Generac Power Systems ATC-300+ Operation And Maintenance Manual

O & M Manual for ATC-300+ 40-400A (480/600Vac) ATC-300+ 3-Position Contactor Based Transfer Switch
Instruction Booklet
Description Page
Introduction . . . . . . . . . .
Operation . . . . . . . . . . . .
Testing and Problem Solving Adjustments
Maintenance . . . . . . . . . .
Renewal Parts Guide ATC-300+ Contactor Based ATS Quick Start Instructions . .26
Appendix A: Pickup / Dropout Tables . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
. . . . . . . . . . . . . . . . . . . . . . . . 2
. . . . . . . . . . . . . . . . . . . 6
. . . . . . . . . . . . . . . . . . . . . . . . 7
. . . . . . . . . . . . . . . . . . . . . . . .15
. . . . . . . . . . . . . . . . . . . . . . . .21
. . . . . . . . . . . . . . . . . . . . . . .22
. . . . . . . . . . . . . . . . . . . . . . . .24
. . . . . . . . . . . . . . . . . . . . . . . . . . . .25
. . . . . . .36
   
IB01602078E For more information visit: www.generac.com
Instruction Booklet
Cat No: ATC3C3X30400WRU Style No:
ASSEMBLED IN MEXICO WITH U.S. COMPONENTS 30 - 43465
ITEM: 001
PIECE: 001
CS#: 123456
J050412234
Volts: 240
Poles: 3
Amps: 400
Phase: 3
Hertz: 60
Wire: 3/4
GO No: ABC0123
OF: 001
Page 2 Effective: September 2011
40-400A (480/600Vac) ATC-300+ 3-Postion
Contactor Based Transfer Switch
Section 1: Introduction
WARNING
READ AND UNDERSTAND THE INSTRUCTIONS CONTAINED HEREIN­AFTER BEFORE ATTEMPTING TO UNPACK, ASSEMBLE, OPERATE, OR MAINTAIN THIS EQUIPMENT.
HAZARDOUS VOLTAGES ARE PRESENT INSIDE TRANSFER SWITCH
CLOSURES THAT CAN CAUSE DEATH OR SEVERE PERSONAL
EN INJURY. FOLLOW PROPER INSTALLATION, OPERATION, AND MAIN­TENANCE PROCEDURES TO AVOID THESE VOLTAGES
TRANSFER SWITCH EQUIPMENT COVERED BY THIS INSTRUCTION BOOK IS PLATE RATINGS. OPERATION OUTSIDE OF TH CAUSE THE EQUIPMENT TO FAIL RESULTING IN DEATH, SERIOUS BODILY INJURY, AND/OR PROPERTY DAMAGE. ALL RESPONSIBLE PERSONNEL SHOULD LOCATE THE DOOR MOUNTED EQUIPMENT NAMEPLATE AND BE FAMILIAR WITH THE INFORMATION PROVIDED ON THE NAMEPLATE. A TYPICAL EQUIPMENT NAMEPLATE IS SHOWN IN FIGURE 1.
DESIGNED AND TESTED TO OPERATE WITHIN ITS NAME-
Figure 1. Typical Automatic Transfer Switch (ATS) Equipment Nameplate.
All possible contingencies that may arise
during installation, oper­ation, or maintenance, and all details and va ment do no purport to be covered by these instructions. If further information is desired by the purchaser r
egarding a particular installation, operation, or maintenance of particular equipment, please contact an authorized Generac Sales Representative or the installing contractor.
.
ESE RATINGS MAY
riations of this equip-
1.1 Preliminary Comments and Safety Precautions
This technical document is intended to cover most aspects asso­ciated with the installation, application, operation, and mainte­nance of the Automatic Transfer Controller (ATC-300+) controlled c
ontactor based ATS with ratings from 40 through 400 amperes (A). It is provided as a guide for authorized and qualified personnel only. Please refer to the specific WARNING and CAUTION in Section 1.1.2 before proceeding. If further infor­mation is required by the purchaser regarding a particular installa­tion, application, or maintenance activity, plea
se contact an authorized Generac sales representative or the installing contrac­tor.
1.1.1 Warranty and Liability Information
No warranties, expressed or implied, including warranties of fit­ness for a particular purpose of merchant
ability, or warranties arising from course of dealing or usage of trade, are made regard­ing the information, recommendations and de
scriptions contained herein. In no event will Generac be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capi­tal, loss of power, additional expenses in the use
of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information and descrip­tions contained herein.
