Generac Power Systems 9592-3 User Manual

V
Part No. 98773
OWNER’S
Manual
Series Q-55G and Q-70G
AIR-COOLED
RECREATIONAL VEHICLE GENERATORS
Revision 1 (06/02/98)
C O R P ORATION
Printed in U.S.A.

GENERAL SAFETY RULES

THE MANUFACTURER SUGGESTS THAT THESE "RULES" FOR SAFE OPERATION BE COPIED AND POSTED IN POTENTIAL HAZARD AREAS OF THE INDUSTRIAL VEHICLE. SAFETY SHOULD BE STRESSED TO ALL OPERATORS AND POTENTIAL OPERATORS OF THIS EQUIPMENT.
Study these SAFETY RULES carefully before operating or servicing applicable equipment. Become familiar
with this Owner's Manual and with your generator. Safe, efficient and reiiable operation can only be achieved if generator is properly installed, operated and main tained. Many accidents are caused by failing to follow simple and fundamental rules or precautions. The man
ufacturer suggests that these GENERAL SAFETY RULES be copied and posted in potential hazard areas of the industrial vehicle. Safety should be stressed to all operators and potential operators of equipment.
The manufacturer cannot possibly anticipate every pos sible circumstance that might involve a hazard. The warnings in this Manual and on tags and decals affixed
to the unit are, therefore, not all-inclusive. If you use a procedure, work method or operating technique Generac does not specifically recommend, you must satisfy yourself that it is safe for you and others. You must also make sure the procedure, work method or operating technique that you chose does not render the generator to be unsafe.
For fire safety, the industrial mobile generator must be properly installed and maintained. Installation must always remain in compliance with applicable codes and standards. In addition, the generator must be installed in conformance to the manufacturer’s detailed installation instructions. Following installation, nothing must be done that might render the generator in noncompliance with such codes, standards and instructions.
The RV generator produces extremely high and dangerous electrical voltages and can cause dan gerous, and possibly fatal, electrical shock. Avoid contact with bare wires, terminals, etc. while the unit is running. If you must work around an operat ing generator, stand on an insulated, dry surface to reduce shock hazard.
Never work on this equipment or handle any elec
trical device while standing in water, while barefoot, or while hands or feet are wet. Dangerous electri cal shock will result.
Have the generator properly grounded (bonded)
during installation onto the vehicle, either by solid mounting to the vehicle frame or chassis or by means of an approved bonding conductor. DO NOT disconnect the bonding conductor, if so equipped. DO NOT reconnect the bonding conduc tor to any generator part that might be removed or disassembled during routine maintenance. If the grounding conductor must be replaced, use only a flexible conductor that is of No. 8 AWG copper wire minimum.
Inspect the generator periodically. Repair or re
place all damaged or defective parts immediately.
• In case of accident caused by electric shock, shut down the source of electrical power down at once. If this cannot be done, free victim from live conduc tor. AVOID DIRECT CONTACT WITH THE VIC­TIM. Use a dry board, dry rope, or other non-con ducting implement to free the victim from live con ductor. If victim is unconscious, apply CPR (cardio pulmonary resuscitation) and get medical help.
Inspect fuel system frequently for leaks or damage. Repair or replace any damaged or leaking compo nent immediately. Never attempt to change, alter or modify the generator fuel system in any way that might affect safety or compliance with applicable codes and standards’.
The generator engine gives off DEADLY carbon monoxide gas through its exhaust system. This dangerous gas, if breathed in sufficient concentra tions, can cause unconsciousness or even death. This exhaust system must have been properly in stalled, in strict compliance with applicable codes and standards. Following installation, you must do nothing that might render the system unsafe or in non-compliance with such codes and standards. The generator compartment must be completely vapor sealed from vehicle interior. There must be no possibility of exhaust fumes entering the vehicle interior. Never operate this equipment with a leak ing or defective exhaust system.
Never use the generator or any of its parts as a step. Stepping on the unit can stress and break parts and may result in dangerous operating conditions from leaking exhaust gases, fuel leakage, oil leakage, coolant leakage, etc.
Do not smoke around the generator. Wipe up any fuel, oil and coolant spills immediately. Never leave oily or fuel soaked rags in the generator compart ment or on the generator itself. Keep the area around the generator clean and free of debris.
Adequate ventilation is required to expel toxic fumes and gasoline vapors from the generator com partment. Do not alter the installation of this equip ment in any manner that might obstruct air and ventilation openings. Such openings must be kept clear and unobstructed.
Keep hands, feet, clothing, etc., away from drive belts, fans and other moving parts of this equip ment. Never remove any drive belt or fan guards
while the unit is operating. Some generators may use LP gas (propane) as a
fuel. LP gas is highly EXPLOSIVE. The gas is heavier than air and tends to settle in low areas where even the slightest spark can ignite the gas and cause an explosion.
Before performing any maintenance on the gener ator set, disconnect its battery cables to prevent accidental start up. Disconnect the cable from the battery post indicated by a NEGATIVE, MEG or (-) first. Reconnect that cable last.
IDENTIFICATION RECORD
Please record the following information, from the generator DATA PLATE or information decai:
1. Modei Number
3. kW Rating,
5. Phase
______
r
NDIieL[ SERIES [ SERIALr
V
___________________
2. Serial Number____________________________
4. Rated Voltage,
6. Hertz
1 VO.TSI 1
1 *HPS| 1
1 WATTS 1 1
PHASE-1 HERT2-«0 RPM-VARIA8LE____________
CLASS r INSULATION AT 40*C CtXTINUOUS DUTY
FDR SERVICE CENTER LOCATIONS
CALL 800-333-1332 — 24 HOURS A DAY
GENERAC CORPORATION
VAUKESHA, WIS
U.S. AND FOREIGN PATENTS PENDING
MADE IN U.S.A.
__________
I -

