Generac Power Systems GUARDIAN SERIES 005870-1, GUARDIAN 005872-1, GUARDIAN 005871-1 Overview

GENERAC® GUARDIAN® SERIES
STANDBY GENERATORS - PREPACKAGED
8 kW - 10 kW - 14 kW
Air-Cooled Gas Engine Generator Sets
INCLUDES:
• True Power® Electrical Technology
• Two Line LCD Tri-lingual Digital Nexus™ Controller
• 10, 12 or 14 Circuit Automatic Transfer Switch with Built-In Priority Load Center
• Pre-wired External Connection Box
• External Main Circuit Breaker, System Status & Maintenance Interval LED Indicators
• Sound Attenuated Enclosure
• Flexible Fuel Line Connector
• Composite Mounting Pad
• Pre-wired conduits
• Natural Gas or LP Gas Operation
• 3 Year Limited Warranty
• UL 2200 Listed
Standby Power Rating
Model 005870-1 (Steel - Bisque) - 8 kW 60Hz Model 005871-1 (Steel - Bisque) - 10 kW 60Hz Model 005872-1 (Steel - Bisque) - 14 kW 60Hz
FEATURES
¡ INNOVATIVE DESIGN & PROTOTYPE TESTING are key components
of GENERAC’S success in “IMPROVING POWER BY DESIGN.” But it doesn’t stop there. Total commitment to component testing, reliability testing, environmental testing, destruction and life testing, plus testing to applicable CSA, NEMA, EGSA, and other standards, allows you to choose GENERAC POWER SYSTEMS with the confidence that these systems will provide superior performance.
¡ TRUE POWER® ELECTRICAL TECHNOLOGY: Superior harmonics and
sine wave form produce less than 5% Total Harmonic Distortion for utility quality power. This allows confident operation of sensitive electronic equipment and micro-chip based appliances, such as variable speed HVAC.
¡ TEST CRITERIA:
PROTOTYPE TESTED NEMA MG1-22 EVALUATION
SYSTEM TORSIONAL TESTED MOTOR STARTING ABILITY
¡ SOLID-STATE, FREQUENCY COMPENSATED VOLTAGE REGULATION.
This state-of-the-art power maximizing regulation system is standard on all Generac models. It provides optimized FAST RESPONSE to changing load conditions and MAXIMUM MOTOR STARTING CAPABILITY by electronically torque-matching the surge loads to the engine. Digital voltage regulation at +/- 1%.
¡ SINGLE SOURCE SERVICE RESPONSE from Generac’s extensive dealer
network provides parts and service know-how for the entire unit, from the engine to the smallest electronic component.
¡ GENERAC TRANSFER SWITCHES. Long life and reliability are
synonymous with GENERAC POWER SYSTEMS. One reason for this confidence is that the GENERAC product line includes its own transfer systems and controls for total system compatibility.
FEATURES Generac
®
Guardian® Series Standby Generator - 8 kW - 10 kW - 14 kW
•Generac (OHVI) Design
•“Spiny-lok” cast iron cylinder walls
•Electronic ignition/spark advance
•Full pressure lubrication system
ENGINE
•Low oil pressure shutdown system
•High temperature shutdown
•Revolving field
• Skewed stator
•Displaced phase excitation
•Automatic voltage regulation
GENERATOR
•UL 2200 Listed
•Fully Automatic
•Pre-wired, color coded conduits
•Remote Mounting
SWITCH
TRANSFER
•UL Listed
•Manual/Auto/Off switch
Maximizes engine “breathing” for increased fuel efficiency. Plateau honed cylinder walls and plasma moly rings helps the engine run cooler, reducing oil consumption resulting in longer engine life.
Rigid construction and added durability provide long engine life.
These features combine to assure smooth, quick starting every time.
Pressurized lubrication to all vital bearings means better performance, less maintenance and longer engine life. Now featuring a 2 year/200 hour oil change interval.
