Generac Power Systems EcoGen Series, 005818-0, EcoGen 6kW Owner's Manual

Owner's Manual
EcoGen 6kW Generator
C
LISTE
D
U
S
NOT INTENDED FOR USE IN CRITICAL LIFE SUPPORT APPLICATIONS.
ONLY QUALIFIED ELECTRICIANS OR CONTRACTORS

SHOULD ATTEMPT INSTALLATION!
DEADLY EXHAUST FUMES! OUTDOOR

INSTALLATION ONLY!

Table of Contents

Introduction .............................................. 1
Read This Manual Thoroughly ................................................1
Safety Rules ............................................. 1
Contents ...............................................................................1
Operation and Maintenance....................................................1
How to Obtain Service ...........................................................1
Standards Index .....................................................................3
General Information ................................. 4
1.1 Unpacking/Inspection .....................................................4
1.2 Protection Systems ........................................................4
1.3 Emission Information......................................................4
1.4 The Generator ................................................................5
1.5 Specifications ................................................................5
1.6 Ready to Run .................................................................5
1.7 Fuel Requirements and Recommendations ......................6
1.8 Fuel Consumption ..........................................................6
1.9 Location .........................................................................6
1.10 Battery Requirements .....................................................9
1.11 Battery Installation ..........................................................9
1.12 The Battery ....................................................................9
1.13 Battery Charger ............................................................10
Operation ................................................ 12
3.1 Control Panel Interface .................................................12
3.2 Automatic Operation .....................................................13
3.3 Sequence of Automatic Operation .................................13
3.4 Side Compartment .......................................................14
3.5 Protection Systems ......................................................14
Maintenance ........................................... 16
4.1 Fuse .............................................................................16
4.2 Checking the Engine Oil Level .......................................16
4.3 Changing the Engine Oil ................................................16
4.4 Changing the Engine Air Cleaner ...................................17
4.5 Spark Plugs ..................................................................17
4.6 Battery Maintenance .....................................................18
4.7 Adjusting GT-530 Valve Clearance .................................18
4.8 Cooling System ............................................................19
4.9 Attention After Submersion ...........................................19
4.10 Corrosion Protection.....................................................19
4.11 Out of Service Procedure ..............................................19
4.12 Service Schedule .........................................................21
Troubleshooting ..................................... 22
5.1 Troubleshooting Guide ..................................................22
Post Installation Start-up and
Adjustments ........................................... 10
2.1 Activate the Generator ..................................................10
2.2 Before Initial Startup .....................................................10
2.3 Electrical Checks ..........................................................10
2.4 Generator Tests Under Load ..........................................12
2.5 Checking Automatic Operation ......................................12
Appendix................................................. 23
6.1 Menu System Navigation ..............................................23
Installation Diagrams ............................ 25
Oil Make-up System ............................... 29
Notes ....................................................... 30
Warranty ................................................. 32

Safety Rules

INTRODUCTION

Thank you for purchasing this compact, high performance, air-cooled, engine-driven generator. It is designed to supply electrical power to operate an inverter/battery charger as a component in an off-grid power solution.
This unit is factory installed in an all-weather, metal enclosure and is intended exclusively for outdoor installation. This generator will operate using vapor withdrawn liquid propane (LP).
NOTE:
This generator is suitable for supplying typical residential loads such as Induction Motors (sump pumps, refrigerators, air conditioners, furnaces, etc.), Electronic Components (computer, monitor, TV, etc.), Lighting Loads and Microwaves.

READ THIS MANUAL THOROUGHLY

If any portion of this manual is not understood, contact the nearest Dealer for starting, operating and servicing procedures.
SAFETY RULES
Throughout this publication, and on tags and decals affixed to the genera­tor, DANGER, WARNING, CAUTION and NOTE blocks are used to alert personnel to special instructions about a particular operation that may be hazardous if performed incorrectly or carelessly. Observe them carefully. Their definitions are as follows:
INDICATES A HAZARDOUS SITUATION OR ACTION WHICH, IF
NOT AVOIDED, WILL RESULT IN DEATH OR SERIOUS INJURY.
Indicates a hazardous situation or action which, if not
avoided, could result in death or serious injury.
This symbol points out potential electrical shock hazard.
The operator is responsible for proper and safe use of the equipment. The manufacturer strongly recommends that the operator read this Owner's Manual and thoroughly understand all instructions before using this equipment. The manufacturer also strongly recommends instructing other users to properly start and operate the unit. This prepares them if they need to operate the equipment in an emergency.

