Throughout this publication, “DANGER!” and “CAUTION!” blocks are used to alert the mechanic to special
instructions concerning a particular service or operation that might be hazardous if performed incorrectly or
carelessly. PAY CLOSE ATTENTION TO THEM.
DANGER! UNDER THIS HEADING WILL BE FOUND SPECIAL INSTRUCTIONS WHICH, IF NOT COMPLIED
WITH, COULD RESULT IN PERSONAL INJURY OR DEATH.
*
CAUTION! Under this heading will be found special instructions which, if not complied with, could result
in damage to equipment and/or property.
*
These “Safety Alerts” alone cannot eliminate the hazards that they signal. Strict compliance with these special
instructions plus “common sense” are major accident prevention measures.
NOTICE TO USERS OF THIS MANUAL
This SERVICE MANUAL has been written and published by Generac to aid our dealers' mechanics and company service personnel when servicing the products described herein.
It is assumed that these personnel are familiar with the servicing procedures for these products, or like or
similar products manufactured and marketed by Generac. That they have been trained in the recommended
servicing procedures for these products, including the use of common hand tools and any special Generac
tools or tools from other suppliers.
Generac could not possibly know of and advise the service trade of all conceivable procedures by which a
service might be performed and of the possible hazards and/or results of each method. We have not undertaken any such wide evaluation. Therefore, anyone who uses a procedure or tool not recommended by
Generac must first satisfy themselves that neither his nor the products safety will be endangered by the service procedure selected.
All information, illustrations and specifications in this manual are based on the latest product information
available at the time of publication.
When working on these products, remember that the electrical system and engine ignition system are capable of violent and damaging short circuits or severe electrical shocks. If you intend to perform work where
electrical terminals could be grounded or touched, the battery cables should be disconnected at the battery.
Any time the intake or exhaust openings of the engine are exposed during service, they should be covered to
prevent accidental entry of foreign material. Entry of such materials will result in extensive damage when the
engine Is started.
During any maintenance procedure, replacement fasteners must have the same measurements and
strength as the fasteners that were removed. Metric bolts and nuts have numbers that indicate their strength.
Customary bolts use radial lines to indicate strength while most customary nuts do not have strength markings. Mismatched or incorrect fasteners can cause damage, malfunction and possible injury.
Components on Generac recreational vehicle generators are designed and manufactured to comply with
Recreational Vehicle Industry Association (RVIA) Rules and Regulations to minimize the risk of fire or explosion. The use of replacement parts that are not in compliance with such Rules and Regulations could result
in a fire or explosion hazard. When servicing this equipment, it is extremely important that all components be
properly installed and tightened. If improperly installed and tightened, sparks could ignite fuel vapors from fuel
system leaks.
The Megohmmeter...........................................20
Stator Insulation Resistance Test .....................20
Cleaning the Generator ....................................21
Drying the Generator .......................................21
Page 9
Page 12
SECTION 1.1
GENERATOR FUNDAMENTALS
PART 1
GENERAL INFORMATION
MAGNETISM
Magnetism can be used to produce electricity and
electricity can be used to produce magnetism.
Much about magnetism cannot be explained by our
present knowledge. However, there are certain patterns of behavior that are known. Application of these
behavior patterns has led to the development of generators, motors and numerous other devices that utilize magnetism to produce and use electrical energy.
See Figure 1. The space surrounding a magnet is permeated by magnetic lines of force called “flux”. These
lines of force are concentrated at the magnet's north
and south poles. They are directed away from the
magnet at its north pole, travel in a loop and re-enter
the magnet at its south pole. The lines of force form
definite patterns which vary in intensity depending on
the strength of the magnet. The lines of force never
cross one another. The area surrounding a magnet in
which its lines of force are effective is called a “magnetic field”.
Like poles of a magnet repel each other, while unlike
poles attract each other.
NOTE: The “right hand rule” is based on the “current flow” theory which assumes that current
flows from positive to negative. This is opposite
the “electron” theory, which states that current
flows from negative to positive.
Figure 2. The Right Hand Rule
ELECTROMAGNETIC INDUCTION
Figure 1. Magnetic Lines of Force
ELECTROMAGNETIC FIELDS
All conductors through which an electric current is
flowing have a magnetic field surrounding them. This
field is always at right angles to the conductor. If a
compass is placed near the conductor, the compass
needle will move to a right angle with the conductor.
The following rules apply:
directly proportional to the increase in current flow
and the field is distributed along the full length of
the conductor.
• Thedirectionofthelinesofforcearoundaconductor can be determined by what is called the “right
hand rule”. To apply this rule, place your right hand
around the conductor with the thumb pointing in
the direction of current flow. The fingers will then be
pointing in the direction of the lines of force.
An electromotive force (EMF) or voltage can be produced in a conductor by moving the conductor so that
it cuts across the lines of force of a magnetic field.
Similarly, if the magnetic lines of force are moved so
that they cut across a conductor, an EMF (voltage)
will be produced in the conductor. This is the basic
principal of the revolving field generator.
Figure 3, below, illustrates a simple revolving field
generator. The permanent magnet (Rotor) is rotated
so that its lines of magnetic force cut across a coil of
wires called a Stator. A voltage is then induced into
the Stator windings. If the Stator circuit is completed
by connecting a load (such as a light bulb), current
will flow in the circuit and the bulb will light.
Figure 3. A Simple Revolving Field Generator
Page 10
Page 13
GENERAL INFORMATION
S
TATOR
ROT
OR
MAGNETIC FIEL
D
CURRENT
VOLTAGE
ONE CYCLE
0
180
360
(+)
(-)
STATOR
ROTOR
GENERATOR
120 VAC
120 VAC
+
-
AC OUTPUT
STATOR
240 VAC
CAPACITOR
STATOR
BRUSHES
120 V
120 V
+
-
SLIP
RINGS
AC OUTPUTDC CURRENT
STATOR
240 V
PART 1
SECTION 1.1
GENERATOR FUNDAMENTALS
A SIMPLE AC GENERATOR
Figure 4 shows a very simple AC Generator. The generator consists of a rotating magnetic field called a
ROTOR and a stationary coil of wire called a STATOR.
The ROTOR is a permanent magnet which consists of
a SOUTH magnetic pole and a NORTH magnetic pole.
As the MOTOR turns, its magnetic field cuts across
the stationary STATOR. A voltage is induced Into
the STATOR windings. When the magnet's NORTH
pole passes the STATOR, current flows in one direction. Current flows in the opposite direction when the
magnet's SOUTH pole passes the STATOR. This constant reversal of current flow results in an alternating
current (AC) waveform that can be diagrammed as
shown in Figure 5.
The ROTOR may be a 2-pole type having a single
NORTH and a single SOUTH magnetic pole. Some
ROTORS are 4-pole type with two SOUTH and two
NORTH magnetic poles. The following apply:
1. The 2-pole ROTOR must be turned at 3600 rpm to produce an AC frequency of 60 Hertz, or at 3000 rpm to
deliver an AC frequency of 50 Hertz.
2. The 4-pole ROTOR must operate at 1800 rpm to deliver
a 60 Hertz AC frequency or at 1500 rpm to deliver a 50
Hertz AC frequency.
A MORE SOPHISTICATED AC GENERATOR
Figure 6 and 7 show two methods of creating alternating current that are implemented on GP Series portable generator product.
Figure 6 shows a consistent voltage being induced to
the rotor from a capacitor which is installed in series
with the DPE winding. As a result a regulated voltage
is induced into the STATOR.
Figure 4. A Simple AC Generator
Figure 5. Alternating Current Sine Wave
Figure 6. Capacitive Discharge
Figure 7 shows a regulated direct current being delivered into the ROTOR windings via carbon BRUSHES
AND SLIP RINGS. This results in the creation of
a regulated magnetic field around the ROTOR. As
a result, a regulated voltage is induced into the
STATOR. Regulated current delivered to the ROTOR
is called “EXCITATION” current.
Figure 7. Direct Excitation
Page 11
Page 14
SECTION 1.1
CAPACITOR
STATOR
EXCITATION
WINDING
STATOR
POWER
WINDING
STATOR
POWER
WINDING
MAGNETIC
FIELD
MAGNETIC
FIELD
MLB = MAIN LINE
CIRCUIT BREAKER
ROTOR
TO LOAD
MLB
ENGINE DIRECT
DRIVE
AUTOMATIC
VOLTAGE
REGULATOR
+-
STATOR
EXCITATION
WINDING
STATOR
POWER
WINDING
STATOR
POWER
WINDING
MAGNETIC
FIELD
MAGNETIC
FIELD
SENSING
MLB = MAIN LINE
CIRCUIT BREAKER
ROTOR
TO LOAD
MLB
ENGINE DIRECT
DRIVE
120 VAC120 VAC
240 VAC
120 VAC120 VAC
240 VAC
AB
CAPACITIVE DISCHARGEDIRECT EXCITATION
GENERATOR FUNDAMENTALS
PART 1
GENERAL INFORMATION
Figure 8. Generator Operating Diagram
The revolving magnetic field is driven by the engine
at constant speed. This constant speed is maintained
by a mechanical engine governor. Units with a 2-pole
rotor require an operation speed of 3600 rpm to deliver a 60 Hertz AC output.
Generator operation may be described briefly as follows.
1. Some “residual” magnetism is normally present in the
Rotor, which is sufficient to induce approximately 1 to 2
Volts AC in to the Stator’s AC Power Windings and DPE
winding.
2. See Figure 8.
A. Dur ing startup, the “residual” voltage that
is induced into the DPE winding will initially
charge the capacitor to a greater potential.
When the capacitor is discharged the voltage
is in turn induced back into the Rotor which will
exponen tially raise the voltage to 120/240.
B. During startup, the “residual” voltage that is
induced into the DPE winding will turn on the
voltage regulator allowing DC excitation current
to be delivered to the rotor and raise the voltage
to 120/240.
Page 12
Page 15
GENERAL INFORMATION
PART 1
SECTION 1.2
MEASURING ELECTRICITY
METERS
Devices used to measure electrical properties are called
meters. Meters are available that allow one to measure
(a) AC voltage, (b) DC voltage, (c) AC frequency, and
(d) resistance in ohms. The following apply:
A meter that will permit both voltage and resistance to
be read is the “volt-ohm-milliammeter” or “VOM”.
Some VOMs are of the “analog” type (not shown).
These meters display the value being measured by
physically deflecting a needle across a graduated
scale. The scale used must be interpreted by the user.
“Digital” VOMs (Figure 1) are also available and are
generally very accurate. Digital meters display the
measured values directly by converting the values to
numbers.
NOTE: Standard AC volt me te rs react to the
AVERAGE value of alternating current. When working with AC, the effective value is used. For that
reason a different scale is used on an AC voltmeter. The scale is marked with the effective or “rms”
value even though the meter actually reacts to the
average value. That is why the AC voltmeter will
give an incorrect reading if used to measure direct
current (DC).
MEASURING AC VOLTAGE
An accurate AC voltmeter or a VOM may be used to
read the generator's AC output voltage. The following
apply:
1. Always read the generator's AC output voltage only at
the unit's rated operating speed and AC frequency.
2. The generator's Voltage Regulator can be adjusted for
correct output voltage only while the unit is operating at
its correct rated speed and frequency.
3. Only an AC voltmeter may be used to measure AC
voltage. DO NOT USE A DC VOLTMETER FOR THIS
PURPOSE.
DANGER! GENERATORS PRODUCE HIGH
AND DANGEROUS VOLTAGES. CONTACT
*
WITH HIGH VOLTAGE TERMINALS WILL
RESULT IN DANGEROUS AND POSSIBLY
LETHAL ELECTRICAL SHOCK.
MEASURING DC VOLTAGE
A DC voltmeter or a VOM may be used to measure
DC voltages. Always observe the following rules:
1. Always observe correct DC polarity.
a. Some VOM's may be equipped with a polar-
ity switch.
b. On meters that do not have a polarity switch,
DC polarity must be reversed by reversing
the test leads.
2. Before reading a DC voltage, always set the meter to a
higher voltage scale than the anticipated reading. If in
doubt, start at the highest scale and adjust the scale
downward until correct readings are obtained.
Figure 1. Digital VOM
3. The design of some meters is based on the “current
flow” theory while others are based on the “electron flow”
theory.
a. The “current flow” theory assumes that direct
current flows from the positive (+) to the
negative (-).
b. The “electron flow” theory assumes that cur-
rent flows from negative (-) to positive (+).
NOTE: When testing generators, the “current flow”
theory is applied. That is, current is assumed to
flow from positive (+) to negative (-).
MEASURING AC FREQUENCY
The generator's AC output frequency is proportional to
Rotor speed. Generators equipped with a 2-pole Rotor
must operate at 3600 rpm to supply a frequency of 60
Hertz. Units with 4-pole Rotor must run at 1800 rpm to
deliver 60 Hertz.
Page 13
Page 16
SECTION 1.2
1.00 A
BATTERY
+-
RELAY
MEASURING ELECTRICITY
PART 1
GENERAL INFORMATION
Correct engine and Rotor speed is maintained by an
engine speed governor. For models rated 60 Hertz,
the governor is generally set to maintain a no-load frequency of about 62 Hertz with a corresponding output
voltage of about 124 volts AC line-to-neutral. Engine
speed and frequency at no-load are set slightly high
to prevent excessive rpm and frequency droop under
heavy electrical loading.
MEASURING CURRENT
CLAMP-ON:
To read the current flow, in AMPERES, a clamp-on
ammeter may be used. This type of meter indicates
current flow through a conductor by measuring the
strength of the magnetic field around that conductor.
The meter consists essentially of a current transformer with a split core and a rectifier type instrument connected to the secondary. The primary of the current
transformer is the conductor through which the current
to be measured flows. The split core allows the instrument to be clamped around the conductor without
disconnecting it.
Current flowing through a conductor may be measured
safely and easily. A line-splitter can be used to measure
current in a cord without separating the conductors.
NOTE: If the physical size of the conductor or ammeter capacity does not permit all lines to be measured
simultaneously, measure current flow in each individual line. Then, add the individual readings.
IN-LINE:
Alternatively, to read the current flow in AMPERES, an
in-line ammeter may be used. Most Digital Volt Ohm
Meters (VOM) will have the capability to measure
amperes.
