Generac Power Systems 53187 User Manual

m
Miinual Part No. 05580

SERVICE

MANUAL

NP and IM Series
RECREATIONAL
VEHICLE &
NDUSTRIAL
AC GENERATORS
Liquid-Cooled Diesel Engine Models
CORPORATION
Issued- 01A>4/93
*P. O. Box 8 *Waukesha, Wisconsin 53187
Printed in U.S.A.

IMPORTANT SAFETY NOTICE

Proper service and repair is important to the safe, economicai and reliabie operation of ali recreationai vehicie and industrial mobile generators. Troubleshooting, testing and servicing procedures recommended by Generac and described in this manual are effective methods of performing such operations. Some of these operations or proce dures may require the use of specialized equipment. Such equipment should be used
when and as recommended.
It is important to note that the manual contains various DANGER, CAUTION and NOTE blocks. These should be read carefully in order to minimize the risk of personal injury or to prevent improper methods or practices from being used which could damage equipment or render it unsafe. These DANGER, CAUTION and NOTE blocks are not exhaustive. Generac could not possibly know, evaluate and advise the recreational vehicle trade of all conceivable ways in which operations described in this manual might be accomplished, or the possible hazardous consequences of each way. Consequently, Generac has not taken any such broad evaluation. Accordingly, anyone who uses any troubleshooting, testing or service procedure that is not recommended by Generac must first satisfy himself that neither his nor the equipment’s safety will be jeopardized by the procedure or method he selects.
TABLE OF CONTENTS
#
SERVICE
MANUAL
NP and IM Series
RECREATIONAL
VEHICLE &
INDUSTRIAL
MOBILE
AC
PART
TITLE
THE REVOLVING FIELD AC GENERATOR
ENGINE MECHANICAL
ENGINE LUBRICATION AND COOLING
SYSTEM
ENGINE FUEL SYSTEM
ENGINE ELECTRICAL SYSTEM
ELECTRICAL DATA
GENERATORS
Liquid-Cooled
Diesel Engine Models
Parti
THE REVOLVING
FIELD
AC
GENERATOR
NP and IM Series
RECREATIONAL
VEHICLE &
INDUSTRIAL
MOBILE
SECTION
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8
1.9
TABLE OF CONTENTS
TITLE
Introduction
How a Generator Works
Major Components
(Units with 15 inch Stator)
Major Components
(Units with 10 Inch Stator)
Introduction to Troubleshooting
Troubleshooting
(Units with 15 Inch Stator)
Troubleshooting
(Units with 10 Inch Stator)
Insulation Resistance Tests
Operational Tests & Adjustments
AC GENERATORS
Liquid-Cooled Diesel Engine Models
PARTI
THE REVOLVING FIELD AC GENERATOR

INTRODUCTION

SECTION 1.1
INTRODUCTION
Section 1.1
Service Manual Familiarization
This SERVICE MANUAL is divided into six (6)
PARTS. Each PART consists of two or more SEC
TIONS. In turn, each SECTION is divided into SUB
SECTIONS.
At the front of the manual is a main TABLE OF
CONTENTS divider page which lists the titles of Parts
1 through 6.
Each PART of the manual is also identified by a
divider page which Identifies the SECTIONS that make
up that PART.
PMes are numbered so as to identify the PART and SECTION, as well as the specific page number. For example, "Page 2.1-3" indicates Page 3 of Part 2, Section 1. This type of numbering system permits indi vidual Sections of the manual to be kept current without affecting the entire manual.