CONTENTS

This manual contains important instructions that should be followed dur­ing installation and maintenance of the generator and batteries for the 6kW LP, V-twin GT-530 Engine.

OPERATION AND MAINTENANCE

It is the operator's responsibility to perform all safety checks, to make sure that all maintenance for safe operation is performed promptly, and to have the equipment checked periodically by a Dealer. Normal maintenance ser­vice and replacement of parts are the responsibility of the owner/operator and, as such, are not considered defects in materials or workmanship within the terms of the warranty. Individual operating habits and usage contribute to the need for maintenance service.
Proper maintenance and care of the generator ensures a minimum number of problems and keep operating expenses at a minimum. See a Dealer for service aids and accessories.

HOW TO OBTAIN SERVICE

When the generator requires servicing or repairs, contact a Dealer for assistance. Service technicians are factory-trained and are capable of handling all service needs.
When contacting a Dealer about parts and service, always supply the complete model number and serial number of the unit as given on its data decal, which is located on the generator. See section "The Generator" for decal location.
Model No. _________________ Serial No. ______________
Indicates a hazardous situation or action which, if not
avoided, could result in minor or moderate injury.
NOTE:
Notes contain additional information important to a procedure and will be found within the regular text body of this manual.
These safety warnings cannot eliminate the hazards that they indicate. Common sense and strict compliance with the special instructions while performing the action or service are essential to preventing accidents.
Four commonly used safety symbols accompany the DANGER, WARNING and CAUTION blocks. The type of information each indicates is as follows:
This symbol points out important safety information that, if not followed, could endanger personal safety and/or
n
property of others.
This symbol points out potential explosion hazard.
This symbol points out potential fire hazard.
Data Label Sample
1
Safety Rules
IMPORTANT SAFETY INSTRUCTIONS! SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe operation be copied and posted near the unit’s installation site. Safety should be stressed to all operators and potential operators of this
n
equipment.
Study these SAFETY RULES carefully before installing, operating or servicing this equipment. Become familiar with this Owner’s Manual and with the unit. The generator can operate safely, effi­ciently and reliably only if it is properly installed, operated and maintained. Many accidents are caused by failing to follow simple and fundamental rules or precautions.
The manufacturer cannot anticipate every possible circumstance that might involve a hazard. The warnings in this manual, and on tags and decals affixed to the unit are, therefore, not all-inclusive. If using a procedure, work method or operating technique the manu­facturer does not specifically recommend, ensure that it is safe for others. Also make sure the procedure, work method or operating technique utilized does not render the generator unsafe.
Despite the safe design of this generator, operating this equipment imprudently, neglect-
n
ing its maintenance or being careless can cause possible injury or death. Permit only responsible and capable persons to install, operate and maintain this equipment.
Potentially lethal voltages are generated by
these machines. Ensure all steps are taken to render the machine safe before attempting to work on the generator.
Parts of the generator are rotating and/or hot during operation. Exercise care near run-
n
ning generators.
Installation must always comply with appli­cable codes, standards, laws and regula-
n
tions.
A running generator gives off carbon mon­oxide, and odorless, colorless poison gas.
n
Breathing in carbon monoxide can cause headaches, fatigue, diziness, nausea, vomit­ting, confusion, fainting, siezures or death.
Install a battery operated carbon monoxide alarm indoors,
according to manufacturer's instructions/recommendations.
Adequate, unobstructed flow of cooling and ventilating air is
critical to correct generator operation. Do not alter the instal­lation or permit even partial blockage of ventilation provisions, as this can seriously affect safe operation of the generator. The
generator MUST be installed and operated outdoors only.
Keep hands, feet, clothing, etc., away from drive belts, fans,
and other moving or hot parts. Never remove any drive belt or fan guard while the unit is operating.
When working on this equipment, remain alert at all times.
Never work on the equipment when physically or mentally fatigued.
Inspect the generator regularly, and contact the nearest Dealer
for parts needing repair or replacement.
Before performing any maintenance on the generator, discon-
nect its battery cables to prevent accidental start up. Disconnect the cable from the battery post indicated by a NEGATIVE, NEG or (–) first, then remove the POSITIVE, POS or (+) cable. When reconnecting the cables, connect the POSITIVE cable first, the NEGATIVE cable last.
Never use the generator or any of its parts as a step. Stepping
on the unit can stress and break parts, and may result in dan­gerous operating conditions from leaking exhaust gases, fuel leakage, oil leakage, etc.