This usually requires the positive meter test lead to be
connected to the correct amperes plug, and the meter
to be set to the amperes position. Once the meter is
properly set up to measure amperes the circuit being
measured must be physically broken. The meter will
be in-line or in series with the component being measured.
In Figure 4 the control wire to a relay has been
removed. The meter is used to connect and supply
voltage to the relay to energize it and measure the
amperes going to it.
Figure 2. Clamp-On Ammeter
Figure 3. A Line-Splitter
Page 14
Figure 4. A VOM as an In-line meter
MEASURING RESISTANCE
The volt-ohm-milliammeter may be used to measure
the resistance in a circuit. Resistance values can be
very valuable when testing coils or windings, such as
the Stator and Rotor windings.
When testing Stator windings, keep in mind that the
resistance of these windings is very low. Some meters
are not capable of reading such a low resistance and
will simply read CONTINUITY.
If proper procedures are used, the following conditions
can be detected using a VOM:
current flow (number of electrons
past a given point)
OHM - Unit measuring resistance
or opposition to flow
VOLT - Unit measuring force or
difference in potential
causing current flow
Conductor of a
Circuit
VOLTS
(E)
AMPS
(I)
OHMS
(R)
PART 1
SECTION 1.2
MEASURING ELECTRICITY
Component testing may require a specific resistance value or a test for INFINITY or CONTINUITY.
Infinity is an OPEN condition between two electrical
points, which would read as no resistance on a VOM.
Continuity is a CLOSED condition between two electrical points, which would be indicated as very low resistance or “ZERO” on a VOM.
ELECTRICAL UNITS
AMPERE:
The rate of electron flow in a circuit is represented
by the AMPERE. The ampere is the number of electrons flowing past a given point at a given time. One
AMPERE is equal to just slightly more than six thousand million billion electrons per second (6.25 x 1018).
With alternating current (AC), the electrons flow first in
one direction, then reverse and move in the opposite
direction. They will repeat this cycle at regular intervals. A wave diagram, called a “sine wave” shows that
current goes from zero to maximum positive value,
then reverses and goes from zero to maximum negative value. Two reversals of current flow is called a
cycle. The number of cycles per second is called frequency and is usually stated in “Hertz”.
VOLT :
The VOLT is the unit used to measure electrical
PRESSURE, or the difference in electrical potential
that causes electrons to flow. Very few electrons will
flow when voltage is weak. More electrons will flow as
voltage becomes stronger. VOLTAGE may be considered to be a state of unbalance and current flow as
an attempt to regain balance. One volt is the amount
of EMF that will cause a current of 1 ampere to flow
through 1 ohm of resistance.
OHM:
The OHM is the unit of RESISTANCE. In every circuit
there is a natural resistance or opposition to the flow
of electrons. When an EMF is applied to a complete
circuit, the electrons are forced to flow in a single
direction rather than their free or orbiting pattern. The
resistance of a conductor depends on (a) its physical
makeup, (b) its cross-sectional area, (c) its length, and
(d) its temperature. As the conductor's temperature
increases, its resistance increases in direct proportion.
One (1) ohm of resistance will permit one (1) ampere
of current to flow when one (1) volt of electromotive
force (EMF) is applied.
OHM'S LAW
A definite and exact relationship exists between VOLTS,
OHMS and AMPERES. The value of one can be calculated when the value of the other two are known. Ohm's
Law states that in any circuit the current will increase
when voltage increases but resistance remains the
same, and current will decrease when resistance
Increases and voltage remains the same.
Figure 5. Electrical Units
Figure 6. Ohm's Law
If AMPERES is unknown while VOLTS and OHMS are
known, use the following formula:
OHMS
If VOLTS is unknown while AMPERES and OHMS are
known, use the following formula:
If OHMS is unknown but VOLTS and AMPERES are
known, use the following:
AMPERES
AMPERES =
VOLTS = AMPERES x OHMS
OHMS
VOLTS
VOLTS
=
Page 15
Page 18
STATOR
ROTOR
ENGINE
CAPACITOR
DIODE B
COIL 2
COIL 1
DIODE A
CAPACITOR
STATOR
EXCITATION
WINDING
STATOR
POWER
WINDING
STATOR
POWER
WINDING
MAGNETIC
FIELD
MAGNETIC
FIELD
MLB = MAIN LINE
CIRCUIT BREAKER
ROTOR
TO LOAD
MLB
ENGINE DIRECT
DRIVE
AUTOMATIC
VOLTAGE
REGULATOR
+-
STATOR
EXCITATION
WINDING
STATORPOWER
WINDING
STATORPOWER
WINDING
MAGNETIC
FIELD
MAGNETIC
FIELD
SENSING
MLB = MAIN LINECIRCUIT BREAKER
ROTOR
TO LOAD
MLB
ENGINE - DIRECTDRIVE
120 VAC120 VAC
240 VAC
120 VAC120 VAC
240 VAC
SECTION 1.3
BRUSHLESS, CAPACITOR EXCITATION SYSTEM
PART 1
GENERAL INFORMATION
INTRODUCTION
A typical brushless type portable generator will need
4 major components to function—a prime mover, a
stator, a rotor, and a capacitor.
As the engine starts to crank, residual magnetism
from the rotor creates magnetic lines of flux. The
lines begin to cut the excitation winding and induce
a small voltage into the winding. The voltage causes
the capacitor to charge. When the capacitor has fully
charged it will discharge a voltage that will be induced
back into the rotor. The AC voltage induced into the
rotor is rectified using a diode. The magnetic lines of
flux from the rotor will increase, causing output voltage to increase. The charge and discharge relationship that the capacitor and rotor share is the voltage
regulation system that allows the generator to maintain 240 volts.
Figure 1 shows the major components of a typical GP
Series brushless AC generator.
a tapered crankshaft and is held in place with a single
through bolt.
Note: Some Rotors have a magnet placed inside
to help excite the rotor after it has been left idle
for a long period of time.
Figure 2. Rotor and Diodes
Figure 1. AC Generator Exploded View
The stator has three windings wound separately
inside the can. Two are the power windings and are
STATOR ASSEMBLY
located on Wire 44 (Hot) and Wire 33 (Neutral), the
other winding is located on Wire 11 (Hot) and Wire 22
(Neutral). The third winding is called the DPE winding
or Displaced Phase Excitation winding and is located
on Wire 2 and Wire 6.
The 2-pole rotor must be operated at 3600 rpm to
supply a 60 Hertz AC frequency. The term “2-pole”
means the rotor has a single north magnetic pole and
a single south magnetic pole. It spins freely inside
the stator can and is excited by the charging and discharging of the capacitor. It has two diodes that rectify voltage induced from the Excitation winding to DC
voltage. The rotor bearing is pressed onto the end of
the rotor shaft. The tapered rotor shaft is mounted to
Page 16
ROTOR ASSEMBLY
CIRCUIT BREAKERS
Each individual circuit on the generator is protected
by a circuit breaker to prevent overload.
Figure 3. Generator Operating Diagram
Page 19
GENERAL INFORMATION
CAPACITOR 28µf
WIRE 2
WIRE 6
RED (R2 – 33)
BLUE (R1 – 44)
BROWN (L2 – 22)
WHITE (L1 – 11)
WIRE 2
WIRE 6
11 22 33 44
CAPACITOR 47µf (440 VAC)
PART 1
SECTION 1.3
BRUSHLESS, CAPACITOR EXCITATION SYSTEM
OPERATION
STARTUP:
When the engine is started, residual magnetism from
the rotor induces a voltage into (a) the stator AC
power windings, (b) the stator excitation or DPE windings. In an “On-speed” (engine cranking) condition,
residual magnetism is capable of creating approximately one to three Volts AC.
ON-SPEED OPERATION:
As the engine accelerates, the voltage that is induced
into the stator windings increases rapidly, due to the
increasing speed at which the rotor operates.
FIELD EXCITATION:
An AC voltage is induced into the stator excitation
(DPE) windings. The DPE winding circuit is completed
to the capacitor where the charging and discharging
causes a voltage to be induced back in to the rotor
which will regulate voltage. The greater the current
flow through the rotor windings, the more concentrated the lines of flux around the rotor become. The
more concentrated the lines of flux around the rotor
that cut across the stationary stator windings, the
greater the voltage that is induced into the stator
windings. Initially, the AC power winding voltage is
low, but as the capacitor is charged and discharged
this relationship between the rotor and the capacitor
is what will regulate voltage at a desired level.
AC POWER WINDING OUTPUT:
A regulated voltage is induced into the stator AC
power windings. When electrical loads are connected
across the AC power windings to complete the circuit,
current can flow in the circuit.
A
Figure 4. Alternator Configuration A
B
Figure 5. Alternator Configuration B
Page 17
Page 20
STATOR
ROTOR
ENGINE
BRUSHES
VOLTAGE REGULATOR
Section 1.4
BRUSHED EXCITATION SYSTEM
PART 1
GENERAL INFORMATION
INTRODUCTION
A typical brushed type portable generator will need 4
major components to function: a prime mover, a stator, a rotor, and a voltage regulator.
As the engine starts to crank, residual magnetism
from the rotor creates magnetic lines of flux. The lines
begin to cut the excitation winding and induce a small
voltage into the voltage regulator. The excitation voltage will power the voltage regulator and the voltage
regulator will start to sense AC voltage from Wires
S15 and S16. The lower voltage from the sensing
wires will cause DC excitation to the rotor to be driven
up until AC output is at desired level of 240VAC. Once
the generator has reached 240VAC it will maintain the
DC voltage, regulating the alternator when loads are
applied and removed.
to the negative (-) slip ring and brush on Wire 0. This
current flow creates a magnetic field around the rotor
having a flux concentration that is proportional to the
amount of current flow.
ROTOR RESIDUAL MAGNETISM
The generator revolving field (rotor) may be considered to be a permanent magnet. Some “residual”
magnetism is always present in the rotor. This residual magnetism is sufficient to induce a voltage into the
stator AC power windings that is approximately 2-5
volts AC.
Note: Some Rotors have a magnet placed inside
to help excite the rotor after it has been left idle
for a long period of time.
VOLTAGE REGULATOR
Refer to Figure 3 for the proper identification of the
voltage regulator. Unregulated AC output from the
stator excitation winding is delivered to the regulator’s
DPE terminals, via Wire 2 and Wire 6. The voltage
regulator rectifies that current and, based on stator
AC power winding sensing, regulates it. The rectified
and regulated excitation current is then delivered to
the rotor windings from the positive (+) and negative
(-) regulator terminals, via Wire 4 and Wire 0. Stator
AC power winding “sensing” is delivered to the regulator via Wires S15 and S16.
Figure 1. AC Generator Exploded View
STATOR ASSEMBLY
The stator has three windings wound separately
inside the can. Two are the power windings and are
located on Wire 44 (Hot) and Wire 33 (Neutral); the
other winding is located on Wire 11 (Hot) and Wire 22
(neutral). The third winding is called DPE winding or
Displaced Phase Excitation winding and is located on
Wire 2 and Wire 6.
BRUSH HOLDER AND BRUSHES
The brush holder is retained to the rear bearing carrier by means of two Taptite screws. A positive (+) and
a negative (-) brush are retained in the brush holder.
Wire 4 connects to the positive (+) brush and Wire
0 to the negative (-) brush. Rectified and regulated
excitation current are delivered to the rotor windings
via Wire 4, and the positive (+) brush and slip ring.
The excitation current passes through the windings
Page 18
OPERATION
STARTUP:
When the engine is started, residual magnetism from
the rotor induces a voltage into (a) the stator AC
power windings, (b) the stator excitation or DPE windings. In an “on-speed” (engine cranking) condition,
residual magnetism is capable of creating approximately one to three volts AC.
ON-SPEED OPERATION:
As the engine accelerates, the voltage that is induced
into the stator windings increases rapidly, due to the
increasing speed at which the rotor operates.
FIELD EXCITATION:
An AC voltage is induced into the stator excitation
(DPE) windings. The DPE winding circuit is completed to the voltage regulator, via Wire 2 and Wire
6. Unregulated alternating current can flow from the
winding to the regulator. The voltage regulator “senses” AC power winding output voltage and frequency
via stator Wires S15 and S16.
The regulator changes the AC from the excitation
winding to DC. In addition, based on the Wire S15
and Wire S16 sensing signals, it regulates the flow of
direct current to the rotor. The rectified and regulated
current flow from the regulator is delivered to the rotor
windings, via Wire 4, and the positive brush and slip
ring. This excitation current flows through the rotor
Page 21
GENERAL INFORMATION
AUTOMATIC
VOLTAGE
REGULATOR
+-
STATOR
EXCITATION
WINDING
STATOR
POWER
WINDING
STATOR
POWER
WINDING
MAGNETIC
FIELD
MAGNETIC
FIELD
SENSING
MLB = MAIN LINE
CIRCUIT BREAKER
ROTOR
TO LOAD
MLB
ENGINE DIRECT
DRIVE
120 VAC120 VAC
240 VAC
VOLTAGE REGULATOR
AVR SENSING
DPE
NOT USED
RED (R2 – 11)
BLUE (R1 – 22)
BLUE
BLUE
4 (+) RED
S15
2
S16
6
0 (-) WHITE
BROWN (L2 – 33)
WHITE (L1 – 44)
WHITE
GREEN
C1 FEMALE
C1 MALE
PART 1
windings and through the negative (-) slip ring and
brush on Wire 0.
The greater the current flow through the rotor windings, the more concentrated the lines of flux around
the rotor become. The more concentrated the lines
of flux around the rotor that cut across the stationary
stator windings, the greater the voltage that is induced
into the stator windings.
Initially, the AC power winding voltage sensed by the
regulator is low. The regulator reacts by increasing
the flow of excitation current to the rotor until voltage increases to a desired level. The regulator then
maintains the desired voltage. For example, if voltage
exceeds the desired level, the regulator will decrease
the flow of excitation current. Conversely, if voltage
drops below the desired level, the regulator responds
by increasing the flow of excitation current.
AC POWER WINDING OUTPUT:
A regulated voltage is induced into the stator AC
power windings. When electrical loads are connected
across the AC power windings to complete the circuit,
current can flow in the circuit.
