Generac Power Systems C Option, 8617, 9555 Operator's Manual

POWER SYSTEMS, INC.
®
Operator’s Manual
“C” Option Control Panel
This manual should remain with the unit.
NOT IN AUTOMATIC START MODE
OVER
CRANK
OVER SPEED
TEST
RESET
PREHEAT
30 SEC
MAX
PRE ALARM
LOW OFF
HIGH COOL
TEMP.
LOW
OIL
PRESS.
RPM
SENSOR
LOSS
150
200
100
25
TEMP
START
STOP
300
200
100
50
0
100
L
OI
AUTO
MANUAL
OFF
FUSE
15-A AG
A
200
150
100
50
0
40
40
AMPS
C
0
3
1
Hz
0000 1
TOTAL HOURS
60
INCREASE
VO LTAG E
ADJUS
65
T
PRESS
PRE ALARM
HIGH COOL TEMP
LOW COOL TEMP
ALARM HORN
ON - OFF
HIGH
BATT
VOLTA G E
LOW
BATT
VOLTAGE
RUPTURE
BASIN
FILLING
LOW
FUEL
HIGH
FUEL
Generac®Power Systems, Inc.
Important Safety Instructions
“C” Option Control Panel
SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe operation be copied and posted in potential hazard areas. Safety should be stressed to all operators and potential operators of this equipment.
!
!
Study these SAFETY RULES carefully before installing, operating, or servicing this equipment. Become familiar with this manual and all literature pertaining to the generator set and related equip­ment. This equipment can operate safely, efficiently, and reliably only if it is properly installed, operated, and maintained. Many accidents are caused by failing to follow simple and fundamental rules or precau­tions.
Generac cannot possibly anticipate every possible cir­cumstance that might involve a hazard. The warn­ings in this manual, and on tags and decals affixed to the equipment, are, therefore, not all-inclu­sive. If using a procedure, work method, or operating technique Generac does not specifically recommend, you must satisfy yourself that it is safe for you and oth­ers. Also must make sure the procedure, work method, or operating technique that is used does not render the equipment unsafe.
GENERAL HAZARDS
• For safety reasons, Generac recommends that this equipment be installed and serviced by a Generac Authorized Service Dealer or other qualified electri­cian or installation technician who is familiar with applicable codes, standards, and regulations. The operator also must comply with all such codes, stan­dards, and regulations.
• When working on this equipment, remain alert at all times. Never work on the equipment when physical­ly or mentally fatigued.
• Inspect the equipment regularly, and promptly repair or replace all worn, damaged or defective parts, using only factory-approved parts.
• Before performing any maintenance on the generator or any related equipment, disconnect the generator’s battery cables and remove panel fuse to prevent acci­dental startup. Disconnect the cable from the battery post, indicated by a NEGATIVE, NEG, or (–) first. Reconnect that cable last.
ELECTRICAL HAZARDS
• Generators produce dangerous electrical voltages and can cause fatal electrical shock. Avoid contact with bare wires, terminals, connections, etc., while the generator and related equipment are running. Ensure all appropriate covers, guards, and barri­ers are in place before operating the equipment. If working around an operating unit, stand on an insulated, dry surface to reduce potential shock hazards.
• Do not handle any kind of electrical device while standing in water, while barefoot, or while hands or feet are wet. DANGEROUS ELECTRICAL SHOCK MAY RESULT.
• If people must stand on metal or concrete while installing, operating, servicing, adjusting, or repair­ing this equipment, place insulative mats over a dry wooden platform. Work on the equipment only while standing on such insulative mats.
• Wire gauge sizes of electrical wiring, cables, and cord sets must be adequate to handle the maximum elec­trical current (amperage) to which they will be sub­jected to.
• Before installing or servicing this equipment, make sure that all power voltage supplies are positively TURNED OFF at their source. Failure to do so will result in hazardous and possibly fatal electrical shock.
• When installed with an automatic transfer switch, the generator may crank and start anytime, without warning. To prevent injuries caused by sudden start­up, disable the generator’s automatic start circuit before working on, or around, the unit. Then, place a “Do Not Operate” tag on the generator control panel and on the transfer switch.
• In case of an accident caused by electric shock, immediately shut down the source of electrical power. If this is not possible, attempt to free the vic­tim from the live conductor. AVOID DIRECT CON­TACT WITH THE VICTIM. Use a nonconducting implement, such as, a rope or board, to free the vic­tim from the live conductor. If the victim is uncon­scious, apply first aid and get immediate medical help.
• Never wear jewelry when working on this equipment. Jewelry can conduct electricity, resulting in electric shock, or may get caught in moving components, causing injury.
F
IRE HAZARDS
• For fire safety, the generator and related equipment must be installed and maintained properly. Installation always must comply with applicable codes, standards, laws, and regulations. Adhere strictly to local, state, and national electrical and building codes. Comply with regulations the Occupational Safety and Health Administration (OSHA) has established. Also, ensure that the equipment is installed in accordance with the man­ufacturer’s instructions and recommendations. Following proper installation, do nothing that might alter a safe installation and render the unit in noncompliance with the aforementioned codes, standards, laws, and regulations.
!!
Table of Contents
“C” Option Control Panel
Generac®Power Systems, Inc. 1
Part I - C Option Control Panel
Safety Rules ....................................Inside Front Cover
Section 1 — General Information ................................2
1.1 Overview ..............................................................2
1.2 Control Panel Components ..................................2
1.3 Optional Equipment ............................................2
1.3.1 Remote Annunciator Panel......................2
1.3.2 Remote Relay Panel ................................2
1.3.3 Additional Options..................................2
1.4 Panel Face Components ......................................2
1.4.1 AC Voltmeter ..........................................2
1.4.2 AC Ammeter ..........................................2
1.4.3 Frequency Meter ....................................2
1.4.4 Line-Phase Selector Switch ....................3
1.4.5 Voltage Adjust Potentiometer ..................3
1.4.6 Coolant Temperature Gauge ..................3
1.4.7 Oil Pressure Gauge ................................3
1.4.8 DC Voltmeter ..........................................3
1.4.9 Hourmeter ..............................................3
1.4.10 Start/Stop Switch....................................4
1.4.11 Auto/Off/Manual Switch ..........................4
1.4.12 Panel Fuse ..............................................4
1.5 Engine Monitor Panel ..........................................4
1.5.1 Not in Automatic Start Mode Lamp ........4
1.5.2 Overcrank Lamp ....................................4
1.5.3 High Coolant Temperature Lamp............4
1.5.4 Overspeed Lamp ....................................4
1.5.5 Low Oil Pressure Lamp ..........................5
1.5.6 RPM Sensor Loss Lamp..........................5
1.5.7 Test/Reset Switch....................................5
1.6 Optional Annunciator Panel ................................5
1.7 Optional Remote Annunciator..............................6
1.8 Optional Alarm Relay ..........................................6
1.9 Preparation Before Startup ..................................6
1.9.1 Prior to Initial Startup ............................6
1.9.2 Startup Inspection ..................................7
Section 2 — Operation ....................................................7
2.1 Operating Unit with Manually-Operated
Transfer Switch ..................................................7
2.2 Operating Unit with Automatic Transfer Switch ..7
2.2.1 Manual Startup and Transfer ................7
2.2.2 Manual Retransfer and Engine
Shutdown ..............................................7
2.2.3 Preventing Automatic Startup ................8
Appendix 1 – Electrical Data ........................................9
Appendix 2 – Exploded Views and Parts Lists ......16
Appendix 3 – Interconnection Diagrams ................24
P
art II - Remote Annunciator Panels
Section 1 — General Information ..............................29
1.1 Three Light Remote Annunciator ......................29
1.1.1 Installation............................................29
1.2 Five Light Remote Annunciator..........................29
1.2.1 Operation..............................................30
1.2.2 Customer Connections..........................30
1.2.3 Parts Included with Remote Panel ........30
1.3 18 Light Remote Annunciator ............................30
1.3.1 Generator Stop Signals ........................31
1.3.2 Latchable Signals..................................31
1.3.3 Other Lamps ........................................31
1.3.4 Panel Wiring Interconnections ..............31
1.4 Troubleshooting ................................................31
1.5 Annunciated Signals ..........................................32
1.6 Pre-Alarms ........................................................32
Appendix 4 — Electrical Data......................................33
Appendix 5 — Exploded Views and Parts Lists ......41
Appendix 6 — Notes ......................................................47
AUTHORIZED SERVICE
DEALER LOCATION
To locate the nearest GENERAC AUTHORIZED
SERVICE DEALER, please call this number:
1-800-333-1322
DEALER LOCATION INFORMATION
CAN BE OBTAINED AT THIS NUMBER.
1.1 OVERVIEW
The “C” option control panel is an analog generator set control panel designed for Generac’s range of standby generators. It allows for either manual or automatic startup and shutdown.
The panel is housed in a steel sheet metal enclosure that meets NEMA 1 specifications. The front face of the panel includes a number of analog meters and gauges that indicate generator operating conditions, several indicator lamps for annunciation of engine fault shutdowns, and various other generator set con­trols.
1.2 CONTROL PANEL COMPONENTS
The control panel contains one main printed-circuit board (PCB), the automatic voltage regulator (AVR), optional components, such as battery monitor, dry contact boards, run relay, etc., and terminal blocks for external connections.
To find locations of the circuit board, refer to Appendix 2 for the control panel exploded view.
Remove the 15-amp fuse from the front of the panel during all engine maintenance to guard against accidental or remote startup.
1.3 OPTIONAL EQUIPMENT
1.3.1 REMOTE ANNUNCIATOR PANEL
When connected to the generator via a 19 wire connec­tion link, this multi-light remote indicator panel will display the generator’s status.
1.3.2 DRY CONTACTS
This panel is similar to the remote annunciator, but, in addition to indicator lights, it provides relay contact closures for status (e.g., alarms). The dry contact boards are form C rated contacts. The five function dry contacts are normally open (N.O.). The six function dry contacts are either normally open (N.O.) or normally closed (N.C.).
1.3.3 ADDITIONAL OPTIONS
The following are some of the more frequently request­ed optional accessories for the “C” option control panel:
• Emergency stop button
• Oil temperature gauge
• Engine run relay
• 100 dBa alarm horn
• Over/Under voltage relay
• Pre-alarm kit
• Control panel heater(s)
• Voltage change over switch (special)
• Battery monitor
• Over/Under frequency relay
• Over/Under current relay
1.4 PANEL FACE COMPONENTS
(FIGURE 1.1, PAGE 3)
1.4.1 AC VOLTMETER
This meter indicates the generator AC output voltage. (Also see “Line-phase Selector Switch” and “Voltage Adjust Potentiometer” in this section). To determine the nominal rated AC voltage of the unit, refer to the unit’s data plate.
NOTE:
Some generators are reconnectable to a variety of voltages. Some units may be equipped with a rotary “Voltage Selector Switch.” Be sure to read the “Generator AC Lead Connections” section in the Owner’s Manual.
1.4.2 AC AMMETER
This meter indicates the current draw of connected electrical loads, in amps. (Also see “Line-phase Selector Switch”). For continuous operation, never exceed the rated maximum continuous current capacity of the generator.