EXHAUST HAZARDS

Generator engine exhaust contains DEADLY carbon monox-
ide, an odorless, colorless poisonous gas. Breathing carbon monoxide can cause: dizziness, throbbing temples, nausea, muscular twitching, headache, vomiting, weakness and sleepi­ness, inability to think clearly, fainting, unconsciousness or even death. If you experience any carbon monoxide poisoning symptoms, move into fresh air and immediately seek medical attention.
Never operate the generator set with the vehicle inside any
garage or other enclosed area.

GENERAL HAZARDS

For safety reasons, the manufacturer recommends that this equip-
ment be installed, serviced and repaired by a Service Dealer or other competent, qualified electrician or installation technician who is familiar with applicable codes, standards and regulations. The operator also must comply with all such codes, standards and regulations.
The engine exhaust fumes contain carbon monoxide, which
can be DEADLY. This dangerous gas, if breathed in sufficient concentrations, can cause unconsciousness or even death. Do NOT alter or add to the exhaust system or do anything that might render the system unsafe or in noncompliance with appli­cable codes and standards.
2

ELECTRICAL HAZARDS

All generators covered by this manual produce dangerous
electrical voltages and can cause fatal electrical shock. Utility power delivers extremely high and dangerous voltages to the transfer switch as does the standby generator when it is in operation. Avoid contact with bare wires, terminals, connec­tions, etc., while the unit is running. Ensure all appropriate covers, guards and barriers are in place, secured and/or locked before operating the generator. If work must be done around an operating unit, stand on an insulated, dry surface to reduce shock hazard.
Do not handle any kind of electrical device while stand-
ing in water, while barefoot, or while hands or feet are wet. DANGEROUS ELECTRICAL SHOCK MAY RESULT.
Safety Rules
The National Electrical Code (NEC) requires the frame and external
electrically conductive parts of the generator to be connected to an approved earth ground. Local electrical codes also may require proper grounding of the generator electrical system.
After installing this home standby electrical system, the genera-
tor may crank and start at any time without warning. When this occurs, load circuits are transferred to the STANDBY (genera­tor) power source. To prevent possible injury if such a star t and transfer occur, always set the generator’s AUTO/OFF/MANUAL switch to its OFF position before working on equipment and remove the 7.5A fuse from the generator control panel.
In case of accident caused by electric shock, immediately shut
down the source of electrical power. If this is not possible, attempt to free the victim from the live conductor. AVOID DIRECT CONTACT WITH THE VICTIM. Use a nonconducting implement, such as a dry rope or board, to free the victim from the live conductor. If the victim is unconscious, apply first aid and get immediate medical help.
Never wear jewelry when working on this equipment. Jewelry
can conduct electricity resulting in electric shock, or may get caught in moving components causing injury.

FIRE HAZARDS

For fire safety, the generator must be installed and maintained
properly. Installation must always comply with applicable codes, standards, laws and regulations. Adhere strictly to local, state and national electrical and building codes. Comply with regulations the Occupational Safety and Health Administration (OSHA) has established. Also, ensure that the generator is installed in accordance with the manufacturer’s instructions and recommendations. Following proper installa­tion, do nothing that might alter a safe installation and render the unit in noncompliance with the aforementioned codes, standards, laws and regulations.
Keep a fire extinguisher near the generator at all times.
Extinguishers rated “ABC” by the National Fire Protection Association are appropriate for use on the standby electric system. Keep the extinguisher properly charged and be familiar with its use. Consult the local fire department with any ques­tions pertaining to fire extinguishers.