TABLE OF CONTENTS

GENERAL SAFETY RULES. IDENTIFICATION RECORD
READ THIS MANUAL THOROUGHLY
Operation and Maintenance............................................ 3
How to Obtain Service
GENERATOR FEATURES................................................ 4
GENERATOR FAMILIARIZATION
Generator Applicability.................................................... 5
Installation....................................................................... 5
Safety.............................................................................. 5
Generator AC Connection System
OPERATING INSTRUCTIONS
Generator Panel
Automatic Choke
Before Starting the Engine Starting Stopping the Generator Applying Loads to Generator
Wattage Reference Guide ADDITIONAL INFORMATION
Automatic Low Oil Pressure Shutdown
High Temperature Shutdown
Muffler Kits...................................................................... 9
Field Boost Over-Voltage Protection
25-Hour Break in Period................................................10
25-Hour Check Up.........................................................10
Operation in High Grass or Brush
...........................................................................
.............................................................
............................................................
.....................................................................
..........................
.............................................
....................................................
.................................
.............................................
..................................................
..........................................
..............................................
.........................................
.................................................
.................................
inside cover
.............................
..........................
10
SPECIFICATIONS
1
3
3
Generator Specifications..........................................11
Engine Specifications...............................................11
Fuel Requirements...................................................11
Engine Oil Requirements
.........................................
11
Optional LP Gas Fuel System..................................11
MAINTENANCE
Checking Engine Oil Level........................................12
Change Engine Oil....................................................12
Change Oil Filter.......................................................12
5
Engine Air Cleaner....................................................13
Clean Air Intake Screen............................................13
Engine Spark Plugs
6 6 7 7 7 7 8
Fuel Filter..................................................................13
MISCELLANEOUS MAINTENANCE
Spark Arrestor Mufflers.............................................14
Cleaning the Generator
Battery.......................................................................14
Major Service Manual Drive Belts
................................................................14
Exercising the Generator
9 9
9 9
Out of Service Protection...........................................15
Return the Unit to Service after Storage
TROUBLESHOOTING.................................................16
..................................................
............................................
...............................................
..........................................
..................
13
14
14
15
15
ELECTRICAL DATA....................................................17
REPAIR PARTS
..................................................
18 to 29
-2-