1.1.2 Safety Precautions
All safety codes, safety standards, and/or regulations must be strictly observed in the installation, operation, and maintenance of this device.
WARNING
THE WARNINGS AND CAUTIONS INCLUDED AS PART OF THE PRO­CEDURAL STEPS IN THIS DOCUMENT ARE FOR PERSONAL SAFETY AND PROTECT OF A TYPICAL WARNING LABEL HEADING IS SHOWN ABOVE TO FAMILIARIZE PERSONNEL WITH THE STYLE OF PRESENTATION. THIS WILL HELP TO INSURE THAT PERSONNEL ARE ALERT TO WARNINGS, WHICH APPEAR THROUGHOUT THE DOCUMENT. IN ADDITION, WARNINGS AND CAUTIONS ARE ALL UPPER CASE AND BOLDFACE.
ION OF EQUIPMENT FROM DAMAGE. AN EXAMPLE
For more information visit: www.generac.com IB01602078E
CAUTION
COMPLETELY READ AND UNDERSTAND THE MATERIAL PRESENTED IN THIS DOCUMENT BEFORE ATTEMPTING INSTALLATION, OPERA­TION, OR APPLICATION OF THE EQUIPMENT. IN ADDITION, ONLY QUALIFIED WORK ASSOCIATED WITH THIS EQUIPMENT. ANY WIRING INSTRUCTIONS PRESENTED IN THIS DOCUMENT MUST BE FOL­LOWED PRECISELY. FAILURE TO DO SO COULD CAUSE PERMANENT EQUI
PERSONS SHOULD BE PERMITTED TO PERFORM ANY
PMENT DAMAGE.
40-400A (480/600Vac) ATC-300+ 3-Postion
Source 1
Source 2
Load
LOGIC
PANEL
VOLTAGE SELECTION AND TRANSFORMER PANEL
POWER PANEL
Contactor Based Transfer Switch
Instruction Booklet
Effective: September 2011 Page 3
1.2 General Information
Transfer switches are used to protect critical electrical loads against loss of power. The load’s Source 1 power source is backed up by a Source 2 power source. A transfer switch is connected to both the Source 1 and Source 2 power sources and supplies the load with power from one of the two sources. In the event that power is lost from Source 1, the transfer switch trans­fers the load to the Source 2 power source. This transfer is auto­matic. Once Source 1 power is restored, the load is automatically trans (Figure 2).
ferred back to the Source 1 power source
and the Source 2 power source fails while the Source 1 power source is still unavailable, the ATS remains connected to the Source 2 power source.
ATSs automatically perform the transfer function and include
e basic elements:
thre
1. A power contactor to connect and disconnect the load to nd from either power source.
a
2. Solenoids to make the transfer of the main contacts from
source to source.
3. Intelligence/supervisory circuits
condition of the power sources and thus provide the intelli­gence necessary for the switch and related circuit operation.
to constantly monitor the
1.2.1 Design Configuration
The Generac contactor based ATS is a compact design that uses a power contactor to transfer essential loads from one power source to another (Figure 3 [400A]).
Figure 2. Typical Load Transfer Switch Schematic (Contactor Type).
In ATS equipment, the switch’s intelligence system initiates the
fer when the Source 1 power fails, falls below, or rises
trans above a preset voltage. If the Source 2 power source is a standby generator, the ATS initiates generator startup and trans­fers to the Source 2 power source when sufficient generator
age is available. When Source 1 power is restored, the ATS
volt automatically transfers back and initiates generator shutdown. In the event the Source 1 power source fails and the Source 2 power source does not appear, the ATS remains connected to the Source 1 power source until the Source 2 power source does appear. Conversely, if connected to the Source 2 power source
Figure 3. Typical Power Panel for a 400A Model.
The Generac contactor based ATS was designed with easy installation and simplified maint els comprise the contactor based ATS design:
1. Power panel;
2. Voltage selection and transformer panel (if required); and
3. Microprocessor-based logic panel.
enance in mind. Three main pan-
IB01602078E For more information visit: www.generac.com
Instruction Booklet
AT C 3 C3 X 3 0400 W R U
1to2 3 4 5 6 7 8 9to
12 13 14 15
to
Page 4 Effective: September 2011
40-400A (480/600Vac) ATC-300+ 3-Postion
Contactor Based Transfer Switch
Table 1. Withstand Ratings.
