation ClassClass B
Outlets5-20R (2), 12 VDC (1)
DC Volts12 VDC
Rated DC Current5 Amp
0.85 gal (3.2L) Unleaded
0.82 gal (3.1L) Unleaded
6Owner’s Manual for Portable Generator
Page 9
Add Engine Oil
10W-30
SAE 30
Synthetic 5W-30
000729
000730
A
B
(000105)
DANGER
Explosion and Fire. Fuel and vapors are
extremely flammable and explosive. Add fuel
in a well ventilated area. Keep fire and spark
away. Failure to do so will result in death
or serious injury.
000728
A
B
CAUTION
Engine damage. Verify proper type and quantity of
engine oil prior to starting engine. Failure to do so
could result in engine damage.
Add recommended engine oil as shown in the
following chart.
NOTE: Use petroleum based oil (supplied) for
engine break-in before using synthetic oil.
.
1. Place generator on a level surface.
2. Remove the Left Side Service Cover.
3. Remove oil fill cap (A) located on bottom
of engine crankcase. See Figure 2-4.
4. Add recommended engine oil. The full
level is the base of the threads in the filler
neck (B). DO NOT OVERFILL!
5. Replace oil fill cap and hand-tighten.
(000135)
DANGER
Do not overfill fuel tank. Fill to 1/2 in. of top of tank to
allow for fuel expansion. Overfilling may cause fuel to
spill onto engine causing fire or explosion, which will
result in death or serious injury.
(000166)
Fuel requirements are as follows:
• Clean, fresh, unleaded gasoline.
• Minimum rating of 87 octane/87 AKI (91
RON).
• Up to 10% ethanol (gasohol) is acceptable
(where available; non-ethanol-premium fuel
is recommended).
• DO NOT use E85.
• DO NOT use a gas oil mix.
• DO NOT modify engine to run on alternate
fuels. Stabilize fuel prior to storage.
1. Verify unit is OFF and cooled for a mini-
mum of two minutes prior to fueling.
2. Place unit on level ground in a well venti-
lated area.
3. Clean area around fuel cap and remove
cap slowly (A). See Figure 2-5.
4. Add recommended fuel to 2 inches below
top (B). Do not overfill. See Figure 2-5.
5. Install fuel cap.
Figure 2-5. Add Recommended Fuel
NOTE: Allow spilled fuel to evaporate before
starting unit.
IMPORTANT NOTE: It is important to prevent gum deposits from forming in fuel
system parts such as the carburetor, fuel
hose or tank during storage. Alcoholblended fuels (called gasohol, ethanol or
methanol) can attract moisture, which
leads to separation and formation of acids
during storage. Acidic gas can damage the
fuel system of an engine while in storage.
To avoid engine problems, the fuel system
Figure 2-4. Add Engine Oil
Fuel
should be emptied before storage of 30
days or longer. See the Storage section.
Never use engine or carburetor cleaner
products in the fuel tank as permanent
damage may occur.
Owner’s Manual for Portable Generator7
Page 10
Section 3 Operation
(000179a)
DANGER
The exhaust system must be properly maintained. Do
not alter or modify the exhaust system as to render it
unsafe or make it noncompliant with local codes and/or
standards. Failure to do so will result in death
or serious injury.
(000118)
DANGER
Risk of fire. Do not use generator without
spark arrestor installed. Failure to do so
could result in death or serious injury.
(000178a)
Asphyxiation. Always use a battery operated carbon
monoxide alarm indoors and installed according to
the manufacturer’s instructions. Failure to do so
could result in death or serious injury.
WARNING
(000110)
WARNING
Risk of Fire. Hot surfaces could ignite
combustibles, resulting in fire. Fire could
result in death or serious injury.
(000108)
WARNING
Hot Surfaces. When operating machine, do not
touch hot surfaces. Keep machine away from
combustibles during use. Hot surfaces
could result in severe burns or fire.
(000136)
CAUTION
Equipment and property damage. Disconnect electrical
loads prior to starting or stopping unit. Failure to do so
could result in equipment and property damage.
Operation and Use Questions
Call Generac customer service at 1-888-GENERAC (1-888-436-3722) with questions or
concerns about equipment operation and
maintenance.
Before Starting Engine
1. Verify engine oil level is correct.
2. Verify fuel level is correct.
3. Verify unit is secure on level ground, with
proper clearance and is in a well ventilated
area.