READ THIS MANUAL THOROUGHLY

If you don’t understand any portion of this manual, contact Generac for a demonstration of actual starting, operating and servicing procedures.
Throughout this publication and on tags and decals affixed to the generator, DANGER and CAUTION blocks are used to alert you to special instructions about a particular operation that may be hazardous if per formed incorrectly or carelessly. Observe them care fully.
These safety warnings cannot eliminate the hazards that they indicate. Strict compliance with the special instructions while performing the service plus "common sense" are major measures to prevent accidents.
The following definitions apply to DANGER, CAUTION and NOTE blocks found throughout the manual.
DANGER: AFTER THIS HEADING YOU CAN READ HANDLING, INSTALLING, OPERATING OR SERVICING INSTRUCTIONS THAT, IF NOT STRICTLY COMPLIED WITH, MAY RESULT IN PERSONAL INJURY.
CAUTION: After this heading you can read instruc tions for handling, installing, operating or servicing the generator that, if not strictly complied with, may result in damage to equipment and/or property.
NOTE: After this heading you can read explanatory
statements that require special emphasis. The operator (driver) is responsible for proper and safe
use of the vehicle, equipment on the vehicle, and the safety of all vehicle occupants. We strongly recom mend that the operator read this Owner’s Manual and thoroughly understand all instructions before using this equipment. We also strongly recommend instructing other occupants in the vehicle to properly start and
operate the generator. This prepares them if they need to operate the equipment in an emergency.
OPERATION AND MAINTENANCE
It is the operator’s responsibility to perform all safety checks: to make sure that all maintenance for safe operation is performed promptly; and to have the equip ment checked by an Authorized Dealer periodcially. Normal maintenance service and replacement of parts are the responsibility of the Owner/Operator and, as such, are not considered defects in materials or work manship within the terms of the warranty. Individual operating habits and usage contribute to the need for maintenance service.
Proper maintenance and care of your industrial mobile generator assures a minimum number of problems and keeps your operating expenses at a minimum. See your authorized Dealer/Distributor for service aids and accessories.
HOW TO OBTAIN SERVICE
When your industrial mobile generator set requires ser vicing or repairs, simply contact an Authorized Service Station for assistance. Sen/ice technicians are factory­trained and are capable of handling all of your service needs.
When contacting an Authorized Service Facility or the factory about parts and service, always supply the com plete model number and serial number of your unit as given on its data plate.
The warranty on your generator is included in this Owner's Manual, as well as listings for repair parts.
-S-

GENERATOR FEATURES

REFERENCE NUMBER IDENTIFICATION
1. Generator Air Intake Screen
2. Engine Start/Stop Switch
3. 15 amp Fuse
4. 20 or 30 amp Circuit Breaker
5. Optional Remote Panel Receptacle
6. Generator AC Output Leads
7. 30 amp Circuit Breaker
8. Starter Contactor
9. Fuel Inlet
10. Fuel Pump Primer Switch
11. Fuel Pump
12. Oil Filter
13. Oil Drain Plug
14. Oil Dipstick and Filler Tube
-4-

