Generac Power Systems Automatic Standby Generator, 8kW 11kW, 13kW, 14kW, 15kW, 16kW, 17kW, 20kW, 8kW, 11kW, 6244 Owner's Manual
Specifications and Main Features
Frequently Asked Questions
User Manual
Owner’s Manual
Automatic Standby Generator
Reference all appropriate documentation.
This manual should remain with the unit.
n
NOT INTENDED FOR USE IN CRITICAL LIFE SUPPORT APPLICATIONS.
n
ONLY QUALIFIED ELECTRICIANS OR CONTRACTORS SHOULD ATTEMPT
INSTALLATION.
n
DEADLY EXHAUST FUMES! OUTDOOR INSTALLATION ONLY!
LISTED
C
US
Home Standby Models:
8kW to 20kW
WARNING!
California Proposition 65
Engine exhaust and some of its constituents are known to the state of California to cause cancer,
birth defects, and other reproductive harm.
WARNING!
California Proposition 65
This product contains or emits chemicals known to the state of California to cause cancer,
birth defects, and other reproductive harm.
Use this page to record important information about your generator set.
Record the information found on your unit data label on this page. For the
location of the unit data label, see Section 2 General Information. The
unit has a label plate affixed to the inside partition, to the left of the control
panel console as shown in Figures 2-1, 2-2, and 2-3. For directions on
how to open the top lid and remove the front panel, see Section 3 Operation. The Unit Identification label provides the following information:
• Model Number
• Serial Number
• Control Panel Part Number
• Voltage Rating of the unit
• Maximum Current Rating of the unit (AMPS)
When contacting an Authorized Service Dealer about parts and service,
always supply the complete model number and serial number of the unit.
Operation and Maintenance: Proper maintenance and care of the generator ensures a minimum number of problems and keeps operating
expenses at a minimum. It is the operator’s responsibility to perform all
safety checks, to make sure that all maintenance for safe operation is
performed promptly, and to have the equipment checked periodically by
an Authorized Service Dealer. Normal maintenance, service and replacement of parts are the responsibility of the owner/operator and, as such,
are not considered defects in materials or workmanship within the terms
of the warranty. Individual operating habits and usage may contribute to
the need for additional maintenance or service.
When the generator requires servicing or repairs, contact an Authorized
Service Dealer for assistance. Authorized service technicians are factorytrained and are capable of handling all service needs.
Also included is Spanish, French Canadian and Portuguese.
ii
This page intentionally left blank.
iii
Section 1 Safety
**
$
!
+
INTRODUCTION: Thank you for purchasing this compact, high performance, air-cooled, engine-driven stationary automatic standby generator
set. Every effort was made to make sure that the information and instructions in this manual were both accurate and current at the time the manual was written. However, the manufacturer reserves the right to change, alter or otherwise improve this product or manual at any time without
prior notice.
This generator is designed to automatically supply electrical power to operate critical loads during a utility power failure. This unit is factory
installed in an all-weather metal enclosure and is intended exclusively for outdoor installation. This generator will operate using either vapor
withdrawn liquid propane (LP) or natural gas (NG).
NOTE: When properly sized, this generator is suitable for supplying typical residential loads such as Induction Motors (sump pumps,
refrigerators, air conditioners, furnaces, etc.), Electronic Components (computer, monitor, TV, etc.), Lighting Loads and Microwaves.
READ THIS MANUAL THOROUGHLY:
mends that the operator read and thoroughly understand the instructions and contents of this owner’s manual before attempting to use the equipment. If any portion of this publication is not understood, contact the nearest Authorized Service Dealer for starting, operating and servicing
procedures.
SAVE THESE INSTRUCTIONS: The manufacturer suggests that this manual and the rules for safe operation be copied and posted near the
unit’s installation site. Safety should be stressed to all operators and potential operators of this equipment.