Contents of Manual
Part 1 - The Revolving Field AC Generator
Section 1.1- Introduction Section 1.2- How a Generator Works Section 1.3- Major Components (Units with 15 inch Stator) Section 1.4- Major Components (Units with 10 inch Stator) Section 1.5- Introduction to Troubleshooting Section 1.6- Troubleshooting (Units with 15 inch
Stator) Section 1.7- Troubleshooting (Units with 10 inch
Stator)
Section 1.8- Insulation Resistance Tests
Section 1.9- Operational Tests & Adjustments
Part 2- Engine Mechanical
Section 2.1- Engine Specifications & Charts Section 2.2- General Information Section 2.3- Engine Disassembly Section 2.4- Disassembly and Inspection Section 2.5- Engine Reassembly
Part 3- Engine Lubrication & Cooling System
Section 3.1- Engine Lubrication System Section 3.2- Water Pump and Thermostat Section 3.3- Cooling and Ventilating Air Section 3.4- Periodic Maintenance
Part 4- Engine Fuel System
Section 4.1- Introduction to the Diesel Fuel System Section 4.2- Fuel Pump
Section 4.3- Governor
Section 4.4- Fuel Injection Pump Section 4.5- Fuel Nozzles and Holders
Part 5- Engine Electrical System
Section 5.1- Introduction to DC Control Systems Section 5.2- Engine Cranking System Section 5.3- Battery Charge System Section 5.4- Preheat System Section 5.5- Engine Protective Systems Section 5.6- Remote Radiator Fan (Model 9319) Section 5.7- Remote Panels Section 5.8- Troubleshooting Row Charts Section 5.9- Troubleshooting Test Procedures
Part 6- Electrical Data
Page 6.1-1- Resistances of Rotors & Stators Page 6.1-1- Index to Wiring Diagrams and Eiectrical Schematics
Identifying Units By Stator Diameter
Throughout the Manual, generators are identified as having either a "15 inch" ora "10 inch" stator. These numbers refer to the DIAMETER of the stator can laminations. See Figures 1 and 2 on next page.
In addition to the diameter and construction of the
stator assembly, the following differences exist be tween units with 10 inch stator and those having a 15 inch stator:
1. Units with 15 inch stator laminations are equipped
with a Part No. 67680 Voitage Regulator.
a. This type of Voltage Regulator mounts three advi sory lamps (LED’s) which greatly simplify trouble shooting. b. The 67680 R^ulator requires a sensing voltage of 240 volts AC. To provide the required 240 volts, a step-up transformer (120 to 240 VAC) is used.
2. Units with 10 inch stator laminations are equipped with a Part No. 81918 Voltage Regulator.
a. The 81918 Regulator mounts a single lamp (LED) which remains on as long as sensing voltage is
available. b. The 81918 Regulator requires a sensing voitage of 120 volts AC and the step-up transformer is NOT required.
Three Different Engine DC Control Sys
tems
The NP/IM series generators maybe equipped with
any one of three different kiinds of engine DC control systems. For convenience, the three different DC sys tems have been arbitrarily identified as Type 1, Type 2 and Type 3.
Refer to Part 5. "ENGINE ELECTRICAL SYS
TEM", for a description Type 1, 2 and 3 DC control systems.
PAGE 1.1-1
SECTION 1.1 INTRODUCTION
PARTI
THE REVOLVING FIELD AC GENERATOR
Figure 2. Typical 10 Inch Stator
PAGE 1.1-2
PARTI
THE REVOLVING FIELD AC GENERATOR

HOW A GENERATOR WORKS

SECTION 1.2
HOW A GENERATOR WORKS
1
Section i.2
It has long been known that a relationship exists
General
between magnetism and electricity. The revolving field generator (or alternator) depends on this relationship
for its operation. In order to diagnose problems and
repair a generator, the service technician must under
stand this relationship.
Why Generators Produce Electricity.
Generators produce an electrical current flow be
cause of the following laws of magnetic induction:
□ When a magnetic field is moved so that it cuts across
a conductor, a voltage and current flow are induced
into the conductor.
□ When current flows through a conductor, a magnetic
field is created around that conductor.
MAGNETIC FIELD CREATES A VOLTAGE;
See Figure 1. When a wire, or coil of wire, is moved
through a magnetic field, an electromotive force (EMF)
or voltage is induced into the wire. Conversely, move ment of the magnetic field so that its lines of flux cut across the wire will induce a voltage into the wire. If the ends of the wire are connected to form a complete circuit, current will flow in the wire. The direction in
which the current flows depends on the polarity of the
magnetic field and the direction in which the magnet is moved.
11
Z-
oCOIi
K
11
Figure 1. Magnetism Creates Electricity
Figure 2. Current Flow Creates a Magnetic Field
------
CURRENT FLOW CREATES A MAGNETIC FIELD:
See Rgure 2. Current flow through a wire or coil of
wire will create a magnetic field around the wire. The
strength of the magnetic field depends on the amount of current flow and the number of loops or coils in the
wire. The direction (polarity) of the magnetic field de
pends on the direction of current flow through the wire.
