Not intended for use as Primary Power in place of utility
DEADLY EXHAUST FUMES. OUTDOOR INSTALLATION ONLY!
or in life-support applications.
INTRODUCTION
Thank you for purchasing this compact, high performance, air-cooled, engine-driven generator. It is
designed to automatically supply electrical power to
operate critical loads during a utility power failure.
This unit is factory installed in an all-weather, metal
enclosure that is intended exclusively for outdoor installation. This generator will operate using either
vapor withdrawn liquid propane (LP) or natural gas
(NG).
NOTE:
This generator is suitable for supplying typical
residential loads such as Induction Motors (sump
pumps, refrigerators, air conditioners, furnaces,
etc.), Electronic Components (computer, monitor,
TV, etc.), Lighting Loads and Microwaves.
READ THIS MANUAL THOROUGHLY
If any portion of this manual is not understood,
contact the nearest Authorized Dealer for starting,
operating and servicing procedures.
Throughout this publication, and on tags and decals
affixed to the generator, DANGER, WARNING,
CAUTION and NOTE blocks are used to alert personnel to special instructions about a particular operation that may be hazardous if performed incorrectly
or carelessly. Observe them carefully. Their definitions are as follows:
DANGER
After this heading, read instructions that, if not
strictly complied with, will result in serious personal injury, including death, in addition to property
damage.
After this heading, read instructions that, if not
strictly complied with, may result in serious personal injury or property damage.
After this heading, read instructions that, if not
strictly complied with, could result in damage to
equipment and/or property.
NOTE:
After this heading, read explanatory statements
that require special emphasis.
These safety warnings cannot eliminate the hazards that they indicate. Common sense and strict
compliance with the special instructions while
performing the service are essential to preventing
accidents.
Four commonly used safety symbols accompany the
DANGER, WARNING and CAUTION blocks. The type
of information each indicates follows:
This symbol points out potential explosion haz-
ard.
This symbol points out potential fire hazard.
This symbol points out potential electrical shock
hazard.
The operator is responsible for proper and safe use
of the equipment. The manufacturer strongly recommends that the operator read this Owner's Manual
and thoroughly understand all instructions before
using this equipment. The manufacturer also strongly recommends instructing other users to properly
start and operate the unit. This prepares them if they
need to operate the equipment in an emergency.
CONTENTS
This manual contains pertinent owner’s information
for these models:
It is the operator's responsibility to perform all safety
checks, to make sure that all maintenance for safe
operation is performed promptly, and to have the
equipment checked periodically by an Authorized
Dealer. Normal maintenance service and replacement
of parts are the responsibility of the owner/operator
and, as such, are not considered defects in materials
or workmanship within the terms of the warranty.
Individual operating habits and usage contribute to
the need for maintenance service.
Proper maintenance and care of the generator ensures
a minimum number of problems and keep operating
expenses at a minimum. See an Authorized Dealer
for service aids and accessories.
HOW TO OBTAIN SERVICE
When the generator requires servicing or repairs,
contact an Authorized Dealer for assistance. Service
technicians are factory-trained and are capable of
handling all service needs.
When contacting an Authorized Dealer about parts
and service, always supply the complete model number and serial number of the unit as given on its data
decal, which is located on the generator. See section
"The Generator" for decal location.
Model No. ____________ Serial No. ______________
This symbol points out important safety infor-
mation that, if not followed, could endanger
personal safety and/or property of others.
Table of Contents
Air-cooled Generators
Introduction ........................Inside Front Cover
Read This Manual Thoroughly ........................ IFC
SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe operation
be copied and posted near the unit’s installation site. Safety should be stressed to all opera-
tors and potential operators of this equipment.
The engine exhaust from this product•
contains chemicals known to the state
defects or other reproductive harm.
This product contains or emits chemicals•
known to the state of California to cause
cancer, birth defects or other reproductive harm.
Study these SAFETY RULES carefully before installing, operating or servicing this equipment. Become
familiar with this Owner’s Manual and with the
unit. The generator can operate safely, efficiently and
reliably only if it is properly installed, operated and
maintained. Many accidents are caused by failing to
follow simple and fundamental rules or precautions.
The manufacturer cannot anticipate every possible
circumstance that might involve a hazard. The warnings in this manual, and on tags and decals affixed
to the unit are, therefore, not all-inclusive. If using
a procedure, work method or operating technique
the manufacturer does not specifically recommend,
ensure that it is safe for others. Also make sure the
procedure, work method or operating technique utilized does not render the generator unsafe.
WARNING:•
of California to cause cancer, birth
WARNING:•
DANGER
Despite the safe design of this generator,
operating this equipment imprudently, neglecting
its maintenance or being careless can cause
possible injury or death. Permit only responsible
and capable persons to operate or maintain this
equipment.
Potentially lethal voltages are generated by
these machines. Ensure all steps are taken to
render the machine safe before attempting to
work on the generator.
Parts of the generator are rotating and/or hot
during operation. Exercise care near running
generators.
GENERAL HAZARDS
For safety reasons, the manufacturer recommends •
that the installation, initial start-up and maintenance of this equipment is carried out by an
Authorized Dealer.
The engine exhaust fumes contain carbon monox-•
ide, which can be DEADLY. This dangerous gas, if
breathed in sufficient concentrations, can cause
unconsciousness or even death. Do NOT alter or
add to the exhaust system or do anything that
might render the system unsafe or in noncompliance with applicable codes and standards.
Keep hands, feet, clothing, etc., away from drive •
belts, fans, and other moving or hot parts. Never
remove any drive belt or fan guard while the unit
is operating.
Adequate, unobstructed flow of cooling and venti-•
lating air is critical to correct generator operation.
Do not alter the installation or permit even partial
blockage of ventilation provisions, as this can seriously affect safe operation of the generator. The
generator MUST be installed outdoors.
When working on this equipment, remain alert •
at all times. Never work on the equipment when
physically or mentally fatigued.
Inspect the generator regularly, and contact the •
nearest Authorized Dealer for parts needing repair
or replacement.
Before performing any maintenance on the gen-•
erator, disconnect its battery cables to prevent
accidental start up. Disconnect the cable from the
battery post indicated by a NEGATIVE, NEG or
(–) first, then remove the POSITIVE, POS or (+)
cable. When reconnecting the cables, connect the
POSITIVE cable first, the NEGATIVE cable last.
Never use the generator or any of its parts as a •
step. Stepping on the unit can stress and break
parts, and may result in dangerous operating conditions from leaking exhaust gases, fuel leakage,
oil leakage, etc.
2
IMPORTANT SAFETY INSTRUCTIONS
Air-cooled Generators
ELECTRICAL HAZARDS
All generators covered by this manual produce •
dangerous electrical voltages and can cause fatal
electrical shock. Utility power delivers extremely
high and dangerous voltages to the transfer switch
as does the standby generator when it is in operation. Avoid contact with bare wires, terminals,
connections, etc., while the unit is running. Ensure
all appropriate covers, guards and barriers are in
place, secured and/or locked before operating the
generator. If work must be done around an operating unit, stand on an insulated, dry surface to
reduce shock hazard.
Do not handle any kind of electrical device while •
standing in water, while barefoot, or while hands or
feet are wet. DANGEROUS ELECTRICAL SHOCK
MAY RESULT.
The National Electrical Code (NEC) requires the •
frame and external electrically conductive parts of
the generator to be connected to an approved earth
ground. Local electrical codes also may require
proper grounding of the generator electrical system.
After installing this home standby electrical sys-•
tem, the generator may crank and start at any
time without warning. When this occurs, load circuits are transferred to the STANDBY (generator)
power source. To prevent possible injury if such a
start and transfer occur, always set the generator’s
AUTO/OFF/MANUAL switch to its OFF position
before working on equipment and remove the 15A
fuse from the generator control panel.
In case of accident caused by electric shock, imme-•
diately shut down the source of electrical power. If
this is not possible, attempt to free the victim from
the live conductor. AVOID DIRECT CONTACT WITH
THE VICTIM. Use a nonconducting implement,
such as a dry rope or board, to free the victim from
the live conductor. If the victim is unconscious,
apply first aid and get immediate medical help.
Never wear jewelry when working on this equip-•
ment. Jewelry can conduct electricity resulting in
electric shock, or may get caught in moving components causing injury.
FIRE HAZARDS
For fire safety, the generator must be installed and •
maintained properly. Installation must always
comply with applicable codes, standards, laws
and regulations. Adhere strictly to local, state
and national electrical and building codes. Comply
with regulations the Occupational Safety and
Health Administration (OSHA) has established.
Also, ensure that the generator is installed in
accordance with the manufacturer’s instructions
and recommendations. Following proper installation, do nothing that might alter a safe installation
and render the unit in noncompliance with the
aforementioned codes, standards, laws and regulations.
Keep a fire extinguisher near the generator at all •
times. Extinguishers rated “ABC” by the National
Fire Protection Association are appropriate for
use on the standby electric system. Keep the extinguisher properly charged and be familiar with its
use. Consult the local fire department with any
questions pertaining to fire extinguishers.
EXPLOSION HAZARDS
Do not smoke around the generator. Wipe up any •
fuel or oil spills immediately. Ensure that no combustible materials are left in the generator compartment, or on or near the generator, as FIRE or
EXPLOSION may result. Keep the area surrounding the generator clean and free from debris.
Gaseous fluids such as natural gas and liquid pro-•
pane (LP) gas are extremely EXPLOSIVE. Install
the fuel supply system according to applicable
fuel-gas codes. Before placing the home standby
electric system into service, fuel system lines must
be properly purged and leak tested according to
applicable code. After installation, inspect the fuel
system periodically for leaks. No leakage is permitted.
STANDARDS INDEX
In the absence of pertinent standards, codes, regulations and laws, the published information listed
below may be used as installation guide for this
equipment.
1. NFPA No. 37, STATIONARY COMBUSTION
ENGINES AND GAS TURBINES, available from
the National Fire Protection Association, 470
Atlantic Avenue, Boston, MA 02210.
2. NFPA No. 76A, ESSENTIAL ELECTRICAL
SYSTEMS FOR HEALTH CARE FACILITIES,
available same as Item 1.
3. NFPA No. 54, NATIONAL FUEL GAS CODE,
available same as Item 1.
4. NFPA No. 58, AMERICAN NATIONAL STANDARD
FOR STORAGE AND HANDLING OF LIQUEFIED
PETROLEUM GAS, available same as Item 1.
5. NFPA No. 70, NFPA HANDBOOK OF NATIONAL
ELECTRIC CODE, available same as Item 1.
6. Article X, NATIONAL BUILDING CODE, available
from the American Insurance Association, 85
John Street, New York, N.Y. 10038.
7. AGRICULTURAL WIRING HANDBOOK, available from the Food and Energy Council, 909
University Avenue, Columbia, MO 65201.
8. ASAE EP-3634, INSTALLATION AND
MAINTENANCE OF FARM STANDBY ELECTRICAL
SYSTEMS, available from the American Society
of Agricultural Engineers, 2950 Niles Road, St.
Joseph, MI 49085.
9. NFPA No. 30, FLAMMABLE AND COMBUSTIBLE
LIQUIDS CODE, available same as Item 1.
3
DANGER
Section 1 — General Information
Air-cooled Generators
1.2 PROTECTION SYSTEMS
Unlike an automobile engine, the generator may have
Only qualified electricians or contractors should
attempt such installations, which must comply
strictly with applicable codes, standards and regulations.
