Generac Power Systems Automatic Standby Generator, 8kW 11kW, 13kW, 14kW, 15kW Owner's Manual

...
Owner’s Manual
Automatic Standby Generator
Reference all appropriate documentation. This manual should remain with the unit.
n
NOT INTENDED FOR USE IN CRITICAL LIFE SUPPORT APPLICATIONS.
n
ONLY QUALIFIED ELECTRICIANS OR CONTRACTORS SHOULD ATTEMPT
INSTALLATION.
n
LISTED
C
US
Home Standby Models:
8kW to 20kW
WARNING!
California Proposition 65
Engine exhaust and some of its constituents are known to the state of California to cause cancer,
birth defects, and other reproductive harm.
WARNING!
California Proposition 65
This product contains or emits chemicals known to the state of California to cause cancer,
birth defects, and other reproductive harm.
Use this page to record important information about your generator set.
Record the information found on your unit data label on this page. For the location of the unit data label, see Section 2 General Information. The unit has a label plate affixed to the inside partition, to the left of the control panel console as shown in Figures 2-1, 2-2, and 2-3. For directions on how to open the top lid and remove the front panel, see Section 3 Opera­tion. The Unit Identification label provides the following information:
• Model Number
• Serial Number
• Control Panel Part Number
• Voltage Rating of the unit
• Maximum Current Rating of the unit (AMPS)
When contacting an Authorized Service Dealer about parts and service, always supply the complete model number and serial number of the unit.
Operation and Maintenance: Proper maintenance and care of the gen­erator ensures a minimum number of problems and keeps operating expenses at a minimum. It is the operator’s responsibility to perform all safety checks, to make sure that all maintenance for safe operation is performed promptly, and to have the equipment checked periodically by an Authorized Service Dealer. Normal maintenance, service and replace­ment of parts are the responsibility of the owner/operator and, as such, are not considered defects in materials or workmanship within the terms of the warranty. Individual operating habits and usage may contribute to the need for additional maintenance or service.
When the generator requires servicing or repairs, contact an Authorized Service Dealer for assistance. Authorized service technicians are factory­trained and are capable of handling all service needs.
To find your Local AUTHORIZED SERVICE DEALER
AUTHORIZED SERVICE
DEALER LOCATION
To locate the nearest AUTHORIZED
SERVICE DEALER, please call this
number:
1-800-333-1322
or, visit the dealer locator at:
www.generac.com/Service/DealerLocator/
i

Table of Contents

Section 1 — Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.1 — General Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.2 — General Safety Hazards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.3 — Exhaust Hazards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.4 — Electrical Hazards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.5 — Fire Hazards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.6 — Explosion Hazards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Section 2 — General Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.1 — The Generator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.2 — Protection Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.3 — Emission Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.4 — Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.5 — Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Section 3 — Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.1 — Control Panel Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.2 — Using the Auto/Off/Manual Buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.3 — Interface Menu Displays. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.4 — Automatic Transfer Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.5 — Turning the Generator Off When Operating Under Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.6 — Manual Transfer Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.7 — Side Compartment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.8 — Alarm Response Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.9 — Battery Charger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.10 — Setting the Exercise Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Section 4 — Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.1 — Performing Scheduled Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.2 — Service Schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.3 — Checking Engine Oil Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
4.4 — Changing the Engine Air Cleaner. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
4.5 — Spark Plugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
4.6 — Valve Lash Adjustment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
4.7 — Battery Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
4.8 — Attention After Submersion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.9 — Corrosion Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.10 — Out of Service Procedure (includes removal and return from service). . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Section 5 — Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Section 6 — Quick Reference Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Also included is Spanish, French Canadian and Portuguese.
ii
This page intentionally left blank.
iii

Section 1 Safety

**
$
!
+
INTRODUCTION: Thank you for purchasing this compact, high performance, air-cooled, engine-driven stationary automatic standby generator
set. Every effort was made to make sure that the information and instructions in this manual were both accurate and current at the time the man­ual was written. However, the manufacturer reserves the right to change, alter or otherwise improve this product or manual at any time without prior notice.
This generator is designed to automatically supply electrical power to operate critical loads during a utility power failure. This unit is factory installed in an all-weather metal enclosure and is intended exclusively for outdoor installation. This generator will operate using either vapor withdrawn liquid propane (LP) or natural gas (NG).
NOTE: When properly sized, this generator is suitable for supplying typical residential loads such as Induction Motors (sump pumps, refrigerators, air conditioners, furnaces, etc.), Electronic Components (computer, monitor, TV, etc.), Lighting Loads and Microwaves.
READ THIS MANUAL THOROUGHLY:
mends that the operator read and thoroughly understand the instructions and contents of this owner’s manual before attempting to use the equip­ment. If any portion of this publication is not understood, contact the nearest Authorized Service Dealer for starting, operating and servicing procedures.
SAVE THESE INSTRUCTIONS: The manufacturer suggests that this manual and the rules for safe operation be copied and posted near the unit’s installation site. Safety should be stressed to all operators and potential operators of this equipment.
SAFETY: Throughout this manual, and on tags and decals affixed to the unit, DANGER, WARNING, CAUTION and NOTE blocks are used to alert personnel to special instructions about a particular operation, function or service that may be hazardous if performed incorrectly or care­lessly. Observe them carefully. Their definitions are as follows:
INDICATES A HAZARDOUS SITUATION OR ACTION WHICH, IF NOT AVOIDED, WILL RESULT IN DEATH OR SERIOUS
Indicates a hazardous situation or action which, if not avoided, could result in death or serious injury.
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTE: Notes contain additional information important to an operation or procedure.
Four commonly used safety symbols accompany the DANGER, WARNING and CAUTION blocks. The type of information each indicates is as follows:
This symbol points out important Safety Information that, if not followed, could endanger personal safety and/or property of others.
The operator is responsible for proper and safe use of this equipment. The manufacturer strongly recom-
INJURY.
This symbol points out a potential Explosion Hazard.
This symbol points out a potential Fire Hazard.
This symbol points out a potential Electrical Shock Hazard.
These “Safety Alerts” cannot eliminate the hazards that they signal. Strict compliance with these special instructions, plus common sense are major accident prevention measures.
Automatic Standby Generator Owner’s Manual 1

1.1 — General Safety

*
+
*
*
*
*
Study these safety rules carefully before operating or servicing this equipment. Become familiar with this Owner’s Manual and with the unit. The generator can operate safely, efficiently and reliably only if it is properly installed, operated and maintained. Many accidents are caused by failing to follow simple and fundamental rules or precautions.
The manufacturer cannot anticipate every possible circumstance that might involve a hazard. The warnings in this manual, and on tags and decals affixed to the unit are, therefore, not all-inclusive. If using a procedure, work method or operating technique the manufacturer does not specifically recommend, ensure that it is safe for personnel. Also make sure the procedure, work method or operating technique utilized does not render the generator unsafe.
Despite the safe design of this generator, operating this equipment imprudently, neglecting its maintenance or being careless can cause possible injury or death. Permit only responsible and capable persons to install, operate and maintain this equipment.
Potentially lethal voltages are generated by these machines. Ensure steps are taken to make the machine safe before attempting to work on the generator.
Parts of the generator are rotating and/or hot during operation. Exercise care near a running generator.
The installation of this generator must always comply with applicable codes, standards, laws and regulations.
A running generator gives off DEADLY carbon monoxide, an odorless, colorless, poisonous gas. Breathing carbon monoxide can cause dizziness, throbbing temples, nausea, muscular twitching, headache, vomiting, weakness, sleepiness, inability to think clearly, fainting, unconsciousness or even death.
The control panel for this unit is intended to be operated by qualified service personnel only.