STANDARDS INDEX

In the absence of pertinent standards, codes, regulations and laws, the published information listed below may be used for installation guidance for this equipment.
1. NFPA No. 37, STATIONARY COMBUSTION ENGINES AND GAS TURBINES, available from the National Fire Protection Association, 470 Atlantic Avenue, Boston, MA 02210.
2. NFPA No. 76A, ESSENTIAL ELECTRICAL SYSTEMS FOR HEALTH CARE FACILITIES, available same as Item 1.
3. NFPA No. 54, NATIONAL FUEL GAS CODE, available same as Item 1.
4. NFPA No. 58, AMERICAN NATIONAL STANDARD FOR STORAGE AND HANDLING OF LIQUEFIED PETROLEUM GAS, available same as Item 1.
5. NFPA No. 70, NFPA HANDBOOK OF NATIONAL ELECTRIC CODE, available same as Item 1.
6. Article X, NATIONAL BUILDING CODE, available from the American Insurance Association, 85 John Street, New York, N.Y. 10038.
7. AGRICULTURAL WIRING HANDBOOK, available from the Food and Energy Council, 909 University Avenue, Columbia, MO
65201.
8. ASAE EP-3634, INSTALLATION AND MAINTENANCE OF FARM STANDBY ELECTRICAL SYSTEMS, available from the American Society of Agricultural Engineers, 2950 Niles Road, St. Joseph, MI 49085.
9. NFPA No. 30, FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE, available same as Item 1.

EXPLOSION HAZARDS

Do not smoke around the generator. Wipe up any fuel or oil
spills immediately. Ensure that no combustible materials are left in the generator compartment, or on or near the generator, as FIRE or EXPLOSION may result. Keep the area surrounding the generator clean and free from debris.
Gaseous fluids such as natural gas and liquid propane (LP)
gas are extremely EXPLOSIVE. Install the fuel supply system according to applicable fuel-gas codes. Before placing the home standby electric system into service, fuel system lines must be properly purged and leak tested according to applica­ble code. After installation, inspect the fuel system periodically for leaks. No leakage is permitted.
CALIFORNIA PROPOSITION 65 WARNING
Engine exhaust and some of its constituents are known
to the State of California to cause cancer, birth defects
and other reproductive harm.
CALIFORNIA PROPOSITION 65 WARNING
This product contains or emits chemicals known to the
State of California to cause cancer, birth defects and
other reproductive harm.
3

General Information

Only qualified electricians or contractors
should attempt such installations, which must
n
comply strictly with applicable codes, stan­dards and regulations.

1.1 UNPACKING/INSPECTION

After unpacking, carefully inspect the contents for damage.
This standby generator set is ready for installation with a factory
supplied and pre-mounted base pad and has a weather protec­tive enclosure that is intended for outdoor installation only.
If this generator is used to power electrical load circuits normally powered by a utility power
source, it is required by code to install a trans­fer switch. The transfer switch must effectively isolate the electrical system from the utility distribution system when the generator is oper­ating (NEC 700, 701 & 702). Failure to isolate an electrical system by such means will result in damage to the generator and also may result in injury or death to utility power workers due to backfeed of electrical energy.
If any loss or damage is noted at time of delivery, have the person(s) making the delivery note all damage on the freight bill or affix their signature under the consignor's memo of loss or damage.
If a loss or damage is noted after delivery, separate the damaged materials and contact the carrier for claim procedures.
“Concealed damage” is understood to mean damage to the con­tents of a package that is not in evidence at the time of delivery, but is discovered later.
To properly open the roof, press down on the center top lip and turn the locks on both ends. If pressure is not applied from the top, the roof may appear stuck. Always verify that the side locks are unlocked before attempting to lift the roof.

1.2 PROTECTION SYSTEMS

Unlike an automobile engine, the generator may have to run for long periods of time with no operator present to monitor engine conditions. For that reason, the engine is equipped with the fol­lowing systems that protect it against potentially damaging condi­tions:
1. Low Oil Pressure Sensor 6. Low Battery
2. High Temperature Sensor 7. Under-frequency
3. Overcrank 8. Undervoltage
4. Overspeed 9. Overvoltage
5. RPM Sensor 10. Internal Failure
There are readouts on the control panel to notify personnel that one of these failures has occurred. There is a Status message on the display that displays when all of the conditions described in the "Ready to Run" section are true.