GENERATOR FAMILIARIZATION

GENERATOR APPLICABILITY
Q-55G and Q-70G generators have been designed and manufactured for supplying electrical po\wer for recrea tional vehicles. You should not modify the generator or use it for any application other than for what it was designed. If there are any questions pertaining to its application, write or call the factory. Do not use the unit
until you have been advised by competent authority.
DANGER: FOR FIRE SAFETY, THE GENERATOR MUST HAVE BEEN PROPERLY INSTALLED IN COMPLIANCE WITH (1) ANSI 119.2-1975/NFPA 501C-1974 "STANDARD FOR RECREATIONAL VEHICLES", PART III, "INSTALLATION OF ELEC TRICAL SYSTEMS." THE GENERATOR ALSO MUST HAVE BEEN INSTALLED IN STRICT COM PLIANCE WITH THE MANUFACTURER’S DE TAILED INSTALLATION INSTRUCTIONS. AFTER INSTALLATION, DO NOTHING THAT MIGHT RENDER THE UNIT IN NON-COMPLIANCE WITH SUCH CODES, STANDARDS AND INSTRUC TIONS.
You can use your generator set to supply electrical power for operating one of the following electrical loads:
Q-55G: 120 and/or 240 volts, single phase, 60 Hz
electrical loads. These loads can require up to 5500 watts (5.5 kW) of power, but cannot exceed 45.8 AC amperes of current at 120 volts or exceed 22.9 AC amperes at 240 volts.
Q-70G: 120 and/or 240 volts, single phase, 60 Hz
electrical loads. These loads can require up to 7000 watts (7.0 kW) of power, but cannot exceed 58.3 AC amperes of current at 120 volts or exceed 29.1 AC amperes at 240 volts.
An INSTALLATION MANUAL was shipped with the generator. That Manual contains manufacturer’s in structions and recommendations for installing the unit into an industrial vehicle. After installation, installers should fonvard the Installation Manual to Owners/Oper­ators for their information.
Owners/Operators have the responsibility to make sure that nothing is done that might render the installation unsafe or in non-compliance with applicable codes, standards and instructions.
SAFETY
Before using the generator set, carefully read GEN
ERAL SAFETY RULES inside the cover. Comply with these RULES to prevent accidents and damage to equipment and/or property. Generac suggests copying and posting the GENERAL SAFETY RULES to potential operators of this equipment.
GENERATOR AC CONNECTION SYSTEM
These air-cooled Q Series generator sets are equipped with dual stator AC power windings. These two stator windings supply electrical power to customer electrical
loads by means of a dual 2-wire connection system. The generator may have been installed so that units
only power 120 volts AC loads (Figure 1); or you can wire them to connect both 120 and/or 240 volts AC
electrical loads. Be sure to remove the jumper between the circuit breakers when connecting for 120/240 volts.
CAUTION: Do not overload the generator. Some
installations may require that electrical loads be
alternated to avoid overloading. Applying exces sively high electrical loads may damage the gener ator and may shorten its life. Add up the rated watts of all electrical lighting, appliance, tool and motor
loads the generator will power at one time. This
total should not be areater than the wattage capac
ity of the generator. If an electrical device nameplate gives only volts and amps, multiply volts times amps to obtain watts (volts x amps = watts). Some electric motors require more watts of power (or amps of current) for starting than for continuous operation.
INSTALLATION
This Owner’s Manual has been prepared under the assumption that a competent, qualified technician in stalled the generator into an industrial vehicle. We also assume the installer complied with all applicable codes, standards and regulations pertaining to installation.
QROUNOED
NEUTRAL
Figure 1Connection for 120 Volts Only
5-