1.4.3 FREQUENCY METER
This meter indicates the generator’s AC output fre­quency in “Hertz” (cycles per second).
!
Section 1 — General Information
“C” Option Control Panel
2 Generac®Power Systems, Inc.
Generac®Power Systems, Inc. 3
1.4.4 LINE-PHASE SELECTOR SWITCH
This four-position switch permits selection of either line-to-line or line-to-neutral readings on the panel voltmeter and ammeter. Switch positions are as fol­lows:
1.4.5 VOLTAGE ADJUST POTENTIOMETER
This potentiometer permits the operator to “fine­adjust” the generator’s AC output voltage. Adjustment range is plus or minus five percent from the mid­point. Turn the knob clockwise to increase voltage, counterclockwise to decrease voltage.
1.4.6 COOLANT TEMPERATURE GAUGE
This gauge indicates the engine coolant temperature. Normal operating temperature should read between 185° to 215°F (85° to 102°C). If coolant temperature exceeds a safe level, the engine shuts down automat­ically.
NOTE:
Actual coolant temperature reading may vary due to variables, such as, ambient temperature, applied load, or cooling system condition.
1.4.7 OIL PRESSURE GAUGE
This gauge indicates oil pressure during operation. After warm-up, oil pressure should be about 25-90 psi. Generac recommends that the operator record the normal oil pressure during initial startup. Sudden changes in oil pressure after first starting indicate a possible engine problem.
NOTE:
Engine oil pressure may vary, depending on oil viscosity, oil temperature, engine speed, ambient temperature, etc. The engine automatically shuts down if oil pressure drops below a safe level. (10 psi.)
1.4.8 DC AMMETER
The engine is equipped with a belt-driven DC alter­nator, which charges the battery while the unit is run­ning. This ammeter indicates the rate of charge to the battery during operation. If the needle drops to the left of zero, the battery is discharging. Investigate and correct this problem immediately. Erratic movement of the needle should also be corrected immediately.
1.4.9 HOURMETER
The hourmeter provides a continuous indication of engine/generator operating time, in hours and tenths of hours. Use the hourmeter with the periodic main­tenance schedule.
Section 1 — General Information
“C” Option Control Panel
Figure 1.1 – “C” Option Panel Components
Switch Single-phase Units Three-phase units
1 Line E1 to Neutral Line E1 to E2
2 Line E3 to Neutral Line E2 to E3
3 Line E1 to E3 Line E3 to E1
O No Reading No Reading
0
1
2
4 Generac®Power Systems, Inc.
1.4.10 START/STOP SWITCH
Use this switch to crank and start the engine manu­ally, or to shut down an operating engine.
• To crank and start engine, first set the
Auto/Off/Manual switch to its “Manual” position.
• Hold the Start/Stop switch at “Start.” When the
engine starts, release the switch to its center (run) position.
• To shut engine down, move the switch to its “Stop”
position.
1.4.11 AUTO/OFF/MANUAL SWITCH
This safety switch should be used to prevent auto­matic startup of the engine when working on the engine/generator. Use the switch as follows:
Auto Position
Always set switch to AUTO for automatic system operation. This means that, when this generator is installed with a GTS-type automatic transfer switch, the generator automatically cranks and starts when the utility source voltage drops below a preset level, or the unit exercises, if programmed to do so.
Off Position
The engine cannot be started either automatically or manually. Always set switch to OFF before working on, or around, the engine-generator.
Manual Position
The engine can be cranked and started manually using the panel Start/Stop switch. The engine will not start automatically.
NOTE:
Also see “Engine Monitor Panel.” With switch set to either OFF or MANUAL, a “Not in Automatic Start Mode” lamp lights up on the panel.
1.4.12 PANEL FUSE
This fuse protects the control console’s DC circuits against overload. If the fuse element melts open due to an overload, engine cranking and startup will not be possible. Should fuse replacement become neces­sary, use only an identical fuse (part number
022676).
1.5 ENGINE MONITOR PANEL
This panel has five advisory shutdown lamps for sep­arate engine fault conditions, plus a “Not in Automatic Start Mode” lamp. Cranking and starting will not be possible while any one, or more, of engine fault conditions lamps is lit, with the exception of “Not in Auto” illuminated in the manual mode. The following apply:
• A “lamp ON” condition indicates that fault condi­tion has been “latched” by DC control/latch-crank circuit board.
• If any one of the lamps is ON (fault condition latched), the engine cannot be cranked either man­ually or automatically.
• To unlatch a fault (that is, to turn a lamp OFF) and permit cranking, push the Test/Reset switch in. The lamp will then go OFF, allowing for additional cranking.
1.5.1 NOT IN AUTOMATIC START MODE LAMP
This lamp comes ON to indicate that automatic start­up of the engine is not possible. The lamp lights up whenever the Auto/Off/Manual switch is set to OFF or MANUAL.
1.5.2 OVERCRANK LAMP
The control console houses a DC control/latch-crank circuit board (the “C” board) that controls engine startup and shutdown. During automatic startup, the engine cranks for about 14 seconds, rests for about eight seconds, and so on, until eight crank-rest cycles have occurred. At the end of eight attempts, cranking stops, and the overcrank lamp goes ON.
1.5.3 HIGH COOLANT TEMPERATURE LAMP
This lamp comes ON if coolant temperature is too high or coolant level is too low. The engine shuts down automatically when such unsafe conditions occur. The following apply:
• If the engine is started with an existing high coolant temperature or low coolant level condition, the engine shuts down, and the lamp comes ON when engine speed reaches about 1000 rpm.
• If the engine starts normally but high tempera­ture/low coolant level develops later, the engine shuts down, and the light comes ON immediately.
1.5.4 OVERSPEED LAMP
An engine overspeed above a safe limit causes the engine to automatically shut down, which turns ON the indicator lamp. The overspeed lamp comes on when the unit is run at a 15% faster rpm than rated.
Section 1 — General Information
“C” Option Control Panel
Generac®Power Systems, Inc. 5
1.5.5 LOW OIL PRESSURE LAMP
This lamp lights up (latches) to indicate low oil pres­sure in the engine as follows:
• During cranking, after engine has reached 800 to 1000 rpm, the circuit allows four seconds for oil pressure to build.
• In auto mode, if the unit runs above 800-1000 rpm for more than four seconds, and oil pressure is below a safe level, the engine shuts down, but the lamp does NOT go ON. The system then actuates eight restart attempts; the engine shuts down, and the lamp goes ON.
• If the engine starts normally with good oil pres­sure, but oil pressure drops later, the system waits five seconds for oil pressure to be restored. If pres­sure is still low after a five-second delay, the engine shuts down, and the lamp goes ON immediately.
1.5.6 RPM SENSOR LOSS LAMP
Units with the “C” Option console are equipped with an rpm sensor, which is mounted directly over the engine flywheel gear teeth. This sensor is a magnetic pickup that emits an electrical pulse at the passage of each flywheel gear tooth. Sensor electrical signals are used by the DC control/latch-crank circuit board as engine speed (rpm) signals. The circuit board uses these rpm signals (a) to establish a starter lockout speed, and (b) to shut down the engine if the engine runs too fast (overspeed). If the rpm signals to the circuit board are lost, engine shutdown occurs, but the lamp will not light, (i.e., the condition will not latch), then, depending on whether the sensor signal loss occurred during a manual or an automatic start attempt, the following events occur:
Manual Startup
If the engine starts within two seconds after cranking begins, shutdown occurs as soon as the Start/Stop switch is released, but without a lamp ON condition (latching does not occur). If engine does not start within two seconds after cranking begins, which dis­ables starting, the rpm sensor loss light goes ON.
Automatic Startup
The engine recranks within about one second after it has stopped. If sensor loss persists, engine shuts down, and lamp lights about two seconds after cranking has restarted.
If engine starts within two seconds after recrank has begun, the starter remains engaged until the two-sec­ond delay is over.
1.5.7 TEST/RESET SWITCH
To test all lamps, push this switch in. Following any fault shutdown with any monitor panel lamp illumi­nated, engine cranking is inhibited. To reset the sys­tem (unlatch a fault) and crank the engine again, push the switch in (lamp must go out). If the switch is actuated with the engine running, only the lamps will be tested. The engine will not shut down.
NOTE:
If engine shuts down due to some unmonitored problem (such as, out of fuel or failed ignition sys­tem), none of the lamps will come ON. If such an unmonitored shutdown occurs with the Auto/Off/Manual switch set to AUTO, engine recranks and attempts to start for any of the cycles remaining in the eight-crank limit. After all eight crank cycles have been used, the engine shuts down, and the OVERCRANK lamp goes ON.
1.6 OPTIONAL ANNUNCIATOR PANEL
Some units may come equipped with a factory­installed annunciator panel having up to nine annun­ciated fault conditions displayed (Figure 1.2). This optional panel is often called a “prealarm” panel, since it warns of impending problems before an actu­al fault shutdown occurs.
The panel is designed to monitor various engine con­dition-sensing devices having normally-open (N.O.) or normally-closed (N.C.) contacts.
Figure 1.2 — Optional Annunciator (Prealarm)
Panel
Section 1 — General Information
“C” Option Control Panel
PRE-ALARM
LOW OIL
PRESSURE
PRE-ALARM HIGH COOL
TEMP
LOW COOL
TEMP
LOW FUEL
ALARM HORN
ON/OFF
HIGH BATTERY VOLTAG E
LOW BATTERY VOLTAG E
HIGH OIL TEMP
SHUTDOWN
HIGH
OIL TEMP
PRE-ALARM
6 Generac®Power Systems, Inc.
1.7 OPTIONAL REMOTE ANNUNCIATOR
An optional 18-light REMOTE annunciator panel that can be mounted on a wall (Figure 1.3) is also avail­able. For information on the remote annunciator pan­els, ask the local dealer/distributor or consult the fac­tory. Ask for information on the Models 9555 and 9556 remote annunciator panels. The following apply to the remote annunciator panels:
• It is designed for use with installation having a
Generac Power Systems GTS-type transfer switch and a “C” Option control panel.
• The panel is available in both flush-mounted
(Model 9556) and surface-mounted (Model 9555) configurations.
• The panel has a built-in audible alarm horn, with a
reset switch to turn off the horn without disturbing the lighted indication.
• Remote monitoring of the standby generator set
provides enough information to avoid unnecessary maintenance trips to the generator site.
Figure 1.3 — Optional 18-Light Remote
Annunciator
1.8 STANDARD ALARM RELAY
The generator’s DC control/latch-crank circuit board is equipped with an alarm relay “driver”. All units with “C” Option control panels are equipped with an alarm relay that is connected to the circuit board driver (Figure 1.4). If any one or more of the five annunciated shutdown faults occur, the circuit board driver energizes the optional alarm relay.
A remote-mounted alarm or annunciator device may be connected across the relay contacts so that a fail­ure will turn on the remote alarm or device. The con­nected alarm device may range from an alarm horn to a warning light to a telephone dialer with a pre­recorded message. The alarm relay normally-open, normally-closed, and common contacts are shown in Figure 1.4.