UL 1008 WITHSTAND AND CLOSE-ON RATINGS (kA)
UL 1008 Ampere Rating 480 Volts 600 Volts
Any
Breaker
100 30,000 30,000 22,000 35,000
200 30,000 30,000 22,000 35,000
260 30,000 50,000
320 30,000 50,000
400 30,000 50,000
1.3 ATS Catalog Number Identification
Transfer switch equipment catalog numbers provide a significant amount of relevant information that pertains to a particular piece of equipment. The Catalog Number Identification Table (Table 2) provides the required interpretation information. An example is offered here to initially simplify the process.
Example: C
atalog Number (circled numbers correspond to position
headings in Table 2).
Specific Breaker
Any
Breaker
Specific Breaker
Figure 4. Contactor Based ATS (400A).
Each panel is independently mounted with interconnecting wiring terminated at the connector receptacles on the ATC-300+ Con­troller. Door or individual panel removal is achieved without dis­turbing critical connections by removing the connectors from the
eptacles and cutting the wire ties that secure the wires to the
rec door.
Mounting the enclosure is simple using top and bottom mounting flanges with elonga ing holes, along with power panel positioning bolts and pre­tapped inse tial enclosure installation. Refer to Section 4 for specific mount­ing and modification details.
rts, insure proper power panel mounting after the ini-
ted (teardrop) mounting holes. These mount-
The catalog number ATC3C3X30400WRU describes an ATS with a 3-pole, 3 position Power Contactor mounted on a baseplate within the enclosure. The intelligence represented by the logic panel is ATC-300+ controller. The continuous current rating of this equipment is 400A and applicable at 240 Vac, 60 Hz. The transfer switch equipment is enclosed in a NEMA 3R enclosure and is listed for UL applications.
For more information visit: www.generac.com IB01602078E
Instruction Booklet
40-400A (480/600Vac) ATC-300+ 3-Postion Contactor Based Transfer Switch
Table 2. Transfer Switch Catalog Number Explanation
POSITIONS 1 TO 2 POSITION 3 POSITION 4 POSITIONS 5 TO 6
BASIC DEVICE SWITCHING DEVICE CONTROL PANEL SWITCHING DEVICE
Automatic Transfer Switch AT Contactor C ATC-300+ Controller 3 3 Position Power Contactor C3
POSITION 7 POSITION 8 POSITIONS 9 TO 12 POSITION 13 POSITION 14 POSITION 15
SWITCHING DEVICE
ARRANGEMENT
Fixed Mount X Two (2) 40A – 0040 208 Vac/60 Hz B Type 1 S UL/CSA Listing U
150A 0150 380 Vac/50 Hz H Open K
*For 225A to 400A, 600 Vac application, please refer to IB01602024E
NUMBER
OF POLES
Three (3) 80A – 0080 220 Vac/50 Hz G Type 12 J No Listing X
Four (4) 100A – 0100 240 Vac/60 Hz W Type 3R R
AMPERE
RATING
200A – 0200 415 Vac/50 Hz O
*225A – 0225 480 Vac/60 Hz X
*260A – 0260 600 Vac/60 Hz E
*400A – 0400
VOLTAGE/
FREQUENCY ENCLOSURE LISTING
Effective: September 2011 Page 5
1.4 Environmental Conditions
1.4.1 Operational Conditions
Normally, an ATS is applied indoors in an electrical equipment room. In the appropriate enclosure, it can be used for outdoor applications where the equipment is subject to falling rain, freez ing temperatures, and no greater than 90% humidity (non-con­densing). The ambient temperature range for operation is between -20 and 70°C (-4 to 158°F).
1.5 Glossary
With respect to their use within this document and as they relate to transfer switch and controller operation, the following termi nology is defined.
Available
A source is defined as “available” when it is within its undervolt­age/overvoltage/ underfrequency/overfrequency (if applicable) setpoint ranges for the nominal voltage and frequency setting.
Connected
Connected is defined as when the input is shorted by an external contact or connection.
Failed or Fails
A source is defined as “failed” when it is outside of the applica­ble voltage and frequency setpoint ranges for the nominal volt­age and frequency setting for a time exceeding 0.5 seconds after the time delay emergency fail (TDEF) time delays expires.
Failsafe
Failsafe is a feature that prevents disconnection from the only available power source and also forces a transfer or re-transfer operation to the only available power source.
-
Re-Transfer
Re-transfer is defined as a change of the load connection from the Source 2 to the Source 1.
Source 1
Source 1 is the primary source (normal source, normal power source, or normal).
-
Source 2
Source 2 is the secondary source (emergency source, emer­gency power source, emergency, standby, or backup source).
