Generac Power Systems CENTURION SERIES, CENTURION 005888-0 Specification

7kW
®
CENTURION
SERIES
ES Standby Generator System
Air-Cooled Gas Engine
®
7kW
1 of 5
INCLUDES:
• Digital LED Controller
• Automatic Transfer Switch
with Built-In Priority Load Center
• Composite All Weather Enclosure
• Sound Attenuated Enclosure
• External Main Circuit Breaker
• Flexible Fuel Line Connector
• Composite Mounting Pad
• Natural Gas or LP Gas Operation
• 2 Year Limited Warranty
• UL 2200 Listed
Standby Power Rating
Model 005888-0 (Composite Polymer - Bisque) - 7 kW 60Hz
FEATURES
¡ INNOVATIVE DESIGN & PROTOTYPE TESTING are key components of
GENERAC’S success in “IMPROVING POWER BY DESIGN.” But it doesn’t stop there. Total commitment to component testing, reliability testing, environmental testing, destruction and life testing, plus testing to applicable CSA, NEMA, EGSA, and other standards, allows you to choose GENERAC POWER SYSTEMS with the confidence that these systems will provide superior performance.
¡
ES
: Offers an extreme value for those who desire automatic backup power at
the most affordable price.
¡ TEST CRITERIA:
PROTOTYPE TESTED NEMA MG1-22 EVALUATION
SYSTEM TORSIONAL TESTED MOTOR STARTING ABILITY
¡ SOLID-STATE, FREQUENCY COMPENSATED VOLTAGE REGULATION.
This state-of-the-art power maximizing regulation system is standard on all Generac models. It provides optimized FAST RESPONSE to changing load conditions and MAXIMUM MOTOR STARTING CAPABILITY by electronically torque-matching the surge loads to the engine.
¡ SINGLE SOURCE SERVICE RESPONSE from Generac’s dealer network
provides parts and service know-how for the entire unit, from the engine to the smallest electronic component.
¡ GENERAC TRANSFER SWITCHES. Long life and reliability are
synonymous with GENERAC POWER SYSTEMS. One reason for this confidence is that the GENERAC product line includes its own transfer systems and controls for total system compatibility.
ES Standby Generator System - 7 kW features and benefits
7kW
Engine
•Generac OHV engine A durable, reliable powertrain for maximum power output.
•Cast iron cylinder walls Rigid construction and added durability provide long engine life.
2 of 5
•Electronic ignition/spark advance These features combine to assure smooth, quick starting every time.
•Pressurized filtration system Better performance, less maintenance and significantly longer engine life.
•Low oil pressure shutdown system Shutdown protection prevents catastrophic engine damage due to low oil.
•High temperature shutdown Prevents damage due to overheating.
•Spin-on automotive type oil filter Captures and collects harmful impurities with easy serviceability.
Generator
•Revolving field
•Displaced phase excitation
•Automatic voltage regulation Regulates the output voltage to ±5% prevents damaging voltage spikes.
•UL 2200 listed For your safety.
Allows for a smaller, light weight unit that operates 25% more efficiently than a revolving armature generator.
Maximizes motor starting capability.
Transfer Switch
•Fully automatic Transfers your vital electrical loads to the energized source of power.
•Remote mounting Mounts near your existing distribution panel for simple, low cost installation.
•Flush mountable Can be installed between studs like a standard electrical panel.
•UL listed For your safety.
Controls
•Auto/Off/Manual switch Selects the operating mode.
•Utility voltage sensing Constantly monitors utility voltage, setpoints 60% dropout, 80% pick-up, of standard voltage.
•Utility interrupt delay Prevents nuisance start-ups of the engine, adjustable 10-30 seconds.
•Engine warm-up Ensures engine is ready to assume the load, setpoint approximately 5 seconds.
•Engine cool-down Allows engine to cool prior to shutdown, setpoint approximately 1 minute.
•Seven day exerciser Operates engine to prevent oil seal drying and damage between power outages.
•Timed Trickle Battery charger Maintains battery charge level to ensure starting.
•Main line circuit breaker Protects generator from overload.
Unit
•Weather protective enclosure Ensures protection against mother nature. Tool-less removal of roof and sides. Three lift-out panels for easy access to all routine maintenance items. Composite polymer enclosure will not rust and is ideal for harsh and coastal installations.
•Enclosed critical grade muffler Quiet, critical grade muffler is mounted inside the unit to prevent injuries.
•Small, compact, attractive Makes for an easy, eye appealing installation.
•SAE Sound attenuated enclosure ensures quiet operation.
Installation System
•1ft. (305mm) flexible fuel line connector Easy installation.