A Simple AC Generator
See Figure 3. In the simple generator shown, the
revolving magnetic field (Rotor) is a permanent mag net. As the magnet rotates, its magnetic lines of flux cut across a stationary coil of wire called a STATOR. If the stator circuit is completed (by adding a load such as the light bulb), current will flow through the circuit.
A More Sophisticated Generator
In Figure 4, direct current (DC) is delivered to the ROTOR coil through CARBON BRUSHES and SLIP RINGS, to create a magnetic field around the ROTOR. The greater the current flow through the ROTOR wind ings, the stronger the magnetic field around the ROTOR. The ROTOR’S magnetic field cuts across the stationary STATOR windings, to induce a voltage into those windings, with the induced voltage proportional to the strength of the ROTOR’S magnetic field.
STATOR
Û. T 1«V.
üэ”r^
¿»V.
< o
z
UJ-
a.
oc
u 3
ou
Figure 4. A More Sophisticated Generator
BRUSHES
RINGS
PAGE 1.2-1
SECTION 1.2 HOW A GENERATOR WORKS
Operational Analysis- Units with 10 inch Stator Laminations
NOTE: See "IDENTIFYING UNITS BY STATOR DIAMETER" on Page 1.1-1.
PARTI
THE REVOLVING FIELD AC GENERATOR
1
Generator Operation may be briefly described as
follows:
CZl The ROTOR is attached to the engine PTO shaft
and rotates at the same speed as the engine.
□ As the Rotor turns, its magnetic lines of flux cut
across the stationary coils of (a) a stator excitation winding and (b) dual stator AC power windings. A voltage is induced into these stationary windings.
□ Current flow from the Stator excitation winding is
delivered to the Voltage Regulator as unregulated alternating current.
□ Current flow from the Stator AC power windings is
delivered to connected electrical loads.
□ Sensing leads deliver a signal of ACTUAL power
winding output voltage to the Voltage Regulator,
from the Stator AC power windings.
□ The Voltage Regulator electronically compares the
ACTUAL power winding voltage to a REFERENCE voltage which was pre-set.
□ If the ACTUAL power winding voltage is less than the
Regulator’s REFERENCE voltage. Regulator action will (a) change the excitation winding output to direct current (DC), and (b) increase the excitation current flow to the Rotor.
□ If the ACTUAL power winding voltage is more than
the Regulator’s REFERENCE voltage, regulator ac tion will (a) change the excitation current to direct current, and (b) decrease excitation current to the
Rotor.
□ The regulated direct current flow to the Rotor is
delivered via brushes and slip rings.
□ A regulated voltage is induced into the Stator AC
power windings as the Voltage Regulator acts to
maintain an ACTUAL voltage as close as possible to
an adjusted REFERENCE voltage.
A = EXCITATION WINDING B = STATOR AC POWER WINDING C = STATOR AC POWER WINDING CB1 = MAIN CIRCUIT BREAKERS
CB4 = EXCITATION CIRCUIT BREAKER TP = THERMAL PROTECTOR
PAGE 1.2-2
Figure 5. Operating Diagram- Units with 10 Inch Stator Laminations
PART 1 THE REVOLVING FIELD AC GENERATOR
Operational Analysis- Units with 15 Inch Stator Laminations
Some differences exist between generator models
having a 10 inch diameter stator and those with a 15 inch diameter Stator. You may wish to review "IDENTI FYING UNITS BY STATOR DIAMETER" on Page 1:1-
1.
Figure 6 is an Operating Diagram for NF eries
generators with a 15* inch diameter stator. T units are equipped with a Part No. 67680 voltagi n re­which requires 240 volts AC sensing. Tf ram,
SENSING TRANSFORMER serves to itor’s stator’s line-to-neutral sensing voltage to 24 ts.