Source 1: Failed or Fails
Source 1 is defined as “failed” when it is outside of its under­voltage/overvoltage/ underfrequency/overfrequency (if applica­ble) setpoint ranges for the nominal voltage and frequency setting.
Source 2: Failed or Fails
Source 2 is defined as “failed” when it is outside of its under­voltage/overvoltage/ underfrequency/overfrequency (if applica­ble) setpoint ranges for the nominal voltage and frequency setting for a time exceeding 0.5 seconds after the Time Delay Emergency Fail (TDEF) time delay expires.
Transfer
Transfer is defined as a change of the load connection from the Source 1 to the Source 2 power source.
Unconnected
Unconnected is defined as when the input is not shorted by an external contact or connection.
IB01602078E For more information visit: www.generac.com
Instruction Booklet
Page 6 Effective: September 2011
40-400A (480/600Vac) ATC-300+ 3-Postion
Contactor Based Transfer Switch
Section 2: Receiving, Handling, and Storage
2.1 Receiving
Every effort is made to ensure that the ATS equipment arrives at its destination undamaged and ready for installation. Packing is designed to protect internal components as well as the enclo sure. Care should be exercised, however, to protect the equip­ment from impact at all times. Do not remove the protective packaging until the equipment is ready for installation.
When the ATS equipment reaches its destination, the customer should inspect the shipping container for any obvious signs of rough handling and/or external damage that occurred during transportation. Record any external and internal damage for reporting to the transportation carrier and Generac, once a thor ough inspection is complete. All claims should be as specific as possible and include the catalog and General Order numbers.
A shipping label affixed to the shipping container includes a vari­ety of equipment and customer information, such as General Order Number and catalog numbers. Make certain that this infor mation matches other shipping paper information.
Each transfer switch is packed securely with appropriate ship­ping materials to prevent damage during shipment. Do not remove or discard the packing material until the equipment is ready for installation.
Once the top packaging is removed from the shipment, the enclosure door can be opened. A plastic bag of documents will be found in the enclosure, usually attached to the inside of the enclosure. Important documents, such as test reports, wiring diagrams, and appropriate instruction leaflets, are enclosed within the bag and should be filed in a safe place.
-
2.3 Storage
Although well packaged, this equipment is not suitable for out­door storage. The equipment warranty will not be applicable if there is evidence of outdoor storage. If the equipment is to be stored indoors for any period of time, it should be stored with its protective packaging material in place. Protect the equipment at all times from excessive moisture, construction dirt, corrosive conditions, and other contaminants.
It is strongly suggested that the package-protected equipment be stored in a climate-controlled environment with temperatures from -30 to 85°C (-22 to 185°F) and with a relative humidity of 80% or less. DO NOT, under any circumstance, stack other equipment on top of a transfer switch equipment enclosure, whether packaged or not.
-
-
2.2 Handling
As previously mentioned, ATS equipment is packaged for forklift movement. Protect the equipment from impact at all times and DO NOT double stack.
Once the equipment is at the installation location and ready to be installed, packaging material can be removed and discarded. Once the enclosure is unbolted from the wooden pallet, it can be hand moved to its installation position. Be careful not to damage the top or bottom enclosure mounting flanges. Refer to Section 4 of this manual for specific installation instructions.
For more information visit: www.generac.com IB01602078E
40-400A (480/600Vac) ATC-300+ 3-Postion
POWER PANEL
LOGIC PANEL
VOLTAGE SELECTION
AND TRANSFORMER PANEL
Contactor Based Transfer Switch
Section 3: Equipment Description
3.1 General
The ATS consists of three basic panels:
1. The power panel;
2. The voltage selection and transformer panel (if required); and
3. The microprocessor-based logic panel.
These panels are interconnected via connector plugs and mounted in an enclosure (Figure 5
).
Instruction Booklet
Effective: September 2011 Page 7
Figure 5. Three Basic Panels of the ATS (40-400A).
3.2 Power Panel
The power panel is used for making load, power, and neutral con­nections. The power contactor is mounted on a steel baseplate (Figure 6).
3.2.1 Main Contacts
This ATS incorporates a power contactor. The main contacts connect and disconnect the load to and from the different power sources. The power contactor is mechanically and electrically interlocked to prevent the two sets of main contacts from being closed simultaneously.
Figure 6. Typical Power Panel for 40-400A Models.