Test 5 – Check Brushed Rotor Circuit ..............28
Test 6 – Check Capacitor .................................29
Test 7 – Test Brushless DPE Winding ..............30
Test 8 – Test Brushless Stator Windings ..........30
Test 9 – Test Brushed Stator Windings ............31
Test 10 – Check Load Voltage & Frequency ....31
Test 11 – Check Load Watts & Amperage .......31
Test 12 – Adjust Voltage Regulator ..................31
Page 21
Page 24
SECTION 2.1
GO TO PROBLEM 2GO TO PROBLEM 1GO TO PROBLEM 4VERIFY ROTOR IS SPINNING,
GO TO PROBLEM 1
GO TO PROBLEM 3
VOLTAGE &
FREQUENCY BOTH
HIGH OR LOW
FREQUENCY GOOD
VOLTAGE HIGH
ZERO VOLTAGE
ZERO FREQUENCY
FREQUENCY GOOD,
LOW OR RESIDUAL
VOLTAGE
TEST 1 - CHECK
NO LOAD VOLTAGE
& FREQUENCY
NO LOAD VOLTAGE &
FREQUENCY GOOD -
VOLTAGE/FREQUENCY
FALLS OFF UNDER LOAD
If Problem Involves AC Output
REPLACE
ALTERNATOR
REPLACE
ROTOR
STOP TESTING
BAD
BAD
GOOD
GOOD
CONFIGURATION “B”
GOOD
CONFIGURATION “A”
BAD
CONFIGURATION “B”
BAD
CONFIGURATION “A”
Problem 1 – Generator Produces Zero Voltage or Residual Voltage
TEST 2 – CHECK
MAIN CIRCUIT
BREAKER
RESET TO “ON”
OR REPLACE IF BAD
REPLACE COMPONENT
AS NEEDED
STOP
TESTING
TEST 3 – CHECK
CONTINUITY OF
RECEPTACLE PANEL
RE-CHECK VOLTAGE
AT RECEPTACLE
PANEL
RE-CHECK VOLTAGE
AT RECEPTACLE
PANEL
TEST 4 – FIELD
FLASH
ALTERNATOR
REPLACE
BAD
BAD
BAD
REPLACE
S TATO R
BAD
REPLACE
ALTERNATOR
REPLACE
CAPACITOR
ON
GOOD
GOODGOODGOOD
TEST 6 –
CHECK
CAPACITOR
TEST 7 – TEST
BRUSHLESS
DPE WINDING
TEST 8 – TEST
BRUSHLESS
STATOR
WINDINGS
TEST STATOR
FOR SHORTS
TO GROUND
GOOD
BRUSHLESS CAPACITOR TROUBLESHOOTING FLOWCHARTS
PART 2
AC GENERATORS
The GP series portable generators currently use
three different types of alternators. Two of the alternators are brushless capacitor type with different style of
capacitors (Configuration “A” and “B”). The third utilizes a voltage regulator and a brushed excitation system (Configuration “C”). To help with troubleshooting,
two sets of flow charts have been created for these
different styles of alternators.
Identify the configuration of the alternator being serviced using Sections 1.3 and 1.4 of this manual and
proceed to the appropriate flowchart section.
Configuration “A” – Brushless Capacitor, use Section 2.1
Configuration “B” – Brushless Capacitor, use Section 2.1
Configuration “C” – Brushed Excitation, use Section 2.2
Page 22
Page 25
AC GENERATORS
TEST 40 – CHECK & ADJUST ENGINE
GOVERNOR, 389cc ENGINE
TEST 41 – CHECK & ADJUST ENGINE
GOVERNOR, 410cc ENGINE
GO TO
PROBLEM 1
GO TO
PROBLEM 3
GO TO PROBLEM 1,
TEST 6 – CHECK
CAPACITOR
Problem 2 – V
oltage & Frequency Are Both High or Low
FREQUENCY GOOD, LOW OR
RESIDUAL VOLTAGE
FREQUENCY IS GOOD BUT
NO-LOAD VOLTAGE IS HIGH
NO-LOAD FREQUENCY & VOLTAGE GOOD BUT
THEY DROOP TO MUCH WHEN LOAD IS APPLIED
CONFIGURATION “B”
CONFIGURATION “A”
REPLACE
ALTERNATOR
STOP
TESTING
RE-CHECK VOLTAGE
AT RECEPTACLE
PANEL
REPLACE
CAPACITOR
GOOD
BAD
GO TO PROBLEM 12
GO TO PROBLEM 23
REDUCE LOAD
END TEST
Problem 3 – Excessive Voltage/Frequency Droop When Load is Applied
TEST 10 – CHECK
LOAD VOLTAGE &
FREQUENCY
TEST 11 – CHECK
LOAD WATTS &
AMPERAGE
GOOD
GOODGOOD
BAD
OVERLOADED
NOT OVERLOADED
TEST 41 – CHECK
& ADJUST
ENGINE
GOVERNOR,
410cc ENGINE
TEST 40 – CHECK
& ADJUST
ENGINE
GOVERNOR,
389cc ENGINE
CONFIGURATION “B”
STOP
TESTS
REPLACE
Problem 4 – Generator Produces High Voltage at No-Load
TEST 1 – CHECK
NO-LOAD VOLTAGE
AND FREQUENCY
FREQUENCY AND
VOLTAGE O.K.
FREQUENCY O.K.,
BUT VOLTAGE HIGH
FREQUENCY
HIGH
BAD
GO TO “PROBLEM 1”,
TEST 7 – TEST BRUSHLESS
DPE WINDING
FREQUENCY O.K., BUT
VOLTAGE IS STILL HIGH
TEST 6 –
CHECK
CAPACITOR
TEST 40 – CHECK & ADJUST ENGINE
GOVERNOR, 389cc ENGINE
TEST 41 – CHECK & ADJUST ENGINE
GOVERNOR, 410cc ENGINE
GOOD
CONFIGURATION “A”
REPLACE
ALTERNATOR
STOP
TESTING
RE-CHECK VOLTAGE AT
RECEPTACLE PANEL
REPLACE
CAPACITOR
GOOD
BAD
PART 2
SECTION 2.1
BRUSHLESS CAPACITOR TROUBLESHOOTING FLOWCHARTS
Page 23
Page 26
SECTION 2.2
GO TO PROBLEM 6GO TO PROBLEM 5GO TO PROBLEM 5GO TO PROBLEM 7
VOLTAGE &
FREQUENCY BOTH
HIGH OR LOW
FREQUENCY GOOD
VOLTAGE HIGH
ZERO VOLTAGE
ZERO FREQUENCY
FREQUENCY GOOD,
LOW OR RESIDUAL
VOLTAGE
TEST 1 - CHECK
NO LOAD VOLTAGE
& FREQUENCY
NO LOAD VOLTAGE &
FREQUENCY GOOD -
VOLTAGE/FREQUENCY
FALLS OFF UNDER LOAD
If Problem Involves AC Output
VERIFY ROTOR IS SPINNING,
GO TO PROBLEM 5
REPLACE
BRUSHES
STOP TESTING
BAD
BAD
BAD
GOOD
Problem 5 – Generator Produces Zero Voltage or Residual Voltage
TEST 2 – CHECK
MAIN CIRCUIT
BREAKER
RESET TO “ON”
OR REPLACE IF BAD
REPLACE COMPONENT
AS NEEDED
TEST 3 – CHECK
CONTINUITY OF
RECEPTACLE PANEL
TEST 5 – CHECK
BRUSHES
REPLACE
ALTERNATOR
REPLACE AUTOMATIC
VOLTAGE REGULATOR
TEST 12 – ADJUST
AUTOMATIC VOLTAGE
REGULATOR
ON
GOOD
GOOD
STOP TESTING
GOOD
BAD
RE-CHECK VOLTAGE
AT RECEPTACLE
PANEL
BRUSHED EXCITATION TROUBLESHOOTING FLOWCHARTS
PART 2
AC GENERATORS
The GP series portable generators currently use
three different types of alternators. Two of the alternators are brushless capacitor type with different style of
capacitors (Configuration “A” and “B”). The third utilizes a voltage regulator and a brushed excitation system (Configuration “C”). To help with troubleshooting,
two sets of flow charts have been created for these
different styles of alternators.
Identify the configuration of the alternator being serviced using Sections 1.3 and 1.4 of this manual and
proceed to the appropriate flowchart section.
Configuration “A” – Brushless Capacitor, use Section 2.1
Configuration “B” – Brushless Capacitor, use Section 2.1
Configuration “C” – Brushed Excitation, use Section 2.2
Page 24
Page 27
AC GENERATORS
TEST 40 – CHECK & ADJUST ENGINE
GOVERNOR, 389cc ENGINE
TEST 41 – CHECK & ADJUST ENGINE
GOVERNOR, 410cc ENGINE
GO TO
PROBLEM 5
GO TO
PROBLEM 7
GO TO PROBLEM 5,
TEST 12 – ADJUST
VOLTAGE
REGULATOR
Problem 6 – V
oltage & Frequency Are Both High or Low
FREQUENCY GOOD,
LOW OR RESIDUAL
VOLTAGE
FREQUENCY IS GOOD
BUT NO-LOAD
VOLTAGE IS HIGH
NO-LOAD FREQUENCY &
VOLTAGE GOOD BUT THEY
DROOP TO MUCH WHEN
LOAD IS APPLIED
GO TO PROBLEM 12
GO TO PROBLEM 23
REDUCE LOAD
END TEST
Problem 7 – Excessive Voltage/Frequency Droop When Load is Applied
TEST 10 – CHECK
LOAD VOLTAGE &
FREQUENCY
TEST 11 – CHECK
LOAD WATTS &
AMPERAGE
GOOD
GOODGOOD
BAD
OVERLOADED
NOT OVERLOADED
TEST 41 – CHECK
& ADJUST
ENGINE
GOVERNOR,
410cc ENGINE
TEST 40 – CHECK
& ADJUST
ENGINE
GOVERNOR,
389cc ENGINE
BAD
STOP
TESTS
Problem 8 – Generator Produces High Voltage at No-Load
FREQUENCY AND
VOLTAGE O.K.
FREQUENCY O.K.,
BUT VOLTAGE IS
STILL HIGH
TEST 40 – CHECK & ADJUST ENGINE
GOVERNOR, 389cc ENGINE
TEST 41 – CHECK & ADJUST ENGINE
GOVERNOR, 410cc ENGINE
TEST 1 – CHECK
NO-LOAD VOLTAGE
AND FREQUENCY
FREQUENCY O.K.,
BUT VOLTAGE HIGH
FREQUENCY
HIGH
REPLACE AUTOMATIC
VOLTAGE REGULATOR
TEST 12 – ADJUST
AUTOMATIC VOLTAGE
REGULATOR
GOOD
RE-CHECK VOLTAGE
AT RECEPTACLE
PANEL
REPLACE
ALTERNATOR
PART 2
SECTION 2.4
BRUSHED EXCITATION TROUBLESHOOTING FLOWCHARTS
Page 25
Page 28
240
00.01
C.B.
20/30A
SECTION 2.3
AC DIAGNOSTIC TESTS
PART 2
AC GENERATORS
INTRODUCTION
The “Diagnostic Tests” in this chapter may be perfor med in conjunction with the “Flow Charts” of
Section 2.1 and Section 2.2. Test numbers in this
chapter correspond to the numbered tests in the
“Flow Charts”. It may be helpful to read Section 1.2,
“Measuring Electricity.”
NOTE: Test procedures in this Manual are not necessarily the only acceptable methods for diagnosing the condition of components and circuits. All
possible methods that might be used for system
diagnosis have not been evaluated. If any diagnostic method is used other than the method presented in this Manual, the technician must ensure
that neither his personal safety nor the product's
safety will be endangered by the procedure or
method that has been selected.
For visual pictures of the different configurations
of the stators and the wire numbers associated
with different components please see Figures 4
and 5 in Section 1.3, and Figure 3 in Section 1.4.
TEST 1 – CHECK NO-LOAD VOLTAGE AND
FREQUENCY
PROCEDURE:
1. Disconnect or turn OFF all electrical loads connected to
the generator.
TEST 2 – CHECK CIRCUIT BREAKER
PROCEDURE:
The generator has circuit breakers located on the
control panel. If outlets are not receiving power, make
sure the breakers are set to ON or “Closed”.
If a breaker is suspected to have failed, it can be
tested as follows:
1. Set a VOM to measure resistance.
2. With the generator shut down, disconnect all wires from the
suspected circuit breaker terminals to prevent interaction.
3. With the generator shut down, connect one meter test
lead to a one terminal of the breaker and the other
meter test lead to the other terminal. See Figure 2.
4. Set the breaker to its ON or “Closed” position. The meter
should read CONTINUITY.
5. Set the breaker to its OFF or “Open” position and the
meter should indicate INFINITY.
2. Set a VOM to measure AC voltage.
3. Reset all circuit breakers to the on position.
4. Start the engine and let it stabilize and warm up.
Figure 1. VOM Test Leads Connected to a 240 VAC
receptacle
6. Place the meter test leads into an outlet. See Figure 1.
7. Read the AC voltage.
8. Connect a AC frequency meter as described in Step 6.
9. Read the AC frequency.
RESULTS:
No Load Voltage
223.2 – 256.8 VAC62.5 – 62.0 HZ
Refer back to Flow Chart.
Page 26
No Load Frequency
Figure 2. 20/30 Amp Breaker Test Points
RESULTS:
1. If the circuit breaker tests good, refer back to the flow
chart.
2. If the breaker tests bad, it should be replaced.
TEST 3 – CHECK CONTINUITY OF
RECEPTACLE PANEL
DISCUSSION:
Continuity of the receptacle panel is important
because it reflects that the receptacle has continuity
through the wiring and is physically connected to the
stator. Most stator winding values are between 0.01
and 0.02 Ohms of resistance. If a higher than normal
ohm reading is shown then a poor connection could
be the problem preventing that receptacle from receiving power.
PROCEDURE:
1. Set a VOM to measure Resistance.
Page 29
AC GENERATORS
0.01 Ohms
12 AWG12 AWG
MOMENTARY PUSHBUTTON ON/OFF SWITCH
SINGLE POLE SWITCH ON LIVE SIDE
DO NOT SUBSTITUTE ANY OTHER DEVICE
4 ft.
CRIMP ON STANDARD
FEMALE BLADE
CONNECTORS
STANDARD
MALE PLUG
PART 2
SECTION 2.3
AC DIAGNOSTIC TESTS
2. Connect a VOM as shown in Figure 3 to each receptacle
on the unit.