Prepare Generator for Use
Asphyxiation. Running engines produce
carbon monoxide, a colorless, odorless,
poisonous gas. Carbon monoxide, if not
avoided, will result in death or serious injury.
DANGER
(000103)
Know Generator Limits
Overloading a generator can result in damage
to the generator and connected electrical
devices. Observe the following to prevent
overload:
• Add up the total wattage of all electrical
devices to be connected at one time. This
total should NOT be greater than the generator's wattage capacity.
• The rated wattage of lights can be taken
from light bulbs. The rated wattage of tools,
appliances, and motors can be found on a
data label or decal affixed to the device.
• If the appliance, tool, or motor does not
give wattage, multiply volts times ampere
rating to determine watts (volts x amps =
watts).
• Some electric motors, such as induction
types, require about three times more watts
of power for starting than for running. This
surge of power lasts only a few seconds
when starting such motors. Make sure to
allow for high starting wattage when selecting electrical devices to connect to the generator:
1. Figure the watts needed to start the largest
motor.
2. Add to that figure the running watts of all
other connected loads.
The Wattage Reference Guide is provided to
assist in determining how many items the generator can operate at one time.
NOTE: All figures are approximate. See data
label on appliance for wattage requirements.
Recoil Hazard. Recoil could retract unexpectedly.
Kickback could result in death or serious injury.
(000136)
CAUTION
Equipment and property damage. Disconnect electrical
loads prior to starting or stopping unit. Failure to do so
could result in equipment and property damage.
000725
Edge Trimmer500
Electric Blanket400
Electric Nail Gun1200
Electric Range (per element)1500
Electric Skillet1250
*Freezer700
*Furnace Fan (3/5 HP)875
*Garage Door Opener500 to 750
Hair Dryer1200
Hand Drill250 to 1100
Hedge Trimmer450
Impact Wrench500
Iron1200
*Jet Pump800
Lawn Mower1200
Light Bulb100
Microwave Oven700 to 1000
*Milk Cooler1100
Oil Burner on Furnace300
Oil Fired Space Heater (140,000
Btu)
Oil Fired Space Heater (85,000 Btu)225
Oil Fired Space Heater (30,000 Btu)150
*Paint Sprayer, Airless (1/3 HP)600
Paint Sprayer, Airless (hand-held)150
Radio50 to 200
*Refrigerator700
Slow Cooker200
*Submersible Pump (1-1/2 HP)2800
*Submersible Pump (1 HP)2000
*Submersible Pump (1/2 HP)1500
*Sump Pump800 to 1050
*Table Saw (10")1750 to 2000
Television200 to 500
Toaster1000 to 1650
Weed Trimmer500
* Allow 3 times the listed watts for starting these
devices.
400
Transporting/Tipping of the Unit
Do not operate, store or transport the unit at
an angle greater than 15 degrees.
Using the FlexPower™ Switch
When the accessories connected to the generator are going to be used intermittently
(such as a hand drill), the FlexPower™ switch
can be pushed to the ON (I) position. This will
lower generator engine speed when loads are
not being applied, saving fuel, reducing
engine wear and extending runtime.
Starting Pull Start Engines
1. Unplug all electrical loads from the unit's
receptacles before starting engine.
2. Place generator on a level surface.
3. Turn the FlexPower Switch OFF (O).
4. Turn fuel valve to the ON. See Figure 3-6.
Figure 3-6.Fuel Valve ON
5. Press primer bulb (up to six (6) times). See
Figure 3-7.
000726
Figure 3-7.Primer Bulb
6. Slide engine choke to Full Choke position
(right). See Figure 3-8.
Owner’s Manual for Portable Generator9
Page 12
Figure 3-8.Choke Position
000727
(000136)
CAUTION
Equipment and property damage. Disconnect electrical
loads prior to starting or stopping unit. Failure to do so
could result in equipment and property damage.
000725
7. Firmly grasp recoil handle and pull slowly
until increased resistance is felt. Pull rapidly up and away.
8. When engine starts, move choke knob to
1/2-choke position until engine runs
smoothly, then to OFF position. If engine
falters, move choke back to 1/2-choke
position until engine runs smoothly, then to
OFF position.
NOTE: If engine fires, but does not continue to
run, move choke lever to Full Choke and
repeat starting instructions.