1.2 — General Safety Hazards

For safety reasons, this equipment should only be installed, serviced and repaired by a Service Dealer or other competent, qualified electri-
cian or installation technician who is familiar with applicable codes, standards, regulations and product Installation Manual guidelines. The operator also must comply with all such codes, standards, regulations and product Installation Manual guidelines.
The engine exhaust fumes contain carbon monoxide, which can be DEADLY. This dangerous gas, if breathed in sufficient concentrations, can cause unconsciousness or even death. DO NOT alter or add to the exhaust system or do anything that might render the system unsafe or in noncompliance with applicable codes and standards.
Install a carbon monoxide alarm indoors, according to manufacturer’s instructions/recommendations.
Adequate, unobstructed flow of cooling and ventilating air is critical for correct generator operation. Do not alter the installation or permit even partial blockage of ventilation provisions, as this can seriously affect safe operation of the generator. The generator MUST be installed and operated outdoors only.
Keep hands, feet, clothing, etc. away from drive belts, fans, and other moving or hot parts. Never remove any drive belt or fan guard while the unit is operating.
When working on this equipment, remain alert at all times. Never work on the equipment when physically or mentally fatigued.
Inspect the generator regularly, and contact the nearest Dealer for parts needing repair or replacement.
Before performing any maintenance on the generator, remove the control panel fuse and disconnect the Negative (—) battery cable to pre­vent accidental startup. When disconnecting battery cables always remove the NEGATIVE (NEG or “—”) cable first, then remove the POSITVE (POS, or “+”) cable. When reconnecting the cables, connect the POSITIVE cable first, and the NEGATIVE cable last.
Never use the generator or any of its parts as a step. Stepping on the unit can stress and break parts, and may result in dangerous operating conditions from leaking exhaust gases, fuel leakage, oil leakage, etc.
2 Automatic Standby Generator Owner’s Manual

1.3 — Exhaust Hazards

Generator engine exhaust contains DEADLY carbon monoxide, an odorless, colorless, poisonous gas. Breathing carbon monoxide can cause dizziness, throbbing temples, nausea, muscular twitching, headache, vomiting, weakness, sleepiness, inability to think clearly, fainting, unconsciousness or even death. If any carbon monoxide poisoning symptom is experienced, move into fresh air and immediately seek med­ical attention.
This generator is designed for OUTDOOR installation ONLY. Never operate the generator inside any garage or other enclosed space.

1.4 — Electrical Hazards

All generators covered by this manual produce dangerous electrical voltages that can cause fatal electrical shock. Utility power delivers extremely high and dangerous voltages to the transfer switch, as does the standby generator when it is in operation. Avoid contact with bare wires, terminals, connections, etc. while the unit is running. Ensure all appropriate covers, guards and barriers are in place, secured and/or locked before operating the generator. If work must be done around an operating unit, stand on an insulated, dry surface to reduce potential shock hazard.
Do not handle any kind of electrical device while standing in water, while barefoot, or while hands or feet are wet. DANGEROUS ELECTRI­CAL SHOCK MAY RESULT.
This is an Automatic Standby Generator, the generator may crank and start at any time when utility is lost. When this occurs, load circuits are transferred to the STANDBY (generator) power source. To prevent injury, before working on this generator (for inspection, service or mainte­nance), always put the generator into the OFF mode and remove the 7.5 Amp fuse from the generator control panel.
In case of accident caused by electric shock, immediately shut down the source of electrical power. If this is not possible, attempt to free the victim from the live conductor. AVOID DIRECT CONTACT WITH THE VICTIM. Use a nonconducting implement, such as a dry rope or board, to free the victim from the live conductor. If the victim is unconscious, apply first aid and get immediate medical help.
Never wear jewelry when working on this equipment. Jewelry can conduct electricity resulting in electric shock, or may get caught in moving components resulting in injury.

1.5 — Fire Hazards

For fire safety, the generator must be installed and maintained properly. Installation MUST always comply with applicable codes, standards, laws, regulations and product Installation Manual guidelines. Adhere strictly to local, state, and national electrical and building codes. Comply with regulations the Occupational Safety and Health Administration (OSHA) has established. Also, ensure that the generator is installed in accordance with the manufacturer’s instructions and recommendations. Following proper installation, do nothing that might alter a safe instal­lation and render the unit in noncompliance with the aforementioned codes, standards, laws and regulations.
Keep a fire extinguisher near the generator at all times. Extinguishers rated “ABC” by the National Fire Protection Association are appropriate for use on the standby generator. Keep the extinguisher properly charged and be familiar with its use. Consult the local fire department with any questions pertaining to fire extinguishers.

1.6 — Explosion Hazards

Do not smoke around the generator. Wipe up any fuel or oil spills immediately. Ensure that no combustible materials are left in the generator compartment, or on or near the generator as FIRE or EXPLOSION may result. Keep the area surrounding the generator clean and free from debris.
Gaseous fluids such as natural gas and liquid propane (LP) gas are extremely EXPLOSIVE. Install the fuel supply system according to appli­cable fuel-gas codes. Before placing the home standby electric system into service, fuel system lines must be properly purged and leak tested according to applicable code. After installation, inspect the fuel system periodically for leaks. No leakage can be permitted.
Automatic Standby Generator Owner’s Manual 3
If this generator is used to power electrical load circuits normally powered by a utility power source, it is
+
required by code to install a transfer switch. The transfer switch must effectively isolate the electrical system from the utility distribution system when the generator is operating (NEC 702). Failure to isolate an electrical system by such means will result in damage to the generator and also may result in injury or death to utility power workers due to backfeed of electrical energy.
4 Automatic Standby Generator Owner’s Manual

Section 2 General Information

EXHAUST
NCLOSURE
COMPOSITE BASE
OIL FILL CAP
BATTERY COMPARTMEN
FUEL REGULATOR
CIRCUIT BREAKERS
FUEL INLET (BACK)
CONTROL PANEL
OIL
DIPSTICK
AIR FILTER
DATA LABEL
(SEE SAMPLE)
EXHAUST
ENCLOSURE
COMPOSITE BASE
OIL FILTER
OIL FILL CAP
BATTERY COMPARTMENT
FUEL REGULATOR
CIRCUIT BREAKERS
FUEL INLET (BACK)
CONTROL PANEL
OIL
DIPSTICK
AIR FILTER
DATA LABEL
(SEE SAMPLE)
EXHAUST
ENCLOSURE
COMPOSITE BASE
OIL FILTER
OIL FILL CAP
BATTERY COMPARTMENT
FUEL REGULATOR
CIRCUIT BREAKERS
FUEL INLET (BACK)
CONTROL PANEL
OIL
DIPSTICK
AIR FILTER
DATA LABEL
(SEE SAMPLE)

2.1 — The Generator

E
OIL FILTER
Figure 2-1: GH-410 Engine 8kW Unit
Figure 2-2: GH-530 Engine 11kW Unit
T
Automatic Standby Generator Owner’s Manual 5
Figure 2-3: GT-990/GT-999 Engines, 13-20kW Unit
EXHAUST
ENCLOSURE
COMPOSITE BASE
OIL FILTER
OIL FILL CAP
BATTERY COMPARTMENT
FUEL REGULATOR
CIRCUIT BREAKERS
FUEL INLET (BACK)
CONTROL PANEL
OIL
DIPSTICK
AIR FILTER
DATA LABEL
(SEE SAMPLE)