1.1 UNPACKING/INSPECTION
After unpacking, carefully inspect the contents for
damage.
This standby generator set is ready for installa-•
tion with a factory supplied and pre-mounted base
pad and has a weather protective enclosure that is
intended for outdoor installation only.
This UL listed standby generator set may be pack-•
aged with an automatic transfer switch with built
in load center. The combination transfer switch
and load center is pre-wired with a two foot and
30 foot conduit. Circuit breakers for emergency
circuit connections are included (if equipped).
This UL listed, 2-pole switch is rated at 100 • or 200
AC amperes at 250 volts maximum. The 100 Amp
transfer switch is for indoor use only. The 200
Amp transfer switch is for indoor/outdoor use
(if equipped).
If this generator is used to power electrical load
circuits normally powered by a utility power
source, it is required by code to install a transfer
switch. The transfer switch must effectively isolate
the electrical system from the utility distribution
system when the generator is operating (NEC 700,
701 & 702). Failure to isolate an electrical system
by such means will result in damage to the generator and also may result in injury or death to
utility power workers due to backfeed of electrical
energy.
If any loss or damage is noted at time of delivery, have
the person(s) making the delivery note all damage on
the freight bill or affix their signature under the consignor's memo of loss or damage.
If a loss or damage is noted after delivery, separate
the damaged materials and contact the carrier for
claim procedures.
“Concealed damage” is understood to mean damage
to the contents of a package that is not in evidence at
the time of delivery, but is discovered later.
To properly open the roof, press down on the center top lip and release the latch. If pressure is not
applied from the top, the roof may appear stuck.
Always verify that the side lock is unlocked before
attempting to lift the roof.
to run for long periods of time with no operator present to monitor engine conditions. For that reason,
the engine is equipped with the following systems
that protect it against potentially damaging conditions:
1. Low Oil Pressure Sensor
2. High Temperature Sensor
3. Overcrank
4. Overspeed
5. RPM Sensor
6. Low Battery
There are readouts on the control panel to notify
personnel that one of these failures has occurred.
There is also a System Set LED (single cylinder) or a
Status message on the display (V-twins) that displays
when all of the conditions described in the "System
Set LED" section are true.
1.3 NEC REQUIREMENT FOR ARC
FAULT CIRCUIT INTERRUPTION
BREAKER FOR BEDROOMS
In 2001, the National Electric Code (NEC) introduced a requirement for new construction. This new
requirement indicates the need for Arc Fault Circuit
Interrupters to be used to protect the complete
branch circuit that feeds a dwelling bedroom. The
actual NEC requirement is indicated below.
1.3.1 SECTION 210.12 ARC FAULT CIRCUIT
INTERRUPTER PROTECTION
1. Definition: An arc fault circuit interrupter is a
device intended to provide protection from the
effects of arc faults by recognizing characteristics
unique to arcing and by functioning to de-energize the circuit when an arc fault is detected.
2. Dwelling Unit Bedrooms: All branch circuits that
supply 125 volt, single-phase, 15 and 20 ampere
outlets installed in dwelling unit bedrooms shall
be protected by an arc fault circuit interrupter
listed to provide protection of the entire branch
circuit.
Section 210.12 requires that AFCI protection be
provided on branch circuits that supply outlets
(receptacle, lighting, etc.) in dwelling bedrooms. The
requirement is limited to 15 and 20 ampere, 125
volt circuits. There is no prohibition against providing AFCI protection on other circuits or in locations
other than bedrooms. Because circuits are often
shared between a bedroom and other areas such as
closets and hallways, providing AFCI protection on
the complete circuit would comply with 210.12.
4
Section 1 — General Information
Air-cooled Generators
If during the installation of the home standby system
the decision is made to provide back up power to a
bedroom branch circuit, then the circuit breaker in
the transfer switch should be replaced with an Arc
Fault Circuit Interrupter.
It is most important that breakers only be switched
like for like. For instance, if replacing a 15A breaker,
it MUST be replaced with a 15A AFCI breaker.
Likewise, a 20A breaker MUST be replaced with a
20A AFCI.
These AFCI breakers are available at the nearest
hardware store.
Siemens Item # Description
Q115AF 15A Single Pole AFCI
Q120AF 20A Single Pole AFCI
1.4 EMISSION INFORMATION
The Environmental Protection Agency requires that
this generator complies with exhaust emission standards. This generator is certified to meet the applicable EPA emission levels. Additional information
regarding the requirements set by the EPA is as follows:
The generator is certified for use as a stationary
engine for standby power generation. Any other use
may be a violation of federal and/or local laws. It is
important that to follow the maintenance specifications in the "Maintenance" section to ensure that the
engine complies with the applicable emission standards for the duration of the engine’s life. This engine
is certified to operate on Liquid Propane fuel and
pipeline Natural Gas. The emission control system
on the generator consists of the following:
Fuel Metering System•
Carburetor/mixer assembly•
Fuel regulator•
Air Induction System•
Intake pipe/manifold•
Air cleaner•
Ignition System•
Spark plug•
Ignition module•
The Emissions Compliance Period referred to on the
Emissions Compliance Label indicates the number of
operating hours for which the engine has been shown
to meet Federal emission requirements. See the table
below to determine the compliance period for the
generator. The displacement of the generator is listed
on the Emissions Compliance Label.
Normal Operating Range-20° F (-28.8° C) to 77° F (25° C)
* Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power and condition,
etc. Maximum power decreases about 3.5 percent for each 1,000 feet above sea level; and also will decrease about 1 percent for each 6 C (10 F) above 16 C
(60 F) ambient temperature.
** Load current values shown for 120 volts are maximum TOTAL values for two separate circuits. The maximum current in each circuit must not exceed the
value stated for the 240 volts.
*** Circuits to be moved must be protected by same size breaker. For example, a 15 amp circuit in the main panel must be a 15 amp circuit in the transfer
switch.
7,000 NG
8,000 LP
Group 26R, 12
Volts and 350
CCA Minimum
9,000 NG
10,000 LP
12,000 NG
12,000 LP
13,000 NG
14,000 LP
Group 26R, 12 Volts and 525 CCA Minimum
16,000 NG
16,000 LP
16,000 NG
17,000 LP
18,000 NG
20,000 LP
1.6.2 ENGINE
Model8 kW10 kW12/14/16/17 kW20 kW
Type of EngineGH-410GT-530GT-990GT-999
Number of Cylinders1222
Rated Horsepower @ 3,600 rpm14.8183236
Displacement410cc530cc992cc999cc
Cylinder BlockAluminum w/Cast Iron Sleeve
Valve ArrangementOverhead Valves
Ignition SystemSolid-state w/Magneto
Recommended Spark PlugRC14YCBPR6HSRC14YCRC12YC
Spark Plug Gap0.76 mm (0.030 inch)0.76 mm (0.030 inch)1.02 mm (0.040 inch)0.76 mm (0.030 inch)
The “System Set” LED (single cylinder) or "Ready to
Run" on the display (v-twin) is ready when all of the
following conditions are true:
1. The AUTO/OFF/MANUAL switch is set to the
AUTO position.
2. The utility voltage being supplied to the unit is
being sensed by the PCB. If the utility sense voltage is not connected to the unit or if it is below
approximately 150-160 volts AC, then the system
set light will flash rapidly (8kW). This indicates
that if the AUTO/OFF/MANUAL switch is placed
in the Auto position, the generator will start.
3. No alarms are present, for example, low oil pressure, high temperature, etc.
1.8 FUEL REQUIREMENTS
AND RECOMMENDATIONS
With LP gas, use only the vapor withdrawal system. This type of system uses the vapors formed
above the liquid fuel in the storage tank.
The engine has been fitted with a fuel carburetion
system that meets the specifications of the 1997
California Air Resources Board for tamper-proof dual
fuel systems. The unit will run on natural gas or LP
gas, but it has been factory set to run on natural gas.
Should the primary fuel need to be changed to LP
gas, the fuel system needs to be reconfigured. See the
reconfiguring the Fuel System section for instructions
on reconfiguration of the fuel system.
Recommended fuels should have a Btu content of at
least 1,000 Btus per cubic foot for natural gas; or at
least 2,520 Btus per cubic foot for LP gas. Ask the
fuel supplier for the Btu content of the fuel.
Required fuel pressure for natural gas is five (5)
inches to seven (7) inches water column (0.18 to
0.25 psi); and for liquid propane, 10 inches to 12
inches of water column (0.36 to 0.43 psi). The
primary regulator for the propane supply is NOT
INCLUDED with the generator.
NOTE:
All pipe sizing, construction and layout must comply with NFPA 54 for natural gas applications and
NFPA 58 for liquid propane applications. Once the
generator is installed, verify that the fuel pressure
NEVER drops below four (4) inches water column
for natural gas or 10 inches water column for liquid propane.
Prior to installation of the generator, the installer
should consult local fuel suppliers or the fire marshal to check codes and regulations for proper installation. Local codes will mandate correct routing of
gaseous fuel line piping around gardens, shrubs and
other landscaping to prevent any damage.
8
Special considerations should be given when installing the unit where local conditions include flooding,
tornados, hurricanes, earthquakes and unstable
ground for the flexibility and strength of piping and
their connections.
Use an approved pipe sealant or joint compound on
all threaded fitting.
All installed gaseous fuel piping must be purged and
leak tested prior to initial start-up in accordance with
local codes, standards and regulations.
1.9 FUEL CONSUMPTION
Unit
7/8 kW771400.94/341.68/62
9/10 kW1021561.25/461.93/70
12/12 kW1522151.53/562.08/76
13/14 kW1562201.56/582.30/84
16/16 kW1832611.59/582.51/91
16/17 kW1832611.61/592.57/94
18/20 kW2062941.89/692.90/106
* Natural gas is in cubic feet per hour.
** LP is in gallons per hour/cubic feet per hour.
*** Values given are approximate.
Verify that gas meter is capable of providing enough
fuel flow to include household appliances.
1.9.1 BTU FLOW REQUIREMENTS -
NATURAL GAS
BTU flow required for each unit based on 1000 BTU
per cubic foot.
propane (LP) gas are highly explosive. Even the
slightest spark can ignite such fuels and cause
an explosion. No leakage of fuel is permitted.
Natural gas, which is lighter than air, tends to
collect in high areas. LP gas is heavier than air
and tends to settle in low areas.
Nat. GasLP Vapor
1/2 LoadFull Load1/2 LoadFull Load
DANGER
Section 1 — General Information
Air-cooled Generators
NOTE:
A minimum of one approved manual shut-off valve
must be installed in the gaseous fuel supply line.
The valve must be easily accessible. Local codes
determine the proper location.
1.10 RECONFIGURING THE
FUEL SYSTEM
1.10.1 8 KW, 410CC ENGINE
To reconfigure the fuel system from NG to LP, follow
these steps (Figure 1.4):
NOTE:
The primary regulator for the propane supply is
NOT INCLUDED with the generator. A fuel pressure of 10 to 12 inches of water column (0.36 to
0.43 psi) to the fuel inlet of the generator MUST
BE SUPPLIED.
1. Turn off the main gas supply (if connected).
2. Open the roof and remove the door.
3. Remove the battery (if installed).
4. Take the plastic T-handle fuel selector in the poly
bag supplied with the generator.
5. Locate the selector knob on the air box cover,
behind the yellow air filter door and power
bulge. The unit comes from the factory in the NG
(Natural Gas) position. Grasping the T-handle,
insert the pin end into the hole in the selector
knob and pull out to overcome spring pressure
and then twist clockwise 90 degrees and allow
the selector to return in once aligned with the LP
(Liquid Propane) position.