3.3 Voltage Selection
3.3.1 Standard Voltage Selection (208, 240, 480, 600, 60 Hz and 220, 380, 415, 50 Hz.)
The Standard voltage selection panel consists of multi-tap trans­formers, contained in a steel case mounted in the enclosure (Fig­ure 7). The voltage is selected by the default primary taps of both transformers and installing them on the primary taps for the desired voltage. Taps are provided for 208 to 600 Vac to satisfy application voltage. The factory default position is 600 Vac.
simply removing the wires from
CAUTION
WHEN CHANGING THE SELECTED VOLTAGE, THE POWER MUST BE REMOVED FROM THE ATS AND THE WIRES MUST BE MOVED ON THE TAPS OF BOTH TRANSFORMERS.
IB01602078E For more information visit: www.generac.com
Instruction Booklet
Page 8 Effective: September 2011
40-400A (480/600Vac) ATC-300+ 3-Postion
Contactor Based Transfer Switch
Figure 7. Standard Voltage Selection Terminals (Shown Connected to the 480 Vac Taps).
3.4 ATC-300+ Logic Panel
The ATC-300+ is a microprocessor-based transfer switch logic control package. The hardware and software of the controller contain the intelligence/supervisory circuits that constantly moni­tor the condition of the power sources. It provides the intelli­gence necessary for the operation of the ATS (Figure 8).
Figure 8. ATC-300+ Logic Control Panel.
The ATC-300+ controller has an operating temperature of
-20 to 70°C (-4 to 158°F).
The controller circuit board is protected by an insulating confor­mal coating.
The specifications, under normal operating conditions, are as fol­lows:
Tolerance for voltage sensing function: ±1% of full scale
Tolerance for frequency sensing function: ±0.3 Hz of setting
For more information visit: www.generac.com IB01602078E
40-400A (480/600Vac) ATC-300+ 3-Postion Contactor Based Transfer Switch
Instruction Booklet
Effective: September 2011 Page 9
3.5 Features
A variety of standard and optional features are available for Gen­erac ATSs. All features or combinations of features may not be available on specific ATSs. All features and/or accessories are Underwriters Laboratories (UL) listed unless noted.
3.5.1 Standard Features
The following is a list of the standard features for the ATC­300+ATC-300+ Controlled ATS.
1. Time Delay Normal to Emergency (TDNE)
This feature provides a time delay when transferring from the Source 1 to the Source 2 power source. Timing begins when Source 2 becomes available. It permits controlled transfer of the load circuit to Source 2.
Adjustable 0 - 1800 Seconds
2. Time Delay on Engine Starting (TDES)
This feature provides a time delay of the signal to initiate
the engine/generator start cycle in order to override momentary power outages or voltage fluctuations of Source 1.
Adjustable 0 - 120 Seconds
3. Time Delay Emergency to Normal (TDEN)
This feature provides a time delay of the re-transfer opera­tion to permit stabilization of Source 1. Timing begins when Source 1 becomes available. If Source 2 fails during timing, then re-transfer is immediate overriding the time delay.
Adjustable 0 - 1800 Seconds
4. Time Delay for Engine Cool-down (TDEC)
This feature provides a time delay of the signal to initiate the engine/generator stop cycle after the re-transfer opera tion. This allows the engine/generator to cool down by run­ning unloaded. Timing begins on completion of the re­transfer cycle.
Adjustable 0 - 1800 Seconds
5. Source 2 Monitoring and Protection
This feature provides monitoring and protection based on the Source 2 voltage and/or frequency setpoints. All fea ture 5 functions are Failsafe operations.
-
5H. Phase Reversal
For a 3-phase wye source, this feature monitors the phase
sequence of the sources. If a source does not have the same ABC or CBA sequence as the setpoint value, that source will be considered “Unavailable.
For a 3-phase delta source, this feature should be turned off via the PHASE REV setpoint.
5J. All Phase Undervoltage and Underfrequency Protection
Adjustable Undervoltage:
Dropout: 78 - 97% of nominal Pickup: (Dropout +2%) to 99% of nominal
Adjustable Underfrequency:
Dropout: 90 - 97% of nominal Pickup: (Dropout +1Hz) to 99% of nominal
5K. All Phase Overvoltage/Overfrequency
Adjustable Overvoltage:
Dropout: 105 - 110% of nominal Pickup: 103% to (Dropout –2%) of nominal
Adjustable Overfrequency:
Dropout: 103 - 105% of nominal Pickup: 101% to (Dropout -1Hz) of nominal
-
IB01602078E For more information visit: www.generac.com
Instruction Booklet
Page 10 Effective: September 2011
40-400A (480/600Vac) ATC-300+ 3-Postion
Contactor Based Transfer Switch
5L. Source 2 3-Phase Voltage Unbalance
For a 3-phase wye source, this feature monitors phase volt­age ratios. Voltage unbalance (%) is calculated as the dif­ference between the maximum and minimum phase voltage, divided by the minimum phase voltage. User­selectable setpoints are available for dropout and pickup unbalance settings (minimum 2% differential). Dropout is adjustable from 5 to 20%. Pickup is adjustable from 3 to (Dropout –2%). A setpoint for user-selectable time delay from 10 to 30 seconds is provided. The factory default set­points are: 5% dropout, 3% pickup, and 30 seconds time delay. A user-selectable setpoint for enable and disable is also provided.