OPERATING INSTRUCTIONS

GENERATOR CONTROL PANEL
Mounted on the generator control panel (Figure 2) are
the following features:
Fuel Pump Primer: Before starting a cold engine (it has not been started in more than two weeks), you must press this switch to bring fuel from the tank
to the fuel pump. This rocker type switch springs back into its original position when you release it.
Start/Stop Switch: To crank and start the engine,
hold this switch at its START position. Release the switch when the engine starts. To stop an operating engine, place the switch in its STOP position. The switch center position is the RUN position.
15 amp Fuse: Protects the engine DC control
circuit against electrical overload. If the fuse ele ment has melted open due to overloading, the en gine cannot be cranked. If you must replace it, use only an identical 15 amp replacement fuse.
Line Breakers: Protects generator’s AC output
circuit against overload, i.e., prevents unit from exceeding wattage/amperage capacity. NP-50G has one 20 amp breaker and one 30 amp breaker.
NOTE: If your "Q" Series generator has been recon
nected for dual voltage AC output (120/240 volts), you can install line breakers having an amperage rating that is different than stated above. The replacement line breakers consist of two separate breakers with a con necting piece between the breaker handles (so that both breakers will operate at the same time). If the unit is reconnected for dual voltage, it is no longer RVIA listed.
START
FUSE
ISA
MAIN
BREAKER
<0
©
GENERAC
RV.
GENERATOR
GEN. RUN
STOP START
Figure 3Optional Remote Panel (Model 9042)
AUTOMATIC CHOKE
The engine is equipped with an automatic choke that consists of two main components—choke solenoid and prechoke.
Choke Solenoid: During engine cranking (start/stop switch at START), a solid state choke module signals the choke solenoid to actuate and cycle (choke on/choke off) until engine starts. The choke solenoid thus opens and closes the carburetor choke valve only
when the engine is cranking. When the engine starts,
the choke cycling stops. Prechoke: The choke system also has a temperature
sensitive metal strip that adjusts the choke valve angle according to ambient temperatures (i.e. in cold ambient temperatures the choke valve closes more). Once the
engine starts, an element heats the temperature-sensi tive strip to a normal operating condition, opening the choke valve. This may take about 3 minutes in cooler weather.
jj
STOP
FUEL
PRIMER
Figure 2Typical Control Panel
OPTIONAL REMOTE START/STOP PANEL
Optional remote mounted panels are available which
permit you to crank and start the generator from any
convenient location in the industrial vehicle. Figure 3
shows the Model 9042 remote panel which includes (a) start/stop switch and (b) a generator run lamp.
You can also order Model 9043, a remote panel which
includes the (a) start/stop switch, (b) the generator run
lamp and (c) an hourmeter. The hourmeter provides a continuous indication of engine-generator operating time. Use the hourmeter for checking off periodic main tenance requirements on the unit.
BEFORE STARTING THE ENGINE
IMPORTANT: INSTRUCTIONS AND INFORMATION IN THIS MANUAL ASSUME THE GENERATOR HAS BEEN PROPERLY INSTALLED, CONNECTED, SER
VICED, TESTED AND ADJUSTED BY A OUALIFIED
INSTALLATION TECHNICIAN OR INSTALLATION
CONTRACTOR.
Installation: Generator installation must have been properly completed so it complies with all applicable codes, standards and regulations and with the manufacturer’s recommendations.
Engine Lubrication: Have engine crankcase properly serviced with recommended oil before starting. Refer to "Maintenance“ and "Specifica tions” sections for oil servicing procedures and rec ommendations.
CAUTION: Any attempt to crank or start the engine before you have properiy serviced it with the recom mended oii will result in an engine failure.
-6-
Fuel Supply: The engine must have adequate
supply of proper fuel to operate. Before starting, check that sufficient fuel is available.
NOTE: On some installations, the generator en
gine may “share" the vehicle’s gasoline fuel tank with vehicle engine. Some installations may pro vide separate fuel tanks for generator and vehicle engine.
Cooling and Ventilating Air: Air inlet and outlet
openings in the generator compartment must be open and unobstructed for continued proper oper ation. Without sufficient cooling and ventilating air flow, the engine-generator quickly overheats which causes it to quickly shutdown. Overheating could also damage the unit or your vehicle.
Engine Exhaust Gases: Before starting the gen
erator engine, you should be sure there is no way for exhaust gases to enter the vehicle interior and
endangering people or animals. Close windows, doors and other openings in the vehicle that, if open,
might permit exhaust gases to enter the vehicle.
DANGER: THE GENERATOR ENGINE GIVES
OFF DEADLY CARBON MONOXIDE GAS THROUGH ITS EXHAUST SYSTEM. THIS DAN
GEROUS GAS, IF BREATHED IN SUFFICIENT CONCENTRATIONS, CAN CAUSE UNCON