SECTION 1.2
HOW A GENERATOR WORKS
1
Figure 7. Voltage Regulator Part No. 67680
m
A = EXCITATION WINDING B = STATOR AC POWER WINDING C = STATOR AC POWER WINDING CB1 = MAIN CIRCUIT BREAKERS CB4 = EXCITATION CIRCUIT BREAKER TP = THERMAL PROTECTOR
Operating Diagram- Units with 15 Inch Diameter Stator Laminations
PAGE 1.2-3
SECTION 1.2
HOW A GENERATOR WORKS
PARTI
THE REVOLVING FIELD AC GENERATOR
1
PAGE 1.2-4
PARTI
THE REVOLVING FIELD AC GENERATOR
MAJOR COMPONENTS
(UNITS WITH 15 INCH DIAMETER STATOR)
SECTION 1.3- MAJOR COMPONENTS
(UNITS WITH 15 INCH STATOR)
1
Section 1.3
ITEM
QTY DESCRIPTION
1
2 4 3 4 1 Rear Bearing Carrier 5 6 1 7 1
8 10 9 6
10 4 Hex Head Flanged Bolt
11 4 Screw
12 13 1 Flexible Coupling 14
15 1 Flywheel 16
17 1 Air Ring Baffle 18 4 Vibration Mount
19 6
20 2 Socket Head Capscrew
4 Taptite Screw
4 Stud
1
4
1
4 Hex Head Capscrew
Taptite Screw
Rotor Bearing
Rotor Assembly
Stator Assembly
Hex Head Capscrew
Lockwasner
Lockwasher
Fan Ring
Flatwasher
»
ITEM
21 22 23 24 25 26 27 8 Lockwasher
28 29
30 31
32 4 33
34 4 35
36 37 1 38
39
40
QTY
■ 1
DESCRIPTION
1
1
4' 2 2
2
6
4 2
2
4
1
1
4 2
Battery Cable Boot
Starter Motor
Engine Adapter
Hex Head Capscrew
Vibration Isolator
Flatwasher
Hex Head Screw
Hex Nut
Brush
Brush Holder
Screw
Brush Cover
stud
Flanged Nut
Red Starter Cable
Lockwasher
Hex Nut
Lockwasher
Hex Head Capscrew
Figure 1. Exploded View of AC Generator with 15 Inch Stator
PAGE 1.3-1
SECTION 1.3- MAJOR COMPONENTS (UNITS WITH 15 INCH STATOR)
1
AC Generator Disassembly
BRUSH ACCESS AND REMOVAL Figures 1 & 2);
See Rgure 1. Remove the TAPTITE SCREWS
(Item 2) that retain the two BRUSH COVERS (Item 33) to the REAR BEARING CARRIER (Item 4). Remove the BRUSH COVERS (Item 33) to gain access to the
BRUSH HOLDERS (Item 31).
See Figure 2, below. Remove Wires No. 1 and 4
from the BRUSHES in both BRUSH HOLDERS. Re
move the TAPTITE SCREWS that retain the BRUSH
HOLDERS to the REAR BEARING CARRIER. Re move both BRUSH HOLDERS, along with the
BRUSHES
PARTI
THE REVOLVING FIELD AC GENERATOR
To remove the FLEXIBLE COUPLING (Item 13)
from the ROTOR (Item 6), remove four HEX HEAD FLANGED BOLTS (Item 10).
FLYWHEEL REMOVAL (Figure 1):
Remove four SCREWS (Item 11) and
LOCKWASHERS (Item 12). Then, remove FLY WHEEL (Item 15). If desired, the FAN RING (Item 14) can be removed by removing HEX HEAD CAPSCREWS (Item 8) and LOCKWASHERS (Item 9).
ENGINE ADAPTER REMOVAL (Figure 1);
To remove AIR RING BAFFLE (Item 17), remove
CAPSCREWS (Item 8) that retain It to the ENGINE
ADAPTER (Item 23).
Support the engine and remove all fasteners that
retain the ENGINE ADAPTER to the BASE ASSEM BLY. Remove HEX HEAD CAPSCREWS (Item 40) and LOCKWASHERS (Item 27). Finally, remove the EN GINE ADAPTER.
Components Inspection and Testing
REAR BEARING CARRIER REMOVAL (Figure 1):
Remove HEX NUTS (Item 29), LOCKWASHERS (Item 27) and STUDS (Item 3) that retain the REAR BEARING CARRIER (Item 4). To free the REAR BEARING CARRIER (Item 4) from the ROTOR BEAR ING (Item 5), use a soft mallet to tap around the outer
periphery of the BEARING CARRIER. Continue tap ping until the BEARING CARRIER is free of the bear
ing.