1.3 EMISSION INFORMATION

The Environmental Protection Agency requires that this generator comply with exhaust emission standards. This generator is certi­fied to meet the applicable EPA emission levels. Additional infor­mation regarding the requirements set by the EPA is as follows:
The generator is certified for use as a stationary engine for standby power generation. Any other use may be a violation of federal and/ or local laws. It is important to follow the maintenance specifica­tions in the "Maintenance" section to ensure that the engine com­plies with the applicable emission standards for the duration of the engine’s life. This engine is certified to operate on Liquid Propane fuel. The emission control system on the generator consists of the following:
Fuel Metering System
Carburetor/mixer assembly• Fuel regulator
Air Induction System
Intake pipe/manifold• Air cleaner
Ignition System
Spark plug• Ignition module
The Emissions Compliance Period referred to on the Emissions Compliance Label indicates the number of operating hours for which the engine has been shown to meet Federal emission requirements. See the table below to determine the compliance period for the generator. The displacement of the generator is listed on the Emissions Compliance Label.
Displacement Category Compliance Period
A 300 Hours
< 66 cc
66 cc -
< 225 cc
225 cc
B 125 Hours
C 50 Hours
A 500 Hours
B 250 Hours
C 125 Hours
A 1000 Hours
B 500 Hours
C 250 Hours
4
General Information

1.4 THE GENERATOR

Figure 1.1 – 6kW, V-twin, GT-530 Engine
(door removed)
Air Filter External Oil Fill/Dipstick
Engine
Oil Fill
Engine Oil
Dipstick
Enclosure
Oil FilterExhaust
Figure 1.2 – Data Label Sample
Battery Compartment
Composite Base
Control Panel
Data Label
Circuit Breaker
Fuel Inlet (back)
Fuel Regulator

1.5 SPECIFICATIONS

1.5.1 GENERATOR
Fuel Type ....................................................................................... LP vapor only
Rated Voltage ......................................................................................... 120 VAC
Rated Maximum Load Current (Amps) at 120 Volts (LP)* .............................50.0
Main Circuit Breaker ................................................................................ 50 Amp
Phase ................................................................................................................1
Number of Rotor Poles .......................................................................................2
Rated AC Frequency ....................................................................................60 Hz
Battery Requirement ........................ Group 26R, 12 Volts and 525 CCA Minimum
Weight (unit only in lbs.) ................................................................................387
Enclosure ..................................................................................................... Steel
Normal Operating Range: This unit is tested in accordance to UL 2200 standards with an operating temperature of 20 °F (-29 °C) to 122 °F. (50 °C). For areas where temperatures fall below 32 °F (0 °C), a cold weather kit is highly recom­mended. When operated above 104º F (40º C) there may be a decrease in engine power. (Please reference the engine specifications section).
These generators are rated in accordance with UL2200, Safety Standard for Stationary Engine Generator Assemblies; and CSA-C22.2 No. 100-04 Standard for Motors and Generators.
1.5.2 ENGINE
Type of Engine .........................................................................................GT-530
Number of Cylinders ..........................................................................................2
Rated Horsepower @ 3,600 rpm* ...................................................................18
Displacement ............................................................................................. 530cc
Cylinder Block .........................................................Aluminum w/Cast Iron Sleeve
Valve Arrangement ..................................................................... Overhead Valves
Ignition System ................................................................. Solid-state w/Magneto
Recommended Spark Plug ..................................................................... BPR6HS
Spark Plug Gap ................................................................. 0.76 mm (0.030 inch)
Compression Ratio.......................................................................................9.5:1
Starter ..................................................................................................... 12 VDC
Oil Capacity Including Filter ..........................................................Approx. 1.7 Qts
Recommended Oil Filter ............................................................. Part # 070185F
Recommended Air Filter ...............................................................Part # 0E9371
Operating RPM............................................................................................2,600
* Engine power is subject to and limited by such factors as fuel Btu content, ambi-
ent temperature and altitude. Engine power decreases about 3.5 percent for each 1,000 feet above sea level; and also will decrease about 1 percent for each 6 C (10 F) above 16 C (60 F) ambient temperature.