6. Save this tool with the Owner's Manual.
7. Install the battery, door and close the roof.
8. Reverse the procedure to convert back to natural
gas.
Figure 1.4 – Fuel Selector
NOTE:
Use an approved pipe sealant or joint compound
on all threaded fittings to reduce the possibility
of leakage.
To reconfigure the fuel system from NG to LP, follow
these steps:
NOTE:
The primary regulator for the propane supply is
NOT INCLUDED with the generator. A fuel pressure of 10 to 12 inches of water column (0.36 to
0.43 psi) to the fuel inlet of the generator MUST
BE SUPPLIED.
1. Open the roof.
2. For 10kW units: Loosen clamp and slide back
the air inlet hose.
Slide fuel selector on carburetor out towards the •
back of the enclosure (Figures 1.5 and 1.6).
Return the inlet hose and tighten clamp secure-•
ly.
For 12, 14, 16, 17 and 20kW units: remove the air
cleaner cover.
Slide the selector lever out towards the back of •
the enclosure (Figures 1.7 and 1.8).
Return the air cleaner cover and tighten the two •
thumb screws.
Figure 1.5 - 10kW, GT-530 (Inlet Hose Slid Back)
Fuel Selection
Lever - "In"
Position for
Natural Gas
Fuel
3. Close the roof.
4. Reverse the procedure to convert back to natural
gas.
9
Section 1 — General Information
Air-cooled Generators
Figure 1.6 - 10kW, GT-530 (Inlet Hose Slid Back)
Fuel Selection
Lever - "Out"
Position for
Liquid Propane
(Vapor) Fuel
Figure 1.7 - 12, 14, 16, 17, & 20kW,
GT-990/GT-999 (Airbox Cover Removed)
Fuel Selection Lever - "In" Position for Natural Gas Fuel
Figure 1.8 - 12, 14, 16, 17, & 20kW,
GT-990/GT-999 (Airbox Cover Removed)
Fuel Selection Lever - "Out" Position for Liquid Propane
(Vapor) Fuel
1.11 LOCATION
1.11.1 GENERATOR
Install the generator set, in its protective enclosure,
outdoors, where adequate cooling and ventilating air
is always available (Figure 1.9). Consider these factors:
The installation of the generator • must comply
strictly with NFPA 37, NFPA 54, NFPA 58, and
NFPA 70 standards.
Install the unit where air inlet and outlet open-•
ings will not become obstructed by leaves, grass,
snow, etc.. If prevailing winds will cause blowing
or drifting, consider using a windbreak to protect
the unit.
Install the generator on high ground where water •
levels will not rise and endanger it.
Allow sufficient room on all sides of the generator •
for maintenance and servicing. This unit must be
installed in accordance with current applicable
NFPA 37 and NFPA 70 standards; as well as any
other federal, state and local codes for minimum
distances from other structures. DO NOT install
under wooden decks or structures unless there is
at least four (4) feet of clearance above the generator, three (3) feet of clearance on sides and front,
and 18 inches of clearance at back of unit.
Install the unit where rain gutter down spouts, •
roof run-off, landscape irrigation, water sprinklers
or sump pump discharge does not flood the unit
or spray the enclosure, including any air inlet or
outlet openings.
Install the unit where services will not be affected •
or obstructed, including concealed, underground
or covered services such as electrical, fuel, phone,
air conditioning or irrigation.
Where strong prevailing winds blow from one •
direction, face the generator air inlet openings to
the prevailing winds.
Figure 1.9 – Generator Clearances
10
Install the generator as close as possible to the fuel •
supply, to reduce the length of piping.
Install the generator as close as possible to the •
transfer switch. REMEMBER THAT LAWS OR
CODES MAY REGULATE THE DISTANCE AND
LOCATION.
The genset must be installed on a level surface. •
The base frame must be level within two (2) inches
all around.
The generator is typically placed on pea gravel or •
crushed stone. Check local codes if a concrete slab
is required. If a concrete base slab is required, all
federal, state and local codes should be followed.
Special attention should be given to the concrete
base slab which should exceed the length and
width of the generator by a minimum of six (6)
inches (0.152 meters) on all sides.
The engine exhaust fumes contain carbon mon-
oxide, which can be DEADLY. This dangerous
gas, if breathed in sufficient concentrations,
can cause unconsciousness or even death. This
exhaust system must be installed properly, in
strict compliance with applicable codes and standards. Following installation, do nothing that
might render the system unsafe or in noncompliance with such codes and standards.
• Operate the generator outdoors ONLY.
• Keep exhaust gases from entering a confined area
through windows, doors, ventilation or other
openings (Figure 1.9).
1.11.2 TRANSFER SWITCH ( if included)
1.11.2.1 8, 10, 12, 14, 16, 17 and 20kW Units
(if equipped)
The transfer switch that may have shipped inside
the carton with the 8, 10, 12, 14, 16 or 17kW generator is enclosed in a NEMA 1 (indoor rated only)
enclosure. The transfer switch that may have shipped
with the 20kW generator is enclosed in a NEMA 3R (indoor/outdoor rated) enclosure.
Install the transfer switch indoors on a firm, sturdy •
supporting structure.
To prevent switch distortion, level the switch if •
necessary. This can be done by placing washers
between the switch enclosure and mounting surface.
Never install the switch where water or any corro-•
sive substance might drip onto the enclosure.
Protect the switch at all times against excessive •
moisture, dust, dirt, lint, construction grit and
corrosive vapors.
Section 1 — General Information
Air-cooled Generators
If the AUTO/OFF/MANUAL switch is not set to its
OFF position, the generator can crank and start
as soon as the battery cables are connected. If
the utility power supply is not turned off, sparking can occur at the battery posts and cause an
explosion.
1.12 BATTERY REQUIREMENTS
See the Specifications section for correct battery size
and rating.
1.13 BATTERY INSTALLATION
Fill the battery with the proper electrolyte fluid if
necessary and have the battery fully charged before
installing it.
Before installing and connecting the battery, complete
the following steps:
1. Set the generator's AUTO/OFF/MANUAL switch to
OFF.
2. Turn off utility power supply to the transfer
switch.
3. Remove the 7.5A fuse from the generator control
panel.
Battery cables were factory connected at the generator (Figure 1.10). Connect cables to battery posts as
follows:
4. Connect the red battery cable (from starter contactor) to the battery post indicated by a positive,
POS or (+).
5. Connect the black battery cable (from frame
ground) to the battery post indicated by a negative, NEG or (—).
Figure 1.10 – Battery Cable Connections
11
Section 1 — General Information
Air-cooled Generators
NOTE:
Dielectric grease should be used on battery posts
to aid in the prevention of corrosion.
NOTE:
Damage will result if battery connections are made
in reverse.
NOTE:
In areas where temperatures regularly fall below
10° F (-12° C) it is recommended that a pad type
battery heater be installed to aid in cold climate
starting.
1.14 THE BATTERY
DANGER
Do not dispose of the battery in a fire. The
battery is capable of exploding.
A battery presents a risk of electrical shock
and high short circuit current. The following precautions are to be observed when working on
batteries:
• Remove the 7.5A fuse from the generator control
panel.
• Remove watches, rings or other metal objects;
• Use tools with insulated handles;
• Wear rubber gloves and boots;
• Do not lay tools or metal parts on top of the
battery; and
• Disconnect charging source prior to connecting or
disconnecting battery terminals.
Do not open or mutilate the battery. Released
electrolyte has been known to be harmful to the
skin and eyes, and to be toxic.
The electrolyte is a dilute sulfuric acid that is
harmful to the skin and eyes. It is electrically
conductive and corrosive.
The following procedures are to be observed:
• Wear full eye protection and protective clothing;
• Where electrolyte contacts the skin, wash it off
immediately with water;
• Where electrolyte contacts the eyes, flush thor-
oughly and immediately with water and seek
medical attention; and
• Spilled electrolyte is to be washed down with an
acid neutralizing agent. A common practice is to
use a solution of 1 pound (500 grams) bicarbonate
of soda to 1 gallon (4 liters) of water. The bicarbonate of soda solution is to be added until the
evidence of reaction (foaming) has ceased. The
resulting liquid is to be flushed with water and the
area dried.
12
Lead-acid batteries present a risk of fire because
they generate hydrogen gas. The following
procedures are to be followed:
• DO NOT SMOKE when near the battery;
• DO NOT cause flame or spark in battery area; and
• Discharge static electricity from body before touching the battery by first touching a grounded metal
surface.
Be sure the AUTO/OFF/MANUAL switch is set to
the OFF position before connecting the battery
cables. If the switch is set to AUTO or MANUAL,
the generator can crank and start as soon as the
battery cables are connected.
Be sure the utility power supply is turned off
and the 7.5A fuse is removed from the generator control panel, or sparking may occur at the
battery posts as the cables are attached and
cause an explosion.
Servicing of the battery is to be performed or supervised by personnel knowledgeable of batteries and
the required precautions. Keep unauthorized personnel away from batteries.
See the Specifications section for the correct size
and rating when replacing the battery. Have these
procedures performed at the intervals specified in
the “Service Schedule.” A negative ground system is
used. Battery connections are shown on the wiring
diagrams. Make sure the battery is correctly connected and terminals are tight. Observe battery polarity
when connecting the battery to the generator set.
1.15 BATTERY CHARGER
NOTE:
These generators DO NOT contain an internal battery charger.
NOTE:
The manufacturer provides a battery trickle charger that is active when the unit is set up for automatic operation. With the battery installed and
utility power source voltage available to the transfer switch, the battery receives a trickle charge
to prevent self-discharge. The trickle charger is
designed to help extend the life of the battery by
maintaining the battery. The trickle charge feature
cannot be used to recharge a discharged battery.
For units shipped with a transfer switch/load center,
the battery charger is pre-installed in the transfer
switch enclosure.
For units shipped without a transfer switch/load center, a separate battery charger module is included
with the generator.
(For battery charger installation, see the Generator
Install Guidelines and Battery Charger Instructions
included with the unit.)
Section 2 — Post Installation Start-up and Adjustments
DANGER
Air-cooled Generators
2.1 BEFORE INITIAL START-UP
NOTE:
These units have been run and tested at the factory prior to being shipped and do not require any
type of break-in.
Before starting, complete the following:
1. Set the generator’s main circuit breaker to its
OFF (or OPEN) position.
2. Set the generator's AUTO/OFF/MANUAL switch to
the OFF position.
3. Turn OFF all breakers on the load center of the
transfer box (T1 and T2).
4. Turn OFF all loads connected to the transfer
switch terminals T1 and T2.
5. Check the engine crankcase oil level and, if necessary, fill to the dipstick FULL mark with the recommended oil. Do not fill above the FULL mark.
6. Check the fuel supply. Gaseous fuel lines must
have been properly purged and leak tested in
accordance with applicable fuel-gas codes. All
fuel shutoff valves in the fuel supply lines must
be open.
During initial start up only, the generator may exceed
the normal number of start attempts and experience
an “over crank” fault (See the "Overcrank" section).
This is due to accumulated air in the fuel system during installation. Reset the control board and restart
up to two more times, if necessary. If unit fails to
start, contact the local dealer for assistance.
Never operate the engine with the oil level
below the “Add” mark on the dipstick. Doing
this could damage the engine.