IMPORTANT NOTE: Do not overload the
generator. Also, do not overload individual
panel receptacles. If the Overload LED
(red) is lit attached devices stop operating,
stop engine. Reduce loads before restarting engine. Read “Know Generator Limits”
carefully.
Generator Shut Down
1. Shut off all loads and unplug electrical
loads from generator panel receptacles.
2. Let engine run at no-load for several minutes to stabilize internal temperatures of
engine and generator.
3. Turn fuel valve to the OFF. See Figure 3-9.
.
Low Oil Level Shutdown System
The engine is equipped with a low oil level
sensor that shuts down the engine automatically when the oil level drops below a specified level. The engine will not run until the oil
has been filled to the proper level.
If the engine shuts down and there is sufficient
fuel, check engine oil level.
Using the 12 VDC Battery
.
Charger
WARNING
Risk of burn. Battery contains electrolyte solution
which can cause burns and blindness.
If electrolyte contacts skin or eyes, flush with
water and seek immediate medical attention.
The 12 VDC receptacle may be used to
recharge 12 VDC automotive batteries only.
The DC charging output is not regulated. The
circuit protector does not prevent overcharging a battery.
1. Connect the charging cable to the generator first, then the battery. ALWAYS connect
the red lead to positive (+), and the black
to negative (-).
2. Keep the FlexPower™ switch in the OFF
(O) position.
3. Start generator and use as normal.
Charging time will vary with battery size
and condition. Check voltage at battery
terminals once the charging cable has
been unplugged, or generator has been
shut down.
NOTE: This receptacle cannot recharge 6 Volt
batteries and cannot be used to crank an
engine having a discharged battery.
WARNING
WARNING
CAUTION
Do not make battery connections
in reverse. Doing so will result in
equipment damage.
(000137a)
(000163)
(000138a)
(000167)
Figure 3-9.Fuel Valve OFF
10Owner’s Manual for Portable Generator
Page 13
Section 4 Maintenance and Troubleshooting
10W-30
SAE 30
Synthetic 5W-30
000729
Maintenance Recommendations
Regular maintenance will improve performance and extend generator life. See a qualified dealer for service.
Generator warranty does not cover items subjected to operator abuse or negligence. To
receive full warranty value, operator must
maintain generator as instructed in this manual, including proper storage as detailed in
Winter Storage and Long Term Storage.
NOTE: Call 1-888-GENERAC (1-888-436-
3722) with questions about component
replacement.
Maintenance Schedule
Follow maintenance schedule intervals,
whichever occurs first according to use.
NOTE: Adverse conditions will require more
frequent service.
NOTE: All required service and adjustments
should be each season as detailed in the following chart.
At Each Use
Check engine oil level
Every 100 Hours or Every Season*
Change oil ǂ
Clean air filter**
Every 6 Months
Check spark plug
Check muffler
Every Season
Replace spark plug
Replace fuel filter
Inspect/clean spark arrestor
ǂ Change oil after first 5 hours of operation,
then every season.
* Change oil and oil filter every month when
operating under heavy load or in high temperatures.
** Clean more often under dirty or dusty oper-
ating conditions. Replace air filter parts if
they cannot be adequately cleaned.
WARNING
Do not insert any object through the air cooling slots.
Generator can start at any time and could result in
death, serious injury, and unit damage.
• Use a damp cloth to wipe exterior surfaces
clean.
• Use a soft bristle brush to loosen caked on
dirt, oil, etc.
• Use a vacuum to pick up loose dirt and
debris.
• Low pressure air (not to exceed 25 psi)
may be used to blow away dirt. Inspect
cooling air slots and openings on generator.
These openings must be kept clean and
unobstructed.
NOTE: DO NOT use a garden hose to clean
generator. Water can enter engine fuel system
and cause problems. If water enters generator
through cooling air slots, some water will be
retained in voids and crevices of rotor and stator winding insulation. Water and dirt buildup
on generator internal windings will decrease
insulation resistance of windings.
(000142)
Engine Maintenance
WARNING
Accidental start-up. Disconnect spark plug wires
when working on unit. Failure to do so could result
in death or serious injury.
Engine Oil Recommendations
Add recommended engine oil as shown in the
following chart.
NOTE: Use petroleum based oil (supplied) for
engine break-in before using synthetic oil.
.
(000141)
Preventive Maintenance
Dirt or debris can cause improper operation
and equipment damage. Clean generator
daily or before each use. Keep area around
and behind muffler free from combustible
debris. Inspect all cooling air openings on
generator.