ES Standby Generator System - 7 kW specifications
Generator
Model 005888-0
Rated Maximum Continuous Power Capacity (LP) 7,000 Watts* Rated Maximum Continuous Power Capacity (NG) 6,000 Watts* Rated Voltage 240 Rated Maximum Continuous Load Current – 240 Volts 29.2 / 25
Main Line Circuit Breaker 30 Amp Phase 1 Number of Rotor Poles 2 Rated AC Frequency 60Hz Power Factor 1.0
Battery Requirement (not included) Group 26R, 12 Volts and 525 CCA Minimum Unit Weight (Pounds/Kilos) 250/113.4 Dimensions (L x W x H) in./mm 24.4 x 30.2 x 33/618.5 x 767.5 x 837 Sound output in dB(A) at 23 ft. (7m) with generator operating at normal load** 67
Engine
Type of Engine GENERAC OHV Number of Cylinders 1 Displacement 432cc Cylinder Block Aluminum w/Cast Iron Sleeve Valve Arrangement Overhead Valve Ignition System Solid-state w/Magneto Governor System Mechanical Starter 12 VDC Oil Capacity Including Filter Approx. 1.1 Qts./1.0L Operating RPM 3,600 Fuel Consumption Natural Gas ft³/hr (m³/hr)
1/2 Load Full Load
Liquid Propane ft3/hr (gal/hr) [Liters/hr]
1/2 Load Full Load
Note: Fuel pipe must be sized for full load. Required fuel pressure to generator fuel inlet at all load ranges - 5-7" water column (9-13mm mercury) for natural gas, 10-12" water column (19-22mm
mercury) for LP gas.
For Btu content, multiply ft3/hr x 2500 (LP) or ft3/hr x 1000 (NG)
For Megajoule content, multiply m³/hr x 93.15 (LP) or m³/hr x 37.26 (NG)
85 (2.41)
148 (4.19)
36 (0.99) [3.75] 46 (1.26) [4.79]
7kW
3 of 5
Controls
Digital LED Indicators Simple user interface for ease of operation. Mode Switch: Auto Automatic Start on Utility failure. 7 day exerciser.
Off Stops unit. Power is removed. Control and charger still operate.
Manual/Test (start) Start with starter control, unit stays on. If utility fails, transfer to load takes place. Engine Start Sequence Cyclic cranking: 16 sec. on, 7 rest (90 sec. maximum duration) Engine Warm-up 5 sec. Engine Cool-Down 1 min. Starter Lock-out Starter cannot re-engage until 5 sec. after engine has stopped.
2.5 Amp Timed Trickle Battery Charger Standard Automatic Voltage Regulator w/Overvoltage Protection Standard Automatic Low Oil Pressure Shutdown Standard Overspeed Shutdown Standard, 72Hz High Temperature Shutdown Standard Overcrank Protection Standard Safety Fused Standard
**Sound levels are taken from the front of the generator. Sound levels taken from other sides of the generator may be higher depending on installation parameters. Rating definitions - Standby: Applicable
for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with BS5514, ISO3046 and DIN6271). * Maximum wattage and current are subject to and limited by such factors as fuel Btu/megajoule content, ambient temperature, altitude, engine power and condition, etc. Maximum power decreases about 3.5 percent for each 1,000 feet (304.8 meters) above sea level; and also will decrease about 1 percent for each 6° C (10° F) above 16° C (60°F).
ES Standby Generator System - 7 kW features and benefits
7kW
4 of 5
Transfer Switch Features
• Electrically operated, mechanically-held
contacts for fast, positive connections.
• Rated for all classes of load, 100%
equipment rated, both inductive and resistive.
• 2 pole, 250 VAC contactors.
• 160 millisecond transfer time.
• NEMA 1 (indoor rated) enclosure is standard.
• Flush mountable.
Model 005888-0
No. of Poles 2
Current Rating (Amps) 50 Voltage 120/240 1Ø Utility Voltage Monitor (Fixed)*
-Pick-up
-Dropout
Return to Utility* approx. 15 sec. Exercise weekly for 12 minutes* Standard UL Listed Standard Total of Pre-wired Circuits
No. 15A 120V No. 20A 120V No. 20A 240V No. 30A 240V No. 40A 240V No. 50A 240V
Circuit Breaker Protected
Available RMS Symmetrical
Fault Current @ 250 Volts
Weight (Pounds/Kilos) 25/11.3
*Function of Controller
80% 60%
8
5 1
­1
-
-
10,000
Dimensions
Mechanical Dimensions (in inches/mm)
Amps
50
Wire Ranges
Amps Neutral Lug Ground Lug
50 2/0 - #14 2/0 - #14
Height Width
H1 H2 W1 W2
18.5 in 23 in 10.5 in 15.38 in 3.4 in
470 mm 584 mm 267 mm 391 mm 86 mm
Depth
W2
H2
H1
D
W1
ES Standby Generator System - 7 kW available accessories
Model # Product Description
7kW
005819-0 26R Wet Cell Battery
005865-0 Cold Weather Kit
006003-0 Scheduled Maintenance Kit
Every standby generator requires a battery to start the system. Generac offers the recommended 26R wet cell battery for use with all air-cooled standby product.
The CorePower cold weather kit is recommended for CorePower units installed in regions where the temperature regularly falls below 32°F (0°C).
Generac's scheduled maintenance kits provide all the hardware necessary to perform complete routine maintenance on a Generac automatic standby generator.
dimensions
Design and specifications subject to change without notice. Dimensions shown are approximate. Contact your Generac dealer for certified drawings. DO NOT USE THESE DIMENSIONS FOR INSTALLATION PURPOSES.
5 of 5
837mm
[32.95 in.]
76.2mm [3.0 in.] PEA GRAVEL
618.5mm [24.35 in.]
FRONT VIEW
MINIMUM
767.5mm [30.22 in.]
RIGHT SIDE VIEW
Generac Power Systems, Inc. • S45 W29290 HWY. 59, Waukesha, WI 53189 • centuriongenerators.com
©2013 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Bulletin 0186730SBY-L Printed in U.S.A. 05/30/13