Figure 1.4 — Standard Alarm Relay
1.9 PREPARATION BEFORE STARTUP
The instructions in this section assume that the standby generator has been properly installed, serv­iced, tested, adjusted, and otherwise prepared for use by a competent, qualified installation contractor. Be sure to read RULES FOR SAFE OPERATION on the inside of the front cover carefully, before attempt­ing to operate this (and related) equipment.
1.9.1 PRIOR TO INITIAL STARTUP
Before starting the generator for the first time, the installer must complete the following:
• Properly locate and properly mount the generator, transfer switch, and other standby system compo­nents, in strict compliance with applicable codes, standards, and regulations.
• Make sure the fuel supply system to the generator (a) delivers the correct fuel at the correct pressure, and (b) is properly purged and leak-tested accord­ing to code. No fuel leakage is permitted.
• Have the engine crankcase properly filled to the correct level with the recommended oil.
• Have engine cooling system properly filled with rec­ommended coolant mixture. Check the system for leaks and other problems.
• If engine is equipped with a mechanical governor, make sure the governor is properly filled with oil. Use crankcase oil to fill.
• Check engine v-belt tension and belt condition.
• Make sure the generator is properly connected to an approved earth ground.
• The generator battery must be fully charged, prop­erly installed and interconnected, and ready for use.
Section 1 — General Information
“C” Option Control Panel
Generac®Power Systems, Inc. 7
1.9.2 STARTUP INSPECTION
A standard, three-part form entitled “Startup Inspection for Standby Power Systems” (Part No.
67377) must be completed by the installation techni­cian or engineer in order to activate warranty. As stat­ed on the form, inspections are to be performed only by factory-trained personnel. The installer must com­plete the form and distribute copies as follows:
• White copy: Mail to Generac Service Department, P.O. Box 310, Eagle, WI 53119.
• Pink copy: For service file of installing dealer.
• Yellow copy: For the customer’s records.
2.1 OPERATING UNIT WITH MANUALLY
OPERATED TRANSFER SWITCH
If the generator was installed with a transfer switch capable of manual operation only, the following applies: A manually-operated transfer switch is one that will not provide automatic startup and does not include the intelligence circuit, which comprises of a utility voltage sensor PCB, an inphase monitor PCB, a seven day exerciser PCB, or other type of sensing circuits found in a Closed Transition Transfer Switch (CTTS) or a Bypass Isolation Switch (BIS).
2.2 OPERATING UNIT WITH
AUTOMATIC TRANSFER SWITCH
If the generator has been installed with a Generac “GTS”-type automatic transfer switch, the engine may be started and stopped either automatically or manually.
IMPORTANT: BE SURE TO READ THE APPLICA­BLE AUTOMATIC TRANSFER SWITCH MANUAL CAREFULLY. DIFFERENCES EXIST BETWEEN TRANSFER SWITCHES.
2.2.1 MANUAL STARTUP AND TRANSFER
To crank and start the engine and to transfer electri­cal loads to the STANDBY power source, proceed as follows:
• See applicable transfer switch instructions. If so equipped, set the Safety Disconnect Switch to MANUAL.
• On the generator’s Meter and Control Panel, set the Auto/Off/Manual switch to MANUAL.
The safety disconnect switch and the Auto/Off/Manual switches must be set as instructed above, or the generator will crank and start as soon as the utility power to the transfer switch is turned OFF.
• Turn OFF both the NORMAL (utility) and EMER­GENCY (standby) power supplies to the transfer switch, using whatever means is provided (such as the main-line circuit breaker(s).
DO NOT attempt manual operation until all power voltage supplies to the transfer switch have been positively turned OFF; otherwise, extremely dangerous---possibly lethal--- elec­trical shock will result.
• Refer to the instructions that correspond to the installed transfer switch. Manually actuate the switch main contacts to their STANDBY (emer­gency) position, as outlined in the corresponding manual. LOAD circuit must be connected to the STANDBY power supply before proceeding.
• On the generator console, hold the Start/Stop switch START to crank the engine. Hold it until it begins running, then release the switch to its cen­tered (RUN) position.
• Let the engine warm up and stabilize at no-load.
• Turn ON the STANDBY power supply to the trans­fer switch, using whatever means provided (such as STANDBY source main-line circuit breaker).
• The generator will now power the load circuits.
2.2.2 MANUAL RETRANSFER AND ENGINE SHUTDOWN
To retransfer LOAD circuits back to the NORMAL (utility) power source and to stop the engine, proceed as follows:
• Turn OFF both the UTILITY and STANDBY power supplies to the transfer switch, using whatever means provided, such as the main-line circuit breaker(s).
DO NOT attempt manual operation until all power voltage supplies to the transfer switch have been positively turned OFF; otherwise, extremely dangerous---possibly lethal---elec­trical shock will result.
• Refer to the applicable transfer switch instruc­tions. Manually actuate the transfer switch main contacts to their utility position (LOAD connected to UTILITY power supply).
• Turn ON the UTILITY power supply to the transfer switch, using whatever means are provided (such as the UTILITY main-line circuit breaker(s).
• Check that the UTILITY voltage is available to the transfer switch (see appropriate transfer switch instructions).
• Let the generator engine run at no-load for a few minutes. Then, set the generator Start/Stop switch to STOP. Wait for the engine to come to a complete stop.
• Reset the system for fully automatic operation.
Section 2 — Operation
“C” Option Control Panel
DANGER
DANGER
DANGER
!
8 Generac®Power Systems, Inc.
2.2.3 PREVENTING AUTOMATIC STARTUP
When installed with an automatic transfer switch, Generac standby generators can crank and start suddenly, without warning, when UTILITY source voltage drops below a preset value. To prevent possible injuries caused by such sudden starts, disable the automatic transfer switch before working on, or around, the generator. Use any one, or more, of the fol­lowing methods to disable the automatic start function:
• Set the generator’s Auto/Off/Manual switch to OFF. Neither a manual nor an automatic start can be accomplished with this switch set to OFF.
• Remove the fuse from the generator control panel. To remove the fuse, push fuse holder cap in and turn cap counterclockwise. Remove cap and fuse element.
• Refer to the automatic transfer switch instructions. If the transfer switch is so equipped, set its Safety Disconnect switch to MANUAL position to prevent automatic startup and transfer.
• Disconnect battery cable from generator battery post, indicated by a negative, NEG, or (-).
!
Section 2 — Operation
“C” Option Control Panel
DANGER
Generac®Power Systems, Inc. 9
Appendix 1 — Electrical Data
“C” Option Control Panel 24 Volt, 400 kW and Larger
Interconnection Diagram — Drawing No. A7296-B
10 Generac®Power Systems, Inc.
Appendix 1 — Electrical Data
“C” Option Control Panel 24 Volt, 400kW and Larger Electrical Schematic — Drawing No. A4722-A
Generac®Power Systems, Inc. 11
Appendix 1 — Electrical Data
“C” Option Control Panel 24 Volt, 400 kW and Larger
Wiring Diagram – Drawing No. A4723-B
12 Generac®Power Systems, Inc.
Appendix 1 — Electrical Data
“C” Option Control Panel 24 Volt Diesel, Less than 400 kW Control Panel Electrical Schematic – Drawing No. 84850-C
Generac®Power Systems, Inc. 13
Appendix 1 — Electrical Data
“C” Option Control Panel 24 Volt Diesel, Less than 400 kW
Control Panel Wiring Diagram – Drawing No. 84849-C
14 Generac®Power Systems, Inc.
Appendix 1 — Electrical Data
“C” Option Control Panel 12 Volt Gas Control Panel Electrical Schematic – Drawing No. 85023-A
Generac®Power Systems, Inc. 15
Appendix 1 — Electrical Data
“C” Option Control Panel 12 Volt Gas
Control Panel Wiring Diagram – Drawing No. 85024-A
C
3
-
+
0
0
16 Generac®Power Systems, Inc.
Appendix 2 — Exploded Views and Parts Lists
“C” Option Control Panel 24 Volt Diesel Control Panel – Drawing No. 84851-J
4
7
4
2
1
1
7
7
7
2
1
7
A
4
I
Generac®Power Systems, Inc. 17
ITEM PART NO. QTY. DESCRIPTION
1 070023 1 CONTROL PANEL BOTTOM 2 070026 1 SLKSCRND PANEL FRONT 3 070028 1 COVER CON PNL SIDE 4 067680 1 ASSY VOLTAGE REGULATOR 60HZ
092952 1 ASSY VOLTAGE REGULATOR 50HZ 5 039271 1 FITTING 90 DEGREE 3/4 6 034616 1 FITTING STRAIGHT 3/4 7 1 CIRCUIT BREAKER 8 082985 1 RES 100R 5% 5W ASSY=55405 9 082984 1 RES 120R 10% 2W ASSY 55406
10 086266 1 RES WW LUG 75R 5% 25W 11 055444 1 HEATSINK 12 030468 1 WASHER STEP NYLON .20 13 049939 1 RECTIFIER MSC 12A 600V 1N1206R 14 083089 1 ASSY PCB "C" CONTROL 12/24V 15 033147 1 SCREW HHM #10-32 X 1 16 024469 2 SCREW HHTT #10-32 X 3/8 CZ_ 17 084853A 1 HARNESS F/<100KW 24V C DIESEL
084853B 1 HARNESS F/>101KW 24V C DIESEL
084853C 1 HARNESS F/12LMITS 24V C DIESEL
18 029333 6 TIE WRAP 7.4"X.19" NATL UL 19 084875 1 DECAL TERMINAL STRIP 20 055920 1 SWITCH SPST SPADE PNL MNT 21 055867 1 SWITCH TOG SPDT 15A SPD MOM 22 067625 1 SWITCH TOGGLE 3P3T 15/10A 23 032300 1 HOLDER FUSE 24 022676 1 FUSE 15A X AGC15 25 040213 4 PCB SUPPORT SNAP-IN 1/4" 26 0C2428 14 SCREW PHTT #6-32 X 1/2 ZYC 27 061945 1 SWITCH SELECTOR 6A AMP/V 28 071361 1 POT 5K 10% 2.25W PNL 29 050123 1 KNOB PLASTIC .25 SHAFT 30 055349 1 INSULATOR 31 070030 1 COVER GENERAC SILKSCREENED 33 070042 1 FREQUENCY METER 240V 55-65HZ
070042-A 1 FREQUENCY METER 240V 45-55HZ
34 1 AC AMMETER 35 1 AC VOLTMETER 36 083287 1 LIGHT HLDR CLR LNS W/O BULB
ITEM PART NO. QTY. DESCRIPTION
37 070081 1 HOURMETER 38 062304 1 AMMETER 40-0-40 DC 39 055405 1 GAUGE OIL PRESSURE 40 055406 1 GAUGE COOLANT TEMPERATURE 41 070083 1 ASSY PCB ENGINE MONITOR 42 055089 1 CONN PLUG PNL 15P AMP M-N-L 43 070082 1 BLOCKER LIGHT 44 053247 1 LUG RNGTNG INS 22-18 X10 X.322 45 029187 2 SPACER .19 X .31 X .50 PL 46 077043B 1 FLEX CONDUIT .50 ID 50 036904 4 SCREW PPHM #6-32 X 3/4 (NOT SHOWN) 51 036908 2 SCREW PPHM #6-32 X 1-1/4 52 022155 2 WASHER LOCK #6 53 022985 6 WASHER FLAT #6 ZINC 54 022188 2 NUT HEX #6-32 STEEL 55 036918 4 SCREW PPHM #8-32 X 1/2 56 022264 4 WASHER LOCK #8-M4 57 033121 16 SCREW HHC #10-32 X ½ 58 022152 26 WASHER LOCK #10 59 023897 14 WASHER FLAT #10 ZINC 60 022158 20 NUT HEX #10-32 STEEL 61 038150 4 WASHER FLAT #8 ZINC 62 022471 4 NUT HEX #8-32 STEEL 63 084787 1 CABLE RIBBON 16" 64 070370 2 WASHER MICA .203 65 083288 1 LIGHT 28VDC .17A MIN BAYNT MNT 66 023762 4 WASHER SHAKEPROOF EXT #10 STL 68 081767 2 RELAY PNL 24VDC DPDT 10A 70 064000 1 CONTROL PNL SIDE 71 064008 1 COVER CON PNL TOP 72 098940 1 HARNESS C-OPT CTRL PNL 73 066040 1 DECAL - TERM STRIP 77 0C2323 4 SCREW PHTT #6-32 X 5/8 ZYC 78 0C1229 1 DECAL CUST CONN BOX 79 022507 4 SCREW HHC 1/4-20 X 1/2 G5 (NOT
SHOWN) 80 022097 8 WASHER LOCK M6-1/4 (NOT SHOWN) 81 040479 4 VIB MNT 1.0 X 1.0 X 1/4-20 (NOT SHOWN)