Owner’s Manual for Portable Generator11
Page 14
Change Engine Oil
000730
A
B
B
C
A
D
000733
A
B
WARNING
Accidental start-up. Disconnect spark plug wires
when working on unit. Failure to do so could result
in death or serious injury.
When using generator under extreme, dirty,
dusty conditions, or in extremely hot weather,
change oil more frequently.
NOTE: Don’t pollute. Conserve resources.
Return used oil to collection centers.
Change oil while engine is still warm from running, as follows:
1. Place generator on a level surface.
2. Remove the Left Side Service Cover.
3. Remove oil fill cap (A) located on bottom
of engine crankcase. See Figure 4-1.
4. Tip unit and drain oil completely into a suitable container.
5. Add recommended engine oil. The full
level is the base of the threads in the filler
neck (B). DO NOT OVERFILL!
6. Install oil fill cap, and finger tighten.
7. Wipe up any spilled oil.
8. Properly dispose of oil in accordance with
all applicable regulations.
(000141)
4. Clean air filter cover before installing.
NOTE: To order a new air filter, contact the
nearest IASD at 1-888-GENERAC (1-888436-3722).
000731
Figure 4-2. Air Filter Assembly
Service Spark Plug
To service spark plug:
1. Remove spark plug cover (A). See Figure
4-3.
2. Pull spark plug lead from spark plug (B).
3. Use a socket wrench and remove spark
plug.
4. Install new spark plug into cylinder head
and tighten to 15 ft/lb (20.3 Nm).
5. Replace the spark plug lead, making sure
it is fully seated.
6. Replace spark plug cover.
Figure 4-3. Spark Plug
Inspect Muffler and Spark
Figure 4-1. Add Engine Oil
Air Filter
Engine will not run properly and may be damaged if run with a dirty air filter. Service air filter more frequently in dirty or dusty conditions.
To service air filter:
1. See Figure 4-2. Remove the Left Side Service Cover screw (A) and remove cover
(B).
2. Remove filter housing cover (C).
3. Remove air filter (D) and wash in soapy
water. Squeeze filter dry in clean cloth (DO
NOT TWIST).
12Owner’s Manual for Portable Generator
Arrester
NOTE: It is a violation of California Public
Resource Code, Section 4442, to use or operate the engine on any forest-covered, brushcovered, or grass-covered land unless the
exhaust system is equipped with a spark
arrester, as defined in Section 4442, maintained in effective working order. Other states
or federal jurisdictions may have similar laws.
Contact original equipment manufacturer,
retailer, or dealer to obtain a spark arrester
designed for exhaust system installed on this
engine.
NOTE: Use ONLY original equipment replacement parts.
Page 15
Inspect muffler for cracks, corrosion, or other
(000108)
WARNING
Hot Surfaces. When operating machine, do not
touch hot surfaces. Keep machine away from
combustibles during use. Hot surfaces
could result in severe burns or fire.
000735
A
B
C
D
(000168)
DANGER
Explosion and Fire. Fuel and vapors are
extremely flammable and explosive. Keep fire
and spark away. Failure to do so will result
in death or serious injury.
000732
A
damage. Remove spark arrester, if equipped,
inspect for damage or carbon blockage.
Replace parts as required.
Inspect Spark Arrester Screen (50
State)
Figure 4-5. Replace Fuel Filter
1. Remove clamp (A) and screen retainer
(B). See Figure 4-4.
2. Slide spark arrestor screens (C) out from
muffler outlet (D).
3. Inspect screens and replace if torn, perforated or otherwise damaged. Do NOT use
a defective screen. If screens are not damaged, clean with commercial solvent.
4. Replace screens (C) and retainer (B) and
secure with clamp (A).
Figure 4-4. Spark Arrestor Screen
Replace Fuel Filter
Locate fuel filter just below engine intake
housing. See Figure 4-5. Make sure fuel shutoff is OFF (O).
1. Remove the pinch clamps from fuel filter
(A) and pull hoses free.
2. Replace used filter.
3. Push fuel hoses onto barbed filter fittings
until they seat completely.
4. Replace clamps making sure they are
seated on the fittings.
Storage
General
Explosion and Fire. Fuel and vapors are extremely
flammable and explosive. Store fuel in a well
ventilated area. Keep fire and spark away. Failure
to do so will result in death or serious injury.