STATOR REMOVAL (Figure 1):
The STATOR (Item 7) is "sandwiched" between the ENGINE ADAPTER (Item 23) and the REAR BEARING
CARRIER (Item 4). Carefully remove the STATOR
(Item 7). DO NOT PERMIT THE STATOR TO DROP
OR BUMP THE ROTOR DURING REMOVAL.
ROTOR REMOVAL (Figure 1):
Remove the four FLANGED NUTS (Item 35) from STUDS (Item 34). The ROTOR (Item 6), with FLEXI BLE COUPLING (Item 13) attached, can now be pulled
free of the FLYWHEEL (Item 15).
GENERAL;
Following disassembly, generator components
should be cleaned, dryed and inspected or tested.
Never reassemble a generator having defective parts.' Keep major parts separated and keep the mounting hardware along with the parts they are used with. Store
parts in a clean, dry area where condensation, dirt, or
moisture will not damage them.
REAR BEARING CARRIER:
The Rear Bearing Carrier (Figure 1, Item 4) is an aluminum casting. Clean the casting and blow dry with air. Inspect carefully for cracks, obvious damage. An
insert has been pressed into the Carrier center bore, to accommodate the Rotor Bearing. Replace the Rear Bearing Carrier if the center bore diameter is not within
the following dimensions:
BEARING CARRIER CENTER BORE
2.9527-2.9533 Inches (74.999-75.014mm)
ROTOR BEARING:
The rotor bearing is a prelubricated and sealed ball
bearino that requires no additional lubrication for the life of the bearing. Spin the Rotor bearing by hand and check it for binding, seizing, roughness, etc. If the bearing is defective, it must be replaced.
The bearing may be removed from the Rotor shaft
using a bearing puller. A new bearing can then be pressed onto the shaft. Exert pressing force on the bearing inner race only- NEVER on the bearing outer/'"~^^ race.
PAGE 1.3-2
PART 1
THE REVOLVING FIELD AC GENERATOR
SECTION 1.3- MAJOR COMPONENTS
(UNITS WITH 15 INCH STATOR)
1
Components Inspection and Testing
(Continued)
ROTOR ASSEMBLY;
Clean the Rotor with dry, low pressure air (25 psi
or less). If the slip rings are dirty or tarnished, clean them with fine sandpaper. Inspect the Rotor for dam age.
Check the resistance of Rotor windings with a
volt-ohm-milliammeter (VOM). Refer to Section 1.6,
"TROUBLESHOOTING (UNITS WITH 15 INCH STA
TOR)".
Use an Insulation resistance tester, megohmmeter,
or Hi-Pot tester to test the resistance of Rotor insula tion. See Section 1.8,
TESTSr.
If the Insulation resistance is low, dry the Rotor with
warm, dry air. DO NOT EXCEED 185* F. (85’ C.). If
resistance is still low after drying, replace the Rotor
Assembly.
STATOR ASSEMBLY:
Clean the Stator Assembly in the same manner as
the Rotor was cleaned. Inspect ther Stator for damage.
Use a VOM to check Stator windings resistance
(see Section 1.6).
Check the insulation resistance of Stator windings,
as outlined in Section 1.8.
FLEXIBLE COUPLING:
Carefully inspect the Flexible Coupling (Figure 1, Item 13) for damage, cracking. Check mounting holes on couplino for elongation and damage. Replace the Coupling, if it is damaged.
FAN RING AND AIR RING BAFFLE:
Inspect the Fan Ring (Figure 1, Item 14) and the
Air Ring Baffle (Item 17) for damage, cracking. Re place, if damaged.
•INSULATION RESISTANCE
Reassemble the generator In the reverse order of
Generator Reassembly
disassembly. The reassembly process requires a great deal of care. Components must be properly aligned and
retained. Tighten all fasteners to the recommended
torque values (see Part 6, "SPECIFICATIONS AND
CHARTS"). Following reassembly, perform an opera tional test of the unit (Section 1.9).