Note: Only one outlet on each receptacle needs to
be tested.
RESULTS:
1. If any other reading than continuity was measured further troubleshooting will need to be done to determine if
it is the receptacle or the wiring.
2. If receptacles test good, refer back to flow chart.
TEST 4 – FIELD FLASH ALTERNATOR
(CONFIGURATION “A” ONLY)
DISCUSSION:
The alternator utilizes residual magnetism within the
windings to charge the capacitor. If the generator has
been sitting for a long period of time with no activity
the residual magnetism could be lost within the rotor.
Field flashing the rotor while connected in parallel with
the capacitor will force a charge of electricity through
the DPE winding. The voltage that is induced into the
rotor will in turn charge the rotor with enough residual
magnetism that it will be able to charge the capacitor
during normal operation.
Warning:
performing this test.
*
PROCEDURE:
1. Construct an energizing cord that is similar to that shown
in Figure 4 and connect it as shown in Figure 5 on the
next page.
2. Set the START-RUN-STOP switch to the OFF position.
Warning:
more than 1 second at a time.
*
3. Momentarily turn on the energizing cord (one second).
Please keep safety in mind while
Do NOT energize the capacitor for
Figure 3. Checking Continuity of Receptacles
Figure 4. Construction of Energizing Cord
4. Disconnect the energizing cord from the capacitor.
5.
If the field flash was successful, the generator should now
be producing approximately 240 VAC at the main circuit
breaker of the generator when the START-RUN-STOP is
set to the START position.
Page 27
Page 30
+
–
SECTION 2.3
CAPACITOR
DEPRESS SWITCH FOR
ONE SECOND
PLUG ENERGIZING CORD
INTO AC OUTLET
CAPICITOR REMAINS CONNECTED
TO GENERATOR
Danger: The capacitor may need to be
discharged before testing. A capacitor can
be discharged by crossing the terminals
with a metal insulated screw driver.
Danger: Use proper protective equipment
when dealing with a capacitor that has
exploded.
AC DIAGNOSTIC TESTS
PART 2
AC GENERATORS
Figure 5. Connecting Energizing Cord
Warning:
than two times in sequence. If the unit has
*
not produced power after two attempts, other
issues exist and need to be addressed.
RESULTS:
Do not field flash alternator more
3. Inspect the rotor slip rings. If they appear dull or tarnished, they may be polished with fine sandpaper. DO
NOT USE METALLIC GRIT TO POLISH SLIP RINGS.
1. Refer back to flow chart.
TEST 5 – CHECK BRUSHES
DISCUSSION:
The function of the brushes and slip rings is to pro-
vide passage of excitation current from stationary
components to the rotating rotor. Brushes are made
of a special long lasting material and seldom wear
out or fail. However, slip rings can develop a tarnish or
film that can inhibit or offer a resistance to the flow of
electricity. Such a non-conducting film usually develops during non-operating periods. Broken or disconnected wiring can also cause loss of excitation current
to the rotor.
PROCEDURE:
1. See Figure 6. Carefully inspect brush wires. Make sure
2. Disconnect the red and white wire from the brush assem-
they are properly and securely connected.
bly. Remove the brush assembly from the bearing carrier. Inspect the brushes for excessive wear, or damage.
Figure 6. Brushes and Slip Rings
RESULTS:
1. Repair, replace or reconnect wires as necessary.
2. Replace any damaged slip rings or brush holder.
3. Clean and polish slip rings as required.
4. If brush assembly and slip rings look good proceed to
Step 5.
Page 28
Page 31
AC GENERATORS
SET TO READ
CAPACITANCE
59.0 µf
SET TO READ
CAPACITANCE
28.0 µf
CAPACITOR 28µf
PART 2
TEST 6 – CHECK CAPACITOR
DISCUSSION:
The brushless rotor system relies on the charging and
discharging of a capacitor to induce voltage into the
rotor and also to regulate voltage once 240 VAC is
achieved. If the capacitor fails, only residual magnetism of the rotor will be measured at the Main Breaker.
Warning: The capacitor may need to be dis-
charged before testing. A capacitor can be
*
discharged by crossing the terminals with a
metal insulated screw driver.
Warning: Use proper protective equipment
when dealing with a capacitor that has
*
exploded.
PROCEDURE:
1. Consult the owner’s manual of the meter being used for
directions on measuring capacitance. Figures 7 and 8
show a typical meter and how to check capacitance.
SECTION 2.3
AC DIAGNOSTIC TESTS
2. Connect the meter leads directly across the terminals of
the capacitor. The rated µf (micro farad) of the capacitor
is marked on the side of the canister.
3. The meter should display the correct µf reading ± 5µf.
If anything other than the indicated rating is displayed,
replace the capacitor.
RESULTS:
1. Refer back to flow chart
2. Common observations can be made by visually inspecting the capacitor.
a. A capacitor that has gone bad can have a ten-
dency to explode. Use caution when dealing
with an exploded capacitor, the gel from inside
a capacitor can cause skin irritation.
b. A capacitor is defective if the terminal connec-
c. A capacitor is defective if it wobbles while sitting
d. If any of the above observations are observed,
tions are loose on the canister.
on a flat surface.
replace the capacitor.
Figure 7. Capacitor Test Points
(Alternator Configuration “A”)
Figure 8. Capacitor Test Points
(Alternator Configuration “B”)
Page 29
Page 32
SECTION 2.3
AC DIAGNOSTIC TESTS
PART 2
AC GENERATORS
TEST 7 – TEST BRUSHLESS DPE WINDING
DISCUSSION:
A DPE or Displaced Phase Excitation winding is used
to charge a capacitor, which discharges and charges,
releasing a voltage that is induced into the rotor. If
the DPE winding fails, only residual magnetism of the
rotor will be measured at the Main Breaker.
Note: The resistance of stator windings is very
low. Some meters will not read such a low resistance, and will simply indicate CONTINUITY.
Recommended is a high quality, digital type meter
capable of reading very low resistances.
Danger: The capacitor may need to be discharged before testing. A capacitor can be
*
discharged by crossing the terminals with
a metal insulated screw driver.
PROCEDURE:
1. Disconnect Wire 2 and Wire 6 from the capacitor.
2. Set VOM to measure resistance.
3. Connect one meter lead to Wire 2 and connect the other
meter lead to Wire 6.
a. Reading should be approximately 0.97 and 1.13
Ohms.
4. Connect one meter lead to Wire 2 and connect the other
meter lead to a clean frame ground, INFINITY should be
measured.
5. Isolate the stator wire so that the stator is disconnected
from the receptacle panel and the capacitor.
Note: Isolate all main stator leads before proceeding.
6. Connect one meter lead to Wire 2 and connect the other
meter lead to Wire 11. INFINITY should be measured.
TEST 8 – TEST BRUSHLESS STATOR WINDINGS
DISCUSSION:
The brushless stator has three internal windings,
two main power windings and a DPE winding. This
test will ensure that there are no shorts between the
power windings or shorts to ground.
A VOM meter can be used to test the stator windings
for the following faults:
• Anopencircuitcondition
• A“short-to-ground”condition
• Ashortcircuitbetweenwindings
Note: The resistance of stator windings is very
low. Some meters will not read such a low resistance, and will simply indicate CONTINUITY.
Recommended is a high quality, digital type meter
capable of reading very low resistances.
Note: Refer to Figure 4 in Section 1.3 for illustration of Stator Configuration “A”. Some wire numbers will not be marked on the stator.
PROCEDURE:
1. Disconnect Wires 11, 22, 33, 44 from the receptacle
panel so that the stator is isolated.
2. Make sure all of the disconnected leads are isolated
from each other and are not touching the frame during
the test.
3. Set a VOM to measure resistance.
4. Connect one test lead to Stator Lead 11. Connect the
other test lead to Stator Lead 22. Stator resistance
should be between 0.12-0.14 Ohms.
5. Connect one test lead to Stator Lead 33. Connect the
other test lead to Stator Lead 44. Stator resistance
should be between 0.12-0.14 Ohms.
7. Repeat Step 6 using Wire 2 and Wire 44.INFINITY
should be measured.
RESULTS:
1. Stator winding resistance values is a test of winding continuity and resistance. If a very high resistance or INFINITY
is indicated, the winding is open or partially open.
2. Testing for a “grounded” condition: Any resistance reading indicates that the winding is grounded.
3. Testing for a “shorted” condition: Any resistance reading
indicates that the winding is shorted.
4. If stator tests good and wire continuity tests good, refer
back to flow chart.
Page 30
TEST WINDINGS FOR A SHORT TO GROUND:
1. Make sure all leads are isolated from each other and are
not touching the frame.
2. Connect one test lead to a clean frame ground. Connect
the other test lead to Stator Lead Wire 11.
a. The meter should read INFINITY.
b. Any reading other than INFINITY indicates a
“short to ground” condition.
3. Repeat Step 2 using Stator Lead 44
TEST FOR A SHORT CIRCUIT BETWEEN WINDINGS:
1. Connect one test lead to Stator Lead 11. Connect the
other test lead to Stator Lead 33.
a. The meter should read INFINITY.
b. Any reading other that INFINITY indicates a
short between windings.
Page 33
AC GENERATORS
240
PART 2
SECTION 2.3
AC DIAGNOSTIC TESTS
TEST 9 – TEST BRUSHED STATOR WINDINGS
DISCUSSION:
Most brushed stators have three main windings that
are needed to produce voltage. The alternator has
two main power windings that supply power to the
load and a DPE winding to provide excitation voltage
to the rotor. It is important that these windings remain
isolated from ground or the chassis of the alternator.
PROCEDURE:
1. Isolate all stator wires from the control panel and the
voltage regulator.
2. Set a VOM to measure resistance.
3. Refer to Configuration “C” in Section 1.4 for proper test
points for checking the stator. Every connection needs to
be checked coming out of the stator for a short to ground.
RESULTS:
1. If any wire has a direct short to ground or to the chassis
of the alternator replace the alternator assembly.
2. If all wires test good for a short to ground, refer back to
flow chart.
RESULTS:
1. If the unit is overloaded, reduce the load.
2. If load is within limits, but frequency and voltage still drop
excessively, refer back to Flow Chart.
Overloading a generator in excess of its rated wattage
capacity can result in damage to the generator and to
connected electrical devices. Observe the following to
prevent overloading the unit:
Test 45 – Check Oil Level Switch .....................51
Test 46 – Check Oil Pressure Switch ...............51
Test 49 – Test Recoil Function .........................52
Test 50 – Test Engine Function ........................52
Page 33
Page 36
SECTION 3.1
NOTHING
FOUND
FIX BAD COMPONENT
BAD
VISUALLY INSPECT FOR OBSTRUCTIONS
THAT WOULD CAUSE BINDING OF THE
RECOIL ONCE INSTALLED
AN INTERNAL ENGINE FAILURE HAS OCCURED.
VISUALLY INSPECT EXTERNAL
COMPONENTS FOR A FAILURE
THAT WOULD CAUSE THE
ENGINE TO BE SIEZED
REPLACE
BAD
BAD
GOODGOOD
Problem 10 – Recoil Cord Will Not Pull
TEST 49 – TEST
RECOIL
FUNCTION
TEST 50 –
TEST ENGINE
FUNCTION
REPAIR
OR REPLACE
REPAIR
OR REPLACE
BAD
BAD
GOODGOOD
GOOD
GOOD
TEST 26 –
CHECK
SPARK
CHECK FUEL
SUPPLY
CHECK CHOKE
POSITION AND
OPERATION
TEST 27 –
CHECK
SPARK PLUG
TEST 29 –
CHECK
CARBURETION
TEST 33 –
CHECK VALVE
ADJUSTMENT
CHECK FLYWHEEL KEY
TEST 36 – CHECK
ENGINE / CYLINDER
LEAK DOWN TEST /
COMPRESSION TEST
REPLACE SPARK PLUG
PUSH IN AFTER
STARTING
REPLENISH
FUEL
SUPPLY
REPLACE
REPLACE
MAGNETO
REPAIR OR REPLACE AS NECESSARY
REFER TO ENGINE SERVICE MANUAL
GOOD
GOOD
GOOD
GOOD
GOOD
ENGINE MISS
IS APPARENT
LOW FUEL
BAD
BAD
Problem 11 – Engine Starts Hard and Runs Rough
ADJUST VALVES
AND RETEST
BAD
BAD
TEST 40 – CHECK
AND ADJUST
GOVERNOR
TEST 38 – CHECK
FLYWHEEL
389/206/163cc TROUBLESHOOTING FLOW CHARTS
PART 3
ENGINE TROUBLESHOOTING
There are 4 different types of engines on the GP Series
generators: 410cc, 389cc, 206cc, 163cc. Section 3 is
divided into difference subsections that provide engine
troubleshooting for each type of engine. It is imperative
to identify what type of engine is used in order to effectively troubleshoot the problem.
The Specifications section at the front of this manual
provides details about engine displacement for the various GP Series generators.
389cc, 206cc and 163cc Engines, use Section 3.1
410cc Engine, use Section 3.2
Page 34
Page 37
ENGINE TROUBLESHOOTING
ADJUST AND
RE-TEST
REPAIR
OR REPLACE
OFF
TURN
ON
GOOD
GOOD
SPARK
GOOD
GOOD
GOOD
GOOD
TEST 26 –
CHECK
SPARK
CHECK
FUEL
SUPPLY
CHECK FUEL
SHUTOFF
VALVE
TEST 27 –
CHECK SPARK
PLUG
TEST 38 –
CHECK
FLYWHEEL
TEST 29 –
CHECK
CARBURETION
TEST 33 –
CHECK VALVE
ADJUSTMENT
CHECK
FLYWHEEL
KEY
TEST 36 – CHECK ENGINE /
CYLINDER LEAK DOWN TEST /
COMPRESSION TEST
REPLENISH
FUEL
SUPPLY
REPLACE
FLYWHEEL
REPAIR OR REPLACE AS NECESSARY
REFER TO ENGINE SERVICE MANUAL
BAD
BAD
REPLACE
MAGNETO
GOOD
Problem 12 – Engine Turns Over But Will Not Start
TEST 39 – REMOVE
WIRE 18 /
SHUTDOWN LEAD
NO
SPARK
GOOD
BAD
BAD
BAD
BAD
REPLACE SWITCH
BAD
CHECK ENGINE
OIL LEVEL
TEST 45 –
CHECK OIL
LEVEL SWITCH
TEST 24 – TEST
OFF-ON SWITCH
REPLACE SWITCH
REPLENISH
OIL
REPLACE LOW OIL ALARM
GOOD
GOOD
OIL LEVEL O.K.