1.6 READY TO RUN

The "Ready to Run" on the display is ready when all of the following conditions are true:
1. The AUTO/OFF/MANUAL switch is set to the AUTO position.
2. The utility voltage being supplied to the unit is being sensed by the PCB. If the utility sense voltage is not connected to the unit or if it is below approximately 150-160 volts AC, then the system will display the message "No Utility Present". This indicates that if the AUTO/OFF/MANUAL switch is placed in the Auto position, the generator will start.
3. No alarms are present, for example, low oil pressure, high temperature, etc.
5
General Information

1.7 FUEL REQUIREMENTS AND RECOMMENDATIONS

This unit uses a LP vapor withdrawal system only. This type of system uses the vapors formed above the liquid fuel in the storage tank.
Recommended fuels should have a Btu content of at least 2,520 Btus per cubic foot for LP gas. Ask the fuel supplier for the Btu content of the fuel.
Required fuel pressure for liquid propane, 10 inches to 12 inches
of water column (0.36 to 0.43 psi). The primary regulator for the propane supply is NOT INCLUDED with the generator.
NOTE:
All pipe sizing, construction and layout must comply NFPA 58 for liquid propane applications. Once the generator is installed, verify that the fuel pressure NEVER drops below 10 inches water column.
Prior to installation of the generator, the installer should consult local fuel suppliers or the fire marshal to check codes and regula­tions for proper installation. Local codes will mandate correct rout­ing of gaseous fuel line piping around gardens, shrubs and other landscaping to prevent any damage.
Special considerations should be given when installing the unit where local conditions include flooding, tornados, hurricanes, earthquakes and unstable ground for the flexibility and strength of piping and their connections.
Use an approved pipe sealant or joint compound on all threaded fitting.
All installed gaseous fuel piping must be purged and leak tested prior to initial start-up in accordance with local codes, standards and regulations.

1.8 FUEL CONSUMPTION

Unit
6 kW 0.82/30 1.47/54
** LP is in gallons per hour/cubic feet per hour.
*** Values given are approximate.
Verify that gas pipe and regulator is capable of providing enough fuel flow to include household appliances.
Gaseous fuels such as liquid propane (LP) gas are highly explosive. Even the slightest
spark can ignite fuel and cause an explo-
sion. No leakage of fuel is permitted. LP gas is heavier than air and tends to settle in low areas.
1/2 Load Full Load
LP Vapor
NOTE:
A minimum of one approved manual shut-off valve must be installed in the gaseous fuel supply line. The valve must be eas­ily accessible. Local codes determine the proper location.