Risk of Fire. Verify machine has properly
cooled before installing cover and storing
machine. Hot surfaces could result in fire.
It is recommended to start and run the generator for 30 minutes, every 30 days. If this is not
possible, refer to the following list to prepare
unit for storage.
• DO NOT place a storage cover on a hot
generator. Allow unit to cool to room temperature before storage.
• DO NOT store fuel from one season to
another unless properly treated.
• Replace fuel container if rust is present.
Rust in fuel will cause fuel system problems.
• Cover unit with a suitable protective, moisture resistant cover.
• Store unit in a clean and dry area.
• Always store generator and fuel away from
heat and ignition sources.
DANGER
(000143)
WARNING
(000109)
Owner’s Manual for Portable Generator13
Page 16
Prepare Fuel System for Storage
A
(000181)
WARNING
Vision Loss. Eye protection is required to avoid
spray from spark plug hole when cranking engine.
Failure to do so could result in vision loss.
Fuel stored over 30 days can go bad and
damage fuel system components. Keep fuel
fresh, use fuel stabilizer.
If fuel stabilizer is added to fuel system, prepare and run engine for long term storage.
Run engine for 10-15 minutes to circulate stabilizer throughout fuel system. Adequately
prepared fuel can be stored up to 24 months.
NOTE: If fuel has not been treated with fuel
stabilizer, it must be drained into an approved
container. See Figure 4-6. Run engine until it
stops from lack of fuel. Use of fuel stabilizer in
fuel storage container is recommended to
keep fuel fresh.
000734
Figure 4-6. Carburetor Drain Valve
1. Change engine oil.
2. Remove spark plug.
3. Pour tablespoon (5-10cc) of clean engine
oil or spray a suitable fogging agent into
cylinder.
4. Pull starter recoil several times to distribute oil in cylinder.
5. Install spark plug.
6. Pull recoil slowly until resistance is felt.
This will close valves so moisture cannot
enter engine cylinder. Gently release
recoil.
Change Oil
Change engine oil before storage. See
Change Engine Oil.
14Owner’s Manual for Portable Generator
Page 17
Troubleshooting
PROBLEMCAUSECORRECTION
Engine won't start.1. No fuel in tank.
2. Fuel valve turned off.
3. Defective spark plug.
4. Plugged fuel filter.
5. Defective or stuck engine stop
switch.
1. Add fuel to tank.
2. Turn fuel valve on.
3. Replace spark plug.
4. Replace fuel filter.
5. Replace engine start switch.
Engine starts, then shuts
down.
Engine starts, then runs
rough.*
No AC output.1. Generator overloaded (Over-
1. Low fuel level.
2. Fuel tank vent closed.
3. Incorrect engine oil level.
4. Contaminated fuel.
5. Defective low oil level switch.
6. Defective ignition coil.
1. Choke is stuck or left on.
2. Dirty or clogged air filter.
3. Defective or dirty spark plug.
4. Dirty fuel filter.
5. Defective EcoMode switch.
load LED is on and Ready
LED is flashing. See
Figure 2-
2).
2. AC voltage is low (Overload
LED is on and Ready LED is
flashing. See
3. Inverter module overheated
(Overload LED is on and
Ready LED is flashing. See
Figure 2-2).
Figure 2-2).
4. Short circuit in electrical
device (Overload LED is on
and Ready LED is flashing.
Figure 2-2).
See
5. Defective inverter assembly.
No DC output. **1. DC circuit breaker is open.
2. Defective DC circuit breaker.
3. Defective rectifier.
1. Add fuel to tank.
2. Open fuel tank vent.
3. Check engine oil level. Add or
drain as needed.
4. Replace fuel filter.
5. Replace low oil level switch.
6. Replace ignition coil.
1. Turn choke off.
2. Clean or replace the air filter
element.
3. Replace spark plug.
4. Replace fuel and fuel filter.
5. Replace EcoMode switch.
1. Shut down generator to reset
module. Reduce loads and
restart generator.
2. Verify the choke is OFF.
3. Verify service door is ON. Let
cool for 15 minutes and start
generator.
4. Check condition of extension
cords and items being powered.
5. Replace inverter assembly.
1. Reset DC circuit breaker.
2. Replace DC circuit breaker.
3. Replace rectifier.
Fuel leaks from drain
hoses.
* Engine speed increases and decreases — This is normal as the generator starts up and as loads