Components In Generator Control Panel
INTRODUCTION:
Rgure 3 (next page) Is an exploded view of the generator control panel. The Panel houses or mounts several Important AC generator components, as well as components that are part of the engine DC electrical systems.
ENGINE ELECTRICAL SYSTEM COMPONENTS;
The Control Panel houses the following compo
nents that are part of the engine electrical system. For Information on these components, refer to Part 5 of this Manual, "ENGINE ELECTRICAL SYSTEM".
□ The 14 and 30 amp Fuses (Items 4 and 5). □ The 10 amp DC Circuit Breaker (Item 6). □ The two 12 volts DC Relays (Items 7 and 8). □ The DC Voltage Regulator (Item 13). □ Engine Control Circuit Board (Item 39).
□ Hourmeter (Item 23).
□ Start-Stop Switch (Item 24).
□ Preheat Switch (Item 25).
AC GENERATOR COMPONENTS:
The following components, housed in the control
panel, are major generator components and will be discussed in this Section and Sub-Section.
□ Excitation Circuit Breaker (Item 11). □ AC Voltage Regulator (Item 14). □ The Sensing Transformer (Item 15). □ AC Circuit Breaker (Item 16).
FLYWHEEL;
Clean the flywheel. Inspect for damage, cracks,
wear, etc. Replace, if necessary.
ENGINE ADAPTER;
Clean the Engine Adapter (Figure 1, Item 23).
Inspect the Adapter carefully for damage, wear, crack
ing, etc. Replace, if necessary.
BRUSH HOLDERS AND BRUSHES:
Inspect Brush Holders and Brushes for damage, cracking, chipping, excessive wear, etc. Replace any defective or damaged part. Brushes must always be
replaced in complete sets.
In addition to the above components, a THERMAL
PROTECTOR is physically imbedded in the wire wind ings of the Stator Assembly. A discussion of this com ponent will also be included in this Section.
EXCITATION CIRCUIT BREAKER;
The excitation circuit breaker is housed in the con
trol panel and connected in series with .the Stator Excitation winding output to the Voltage Regulator.
If this Breaker should open, loss of unregulated
excitation current to the Regulator will occur. The Reg ulator will then shut down and loss of regulated excita tion current to the Rotor will occur. Generator AC output will then be proportional to Rotor residual magnetism only (about 2-7% of rated voltage).
PAGE 1.3-3
SECTION 1.3- MAJOR COMPONENTS (UNITS WITH 15 INCH STATOR)
PARTI
THE REVOLVING FIELD AC GENERATOR
1
ITEM
QTY
1 2* 3* 1 4* 5*
6*
r 1
8* 9 10 1
11** 1
12 13*
14“ 15“
16 17
18 19 20 1 21 1 22 2
* See Part 5,
2
1 1
1 1
1 1
EXCITATION CIRCUIT BREAKER 1 1 1 1 1
4 4 1
'* Part of AC generator circuit, Included in this Section.
"ENGINE ELECTRICAL SYSTEM".
DESCRIPTION
Snap Bushing FUSE HOLDER- 30 amp FUSE HOLDER-14 amp
30 AMP FUSE 14 AMP FUSE
10 amp DC Circuit Breaker
12 volts DC RELAY 12 volts DC RELAY
Solderless Lug
90 Conduit Clamp
Control Panel Box DC VOLTAGE REGULATOR AC VOLTAGE REGULATOR
SENSING TRANSFORMER
AC CIRCUIT BREAKER
Pan Head Screw
Lockwasher Lockwasher
Control Panel
Panel Decal
Pan Head Screw
ITEM
23* 1 24* 1 25*
26 2
27
28 29 30 31 32 1 33 34 35 36 37 4
39*
40 41 42 2 44 1 45 46 47 48
QTY
1 2
10
8 8
8 Pan Head Screw
8 8 4
1 6
2
1 4 4 4
DESCRIPTION
HOURMETER
START-STOP SWITCH
PREHEAT SWITCH
Hex Head Capscrew
External Lockwasher
Lockwasher Flatwasher
Hex Head Capscrew
Customer Leeds (Not Shown).