2.2 — Protection Systems

The generator may have to run for long periods of time with no operator present to monitor the engine/generator conditions. Therefore, the gen­erator is equipped with a number of systems to automatically shut down the unit to protect it against potentially damaging conditions. Some of
these systems are as follows:
Low Oil Pressure Sensor
High Temperature Sensor
Overcrank Sensor
Overspeed Sensor
RPM Sensor
The control panel contains a display which alerts the operator when a fault condition occurs. The above list is not all inclusive. For more informa­tion about alarms and control panel operation, see Section 3 Operation.
Under-frequency Sensor
Undervoltage Sensor
Overvoltage Sensor
Internal Failure Sensor
Low Battery Voltage Alarm
6 Automatic Standby Generator Owner’s Manual

2.3 — Emission Information

The U.S. Environmental Protection Agency (EPA) requires that this generator comply with exhaust emission standards. This generator is certified to meet the applicable EPA emission levels, and is certified for use as a stationary engine for standby power generation. Any other use may be a violation of federal and/or local laws. To ensure that the engine complies with the applicable emission standards for the duration of the engine’s life, it is important to follow the maintenance specifications in the Section 4 Maintenance. This generator is certified to operate on Liquid Propane Vapor fuel or pipeline Natural Gas.
For generators 13kW and greater, the Emission Control System code is EM (Engine Modification). The Emission Control System on this generator consists of the following components:
Air Induction System
Intake Pipe / Manifold
Air Cleaner
Fuel Metering System
Carburetor / Mixer Assembly
Fuel Regulator
Ignition System
Spark Plug
Ignition Module
Exhaust System
Exhaust Manifold
Muffler
Catalyst (11kW generator only)
Automatic Standby Generator Owner’s Manual 7

2.4 — Specifications

2.4.1 — Generator
Model 8kW 11kW 13kW 14kW 15kW 16kW 17kW 20kW
Rated Voltage 240
Rated Maximum Load Current (Amps) at 240 Volts (LP)*
Main Circuit Breaker 35 Amp 50 Amp 55 Amp 60 Amp 60 Amp 65 Amp 65 Amp 90 Amp
Phase 1
Rated AC Frequency 60 Hz
Battery Requirement
Weight (unit only in lbs./kilos)
Enclosure
Normal Operating Range
These generators are rated in accordance with UL 2200, Safety Standard for Stationary Engine Generator Assemblies, and CSA-C22.2 No. 100-04 Standard for Motors and Generators. * Natural Gas ratings will depend on specific fuel Btu/joules content. Typical derates are between 10-20% off the LP gas rating. ** Circuits to be moved must be protected by same size breaker. For example, a 15 amp circuit in the main panel must be a 15 amp circuit in the transfer switch.
33.3 45.8 54.2 58.3 62.5 66.6 70.8 83.3
Group 26R, 12 Volts and 525 CCA Minimum (Generac Part No. 0H3421S)
360/163.3 407/184.6 435/197.3 435/197.3 471/213.6 471/213.6 Steel -
471/213.6
Aluminum -
437/198.2
Steel Steel Steel Steel Steel Steel
This unit is tested in accordance to UL 2200 standards with an operating temperature of -20º F (-29º C) to 122º F (50º C). For areas where tem-
peratures fall below 32º F (0º C) a cold weather kit is highly recommended. When operated above 77º F (25º C) there may be a decrease in engine
power. Please reference the engine specifications section.
Steel/
Aluminum
451/204.6
Aluminum
2.4.2 — Engine
Model 8kW 11kW 13/14/15/16/17kW 20kW
Type of Engine GH-410 GT-530 GT-990 GT-999
Number of Cylinders 1 2 2 2
Displacement 410cc 530cc 992cc 999cc
Cylinder Block Aluminum w/Cast Iron Sleeve
Recommended Spark Plug RC14YC BPR6HS RC14YC RC12YC
Spark Plug Gap 0.76mm (0.030”) 0.76mm (0.030”) 1.02mm (0.040”) 0.76mm (0.030”)
Starter 12 VDC
Oil Capacity Including Filter Approx. 1.5 Qts./1.4L Approx. 1.7 Qts./1.6L Approx. 1.9 Qts/1.8L Approx. 1.9 Qts/1.8L
Recommended Oil Filter Part #070185F
Recommended Air Filter Part #0E9371A Part #0E9371A Part #0J8478 Part #0J8478
Engine power is subject to and limited by such factors as fuel Btu/joules content, ambient temperature and altitude. Engine power decreases about 3.5 percent for each 1,000 feet (304.8 meters) above sea level, and also will decrease about 1 percent for each 6º C (10º F) above 15º C (60º F) ambient tem­perature.
The specification sheet for your generator was included in the documentation provided with the unit at the time of purchase. For additional copies, consult your local Authorized Service Dealer for your specific generator model.
8 Automatic Standby Generator Owner’s Manual
2.4.3 — Fuel Requirements
$
The engine has been fitted with a dual fuel carburetion system. The unit will run on natural gas or LP gas (vapor), but it has been factory set to run on natural gas. The fuel system will be configured for the available fuel source during installation.
Recommended fuels should have a btu content of at least 1,000 Btus per cubic foot (37.26 megjoules per cubic meter) for natural gas, or at least 2,500 Btus per cubic foot (93.15 megajoules per cubic meter) for LP gas (vapor).
NOTE: If converting to LP gas from natural gas, a minimum LP tank size of 250 gallons (946 liters) is recommended. See the Installa­tion Manual for complete procedures and details.
Gaseous fuels such as natural gas and liquid propane gas are highly explosive. Even the slightest spark can ignite such fuels and cause an explosion. No leakage of fuel is permitted. Natural gas, which is lighter than air, tends to collect in high areas. LP gas is heavier than air and tends to settle in low areas
2.4.4 — Battery Requirements
Group 26R, 12V, minimum 525CCA (Generac Part No. 0H3421S).
For proper battery maintenance procedures, see Section 4 Maintenance.
2.4.5 — Battery Charger
The battery charger is integrated into the control panel module in all models. It operates as a “Smart Charger” which ensures output charging lev­els are safe and continuously optimized to promote maximum battery life.
2.4.6 — Engine Oil Requirements
For proper oil viscosity, see chart in Figure 4-1: Recommended Oil Based on Temperature.

2.5 — Accessories

There are performance enhancing accessories available for air-cooled generators.
Accessory Description
Cold Weather Kit Recommended in areas where temperatures regularly fall below 32º F (0º C).
Scheduled Maintenance Kit Includes all pieces necessary to perform maintenance on the generator along with oil recommendations.
Auxiliary Transfer Switch Lock­out
Fascia Skirt Wrap Standard on all 20kW units. It is available for all other current production air-cooled units. It snaps together to pro-
Mobile Link™ Provides a personalized web portal that displays the generator’s status, maintenance schedule, event history and
Touch-Up Paint Kit Very important to maintain the look and integrity of the generator enclosure. This kit includes touch-up paint and
Enables any of the transfer switches to completely lock out one large electrical load by tying into its control system.
vide a smoothing, contoured look as well as rodent/insect protection.
much more. This portal is accessible via computer, tablet or smart phone. Sends emails and/or text notifications the moment there is any change in the generator’s status. Notification settings can be customized to what type of alert is sent and how often. For more information, visit www.standbystatus.com.
instructions.
Contact a Dealer for additional information on accessories.
Automatic Standby Generator Owner’s Manual 9
This page intentionally left blank.
10 Automatic Standby Generator Owner’s Manual