OIL LEVEL LOW
BAD
PART 3
389/206/163cc TROUBLESHOOTING FLOW CHARTS
SECTION 3.1
Page 35
Page 38
SECTION 3.1
BAD
REPLACE
BAD
BAD
REPLACE
REPLACE MAGNETO
REPAIR OR
REPLACE
GOOD
GOOD
BAD
BAD - ENGINE
MISS APPARENT
GOOD
TEST 30 –
CHOKE TEST
TEST 26 –
CHECK
IGNTION
SPARK
TEST 27 – CHECK
SPARK PLUG
TEST 38 –
CHECK
FLYWHEEL
*Acceptable running limits for the engine are between 59-61 Hertz.
ADJUST / RE-TEST
TEST 33 –
CHECK VALVE
ADJUSTMENT
Problem 13 – Engine “Hunts” / Erratic Idle
NO
SURGING
STILL
SURGING
TEST 29 –
CHECK
CARBURETION
GOOD
TEST 40 –CHECK
AND ADJUST
GOVERNOR
389/206/163ccTROUBLESHOOTING FLOW CHARTS
PART 3
ENGINE TROUBLESHOOTING
Page 36
Page 39
ENGINE TROUBLESHOOTING
RECHARGE OR REPLACE BATTERY
– CLEAN, REPAIR OR REPLACE
BAD CABLE(S)
BAD
REPLACE
BAD
GOOD
NO VOLTAGE
MEASURED
BAD
12 VDC
MEASURED
REPLACE STARTER
MOTOR IF DEFECTIVE
GOOD
CHECK FOR MECHANICAL BINDING
OF THE ENGINE OR ROTOR
Problem 20 – Engine Will Not Crank
TEST 21 – CHECK
BATTERY
& CABLES
TEST 23 – CHECK
START-RUN-STOP
SWITCH
TEST 25 – CHECK
STARTER MOTOR
TEST 22 – CHECK
VOLTAGE AT
STARTER
CONTACTOR
NOTHING
FOUND
FIX BAD COMPONENT
BAD
VISUALLY INSPECT FOR OBSTRUCTIONS
THAT WOULD CAUSE BINDING OF THE
RECOIL ONCE INSTALLED
AN INTERNAL ENGINE FAILURE HAS OCCURED.
POSSIBLE FAILURE COULD BE THE RESULT OF
A COMPRESSION RELEASE FAILURE. CONSULT
ENGINE SERVICE MANUAL P/N 0C1103A FOR
FURTHER ENGINE SERVICE INFORMATION.
VISUALLY INSPECT EXTERNAL
COMPONENTS FOR A FAILURE
THAT WOULD CAUSE THE
ENGINE TO BE SIEZED
REPLACE
BAD
BAD
GOODGOOD
Problem 21 – Recoil Cord Will Not Pull (If So Equipped)
TEST 50 –
TEST ENGINE
FUNCTION
TEST 49 – TEST
RECOIL
FUNCTION
PART 3
SECTION 3.2
410cc TROUBLESHOOTING FLOW CHARTS
Page 37
Page 40
SECTION 3.2
BAD
PULL OUT
ADJUST AND
RE-TEST
REPAIR
OR
REPLACE
REPLACE
REPLACE
OFF
TURN
ON
GOOD
GOOD
SPARK
GOOD
GOOD
GOOD
GOOD
GOOD
TEST 26 –
CHECK
SPARK
CHECK
FUEL
SUPPLY
CHECK FUEL
SHUTOFF
VALVE
PULL CHOKE
FULL OUT
TEST 23 – TEST
START-RUN-STOP
SWITCH
TEST 27 –
CHECK SPARK
PLUG
TEST 29 –
CHECK
CARBURETION
TEST 33 –
CHECK VALVE
ADJUSTMENT
TEST 36 – CHECK ENGINE /
CYLINDER LEAK DOWN TEST /
COMPRESSION TEST
REPLENISH
FUEL
SUPPLY
REPAIR OR REPLACE AS NECESSARY
REFER TO ENGINE SERVICE MANUAL
P/N 0C1103A FOR FURTHER ENGINE
SERVICE INFORMATION
BAD
Problem 22 – Engine Cranks But Will Not Start
TEST 39 – REMOVE
WIRE 18 /
SHUTDOWN LEAD
FULL OUT
NO
SPARK
BAD
GOOD
BAD
BAD
BAD
BAD
REPLACE
REPLACE MAGNETO
GO TO
“PROBLEM 24”
GOOD
TEST 38 –
CHECK
FLYWHEEL
TEST 38 –
CHECK
FLYWHEEL KEY
410cc TROUBLESHOOTING FLOW CHARTS
PART 3
DC CONTROL
Page 38
Page 41
DC CONTROL
REPAIR
OR REPLACE
REPAIR
OR REPLACE
BAD
BAD
GOOD
GOOD
GOOD
TEST 26 –
CHECK
SPARK
CHECK FUEL
SUPPLY
CHECK CHOKE
POSITION AND
OPERATION
TEST 27 –
CHECK
SPARK PLUG
TEST 29 –
CHECK
CARBURETION
TEST 33 –
CHECK VALVE
ADJUSTMENT
CHECK FLYWHEEL KEY
TEST 36 – CHECK
ENGINE / CYLINDER
LEAK DOWN TEST /
COMPRESSION TEST
REPLACE SPARK PLUG
PUSH IN AFTER
STARTING
REPLENISH
FUEL
SUPPLY
REPAIR OR REPLACE AS NECESSARY
REFER TO ENGINE SERVICE MANUAL
P/N 0C1103A FOR FURTHER ENGINE
SERVICE INFORMATION
GOOD
GOOD
GOOD
GOOD
GOOD
ENGINE MISS
IS APPARENT
LOW FUEL
BAD
Problem 23 – Engine Starts Hard and Runs Rough
ADJUST VALVES
AND RETEST
BAD
BAD
TEST 41 – CHECK
AND ADJUST
GOVERNOR
BAD
REPLACE
REPLACE MAGNETO
GOOD
TEST 38 –
CHECK
FLYWHEEL
REPLACE SWITCH
REPLACE OIL
PRESSURE MODULE
BAD
TEST 46 – TEST OIL
PRESSURE SWITCH
TEST 23 – TEST
START-RUN-STOP
SWITCH
REPLACE SWITCH
REPLENISH
OIL
GOOD
GOOD
OIL LEVEL O.K.
OIL LEVEL LOW
BAD
Problem 24 – Engine Starts Then Shuts Down
CHECK ENGINE
OIL LEVEL
PART 3
SECTION 3.2
410cc TROUBLESHOOTING FLOW CHARTS
Page 39
Page 42
SECTION 3.2
BAD
BAD
REPLACE
REPAIR OR
REPLACE
GOOD
GOOD
BAD
BAD - ENGINE
MISS APPARENT
GOOD
TEST 30 –
CHOKE TEST
TEST 26 –
CHECK
SPARK
TEST 27 – CHECK
SPARK PLUG
*Acceptable running limits for the engine are between 59-62 Hertz.
ADJUST / RE-TEST
TEST 33 –
CHECK VALVE
ADJUSTMENT
Problem 26 – Engine “Hunts” / Erratic Idle
NO
SURGING
STILL
SURGING
TEST 29 –
CHECK
CARBURETION
GOOD
TEST 41 –CHECK
AND ADJUST
GOVERNOR
BAD
REPLACE
REPLACE MAGNETO
GOOD
TEST 38 –
CHECK
FLYWHEEL
REPLACE
BAD
REPLACE FUSE
BAD
REPLACE
BATTERY
CHARGER
Problem 25 – Battery Will Not Charge
CHECK CONNECTIONS
ON BATTERY CHARGE
SOCKET
GOODGOOD
TEST 20 –
CHECK 1.5
AMP FUSE
410cc TROUBLESHOOTING FLOW CHARTS
PART 3
ENGINE TROUBLESHOOTING
Page 40
Page 43
NOTES
Page 41
Page 44
1A1B1
WHT
STOPRUNSTART
0 GD13A
TO MAGNETO
GROUND TO
STARTER CONTACTOR
SECTION 3.3
DIAGNOSTIC TESTS
PART 3
DC CONTROL
TEST 20 – CHECK 1.5 AMP FUSE
Figure 1. A Typical 1.5 Amp Fuse
DISCUSSION:
The fuse protects the wiring and the battery charger
from a short circuit.
PROCEDURE:
Push in on fuse holder cap and turn counterclockwise.
Then, remove the cap with fuse. Inspect the fuse.
RESULTS:
If the fuse element has melted open, replace the fuse
with an identical size fuse. If fuse is good, refer back
to flow chart.
TEST 21 – CHECK BATTERY & CABLES
PROCEDURE:
Inspect the battery cables and battery posts or termi-
nals for corrosion or tightness. Measure the voltage at
the terminal of the Starter Contactor and verify 11-12
volts DC is available to the generator during cranking.
If voltage is below 11 volts DC, measure at the battery
terminals during cranking. If battery voltage is below
11 volts DC, recharge/replace battery. If battery or
cables are still suspected, connect an alternate battery and cables to the generator and retest.
TEST 22 – CHECK VOLTAGE AT STARTER
CONTACTOR (SC)
PROCEDURE:
1. Set voltmeter to measure DC voltage.
2. Disconnect Wire 16 from the Starter Contactor located
on the Starter motor.
3. Connect the positive meter test lead to Wire 16 previously removed. Connect the negative meter test lead to
frame Ground.
4. Place the START-RUN-STOP Switch to START. 12 VDC
should be measured.
5. Reconnect Wire 16 to the Starter Motor.
RESULTS:
Refer back to flow chart.
TEST 23 – CHECK START-RUN-STOP SWITCH
DISCUSSION:
The START-RUN-STOP switch utilizes ground potential
to start and shutdown the engine. When the switch is
actuated to the START position a ground is applied to
the starter contactor where positive 12VDC is already
available allowing the engine to crank. Once the ground
is removed by putting the switch in the RUN position it disengages the starter allowing the engine to
operate normally. When the switch is actuated to the
STOP position a ground is applied to the magneto coils
grounding them out and inhibiting spark from occurring.
RESULTS:
1. Clean battery posts and cables as necessary. Make sure
battery cables are tight.
2. Recharge the battery, if necessary.
3. Replace the battery, if necessary.
4. If battery is good, but engine will not crank, refer back to
Flow Charts.
Page 42
Figure 2. START-RUN-STOP Switch
PROCEDURE:
1. Set a voltmeter to measure resistance.
2. Remove all wires from the START-RUN-STOP Switch
(SW1).
Page 45
DC CONTROL
OFF
ON
OIL LEVEL ALARM
OFF-ON SWITCH
TO FRAME GROUND
TO FRAME GROUND
FROM OIL LEVEL SWITCH
TEST POINT A
MAGNETO
SHUTDOWN HARNESS
WIRE 18
00.01
PART 3
SECTION 3.3
DIAGNOSTIC TESTS
3. Connect one meter lead to Terminal 2 and connect the
other meter lead to Terminal 1. Actuate switch to the
START position. CONTINUITY should be measured.
4. Actuate switch to the STOP position. INFINITY should be
measured.
5. Keep one meter lead on Terminal 2 and connect the
other meter lead to Terminal 3. Actuate switch to the
STOP position. CONTINUITY should be measured.
6. Actuate switch to the START position. INFINITY should
be measured.
7. Connect one meter test lead to disconnected Wire 0
from Terminal 2 and connect the other meter test lead to
the positive post of the battery, 12 VDC should be measured. If voltage is not measured, repair or replace Wire
13A between the starter contactor and the START-RUNSTOP switch.
8. Reconnect all wires to the switch.
RESULTS:
1. If anything but the readings above were measured
replace the START-RUN-STOP switch.
2. Refer back to flow chart.
TEST 24 – TEST OFF-ON SWITCH
DISCUSSION:
The OFF-ON switch applies a ground to the shutdown
harness (Wire 18). By applying a ground to the harness it grounds out the magneto and inhibits spark.
PROCEDURE:
1. Disconnect Point A from the switch harness (see Figure 3).
2. Connect one meter lead to the female side of the connector and connect other meter test lead to a clean
frame ground.
3. Actuate the switch back and for th between ON and
OFF. CONTINUITY should only be measure in the OFF
position.
RESULTS:
1. If switch failed Step 3, replace the OFF-ON switch.
2. If OFF-ON switch is good, refer back to flow chart.
TEST 25 – CHECK STARTER MOTOR
The following conditions can affect starter motor performance:
1. A binding or seizing condition in the Starter Motor bearings.
2. A shorted, open or grounded armature.
a. Shorted, armature (wire insulation worn and
wires touching one another). Will be indicated
by low or no RPM.
b. Open armature (wire broken) will be indicated
by low or no RPM and excessive current draw.
c. Grounded armature (wire insulation worn and wire
touching armature lamination or shaft). Will be
indicated by excessive current draw or no RPM.
3. A defective Starter Motor switch.
4. Broken, damaged or weak magnets.
5. Starter drive dirty or binding.
Figure 3. OFF-ON Switch Test Points (389cc Engine)
Page 43
Page 46
STARTER
PINION
SECTION 3.3
DIAGNOSTIC TESTS
PROCEDURE:
The battery should have been checked prior to this
test and should be fully charged.
Set a voltmeter to measure DC voltage (12 VDC).
Connect the meter positive (+) test lead to the Starter
Contactor stud which has the small jumper wire connected to the Starter. Connect the common (-) test
lead to the Starter Motor frame.
Set the Star t-Stop Switch to its START position and
observe the meter. Meter should Indicate battery voltage,
Starter Motor should operate and engine should crank.
RESULTS:
1. If battery voltage is indicated on the meter but Starter
Motor did not operate, remove and bench test the
Starter Motor (see following test).
2. If battery voltage was indicated and the Starter Motor
tried to engage (pinion engaged), but engine did not
crank, check for mechanical binding of the engine or
rotor.
NOTE: If a starting problem is encountered, the
engine itself should be thoroughly checked to
eliminate it as the cause of starting difficulty. It is
a good practice to check the engine for freedom
of rotation by removing the spark plugs and turning the crankshaft over slowly by hand, to be sure
it rotates freely.