Appendix 2 — Exploded Views and Parts Lists
“C” Option Control Panel 24 Volt Diesel
Control Panel – Drawing No. 84851-J
18 Generac®Power Systems, Inc.
5
5
3
6
3
0
0
9
9
5
9
625
9
3
0
3
9
0
S
O
O
SS
S
.
G
G
8
6
3
O
+
-
)
CA
Appendix 2 — Exploded Views and Parts Lists
“C” Option Control Panel 24 Volt Gas Control Panel – Drawing No. 84711-N
4
1
2
282
4
1
1
4
4
2
2
4
1
M A
R F
7 4
RAM #
F WIRE HARNE N
DIA
TALLATI
EE WIRIN
IN
4
4
1
7
MI
2-PLCS
7
Generac®Power Systems, Inc. 19
ITEM PART NO. QTY. DESCRIPTION
1 070023 1 CONTROL PANEL BOTTOM 2 070026 1 CONTROL PANEL FRONT 3 070028 1 CONTROL PANEL SIDE 4 067680 1 REGULATOR ASSEMBLY VOLTAGE B&D 5 039271 1 FITTING 90 DEGREE 3/4 6 034616 1 FITTING STRAIGHT 3/4 7 057159 1 CIRCT BRK 2 X 1 ETA 46-500-P
053623 1 CIRCT BRK 2.5 X 1 ETA 46-500-P 054502 1 CIRCT BRK 3 X 1 ETA 46-500-P 056247 1 CIRCT BRK 3.5 X 1 ETA 46-500-P 049350 1 CIRCT BRK 4 X 1 ETA 46-500-P 048476 1 CIRCT BRK 4.5 X 1 AUT30KW CNT45K 048512 1 CIRCT BRK 5 X 1 ETA 46-500-P 054450 1 CIRCT BRK 5.5 X 1 ETA 46-500-P 048505 1 CIRCT BRK 6 X 1 ETA 46-500-P 048467 1 CIRCT BRK 7 X 1 ETA 46-500-P 048468 1 CIRCT BRK 8 X 1 ETA 46-500-P
048470 1 CIRCT BRK 9 X 1 ETA 46-500-P 8 057335 1 BLOCK TERM 20A 20 X 6 X 1100V 9 046669 7 BLOCK TERM JUMPER FOR S141
10 ** 081767 1 RELAY PNL 24VDC DPDT 10A 11 070042 1 METER FREQUENCY 55-65HZ
070042A 1 METER FREQUENCY 240V 45-55HZ
12 070054 1 AMMETER AC 0 TO 50
070055 1 AMMETER AC 0 TO 100
070056 1 AMMETER AC 0 TO 150
070045 1 AMMETER AC 0 TO 200
070057 1 AMMETER AC 0 TO 300
070058 1 AMMETER AC 0 TO 400
070059 1 AMMETER AC 0 TO 600
070060 1 AMMETER AC 0 TO 800
13 070043 1 METER VOLT AC 0-300
070044 1 METER VOLT AC 0-600
14 083089 1 ASSY BOARD "C" CONTROL 12/24V 15 0C2428 8 SCREW TAPTITE PH #6-32 X 1/2 ZYC 17 064000 1 CONTROL PANEL SIDE 18 064008 1 COVER CONTROL PANEL TOP (NOT
SHOWN) 19 084736 1 DECAL TERMINAL STRIP 20 026536 1 PLUG STEEL 0.5 21 055867 1 SWITCH SPDT 15A SPD TGGL MOM 22 067625 1 SWITCH 3P TRIP THR 15/10A TGGL 23 032300 1 HOLDER FUSE 24 022676 1 FUSE 15A X AGC15 25 040213 4 PCB SUPPORT SNAP-IN 1/4 26 024469 2 SCREW TAPTITE #10-32 X 3/8 BP 27 061945 1 SWITCH 6A AMP/V SELECTOR 28 071361 1 POTENTIOMETER 5K +/-10% 2.25W PNL 29 050123 1 KNOB PLASTIC .25 SHAFT 30 055349 1 INSULATOR 31 070030 1 COVER GENERAC SILKSCREEN
ITEM PART NO. QTY. DESCRIPTION
32 * 084717 1 ASSEMBLY TIME RELAY 33 084733 1 HARNESS CONTROL PANEL C 34 083287 1 LIGHT HLDR CLR LNS W/O BULB 35 083288 1 LIGHT 28V DC .17A MIN BAYNT MNT 37 070081 1 METER HOURS 38 062304 1 AMMETER 40-0-40 DC 39 055405 1 GAUGE OIL PRESSURE 40 055406 1 GAUGE COOLANT TEMPERATURE 41 066040 1 DECAL TERMINAL STRIP 42 055089 1 CONN ELEC AMP M-N-L 15 PLUG PNL 43 070082 1 BLOCKER LIGHT 44 053247 1 LUG RNGTNG INS 22-18 X 10 X .322 45 029187 2 SPACER .19 X .31 X .50 ST/ZNC 46 077043B 16" FLEX CONDUIT .50 ID 47 029333 6 TIE WRAP 7" WHITE 49 0C2323 10 SCREW PHM SWAGE 6-32 X 5/8 Z/YC 50 036904 2 SCREW PPHM #6-32 X 3/4 (NOT SHOWN) 51 036908 2 SCREW PPHM #6-32 X 1-1/4 52 022155 2 WASHER LOCK #6 53 022985 6 WASHER FLAT #6-M4 54 022188 2 NUT HEX #6-32 STEEL 55 036918 4 SCREW PPHM #8-32 X 1/2 56 022264 11 WASHER LOCK M4 57 033121 14 SCREW HHM 10-32 X 1/2 58 022152 22 WASHER LOCK #10 59 023897 15 WASHER FLAT #10 ZINC 60 022158 11 NUT HEX #10-32 STEEL 61 038150 8 WASHER FLAT #8 ZINC 62 022471 4 NUT HEX #8-32 STEEL 63 084787 1 CABLE RIBBON 16" 64 070083 1 ASSEMBLY ENGINE MONITOR 65 082985 1 ASSEMBLY RESISTER 68 OHM 5W 66 082984 1 ASSEMBLY RESISTER 120 OHM 2W 67 098940 1 HARNESS C-OPT CTRL PNL 69 023762 3 WASHER SHAKEPROOF EXT #10 STL 70 055444 1 SINK HEAT 71 030468 1 WASHER STEP NYLON .20 72 049939 1 RECTIFIER MSC 12A 600V 1N1206R 73 070370 2 WASHER MICA .203 75 086266 1 RESISTOR WW LUG 75R 5% 25W 76 022507 4 SCREW HHC 1/4-20 X 1/2 G5 (NOT
SHOWN) 77 022097 8 WASHER LOCK M6-1/4 (NOT SHOWN) 78 040479 4 MOUNT VIBR 1.0 X 1.0 X 1/4-20 (NOT
SHOWN) 79 0441140156 1 WIRE ASSY 18AWG #0 (NOT SHOWN) 80 033147 1 SCREW HHM #10-32 X 1 (NOT SHOWN) 81 0C1299 1 DECAL WARNING