2.2 CHECK TRANSFER SWITCH
2.3 ELECTRICAL CHECKS
Complete electrical checks as follows:
1. Set the generator's main circuit breaker to its
OFF (or OPEN) position.
2. Set the generator's AUTO/OFF/MANUAL switch to
the OFF position.
3. Turn OFF all breakers on the load center of the
transfer box (T1 and T2).
4. Turn on the utility power supply to the transfer
switch using the means provided (such as a utility
main line circuit breaker).
DANGER
The transfer switch is now electrically “hot.”
Contact with “hot” parts will result in extremely
hazardous and possibly fatal electrical shock.
Proceed with caution.
5. Use an accurate AC voltmeter to check utility
power source voltage across transfer switch terminals N1 and N2. Nominal line-to-line voltage
should be 240 volts AC.
6. Check utility power source voltage across terminals N1 and the transfer switch neutral lug; then
across terminal N2 and neutral. Nominal line-toneutral voltage should be 120 volts AC.
7. When certain that utility supply voltage is compatible with transfer switch and load circuit ratings,
turn OFF the utility power supply to the transfer
switch.
8. On the generator panel, set the Auto/Off/ Manual
switch to MANUAL. The engine should crank and
start.
9. Let the engine warm up for about five minutes to
allow internal temperatures to stabilize. Then, set
the generator’s main circuit breaker to its ON (or
closed) position.
OPERATION
Refer to the "Manual Transfer Operation" section, of
the owner’s manual for procedures.
DANGER
Do not attempt manual transfer switch opera-
tion until all power voltage supplies to the
transfer switch have been positively turned off.
Failure to turn off all power voltage supplies
will result in extremely hazardous and possibly
fatal electrical shock.
Proceed with caution! Generator power voltage
is now supplied to the transfer switch. Contact
with live transfer switch parts will result in dangerous and possibly fatal electrical shock.
10. Connect an accurate AC voltmeter and a frequency meter across transfer switch terminal lugs E1
and E2. 8kW voltage should be 230-240 volts at
a frequency of 61-63 Hertz. 12, 14, 16, 17 and
20kW voltage should be 247-249 at a frequency
of 59.5-60.5 Hertz. 10kW voltage should be
220-230 volts at a frequency of 59.5-60.5 Hertz.
11. Connect the AC voltmeter test leads across terminal lugs E1 and neutral; then across E2 and
neutral. In both cases, voltage reading should be
121-126 volts AC (8kW), and 125-126 volts AC
(10, 12, 14, 16, 17 and 20kW).
13
Section 2 — Post Installation Start-up and Adjustments
Air-cooled Generators
12. Set the generator’s main circuit breaker to its
OFF (or OPEN) position. Let the engine run at noload for a few minutes to stabilize internal engine
generator temperatures.
13. Set the generator's AUTO/OFF/MANUAL switch to
OFF. The engine should shut down.
NOTE:
It is important not to proceed until certain that
generator AC voltage and frequency are correct
and within the stated limits. Generally, if both AC
frequency and voltage are high or low, the engine
governor requires adjustment* (*GH410 only). If
frequency is correct, but voltage is high or low, the
generator’s voltage regulator requires adjustment.
2.4 GENERATOR TESTS UNDER LOAD
To test the generator set with electrical loads applied,
proceed as follows:
1. Set generator’s main circuit breaker to its OFF
(or OPEN) position.
2. Turn OFF all breakers on the load center of the
transfer box (T1 and T2).
3. Set the generator's AUTO/OFF/MANUAL switch to
OFF.
4. Turn OFF the utility power supply to the transfer
switch, using the means provided (such as a utility main line circuit breaker).
Do not attempt manual transfer switch opera-
tion until all power voltage supplies to the
transfer switch have been positively turned off.
Failure to turn off all power voltage supplies
will result in extremely hazardous and possibly
fatal electrical shock.
5. Manually set the transfer switch to the STANDBY
position, i.e., load terminals connected to the
generator's E1/E2 terminals. The transfer switch
operating lever should be down.
6. Set the generator's AUTO/OFF/MANUAL switch
to MANUAL. The engine should crank and start
immediately.
7. Let the engine stabilize and warm up for a few
minutes.
8. Set the generator’s main circuit breaker to its ON
(or CLOSED) position. Loads are now powered
by the standby generator.
9. Turn ON the load center of the transfer switch
(T1 and T2).
10. Connect an accurate AC voltmeter and a frequency meter across terminal lugs E1 and E2.
8kW voltage should be greater than 230 volts and •
frequency should be greater than 58 Hz.
10, • 12, 14, 16, 17 and 20kW voltage should be
greater than 240 volts and frequency should be
60 Hz.
11. Let the generator run at full rated load for 20-30
minutes. Listen for unusual noises, vibration or
other indications of abnormal operation. Check
for oil leaks, evidence of overheating, etc.
12. When testing under load is complete, turn OFF
electrical loads.
13. Set the generator's main circuit breaker to its
OFF (or OPEN) position.
14. Let the engine run at no-load for a few minutes.
15. Set the AUTO/OFF/MANUAL switch to OFF. The
engine should shut down.
2.5 CHECKING AUTOMATIC
OPERATION
To check the system for proper automatic operation,
proceed as follows:
1. Set generator’s main circuit breaker to its OFF
(or OPEN) position.
2. Check that the AUTO/OFF/MANUAL switch is set
to OFF.
3. Turn OFF the utility power supply to the transfer
switch, using means provided (such as a utility
main line circuit breaker).
4. Manually set the transfer switch to the UTILITY
position, i.e., load terminals connected to the utility power source side.
5. Turn ON the utility power supply to the transfer
switch, using the means provided (such as a utility main line circuit breaker).
6. Set the generator's main circuit breaker to its ON
(or CLOSED) position.
7. Set the AUTO/OFF/MANUAL switch to AUTO. The
system is now ready for automatic operation.
8. Turn OFF the utility power supply to the transfer
switch.
With the AUTO/OFF/MANUAL switch at AUTO, the
engine should crank and start when the utility source
power is turned OFF after a 10 second delay. After
starting, the transfer switch should connect load
circuits to the standby side after a five (5) second
delay. Let the system go through its entire automatic
sequence of operation.
With the generator running and loads powered by
generator AC output, turn ON the utility power supply
to the transfer switch. The following should occur:
After about 15 seconds, the switch should transfer •
loads back to the utility power source.
About one minute after re-transfer, the engine •
should shut down.
14
GOVERNOR
SHAFT
PRIMARY
ADJUST
SCREW
GOVERNOR
CLAMP
BOLT
SECONDARY
ADJUST SCREW
Section 2 — Post Installation Start-up and Adjustments
Air-cooled Generators
2.6 ENGINE GOVERNOR ADJUSTMENT
If both AC frequency and voltage are correspondingly
high or low, adjust the engine governor as follows:
2.6.1 8 KW UNITS
The engine must be OFF to perform steps 1 and
2.
1. Loosen the governor clamp bolt (Figure 2.1).
2. Hold the governor lever at its wide open throttle
position (clockwise), and rotate the governor
shaft clockwise as far as it will go. Then, tighten
the governor lever clamp bolt to 70 inch-pounds
(8 N-m).
Figure 2.1 — Engine Governor Adjustment
Single Cylinder Engines
2.6.3 ADDITIONAL CORROSION
PROTECTION
Periodically spray all engine linkage parts and brackets with corrosion inhibiting spray such as WD-40 or
a comparable product.
2.7 VOLTAGE REGULATOR
ADJUSTMENT
2.7.1 8 & 10KW UNITS
Due to the brushless design of these two alternators,
no voltage regulator is used and therefore no voltage
adjustment is required.
2.7.2 12, 14, 16, 17 & 20KW UNITS
With the frequency between 59.5 -60.5 Hertz at noload, slowly turn the slotted potentiometer (Figure
2.2) until line voltage reads 247-249 volts.
Figure 2.2 – Voltage Adjustment Potentiometer
3. Start the generator; let it stabilize and warm up
at no-load.
4. Connect a frequency meter across the generators
AC output leads.
5. Turn the primary adjust screw to obtain a frequency reading of 61.5 Hertz. Turn the secondary
adjust screw to obtain a frequency of 62.5 Hz.
2.6.2 12, 14, 16, 17 & 20KW UNITS
All V-twin units DO NOT require an engine governor adjustment due to their design.
NOTE:
Turn to
adjust voltage.
NOTE:
The access panel on top of the control panel must
be removed to adjust the voltage regulator.
NOTE:
The voltage regulator is housed behind the generator's control panel. The regulator maintains a voltage in direct proportion to frequency at a 2-to-1
ratio. For example, at 60 Hertz, line-to-neutral
voltage will be 124 volts.
15
Section 3 — Operation
Air-cooled Generators
3.1 CONTROL PANEL INTERFACE
3.1.1 USING THE AUTO/OFF/MANUAL
SWITCH
1. “AUTO” Position – Selecting this switch activates
fully automatic system operation. It also allows
the unit to automatically start and exercise the
engine every seven days with the setting of the
exercise timer (see the Setting the Exercise Timer
section).
2. “OFF” Position – This switch position shuts down
the engine. This position also prevents automatic
operation.
3. “MANUAL” Position – Set the switch to MANUAL
to crank and start the engine. Transfer to standby
power will not occur unless there is a utility failure.
Figure 3.1 – 8kW Generator Control Panel
With the switch set to AUTO, the engine may
crank and start at any time without warning.
Such automatic starting occurs when utility
power source voltage droops below a preset
level or during the normal exercise cycle. To
prevent possible injury that might be caused
by such sudden starts, always set the switch to
OFF and remove the fuses before working on or
around the generator or transfer switch. Then,
place a “DO NOT OPERATE” tag on the generator panel and on the transfer switch.
16
(FIGURES 3.1 & 3.2)
SYSTEM READY
LOW BATTERY
LOW OIL PRESSURE
HIGH OIL TEMPERATURE
OVERSPEED
RPM SENSOR LOSS
OVERCRANK
SET
EXERCISE
Figure 3.2 – 10/12/14/16/17 & 20kW Generator
Control Panel
ECS
ENTER
3.1.2 SETTING THE EXERCISE TIMER
This generator is equipped with an exercise timer.
Once it is set, the generator will start and exercise
every seven days, on the day of the week and at the
time of day specified. During this exercise period,
the unit runs for approximately 12 minutes and then
shuts down. Transfer of loads to the generator output does not occur during the exercise cycle unless
utility power is lost.
8kW
A switch on the control panel (see Figure 3.1) permits selection of the day and time for the system to
exercise. At the chosen time, perform the following
sequence to select the desired day and time of day
the system will exercise. Remember seasonal time
changes affect the exercise settings.
1. Verify that the AUTO/OFF/MANUAL switch is set
to AUTO.
2. Press and hold the “Set Exercise” switch for several seconds. All the red LED’s will stop flashing
immediately and the generator will start.
3. The generator will start and run for approximately 12 minutes and then shut down. The exerciser
is now set to run at this time of day each week.
Example: If the “Set Exercise” pressed on Saturday
afternoon at 2:00 p.m., the generator will start and
exercise for approximately 12 minutes every Saturday
at 2:00 p.m.
Section 3 — Operation
Air-cooled Generators
NOTE:
The exerciser will only work in the AUTO mode
and will not work unless this procedure is performed. The exerciser will need to be reset every
time the 12 volt battery is disconnected and then
reconnected, and when the fuse is removed and/
or replaced.