Section 3 Operation

*
*
*

3.1 — Control Panel Interface

The control panel on this unit is intended to only be operated by qualified service personnel.
The Control panel interface is located under the lid of the enclosure. Before attempting to lift the lid of the enclosure, verify that both left and right side locks are unlocked. To remove the front cover, lift the cover straight up to disengage the side hooks, then tilt and lift it away from the unit.
When closing the unit, ensure that both left and right side locks are securely locked. See Figure 3-1.
.
The enclosed keys provided with this unit are for service personnel usage only.
SIDE LOCK
Figure 3-1: Generator With Lid Open/Side Lock Location
Set to AUTO, the occurs cycle. remove NOT
NOTE: The generator is to be run with all appropriate panels in place, including during troubleshooting by a technician.
Automatic Standby Generator Owner’s Manual 11
when
To
prevent possible injury
the
OPERA
engine may
utility
fuses before work
TE”
power
tag on the
source voltage drops
generator
crank and
that might be
ing on or around the
start
at any time
below a
caused
panel and on the
without warning.
preset
by such
generator
trans
fer
Such
automatic starting
level or
sudden starts, always
or
switch.
during
transfer
the
switch.
normal exercise
set to OFF and
Then, place a “DO
Figure 3-2: Generator Control Panel

3.2 — Using the Auto/Off/Manual Buttons

Button Description of Operation
Auto
Off This button shuts down the engine and also prevents automatic operation of the unit.
Manual This button will crank and start the generator. Transfer to standby power will not occur unless there is a utility
Selecting this button activates fully auto engine every seven days with the
failure.
setting
matic system operation.
of
the exercise timer
(see
It
also allows the unit
the Setting the Exercise
to
automati
Timer
cally
star
section).
t
and exercise the
NOTE: Damage caused by mis-wiring of the interconnect wires is not warrantable.

3.3 — Interface Menu Displays

The LCD display:
Feature Description
HOME page The default page which will be displayed if no buttons are pressed for 60 seconds. This page normally shows the current Status
message and the current date and time. The highest priority active Alarm/Warning will be automatically posted on this page as well as flashing the backlight when such a condition is detected. In the case of multiple Alarms/Warnings, only the first message will be displayed. To clear an Alarm or Warning, press the OFF button and then press the ENTER key.
Display Backlight Normally off. If the operator presses any button, the backlight will automatically light and remain on for 30 seconds.
MAIN MENU page Allows the operator to navigate to all other pages or sub-menus by using the Arrows and Enter buttons. This page can be
accessed at any time with several presses of the dedicated Escape button. Each press of the Escape button takes the operator to the previous menu until the MAIN MENU displays. This page contains information for - History; Status; Edit; Debug.
3.3.1— Menu System Navigation
To get to the MENU, use the “Escape” button from any page. It may require pressing it many times before getting to the MENU page. Navigate to the desired menu by using the
12 Automatic Standby Generator Owner’s Manual
/ buttons. When the desired menu is displayed and flashing, press the “Enter” button. See Figure 3-3.
2013 HSB MENU MAP
0198170GST-B 02/25/13
Page 1 of 4
UP ARROW =
+
DOWN ARROW =
-
“Run Log”
ESC
ENTER
ENTER
ESC
SYSTEM
BATTERY
DATE/TIME
SUB MENUS
HISTORY
EDIT
MAINT
DEALER
Inspect Battery 200 RnHr or 12/27/13
and
Next Maintenance 200 RnHr or 12/27/13
Exercise Time
Å
14:00 Wednesday
Æ
Firmware Update
Å
Press Enter
Æ
Battery Condition
“Good” or “Check Battery”
Current Date/Time
02/14/13 07:40
ESC
ESC
ESC
ENTER
ENTER
Current Date/Time
Å
2/12/13 12:22
Æ
ESC ENTER
ESC
ESC
ESC ESC
ENTER
ENTER
ESC
ESC
ESC
ESC
ENTER
ENTER
ENTERENTER
ESC
ESC
ESC
ENTER
MAINT:
Maint. Log
Run Hrs
Scheduled
ENTER
ESC
ENTER
Select Day
- Wednesday +
ENTER
ENTER
ENTERENTER
Select Month (1-12)
- 2 +
Run Hours (H)
0.0
ENTER
Select Date (1-31)
- 13 +
ENTER
Select Year (0-99)
- 13 +
ENTER
ENTER
ENTER
ENTER
Switched to “OFF”
Hours of Protection
0 (H)
Access Requires Password
Language
Å
English
Æ
Possible Message(s)
Corrupted File
Invalid File
File Not Found
Unsupported Device
"Current:V XXXX "
"USB: V XXXX"
"Are You Sure?"
"- Yes or No +"
ESC
ENTER
Firmware Update
Å
Insert USB
Æ
“Alarm Log”
- Alarm Log +
- Run Log +
- 1 thru 50 +
- 1 thru 50 +
ESCENTER
ESCENTER
Select “Yes” then Press “Enter” to continue or Press
“ESCAPE” to escape out of updating.
During update process the Blue “Manual” light flashes, then
the Green “Auto” light flashes. Sequence does this twice.
When update is complete the unit returns to Install Wizard
menu.
When the controller powers up the very first screen displays
the version number for a few seconds.
When update is complete remove Thumb Drive.
- 1 thru 50 + "Battery Maintained"
"Schedule A Serviced"
"Schedule B Serviced"
"Maintenance Reset"
"Inspect Battery"
"Service Schedule A"
"Service Schedule B"
Warning Message(s)
"Low Battery"
"Exercise Set Error"
"FIRMWARE ERROR-9"
"Fuel Pressure"
"Battery Problem"
"Charger Warning"
"Charger Missing AC"
"Overload Warning"
"Overload Cooldown"
"SEEPROM ABUSE"
"USB Warning"
"Download Failure"
Running Manual
Running-Utility Lost
Running-Remote Start
Running-2 Wire Start
Running - Exercise
Switched Off
Stopped - Auto
Stopped - Alarm
Alarm Message(s)
"High Engine Temp."
"Low Oil Pressure"
"Overcrank"
"Overspeed"
"RPM Sense Loss"
"Underspeed"
"Internal Fault"
"FIRMWARE ERROR-7"
"WIRING ERROR"
"Over Voltage"
"Under Voltage"
"Overload Remove Load"
"Low Volts Remove Load"
"Stepper Over Current"
"Fuse Problem"
ESC
Select Min (0-59)
- 0 +
ESC
Select Hour (0-23)
- 14 +
ESC
Select Min (0-59)
- 0 +
ESC
Select Hour (0-23)
- 14 +
ESC
Quiet Test Mode ?
- YES or NO + Quiet Test Mode only
on certain models
Language
+ English -
Language
+ Espanol -
Language
+ Francais -
Language
+ Portuguese -
+
-
+
-
+
-
+
Figure 3-3: Navigation Menu
Automatic Standby Generator Owner’s Manual 13