SAFETY: Throughout this manual, and on tags and decals affixed to the unit, DANGER, WARNING, CAUTION and NOTE blocks are used to
alert personnel to special instructions about a particular operation, function or service that may be hazardous if performed incorrectly or carelessly. Observe them carefully. Their definitions are as follows:
INDICATES A HAZARDOUS SITUATION OR ACTION WHICH, IF NOT AVOIDED, WILL RESULT IN DEATH OR SERIOUS
Indicates a hazardous situation or action which, if not avoided, could result in death or serious injury.
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTE: Notes contain additional information important to an operation or procedure.
Four commonly used safety symbols accompany the DANGER, WARNING and CAUTION blocks. The type of information each indicates is as
follows:
This symbol points out important Safety Information that, if not followed, could endanger personal safety and/or
property of others.
The operator is responsible for proper and safe use of this equipment. The manufacturer strongly recom-
INJURY.
This symbol points out a potential Explosion Hazard.
This symbol points out a potential Fire Hazard.
This symbol points out a potential Electrical Shock Hazard.
These “Safety Alerts” cannot eliminate the hazards that they signal. Strict compliance with these special instructions, plus common sense are
major accident prevention measures.
Automatic Standby Generator Owner’s Manual1
1.1 — General Safety
*
+
*
*
*
*
Study these safety rules carefully before operating or servicing this equipment. Become familiar with this Owner’s Manual and with the unit. The
generator can operate safely, efficiently and reliably only if it is properly installed, operated and maintained. Many accidents are caused by failing
to follow simple and fundamental rules or precautions.
The manufacturer cannot anticipate every possible circumstance that might involve a hazard. The warnings in this manual, and on tags and
decals affixed to the unit are, therefore, not all-inclusive. If using a procedure, work method or operating technique the manufacturer does not
specifically recommend, ensure that it is safe for personnel. Also make sure the procedure, work method or operating technique utilized does not
render the generator unsafe.
Despite the safe design of this generator, operating this equipment imprudently, neglecting its maintenance or
being careless can cause possible injury or death. Permit only responsible and capable persons to install, operate
and maintain this equipment.
Potentially lethal voltages are generated by these machines. Ensure steps are taken to make the machine safe
before attempting to work on the generator.
Parts of the generator are rotating and/or hot during operation. Exercise care near a running generator.
The installation of this generator must always comply with applicable codes, standards, laws and regulations.
A running generator gives off DEADLY carbon monoxide, an odorless, colorless, poisonous gas. Breathing carbon
monoxide can cause dizziness, throbbing temples, nausea, muscular twitching, headache, vomiting, weakness,
sleepiness, inability to think clearly, fainting, unconsciousness or even death.
The control panel for this unit is intended to be operated by qualified service personnel only.
1.2 — General Safety Hazards
•For safety reasons, this equipment should only be installed, serviced and repaired by a Service Dealer or other competent, qualified electri-
cian or installation technician who is familiar with applicable codes, standards, regulations and product Installation Manual guidelines. The
operator also must comply with all such codes, standards, regulations and product Installation Manual guidelines.
•The engine exhaust fumes contain carbon monoxide, which can be DEADLY. This dangerous gas, if breathed in sufficient concentrations, can
cause unconsciousness or even death. DO NOT alter or add to the exhaust system or do anything that might render the system unsafe or in
noncompliance with applicable codes and standards.
•Install a carbon monoxide alarm indoors, according to manufacturer’s instructions/recommendations.
•Adequate, unobstructed flow of cooling and ventilating air is critical for correct generator operation. Do not alter the installation or permit even
partial blockage of ventilation provisions, as this can seriously affect safe operation of the generator. The generator MUST be installed and
operated outdoors only.
•Keep hands, feet, clothing, etc. away from drive belts, fans, and other moving or hot parts. Never remove any drive belt or fan guard while the
unit is operating.
•When working on this equipment, remain alert at all times. Never work on the equipment when physically or mentally fatigued.
•Inspect the generator regularly, and contact the nearest Dealer for parts needing repair or replacement.