Superior shutdown protection prevents catastrophic engine damage due to low oil.
Prevents damage due to overheating.
Allows for smaller, light weight unit that operates 25% more efficiently than a revolving armature generator.
Produces a smooth output waveform for compatibility with electronic equipment.
Maximizes motor starting capability.
Regulates the output voltage to ±1% prevents damaging voltage spikes.
For your safety.
Transfers your vital electrical loads to the energized source of power.
Ensures the easiest, trouble free installation.
Mounts near your existing distribution panel for simple, low cost installation.
For your safety.
Selects the operating mode.
•Utility voltage sensing
•Generator voltage sensing
•Utility interrupt delay
•Engine warm-up
•Engine cool-down
•Programmable seven day exerciser
NEXUS™ CONTROLS
•Smart battery charger
•Main Line Circuit Breaker
•Electronic governor
•Weather protective enclosure
•Enclosed critical grade muffler
UNIT
•Small, compact, attractive
•SAE
•Pre-wired External Connection Box
•1’ Flexible Fuel Line Connector
•Composite Mounting Pad
•Pre-wired conduits
SYSTEM
•UL Listed wire nuts
INSTALLATION
Constantly monitors utility voltage, setpoints 60% dropout, 80% pick-up, of standard voltage.
Constantly monitors generator voltage to ensure the cleanest power delivered to the home.
Prevents nuisance start-ups of the engine, adjustable 10-30 seconds.
Ensures engine is ready to assume the load, setpoint approximately 5 seconds.
Allows engine to cool prior to shutdown, setpoint approximately 1 minute.
Operates engine to prevent oil seal drying and damage between power outages by running the generator for 12 minutes every week.
Delivers charge to the battery only when needed at varying rates depending on outdoor air temperature.
Protects generator from overload.
Maintains constant 60 Hz frequency.
Ensures protection against mother nature. Hinged key locking roof panel for security. Lift-out front for easy access to all routine maintenance items. Electrostatically applied textured epoxy paint for added durability.
Quiet, critical grade muffler is mounted inside the unit to prevent injuries.
Makes for an easy, eye appealing installation.
Sound attenuated enclosure ensures quiet operation.
Easy Installation - Virtually all hardware included, plus step-by-step photographed Installation Guide.
SPECIFICATIONS
®
GENERATOR Model 005870-1 (8 kW) Model 005871-1 (10 kW) Model 005872-1 (14 kW)
Rated Maximum Continuous Power Capacity (LP) 8,000 Watts* 10,000 Watts* 14,000 Watts* Rated Maximum Continuous Power Capacity (NG) 7,000 Watts* 9,000 Watts* 13,000 Watts*
Rated Voltage 240 240 240 Rated Maximum Continuous Load Current – 240 Volts 33.3 LP/29.2 NG 41.6 LP/37.5 NG 58.3 LP/54.2 NG Total Harmonic Distortion Less than 5% Less than 5% Less than 5% Main Line Circuit Breaker 35 Amp 45 Amp 60 Amp Phase 1 1 1 Number of Rotor Poles 2 2 2 Rated AC Frequency 60Hz 60Hz 60Hz Power Factor 1 1 1
Battery Requirement (not included)
Unit Weight (Pounds/Kilos) 340/154.2 387/175.4 439/199.1 Dimensions (L x W x H) Inches/mm 48 x 25 x 29 (1218 x 638 x 732) Sound output in dB(A) at 23 ft. with generator operating at normal load 62 63 66
Group 26R 12 Volts and 525
Cold-cranking Amperes Minimum
ENGINE Model 005870-1 (8 kW) Model 005871-1 (10 kW) Model 005872-1 (14 kW)
Type of Engine GENERAC OHVI GENERAC OHVI V-TWIN GENERAC OHVI V-TWIN Number of Cylinders 1 2 2 Displacement 410cc 530cc 992cc Cylinder Block Aluminum w/Cast Iron Sleeve Aluminum w/Cast Iron Sleeve Aluminum w/Cast Iron Sleeve Valve Arrangement Overhead Valve Overhead Valve Overhead Valve Ignition System Solid-state w/Magneto Solid-state w/Magneto Solid-state w/Magneto Governor System Electronic Electronic Electronic Compression Ratio 9.4:1 9.5:1 9.5:1 Starter 12 Vdc 12 Vdc 12 Vdc Oil Capacity Including Filter Approx. 1.5 Qts./1.4L Approx. 1.7 Qts./1.6L Approx. 1.9 Qts./1.8L Operating RPM 3,600 3,600 3,600 Fuel Consumption Natural Gas cu.ft./hr.