10 to 20 KW - INSTALLATION ASSISTANT
Upon first power up of the generator, the display
interface will begin an installation assistant. The
assistant will prompt the user to set the minimum
settings to operate. These settings are simply: Current
Date/Time and Exercise Day/Time. The maintenance
intervals will be initialized when the exercise time is
entered (Figure 3.2).
The exercise settings can be changed at any time via
the "EDIT" menu (see Appendix, "Menu System").
If the 12 volt battery is disconnected or the fuse
removed, the Installation Assistant will operate upon
power restoration. The only difference is the display
will only prompt the customer for the current Time
and Date.
IF THE INSTALLER TESTS THE GENERATOR
PRIOR TO INSTALLATION, PRESS THE “ENTER”
KEY TO AVOID SETTING UP THE EXERCISE
TIME. THIS WILL ENSURE THAT WHEN THE
CUSTOMER POWERS UP THE UNIT, HE WILL
STILL BE PROMPTED TO ENTER AN EXERCISE
TIME.
NOTE:
The exerciser will only work in the AUTO mode and
will not work unless this procedure is performed.
The current date/time will need to be reset every
time the 12 volt battery is disconnected and then
reconnected, and/or when the fuse is removed.
3.1.3 DISPLAY INTERFACE
8 kW LED Display
Seven (7) LED’s are provided for user status indications. The LED functions are:
1. System Ready (green)
2. Low Battery (red)
3. Low Oil Pressure (red)
4. High Oil Temperature (red)
5. Over Speed (red)
6. RPM Sensor Loss (red)
7. Over Crank (red)
See the Protection Systems section for details.
10 to 20KW DISPLAY INTERFACE MENUS
The LCD display is organized as detailed below:
The “Home” page, this page is the default page •
which will be displayed if no keys are pressed for
30 seconds. This page normally shows the current
Status message and the current date and time.
The highest priority active Alarm and/or Warning
will be automatically posted on this page as well as
flashing the backlight when such an event is detected. In the case of multiple Alarms or Warnings,
only the first message will be displayed. To clear
an Alarm or Warning, see the Protection Systems
section - Clear Alarm.
The display backlight is normally off. If the user •
presses any key, the backlight will come on automatically and remain on for 30 seconds after the
last key was pressed.
The “Main Menu” page will allow the user to •
navigate to all other pages or sub-menus by using
the Left/Right and Enter keys. This page can be
accessed at any time with several presses of the
dedicated Escape key. Each press of the Escape
key takes you back to the previous menu until the
main menu is reached. This page displays the following options: HISTORY; STATUS; EDIT; AND
DEBUG. (See the Appendix - "Menu System".)
3.2 AUTOMATIC TRANSFER
OPERATION
To select automatic operation, do the following:
1. Make sure the transfer switch main contacts are
set to their UTILITY position, i.e., loads connected to the utility power source (Figure 3.2).
2. Be sure that normal UTILITY power source voltage is available to transfer switch terminal lugs
N1 and N2 (Refer to the Electrical Data section).
3. Set the generator’s AUTO/OFF/MANUAL switch to
AUTO.
4. Set the generator’s main circuit breaker to its ON
(or CLOSED) position.
With the preceding steps complete, the generator will
start automatically when utility source voltage drops
below a preset level. After the unit starts, loads are
transferred to the standby power source. Refer to the
Sequence of Automatic Operation section.
17
Section 3 — Operation
Air-cooled Generators
3.3 SEQUENCE OF AUTOMATIC
OPERATION
3.3.1 UTILITY FAILURE
Initial Conditions: Generator in Auto, ready to run,
load being supplied by utility source. When utility
fails (below 65% of nominal), a 10 second (optionally
programmable on the 17 and 20kW only) line interrupt delay time is started. If the utility is still gone
when the timer expires, the engine will crank and
start. Once started, a five (5) second engine warmup timer will be initiated. When the warm-up timer
expires, the control will transfer the load to the generator. If the utility power is restored (above 75% of
nominal) at any time from the initiation of the engine
start until the generator is ready to accept load (5
second warm-up time has not elapsed), the controller will complete the start cycle and run the generator through its normal cool down cycle; however, the
load will remain on the utility source.
3.3.2 CRANKING
The system will control the cyclic cranking as follows:
16 second crank, seven (7) second rest, 16 second
crank, seven (7) second rest followed by three (3)
additional cycles of seven (7) second cranks followed
by seven (7) second rests.
Choke Operation
1. The 990/999cc engines have an electric choke in
the air box that is automatically controlled by the
electronic control board.
2. The 530cc engines have an electric choke on the
divider panel air inlet hose that is automatically
controlled by the electronic control board.
3. The 410cc engines have a choke behind the air
box that is automatically controlled by the electronic control board.
Failure to Start
This is defined as any of the following occurrences
during cranking.
1. Not reaching starter dropout within the specified
crank cycle. Starter dropout is defined as four (4)
cycles at 1,000 RPM.
2. Reaching starter dropout, but then not reaching
2200 RPM within 15 seconds. In this case the
control board will go into a rest cycle for seven
(7) seconds, then continue the rest of the crank
cycle.
During a rest cycle the start and fuel outputs are
de-energized and the magneto output is shorted to
ground.
Cranking Conditions
The following notes apply during cranking cycle.
1. Starter motor will not engage within five (5) seconds of the engine shutting down.
2. The fuel output will not be energized with the
starter.
3. The starter and magneto outputs will be energized together.
4. Once the starter is energized the control board
will begin looking for engine rotation. If it does
not see an RPM signal within three (3) seconds
it will shut down and latch out on RPM sensor
loss.
5. Once the control board sees an RPM signal it will
energize the fuel solenoid, drive the throttle open
and continue the crank sequence.
6. Starter motor will disengage when speed reaches
starter dropout.
7. If the generator does not reach 2200 RPM within
15 seconds, re-crank cycle will occur.
8. If engine stops turning between starter dropout
and 2200 RPM, the board will go into a rest cycle
for seven (7) seconds then re-crank (if additional
crank cycles exist).
9. Once started, the generator will wait for a holdoff period before starting to monitor oil pressure
and oil temperature (refer to the Alarm Messages
section for hold-off times).
10. During Manual start cranking, if the Mode switch
is moved from the Manual position, the cranking
stops immediately.
11. During Auto mode cranking, if the Utility returns,
the cranking cycle does NOT abort but continues
until complete. Once the engine starts, it will run
for one (1) minute, then shut down.
3.3.3 LOAD TRANSFER
The transfer of load when the generator is running is
dependent upon the operating mode as follows:
1. Manual
Will not transfer to generator if utility is present.•
Will transfer to generator if utility fails (below •
65% of nominal for 10 consecutive seconds.
Will transfer back when utility returns for 15 con-•
secutive seconds. The engine will continue to run
until removed from the Manual mode.
18
2. Auto
DANGER
Will start and run if Utility fails for 10 consecu-•
tive seconds.
Will start a five (5) second engine warm-up •
timer.
Will not transfer if utility subsequently returns.•
Will transfer to generator if utility is still not pres-•
ent.
Will transfer back to utility once utility returns •
(above 75% of nominal) for 15 seconds.
Will transfer back to utility if the generator is •
shut down for any reason (such as the switch is
in the OFF position or a shutdown alarm.
After transfer, will shut down engine after one (1) •
minute cool-down time.
3. Exercise
Will not exercise if generator is already running •
in either Auto or Manual mode.
During exercise, the controller will only transfer •
if utility fails during exercise for 10 seconds, and
will switch to Auto mode.
Section 3 — Operation
Air-cooled Generators
Do not attempt to activate the transfer switch
manually until all power voltage supplies to the
switch have been positively turned off. Failure
to turn off all power voltage supplies may result
in extremely hazardous and possibly fatal electrical shock.
4. Use the manual transfer handle inside the transfer switch to move the main contacts to their
STANDBY position, i.e., loads connected to the
standby power source (Figure 3.3).
5. To crank and start the engine, set the AUTO/OFF/
MANUAL switch to MANUAL.
6. Let the engine stabilize and warm up for a few
minutes.
7. Set the generator’s main circuit breaker to its ON
(or CLOSED) position. The standby power source
now powers the loads.
Figure 3.3 – Manual Transfer Switch Operation
3.3.4 UTILITY RESTORED
Initial Condition: Generator supplying power to
customer load. When the utility returns (above 75%
of nominal), a 15 second return to utility timer will
start. At the completion of this timer, if the utility
supply is still present and acceptable, the control
will transfer the load back to the utility and run the
engine through a one (1) minute cool down period
and then shut down. If utility fails for three (3) seconds during this cool down period, the control will
transfer load back to the generator and continue to
run while monitoring for utility to return.
3.4 MANUAL TRANSFER OPERATION
3.4.1 TRANSFER TO GENERATOR
POWER SOURCE
To start the generator and activate the transfer switch
manually, proceed as follows:
1. Set the generator’s AUTO/OFF/MANUAL switch to
OFF.
2. Set the generator’s main circuit breaker to its
OFF (or OPEN) position.
3. Turn OFF the utility power supply to the transfer
switch using the means provided (such as a utility
main line circuit breaker).
3.4.2 TRANSFER BACK TO UTILITY POWER
SOURCE
When utility power has been restored, transfer back
to that source and shut down the generator. This can
be accomplished as follows:
1. Set the generator’s main circuit breaker to its
OFF (or OPEN) position.
2. Let the engine run for a minute or two at no-load
to stabilize the internal temperatures.
3. Set the generator’s AUTO/OFF/MANUAL switch
to its OFF (or OPEN) position. The engine should
shut down.
4. Check that utility power supply to the transfer
switch is turned OFF.
19
DANGER
Section 3 — Operation
Air-cooled Generators
Do not attempt to activate the transfer switch
manually until all power voltage supplies to the
switch have been positively turned off. Failure
to turn off all power voltage supplies may result
in extremely hazardous and possibly fatal electrical shock.
5. Use the manual transfer handle inside the transfer switch to move the main contacts back to their
UTILITY position, i.e., loads connected to the utility power source (Figure 3.2).
6. Turn ON the utility power supply to the transfer
switch using the means provided.
7. Set the system to automatic operation as outlined
in Automatic Transfer Operation section.
Figure 3.4 – Side Compartment
3.5 SIDE COMPARTMENT (V-TWIN
ONLY)
Local codes may require this compartment to be
locked. A hasp is provided so the owner can secure
the compartment with their own padlock. Check
local codes in the area.
3.5.1 MAIN CIRCUIT BREAKER
This is a 2-pole breaker rated according to the
Specifications section.
3.5.2 EXTERIOR READY LIGHTS
Green LED ‘Ready’ light (10, 12, 14, 16, 17 & 20 •
KW) is on when utility is present and switch is in
AUTO indicating the generator is ready and when
the generator is running.
Red LED ‘Alarm’ light (10, 12, 14, 16, 17 & 20 •
KW) is on when the generator is OFF or a fault is
detected. (See the Protections Systems section.)
Yellow LED ‘Maintenance’ light (17 & 20 KW) (See •
the Protections Systems section.)
3.5.3 120 VAC GFCI OUTLET & 15 AMP
These models are equipped with an external, 15 amp,
120 volt, GFCI convenience outlet that is located in
a compartment on the right side of generator (Figure
1.3).
When the generator is running, in the absence of utility power, this outlet may also be used to power items
outside your home such as lights or power tools. This
outlet may also be used when utility power is present by running the generator in manual mode. This
outlet does not provide power if the generator is not
running. This outlet is protected by a 15 amp circuit
breaker in the same compartment as the outlet. (Do
not use when the generator is running in exercise
mode.)