When an unbalance condition is detected on Source 2, the Unbalance Timer (TD UNBAL) starts timing. After TD UNBAL times out, Source 2 is declared “failed”.
For a 3-phase delta source, this feature should be turned off via the VOLT UNBAL setpoint.
6. Test Operators
Generac ATSs are provided with a Test Pushbutton that simulates a loss of the Source 1 power source as standard (Feature 6B). All programmed time delays (TDNE, TDEN, etc.) will be performed as part of the Test. Engine run time of the Test is equal to the Plant Exerciser (Feature 23) pro grammed setpoint. All Tests are Failsafe protected.
6B. Test Pushbutton
Programmable setpoints include:
1. Load or No Load Testing, or Disabled
2. Engine run time equal to the plant exerciser (Feature 23) setting
7. Time Delay Emergency Fail (TDEF)
This feature provides a time delay that prevents a con­nected Source 2 power source from being declared “Failed” in order to override momentary generator fluctuations. If the Source 2 power source remains in the failed state then,
0.5 seconds after the TDEF timer expires, the transfer
switch will proceed with the programmed sequence for retransfer. This time delay is only implemented when the Source 2 power source is a generator.
Adjustable 0 - 6 Seconds
8. Time Delay Bypass Pushbutton
This feature provides a way (by pushing the Help and Step pushbutton simultaneously) to bypass the TDNE (Feature 1) and/or TDEN (Feature 2) time delays. The Time Delay Bypass function, when activated by pushing the Help and Step pushbutton simultaneously, will reduce any or all of the programmed time delay to zero.
8C. Bypass TDEN
This feature provides one set of pushbuttons to bypass the TDEN time delay.
8D. Bypass TDNE
This feature provides one set of pushbuttons to bypass the TDNE time delay.
12. Power Source Annunciation
This feature provides LEDs to give switch position and power source availability indications.
Switch Position
Provides LEDs to indicate the switch position
12C. Source 1 - Source Connected
This feature provides a green LED that, when lit, indicates
the load is connected to Source 1.
12D. Source 2 - Source Connected
This feature provides a red LED that, when lit, indicates the
load is connected to Source 2.
Power Source Availability
Provides LEDs to indicate if a power source is available.
LEDs may be integral or separate from the controller.
12G. Source 1 - Available
This feature provides a white LED that, when lit, indicates
Source 1 is available.
12H. Source 2 - Available
-
This feature provides an amber LED that, when lit, indi-
cates Source 2 is available.
14. Relay Auxiliary Contacts
14G. Source 1 Present: Provides two (2) normally open and two
(2) normally closed contacts. The relay is energized when Source 1 is available.
14H. Source 2 Present: Provides two (2) normally open and two
(2) normally closed contacts. The relay is energized when Source 2 is available.
15. Switch Position Indication Contact
This feature provides a contact that indicates if the power switching device is in the “Open” or “Closed” position.
15E. Source 1 Position Indication Contact
This feature provides 1 dry form “C” contact that indicates the position of the Source 1 power switching device.
15F. Source 2 Position Indication Contact
This feature provides 1 dry form “C” contact that indicates the position of the Source 2 power switching device.
23. Plant Exerciser (PE)
This feature provides a means for automatic testing of the
engine generator set or standby power system. All pro grammed time delays will be performed during plant exer­ciser operations.
-
For more information visit: www.generac.com IB01602078E
40-400A (480/600Vac) ATC-300+ 3-Postion Contactor Based Transfer Switch
Instruction Booklet
Effective: September 2011 Page 11
23K. Plant Exerciser Selectable – Disabled/1/7/14/28 Day Inter-
val
This feature provides for automatic test operation of the
generator. Available test cycles are daily, 7, 14, or 28 days with duration equal to the programmed engine test time.
Programmable setpoints allow for selection of three test
cycles:
Engine Start/Run Only (No Load);
Exercise with Load Transfer; or
Disabled
This is a “Failsafe” operation.