1/2 Load Full Load
Liquid Propane ft3/hr (gal/hr) [Liter/hr]
1/2 Load Full Load
Required fuel pressure to generator fuel inlet at all load ranges - 5 to 7 inches of water column for natural gas, 10 to 12 inches of water column for LP gas For Btu content, multiply ft3/hr x 2520 (LP) or ft3/hr x 1000 (NG)
77
139
34 (0.94) [3.56] 62 (1.68) [6.36]
CONTROLS
2-Line Plain Text LCD Display Simple user interface for ease of operation. Mode Switch
-Auto Automatic Start on Utility failure. 7 day exerciser.
-Off Stops unit. Power is removed. Control and charger still operate.
-Manual/Test (start) Start with starter control, unit stays on. If utility fails, transfer to load takes place. Programmable start delay between 10-30 seconds Standard Engine Start Sequence Cyclic cranking: 16 sec. on, 7 rest (90 sec. maximum duration). Engine Warm-up 5 seconds Engine Cool-Down 1 minute Starter Lock-out Starter cannot re-engage until 5 sec. after engine has stopped. Smart Battery Charger Standard Automatic Voltage Regulation with Over and Under Voltage Protection Standard Automatic Low Oil Pressure Shutdown Standard Overspeed Shutdown Standard, 72Hz High Temperature Shutdown Standard Overcrank Protection Standard Safety Fused Standard Failure to Transfer Protection Standard Low Battery Protection Standard 50 Event Run Log Standard Future Set Capable Exerciser Standard Incorrect Wiring Protection Standard Internal Fault Protection Standard Common External Fault Capability Standard
Rating definitions - Standby: Applicable for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with BS5514, ISO3046 and DIN6271). * Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power and condition, etc. Maximum power decreases about 3.5 percent for each 1,000 feet above sea level; and also will decrease about 1 percent for each 12° C (10° F) above 15.5° C (60°F). Sound output ratings from certain points on the
generator subject to change based on installation parameters.
Group 26R 12 Volts and 525
Cold-cranking Amperes Minimum
102 156
46 (1.25) [4.73] 70 (1.93) [7.31]
Group 26R 12 Volts and 525
Cold-cranking Amperes Minimum
156 220
58 (1.56) [5.91] 84 (2.30) [8.71]
Generac® Guardian® Series Standby Generator - 8 kW - 10 kW - 14 kW
H2
H1
W1
®
TRANSFER
SWITCH
8KW - 17KW
(IF SUPPLIED)
TRANSFER
SWITCH
20KW
(IF SUPPLIED)
H1
W1
W2
H2
H1
W1
W2
®
EZ Switch™ Features
EZ SWITCH™ & LOAD CENTER
No. of Poles 2 2 2
Current Rating (amps) 100 100 100 Voltage Rating (VAC) 250 250 250 Utility Voltage Monitor (fixed)
-Pick-up
-Dropout
Return to Utility approx. 15 sec. approx. 15 sec. approx. 15 sec. Exerciser weekly for 12 minutes Standard Standard Standard UL Listed Standard Standard Standard
Dimensions (H” x W” x D”) Inches(mm) 26.5 x 12.5 x 7 (658 x 308 x 172)
Total of Pre-wired Circuits
No. 15A 120V No. 20A 120V No. 20A 240V No. 30A 240V No. 40A 240V No. 50A 240V
Circuit Breaker Protected
Available RMS Symmetrical Fault Current @ 250 Volts
W2
Model 005870-1
(8 kW)
80% 60%
10
3 3 1 1
-
-
Model 005871-1
(10 kW)
80% 60%
12
5 3
­1 1
-
10,000 10,000 10,000
Model 005872-1
(14 kW)
80% 60%
14
4 6 1
­1
-
• Electrically operated, mechanically-held contacts for
fast, positive connections.