SCIOUSNESS OR EVEN DEATH. DO NOT OPER ATE THE GENERATOR IF ITS EXHAUST SYSTEM
IS LEAKING OR HAS BEEN DAMAGED. SYMP
TOMS OF CARBON MONOXIDE POISONING ARE
(A) INABILITY TO THINK COHERENTLY, (B) VOMITTING, (C) TWITCHING MUSCLES, (D) THROBBING TEMPLES, (E) DIZZINESS, (F)
HEADACHE, (G) WEAKNESS AND SLEEPINESS. IF YOU FEEL ANY OF THESE SYMPTOMS, MOVE INTO FRESH AIR IMMEDIATELY. IF SYMPTOMS PERSIST, GET MEDICAL HELP.
STARTING
IMPORT ANT: Read the vehicle manufacturer’s instruc tions. The owner/operator should become familiar with the vehicle in which this generator is installed. Differ ences exist between vehicles. For example, some ve hicles may use a transfer switch to isolate dockside power from the generator, while other vehicles may use an isolating receptacle. Some vehicles may be equipped with a DC converter which allows the gener ator to power certain DC lighting and other DC loads.
To crank and start the generator engine, proceed as follows;
1. Turn CFF electrical loads, using whatever means provided in your vehicle (such as a main line circuit breaker or transfer switch.
NOTE: If you start the engine with start/stop switch on
the generator control panel, turn CFF loads by setting the panel’s main breakers to their "CFF“ or “CPEN" positions. Electrical load circuits will be turned CN after the generator has started, stabilized and warmed up.
2. If you have not started the engine in more than two weeks, press the Fuel Pump Primer switch and hold
it for about 30 seconds to activate the automatic shut-off function. However, if the engine is warm, skip Step 2.
3. To crank and start the engine, hold the start/stop switch at START. Release the switch when the engine starts.
CAUTION: If the engine does not start after it has
been cranking for 15 seconds, release the start/stop
switch and try again. Holding the switch for longer than 15 seconds can damage the starter motor.
4. Let the engine run at no-load for a few minutes to stabilize and warm up the engine.
5. Turn CN electrical loads, using whatever means provided (such as a main circuit breaker or transfer switch).
STOPPING THE GENERATOR
1. Turn CFF all electrical loads, using whatever means provided (such a main circuit breaker or
transfer switch).
2. Let the generator run at no-load for a few minutes, to stabilize internal engine-generator tempera tures.
3. Press STCP on the start/stop switch. The engine will come to complete stop.
APPLYING LOADS TO GENERATOR
When applying electrical loads to the generator, ob serve these guidelines:
Before applying electrical loads, let the generator stabilize and warm up for a minute or two.
DC NCT overload the generator.
Letting Engine Stabilize: The generator supplies cor
rect rated frequency and voltage only at the proper governed speed. Some electrical appliances may be extremely sensitive to voltage and frequency. Incorrect frequencies and/or voltages can damage those appli ances.
If electrical loads are applied at reduced operating speeds, such loads imposed on the engine when suffi cient power is not available may shorten engine life.
Never turn CN electrical loads until after the generator engine has started and stabilized CN-speed.
-7-
Do Not Overload the Generator: You can read the rated wattage/amperage capacity of your generator on the generator data plate (see 'Identification Record" on Page 1).
Applying electrical loads in excess of the unit’s rated capacity can bum out the unit and anything connected to it. Also, overloading trips main circuit breakers.
To avoid overloading, add up the wattage of all con nected electrical lighting, appliance, tool and motor loads. This total should not be greater than the generator’s rated wattage capacity.
• Most lighting, appliance, tool and motor loads indi cate their reouired watts on their nameplate or data plate. For light bulbs, simply note the wattage rating of the bulb.
WATTAGE REFERENCE GUIDE
If a load does not show its rated wattage, multiply that load’s rated VOLTS times AMPS to obtain
WATTS.
Induction type motors (such as those that run the vehicie’s furnace fan, refrigerator, air conditioner, etc.) need about 2-1/2 times more watts of power for starting than for running (for a few seconds during motor starting). Be sure to allow for this when connecting electrical loads to the generator. Rrst, figure the watts needed to start electric motors in the system. To that figure, add the running wattages of other items that will be operated by the generator.
Do not apply heavy electrical loads for the first two or three hours of operation.
RUNNING
WATTS *Air Conditioner (12,000 Btu) Battery Charger (20 amp)
.................................
.......................................
1700
500
Belt Sander (3').......................................................1000
Chain Saw Circular Saw (6-12/")
..............................................................
....................................
800 to 1000
1200
Coffee Maker..........................................................1000
‘Compressor (1 HP)