26. Source 1 - Monitoring and Protection
This feature provides Source 1 monitoring and protection
functions. If the Source 1 power supply fails, then the Automatic Transfer Controller will begin the sequence of operations necessary to transfer the load circuit to the Source 2 power supply. All Feature 26 monitoring and protection functions are Failsafe operations.
26D. Go to Source 2
This feature provides the capability for an external contact opening to initiate a load circuit transfer to the Source 2 power source. This includes starting the engine/generator, performing the programmed time delays, and the transfer operation. Re-transfer will occur when the external con tact is closed or under a Failsafe condition.
26H. Phase Reversal Protection
For a 3-phase wye source, this feature monitors the phase
sequence of the sources. If a source does not have the same ABC or CBA sequence as the phase reversal set point, the source will be considered “Unavailable”.
For a 3-phase delta source, this feature should be turned
off via the PHASE REV setpoint.
26J. All Phase Undervoltage and Underfrequency Protection
Adjustable Undervoltage:
Dropout: 78 - 97% of nominal Pickup: (Dropout +2%) to 99% of nominal
Adjustable Underfrequency:
Dropout: 90 - 97% of nominal Pickup: (Dropout +1Hz) to 99% of nominal
26K. All Phase Overvoltage/Overfrequency
Adjustable Overvoltage:
Dropout: 105 - 110% of nominal Pickup:103% to (Dropout –2%) of nominal
Adjustable Overfrequency:
Dropout: 103 - 105% of nominal Pickup: 101% to (Dropout -1Hz) of nominal
-
-
26L. Source 1 3-Phase Voltage Unbalance
.For a 3-phase wye source, this feature monitors phase voltage ratios. Voltage unbalance (%) is calculated as the difference between the maximum and minimum phase voltage, divided by the minimum phase voltage. User­selectable setpoints are available for dropout and pickup unbalance settings (minimum 2% differential). Dropout is adjustable from 5 to 20%. Pickup is adjustable from 3 to (Dropout –2%)). A setpoint for user-selectable time delay from 10 to 30 seconds is provided. The factory default setpoints are: 5% dropout, 3% pickup, and 30 seconds time delay. A user-selectable setpoint for enable and dis­able is also provided.
When an unbalance condition is detected on Source 1, the Unbalance Timer (TD UNBAL) starts timing. After TD UNBAL times out, Source 1 is declared “failed”.
For a 3-phase delta source, this feature should be turned off via the VOLT UNBAL setpoint.
29. Alternate Transfer Modes of Operation
Provides standard or optional transfer modes, mode selec­tion devices, and operational methods for ATSs.
29J. Type of Operation (MANTR) Operation (new feature)
This feature provides for a selection between an automatic transfer and re-transfer mode or a manual pushbutton re­transfer to Normal from the Emergency Source mode. If this option is not selected the factory default selection is automatic.
32. Delayed Transition Transfer Modes for Open Transition Transfer Switches
This feature provides delayed transition transfer modes for an open transition transfer switch. Often used in sys tems with inductive loads, a delayed transition transfer switch may prevent or reduce in-rush currents due to out of phase switching of inductive loads.
32A. Time Delay Neutral
This feature provides a time delay in the neutral position during the transfer and re-transfer operations during which both Source 1 and Source 2 are disconnected from the load circuit. The time delay is programmable and is the same for both transfer and re-transfer operations.
Adjustable 0 - 120 Seconds
35. Pre-Transfer Signal
This feature provides a signal to a remote device prior to a
re-transfer operation. It provides one Form “C” contact (NO/NC) for interface with other equipment (typically ele vator controls). The contacts close/open on a timed basis prior to transfer in either direction. After TDNE/TDEN times out, this relay closes and the Pre-transfer Timer (TPRE) starts timing. After the TPRE times out, the trans fer proceeds by starting the TDN timer if enabled. The pre-transfer relay opens after the transfer is complete.
Adjustable 0 - 120 Seconds
35A. Pre-Transfer Signal with 1 N.O. and 1 N.C. Contacts
This feature provides pre-transfer signal and includes 1
N.O. and 1N.C. contacts.
-
-
-
IB01602078E For more information visit: www.generac.com
Instruction Booklet
Page 12 Effective: September 2011
40-400A (480/600Vac) ATC-300+ 3-Postion
Contactor Based Transfer Switch
36. Emergency Inhibit (new feature)
This feature enables the Emergency inhibit control input to
inhibit transfers to the Emergency Source. See Control Inputs section for more information.