•Before performing any maintenance on the generator, remove the control panel fuse and disconnect the Negative (—) battery cable to prevent accidental startup. When disconnecting battery cables always remove the NEGATIVE (NEG or “—”) cable first, then remove the
POSITVE (POS, or “+”) cable. When reconnecting the cables, connect the POSITIVE cable first, and the NEGATIVE cable last.
•Never use the generator or any of its parts as a step. Stepping on the unit can stress and break parts, and may result in dangerous operating
conditions from leaking exhaust gases, fuel leakage, oil leakage, etc.
2Automatic Standby Generator Owner’s Manual
1.3 — Exhaust Hazards
•Generator engine exhaust contains DEADLY carbon monoxide, an odorless, colorless, poisonous gas. Breathing carbon monoxide can
cause dizziness, throbbing temples, nausea, muscular twitching, headache, vomiting, weakness, sleepiness, inability to think clearly, fainting,
unconsciousness or even death. If any carbon monoxide poisoning symptom is experienced, move into fresh air and immediately seek medical attention.
•This generator is designed for OUTDOOR installation ONLY. Never operate the generator inside any garage or other enclosed space.
1.4 — Electrical Hazards
•All generators covered by this manual produce dangerous electrical voltages that can cause fatal electrical shock. Utility power delivers
extremely high and dangerous voltages to the transfer switch, as does the standby generator when it is in operation. Avoid contact with bare
wires, terminals, connections, etc. while the unit is running. Ensure all appropriate covers, guards and barriers are in place, secured and/or
locked before operating the generator. If work must be done around an operating unit, stand on an insulated, dry surface to reduce potential
shock hazard.
•Do not handle any kind of electrical device while standing in water, while barefoot, or while hands or feet are wet. DANGEROUS ELECTRICAL SHOCK MAY RESULT.
•This is an Automatic Standby Generator, the generator may crank and start at any time when utility is lost. When this occurs, load circuits are
transferred to the STANDBY (generator) power source. To prevent injury, before working on this generator (for inspection, service or maintenance), always put the generator into the OFF mode and remove the 7.5 Amp fuse from the generator control panel.
•In case of accident caused by electric shock, immediately shut down the source of electrical power. If this is not possible, attempt to free the
victim from the live conductor. AVOID DIRECT CONTACT WITH THE VICTIM. Use a nonconducting implement, such as a dry rope or board,
to free the victim from the live conductor. If the victim is unconscious, apply first aid and get immediate medical help.
•Never wear jewelry when working on this equipment. Jewelry can conduct electricity resulting in electric shock, or may get caught in moving
components resulting in injury.
1.5 — Fire Hazards
•For fire safety, the generator must be installed and maintained properly. Installation MUST always comply with applicable codes, standards,
laws, regulations and product Installation Manual guidelines. Adhere strictly to local, state, and national electrical and building codes. Comply
with regulations the Occupational Safety and Health Administration (OSHA) has established. Also, ensure that the generator is installed in
accordance with the manufacturer’s instructions and recommendations. Following proper installation, do nothing that might alter a safe installation and render the unit in noncompliance with the aforementioned codes, standards, laws and regulations.
•Keep a fire extinguisher near the generator at all times. Extinguishers rated “ABC” by the National Fire Protection Association are appropriate
for use on the standby generator. Keep the extinguisher properly charged and be familiar with its use. Consult the local fire department with
any questions pertaining to fire extinguishers.
1.6 — Explosion Hazards
•Do not smoke around the generator. Wipe up any fuel or oil spills immediately. Ensure that no combustible materials are left in the generator
compartment, or on or near the generator as FIRE or EXPLOSION may result. Keep the area surrounding the generator clean and free from
debris.
•Gaseous fluids such as natural gas and liquid propane (LP) gas are extremely EXPLOSIVE. Install the fuel supply system according to applicable fuel-gas codes. Before placing the home standby electric system into service, fuel system lines must be properly purged and leak
tested according to applicable code. After installation, inspect the fuel system periodically for leaks. No leakage can be permitted.