* USED ON 13.3L SPARK IGNITED ONLY ** USED ON 13.3L TURBO SPARK ONLY
Appendix 2 — Exploded Views and Parts Lists
“C” Option Control Panel 24 Volt Gas
Control Panel – Drawing No. 84711-N
20 Generac®Power Systems, Inc.
Appendix 2 — Exploded Views and Parts Lists
“C” Option Control Panel 12 Volt Diesel Control Panel – Drawing No. 85027-H
Generac®Power Systems, Inc. 21
ITEM PART NO. QTY. DESCRIPTION
1 070023 1 CONTROL PANEL BOTTOM 2 070026 1 CONTROL PANEL FRONT 3 070028 1 CONTROL PANEL SIDE 4 067680 1 REGULATOR VOLT 60HZ
092952 1 REGULA TOR VOLT 50HZ 5 039271 1 FITTING 90 DEGREE 3/4 6 034616 1 FITTING STRAIGHT 3/4 7 057159 1 CIRCT BRK 2 X 1 ETA 46-500-P
053623 1 CIRCT BRK 2.5 X 1 ETA 46-500-P
054502 1 CIRCT BRK 3 X 1 ETA 46-500-P
056247 1 CIRCT BRK 3.5 X 1 ETA 46-500-P
049350 1 CIRCT BRK 4 X 1 ETA 46-500-P
048476 1 CIRCT BRK 4.5 X 1 AUT 30KW CNT45K
048512 1 CIRCT BRK 5 X 1 ETA 46-500-P
054450 1 CIRCT BRK 5.5 X 1 ETA 46-500-P
048505 1 CIRCT BRK 6 X 1 ETA 46-500-P
048467 1 CIRCT BRK 7 X 1 ETA 46-500-P
048468 1 CIRCT BRK 8 X 1 ETA 46-500-P
048470 1 CIRCT BRK 9 X 1 ETA 46-500-P 8 044213 1 RESIST MISC 10R X 12W 9 025192 1 RECTIFIER MSC 2A 600V 1N5062
10 048352 1 RESIST MISC 5R X 25W
057907 1 RESISTOR WW LUG 10R 10% 25W
057405 1 RESIST MISC 25R X 25W
11 055444 1 HEAT SINK 13.3L 12 030468 1 WASHER STEP NYLON .20 13 049939 1 RECTIFIER MSC 12A 600V 1N1206R 14 083089 1 BOARD "C" CONTROL 12/24V 15 024469 2 SCREW TAPTITE #10-32X3/8 BP 17 085058 1 HARNESS 12 VOLT DIESEL 18 029333 6 TIE WRAP 7" WHITE 19 070097 1 DECAL TERMINAL STRIP 20 055920 1 SWITCH 1PST PSADE PNL MNT 21 055867 1 SWITCH SPDT 15A SPD TGGL MOM 22 067625 1 SWITCH 3P TRIP THR 15/10A TGGL 23 032300 1 HOLDER FUSE 24 022676 1 FUSE 15A X AGC15 25 040213 4 CONN PCB SUP SNAP-IN 26 0C2428 8 SCREW TAPTITE PH #6-32 X 1/2 ZYC 27 061945 1 SWITCH 6A AMP/V SELECTOR 28 071361 1 POTENTIO PNL 5K +/-10% 2.25W 29 050123 1 KNOB PLASTIC .25 SHAFT 30 055349 1 INSULATOR 31 070030 1 COVER SILKSCREEN 32 070080 2 INSULATOR 33 070042 1 METER FREQUENCY 55-65HZ
070042A 1 METER FREQUENCY 240V 45-55HZ
34 070054 1 AMMETER AC 0 TO 50
070055 1 AMMETER AC 0 TO 100
070056 1 AMMETER AC 0 TO 150
070045 1 AMMETER AC 0 TO 200
ITEM PART NO. QTY. DESCRIPTION
070057 1 AMMETER AC 0 TO 300 070058 1 AMMETER AC 0 TO 400 070059 1 AMMETER AC 0 TO 600 070060 1 AMMETER AC 0 TO 800
35 070043 1 METER VOLT AC 0 TO 300
070044 1 METER VOLT AC 0 TO 600 36 070202 1 LIGHT PANEL 37 070081 1 METER HOURS 38 062304 1 AMMETER 40-0-40 DC 39 055405 1 GAUGE OIL PRESSURE 40 055406 1 GAUGE COOLANT TEMPERATURE 41 070083 1 ASSY ENGINE MONITOR 42 055089 1 CONN ELEC AMP M-N-L 15PLUG PNL 43 070082 1 BLOCKER LIGHT 44 053247 1 LUG RNGTNG INS 22-18 X 10 X .322 45 029187 2 SPACER .19 X .31 X .50 ST/ZNC 46 077043B 16" FLEX CONDUIT .50 ID 49 0C2323 12 SCREW PHM SWAGE 6-32X5/8 Z/YC 51 036908 2 SCREW PPHM #6-32 X 1-1/4 52 022155 2 WASHER LOCK #6 53 022985 2 WASHER FLAT #6 54 022188 2 NUT HEX #6-32 STEEL 55 036918 4 SCREW HHM #8-32 X 1/2 56 022264 6 WASHER LOCK M4 57 033121 14 SCREW HHM 10-32 X 1/2 58 022152 20 WASHER LOCK #10 59 023897 12 WASHER FLAT #10 60 022158 9 NUT HEX #10-32 STEEL 61 038150 4 WASHER FLAT #8 ZINC 62 022471 4 NUT HEX #8-32 STEEL 63 084787 1 CABLE RIBBON 16" 64 070370 2 WASHER MICA .203 65 063617 1 RELAY PNL 12VDC DPDT 10A @ 240VA 66 023762 1 WASHER SHAKEPROOF EXT #10 STL 67 057335 1 BLOCK TERM 20A 20 X 6 X 1100V 68 046669 5 JUMPER TERMINAL BLOCK 69 098940 1 HARNESS C-OPTION CONTROL PANEL 70 064000 1 SIDE CONTROL PANEL 71 064008 1 COVER CONTROL PANEL TOP
(NOT SHOWN) 72 066040 1 DECAL TERMINAL STRIP 73 022507 4 SCREW HHC 1/4-20 X 1/2 G5
(NOT SHOWN) 74 022097 8 WASHER LOCK M6-1/4 (NOT SHOWN) 75 040479 4 MOUNT VIBR 1.00X1.00X1/4-20
(NOT SHOWN) 76 036904 2 SCREW PPHM #6-32 X 3/4
(NOT SHOWN) 77 0441140156 1 ASSY WIRE 18AWG #15 (NOT SHOWN) 78 033147 1 SCREW HHM #10-32 X 1 (NOT SHOWN)
Appendix 2 — Exploded Views and Parts Lists
“C” Option Control Panel 12 Volt Diesel
Control Panel – Drawing No. 85027-H
22 Generac®Power Systems, Inc.
3
9
5
9
9
0
8
9
3
9
0
5
5
3
6
0
6
9
G
G
850
OR
S
O
O
SS
S
.
)
CA
Appendix 2 — Exploded Views and Parts Lists
“C” Option Control Panel 12 Volt Gas Control Panel – Drawing No. 085026-J
4
1
2
M A
4
4
24 F
RAM #
F WIRE HARNE N
DIA
TALLATI
EE WIRIN
IN
282
7
2
1
2
1
4
2
7
4
4
2
MI
2-PLCS
1
Generac®Power Systems, Inc. 23
ITEM PART NO. QTY. DESCRIPTION
1 070023 1 PANEL BOTTOM CONTROL 2 070026 1 PANEL FRONT CONTROL 3 070028 1 PANEL SIDE CONTROL 4 067680 1 REGULATOR ASSY VOLTAGE 60HZ
092952 1 REGULATOR ASSY VOLTAGE 50HZ 5 039271 1 FITTING 90DEGREE ¾ 6 034616 1 FITTING STRAIGHT ¾ 7 057159 1 CIRCT BRK 2 X 1 ETA 46-500-P
053623 1 CIRCT BRK 2.5 X 1 ETA 46-500-P
054502 1 CIRCT BRK 3 X 1 ETA 46-500-P
056247 1 CIRCT BRK 3.5 X 1 ETA 46-500-P
049350 1 CIRCT BRK 4 X 1 ETA 46-500-P
048476 1 CIRCT BRK 4.5 X 1 AUT30KW CNT45K
048512 1 CIRCT BRK 5 X 1 ETA 46-500-P
054450 1 CIRCT BRK 5.5 X 1 ETA 46-500-P
048505 1 CIRCT BRK 6 X 1 ETA 46-500-P
048467 1 CIRCT BRK 7 X 1 ETA 46-500-P
048468 1 CIRCT BRK 8 X 1 ETA 46-500-P
048470 1 CIRCT BRK 9 X 1 ETA 46-500-P 8 044213 1 RESIST MISC 10RX12W 9 025192 1 RECTIFIER MSC 2A 600V 1N5062
10 044213 1 RESIST MISC 10RX12W 11 055444 1 HEAT SINK 13.3L 12 030468 1 WASHER STEP NYLON .20 13 049939 1 RECTIFIER MSC 12A 600V 1N1206R 14 083089 1 ASSY PCB "C" CONTROL 12/24V 15 024469 2 SCREW TAPTITE #10-32X3/8 BP 17 085025 1 HARNESS 12-V.GAS 18 029333 6 TIE WRAP 7" WHITE 19 070097 1 DECAL TERMINAL STRIP 20 026536 1 PLUG STEEL 0.5 21 055867 1 SWITCH SPDT 15A SPD TGGL MOM 22 067625 1 SWITCH 3P TRIP THR 15/10A TGGL 23 032300 1 FUSE HOLDER 24 022676 1 FUSE 15A X AGC15 25 040213 4 PCB SUPPORT SNAP-IN 1/4 26 0C2428 8 SCREW TAPTITE PH #6-32X1/2 ZYC 27 061945 1 SWITCH 6A AMP/V SELECTOR 28 071361 1 POTENTIO PNL 5K +/-10% 2.25W 29 050123 1 KNOB PLASTIC .25 SHAFT 30 055349 1 INSULATOR 31 070030 1 COVER GENERAC SILKSCREEN 32 070080 2 INSULATOR 33 070042 1 METER FREQUENCY 60HZ
070042A 1 METER FREQUENCY 50HZ
34 070054 1 AC AMMETER-0 TO 50
070055 1 AC AMMETER-0 TO 100
070056 1 AC AMMETER-0 TO 150
ITEM PART NO. QTY. DESCRIPTION
070045 1 AC AMMETER-0 TO 200 070057 1 AC AMMETER-0 TO 300 070058 1 AC AMMETER-0 TO 400 070059 1 AC AMMETER-0 TO 600 070060 1 AC AMMETER-0 TO 800
35 070043 1 AC VOLTMETER-0 TO 300
070044 1 AC VOLTMETER-0 TO 600 36 070202 1 LIGHT PANEL #26306C 37 070081 1 METER HOURS 38 062304 1 AMMETER 40-0-40 DC 39 055405 1 GAUGE OIL PRESSURE 40 055406 1 GAUGE COOLANT TEMPERATURE 41 070083 1 ASSY ENGINE MONITOR 42 055089 1 CONN ELEC AMP M-N-L 15PLUG PNL 43 070082 1 LIGHT BLOCKER 44 053247 1 LUG RNGTNG INS 22-18X10X.322 45 029187 2 SPACER .19X.31X.50 ST/ZNC 46 077043B 16" FLEX CONDUIT .50 ID 49 0C2323 12 SCREW PHM SWAGE 6-32X5/8 Z/YC 51 036908 1 SCREW PPHM #6-32 X 1-1/4 52 022155 2 WASHER LOCK #6 53 022985 2 WASHER FLAT #6 54 022188 2 NUT HEX #6-32 STEEL 55 036918 4 SCREW PPHM #8-32 X ½ 56 022264 6 WASHER LOCK M4 57 033121 14 SCREW HHM 10-32 X ½ 58 022152 22 WASHER LOCK #10 59 023897 14 WASHER FLAT #10 ZINC 60 022158 9 NUT HEX #10-32 STEEL 61 038150 4 WASHER FLAT #8 ZINC 62 022471 4 NUT HEX #8-32 STEEL 63 084787 1 CABLE RIBBON 16" 64 070370 2 WASHER MICA .203 65 063617 1 RELAY PNL 12VDC DPDT 10A@240VA 66 023762 1 WASHER SHAKEPROOF EXT #10 STL 67 057335 1 BLOCK TERM 20A 20 X 6 X 1100V 68 046669 5 BLOCK TERM JUMPER 69 098940 1 HARNESS "C" OPTION 70 064000 1 PANEL SIDE CONTROL 71 064008 1 PANEL TOP CONTROL (NOT SHOWN) 72 066040 1 DECAL TERMINAL STRIP 73 036904 2 SCREW PPHM #6-32 X 3/4 (NOT SHOWN) 74 022507 4 SCREW HHC 1/4-20 X 1/2 G5 75 040479 4 MOUNT VIBR 1.00X1.00X1/4-20 76 022097 8 WASHER LOCK M6-1/4 77 0441140156 1 ASSY WIRE 18AWG #0 (NOT SHOWN) 78 033147 1 SCREW HHM #10-32 X 1 (NOT SHOWN) 79 0C1299 1 DECAL WARNING
Appendix 2 — Exploded Views and Parts Lists
“C” Option Control Panel 12 Volt Gas
Control Panel – Drawing No. 085026-J
24 Generac®Power Systems, Inc.
3
O
CO
O
L
U
L
5
O
R
O
D
S
S
S
CH
O
5
O
C
CO
C
ON
/
S
T
09
5A
9
U
Y C
S
O
3
O
1
5
5
5
G
O
E
U
C
OR
5
5
5
83
8
4
0
87
G
O
OR
CU
O
D
O
M
5
5
5
506
505
500
50
50
506
500
50
505
37
5
5
5
8
9
5
9
5
5
O
S:
,
,
S
Q
K
C
G
O
S
S
G
S
S
M
S
O
O
O
O
S
S
S
S
S
G
S
O
G
O
CO
O
.