3.4 — Automatic Transfer Operation

To select automatic operation:
1. Make sure the transfer switch main contacts are set to their UTILITY position (loads connected to the utility power source).
2. Be sure that normal UTILITY power source voltage is available to transfer switch terminal lugs N1 and N2.
3. Press the AUTO button on the Control Panel Interface.
4. Set the Main Circuit Breaker (Generator Disconnect) to its ON (Closed) position.
With these steps complete, the generator will start automatically when utility source voltage drops below a preset level. After the unit starts, loads are transferred to the standby power source.
3.4.1— Automatic Sequence of Operation
3.4.1.1 — Utility Failure
With the generator set to AUTO, when the utility fails (below 65% of nominal) a 10 second (optionally programmable) line interrupt delay time is started. If the utility is still gone when the timer expires, the engine will crank and start. Once started, a 5 second engine warm-up timer will be ini­tiated. When the warm-up time expires, the controller will transfer the load to the generator. If the utility power is restored (above 75% nominal) at any time from the initiation of the engine start until the generator is ready to accept load (5 second warm-up time has not elapsed), the controller will complete the start cycle and run the generator through its normal cool down cycle, however, the load will remain on the utility source.
3.4.1.2 — Cranking
The system will control the cyclic cranking as follows:
8kW unit - 5 cranking cycles as follows: 15 second crank, seven (7) second rest, followed by four (4) additional cycles of seven (7) second cranks followed by seven (7) second rests.
11 -20kW units - 5 cranking cycles as follows: 16 second crank, seven (7) second rest, 16 second crank, seven (7) second rest, followed by three (3) additional cycles of seven (7) second cranks followed by seven (7) second rests.
3.4.1.3 — Load Transfer
The transfer of load when the generator is running is dependent upon the operating mode:
MANUAL Will not transfer to generator if utility is present.
Will transfer to generator if utility fails (below 65% of nominal for 10 consecutive seconds).
Will transfer back when utility returns for 15 consecutive seconds. The engine will continue to run until removed from the MANUAL mode.
AUTO Will start and run if utility fails for 10 consecutive seconds (factory default).
Will start a 5 second engine warm-up timer.
•Will not transfer if utility subsequently returns.
•Will transfer to generator if utility is not present.
Will transfer back to utility once utility returns (above 75% of nominal) for 15 seconds.
Will not transfer back to utility unless utility returns. The generator will shut down if the OFF button is pressed or a shutdown alarm is present.
Once utility power is returned, the generator will shut down after 1 minute cool-down time.
EXERCISE Will not exercise if generator is already running in either AUTO or MANUAL mode.
During exercise, the controller will only transfer if utility fails during exercise for 10 seconds, and will switch to AUTO.
14 Automatic Standby Generator Owner’s Manual

3.5 — Turning the Generator Off When Operating Under Load

NOTE: Important! To turn the generator off during prolonged utility outages to perform maintenance or conserve fuel, follow these simple, but important steps:
To turn the generator OFF (while running in AUTO and online):
1. Turn OFF (or OPEN) the main Utility disconnect.
2. Turn OFF (or OPEN) the Main Line Circuit Breaker (MLCB) on the generator.
3. Turn the generator OFF.
To turn the generator back ON:
1. Put the generator back into AUTO and allow to start and warm-up for a few minutes.
2. Turn ON (or CLOSE) the MLCB on the generator.
The system will now be operating in its automatic mode. The main utility disconnect can be turned ON (or CLOSED), but to shut the unit off, this complete process must be repeated.

3.6 — Manual Transfer Operation

DO NOT attempt to activate the transfer switch manually until all power voltage supplies to the switch have been completely turned off. Failure to turn off all power voltage supplies may result in extremely hazardous and possi­bly fatal electrical shock.
Prior to automatic operation, manually exercise the transfer switch to verify that there is no interference with proper operation of the mechanism. Manual operation of the transfer switch is required if electronic operation should fail.
3.6.1— Transfer to Generator Power Source
1. Press the Control Panel OFF button.
2. Set the Main Circuit Breaker (Generator Disconnect) to its OFF (OPEN) position.
3. Turn off the utility power supply to the transfer switch using the means provided (such as a utility main line circuit breaker).
4. Use the manual transfer handle inside the transfer switch to move the main contacts to their STANDBY positions (loads connected to the standby power source).
5. To crank and start the engine, press the Control Panel MANUAL button.
6. Allow the engine to stabilize and warm up for a few minutes.
7. Set the Main Circuit Breaker (Generator Disconnect) to its ON (CLOSED) position. The standby power source now powers the loads.
Figure 3-4: Manual Transfer Switch Operation
Automatic Standby Generator Owner’s Manual 15
3.6.2— Transfer Back to Utility Power Source
120V GFCI OUTLET
15 Amp OUTLET BREAKER
MAIN CIRCUIT BREAKER
LED INDICATOR LIGHTS
When utility power has been restored, transfer back to utility source and shut down the generator. To manually transfer back to utility power and shut down the generator:
1. Set the Main Circuit Breaker (Generator Disconnect) to its OFF (OPEN) position.
2. Allow the engine to run for 2 minutes at no-load to stabilize the internal temperatures.
3. Press the Control Panel OFF button. The engine should shut down.
4. Ensure that utility power supply to the transfer switch is turned off.
5. Use the manual transfer handle inside the transfer switch to move the main contacts back to their UTILITY posi­tions (loads connected to the utility power source).
6. Turn on the utility power supply to the transfer switch using the means provided.
7. Press the Control Panel AUTO button.

3.7 — Side Compartment

Local codes may require this compartment to be locked. A hasp is provided so the owner/operator can secure the compartment with his or her own padlock. Check local codes for side compartment locking requirements.
Figure 3-5: Open Side Compartment
3.7.1— Main Circuit Breaker (Generator Disconnect)
This is a 2-pole breaker rated according to relevant specifications.
3.7.2— LED Indicator Lights
Green LED “Ready” light is on when utility is present and the Control Panel button is in the AUTO position. This also indicates when the gen­erator is running.
Red LED “Alarm” light is on when the generator is OFF or a fault is detected and means contact your authorized servicing dealer.
Yellow LED “Maintenance” light. Note: Yellow LED may be on at the same time as either the Red or Green LEDs.
16 Automatic Standby Generator Owner’s Manual
3.7.3— 120V GFCI Outlet/15 Amp Breaker (17 & 20 kW Only)
All units are equipped with an external 15 amp, 120 volt GFCI convenience outlet located in the top corner of the compartment.
When the generator is running, in the absence of utility power, this outlet may also be used to power items outside the home such as lights or power tools. This outlet may also be used when utility power is present by running the generator in manual mode.
This outlet does not provide power if the generator is not running. Do not use this outlet when the generator is in Exercise mode. This outlet is protected by a 15 amp circuit breaker in the side compartment.

3.8 — Alarm Response Procedures

The generator is protected by a series of sensors that will detect an Alarm/Warning condition and alert the owner/operator of the condition via the Control Panel display. When certain alarm conditions are detected, the generator will shut down.
Alarm/Warning conditions can include (this is not a complete list):
Low Oil Pressure
High Engine Temperature
Low Battery
Under-voltage
Exercise Set Error
NOTE: Unless properly trained to clear and correct Warning and Alarm conditions, contact the nearest Authorized dealer or Trained Technician.

3.9 — Battery Charger

NOTE: The battery charger is integrated into the control module in all models.
The battery charger operates as a “Smart Charger” that ensures:
Output is continually optimized to promote maximum battery life.
Charging levels are safe.
NOTE: A warning is displayed on the LCD when the battery needs service.

3.10 — Setting the Exercise Timer

This generator specified. During this exercise the exercise cycle unless utility power
The exercise settings can be changed at any time via the "EDIT"
If
the
prompt the customer for the
The exerciser volt battery
12 volt
is
is
equipped with an exercise
period, the unit runs for approximately
is lost.
battery
is
disconnected
current Time and Date.
will
only work in the AUTO mode and
disconnected
and then reconnected, and/or when the fuse
or
timer.
Once
it is set,
the fuse removed, the
will
not
work
the generator will
12
minutes and then shuts
menu.
Installation Wizard
unless
this
procedure
is removed.
star
t
and exercise every seven days, on the day
will
operate upon power restoration. The
is
performed. The current date/time
down.
Transfer
of
of
the week and at the time
loads
to
the generator output does not occur
only difference
will
need
to
be reset every time the
is
the display will only
of
day
during
12
Automatic Standby Generator Owner’s Manual 17
This page intentionally left blank.
18 Automatic Standby Generator Owner’s Manual

Section 4 Maintenance

*
NOTE: Proper maintenance and proper and safe operation is crucial to the life of the generator. Genuine Generac parts MUST be used to ensure warranty coverage.
NOTE: Since most maintenance alerts will occur at the same time (most have two year intervals), only one will appear on the Control Panel display at any one time. Once the first alert is cleared, the next active alert will be displayed.
All service to this generator must be performed by a qualified service person only.