Automatic Standby Generator Owner’s Manual3
If this generator is used to power electrical load circuits normally powered by a utility power source, it is
+
required by code to install a transfer switch. The transfer switch must effectively isolate the electrical system
from the utility distribution system when the generator is operating (NEC 702). Failure to isolate an electrical
system by such means will result in damage to the generator and also may result in injury or death to utility
power workers due to backfeed of electrical energy.
4Automatic Standby Generator Owner’s Manual
Section 2 General Information
EXHAUST
NCLOSURE
COMPOSITE BASE
OIL FILL CAP
BATTERY COMPARTMEN
FUEL
REGULATOR
CIRCUIT
BREAKERS
FUEL INLET
(BACK)
CONTROL
PANEL
OIL
DIPSTICK
AIR FILTER
DATA LABEL
(SEE SAMPLE)
EXHAUST
ENCLOSURE
COMPOSITE BASE
OIL FILTER
OIL FILL CAP
BATTERY COMPARTMENT
FUELREGULATOR
CIRCUIT BREAKERS
FUELINLET(BACK)
CONTROL PANEL
OIL
DIPSTICK
AIR FILTER
DATA LABEL
(SEE SAMPLE)
EXHAUST
ENCLOSURE
COMPOSITE BASE
OIL FILTER
OIL FILL CAP
BATTERY COMPARTMENT
FUEL
REGULATOR
CIRCUIT
BREAKERS
FUEL
INLET
(BACK)
CONTROL
PANEL
OIL
DIPSTICK
AIR FILTER
DATA LABEL
(SEE SAMPLE)
2.1 — The Generator
E
OIL FILTER
Figure 2-1: GH-410 Engine 8kW Unit
Figure 2-2: GH-530 Engine 11kW Unit
T
Automatic Standby Generator Owner’s Manual5
Figure 2-3: GT-990/GT-999 Engines, 13-20kW Unit
EXHAUST
ENCLOSURE
COMPOSITE BASE
OIL FILTER
OIL FILL CAP
BATTERY COMPARTMENT
FUEL
REGULATOR
CIRCUIT
BREAKERS
FUEL
INLET
(BACK)
CONTROL
PANEL
OIL
DIPSTICK
AIR FILTER
DATA LABEL
(SEE SAMPLE)
2.2 — Protection Systems
The generator may have to run for long periods of time with no operator present to monitor the engine/generator conditions. Therefore, the generator is equipped with a number of systems to automatically shut down the unit to protect it against potentially damaging conditions. Some of
these systems are as follows:
• Low Oil Pressure Sensor
• High Temperature Sensor
• Overcrank Sensor
• Overspeed Sensor
• RPM Sensor
The control panel contains a display which alerts the operator when a fault condition occurs. The above list is not all inclusive. For more information about alarms and control panel operation, see Section 3 Operation.
•Under-frequency Sensor
•Undervoltage Sensor
•Overvoltage Sensor
•Internal Failure Sensor
•Low Battery Voltage Alarm
6 Automatic Standby Generator Owner’s Manual
2.3 — Emission Information
The U.S. Environmental Protection Agency (EPA) requires that this generator comply with exhaust emission standards. This generator is certified
to meet the applicable EPA emission levels, and is certified for use as a stationary engine for standby power generation. Any other use may be a
violation of federal and/or local laws. To ensure that the engine complies with the applicable emission standards for the duration of the engine’s
life, it is important to follow the maintenance specifications in the Section 4 Maintenance. This generator is certified to operate on Liquid Propane
Vapor fuel or pipeline Natural Gas.
For generators 13kW and greater, the Emission Control System code is EM (Engine Modification). The Emission Control System on this
generator consists of the following components:
•Air Induction System
•Intake Pipe / Manifold
•Air Cleaner
•Fuel Metering System
•Carburetor / Mixer Assembly
•Fuel Regulator
•Ignition System
•Spark Plug
•Ignition Module
•Exhaust System
•Exhaust Manifold
•Muffler
•Catalyst (11kW generator only)
Automatic Standby Generator Owner’s Manual7
Loading...
+ 25 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.