PART 3
Figure 5. Check Pinion Gear Operation
TOOLS FOR STARTER PERFORMANCE TEST:
The following equipment may be used to complete a
MEASURING CURRENT:
To read the current flow, in AMPERES, a clamp-on
ammeter may be used. This type of meter indicates
current flow through a conductor by measuring the
strength of the magnetic field around that conductor.
DC CONTROL
WARNING!: DO NOT ROTATE ENGINE WITH
ELECTRIC STARTER WITH SPARK PLUGS
*
REMOVED. ARCING AT THE SPARK PLUG
ENDS MAY IGNITE THE GASOLINE VAPOR
EXITING THE SPARK PLUG HOLE.
Figure 4. Starter Motor (SM)
CHECKING THE PINION:
When the Starter Motor is activated, the pinion gear
should move and engage the flywheel ring gear. If the
pinion does not move normally, inspect the pinion for
binding or sticking.
Figure 6. Clamp-On Ammeter
TACHOMETER:
A tachometer is available from your Generac Power
Systems source of supply. Order as P/N 042223. The
tachometer measures from 800 to 50,000 RPM (see
Figure 7).
Page 44
Page 47
METAL STOCK
1/4" THICK STEEL
12"
1.0"
4"
2"
2.625"
3.5"
0.5"
0.5"
DRILL TWO HOLES — 1/2"
FOR STARTER
MOUNTING BRACKET
DRILL TWO HOLES — 1/2"
FOR MOUNTING TACHOMETER
TAP FOR 1/4-20 NC SCREWS
STARTER
CONTACTOR
STARTER
MOTOR
TA CHOMETER
12 VOLT
BATTERY
CLAMP ON
AMP METER
VISE
DC CONTROL
Figure 7. Tachometer
PART 3
SECTION 3.3
DIAGNOSTIC TESTS
Figure 8. Test Bracket Dimensions
TEST BRACKET:
A starter motor test bracket may be made as shown in
Figure 8.
REMOVE STARTER MOTOR:
It is recommended that the Starter Motor be removed
from the engine when testing Starter Motor performance. Assemble starter to test bracket and clamp
test bracket in vise (Figure 9).
TESTING STARTER MOTOR:
1. A fully charged 12 volt battery is required.
2. Connect jumper cables and clamp-on ammeter as
shown in Figure 9.
3. With the Starter Motor activated (jump the terminal on the
Starter Contactor to battery voltage), note the reading on
the clamp-on ammeter and on the tachometer (rpm).
Figure 9. Testing Starter Motor Performance
Note: Take the reading after the ammeter and
tachometer are stabilized , approximately 2-4
seconds.
4. A starter motor in good condition will be within the following specifications:
Minimum rpm 4500
Maximum Amps 50
Note: Nominal amp draw of starter in generator is
60 amps.
TEST 25 – CHECK IGNITION SPARK
PROCEDURE:
A commercially available spark tester may be used
to test the engine ignition system. One can also be
purchased from Generac Power Systems (Part No.
0C5969).
1. Disconnect the spark plug lead from a spark plug.
2. Attach the high tension lead to the spark tester terminal.
3. Ground the spark tester clamp by attaching to the cylinder head (see Figure 10).
Page 45
Page 48
SPARK TESTER CLAMP
GROUNDED TO
CYLINDER HEAD
SPARK TESTER
SPARK PLUG
BOOT
SPARK TESTER CLAMP
CONNECTED TO
SPARK PLUG
SPARK TESTER
SPARK PLUG
BOOT
NORMALMISFIRES
PRE-IGNITIONDETONATION
SECTION 3.3
DIAGNOSTIC TESTS
Figure 10. Testing Ignition System
PART 3
DC CONTROL
Figure 12. Setting Spark Plug Gap
Figure 11. Checking Engine Miss
4. Crank the engine rapidly. Engine must be cranking at
350 rpm or more. If spark jumps the tester gap, you may
assume the ignition system is working properly. Repeat
on remaining cylinder spark plug.
5. If spark jumps the tester gap intermittently, the problem
may be in the Ignition Magneto.
RESULTS:
Refer back to the Flow Chart
PROCEDURE:
Remove spark plugs. Clean with a commercial solvent.
DO NOT BLAST CLEAN SPARK PLUGS. Replace
spark plugs if badly fouled, if ceramic is cracked, or
if badly worn or damaged. Refer to specifications in
the front of this manual for proper replacement spark
plugs and spark plug gaps.
Page 46
TEST 26 – CHECK SPARK PLUGS
Figure 13. Spark Plug Conditions
RESULTS:
1. Clean and regap or replace sparks plug as necessary.
2. Refer back to the Flow Chart.
TEST 29 – CHECK CARBURETION
PROCEDURE:
Before making a carburetion check, be sure the fuel sup-
ply tank has an ample supply of fresh, clean gasoline.
Check that all shutoff valves are open and fuel flows
freely through the fuel line.
Make sure the choke operates properly.
If the engine will not start, remove and inspect the spark
plug. If the spark plug is wet, look for the following:
• Overchoking.
• Excessivelyrichfuelmixture.
Page 49
FEELER GAUGE
ALLEN WRENCH
DC CONTROL
PART 3
SECTION 3.3
DIAGNOSTIC TESTS
• Waterinfuel.
• Intakevalvestuckopen.
• Needle/floatstuckopen.
If the spark plug is dry look for the following:
• Leakingcarburetormountinggaskets.
• Intakevalvestuckclosed.
• Inoperativefuelpump.
• Pluggedfuelfilter(s).
• Varnishedcarburetor
If the engine starts hard or will not start, look for the
following:
• Startingunderload.Makesureallloadsaredisconnected or turned off before attempting to crank and
start the engine.
• Checkthatthechokeisworkingproperly.
1. Remove fuel line at carburetor and ensure that there is
an adequate amount of fuel entering the carburetor.
2. Remove the float bowl and check to see if there is any
foreign matter in bottom of carburetor bowl.
3. The float is plastic and can be removed for access to the
needle so it can be cleaned.
TEST 33 – CHECK VALVE ADJUSTMENT
ADJUSTING VALVE CLEARANCE:
Improperly adjusted valves can cause various engine
related problems including, but not limited to, hard starting,
rough running and lack of power.
Adjust valve clearance with the engine at room temperature. The piston should be at top dead center
(TDC) of its compression stroke (both valves closed).
An alternative method is to turn the engine over and
position the intake valve fully open (intake valve spring
compressed) and adjust the exhaust valve clearance.
Turn the engine over and position the exhaust valve
fully open (exhaust valve spring compressed) and
adjust the intake valve clearance.
Correct valve clearance is given below.
EngineIntake ValveExhaust Valve
189/206cc
389cc
410cc
0.0039 inch0.0059 inch
0.006 ±0.0008 inch0.006 ±0.0008 inch
0.003-0.005 inch0.003-0.005 inch
4. With all of this removed, carburetor cleaner can be used
to clean the rest of the carburetor before reassembly.
5. After cleaning the carburetor with an approved carbure-
tor cleaner, blow dry with compressed air and reassemble.
Shelf life on gasoline is 30 days. Proper procedures
need to be taken for carburetors so that the fuel doesn’t
varnish over time. A fuel stabilizer must be used at all
times in order to ensure that the fuel is fresh at all times.
RESULTS:
If carburetor is varnished, clean or replace. Refer to
back to Flow Chart.
TEST 30 – CHOKE TEST
PROCEDURE:
If the generator is surging it may have a carburetion
problem. A lean condition can cause erratic RPM.
Slowly pull the choke out to see if surging stops. If it
does stop, carburetion should be checked.
Figure 14. Adjusting Valve Clearance
1. Loosen the rocker arm jam nut. Turn the pivot ball stud
while checking the clearance between the rocker arm
and valve stem with a feeler gauge (see Figure 14).
2. When clearance is correct, hold the pivot ball stud with
the allen wrench and tighten the rocker arm jam nut to
the specified torque with a crow's foot. After tightening
the jam nut, recheck valve clearance to make sure it did
not change.
Rocker Arm Jam Nut ft-lbs
189cc 7.48
206cc 7.48
389cc 9-12
410cc 14.01
Page 47
Page 50
CROW'S FOOT
SECTION 3.3
DIAGNOSTIC TESTS
INSTALL ROCKER ARM COVER
1. Use a new rocker arm cover gasket. Install the rocker
arm cover and retain with four screws.
RESULTS:
Adjust valves to specification and retest. If problem
continues, refer to Flow Chart.
TEST 36 – CHECK ENGINE / CYLINDER LEAK
DISCUSSION:
Most engine problems may be classified as one or a
combination of the following:
• Willnotstart.
• Startshard.
• Lackofpower.
• Runsrough.
• Vibration.
• Overheating.
• Highoilconsumption.
DISCUSSION:
The Cylinder Leak Down Tester checks the sealing
(compression) ability of the engine by measuring air
leakage from the combustion chamber. Compression
loss can present many different symptoms. This test
is designed to detect the section of the engine where
the fault lies before disassembling the engine.
PROCEDURE:
1. Remove the spark plug.
2. Gain access to the flywheel. Remove the valve cover.
3. Rotate the engine crankshaft until the piston reaches top
dead center (TDC). Both valves should be closed.
Figure 15. Tightening the Jam Nut
DOWN TEST / COMPRESSION TEST
PART 3
DC CONTROL
4. Lock the flywheel at top dead center.
5. Attach cylinder leak down tester adapter to spark plug
hole.
6. Connect an air source of at least 90 psi to the leak down
tester.
7. Adjust the regulated pressure on the gauge to 80 psi.
8. Read the right hand gauge on the tester for cylinder
pressure. 20 percent leakage is normally acceptable.
Use good judgement, and listen for air escaping at the
carburetor, the exhaust, and the crankcase breather.
This will determine where the fault lies.
CHECK COMPRESSION:
To check engine compression, remove the spark plug.
Insert an automotive type compression gauge into
the spark plug hole. Crank the engine until there is
no further increase in pressure. The highest reading
obtained is the engine compression pressure.
M I N I M U M A L L O WA B L E C O M P R E S S I O N
PRESSURE COLD ENGINE – 60 psi
If compression is poor, look for one or more of the following causes:
• Loosecylinderheadbolts.
• Failedcylinderheadgasket.
• Burnedvalvesorvalveseats.
• Insufficientvalveclearance.
• Warpedcylinderhead.
• Warpedvalvestem.
• Wornorbrokenpistonring(s).
• Wornordamagedcylinderbore.
• Brokenconnectingrod.
• Wornvalveseatsorvalves.
• Wornvalveguides.
NOTE: Refer to Engine Service Manual Part
Number 0C1103A for further engine service information on the 410cc engine.
TEST 38 – CHECK FLYWHEEL
DISCUSSION:
In Test 25, a spark tester was used to check for
engine ignition. If sparking or weak spark occurred,
one possible cause might be the ignition magneto.
This test will check the magnetism of the flywheel and
will check the flywheel key.
Page 48
Page 51
SPARK PLUG
ENGINE WIRE HARNESS
REMOVE LEAD
FLYWHEEL KEY
WIRE 18 TO
START-RUN-STOP SWITCH
(SHUTDOWN LEAD)
WIRE 18
CONNECTION
OFF
ON
OFF-ON SWITCH
MAGNETO
SHUTDOWN HARNESS
WIRE 18
DC CONTROL
PART 3
Figure 16. Engine Ground Harness
SECTION 3.3
DIAGNOSTIC TESTS
2. Remove the flywheel cover so that the magneto is
exposed.
3. Disconnect Wire 18 from the magneto.
4. Repeat Test 25, “Check Ignition Spark.”
RESULTS:
1. If spark now occurs, Wire 18 has a short to ground.
Trace Wire 18 back to the START-RUN-STOP switch
and Oil Pressure Module (If so equipped).
2. If spark still does not occur, refer back to flow chart.
PROCEDURE:
1. Check the flywheel magnet by holding a screwdriver at
the extreme end of its handle and with its point down.
When the tip of the screwdriver is moved to within 3/4
inch (19mm) of the magnet, the blade should be pulled
in against the magnet.
2. For rough running or hard starting engines check the flywheel key. The flywheel’s taper is locked on the crankshaft
taper by the torque of the flywheel nut. A keyway is provided for alignment only and theoretically carries no load
Note: If the flywheel key becomes sheared or even
partially sheared, ignition timing can change.
Incorrect timing can result in hard starting or failure to start.
TEST 39 – REMOVE WIRE 18 / SHUTDOWN
LEAD
DISCUSSION:
Wire 18 on all engines is used to shutdown the unit
when either the switch is placed in the OFF posi-
tion or a low oil condition has occurred. A ground
is applied to the magneto in both instances which
will inhibit spark and shutdown the unit. If a short to
ground exists on this wire the engine will be inhibited
from producing spark. This test will check the integrity
of the wire.
Note: The shutdown lead on units with the 389cc
engine will not be identified as Wire 18. Refer to
Figure 18 for identification of location.
PROCEDURE:
1. Turn off the fuel supply
Figure 17. Wire 18 (410cc Engine)
Figure 18. Shutdown Lead (389cc Engine)
TEST 40 – CHECK / ADJUST GOVERNOR
(389/206/163cc ENGINES)
INITIAL ADJUSTMENT:
1. Loosen the governor lever clamp bolt (See Figure
19).
2. While holding the governor lever in its full “INC. RPM”
position, rotate the governor shaft counter clockwise as
far as it will go.
Note: The governor shaft will only turn approximately 20 degrees from a full clockwise position. Do not apply excessive torque to the
governor shaft.
Page 49
Page 52
SECTION 3.3
GOVERNOR SHAFT
GOVERNOR
CLAMP BOLT
GOVERNOR LEVER
APPLY
LOCTITE
HERE
SPEED ADJUST SCREW
INCREASE RPM
DIAGNOSTIC TESTS
PART 3
DC CONTROL
3. Tighten the governor lever clamp bolt to 110 inchpounds.
RUNNING ADJUSTMENT:
After completing the initial adjustment, final adjust-
ment is accomplished with the engine running under
no-load.
1. Turn the speed adjustment screw counter clockwise
three full turns to avoid a possible engine overspeed
condition.
2. Start the engine and let it warm up and stabilize under
no-load.