This input is located on Pins 7 and 8 of Connector J8 and
is enabled when the Emergency Inhibit is enabled. The con tact is closed for normal operation. Opening this contact will activate the Emergency Inhibit input.
If the Emergency Inhibit contact is opened when the load is
connected to the Normal Source, no action will be taken if the Normal Source is available. If the Normal Source is not available, an immediate transfer to the neutral position will occur.
If the Emergency Inhibit contact is opened when the load is
connected to the Emergency Source, the ATC-300+ will transfer the load to the Normal Source if it is available. If the Normal Source is not available, an immediate transfer to the neutral position will occur.
The Emergency Inhibit input is only active when either
Source 1 or Source 2 is preferred. This input is not active when the Preferred Source selection is set to None.
The Emergency Inhibit input takes priority over the Go To
Emergency input if both inputs are activated at the same time. In this case, the generator will start but a transfer to the Emergency Source will be inhibited until the Emergency Inhibit input is de-activated.
42. Seismic Withstand Capability
Provides transfer switch with seismic capability exceeding
the worst case Zone 4 required per both the Uniform Build ing Code and the California Building Code.
48F. RS-485 with Modbus Option
Provides communications for the ATC-300+ via Modbus
through an integrated RS-485 port. Registers are available to read back status, voltages, frequencies, and historical data. Registers are also available for transfer switch con trol. Setpoints may be read back and/or programmed via a pass-through command. See the ATC-300+ Modbus Com munication Guide pn: 66A7787.
-
3.5.2 Optional Features
The following is a list of the optional features for the ATC-300+ Controlled ATS. All features or combinations of features may not
be available on specific ATSs
9B. Maintenance Selector Switch (MSS)
Marked “OFF”, “ON”. This feature provides selector switch disconnection of control to transfer thus allowing testing of the transfer switch control logic circuitry with out initiating load transfer. Positioning the MSS in the “OFF” position isolates the control circuit, permitting man ual operation of the transfer switch or testing of logic cir­cuitry without load transfer. White indication light is lit ON and display on ATC-300 controller shows “ATS NOT IN AUTOMATIC” when the switch is in maintenance mode.
14. Relay Auxiliary Contacts: This feature provides form “C” relay auxiliary contacts.
14C. Source 1 Present: Provides four (4) normally open and four
(4) normally closed contacts. The relay is energized when Source 1 is available.
-
14D. Source 2 Present: Provides four (4) normally open and four
(4) normally closed contacts. The relay is energized when Source 2 is available.
15. Switch Position Indication Contact
-
-
-
-
This feature provides a contact that indicates if the power switching device is in the “Open” or “Closed position.
15G. Source 1 Position Indication Contact
This feature provides 3 Dry Form “C” contacts that indi­cate the position of the Source 1 power-switching device.
15H. Source 2 Position Indication Contact
This feature provides 3 Dry Form “C” contacts that indi­cate the position of the Source 2 power-switching device.
18. Metering
This feature includes all required external devices (CTs, shorting blocks, fuses, etc.) for a fully functional metering system.
18AN. IQ 250/260 Normal (S1) Only
18AE. IQ 250/260 Emergency (S2) Only
18AL. IQ 250/260 Load
18CN. IQ 110/115 Normal (S1) Only
18CE. IQ 110/115 Emergency (S2) Only
18CL. IQ 110/115 Load
18DN. IQ 130/140/150 Normal (S1) Only
18DE. IQ 130/140/150 Emergency (S2) Only
18DL. IQ 130/140/150 Load
18EN. PXM2250/2260/2270 Normal (S1) Only
18EE. PXM2250/2260/2270 Emergency (S2) Only
18EL. PXM2250/2260/2270 Load
18O. IQ Analyzer Normal (S1) Only
18P. IQ Analyzer Emergency (S2) Only
18Q. IQ Analyzer Normal (S1) & Emergency (S2) Switch Select-
able
18V. IQ Analyzer Load
18R. IQ DP-4000 Normal (S1) Only
18S. IQ DP-4000 Emergency (S2) Only
18T. IQ DP-4000 Normal (S1) & Emergency (S2) Switch Select-
able
18U. IQ DP-4000 Load
18W. Ammeter
A single ammeter is a true RMS sensing device that dis­plays single phase current only.
The ammeter can be mounted on Source 1, Source 2, or load. The meter can also be configured for 1, 2, or 3-phase sensing by supplying one meter per phase for Source 1, Source 2, or load. Ammeters for both Source 1 and Source 2 can also be grouped together.
For more information visit: www.generac.com IB01602078E
+ 28 hidden pages