1.9 LOCATION

The engine exhaust fumes contain carbon monoxide, which can be DEADLY. This dan-
n
gerous gas, if breathed in sufficient con­centrations, can cause unconsciousness or even death. This generator must be installed properly, in strict compliance with applicable codes and standards. Following installation, do nothing that might render the system unsafe or in noncompliance with such codes and standards. Operate the generator outdoors ONLY.
• Keep exhaust gases from entering a confined area through windows, doors, ventilation, crawl spaces or other openings (Figure 1.3).
• It is highly recommended that carbon monox­ide detector(s) be installed indoors according to the manufacturer's instructions/recommen­dations.
• The generator must me mounted safely per applicable codes and the manufacturer's speci­fications. Do NOT alter or add to the exhaust system, or do anything that might render the exhaust system unsafe or in noncompliance with applicable codes and standards.
1.9.1 GENERATOR
Install the generator set, in its protective enclosure, outdoors, where adequate cooling and ventilating air is always available (Figure 1.3). Consider these factors:
The installation of the generator must comply strictly with
NFPA 37, NFPA 58, and NFPA 70 standards.
Install the unit where air inlet and outlet openings will not
become obstructed by leaves, grass, snow, etc.. If prevailing winds will cause blowing or drifting, consider using a wind­break to protect the unit.
Install the generator on high ground where water levels will not
rise and endanger it.
Allow sufficient room on all sides of the generator for mainte-
nance and servicing. This unit must be installed in accordance with current applicable NFPA 37 and NFPA 70 standards; as well as any other federal, state and local codes for minimum distances from other structures. DO NOT install under wooden decks or structures unless there is at least four (4) feet of clear­ance above the generator, three (3) feet of clearance on sides and front, and 18 inches of clearance at back of unit.
Install the unit where rain gutter down spouts, roof run-off,
landscape irrigation, water sprinklers or sump pump discharge does not flood the unit or spray the enclosure, including any air inlet or outlet openings.
6
General Information
Install the unit where services will not be affected or obstructed,
including concealed, underground or covered services such as electrical, fuel, phone, air conditioning or irrigation.
Where strong prevailing winds blow from one direction, face the
generator air inlet openings to the prevailing winds.
Install the generator as close as possible to the fuel supply, to
reduce the length of piping.
Install the generator as close as possible to the transfer switch.
REMEMBER THAT LAWS OR CODES MAY REGULATE THE DISTANCE AND LOCATION.
The genset must be installed on a level surface. The base frame
must be level within two (2) inches all around.
The generator is typically placed on pea gravel or crushed
stone. Check local codes if a concrete slab is required. If a concrete base slab is required, all federal, state and local codes should be followed. Special attention should be given to the concrete base slab which should exceed the length and width of the generator by a minimum of six (6) inches (0.152 meters) on all sides.
Figure 1.3 – Generator Clearances
Annex A — Explanatory Material A4.1.4 (2) Means of demonstrating compliance are by means
of full scale fire test or by calculation procedures.
Because of the limited spaces that are frequently available for installation, it has become apparent that exception (2) would be beneficial for many residential and commercial installations. With that in mind, the manufacturer contracted with an independent testing laboratory to run full scale fire tests to assure that the enclosure would not ignite combustible materials outside the enclosure.
The criteria was to determine the worst case fire scenario within the generator and to determine the ignitability of items outside the engine enclosure at various distances. The enclosure is construct­ed of non-combustible materials and the results and conclusions from the independent testing lab indicated that any fire within the generator enclosure would not pose any ignition risk to nearby combustibles or structures, with or without fire service personnel response.
Based on this testing and the requirements of NFPA 37, Sec 4.1.4, the guidelines for installation of the generators listed above are changed to 18 inches (457mm) from the back side of the genera­tor to a stationary wall or building. For adequate maintenance and airflow clearance, the area above the generator should be at least 4 feet with a minimum of 3 feet at the front and ends of the enclo­sure. This would include trees, shrubs and vegetation that could obstruct airflow. See the diagram on the reverse of this page and the installation drawing within the owner’s manual for details.
Generator exhaust contains DEADLY carbon monoxide gas. This dangerous gas can cause unconsciousness or death. Do not place the unit near windows, doors, fresh air intakes (furnaces, etc.) or any openings in the building or structure, including windows and doors of an attached garage.
1.9.2 NEW INSTALLATION GUIDELINES FOR STATIONARY AIR-COOLED GENERATORS
The National Fire Protection Association has a standard for the installation and use of stationary combustion engines. That standard is NFPA 37 and its requirements limit the spacing of an enclosed generator set from a structure or wall (Figure 1.4).
NFPA 37, Section 4.1.4, Engines Located Outdoors. Engines, and their weatherproof housings if provided, that are installed outdoors shall be located at least 5 ft. from openings in walls and at least 5 ft. from structures having combustible walls. A minimum separa­tion shall not be required where the following conditions exist:
1. The adjacent wall of the structure has a fire resistance rating
of at least 1 hour.
2. The weatherproof enclosure is constructed of noncombus-
tible materials and it has been demonstrated that a fire within the enclosure will not ignite combustible materials outside the enclosure.
If the AUTO/OFF/MANUAL switch is not set to its OFF position, the generator can crank and
start as soon as the battery cables are con-
nected. If the battery charger power supply is not turned off, sparking can occur at the battery posts and cause an explosion.
7
General Information
Figure 1.4 – Installation Guidelines
No windows or openings in the wall permitted
within 5 feet from any point of the generator.
60 inches 60 inches
36 inches
These guidelines are based upon fire testing of the generator enclosure and the manufacturer’s requirement for air flow for proper operation. Local codes may be different and more restrictive than what is described here.
Existing Wall
18 inches
Minimum Distance
Top of Generator
36 inches
Clearance from windows,
36 inches
Clearance from the ends and front of the generator should be 36 inches. This would include shrubs, trees and any kind of vegetation. Clearance at the top should be a minimum of 48 inches from any structure, overhang or projections from the wall. The generator should not be placed under a deck or other structure that is closed in and would limit or contain air flow.
doors, any openings in the wall, shrubs or vegetation over 12” in height
60” Minimum
60” Recommended
Minimum From Ends
Generator
18 inches
Minimum
This drawing supersedes installation instructions in all Carrier air-cooled installation and owners manuals dated
This drawing supersedes installation instructions in all air-cooled installation and owner's manuals dated previous to May 26, 2007.
previous to May 26, 2007.
8
General Information