3. Connect an AC frequency meter to one of the AC output
receptacles. No-load frequency should be between
62.0 - 62.5 hertz.
4. If the frequency/RPM are incorrect, turn the speed adjust
screw until frequency/RPM is within limits. Turn clockwise to increase frequency/RPM, counter clockwise to
decrease the frequency/RPM (see Figure 19).
5. After adjustment is complete add a drop of removable
loctite (Loctite 241) to the threads of the speed adjust
screw (see Figure 19).
TEST 41 – CHECK / ADJUST GOVERNOR
(410cc ENGINE)
DISCUSSION:
The generator AC frequency output is directly pro-
portional to the speed of the rotor. A two-pole rotor
(having a single north and a single south magnetic
pole) will produce an AC frequency of 60 hertz at
3600 RPM.
The generator is equipped with a “voltage over frequency” type AC voltage regulator. The units AC output voltage is generally proportional to AC frequency.
A low or high governor speed will result in a correspondingly low or high AC frequency and voltage output. The governed speed must be adjusted before any
attempt to adjust the voltage regulator is made.
PROCEDURE
1. Loosen the governor clamp bolt (Figure 20).
2. Hold the governor lever at its wide open throttle position,
and rotate the governor shaft clockwise as far as it will
go. Then, tighten the governor lever clamp bolt to 70
inch-pounds (8 Nm).
3. Start the generator; let it stabilize and warm up at
no-load.
4. Connect a frequency meter across the generators AC
output leads.
SECTION 3.3
DIAGNOSTIC TESTS
3. Set VOM to measure resistance.
4. Connect one meter test lead to the previously disconnect wire coming from the oil level switch. Connect the
other meter test lead to frame ground. INFINITY should
be measured.
RESULTS:
1. A reading of CONTINUITY indicates that the switch is no
longer functioning and will need to be replaced.
TEST 46 – CHECK OIL PRESSURE SWITCH
If the engine cranks and starts, then shuts down
almost immediately, the cause may be one or more of
the following:
• Lowengineoillevel.
• Lowoilpressure.
• Adefectiveoilpressureswitch.
5. Turn the primary adjust screw to obtain a frequency
reading of 62.5 Hz.
6. When frequency is correct at no load, check the AC voltage reading. If voltage is incorrect, the voltage regulator
may require adjustment if so equipped.
RESULTS:
1. If, after adjusting the engine governor, frequency and
voltage are good, tests may be discontinued.
2. If frequency is now good, but voltage is high or low, refer
back to flow chart.
3. If engine was overspeeding, check linkage and throttle
for binding. If no governor response is indicated refer to
engine service manual.
4. If engine appears to run rough and results in low frequency, proceed to Problem 26 Flow Chart.
TEST 45 – CHECK OIL LEVEL SWITCH
DISCUSSION:
The 389cc engine does not utilize oil pressure to
lubricate the internal components. It utilizes a splash
type lubrication system. The switch should be normally open as long as the engine is filled with oil. The
switch will close when the oil level drops to low the
switch will close and ground out the magnetos inhibit-
ing spark until the oil level is raised.
PROCEDURE:
1. Verify that the oil level is full.
2. Refer to Figure 3 in Section 3.3. Unplug the wire from
the oil level switch.
Figure 21. Low Oil Pressure Switch
PROCEDURE:
1. Check engine crankcase oil level.
a. Check engine oil level.
b. If necessary, add the recommended oil to
the dipstick FULL mark. DO NOT OVERFILL
ABOVE THE FULL MARK.
2. Do the following:
a. Disconnect Wire 86 and Wire 0 from the oil
pressure switch terminals. Remove the switch
and install an oil pressure gauge in its place.
b. Start the engine while observing the oil pres-
sure reading on gauge.
c. Note the oil pressure.
(1) Normal oil pressure is approximately 35-40
psi with engine running. If normal oil pressure is indicated, go to Step 4 of this test.
Page 51
Page 54
SECTION 3.3
DIAGNOSTIC TESTS
PART 3
DC CONTROL
(2) If oil pressure is below about 10 psi, shut
engine down immediately. A problem exists
in the engine lubrication system. Refer to
Service Manual, Generac P/N 0F6923 for
engine service recommendations.
Note: The oil pressure switch is rated at 10 psi for
single cylinder engines.
3. Remove the oil pressure gauge and reinstall the oil pressure switch. Do NOT connect Wire 86 or Wire 0 to the
switch terminals.
a. Set a voltmeter to measure resistance.
b. Connect the meter test leads across the switch
terminals. With engine shut down, the meter
should read CONTINUITY.
c. Crank and start the engine. The meter should
read INFINITY.
d. Connect one test lead to Wire 0 ( disconnected from
LOP). Connect the other test lead to a clean frame
ground. CONTINUITY should be measured. If CONTINUITY is NOT measured repair or replace Wire 0
between the LOP and the ground terminal connection on the engine mount.
4. If the LOP switch tests good in Step 3 and oil pressure is
good in Step 2, but the unit still shuts down with a LOP
fault, check all wiring connections between the STARTSTOP-RUN switch and the LOP pressure module and
the LOP sender for a short to ground. Any ground on
this wire will cause Wire 18 to receive a ground also
inhibiting spark from occurring. If a short to ground is
found replace the respective wire.
RESULTS:
1. If LOP switch, oil pressure and wiring all test good, refer
back to flow chart.
2. If the LOP switch failed, replace the switch.
3. If no pressure was measured, an internal failure of the
oil pump may have occurred.
TEST 49 – TEST RECOIL FUNCTION
PROCEDURE:
1. Attempt to pull start the engine and make the following
observations while doing so.
a. Does the cord pull easily and smoothly?
b. Does the cord return with no assistance?
c. Does the engine tur n over as the cord is
pulled?
RESULTS:
If the recoil did not perform as the observations are
stated above, possible problems that could be present
are:
1. If the engine can not turn over freely with the spark plug
removed, the engine has suffered some type of internal
failure that has seized it and is inhibiting it from running.
2. Refer back to flow chart.
Page 52
Page 55
PART 4
DISASSEMBLY
GP Series Portable Generators
TABLE OF CONTENTS
PARTTITLE
4.1.Major Disassembly
Page 53
Page 56
SECTION 4.1
1
2
3
4
5
6
PART 4
DISASSEMBLY
MAJOR DISASSEMBLY
MAJOR DISASSEMBLY
DISCUSSION.
Each generator will have its own unique method of disassembly. Provided is a simplified version of disassembly
that does not go into step by step instructions. The figure below represents the basic disassembly and sequence
of steps needed to remove the fuel tank, stator, rotor, and the engine. All of the GP series generators have these
major components and the order of disassembly would not change.
An exploded view of each GP Series generator model is provided on the following pages.
Figure 1. Basic Disassembly Steps
Page 54
Page 57
DISASSEMBLY
PART 4
SECTION 4.1
MAJOR DISASSEMBLY
Page 55
Page 58
SECTION 4.1
MAJOR DISASSEMBLY
Exploded View – GP1800 – Drawing No. 0H0609-A
PART 4
DISASSEMBLY
Page 56
Page 59
DISASSEMBLY
PART 4
SECTION 4.1
MAJOR DISASSEMBLY
ITEMQTY.DESCRIPTION
11ENGINE, 196CC
21RECOIL ASSEMBLY
31CARBURETOR
41AIR CLEANER COVER
51AIR FILTER
63CARBURETOR GASKET
71SPARK PLUG BOOT
81OIL LEVEL SENSOR
91FRAME, 1800W
101FUEL SHUTOFF VALVE
112VIBRATION MOUNT, #1
122VIBRATION MOUNT, #2
131AVR
ITEMQTY.DESCRIPTION
141BRUSH ASSEMBLY
151SPARK ARRESTOR
161MUFFLER ASSEMBLY
171FUEL TANK ASSEMBLY
181FUEL TANK CAP ASSEMBLY
191CONTROL PANEL ASSEMBLY
201ASSEMBLY, ALTERNATOR 1800W
Page 57
Page 60
SECTION 4.1
PORTABLE KIT
MAJOR DISASSEMBLY
Exploded View – GP3250 – Drawing No. 0H0522-C
PART 4
DISASSEMBLY
Page 58
Page 61
DISASSEMBLY
PART 4
SECTION 4.1
MAJOR DISASSEMBLY
ITEMQTY.DESCRIPTION
11ENGINE, 208CC
21RECOIL ASSEMBLY
31CARBURETOR
41AIR CLEANER COVER
51AIR FILTER
63CARBURETOR GASKET
71SPARK PLUG BOOT
81OIL LEVEL SENSOR
91FRAME, 3250W
101FUEL SHUTOFF VALVE
112VIBRATION MOUNT, #1
122VIBRATION MOUNT, #2
131AVR
ITEMQTY.DESCRIPTION
285BOLT, FLANGE M6-1.0 X 40
292BOLT, FLANGE M6-1.0 X 16
301RUBBER GRIP, HANDLE 3250W
311HANDLE, PORTABLE 3250W
321ASSY, HANDLE BRACKET 3250W
331ASSEMBLY, ALTERNATOR BRUSH
TYPE 3250W
141BRUSH ASSEMBLY
151SPARK ARRESTOR
161MUFFLER ASSEMBLY
171FUEL TANK ASSEMBLY
181FUEL TANK CAP ASSEMBLY
191CONTROL PANEL ASSEMBLY
202WHEEL, 7” DIAMETER 3250W
212WHEEL AXLE M12-1.75 THREADS
222NUT, AXLE M12-1.75
232WASHER, FLAT M12
242COTTER PIN
252BUMPER BRACKET 3250W
267NUT, FLANGE M6-1.0
272RUBBER BUMPER, 3250W
Page 59
Page 62
SECTION 4.1
1
2
3
23
24
25
5
48
46
47
50
51
18
49
20
6
4
7
17
52
53
54
55
19
45
43
44
41
42
16
15
13
11
12
8
10
35
36
37
14
32
9
30
27
28
26
38
33
39
31
34
29
40
MAJOR DISASSEMBLY
Exploded View – GP5000 – Drawing No. 0G9384A-C
PART 4
DISASSEMBLY
Page 60
Page 63
DISASSEMBLY
PART 4
SECTION 4.1
MAJOR DISASSEMBLY
ITEMQTY.DESCRIPTION
11FRAME PARTS
21ASSY CRADLE BASE
31CRADLE END
41PANEL RAIL
51BACK RAIL
610
710
81ENGINE/ALT PARTS
91ENGINE, 389cc W/O MUFFLER
104
114WASHER LOCK M8-5/16
124SCREW HHC 5/16-18 x 1-1/4 G5
CURVED HEAD BOLT 5/16-18 x 1.625"
LONG
CAP NUT LOCKING 5/16-18, 5/16" OF
THREAD
VIB MOUNT RUBBER 1.38 x 1.0 x
5/16-18 MALE/FEMALE
ITEMQTY.DESCRIPTION
291EXHAUST PARTS
301BRACKET, MUFFLER SHIELD, BOTTOM
311ASSY MUFFLER, 389cc
321BRACKET, MUFFLER SHIELD TOP
331GASKET, EXHUAST. 389cc
348SCREW HHTT M6-1.0 x 12
354WASHER FLAT 5/16-M8 ZINC
364WASHER LOCK M8-5/16
374SCREW HHC M8-1.25 x 12 G8.8 FT
382STUD M8-125 x 35 G5 ZINC
392HEX NUT M8-1.25 G8 CLEAR ZINC
404SCREW HHC M6-1.0 x 16 C8.8
134NUT LOCK FLG 5/16-18