Pan Head Screw
Lockwasher
Hex Nut
Self Tapping Screw
ENGINE CONTROL CIRCUIT
Spacer Tlut
BOARD
Lockwasher
Hex Nut
Hex Head Capscrew
Panel Wiring Harness
Engine Wire Harness
Vibration Dampener
Hex Nut
Flatwasher
Figure 3. Exploded View of Control Panel
/ 13
PAGE 1.3-4
PARTI
THE REVOLVING FIELD AC GENERATOR
Components In Generator Control Panel (Continued)
AC VOLTAGE REGULATOR:
The Voltage Regulator is powered by stator excitation
winding AC output. Approximately 4 to 8 volts is required from that power source to turn the regulator on.
The Regulator is equipped with three (3) lamps
(LED’s or "light emitting diodes). See Figure 5. These lamps are normally on during operation with no faults in the system. The green EXCITATION lamp and the red REGULATOR lamp are both turned on by stator excita tion winding output. If, for any reason, stator excitation winding output were to be reduced, the two lamps would begin to dim. Finally, at some mid-point voltage and current, the two lamps will no longer glow visibly.
SECTION 1.3- MAJOR COMPONENTS
(UNITS WITH 15 INCH STATOR)
1
NOTE: Sensing input to the Regulator Is actually taken
from Hne-to-neutra! stator leads and Is about 120 volts
AC. However, this voltage Is boosted to about 240 volts AC by the action of a sensing transformer.
The following facts apply to Voltage Regulator opera
tion:
1. The Regulator will shut down on occurence of one or
more of the following conditions:
a. Loss of sensing voltage. b. Loss of stator excitation voltage Input to the
Regulator.
c. Loss of circuit reference.
NOTE: The term "circuit reference" refers to voltage
regulator settings. The Regulator "regulates" excitation
winding current flow to the Rotor windings in order to
maintain a sensing (actual) voltage that Is commen surate with a preset "reference" voltage. The reference
voltage is adjustable within a 20 percent range at the Regulator. Voltage regulation Is accomplished by electronically maintaining an ACTUAL voltage that Is
very close to the Regulator's preset REFERENCE volt age.
The yellow SENSING lamp Is powered by sensing
input to the Regulator from the stator AC power wind ings. The brightness of this lamp (LED) will depend on available sensing voltage.
2. During generator operation, all three Regulator lamps should be ON.
a. REGULATOR lamp ON Indicates the Regulator is functioning normally. b. SENSING lamp ON indicates that normal sensing voltage Is available to the Regulator. c. EXCITATION lamp ON Indicates that unregulated excitation winding output Is available to the Regulator.
3. If the red REGULATOR lamp is OUT, a Voltage Regulator fault exists or the Regulator has shut down due to occurence of one or more Regulator shutdown conditions. See Step 1 above for conditions that will result in Regulator shutdown.
a. Expect to see a generator AC output voltage that is commensurate with the Rotor’s residual mag netism. b. Rotor residual magnetism will supply approximate ly 2 to 7 percent of the unit’s rated voltage.
NOTE: "Residual" magnetism Is that magnetism that Is normally always present In the Rotor. The Rotor may be considered a "permanent magnet".
PAGE 1.3-5
SECTION 1.3- MAJOR COMPONENTS
(UNITS WITH 15 INCH STATOR)
1
Components In Generator Control Panel (Continued)
AC VOLTAGE REGULATOR (CONT’D):
4. If the green EXCITATION lamp goes out, loss of stator excitation winding output to the Regulator has occured.
a. Loss of excitation winding output will result in
Regulator shutdown. The red REGULATOR lamp will
then go out, as well. b. Under this condition, look for a generator AC output voltage that is commensurate with residual Rotor magnetism (about 2-7% of rated volts). c. When the REGULATOR and EXCITATION lamps are both out, the excitation circuit from the stator excitation windings to the voltage regulator Is suspect (inclusive).
5. Should the yellow SENSING lamp go out, loss of
sensing voltage to the Regulator has occured.
a. Loss of sensing may cause the Regulator to shut
down. Both the SENSING lamp and the
REGULATOR lamp will then go out. b. Generator AC output voltage will then be commen
surate with Rotor residual magnetism (2-7% of rated volts). c. Look for a fault in the sensing circuit.