...............................................
2000
‘Compressor (3/4 HP).............................................1800
‘Compressor (1/2 HP).....................................^
......
1400
Curling Iron...............................................................700
‘Deep Freeze............................................................500
Disc Sander (9").....................................................1200
Edge Trimmer...........................................................500
Electric Nail Gun Electric Range (one element) Electric Skillet
....................................................
................................
....................:....................................
1200 1500
1250
‘Furnace Fan (1/3 HP)............................................1200
Hair Dryer...............................................................1200
Hand Drill (Г) Hand Drill (1/2')
..........................................................
...........................................
750 to 1000
1100
Hand Drill (3/8")........................................................500
Hand Drill (1/4")...................................................... 250
Hedge Trimmer Impact Wrench ‘Jet Pump
........................................................
.........................................................
.................................................................
450 500 800
RUNNING
WATTS
Lawn Mower
Light Bulb.......................................................................100
Microwave Oven............................................................700
‘Milk Cooler..................................................................1100
Oil Burner on Furnace
Oil Rred Space Heater (140,000 Btu)............................400
Oil Rred Space Heater (85,000 Btu)..............................225
Oil Rred Space Heater (30,000 Btu)..............................150
‘Paint Sprayer, Airless (1/3 HP).....................................600
Paint Sprayer, Airless (handheld)..................................150
Radio...................................................................
‘Refrigerator
Slow Cooker..................................................................200
‘Submersible Pump (1-1/2 HP)....................................2800
‘Submersible Pump (1 HP)
‘Submersible Pump (1/2 HP).......................................1500
Sump Pump...................................................................600
‘Table Saw (10") Television
Weed Trimmer................................................................500
‘ Allow 2-1/2 times the listed watts for starting these devices.
..............................................................
...................................................
................................;.................................
......
....................................2000
.........................
..........................................................
.................
1750 to 2000
200 to 500
1200
300
50 to 200
600
-8-
This section discusses some of the engine protective devices, overload protection and breaking in a new generator.
AUTOMATIC LOW OIL PRESSURE
SHUTDOWN
The engine is equipped with a normally-closed (N.C.) oil pressure switch (Figure 4). Engine oil pressure holds the switch open during cranking and operation. Should oil pressure drop below about 2-6 PSI, the switch con
tacts close and the engine automatcially shuts down.
Figure 4Switches for Enghe Safety Shutdown
ADDITIONAL INFORMATION
OVER VOLTAGE PROTECTION
A solid state voltage regulator (Rgure 6) controls the generator’s AC output voltage. This regulator supplies an excitation current to the rotor. By regulating the rotor’s excitation current, the strength of its magnetic field is regulated and, in turn, the voltage delivered to connected electricaJ loads is controlled. When the AC frequency is 60 Hz, voltage is regulated at 120 volts (voltage-to-frequency ratio is 2-to-1).
HIGH TEMPERATURE SHUTDOWN
An oil temperature switch (Figure 4) with normally-open
(N.O.) contacts is mounted near the oil filter. If oil temperature were to exceed about 284®F (140“C), the switch contacts close and the engine shuts down.
FIELD BOOST
The Controller Circuit Board houses a field boost diode and resistor which are not part of the automatic choke circuit. These two components are part of a "field boost" circuit (Figure 5). During engine cranking only, a posi tive DC (battery) voltage is delivered through the diode,
resistor, brushes and slip rings, and to the generator
rotor. Application of this voltage to the rotor "flashes the field’ whenever it is started. Hashing of the field each time the generator starts makes sure that a sufficiently
strong magnetic field is available to produce the re
quired "pick up" voltage in the stator windings.
The voltage regulator also incorporates a "voltage surge
protection circuit." This circuit prevents troublesome
surges in the generator AC ou^ut voltage. Voltage
surge is a common cause of damage to electronic equipment.
-9-
Loading...
+ 25 hidden pages