O
U
S
OU
3
CO
C
S
500
U
506
C
O
O
U
C
OR
O
8
35
O
S
O
O
C
O
O
U
S.
S
09
0
CO
C
Y
209 NC CONTACTS OPEN ON ANNUNCIATED SHUTDOWN
211 NO CONTACTS CLOSE ON ANNUNCIATED SHUTDOWN
210 C CONNECT TO FUSE +12V DC CIRCUIT AS SHOWN
8
9
0
O
COO
T
S
CH
O
O
SS.
GH
.
O
U
L
CH
G
E
U
K
3
Y
Y
3
,
.
CH
U
/
U
O/O
F
Appendix 3 — Interconnection Diagram
“C” Option Control Panel 12 Volt Gas Interconnection Diagram – Drawing No. 87625
TE Y
ET "A"
LAN
WIT
IN EN
1
1
2
1
1
2
IL PRE
W
W
L
TEMP.
L
1
1
4
2
LANT TEMP
PREALARM HI
1
1
1
EL LEVE
W F
WIT
L
1
EL TAN F
1
T
IAT N
HT - REM
ANN
LI
1
2
22
1
2
1
1
1
1
LE BATTERY IN
EE IN N
LT
3-PHASE TRANSFER SWITCHE
UIPPED WITH NEUTRAL BLOC
ER WITH 12 V
THER VARIATI R
HAR
1-PHASE & 4-POLE
WN. F
TE
H
N
1. 3-POLE
GENERALLY NOT E
2. 2 AMP
1
F T
A AL
WIT
MAN
L PANEL
NTR
R
ENERAT N
HT
"D" & "E" ET
EE IN .
PREALARM LI
BATTERY ALAR
HI-L
NIT N
PTI "-
IAT
SEE INSET "G"
R "
N
T TP ALARM RELA
T WIRE
WN F
NNE
TE ANN
H
NNE
RN
-211
REM
-21
T TB
TLY T
2
ALARM H 2
WITH
DIRE
NIT
DEL
N
. M
TB2 TERMINAL
THR
CONTACTS. FOR "A" & "B" OPTION UNITS
L PANE
NTR
R
ENERAT
TE N
NIT
INE M EN
AR
IT B IR
2 #7
22
1
2
ME
A
T
L
E
WIT
FER
TE N
TRAN T
TE
-N T
XILIAR A
NTA
1
PPL
TILIT
2
TB
17
1
TI
TRA
TAR
NNE
NE
2-WIRE
R A
E
PANEL W
ENERAT
Generac®Power Systems, Inc. 25
Appendix 3 — Interconnection Diagram
“C” Option Control Panel 12 Volt Gas
Interconnection Diagram – Drawing No. 87625
G
COO
T
O
L
CK
CK
N
0
O
S
C
G
BLAC
WHITE
2
8
9
OS
T
G
WHITE
BLAC
S
50
O
S
S
S
S
CH
S
"
S
"
S
S
CH
S
600
O
S
S
U
CO
C
S
5
C
OS
ON
C
S
S
S
C
OS
O
C
ON
O
8
G
O
U
C
OR
O
U
R
Y
O
U
R
O
S
9555
9556
8
G
O
E
U
C
OR
S
S
C
OS
O
C
ON
O
8
G
O
U
C
OR
O
G
G
OU
D
)
O
Y
)
D
O
O
O
N
S
G"
O
S
CH
O
E
5
O
5
N CK
9
5
5
9
O
CO
O
O
D
9
G
E
T
0
AM
P
/
F G
R
C
Y
0
C
Y
S
0
C
G
/
C
G
S
S
S
1
PPE R
T
­IAT
12M
12AF
E
HAR
12VD
TANDB
TEM Y
INE
HT - REM
DEL
LI
M
1
N
ANN
2
1
EN
LAN
IN EN
2 2
BLA
REE
K
REEN
12 VD
ER W
HAR
VA
TILIT
A.
12
ET "A"-1 IN
NL
ENERAT
T
NTA
ERIE
WIT
FER
LT "N"
XILIARY
V
TRAN
T
TANDARD A
ITI
H P
WIT
T
NTA
4-64-
ATI
IAT N
N INDI ITI
TE ANN
H P
WIT
HT REM LI
"N"
1
T
T
ET "E IN
PPE R
ENERAT
ATI
IAT N
N INDI ITI
TE ANN
H P
HT REM
WIT
LI
"Y"
1
T
T
ET "D IN
R
N ALARM H PTI
"A" & "B"
N R
INE EN
BATTER
BATTERY NEGATIVE
POSITIVE TERMINAL
T
T
LAN
INE EN
TA
THERM
A LT V
2
1
ERIE
WIT
FER
LT "Y" V
TRAN
2 T
12
BLA
NA
REE
BLA
PTI
K
REEN
AR L B
NTR
T
WIT RN
H
22
TE N
BLACK/RE
D DI
1
ET " IN
26 Generac®Power Systems, Inc.
3
O
CO
O
L
U
L
0
9
O
R
O
D
S
S
S
CH
O
5
O
C
CO
C
ON
/
S
T
09
0A
9
U
Y C
S
O
3
U
L
O
1
0
0
0
G
O
E
U
C
OR
0
0
9
0
9 83
8
O
4
8
6
G
O
OR
CU
O
D
O
M
0
0
0
506
505
500
50
505
37
0
0
0
9
8
S
S
OR 9
5
9
9
5
5 O
COO
T
S
CH
O
O
SS.
GH
.
O
U
L
CH
G
E
U
K
3
3
Y
Y
3
0220
C
O
C
O
S:
,
,
S
Q
K
Q
T
C"
S
S
S
"
G
S
O
G
O
CO
O
.
O
U
S
OU
3
CO
C
S
500
U
506
C
O
O
U
C
OR
O
8
35
O
S
O
O
C
O
O
U
S
S
09
0
CO
C
O
209 NC CONTACTS OPEN ON ANNUNCIATED SHUTDOWN
211 NO CONTACTS CLOSE ON ANNUNCIATED SHUTDOWN
210 C CONNECT TO FUSE +24V DC CIRCUIT AS SHOWN
,
.
CH
U
/
U
O/O
F
Appendix 3 — Interconnection Diagram
“C” Option Control Panel 24 Volt Diesel Interconnection Diagram – Drawing No. 87624
LAN
WIT
IN EN
IL PRE
W
W
L
TEMP.
L
21
22
LANT TEMP
PREALARM HI
22
22
EL LEVE
W F
WIT
L
22
EL TAN F
21
22
3-PHASE TRANSFER SWITCHE
UIRE 120 VAC FOR ENGINE COOLAN
UIPPED WITH NEUTRAL BLOC
"D" & "E ET
1-PHASE & 4-POLE
TE N
EE IN .
2. 4.0L & 6.4L UNITS RE
1. 3-POLE
GENERALLY NOT E
"B" & "
. NIT
N PTI
L PANEL
"-
IAT
ALARM RELAY
SEE INSET "G"
NTR
R "
N
T T
R
T WIRE
WN F
NNE
TE ANN
H
NNE
ENERAT
RN
-211
REM
N
-21
T TB
TLY T
2
HT
ALARM H 2
WITH
DIRE
NIT
DEL
N
. M
CONTACTS. FOR "A" & "B" OPTION UNITS
TB2 TERMINAL
PREALARM LI
THR
NIT
INE M EN
AR
IT B IR
T
IAT
21
22
22
22
2
1
21
2
1
4
22
22
ME
1
A
2
T
L
N
TE
PPL
TILIT
-N T
XILIAR A
NTA
TRA NE
N
HT - REM
ANN
LI
22
22
22
22
2
22
1
471 #
E
WIT
FER
TE N
TRAN T
22
N
N
NON
22
BATTERY ALAR
HI-L
L PANE
NTR
T I
F T
A AL
MAN
WIT
R
ENERAT
TE N
TE
RE
N
TB
17
1
TI
TRA
TAR
NNE
NE
2-WIRE
R A
E
PANEL W
ENERAT
Generac®Power Systems, Inc. 27
Appendix 3 — Interconnection Diagram
“C” Option Control Panel 24 Volt Diesel
Interconnection Diagram – Drawing No. 87624
G
E
T
0
C
Y
G
E
T O
L R
3
S
"
0
/
F
G
R
3
3
G
S
O
Y 0
C
CK
N
0
6
R
Y
OU
D
O
R
8
G
WHITE
8
G
WHITE
OS
T
G
R
OS
T
G C
OR
OS
T
BLAC
G
D
N CK
CK
0
C
Y
3
3
G
S
O
Y
O
S
C
G
R
S
C"
0
3A
O
L
T
G
E
Y 0
C
R G
E
0
6
3
3
G
S
O
U
L
G
R
8
8
OS
T
OS
T
G
R
OS
T
8
S
50
O
S
S
S
S
CH
S
"
O
S
9555
9556
8
G
O
E
S
S
C
OS
O
C
ON
O
8
G
O
U
C
OR
O
U
R
9
5
S
"
S
S
CH
S
600
O
S
S
Y
O
U
R
S
S
C
OS
O
C
ON
O
8
G
O
U
C
OR
9
5
S
S
OR
O
5
0
O
E O
S
CH
S
G"
O
O
O
N
C
/
D
O
CO
O
O
D
9
PPE R
PPER PANE T
V A
TILIT
24
NL
RANKIN
CONTACTO
GROUN
BLA
BLA
REE
INE
2
1
LITER EN .
1
TA
IN
21
21
21
LAN
EN
& THERM
NL
ENERAT
ERIE
LT "N" V
T
WIT
FER
TRAN
ATI
IAT N
N INDI ITI
TE ANN
H P
WIT
HT REM LI
"N"
1
T
T
ET "E IN
NA
TA
TA
THERM
HEATE
IN EN
REEN
LAN
TA
INE HEATE EN
THERM
.4 LITE
-
4.
PTI
THERM
VA
E
INE
TILIT
12
HAR
LITER EN
LT
. .4-1
-
V A 24
TILIT
2 AMP 24 V
ET " IN
WITH 4.
T
-
HT - REM
DEL
LI
M
1
2
1
K
REEN
N R
BLACKBLA
REE
NLY
INE
PPE R
ENERAT
ERIE
LT "Y" V
2 T
WIT
FER
TRAN
ATI
N INDI ITI
H P
WIT
"Y" T
IAT N
TE ANN
HT REM LI
1 T
ET "D
LITER EN .