20
(FIGURES 3.4 & 3.5)
BREAKER (17 & 20 KW ONLY)
Figure 3.5 – Open Side Compartment
120V GFCI Outlet15 Amp Outlet Breaker
Main Circuit BreakerLED Indicator Lights
3.6 PROTECTION SYSTEMS
3.6.1 ALARMS
Highest Priority (Latching) Displayed on the control panel and the external red LED (V-twins only).
They must be cleared before the alarm message goes
away. The alarm log records each occurrence (see
Appendix - "Menu System").
Low Oil Pressure (Shutdown Alarm)
A five (5) second delay on start-up and seven (7) second delay once the engine is running.
This switch (Figure 3.6) has normally closed contacts that are held open by engine oil pressure during operation. Should the oil pressure drop below
the five (5) PSI range, switch contacts close and the
engine shuts down. The unit should not be restarted
until oil level is verified.
Section 3 — Operation
Air-cooled Generators
High Engine Temperature (Shutdown Alarm –
Auto Reset)
A 10 second delay on start-up and one (1) second
delay before shutdown. Auto reset when the condition
clears and restart the engine if a valid start signal is
still present.
This switch’s contacts (Figure 3.6) close if the temperature should exceed approximately 144° C (293°
F), initiating an engine shutdown. Once the oil temperature drops to a safe level the switch’s contacts
open again.
Over Crank (Shutdown Alarm)
This occurs if the engine has not started within the
specified crank cycle. (See "Cranking" section.)
Figure 3.6 – Low Oil Pressure and
High Temperature Switches
Low Oil Switch
L
o
o
s
e
Oil Filter
Oil
Drain
Hose
NOTE:
The oil drain hose may be routed in the opposite
direction as shown in figure.
High Temp Switch
n
Over Speed (Shutdown Alarm)
4320 RPM for three (3) seconds or 4500 RPM immediately. This feature protects the generator from damage by shutting it down if it happens to run faster
than the preset limit. This protection also prevents
the generator from supplying an output that could
potentially damage appliances connected to the generator circuit. Contact the nearest authorized dealer
if this failure occurs.
RPM Sense Loss (Shutdown Alarm)
During cranking, if the Control Board does not see
a valid RPM signal within three (3) seconds, it will
shut down and lock out on RPM sense loss. While
engine is running, if RPM signal is lost for one (1)
second the Control Board will shut the engine down,
wait 15 seconds, then re-crank the engine. If no RPM
signal is detected within the first three (3) seconds
of cranking, the Control Board will shut the engine
down and latch out on RPM sensor loss. If the RPM
signal is detected, the engine will start and run normally. If the RPM signal is subsequently lost again,
the Control Board will try one more re-crank attempt
before latching out and displaying the RPM sensor
failure message.
Under-frequency (Shutdown Alarm)
After starting, if the generator stays under frequency
for more than 30 seconds it will shut down. The
under-frequency setting is 50 Hz.
Internal Fault (Shutdown Alarm)
This alarm cannot be cleared, call service dealer.
CLEAR ALARM
8kW — Clear the alarm by setting the AUTO/OFF/•
MANUAL switch to the OFF position and back to
AUTO.
10 - 20kW — Clear the alarm by setting the AUTO/•
OFF/MANUAL switch to the OFF position. Press
the ENTER key to unlatch any active fault and
clear the corresponding alarm message.
3.6.2 WARNINGS
Second Priority (Non-latching) Displayed on the
control panel and the external yellow LED (V-twins
only). Warnings automatically clear when the monitored condition goes away. Warnings are recorded in
the alarm log. Warnings cannot cause shutdowns.
Low Battery
The Control Board monitors battery voltage and displays a warning if the battery voltage falls below 11.0
volts for one (1) minute. Warning is automatically
cleared if the battery voltage rises above 11.0 volts.
Battery voltage is not monitored during the crank
cycle.
Exercise Set Error
If the exercise period becomes corrupted, a warning
message will be displayed. This message will only
clear when the exercise period is reset.
21
Oil Dipstick
Oil Fill
Section 4 — Maintenance
Air-cooled Generators
3.6.3 MAINTENANCE ALERTS (10 - 20KW
ONLY)
Third priority
Maintenance Message
When a maintenance period expires, a warning message will be displayed. (16 through 20kW models
include an external yellow LED which will illuminate.)
The alert can be reset by pressing the Enter key,
which will cause the user to be prompted to confirm
the action. Resetting will clear the alert and reset the
maintenance counters for all conditions annunciated.
The history log will record the alert. The maintenance
counter will not accumulate without battery power.
Once battery power is restored, the set time prompt
will be displayed. The maintenance counters will be
adjusted to the new time and date.
NOTE:
Since most maintenance alerts will occur at the
same time (most have two (2) year intervals), only
one will appear on the display at any one time.
Once the first alert is cleared, the next active alert
will be displayed.
4. Install the dipstick.
5. Reset the AUTO/OFF/MANUAL switch to its original position.
Figure 4.1 — Oil Dipstick and Fill, 8kW
Oil Dipstick and Fill
Figure 4.2 — Oil Dipstick, 10kW
4.1 FUSE
The 7.5 amp fuse on the control panel protects the
DC control circuit against overload (Figures 3.1 and
3.2). This fuse is wired in series with the battery output lead to the panel. If this fuse element has melted
open, the engine will not be able to crank or start.
Replace this fuse using only an identical 7.5 amp
replacement fuse. Whenever the fuse is removed or
replaced, the exercise timer needs to be reset.
4.2 CHECKING THE ENGINE
OIL LEVEL
For oil capacities, see the Specifications section.
For engine oil recommendations, see the Engine Oil
Recommendations section. To check the engine oil
level, proceed as follows (Figures 4.1, 4.2 and 4.3):
1. Move the AUTO/OFF/MANUAL switch to the OFF
position.
2. Remove the dipstick and wipe it dry with a clean
cloth.
3. Completely insert the dipstick; then, remove it
again. The oil level should be at the dipstick “Full”
mark. If necessary, add oil to the “Full” mark
only. DO NOT FILL ABOVE THE “FULL” MARK.
Figure 4.3 — Oil Dipstick and Fill,
12, 14, 16, 17 & 20kW
Never operate the engine with the oil level
below the “Add” mark on the dipstick. Doing
this could damage the engine.
22
SA E 30
Sy nt he ti c 5W -3 0
10 W- 30
Section 4 — Maintenance
Air-cooled Generators
4.3 CHANGING THE ENGINE OIL
4.3.1 OIL CHANGE INTERVALS
See the "Service Schedule" section.
4.3.2 ENGINE OIL RECOMMENDATIONS
All oil should meet minimum American Petroleum
Institute (API) Service Class SJ, SL or better. Use
no special additives. Select the oil's viscosity grade
according to the expected operating temperature.
SAE 30 • Î Above 32° F
10W-30 • Î Between 40° F and -10° F
Synthetic 5W-30 • Î 10° F and below
Any attempt to crank or start the engine before
it has been properly serviced with the recommended oil may result in an engine failure.
SAE 30
10W-30
Synthetic 5W-30
4. Refill with the proper recommended oil (see the
Engine Oil Recommendations section). See the
Specifications section for oil capacities.
5. Start the engine, run for one (1) minute, and
check for leaks.
6. Shutdown and recheck oil level, add as needed.
DO NOT OVER FILL.
7. Reset the AUTO/OFF/MANUAL switch to the
AUTO position.
Figure 4.4 – Oil Drain Hose and Filter
Oil Filter
Oil
Drain
Hose
Low Oil Switch
L
o
o
s
e
n
High Temp Switch
4.3.3 OIL & OIL FILTER CHANGE PROCEDURE
To change the oil, proceed as follows:
1. Start the engine by moving the AUTO/OFF/
MANUAL switch to MANUAL and run until it
is thoroughly warmed up. Then shut OFF the
engine by moving the switch to the OFF position.
2. Immediately after the engine shuts OFF, pull the
oil drain hose (Figure 4.4) free of its retaining
clip. Remove the cap from the hose and drain the
oil into a suitable container.
3. After the oil has drained, replace the cap onto the
end of the oil drain hose. Retain the hose in the
clip.
Change the engine oil filter as follows:
1. With the oil drained, remove the old oil filter by
turning it counterclockwise.
2. Apply a light coating of clean engine oil to the gasket of the new filter. See the Specifications section
for recommended filter.
3. Screw the new filter on by hand until its gasket
lightly contacts the oil filter adapter. Then, tighten
the filter an additional 3/4 to one turn (Figure
4.4).
NOTE:
The oil drain hose may be routed in the opposite
direction as shown in figure.
4.4 CHANGING THE ENGINE
AIR CLEANER
4.4.1 12, 14, 16, 17 & 20KW GENERATORS
See "The Generator" section for the location of the air
cleaner. Use the following procedures (Figure 4.5):
1. Lift the roof and remove the door.
2. Turn the two screws counterclockwise to loosen.
3. Remove the cover and air filter.
4. Wipe away dust or debris from inside of the air
box and around edges.
5. Install the new air cleaner into the air box.
6. Install the cover. Turn the two cover screws clock-
wise to tighten.
See the Service Schedule section for air cleaner maintenance. See the Specifications section for air filter
replacement part number.
23
Section 4 — Maintenance
Air-cooled Generators
Figure 4.5 — 12, 14, 16, 17 & 20kW
Engine Air Cleaner
Screw
Cover
Filter
4.4.2 10KW GENERATORS
See "The Generator" section for the location of the air
cleaner. Use the following procedure (Figure 4.6):
1. Lift the roof and remove the door.
2. Turn the worm gear clamp screw counterclockwise to loosen.
3. Pull the old filter off the divider panel hub.
4. Wipe away dust or debris from the panel hub.
5. Install the new air cleaner onto the hub.
6. Turn the worm gear clamp screw clockwise to
tighten.
7. Replace door and roof.
4.4.3 8KW GENERATOR
See "The Generator" section to locate the air box. Use
the following procedures to replace the dirty air filter
within the air box (Figure 4.7).
1. Lift the roof and remove the door.
2. Push back on the latch of the yellow air filter
access door to swing open.
3. Pull out the old air filter and discard appropriately.
4. Install the new filter, open end first into the air
box.
5. Swing the yellow door shut and snap to close.
6. Replace door and close roof securely.
Figure 4.7 — 8kW Engine Air Cleaner Location
Air Cleaner
Cover
Figure 4.6 — 10kW Engine Air Cleaner
Air Filter
24
4.5 SPARK PLUG(S)
Reset the spark plug(s) gap or replace the spark
plug(s) as necessary. See the Service Schedule section
for maintenance requirements.
1. Clean the area around the base of the spark
plug(s) to keep dirt and debris out of the engine.
2. Remove the spark plug(s) and check the condition. Replace the spark plug(s) if worn or if reuse
is questionable. See the Service Schedule section
for recommended inspection. Clean by scraping
or washing using a wire brush and commercial
solvent. Do not blast the spark plug(s) to clean.
3. Check the spark plug gap using a wire feeler
gauge. Adjust the gap to 0.76 mm (0.030 inch)
for 8, 10 and 20kW; and 1.02 mm (0.040 inch)
for 12, 14, 16 and 17kW by carefully bending the
ground electrode (Figure 4.8).