• Rated for all classes of load, 100% equipment rated,
both inductive and resistive.
• 2 pole, 250 VAC contactors.
• 160 millisecond transfer time.
• Dual coil design.
• Main contacts are silver plated or silver alloy to
resist welding and sticking.
• NEMA 1 (indoor rated) enclosure is standard on the
100 amp switch.
• Pre-wired 30 foot (9.1 meter) whip to connect to the
pre-wired external connection box.
• Pre-wired 2 foot (0.61 meter) whip, color coded to
connect into the existing electrical panel.
H1
H2
Mechanical Dimensions (in inches)
Current Rating
No. of Poles
Height Width Depth
H1 H2 W1 W2
673mm 743mm 207mm 317.5mm 178mm
7100 UL Listed 2 26.5 in 29.25 in 8.14 in 12.5 in
Terminal Wire Ranges
ATS Rated Amps Switch Terminal Neutral Lug/Stud Ground Lug
Design and specifications subject to change without notice. Dimensions shown are approximate. Contact your Generac dealer for certified drawings. DO NOT USE THESE DIMENSIONS FOR INSTALLATION PURPOSES.
W1
637.6 [25.1]
100A 2-Pole UL 1 x 1/0-12 1 x 3/8-16 Stud 1 x 2/0-14
1218
[47.9]
731.9 [28.8]
642
[25.3]
LEFT SIDE VIEW
76.2 [3.0]
PEA GRAVEL
MINIMUM
1226 [48.3]
FRONT VIEW
®
AVAILABLE ACCESSORIES
Model # Product Description
5819 26R Wet Cell Battery
Every standby generator requires a battery to start the system. Generac offers the recommended 26R wet cell battery for use with all air-cooled standby product.
If the temperature regularly falls below 32° F, install a cold weather kit to maintain
6212 Cold Weather Kit
optimal battery temperature. Kit consists of battery warmer with thermostat built into the wrap.
5621
Auxiliary Transfer Switch Contact Kit
The auxiliary transfer switch contact kit allows the transfer switch to lock out a single large electrical load you may not need.
The fascia base wrap snaps together around the bottom the new air cooled
5839 Fascia Base Wrap Kit
generators. This offers a sleek, contoured appearance as well as offering protection from rodents and insects by covering the lifting holes located in the base.
5703 Paint Kit Bisque Kit
5662 - 8kW 5663 - 10kW 5664 - 14kW
Scheduled Maintenance Kit
Generac's scheduled maintenance kits provide all the hardware necessary to perform complete routine maintenance on a Generac automatic standby generator.
Completely wireless and battery powered, Generac's Nexus wireless remote monitor
5928 Nexus Wireless Remote
provides you with instant status information without ever leaving the house. Not compatible with CorePower or EcoGen systems.
5951
Advanced Nexus Wireless Remote
Remotely control generator functions with the advanced model's LCD display. In addition to remote testing of the generator, set the excercise cycle and maintenance interval reminders. Not compatible with CorePower or EcoGen systems.
Generac Power Systems, Inc. • S45 W29290 HWY. 59, Waukesha, WI 53189 • generac.com
©2012 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Bulletin 0186140SBY-H Printed in U.S.A . 10/05/12
Loading...