1.10 BATTERY REQUIREMENTS

See the Specifications section for correct battery size and rating.

1.11 BATTERY INSTALLATION

Fill the battery with the proper electrolyte fluid if necessary and have the battery fully charged before installing it.
Before installing and connecting the battery, complete the follow­ing steps:
1. Set the generator's AUTO/OFF/MANUAL switch to OFF.
2. Turn off utility power supply to the transfer switch.
3. Remove the 7.5A fuse from the generator control panel. Battery cables were factory connected at the generator (Figure
1.5). Connect cables to battery posts as follows:
4. Connect the red battery cable (from starter contactor) to the battery post indicated by a positive, POS or (+).
5. Connect the black battery cable (from frame ground) to the battery post indicated by a negative, NEG or (—).
6. Install battery post covers supplied with the generator.
Figure 1.5 – Battery Cable Connections
NOTE:
Dielectric grease should be used on battery posts to aid in the prevention of corrosion.
NOTE:
Damage will result if battery connections are made in reverse.
NOTE: In areas where temperatures regularly fall below 32° F (0° C) it is recommended that a pad type battery heater be installed to aid in cold climate starting.

1.12 THE BATTERY

Do not dispose of the battery in a fire. The
battery is capable of exploding.
A battery presents a risk of electrical shock
and high short circuit current. The following precautions are to be observed when work­ing on batteries:
• Remove the 7.5A fuse from the generator con­trol panel.
• Remove watches, rings or other metal objects.
• Use tools with insulated handles.
• Wear rubber gloves and boots.
• Do not lay tools or metal parts on top of the battery.
• Disconnect charging source prior to connecting
or disconnecting battery terminals.
Do not open or mutilate the battery. Released electrolyte has been known to
n
be harmful to the skin and eyes, and to be toxic.
The electrolyte is a dilute sulfuric acid that is harmful to the skin and eyes. It is electri-
n
cally conductive and corrosive.
The following procedures are to be observed:
• Wear full eye protection and protective clothing.
• Where electrolyte contacts the skin, wash it off immediately with water.
• Where electrolyte contacts the eyes, flush thor­oughly and immediately with water and seek medical attention.
• Spilled electrolyte is to be washed down with an acid neutralizing agent. A common practice is to use a solution of 1 pound (500 grams) bicarbonate of soda to 1 gallon (4 liters) of water. The bicarbonate of soda solution is to be added until the evidence of reaction (foam­ing) has ceased. The resulting liquid is to be flushed with water and the area dried.
Lead-acid batteries present a risk of fire
because they generate hydrogen gas. The fol­lowing procedures are to be followed:
• DO NOT SMOKE when near the battery.
• DO NOT cause flame or spark in battery area.
• Discharge static electricity from body before touching the battery by first touching a ground­ed metal surface.
Be sure the AUTO/OFF/MANUAL switch is set to the OFF position before connecting
n
the battery cables. If the switch is set to AUTO or MANUAL, the generator can crank and start as soon as the battery cables are connected.
9
Loading...
+ 25 hidden pages