DANGER
Section 4 — Maintenance
Air-cooled Generators
Figure 4.8 – Setting the Spark Plug Gap
SET PLUG GAP AT 0.76 mm (.030 inch) - 8, 10 &
20kW; 1.02 mm (.040 inch) - 12, 14, 16 & 17kW
4.6 BATTERY MAINTENANCE
The battery should be inspected per the "Service
Schedule" section. The following procedure should be
followed for inspection:
1. Inspect the battery posts and cables for tightness
and corrosion. Tighten and clean as necessary.
2. Check the battery fluid level of unsealed batteries
and, if necessary, fill with Distilled Water Only. Do
not use tap water in batteries.
3. Have the state of charge and condition checked.
This should be done with an automotive-type battery hydrometer.
Do not dispose of the battery in a fire. The
battery is capable of exploding.
A battery presents a risk of electrical shock
and high short circuit current. The following precautions are to be observed when working on
batteries:
• Remove the 7.5A fuse from the generator control
panel.
• Remove watches, rings or other metal objects;
• Use tools with insulated handles;
• Wear rubber gloves and boots;
• Do not lay tools or metal parts on top of the
battery; and
• Disconnect charging source prior to connecting or
disconnecting battery terminals.
Do not open or mutilate the battery. Released
electrolyte has been known to be harmful to the
skin and eyes, and to be toxic.
The electrolyte is a dilute sulfuric acid that is
harmful to the skin and eyes. It is electrically
conductive and corrosive. The following
procedures are to be observed:
• Wear full eye protection and protective clothing;
• Where electrolyte contacts the skin, wash it off
immediately with water;
• Where electrolyte contacts the eyes, flush thoroughly and immediately with water and seek
medical attention; and
• Spilled electrolyte is to be washed down with an
acid neutralizing agent. A common practice is to
use a solution of 1 pound (500 grams) bicarbonate
of soda to 1 gallon (4 liters) of water. The bicarbonate of soda solution is to be added until the
evidence of reaction (foaming) has ceased. The
resulting liquid is to be flushed with water and the
area dried.
Lead-acid batteries present a risk of fire because
they generate hydrogen gas. The
following procedures are to be followed:
• DO NOT SMOKE when near the battery;
• DO NOT cause flame or spark in battery area; and
• Discharge static electricity from body before touching the battery by first touching a grounded metal
surface.
Be sure the AUTO/OFF/MANUAL switch is set to
the OFF position before connecting the battery
cables. If the switch is set to AUTO or MANUAL,
the generator can crank and start as soon as the
battery cables are connected.
Be sure the utility power supply is turned off
and the 7.5A fuse is removed from the generator control panel, or sparking may occur at the
battery posts as the cables are attached and
cause an explosion.
4.7 ADJUSTING GH-410/GT-530/
990/999 VALVE CLEARANCE
After the first six (6) months of operation, check
the valve clearance in the engine, adjust if necessary.
Important: If feeling uncomfortable about doing
this procedure or the proper tools are not available,
please contact the Authorized Dealer for service
assistance. This is a very important step to ensure
longest life for the engine.
To check valve clearance:
The engine should be cool before checking. If •
valve clearance is 0.002" - 0.004" (0.05 - 0.1mm),
adjustment is not needed.
Remove spark plug wires and position wires away •
from plugs.
Remove spark plugs.•
25
Section 4 — Maintenance
Air-cooled Generators
Make sure the piston is at Top Dead Center (TDC) •
of its compression stroke (both valves closed). To
get the piston at TDC, remove the intake screen at
the front of the engine to gain access to the flywheel
nut. Use a large socket and socket wrench to rotate
the nut and hence the engine in a clockwise direction. While watching the piston through the spark
plug hole. The piston should move up and down.
The piston is at TDC when it is at its highest point
of travel.
To adjust valve clearance (if necessary), (Figure
4.9):
Make sure the engine is at 60° to 80° F.•
Make sure that the spark plug wire is removed •
from the spark plug and out of the way.
Remove the four screws attaching the valve cover.•
Loosen the rocker jam nut. Use an 10mm allen •
wrench to turn the pivot ball stud while checking
clearance between the rocker arm and the valve
stem with a feeler gauge. Correct clearance is
0.002-0.004 inch (0.05-0.1 mm).
Figure 4.9 - Valve Clearance Adjustment
Rocker
Jam Nut
Pivot Ball
Stud
Arm
Valve
Stem
Install spark plugs.•
Re-attach the spark plug wire to the spark plug.•
On the GT-530 and GT-990/999, repeat the process •
for the other cylinder.
4.8 COOLING SYSTEM
Air inlet and outlet openings in the generator compartment must be open and unobstructed for continued proper operation. This includes such obstructions as high grass, weeds, brush, leaves and snow.
Without sufficient cooling and ventilating air flow, the
engine/generator quickly overheats, which causes it
to quickly shut down. (See Figure 4.10 for vent locations.)
Make sure the doors and roof are in place during operation as running the generator with them
removed can effect cooling air movement.
Figure 4.10 – Cooling Vent Locations
NOTE:
Hold the rocker arm jam nut in place as the pivot
ball stud is turned.
When valve clearance is correct, hold the pivot ball
stud in place with the allen wrench and tighten the
rocker arm jam nut. Tighten the jam nut to 174 in/
lbs. torque. After tightening the jam nut, recheck
valve clearance to make sure it did not change.
Install new valve cover gasket.•
Re-attach the valve cover.•
NOTE:
Start all four screws before tightening or it will not
be possible to get all the screws in place. Make
sure the valve cover gasket is in place.
26
The exhaust from this product gets extremely
hot and remains hot after shutdown. High grass,
weeds, brush, leaves, etc. must remain clear of
the exhaust. Such materials may ignite and burn
from the heat of the exhaust system.
The maximum ambient temperature for the gen-
erator is 25° C (77° F).
4.9 ATTENTION AFTER SUBMERSION
If the generator has been submerged in water, it must
not be started and operated. Following any submer-
sion in water, have an Authorized Dealer thoroughly
clean, dry and inspect the generator. If the structure
(ex. home) has been flooded, it should be inspected
by a certified electrician to ensure there won't be any
electrical problems during generator operation or
when utility is returned.
Section 4 — Maintenance
Air-cooled Generators
4.10 CORROSION PROTECTION
Periodically wash and wax the enclosure using automotive type products. Frequent washing is recommended in salt water/coastal areas. Spray engine
linkages with a light oil such as WD-40.
4.11 OUT OF SERVICE PROCEDURE
4.11.1 REMOVAL FROM SERVICE
If the generator cannot be exercised every seven days,
and will be out of service longer than 90 days, prepare the generator for storage as follows:
1. Start the engine and let it warm up.
2. Close the fuel shutoff valve in the fuel supply line
and allow the unit to shut down.
3. Once the unit has shut down, switch to the OFF
position.
4. Set the generator’s main circuit breaker to its
OFF (or OPEN) position.
5. Set the AUTO/OFF/MANUAL switch to OFF and
turn off the utility power to the transfer switch.
Remove the 7.5A fuse from the generator control
panel. Disconnect the battery cables as outlined
in “General Hazards”.
6. While the engine is still warm from running,
drain the oil completely. Refill the crankcase with
oil. See ”Engine Oil Recommendations".
7. Attach a tag to the engine indicating the viscosity
and classification of the oil in the crankcase.
8. Remove the spark plug(s) and spray fogging
agent into the spark plug(s) threaded openings.
Reinstall and tighten the spark plug(s).
9. Remove the battery and store it in a cool, dry
room on a wooden board. Never store the battery
on any concrete or earthen floor.
10. Clean and wipe the entire generator.
4.11.2 RETURN TO SERVICE
To return the unit to service after storage, proceed
as follows:
1. Verify that utility power is turned off and that the
AUTO/OFF/MANUAL switch is set to OFF.
2. Check the tag on the engine for oil viscosity and
classification. Verify that the correct recommended oil is used in the engine (see the Engine Oil
Recommendations section). If necessary, drain
and refill with the proper oil.
3. Check the state of the battery. Fill all cells of
unsealed batteries to the proper level with distilled water. DO NOT USE TAP WATER IN THE
BATTERY. Recharge the battery to 100 percent
state of charge, or, if defective, replace the battery.
See “Specifications,” for type and size.
4. Clean and wipe the entire generator.
5. Make sure the 7.5A fuse is removed from the
generator control panel. Reconnect the battery.
Observe battery polarity. Damage may occur if the
battery is connected incorrectly.
6. Open the fuel shutoff valve.
7. Insert the 7.5A fuse into the generator control
panel. Start the unit by moving the AUTO/OFF/
MANUAL switch to MANUAL. Allow the unit to
warm up thoroughly.
8. Stop the unit by setting the AUTO/OFF/MANUAL
switch to OFF.
9. Turn on the utility power to the transfer switch.
10. Set the AUTO/OFF/MANUAL switch to AUTO.
11. The generator is now ready for service.
NOTE:
If the battery was dead or disconnected, the exercise timer (single cylinder), current date and time
(v-twin) must be reset.
4.11.3 ACCESSORIES
There are performance enhancing accessories available for the air-cooled generators.
Cold Weather Kits• are recommended in areas
where temperatures regularly fall below 10° F (-12°
C).
Scheduled Maintenance Kits• include all pieces
necessary to perform maintenance on the generator along with oil recommendations.
Auxiliary Transfer Switch Lockout• enables any
of the transfer switches to completely lock out
one large electrical load by tying into its control
system.
A Fascia Skirt Wrap• is standard on all 20kW
units. It's available for all other current production air-cooled units. It snaps together to provide a
smoothing, contoured look as well as rodent/insect
protection.
The PowerMaster• load prioritization device allows
home owners to potentially operator two (2) large
electrical loads by giving one (1) priority over the
other.
The Remote Monitor System• is a wireless, indoor
mounted, box that indicates generator run status
and allows for exercise programing as well as provide maintenance reminders.
Touch-up Paint Kits• are very important to main-
tain the look and integrity of the generator enclosure. These kits include touch-up paint and
instructions if the need should arise.
For more details on accessories, please contact an
Authorized Dealer.
27
Section 4 — Maintenance
Air-cooled Generators
4.12 SERVICE SCHEDULE
ATTENTION: It is recommended that all service work
be performed by the nearest Dealer.
SYSTEM/COMPONENTPROCEDUREFREQUENCY
X = Action
R = Replace as Necessary
InspectChangeClean
* = Notify Dealer if Repair is
Needed.
FUEL
Fuel lines and connections*
XM
LUBRICATION
Oil level
Oil
Oil filter
XM or 24 hours of
X2Y or 200 hours
X2Y or 200 hours
COOLING
Enclosure louvers
XXW
BATTERY
Remove corrosion, ensure
dryness
Clean and tighten battery
terminals
Check charge state
Electrolyte level
XXM
XXM
XREVERY 6 M
XREVERY 6 M
ENGINE AND MOUNTING
Air cleaner
Spark plug(s)
XR2Y or 200 hours
XR2Y or 200 hours
GENERAL CONDITION
Vibration, Noise, Leakage,
Temperature*
COMPLETE TUNE-UP*
* Contact the nearest dealer for assistance if necessary.
** Change oil and fi lter after fi rst eight (8) hours of operation and then every 200 hours thereafter, or 2 years, which-
ever occurs fi rst. Change sooner when operating under a heavy load or in a dusty or dirty environment or in high
ambient temperatures.