4.1 — Performing Scheduled Maintenance

It is important to perform Maintenance as specified in the Service Schedule for proper generator operation and to ensure that the generator com­plies with the applicable emission standards for the duration of its useful life. Service and repairs may be performed by any qualified service per­son or repair shop. Additionally, emissions critical maintenance must be performed as scheduled in order for the Emissions Warranty to be valid. Emissions critical maintenance consists of servicing the air filter and spark plugs in accordance with the Service Schedule. The controller will prompt for Schedule A or Schedule B maintenance to be performed. Schedule A maintenance consists of the oil, oil filter and tune-up. Schedule B maintenance includes the oil, oil filter, tune-up, air cleaner, spark plug(s) and valve clearance.

4.2 — Service Schedule

ATTENTION: All service work must be performed by a qualified service person only.
System Component Procedure Frequency
X = Action R= Replace as Necessary * = Notify Dealer if Repair is Needed
Fuel
Fuel lines and connections* X M
Lubrication
Oil level X M or 24 hours of continuous operation
Oil X 2Y or 200 hours of operation**
Oil filter X 2Y or 200 hours of operation**
Cooling
Enclosure louvers X X W
Battery
Remove corrosion, ensure dryness X X Y
Clean and tighten battery terminals X X Y
Check charge state X R Y
Electrolyte level (unsealed batteries only)* X R Every 6 M
Engine and Mounting
Air cleaner X R 400 hours
Spark plug(s) X R 400 hours
Valve Clearance X 400 hours***
General Condition
Vibration, Noise, Leakage* X M
Complete Tune-Up* To be completed by a Dealer 2Y or 200 hours
* Contact the nearest Dealer for assistance if necessary. ** Change oil and filter after the first 25 hours of operation. Continue to check at intervals of 200 hours or 2 years, whichever occurs first. Change sooner when operating under a heavy load or in a dusty or dirty environment or in high ambient temperatures.
*** Check valve clearance after the first 25 hours of operation. Continue to check at intervals of 400 hours.
Inspect Change Clean
W = Weekly
M = Monthly
Y = Yearly
Automatic Standby Generator Owner’s Manual 19
4.2.1— Maintenance Log
1. Battery inspection and charge check (recommended every 6 months for the life of the battery)
Dates Performed:
2. Oil, oil filter, air filter and spark plug replacement (recommended every 200 hours or 2 years, whichever occurs first)
Dates Performed:
3. Valve Adjustment (recommended after the first 6 months after installation or 500 hours of operation, whichever occurs first, and every 500 hours thereafter)
Dates Performed:

4.3 — Checking Engine Oil Level

When power outages necessitate running the generator for extended periods, the oil level should be checked daily. To check the engine oil level:
1. If the generator is running during a utility outage, first turn OFF all associated loads running in the residence using the electrical panel's main disconnect. Then, turn the generator's Main Circuit Breaker to the OFF position.
2. Press the Control Panel OFF button. Wait 5 minutes.
3. Remove the dipstick and wipe it dry with a clean cloth.
4. Completely insert the dipstick and again remove it.
5. Observe the oil level. The level should be at the “Full” mark on the dipstick.
6. If necessary, remove the oil fill cap and add oil to the engine until the level reaches the “Full” mark and reinsert the dipstick and fill cap.
7. Press the Control Panel AUTO button.
8. If the generator was running during a utility outage, first turn the Main Circuit Breaker to the ON position. Then, turn ON the needed loads in the residence.
Never operate the engine with the oil level below the “Add” mark on the dipstick. Doing so could damage the engine.
Hot oil may cause burns. Avoid prolonged or repeated skin exposure with used oil. Thoroughly wash exposed areas with soap.
20 Automatic Standby Generator Owner’s Manual
4.3.1— Engine Oil Recommendations
To maintain the warranty, genuine Generac replacement parts MUST be used, including Generac oil kits (which include an oil and air filter). Gen­erac oil kits can be obtained through an Authorized Dealer or purchased on-line. To purchase on-line, access the maintenance kits page through www.generac.com or directly at shop.generac.com. Follow the prompts to enter delivery information and complete the purchase.
All Generac oil kits meet minimum American Petroleum Institute (API) Service Class SJ, SL, or better. Use no special additives. Select the appro­priate viscosity oil grade according to the expected operating temperature. Synthetic oil also can be used in the appropriate weight as standard.
Figure 4-1: Recommended Oil Based on Temperature
SAE 30 above 32º F (0º C)
10W 30 between 40º and -10º F (4º and -23º C)
Synthetic 5W 30 for all temperature ranges
Any attempt to crank or start the engine before it has been properly serviced with the recommended oil may result in an engine failure.
4.3.2— Changing the Oil and Oil Filter
1. Start the engine by pressing the MANUAL button on the control panel and allow the engine to run until it is thoroughly warmed up. Then,
press the Control Panel OFF button to shut down the engine.
2. A few minutes after the engine shuts OFF, when it has cooled slightly, lift the lid and remove the front panel. Pull the oil drain hose free of its
retaining clip. Remove the cap from the hose and drain the oil into a suitable container.
3. After the oil has drained, replace the cap onto the end of the oil drain hose. Reposition and secure the hose with the retaining clip.
4. With the oil drained, remove the old oil filter by turning it counterclockwise. For filter location, see Figure 4-2.
5. Apply a light coating of clean engine oil to the gasket of the new filter.
6. Screw the new filter on by hand until its gasket lightly contacts the oil filter adapter. Then, tighten the filter an additional 3/4 to one full turn.
7. Refill the engine with the proper recommended oil. For recommended oil, see Figure 4-1.
8. Start the engine, run for 1 minute, and check for leaks.
9. Shutdown the engine and recheck the oil level. Add oil as needed. DO NOT OVER FILL.
10. Re-insert dipstick and/or reattach fill cap.
11. Press the Control Panel AUTO button.
12. Dispose of the used oil and filter at a proper collection center.
Automatic Standby Generator Owner’s Manual 21
Figure 4-2: Oil Filter and Drain Location

4.4 — Changing the Engine Air Cleaner

1. With the generator shut down, lift the lid and remove the front panel.
2. Remove the cover clips and air cleaner cover (11-20kW), or disengage the wire clip and open the air cleaner access door (8kW).
3. Pull out the old air filter and discard.
4. Thoroughly clean the air cleaner enclosure of any dust or debris.
5. Install a new air cleaner.
6. Install the air cleaner cover and cover clips (11-20kW),or close the air cleaner access door and engage the wire clip (8kW).