1
TA
IN
LAN
EN
& THERM
T
TE
I
N
WIT
E
VA 12
TILIT
24M
HAR
AMP 24AF 1
NA
NL
TA
PTI
HEATE
THERM
AR L B
NTR
T
RN H
RE
RE K
BLA
REEN
ET "B IN
22
D DI
22
IN
R
N ALARM H PTI
"A" & "B"
ET " IN
IN
1
1
T
PPE
1
EN
T
NTA
RANKIN
21
21
INE HEATE EN
28 Generac®Power Systems, Inc.
Part II
Remote Annunciator
Panels
Generac®Power Systems, Inc. 29
Section 1 — General Information
Remote Annunciator Panels
1.1 THREE LIGHT REMOTE ANNUNCIATOR
The Generac Three Light Remote Annunciator (Figure 1.1) provides a valuable reference when used with the Generac automatic transfer switch and standby generator with a C option control panel.
This equipment is designed to be mounted remotely from the standby generator set. The panel, when properly interconnected with a Generac standby gen­erator system and transfer switch, annunciates up to three (3) standby electric system operating parame­ters.
Utility Power Supply: This light comes ON when
customer electric loads are being powered by the NORMAL (utility) power source.
Emergency Power Supply: This light comes ON
when customer electric loads are being powered by the EMERGENCY (standby) power source.
Generator Fault Light: This light comes ON when
the generator engine has shut down automatically due to a fault condition (such as low oil pressure, high coolant temperature, overcrank, overspeed, or RPM sensor loss). Fault conditions that will result in an automatic engine shutdown are dis­cussed in the INSTRUCTIONS AND PARTS MANU­AL for the applicable generator set.
Figure 1.1 — Model 8848 Annunciator Panel
Lights
1.1.1 INSTALLATION
Mount the annunciator at any convenient location near or remote from the standby generator. Mounting dimensions are shown in Appendix ???. Holes are provided for fastening the panel to a desk, wall or other convenient object. Four 7/8” (22mm) holes are also provided for routing of required wiring into the panel. Installation must comply with all applicable codes and regulations.
Required wiring between the Model 8848 annuncia­tor, the Generac generator meter and control (upper) panel, and transfer switch auxiliary contacts are shown in Appendix ???, Interconnection Diagram.
NOTE:
Two different types of auxiliary contacts may be encountered on Generac transfer switches.
1.2 FIVE LIGHT REMOTE ANNUNCIATOR
The Model 8617 Remote Annunciator Panel (Figure
1.2), when properly interconnected with a Generac
standby generator equipped with an Option C control panel, will provide remote annunciation of the same five engine operating parameters as the generator panel. The remote panel mounts five advisory lamps. On occurrence of one or more of the panel monitored faults, the applicable lamp will illuminate and the horn will sound. Both the lamp(s) and the Alarm Horn can be turned OFF by depressing the Reset switch. All five lamps may be tested by actuating the Test switch. The following engine fault conditions will be indicated on the annunciator panel:
• Low Engine Oil Pressure
• High Engine Coolant Temperature/Low Coolant
Level
• Overcrank Condition
• Overspeed Condition
• RPM Sensor Loss Condition
Figure 1.2 — Model 8617 Remote Annunciator
30 Generac®Power Systems, Inc.
Section 1 — General Information
Remote Annunciator Panels
1.2.1 OPERATION
Both the remote and generator panel advisory lamps are controlled by a single DC CONTROL-LATCH­CRANK circuit board housed in the generator control console. Engine mounted, normally open (N.O.) switches and sensors provide the necessary signal to the circuit board on occurrence of a monitored engine fault. should any one (or more) of the moni­tored faults occur, an automatic engine shutdown, illumination of the applicable lamp(s), and sounding of the Alarm Horn will occur. circuit board action will then “latch” the fault. That is, the applicable lamp(s) will remain ON after engine shutdown. While any lamp remains lighted (latched), further attempts at generator cranking and startup are inhibited. A 12 volt DC input is required to operate the panel.
NOTE:
See applicable standby generator owner’s manual for more detailed operational description of remote and generator panel lamps.
1.2.2 CUSTOMER CONNECTIONS
Suitable, approved wiring must be purchased for interconnection of the Remote Annunciator Panel with Terminal block TB2. Connect each wire to a numbered terminal block screw and to an identically numbered terminal in the remote annunciator panel. A total of nine wires are required. Numbered termi­nals may be identified as follows:
• #94 — Low Oil Pressure Shutdown
• #95 — High Coolant Temperature/Low Coolant Level Shutdown
• #96 — Overcrank Shutdown
• #97 — Overspeed Shutdown
• #98 — RPM Sensor Loss Shutdown
• #137 — Test Switch Connections
• #138 — Reset Switch Connections
• #209 — Alarm Relay Normally Closed Contacts*
• #210 — Alarm Relay Common Contacts*
• #211 — Alarm Relay Normally Open Contacts*
* DO NOT EXCEED ONE (1) AMPERE OF CURRENT
ACROSS ALARM RELAY CONTACTS.
1.2.3 PARTS INCLUDED WITH REMOTE PANEL
Factory shipment of any standby generator set which includes the optional Remote Annunciator Panel will include a WIRING HARNESS (Part No. 70287). The WIRING HARNESS includes the following parts:
1. Terminal Block TB2 (Part No. 55911)
2. Terminal Block Decal (Part No. 66040)
3. Alarm Relay (Part No. 63617)
4. The Wiring Harness proper
1.3 18 LIGHT REMOTE ANNUNCIATOR
The Model 9555 Remote Annunciator Panel is a self contained system, utilizing solid state circuits to annunciate up to sixteen (16) engine-driven generator operating parameters (Figure 1.3). The system meets NFPA (National Fire Protection Association) specifica­tions for standby electric power systems.
The system will monitor any sensing device having normally-open (N.O.) contacts which provide a +DC signal to the applicable panel lamp on contacts clo­sure. On contacts closure, both an alarm lamp and an alarm horn are activated and latched in to manu­al reset. The alarm horn may be silenced without dis­turbing the visual indication and with any subse­quent alarm re-activating the horn. The system includes a test circuit.
NOTE:
The one exception to the normally-open (N.O.) contacts rule is the LOW BATTERY VOLTAGE lamp. This lamp must be connected to normally­closed (N.C.) contacts on the battery monitor cir­cuit board, located in the generator control panel.
Figure 1.3 — Model 9555 Remote Annunciator
Panel
Generac®Power Systems, Inc. 31
1.3.1 GENERATOR STOP SIGNALS
All signals occur when generator shutdown occurs as a result of the failure indicated by the illuminated lamp(s).
1. High Water Temperature/Low Water Level: This lamp comes ON and the horn sounds when the gen­erator’s high temperature alarm is active.
2. Low Oil Pressure: This lamp illuminates and the alarm horn sounds when the generator’s low oil pressure alarm is active.
3. Overspeed: This lamp turns ON and the alarm horn sounds when the generator’s overspeed alarm is active.
4. Overcrank: This lamp turns on and the alarm horn sounds when the generator’s overcrank alarm is active.
5. Sensor Loss: This lamp illuminates and the alarm horn sounds when the generator’s rpm sensor loss alarm is active.
1.3.2 LATCHABLE SIGNALS
The following signals can be individually selected by means of miniature rocker switch on the Remote Panel’s monitor circuit board. The available switch positions are “Latch On” and “Latch Off”. “Latch Off ” indicates the lamp will turn ON only when the signal is present. “Latch On” indicates the lamp will be ON until the monitor “Reset” switch is pressed. The alarm horn sounds when “Latch” is selected. The horn will stay ON until either the “Rearm Horn” or the “Reset” switch is pressed.
1. Low Battery Voltage: This lamp illuminates when the generator’s battery voltage drops low, indicating a discharge condition.
2. High Battery Voltage: This lamp will turn ON when generator battery voltage is high, indicating an over­charge condition.
3. Battery Charger Failure: This lamp will illuminate on failure of the generator’s battery charge system.
4. Low Fuel: This lamp illuminates when an occur- rence of a low fuel level in the generator’s fuel tank.
5. Pre-alarm/High Temp.: This lamp will illuminate to warn of an approaching or imminent high coolant temperature shutdown.
6. Pre-alarm/Low Temp.: This lamp will illuminate when the coolant temperature has decreased, indi­cating an engine coolant heater failure.
7. Pre-alarm/Low Oil Pressure: This lamp will illu­minate in advance of a low oil pressure shutdown. It indicates engine oil pressure has decreased to near the point of automatic shutdown.
8. Generator Run: This lamp illuminates to advise that the generator has started and/or is running. Lamp ON indicates the generator “run” circuit is active (Wire #14 on units with 12 volts DC engine control system, Wire #219 on units with 24 volts DC engine control system).
1.3.3 OTHER LAMPS
1. System Ready: This lamp will be ON to indicate the generator set is able to run. If the lamp is OUT, a “stop” signal is present.
2. Not In Auto: This lamp will illuminate to indicate the generator’s Auto-Off-Manual switch is NOT set to “Auto” )that is, the switch is set to either “Manual” or “Off” and automatic operation is not possible).
3. Horn Switch Off: This lamp will turn ON to indi- cate the horn switch on the annunciator panel is turned OFF. With the horn switch set to OFF, lamps will not be affected. However, the alarm horn will not sound.
4. Line Power: This lamp will be ON when the auto­matic transfer switch main contacts are in their “Utility” position (and connected to the “Utility” power supply).
5. Generator Power: This lamp will turn ON when the transfer switch main contacts are in their “Standby” position, i.e., load is connected to the generator power supply.
1.3.4 PANEL WIRING INTERCONNECTIONS
All INPUT signal connections are made at a 24 screw terminal block, located on the Remote Panel’s MONI­TOR CIRCUIT BOARD. Use purchased No. 14 AWG wiring for all interconnections. Maximum recommend­ed distance between the Remote Panel and the standby generator should not exceed 1000 feet (305 meters). See page 36 for installer’s wiring interconnections.
1.4 TROUBLESHOOTING
Troubleshooting the 18 lamp annunciator is limited to checking wire connections at the generator panel, trans­fer switch and annunciator, and checking for proper DC inputs to annunciator terminal strip. If all connections and input DC voltage signals are good but a problem still exists with the annunciator operation, replace annunciator circuit board.
1. Automatic Generator Stop Signals: The horn and lamp are always latched if one of these signals occurs. Generator stop lamps and horn can be reset by either the test/reset switch at the annunciator or reset of fault lamps at the generator.
2. Test/Reset: Pressing the test/reset switch energizes all lamps except the “horn switch off” lamp and the horn. Release of the switch resets the lamps and horn. The test/reset switch has no effect on fault indicators at the genset.
Section 1 — General Information
Remote Annunciator Panels
32 Generac®Power Systems, Inc.
Section 1 — General Information
Remote Annunciator Panels
3. Latch Select: The lamps and horn can be selected to be latched by on-board switch. Unlatched signals activate the lamp only; the lamp is de-energized if the fault signal is cleared. Latching provides an audible signal plus keeps the lamp energized as an indicator even if the pre-alarm fault has been cleared.
4. Rearm: The rearm clears the horn but not the lamps. The lamps are held active by either latch or fault signal. After rearm, horn is enabled to sound if another fault occurs.
5. System Ready Lamp: This lamp indicates the genset is operational. The lamp is energized when­ever power is applied to the annunciator circuit and no generator stop signals are present.
6. Line-Power/Gen Power Lamps: This indicates the position of the transfer switch. When load is trans­ferred to the genset, the “Generator Power” lamp is lit and the horn sounds.