XM
TO BE COMPLETED BY A DEALER2Y or 200 hours
W = Weekly
M = Monthly
Y = Yearly
continuous operation.
of operation.**
of operation.**
28
Section 5 — Troubleshooting
Air-cooled Generators
5.1 TROUBLESHOOTING GUIDE
Problem Cause Correction
The engine will not crank. 1. Fuse blown. 1. Correct short circuit condition,
replace 7.5A fuse in generator
control panel.
2. Loose, corroded or defective 2. Tighten, clean or replace
battery cables. as necessary.
3. Defective starter contactor. (8 kW) 3. *
4. Defective starter motor. 4. *
5. Dead Battery. 5. Charge or replace battery.
The engine cranks but 1. Out of fuel. 1. Replenish fuel/Turn on fuel valve.
will not start. 2. Defective fuel solenoid (FS). 2. *
3. Open #14 wire from 3. *
engine control board.
4. Fouled spark plug(s). 4. Clean, re-gap or replace plug(s).
5. Valve lash out of adjustment. 5. Reset valve lash.
6. Choke not operating. 6. Verify choke plate moves freely.
The engine starts hard 1. Air cleaner plugged 1. Check, replace air cleaner.
and runs rough. or damaged.
2. Fouled spark plug(s). 2. Clean, re-gap or replace plug(s).
3. Fuel pressure incorrect. 3. Confirm fuel pressure to regulator
is 10-12” water column (0.36-0.43
psi) for LP, and 5-7” water column
(0.18-0.25 psi) for natural gas.
4. Fuel selector in wrong position. 4. Move selector to correct position.
The AUTO/OFF/MANUAL 1. Defective switch. 1. *
switch is set to OFF, but 2. AUTO/OFF/MANUAL switch 2. *
the engine continues wired incorrectly.
to run. 3. Defective control board. 3. *
There is no AC output 1. Main line circuit breaker is in 1. Reset circuit breaker
from the generator. the OFF (or OPEN) position. to ON (or CLOSED).
2. Generator internal failure. 2. *
There is no transfer to 1. Defective transfer switch coil. 1. *
standby after utility 2. Defective transfer relay. 2. *
source failure. 3. Transfer relay circuit open. 3. *
4. Defective control logic board. 4. *
Unit consumes large 1. Engine over filled with oil. 1. Adjust oil to proper level.
amounts of oil. 2. Improper type or viscosity of oil. 2. See "Engine Oil Recommendations".
3. Damaged gasket, seal or hose. 3. Check for oil leaks.
4. Engine breather defective. 4. *
*Contact the nearest Authorized Dealer for assistance.
29
Section 6 — Appendix
Air-cooled Generators
6.1 MENU SYSTEM NAVIGATION
To get to the MENU, use the "Esc" key from any
page. It may need to be pressed many times before
getting to the menu page. The currently selected
menu is displayed as a flashing word. Navigate to
the menu required by using the +/- keys. When the
menu required is flashing, press the ENTER key.
Depending on the menu selected, there may be a
list of choices presented. Use the same navigation
method to select the the desired screen (refer to the
Menu System diagram).
6.1.1 CHANGING SETTINGS (EDIT MENU)
To change a setting such as display contrast, go to the
EDIT menu and use the +/- keys to navigate to the
setting to change. Once this setting is displayed (e.g.
Contrast), press the ENTER key to go into the edit
mode. Use the +/- keys to change the setting, press
the ENTER key to store the new setting.
NOTE:
If the ENTER key is not pressed to save the new
setting, it will only be saved temporarily. The next
time the battery is disconnected, the setting will
revert back to the old setting.
NOTE: This Emission Control Warranty Statement pertains to this product only IF the generator size is 15 kW or below.
CALIFORNIA EMISSION CONTROL WARRANTY STATEMENT
YOUR WARRANTY RIGHTS AND OBLIGATIONS
The California Air Resources Board (CARB) and Generac Power Systems, Inc. (Generac) are pleased to explain the Emission
Control System Warranty on your new engine.* In California, new utility, and lawn and garden equipment engines must be
designed, built and equipped to meet the state’s stringent anti-smog standards. Generac will warrant the emission control
system on your engine for the periods of time listed below provided there has been no abuse, neglect, unapproved modification or improper maintenance of your engine.
Your emission control system may include parts such as the carburetor, ignition system and exhaust system. Generac will
repair your engine at no cost to you for diagnosis, replacement parts and labor, should a warrantable condition occur.
MANUFACTURER’S EMISSION CONTROL SYSTEM WARRANTY COVERAGE:
Emissions control systems on 1995 and later model year engines are warranted for two years as hereinafter noted. If, during such warranty period, any emission-related component or system on your engine is found to be defective in materials or
workmanship, repairs or replacement will be performed by a Generac Authorized Warranty Service Facility.
PURCHASER’S/OWNER’S WARRANTY RESPONSIBILITIES:
As the engine purchaser/owner, you are responsible for the completion of all required maintenance as listed in your factory
supplied Owner’s Manual. For warranty purposes, Generac recommends that you retain all receipts covering maintenance
on your engine. However, Generac cannot deny warranty solely due to the lack of receipts or for your failure to ensure the
completion of all scheduled maintenance.
As the engine purchaser/owner, you should, however, be aware that Generac may deny any and/or all warranty coverage or
responsibility if your engine, or a part/component thereof, has failed due to abuse, neglect , improper maintenance or unapproved modifications, or the use of counterfeit and/or “grey market” parts not made, supplied or approved by Generac.
You are responsible for contacting a Generac Authorized Warranty Service Facility as soon as a problem occurs. The
warranty repairs should be completed in a reasonable amount of time, not to exceed 30 days.
Warranty service can be arranged by contacting either your selling dealer or a Generac Authorized Warranty Service Facility.
To locate the Generac Authorized Warranty Service Facility nearest you, call our toll-free number:
1-800-333-1322
IMPORTANT NOTE: This warranty statement explains your rights and obligations under the Emission Control System
Warranty (ECS Warranty), which is provided to you by Generac pursuant to California law. See also the “Generac Limited
Warranties for Generac Power Systems, Inc.,” which is enclosed herewith on a separate sheet, also provided to you by
Generac. The ECS Warranty applies only to the emission control system of your new engine. If there is any conflict in
terms between the ECS Warranty and the Generac Warranty, the ECS Warranty shall apply except in circumstances where
the Generac Warranty may provide a longer warranty period. Both the ECS Warranty and the Generac Warranty describe
important rights and obligations with respect to your new engine.
Warranty service can be performed only by a Generac Authorized Warranty Service Facility. When requesting warranty service, evidence must be presented showing the date of the sale to the original purchaser/owner.
If you have any questions regarding your warranty rights and responsibilities, you should contact Generac at one of
the following addresses:
For Air-cooled Product ... For Liquid-cooled Product ...
ATTENTION WARRANTY DEPARTMENT ATTENTION WARRANTY DEPARTMENT
GENERAC POWER SYSTEMS, INC. GENERAC POWER SYSTEMS, INC.
P.O. BOX 297 211 MURPHY DRIVE
WHITEWATER, WI 53190 EAGLE, WI 53119
Part 1
36
Section 9 – Warranty
Air-cooled Generators
EMISSION CONTROL SYSTEM WARRANTY
Emission Control System Warranty (ECS Warranty) for 1995 and later model year engines:
(a) Applicability: This warranty shall apply to 1995 and later model year engines. The ECS Warranty Period shall begin on the
date the new engine or equipment is purchased by/delivered to its original, end-use purchaser/owner and shall continue
for 24 consecutive months thereafter.
(b) General Emissions Warranty Coverage: Generac warrants to the original, end-use purchaser/owner of the new engine or
equipment and to each subsequent purchaser/owner that each of its engines is ...
(1) Designed, built and equipped so as to conform with all applicable regulations adopted by the CARB pursuant to its
authority, and
(2) Free from defects in materials and workmanship which, at any time during the ECS Warranty Period, may cause a
warranted emissions-related part to fail to be identical in all material respects to the part as described in the engine
manufacturer’s application for certification.
(c) The ECS Warranty only pertains to emissions-related parts on your engine, as follows:
(1) Any warranted, emissions-related parts that are not scheduled for replacement as required maintenance in the Owner’s
Manual shall be warranted for the ECS Warranty Period. If any such part fails during the ECS Warranty Period, it shall
be repaired or replaced by Generac according to Subsection (4) below. Any such part repaired or replaced under the
ECS Warranty shall be warranted for the remainder of the ECS Warranty Period.
(2) Any warranted, emissions-related part that is scheduled only for regular inspection as specified in the Owner’s Manual
shall be warranted for the ECS Warranty Period. A statement in such written instructions to the effect of “repair or
replace as necessary” shall not reduce the ECS Warranty Period. Any such part repaired or replaced under the ECS
Warranty shall be warranted for the remainder of the ECS Warranty Period.
(3) Any warranted, emissions-related part that is scheduled for replacement as required maintenance in the Owner’s
Manual shall be warranted for the period of time prior to the first scheduled replacement point for that part. If the part
fails prior to the first scheduled replacement, the part shall be repaired or replaced by Generac according to Subsection
(4) below. Any such emissions-related part repaired or replaced under the ECS Warranty shall be warranted for the
remainder of the ECS Warranty Period prior to the first scheduled replacement point for such emissions-related part.
(4) Repair or replacement of any warranted, emissions-related part under this ECS Warranty shall be performed at no
charge to the owner at a Generac Authorized Warranty Service Facility.
(5) When the engine is inspected by a Generac Authorized Warranty Service Facility, the owner shall not be held responsible
for diagnostic costs if the repair is deemed warrantable.
(6) Generac shall be liable for damages to other original engine components or approved modifications proximately caused
by a failure under warranty of any emission-related part covered by the ECS Warranty.
(7) Throughout the ECS Warranty Period, Generac shall maintain a supply of warranted emission-related parts sufficient
to meet the expected demand for such emission-related parts.
(8) Any Generac authorized and approved emission-related replacement part may be used in the performance of any ECS
Warranty maintenance or repairs and will be provided without charge to the owner. Such use shall not reduce Generac
ECS Warranty obligations.
(9) Unapproved, add-on, modified, counterfeit and/or “grey market” parts may not be used to modify or repair a Generac
engine. Such use voids this ECS Warranty and shall be sufficient grounds for disallowing an ECS Warranty claim.
Generac shall not be held liable hereunder for failures of any warranted parts of a Generac engine caused by the use of
such an unapproved, add-on, modified, counterfeit and/or “grey market” part.
EMISSION RELATED PARTS INCLUDE THE FOLLOWING:
1) Fuel Metering System:
1.2) LPG/Natural Gas carburetion assembly and its internal components.
a) Fuel controller (if so equipped)
b) Mixer and its gaskets (if so equipped)
c) Carburetor and its gaskets (if so equipped)
d) Primary gas regulator (if so equipped)
e) LP liquid vaporizer (if so equipped)
2) Air Induction System including:
a) Intake pipe/manifold
b) Air cleaner
* Generac engine types covered by this warranty statement include the following:
1) Prepackaged Standby Generator
2) Auxiliary Power Unit (APU) Generator
3) Standby Generator
Part 2
3) Ignition System including:
a) Spark plug
b) Ignition module
4) Catalytic Muffler Assembly (if so equipped) including:
a) Muffler gasket
b) Exhaust manifold
5) Crankcase Breather Assembly including:
a) Breather connection tube
37
GENERAC® POWER SYSTEMS, INC.
P.O. BOX 297 • WHITEWATER, WI 53190
Part No. 0G8334Revision A (04/11/08)Printed in U.S.A.
Catalog No. OMASPB07-3
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.