141
151SCROLL, ALTERNATOR, SKU
163SCREW HHC M5-0.8 x 8 PC8.8
171ELECTRICAL PARTS
181ASSY RCP PANEL 30A RD NOHR MTR
191ASSY POWER LEADS
204SCREW PPPH #8-16 x 1/2" BZC
211ASSY GND WIRE PNL TO ALT
221ASSY GND WIRE ALT TO BASE
231WASHER LOCK SPECIAL 1/4"
241LUG SLDLSS #2-#8 x 17/64 CU
251SCREW HHTT M6-1.0 x 25
ALTERNATOR 6500W METRIC TAPER
SHAFT
411SPACER .34 x .62 x .590 ST/ZNC
421SCREW HHC M8-1.25 x 30 C8.8
431ACCESSORY KIT
441ASSY HANDLE LH
454
462
471ASSY HANDLE RH
482
492SCREW HHFC 1/2-13 x 4.5 ZBC
502NUT LOCK HEX 1/2-13 NYL INS
511FRAME, BENT, FOOT BLACK 03
522RUBBER FOOT
534NUT LOCK FLG 5/16-18
CARRIAGE HEAD BOLT 5/16-18 x 1.75"
LONG
CAP NUT LOCKING 5/16-18, 5/16" OF
THREAD
TIRE 9.5" DIA RUN FLAT PLASTIC HUB/
RUBBER TREAD
261FUEL TANK PARTS 6.6GL
271FUEL TANK ASSY 6.6 GAL
284SCREW HHTT M8-1.25 x 20
542WASHER FLAT 5/16-M8 ZINC
552SCREW HHC 5/16-18 x 1/2 G5
Page 61
Page 64
SECTION 4.1
MAJOR DISASSEMBLY
Exploded View – GP5500 – Drawing No. 0H1253-A
PART 4
DISASSEMBLY
Page 62
Page 65
DISASSEMBLY
PART 4
SECTION 4.1
MAJOR DISASSEMBLY
ITEMQTY.DESCRIPTION
21ASSY CRADLE BASE
31CRADLE END
3A1ASSEMBLY, FRAME 1 PIECE
41PANEL RAIL
51BACK RAIL
610CURVED HEAD BOLT M8-1.25 X 42MM
711CAP NUT LOCKING M8-1.25
91ENGINE, 389cc W /0 MUFFLER
104
114WASHER LOCK M8-5/16
124SCREW HHC M8-1.25 X 30
138NUT LOCK FLG M8-1.25
VIB MOUNT RUBBER 35MM X 25.4 X
M8-1.25
ITEMQTY.DESCRIPTION
251SCREW HHTT M6-1.0 X 25
271FUEL TANK ASSY 6.6 GAL PORTABLE
284SCREW HHTT M8-1.25 X 20
291FUEL CAP, VENTED
301SHIELD, HEAT, SKU
311BRACKET, MUFFLER 389CC
321MUFFLER, 389CC
331GASKET, EXHAUST 389CC
344SCREW HHTT M6-1.0 X 12
354WASHER FLAT 5/16-M8 ZINC
364WASHER LOCK M8-5/16
374SCREW HHC MB-1.25 X 20 G8.8 FT
142WASHER FLAT 13mm
151ALTERNATOR
15A*AVR
15B*BRUSH-ALTERNATOR
15C1SCROLL, ALTERNATOR, SKU
163SCREW HHC M5-0.8 X 8 PC8.8
171CLAMP HOSE .38-.87
181FUEL HOSE, 4 ID, 8.5 OD X 120MM
204SCREW PPPH #8-16 X 1/2" BZC
211ASSY RCP PANEL 25A RD W/HR MTR
221ASSY GND WIRE ALT TO BASE
231WASHER LOCK SPECIAL 1/4"
241LUG SLDLSS #2-#8 X 17/64 CU
382STUD M8-1.25 X 35 G5 ZINC
392HEX NUT M8-1.25 G8 CLEAR ZINC
441ASSY HANDLE LH
454
471ASSY HANDLE RH
482
492AXLE PIN, 1/2" X 4", 3/4" HEAD
502COTTER PIN, 1/8" X 1 1/4" ZN PLT
511FRAME, BENT, FOOT
522RUBBER FOOT, M8-1.25
542WASHER FLAT 5/16-M8 ZINC
552SCREW HHC M8-1.25 X 15
CA RRIAGE HEAD BOLT M8- 1.25 X
46mm LONG
TIRE 9,5" DIA RUN FLAT PLASTIC HUB/
RUBBER TREAD
Page 63
Page 66
SECTION 4.1
1
2
3
23
24
25
5
48
46
47
50
51
18
49
20
6
4
7
17
52
53
19
45
43
44
41
42
16
15
13
11
12
8
10
35
36
37
14
32
9
30
27
28
26
38
33
39
31
34
29
40
MAJOR DISASSEMBLY
Exploded View – GP6500 – Drawing No. 0G9384B-C
PART 4
DISASSEMBLY
Page 64
Page 67
DISASSEMBLY
PART 4
SECTION 4.1
MAJOR DISASSEMBLY
ITEMQTY.DESCRIPTION
11FRAME PARTS
21ASSY CRADLE BASE
31CRADLE END
41PANEL RAIL
51BACK RAIL
610
710
81ENGINE/ALT PARTS
91ENGINE, 389cc W/O MUFFLER
104
114WASHER LOCK M8-5/16
124SCREW HHC 5/16-18 x 1-1/4 G5
CURVED HEAD BOLT 5/16-18 x 1.625"
LONG
CAP NUT LOCKING 5/16-18, 5/16" OF
THREAD
VIB MOUNT RUBBER 1.38 x 1.0 x
5/16-18 MALE/FEMALE
ITEMQTY.DESCRIPTION
284SCREW HHTT M8-1.25 x 20
291EXHAUST PARTS
301BRACKET, MUFFLER SHIELD, BOTTOM
311ASSY MUFFLER, 389cc
321BRACKET, MUFFLER SHIELD TOP
331GASKET, EXHUAST. 389cc
348SCREW HHTT M6-1.0 x 12
354WASHER FLAT 5/16-M8 ZINC
364WASHER LOCK M8-5/16
374SCREW HHC M8-1.25 x 12 G8.8 FT
382STUD M8-125 x 35 G5 ZINC
392HEX NUT M8-1.25 G8 CLEAR ZINC
134NUT LOCK FLG 5/16-18
141
151SCROLL, ALTERNATOR, SKU
163SCREW HHC M5-0.8 x 8 PC8.8
171ELECTRICAL PARTS
181ASSY RCP PANEL 30A RD NOHR MTR
191ASSY POWER LEADS
204SCREW PPPH #8-16 x 1/2" BZC
211ASSY GND WIRE PNL TO ALT
221ASSY GND WIRE ALT TO BASE
231WASHER LOCK SPECIAL 1/4"
241LUG SLDLSS #2-#8 x 17/64 CU
251SCREW HHTT M6-1.0 x 25
ALTERNATOR 6500W METRIC TAPER
SHAFT
404SCREW HHC M6-1.0 x 16 C8.8
411ACCESSORY KIT
421ASSY HANDLE LH
434
442
451ASSY HANDLE RH
462
472SCREW HHFC 1/2-13 x 4.5 ZBC
482NUT LOCK HEX 1/2-13 NYL INS
491FRAME, BENT, FOOT BLACK 03
502RUBBER FOOT
514NUT LOCK FLG 5/16-18
522WASHER FLAT 5/16-M8 ZINC
CARRIAGE HEAD BOLT 5/16-18 x 1.75"
LONG
CAP NUT LOCKING 5/16-18, 5/16" OF
THREAD
TIRE 9.5" DIA RUN FLAT PLASTIC HUB/
RUBBER TREAD
261FUEL TANK PARTS 6.6GL
271FUEL TANK ASSY 6.6 GAL
532SCREW HHC 5/16-18 x 1/2 G5
Page 65
Page 68
SECTION 4.1
MAJOR DISASSEMBLY
Exploded View – GP7000 – Drawing No. 0G9384D-B
PART 4
DISASSEMBLY
Page 66
Page 69
DISASSEMBLY
PART 4
SECTION 4.1
MAJOR DISASSEMBLY
ITEMQTY.DESCRIPTION
11CRADLE END
21BACK RAIL
310
410
51PANEL RAIL
61ASSY CRADLE BASE
103WASHER LOCK M8-5/16
113SCREW HHC 3/8-16 x 1-1/4 G5
121SCREW HHC 5/16-24 x 1-1/4 G5
132SCREW HHC 5/16-18 x 1-1/4 G5
143WASHER LOCK M10
158NUT LOCK FLG 5/16-18
161ALTERNATOR, 7000W
172
181ENGINE, GH410
CURVED HEAD BOLT 5/16-18 x 1.625"
LONG
CAP NUT LOCKING 5/16-18 THREAD,
5/16" OF THREAD
VIB MOUNT RUBBER 1.38 x 1.0 x
5/16-18 MALE/FEMALE
ITEMQTY.DESCRIPTION
301LUG SLDLSS #2-#8 X 17/64 CU
311WASHER LOCK SPECIAL 1/4"
324SCREW PPPH #8-16 x 1/2" BZC
331ASSY GND WIRE ALT TO BASE
341
351SCREW HHTT M6-1.0 x 25 BP
551ACCESSORY KIT
561ASSY HANDLE LH
574CHB CUSTOM 5/16 18 x 46MM LONG
582
591ASSY HANDLE RH
602
612SCREW, HHC 1/2"-13 x 4-1/2" LONG
622
631FRAME, BENT, FOOT
RECEPTACLE PANEL 30A RND W/HR
MTR
CAP NUT LOCKING 5/16-18, 5/16" OF
THREAD
TIRE 9.5" DIA RUN FLAT PLASTIC
HUB/RUBBER TREAD
NUT, LOCK HEX 1/2-13 NYLON
INSERT
191BRACKET, MOUNT
202
212WASHER LOCK M6-1/4
222WASHER FLAT 5/16-M8 ZINC
232WASHER FLAT 1/4-M6 ZINC
242SCREW HHC 5/16-18 x 1-1/2 G5
252SCREW HHC M6-1.0 x 16 C8,8
261BRACKET, MOUNTING, MUFFLER 410
271
281CAPACITOR, VOLTAGE REG VS
VIB MOUNT RUBBER 1.38 x 1.0 x
5/16-18 M/M
CLAMP HOSE .38-.87 [NOT SHOWN,
FUEL HOSE]
642RUBBER FOOT
654NUT LOCK FLG 5/16-18
662WASHER FLAT 5/16-M8 ZINC
672SCREW HHC 5/16-18 X 1/2 G5
681FRAME, BENT, FOOT SUPPORT
692WASHER FLAT 1/2 ZINC
704SCREW HHTT M8-1.25 X 20
711FUEL TANK ASSY 8.0 GAL PORTABLE
721FUEL CAP-VENTED
Page 67
Page 70
SECTION 4.1
MAJOR DISASSEMBLY
Exploded View – GP8000 – Drawing No. 0G9384F-B
PART 4
DISASSEMBLY
Page 68
Page 71
DISASSEMBLY
PART 4
SECTION 4.1
MAJOR DISASSEMBLY
ITEMQTY.DESCRIPTION
11CRADLE END
21BACK RAIL
310
410
51PANEL RAIL
61ASSY CRADLE BASE
102WASHER FLAT 5/16-M8 ZINC
112NUT HEX LOCK M8-1.25 NY INS
122
134NUT LOCK FLG 5/16-18
141ASSEMBLY ENGINE GH-410
151ALTERNATOR 8000W
162
172WASHER LOCK M6-1/4
182WASHER FLAT 1/4-M6 ZINC
192SCREW HHC M6-1.0 x 16 C8.8
201SCREW HHTR 5/16-18 x 3/4
211BRACKET MUFFLER
224SCREW FHSC 3/8-16 x 3/4
231
301LUG SLDLSS #2-#8 x 17/64 CU
311WASHER LOCK SPECIAL 1/4"
324SCREW PPPH #8-16 x 1/2" BZC
331ASSY GND WIRE ALT TO BASE
341ASSY RCP PNL 8KW 30A W/HR MTR
351SCREW HHTT M6-1.0 x 25 BP
551ACCESSORY KIT
561ASSY HANDLE LH
574CHB CUSTOM 5/16 18 x 46MM LONG
582
591ASSY HANDLE RH
CURVED HEAD BOLT 5/16-18 x 1.625"
LONG
CAP NUT LOCKING 5/16-18 THREAD)
5/16" OF THREAD
VIBE MOUNT 25.0 x 31.8 x M8-1.25
M/M
VIB MOUNT RUBBER 1.38 x 1.0 x
5/16-18 MALE/MALE
CLAMP HOSE .38-.87 [NOT SHOWN,
FUEL HOSE]
CAP NUT LOCKING 5/16-18, 5/16" OF
THREAD
ITEMQTY.DESCRIPTION
602
612SCREW, HHC 1/2"-13 x 4-1/2" LONG
622
631FRAME, BENT, FOOT
642RUBBER FOOT
654NUT LOCK FLG 5/16-18
662WASHER FLAT 5/16-M8 ZINC
672SCREW HHC 5/16-18 x 1/2 G5
681FRAME) BENT, FOOT SUPPORT
692WASHER FLAT 1/2 ZINC
704SCREW HHTT M8-1.25 x 20
711FUEL TANK ASSY 8.0 GAL
721FUEL CAP-VENTED
751BEARING CARRIER REAR
761STATOR 8KW
771
78I ROTOR ASSEMBLY, 8kW
79I CAPACITOR
80I CLAMP
815WASHER LOCK M8-5/16
824SCREW IHHC M8-1.25 x 140 G8.8
831WASHER FLAT 5/16-M8 ZINC
841SCREW IHHC 5/16-24 x 8-1/2 G5
851COVER ALTERNATOR INLET
861GROMMET WIRE SLEEVE
872SCREW PPHM M4-0,7 x 10
884WASHER FLAT #10 ZINC
894WASHER LOCK #10
904SCREW PPHM M5-0,8 x 30
911SCREW HHTT M6-1.0 x 12
921
TIRE 9.5" DIA RUN FLAT PLASTIC
HUB/RUBBER TREAD
NUT, HEX LOCK 1-2"-13 NYLON
INSERT
(CASTING) ENGINE ADAPTER
HOUSING
ALTERNATOR FAN VARIED BLADE
SPACING
Page 69
Page 72
SECTION 4.1
MAJOR DISASSEMBLY
PART 4
DISASSEMBLY
Page 70
Page 73
PART 5
ELECTRICAL
DATA
GP Series Portable Generators
TABLE OF CONTENTS
DWG#TITLEPAGE
0H0612-A
0H0523-A
0G9769-C
0G9769-C
0G9849-A
0G9849-A
Electrical Schematic, GP185072
Electrical Schematic, GP3250
Electrical Schematic,
GP5000/5500/6500
Wiring Diagram,
GP5000/5500/6500
Electrical Schematic,
GP7000E/8000E
Wiring Diagram,
GP7000E/8000E
Electrical Formulas78
73
74
75
76
77
Page 71
Page 74
ELECTRICAL SCHEMATIC, GP1850
SENSING
DPE
Brushed Alternator Drawing No. 0H0612-A
PART 5
ELECTRICAL DATA
Page 72
Page 75
ELECTRICAL DATA
SENSING
DPE
PART 5
ELECTRICAL SCHEMATIC, GP3250
Brushed Alternator Drawing No. 0H0523-A
Page 73
Page 76
ELECTRICAL SCHEMATIC, GP5000/5500/6500
Brushed Alternator Drawing No. 0G9769-C
PART 5
ELECTRICAL DATA
Page 74
Page 77
ELECTRICAL DATA
PART 5
WIRING DIAGRAM, GP5000/5500/6500
Brushed Alternator Drawing No. 0G9769-C
Page 75
Page 78
ELECTRICAL SCHEMATIC, GP7000E/8000E
Brushless Alternator Drawing No. 0G9849-A
PART 5
ELECTRICAL DATA
Page 76
Page 79
ELECTRICAL DATA
PART 5
WIRING DIAGRAM, GP7000E/8000E
Brushless Alternator Drawing No. 0G9849-A
Page 77
Page 80
ELECTRICAL FORMULAS
TO FINDKNOWN VALUES1-PHASE
KILOWATTS (kW)
KVA
AMPERES
WATTS
NO. OF ROTOR POLES
FREQUENCY
RPM
kW (required for Motor)
Volts, Current, Power Factor
Volts, Current
kW, Volts, Power Factor
Volts, Amps, Power FactorVolts x Amps
Frequency, RPM
RPM, No. of Rotor Poles
Frequency, No. of Rotor Poles
Motor Horsepower, Efficiency
E x I
1000
E x I
1000
kW x 1000
E
2 x 60 x Frequency
RPM
RPM x Poles
2 x 60
2 x 60 x Frequency
Rotor Poles
HP x 0.746
Efficiency
RESISTANCE
VOLTS
AMPERES
E = VOLTSI = AMPERESR = RESISTANCE (OHMS)PF = POWER FACTOR