7. Horn Switch Off Lamp: This lamp indicates that power to the horn has been disconnected by a horn disable switch.
8. Annunciator Delays: Signals will be annunciated if the exist for the following minimum times:
• Not in Auto, Horn Off, 100 seconds.
• Pre-alarm Low Oil Pressure, 10 seconds.
• All others, 1 second.
Signal Source Lamp Response Latched Rearm
High Temp. Control Board* Red Lamp & Hor n Yes Yes
Low Oil Control Board* Red Lamp & Horn Yes Yes
Overspeed Control board* Red Lamp & Hor n Yes Yes
Overcrank Control Board* Red Lamp & Horn Yes Yes
Sensor Loss Control Board* Red Lamp & Hor n Yes Yes
System Ready Annunciator Green Lamp No N/A
Line Power Transfer Switch Green Lamp No N/A
Generator Power Transfer Switch Yellow Lamp & Horn No Yes
High Battery Battery Monitor Yellow Lamp & Horn Select Yes
Low Battery Battery Monitor Yellow Lamp & HOrn Select Yes
Not In Auto Control Board Red Lamp & Horn No No
Horn Switch Off Annunciator Red Lamp No N/A
Signal Source Lamp Response Latched Rearm
Low Fuel Float Switch Yellow Lamp & Horn Select Yes
High Temperature Temperature Switch Yellow Lamp & Horn Select Yes
Low Temperature Temperature Switch Yellow Lamp & Hor n Select Yes
Low Oil Pressure Switch Yellow Lamp & Horn Select Yes
Generator Run Control Board Yellow Lamp & Horn Select Yes
Battery Charge Fail Battery Monitor Yellow Lamp & Horn Select Yes
1.5 ANNUNCIATED SIGNALS
1.6 PRE-ALARMS
Generac®Power Systems, Inc. 33
Appendix 4 — Electrical Data
Three Light Remote Annunciator
Mounting Dimensions
34 Generac®Power Systems, Inc.
Appendix 4 — Electrical Data
Five Light Remote Annunciator Mounting Dimensions
Generac®Power Systems, Inc. 35
Appendix 4 — Electrical Data
18 Light Remote Annunciator
Mounting Dimensions
36 Generac®Power Systems, Inc.
Appendix 4 — Electrical Data
Three Light Remote Annunciator Interconnection Diagram
Generac®Power Systems, Inc. 37
Appendix 4 — Electrical Data
Five Light Remote Annunciator
Interconnection Diagram
38 Generac®Power Systems, Inc.
Appendix 4 — Electrical Data
Five Light Remote Annunciator Electrical Schematic – Drawing No. 066561
Leg
end
L1 = Low Oil Pressure Lamp
L2 = High Coolant Temperature Lamp
L3 = Overcrank Lamp
L4 = Overspeed Lamp
L5 = RPM Sensor Loss Lamp
SW1 = Reset Switch
SW2 = Test Switch
H1 = Alarm Horn
Appendix 4 — Electrical Data
Three Light Remote Annunciator
Electrical Schematic – Drawing No. 067787
Generac®Power Systems, Inc. 39
/
9
519
525
519
0
0
S
P
0
P
OR
9
0
ON
CO
L
P
CO
L
0
97
8
96
95
98
4
504
502
500
505
506
9
501
.
L
.
(
N
E
:
C
C
O
O
C
C
5/
OW
L
E
E
Y
OR
GH
CH
L
S
Y
CH
R
O
C
8
/
320191816151310
8
40 Generac®Power Systems, Inc.
Appendix 4 — Electrical Data
18 Light Remote Annunciator Wiring Diagram – Drawing No. 086833-C
14 21
ANNUNCIAT
TERMINAL STRI
22
NOTE
BATTERY CHARGER FAILUR
POSITION 4) SHOWN DRIVE
2
BY LOW BATTERY SIGNAL HIGH OR LOW BATTERY SIGNA MAY BE USED
15/22
NTROL PANE
TERMINAL STRI
22
22
"C" OPTI
TRI
9
NTROL PANE
TRANSFE
N N
WIT
AUXILIAR
NTACT
LOW FUE
WIT
22
15/22
14/21
HI
N
1
N N N
22
MONIT
EMBL
L
LOW TEMPERATUR
-
HIGH TEMPERATUR
-
LOW OI
-
21 14
ITEM PART NO. QTY. DESCRIPTION
1 022442 4 NO.6-32 X 3/8” ROUND HEAD MACHINE SCREW 2 064009-A 1 LAMP - YELLOW 3 064009-B 1 LAMP - GREEN 4 067783 1 PANEL (SILKSCREENED) 5 056892 4 NO.10-24 X 3/8” CRIMPTITE SCREW 6 059143 1 FRONT PANEL 7 059144 1 PANEL SUPPORT BRACKET 8 022471 2 NO.8-32 HEX NUT
9 022264 2 NO.8 LOCK WASHER 10 059149 1 GENERAC DECAL 11 046357 1 TERMINAL BLOCK 12 036919 2 NO.8-32 X 5/8” PAN HEAD MACHINE SCREW 13 067784 1 TERMINAL BLOCK DECAL 14 059142 1 ENCLOSURE 15 064009 1 LAMP - RED
Appendix 5 — Exploded Views and Parts Lists
Three Light Remote Annunciator
Drawing No. 067786
Generac®Power Systems, Inc. 41
ITEM PART NO. QTY. DESCRIPTION
1 066040 1 DECAL, TERMINAL BOARD
2 055911 1 BOARD , TERMINAL
3 063617 1 RELAY, ALARM
4 1 BOARD, TERMINAL & DECAL (OPTIONAL PRE-ALARM)
Appendix 5 — Exploded Views and Parts Lists
Five Light Remote Annunciator Mounting Locations in Generator Control Console for Optional Terminal Boards and
Alarm Relay
42 Generac®Power Systems, Inc.
ITEM PART NO. QTY. DESCRIPTION
1 066556 1 FRONT PANEL
2 066558 1 SUPPORT - TERMINAL STRIP
3 064012 1 MONITER PANEL - SILKSCREENED
4 059149 1 DECAL - GENERAC
5 064009 5 INDICATOR LIGHT (RED)
6 055920 2 PUSH BUTTON SWITCH
7 049441 4 #6-32 X 3/8” TAPTITE
8 061286 1 SOUND - ALERT
9 055911 1 TERMINAL STRIP 10 059150-A 1 DECAL 11 036919 2 #8-32 X 5/8” PPHMS 12 022264 2 #8 LOCK WASHER 13 022471 2 #8-32 HEX NUT 14 030957 2 RECEPTACLE LUG 1/4” 15 028799 5 RECEPTACLE LUG 1/4” 16 032012 14.5” #20 BARE COPPER WIRE
2
W
A
TO
4.0
28800
28799
6
6
A
28800
0
94
95
96
97
98
211
37
38 0 2
4
6349
Appendix 5 — Exploded Views and Parts Lists
Five Light Remote Annunciator
Panel Assembly - Drawing No. 066559-B
Generac®Power Systems, Inc. 43
EE
1
1
ETAIL 1 - USE HARNESS BOARD FROM
4 TO MAKE
ENGTH
IRE P/N
199-A
4
7
7
#1
#2
4312
ROM
144
1
1
1
2
144
.0" .0" .0" .0" .0" .0"
12
.0"
12
.5"
4312
.0"
"
ITEM PART NO. QTY. DESCRIPTION
1 098940 1 HARNESS
2 063617 1 RELAY
0
37209
0
0
Appendix 5 — Exploded Views and Parts Lists
Five Light Remote Annunciator Harness (098940) - Drawing No. 070287-C
44 Generac®Power Systems, Inc.
7
1
21
1
7
4
1
Generac®Power Systems, Inc. 45
ITEM PART NO. QTY. DESCRIPTION
1 055911 1 TERMINAL BLOCK VERNITRON #09012
2 071271 1 CONNECTOR 6-CKT AMP P/N 640250
3 028739 12 TIE WRAP 4”
2
0980-3
ON
G
37
09
0
0
09
37
0
2
9
5
31
00
56
5
06
62
.
OR
SC.
300V
569
W
S/30
G
T
1
T
E
G
T
0
8
9
5
6
3
OMTO
8
819.5
ON
8800
0
8
Appendix 5 — Exploded Views and Parts Lists
Five Light Remote Annunciator
Harness (C Option Control Panel) - Drawing No. 098940-C
LGTH
26.
26.
25.
25.1
1 2 21
22
24.7
24.
7. . .1
WIRE DE
L 1007/1
#18 AWG
16 STRAND
DK BLUE COL
TE
AW
LUG #
ETC# AA-2190-06X­INSULATED SNAPSPAD
#6 SCREW 18-22 AW OR EQUIVALEN
LUG #
AMP# 35 OR EQUIVALEN
INSULATED FAST .187 X .020" #18-22 AW
.25" PIGGYBACK FAST ENERAC P/N - 02
FR
A A
A A A A A1
7
4
7
2
1
2
21
1
22
1
ITEM PART NO. QTY. DESCRIPTION
1 086582 1 PANEL, ANNUNCIATOR REAR 2 084968 1 PC BOARD - MONITOR 3 086579 1 SUPPORT, PC BOARD 4 040213 6 PCB STAND OFF 5 086580 2 SUPPORT, PC BOARD 6 036901 6 #6-32 X 3/8” PHCS 7 086581 1 PANEL, ANNUNCIATOR FRONT 8 061282-A 1 DECAL, CLEAR LEXAN
9 061283 1 SWITCH, ON/OFF 10 061284 2 SWITCH, TEST/RESET 11 032300 1 HOLDER, FUSE 12 044299 1 FUSE, 1 AMP 13 061286 1 SOUNALERT 14 077704 1 PLUG 15 086584 1 DECAL, ATTENTION
ITEM PART NO. QTY. DESCRIPTION
16 056892 4 CRIMPTITE 17 025034 2 PLUG BUTTON 18 086583 2 DECAL, ANNUNCIATOR
29* 028739 2 TIE WRAP 30†¥ 048766 1 TERM BLOCK 31†¥ 055869 1 SWITCH - TOGGLE, SPST
32 022985 6 #6 FLAT WASHER 33 022155 6 #6 LOCK WASHER
34 022188 6 #6-32 HEX NUT * NOT SHOWN SERIES
† 86585B — 86583 DECAL ¥ 86585M — 86583M DECAL
23
222
20
46 Generac®Power Systems, Inc.
Appendix 5 — Exploded Views and Parts Lists
18 Light Remote Annunciator Drawing No. 086585$-C
2
1
7
4
#17
1
#19
#18
#23
#22
#21
#20
Appendix 6 — Notes
Five Light Remote Annunciator
Generac®Power Systems, Inc. 47
48 Generac®Power Systems, Inc.
Appendix 6 — Notes
Five Light Remote Annunciator
Generac®Power Systems, Inc. 49
Appendix 6 — Notes
Five Light Remote Annunciator
Part No. 0C4205
GENERAC®POWER SYSTEMS, INC.
P.O. BOX 8
WAUKESHA, WI 53187
Revision B (09/27/02) Printed in U.S.A.
Loading...