4.5 — Spark Plugs

Reset the spark plug(s) gap or replace the spark plug(s) as necessary:
1. With the generator shut down, lift the lid and remove the front panel.
2. Clean the area around the base of the spark plug(s) to keep dirt and debris out of the engine.
3. Remove the spark plug(s) and check the condition. Install a new plug(s) if the old one is worn or if reuse is questionable.
4. Clean the plug(s) by scraping or washing with a wire brush and commercial solvent. Do not blast the plug(s) to clean.
5. Check the spark plug gap using a wire feeler gauge. See Figure 4-3. Adjust the gap by carefully bending the ground electrode to:
For 8, 11, and 20kW units - 0.76 mm (0.030 inch)
For 13, 14, 15, 16, 17kW units - 1.02 mm (0.040 inch)
Figure 4-3: Spark Plug Gap Adjustment
22 Automatic Standby Generator Owner’s Manual

4.6 — Valve Lash Adjustment

After the first six (6) months or 500 hours of operation, check the valve clearance. Adjust if necessary.
Important: Please contact the Dealer for service assistance. This is a very important step to ensure longest life for the engine.
To check valve clearance:
The engine should be cool before checking. If valve clearance is 0.002" - 0.004" (0.05 - 0.1mm), adjustment is not needed.
Remove spark plug wires and position wires away from plugs.
Remove spark plugs.
Make sure the piston is at Top Dead Center (TDC) of its compression stroke (both valves closed). To get the piston at TDC, remove the intake
screen at the front of the engine to gain access to the flywheel nut. Use a large socket and socket wrench to rotate the nut and hence the engine in a clockwise direction. While watching the piston through the spark plug hole. The piston should move up and down. The piston is at TDC when it is at its highest point of travel.
To adjust valve clearance (see Figure 4-4):
Make sure the engine is at 60° to 80° F (16° to 27° C).
Make sure that the spark plug wire is removed from the spark plug and out of the way.
Remove the four screws attaching the valve cover.
Loosen the rocker jam nut. Using a 10mm Allen wrench (530cc engine) or a 13mm Allen wrench (410cc, 990cc and 999cc engines), turn the
pivot ball stud while checking clearance between the rocker arm and the valve stem with a feeler gauge. Correct clearance is 0.002-0.004 inch (0.05-0.1 mm).
NOTE: Hold the rocker arm jam nut in place as the pivot ball stud is turned.
When valve clearance is correct, hold the pivot ball stud in place with the Allen wrench and tighten the rocker arm jam nut. Tighten the jam nut
to 174 in-lbs. (19.68 N-m) torque. After tightening the jam nut, recheck valve clearance to make sure it did not change.
Install new valve cover gasket.
Re-attach the valve cover.
NOTE: Start all four screws before tightening or it will not be possible to get all the screws in place. Make sure the valve cover gasket is in place.
Install spark plugs.
Re-attach the spark plug wire to the spark plug.
Repeat the process for the other cylinder, if necessary.
Automatic Standby Generator Owner’s Manual 23
Rocker
Pivot Ball
Arm
Stud
Jam Nut
Valve Stem
Figure 4-4: Valve Clearance Adjustment

4.7 — Battery Maintenance

The battery should be regularly inspected per the Service Schedule:
1. With the generator shut down, lift the lid and remove the front panel.
2. Inspect the battery posts and cables for tightness and corrosion. Tighten and clean as necessary.
3. Check the battery fluid level of unsealed batteries, and if necessary, fill with distilled water only. DO NOT use tap water. Also, have the Dealer or a qualified Service Technician check the state of charge and condition.
Do not dispose of the battery by incineration. The battery is capable of exploding.
A battery presents a risk of electrical shock and high short circuit current. Strictly observe the following precau­tions when working on batteries:
Remove the 7.5 Amp fuse from the generator control panel.
Remove all jewelry—watches, rings, metal objects, etc.
Use tools with insulated handles.
Wear rubber gloves and boots.
Do not lay tools or metallic objects on top of the battery.
Disconnect the charging source prior to connecting or disconnecting battery terminals.
24 Automatic Standby Generator Owner’s Manual
Do not open or mutilate the battery. Released electrolyte has been known to be harmful to the skin and eyes, and to be toxic. The electrolyte is a dilute sulfuric acid that is harmful to the skin and eyes. It is electrically conduc­tive and corrosive. Strictly observe the following precautions:
Wear full eye protection and protective clothing.
Where electrolyte contacts the skin, wash it off immediately with water.
Where electrolyte contacts the eyes, flush thoroughly and immediately with water and seek medical attention.
Wash down spilled electrolyte with an aid neutralizing agent. A common practice is to use a solution of 1 pound (500 grams) bicarbonate of soda to 1 gallon (4 liters) of water. The bicarbonate of soda solution is to be added until the evidence of reaction (foaming) has ceased. The resulting liquid is to be flushed with water and the area dried.
Lead-acid batteries present a risk of fire because they generate hydrogen gas. Strictly observe the following pre­cautions:
DO NOT smoke when near the battery.
DO NOT cause flame or spark in the battery area.
Discharge static electricity from the body before touching the battery by first touching a grounded metal surface.
Be sure the utility power supply is turned off and the 7.5 Amp fuse is removed from the generator Control Panel, or sparking may occur at the battery posts as the cables are attached and cause an explosion.

4.8 — Attention After Submersion

If the generator has been submerged in water, it MUST NOT be started and operated. Following any submersion in water, have a Dealer thor­oughly clean, dry, and inspect the generator. If the structure (home) has been flooded, it should be inspected by a certified electrician to ensure there won’t be any electrical problems during generator operation or when utility power is returned.

4.9 — Corrosion Protection

Periodically wash and wax the enclosure using automotive type products. Frequent washing is recommended in salt water/coastal areas. Spray engine linkages with a light oil such as WD-40.

4.10 — Out of Service Procedure

4.10.1— Removal From Service
If the generator cannot be exercised every 7 days and will be out of service longer than 90 days, prepare the generator for storage:
1. Start the engine and let it warm up.
2. Close the fuel shutoff valve in the fuel supply line and allow the unit to shut down.
3. Once the unit has shut down, set the generator’s Main Circuit Breaker (Generator Disconnect) to its OFF (OPEN) position.
4. Turn off the utility power to the transfer switch.
5. Remove the 7.5 Amp fuse from the generator’s Control Panel.
6. Disconnect the battery cables. Remove negative cable first.
7. Remove battery charger AC input T1/Neutral cable (has white sleeve) at controller.
8. While the engine is still warm, drain the oil completely, and then refill the crankcase with oil.
9. Attach a tag to the engine indicating the viscosity and classification of the new oil in the crankcase.
10. Remove the spark plug(s) and spray a fogging agent into the spark plug(s)’ threaded openings. Reinstall and tighten the spark plug(s).
Automatic Standby Generator Owner’s Manual 25
11. Remove the battery and store it in a cool, dry room on a wooden board. Never store the battery on any concrete or earthen floor.
12. Clean and wipe down the entire generator.
4.10.2— Return to Service
To return the unit to service after storage:
1. Verify that utility power is turned off.
2. Check the tag on the engine for oil viscosity and classification. If necessary, drain and refill with proper oil.
3. Check the state of the battery. Fill all cells of unsealed batteries to the proper level with distilled water. DO NOT use tap water. Recharge the battery to 100% state of charge. If defective, replace the battery.
4. Clean and wipe down the entire generator.
5. Make sure the 7.5 Amp fuse is removed from the generator Control Panel.
6. Reconnect the battery. Observe battery polarity. Damage may occur if the battery is connected incorrectly. Install positive cable first.
7. Reconnect the battery charger AC input T1/Neutral cable (has white sleeve) at controller.
8. Open the fuel shutoff valve.
9. Insert the 7.5 Amp fuse into the generator Control Panel.
10. Start the unit by pressing the MANUAL button. Allow the unit to warm up for a few minutes.
11. Stop the unit by pressing the Control Panel OFF button.
12. Turn on the utility power to the transfer switch.
13. Set the Control Panel to AUTO.
The generator is ready for service.
NOTE: When a battery is dead or has been disconnected, the exercise timer and current date and time must be reset.
26 Automatic Standby Generator Owner’s Manual

Section 5 Troubleshooting

Problem Cause Correction
The engine will not crank. 1. Fuse blown. 1. Correct short circuit condition by
replacing 7.5 Amp fuse in generator control panel.
2. Loose, corroded or defective 2. Tighten, clean or replace battery cables. as necessary.*
3. Defective starter contact. 3. *See #2.
4. Defective starter motor. 4. *See #2.
5. Dead Battery. 5. Charge or replace battery.
The engine cranks but 1. Out of fuel. 1. Replenish fuel/Turn on fuel valve. will not start. 2. Defective fuel solenoid (FS). 2. *
3. Open #14 wire from engine control 3. Repair wiring. board.
4. Defective spark plug(s). 4. Clean, re-gap or replace plug(s).
5. Valve lash out of adjustment. 5. Reset valve lash.
The engine starts hard 1. Air cleaner plugged 1. Check/replace air cleaner. and runs rough. or damaged.
2. Defective spark plug(s). 2. Clean, re-gap or replace plug(s).
3. Fuel regulator not set. 3. Set fuel regulator.
4. Fuel pressure incorrect. 4. Confirm fuel pressure to regulator
is 10-12” water column (19-22mm mercury) for LP, and 5-7” water column (9-13mm mercury) for natural gas.
5. Fuel selector in wrong position. 5. Move selector to correct position.
6. Choke remains closed. 6. Verify choke plate moves freely.
The generator is set to OFF, 1. Defective button. 1. * but the engine continues to 2. Buttons wired incorrectly. 2. Repair wiring or replace switch. run.
3. Defective control board. 3. *
There is no AC output from 1. Main line circuit breaker is in 1. Reset circuit breaker the generator. the OFF (or OPEN) position. to ON (or CLOSED).
2. Generator internal failure. 2. *
There is no transfer to 1. Defective transfer switch coil. 1. * standby after utility 2. Defective transfer relay. 2. * source failure. 3. Transfer relay circuit open. 3. *
4. Defective control logic board. 4. *
Unit consumes large 1. Engine over filled with oil. 1. Adjust oil to proper level. amounts of oil. 2. Engine breather defective. 2. *
3. Improper type or viscosity of oil. 3. See “Engine Oil
Recommendations”.
4. Damaged gasket, seal or hose. 4. Check for oil leaks.
*Contact an Authorized Service Dealer for assistance.
Automatic Standby Generator Owner’s Manual 27
This page intentionally left blank.
28 Automatic Standby Generator Owner’s Manual

Section 6 Quick Reference Guide

Problem LED
Unit running in AUTO but no power in house.
Unit shuts down during operation. RED
Unit shuts down during operation. RED
Unit was running and shuts down, attempts to restart.
Unit will not start in AUTO with utility loss.
Unit will not start in AUTO with utility loss.
Unit will not start in AUTO with utility loss.
Unit will not start in AUTO with utility loss.
Unit will not start in AUTO with utility loss.
Unit will not start in AUTO with utility loss.
Unit will not start in AUTO with utility loss.
Unit will not start in AUTO with utility loss.
Unit will not start in AUTO with utility loss.
Unit will not start in AUTO with utility loss.
GREEN Check MLCB. NONE
RED
NONE
GREEN
RED
RED
RED
RED
RED
RED
RED
RED
Things to
Check
Check the LEDs/Screen for alarms.
Check the LEDs/Screen for alarms.
Check the LEDs/Screen for alarms.
See if screen says unit not activated.
Check screen for start delay countdown.
Check the LEDs/Screen for alarms.
Check the LEDs/Screen for alarms.
Check the LEDs/Screen for alarms.
Check the LEDs/Screen for alarms.
Check the LEDs/Screen for alarms.
Check the LEDs/Screen for alarms.
Check the LEDs/Screen for alarms.
Check the LEDs/Screen for alarms.
Active Alarm
Check MLCB. Contact servicing dealer if MLCB is in the ON position.
HIGH
TEMPERATURE
OVERLOAD
REMOVE LOAD
RPM SENSE
LOSS
NOT
ACTIVATED
None
LOW OIL
PRESSURE
RPM SENSE
LOSS
OVERCRANK
LOW VOLTS
REMOVE LOAD
FUSE PROBLEM
OVERSPEED Contact servicing dealer.
UNDER
VOLTAGE
UNDERSPEED Contact servicing dealer.
Check ventilation around the intake, exhaust and rear of generator. Contact serving dealer if no obstruction is found.
Clear alarm and remove household loads from the generator. Put back in AUTO and restart.
Clear alarm and remove household loads from the generator. Put back in AUTO and restart. If problem returns, contact servicing dealer to investigate possible fuel issue.
Refer to activation section in Owner’s Manual.
If the start up delay is greater than expected, contact servicing dealer to adjust from 2 to 1500 seconds.
Check oil level. Add oil per Owner’s Manual. Contact servicing dealer if oil level is correct.
Clear alarm. From the MAIN menu on the control panel, navigate to the BAT­TERY MENU. Contact servicing dealer if battery is GOOD. Replace battery If CHECK BATTERY is displayed.
Check fuel line shutoff valve is in the ON position. Clear alarm. Attempt to start the unit in MANUAL. If it does not start or starts and runs rough, contact servic­ing dealer.
Clear alarm and remove household loads from the generator. Put back in AUTO and restart.
Check ATO 7.5 amp fuse. Replace with same type fuse if bad. Contact servicing dealer if fuse is good.
Contact servicing dealer.
Solution
Automatic Standby Generator Owner’s Manual 29
Problem LED
Unit will not start in AUTO with utility loss.
Unit will not start in AUTO with utility loss.
Unit will not start in AUTO with utility loss.
Yellow LED illuminated in any state.
Yellow LED illuminated in any state. YELLOW
Yellow LED illuminated in any state.
Yellow LED illuminated in any state. YELLOW
Yellow LED illuminated in any state. YELLOW
Yellow LED illuminated in any state. YELLOW
RED
RED
RED
YELLOW
YELLOW
Things to
Check
Check the LEDs/Screen for alarms.
Check the LEDs/Screen for alarms.
Check the LEDs/Screen for alarms.
Check screen for additional information.
Check screen for additional information.
Check screen for additional information.
Check screen for additional information.
Check screen for additional information.
Check screen for additional information.
Active Alarm
STEPPER
OVERCURRENT
MISWIRE Contact servicing dealer.
OVERVOLTAGE Contact servicing dealer.
LOW BATTERY
BATTERY
PROBLEM
CHARGER
WARNING
SERVICE A
SERVICE B
Inspect Battery Inspect battery; press ENTER to clear.
Contact servicing dealer.
Clear alarm. From the MAIN menu on the control panel, navigate to the BAT­TERY MENU. Contact servicing dealer if battery is GOOD. Replace battery If CHECK BATTERY is displayed.
Contact servicing dealer.
Contact servicing dealer
Perform SERVICE A maintenance; press ENTER to clear.
Perform SERVICE B maintenance; press ENTER to clear.
Solution
30 Automatic Standby Generator Owner’s Manual

Part No. 0J9943 Rev. D 05/24/2013 Printed in USA © Generac Power Systems, Inc. All rights reserved Specifications are subject to change without notice. No reproduction allowed in any form without prior written consent from Generac Power Systems, Inc.

Generac Power Systems, Inc.
S45 W29290 Hwy. 59
Waukesha, WI 53189
1-888-GENERAC (1-888-436-3722)
generac.com
Loading...