6. If all three lamps go out, look for a fault that might cause both sensing and excitation to fail.
a. Look for dirty or corroded slip rings, bad brushes, defective Rotor. b. Look for open circuit in Wires No. 1 and/or 4.
7. If the red REGULATOR lamp flashes, the Regulator’s STABILITY potentiometer requires ad justment.
PART 1
THE REVOLVING FIELD AC GENERATOR
AC CIRCUIT BREAKER:
The AC circuit breaker protects the unit against cur
rent overload by opening the AC output circuit in the event the generator’s current (amperage) capacity is,/'”^
exceeded. The amperage at which the breaker will trip
(open) is the breaker’s trip rating.
SENSING TRANSFORMER:
The Part No. 67680 Voltage Regulator requires a "line-to-line" sensing voltage (240 volts) for proper operation. However, the sensing Is taken from "line-to­neutral" Wires No. 11 and 22 (120 volts). For that reason, the primary coil of a sensing transformer is
connected in series with the sensing leads. The sensing transformer is a "step-up" type. That is, 120 volts AC in its primary coil will induce 240 volts into its secondary coil. It is the secondary coil voltage that is delivered to the regulator as sensing voltage.
The sensing transformer is housed in the generator control panel and is used on generator’s with the Part No. 67680 Voltage Regulator and with 15 inch diameter stator laminations.
The sensing transformer Is shown pictorially and schematically in Figure 6.
PAGE 1.3-6
The AC circuit breaker used on any specific generator
model will depend on the rated current (amperage) capacity of that model.
PART 1
THE REVOLVING FIELD AC GENERATOR
Thermal Protector !
A Thermal Protector is physically imbedded in the wire windings of the Stator and electrically connected In series with the excitation winding output leads to the Regulator. The device is a normally-closed (N.C.),
temperature sensitive switch. The switch contacts will open when stator temperatures exceed a safe level. The switch is self resetting. That Is, it will re-dose when stator temperatures decrease to a safe level.
If the switch contacts should op>en, excitation winding AC output to the Voltage Regulator will be terminated and the Regulator’s green EXCITATION lamp will go out. Since the Regulator cannot op>erate without excita tion winding output, the red REGULATOR lamp will also go out. Generator AC output voltage will then drop to a value commensurate with the Rotor’s residual mag netism.
If the Thermal Protector contacts open during opera
tion due to a stator overtemperature condition, the cause of the overtemperature condition must be found and corrected. High Internal stator temperatures can be caused by any one of the following:
SECTION 1.3- MAJOR COMPONENTS
(UNITS WITH 15 INCH STATOR
1
rings. The direct current (approximately 9-10 volts DC) flows through the Rotor windings, the negative (-) slip ring and brush, and to ground.
Field boost current creates a magnetic field strength
that is additive to the Rotor’s residual magnetism. The
Increased magnetic field strength during engine crank ing provides an early "pickup* voltage In the stator. The Regulator is turned on more quickly and AC output
occurs sooner. In effect, field boost current "flashes the field" on every startup.
Failure of the field boost system nr^y or may not result In a reduction of AC output to that produced by residual Rotor magnetism. If residual magnetism Is adequate to turn the Regulator on and provide the required pickup voltage, the generator will operate normally with or without field boost. However, if residual magnetism Is not adequate, generator AC output will not build and will be comrr^nsurate with Rotor residual magnetism.
D Insufficient cooling air flow into the generator
interior. Look for blockage of cooling air inlet/out­let openings, air openings that are too small, ambient temperatures that are too high, etc.
□ Exceeding the wattage/amperage capacity of the
generator. If the unit is overloaded for a period of time, internal stator temperatures can rise quickly and cause the Thermal Protector contacts to open.
D A shorted condition in the generator stator wind
ings or in an electrical load connected to the generator’s AC output.
The Thennal Protector is not accessible and cannot be removed and replaced. If the device has failed open, it can be bypassed by connecting excitation lead No. 2
to a bypass lead (Wire No. 5). Once the device has been
bypassed, stator overtemperature protection Is no longer available.
Field Boost
When the generator engine Is cranked, direct current (DC) Is delivered to the Rotor windings. The cunent flow is provided by the action of an Engine Control circuit board housed In the control panel and Is delivered to the Rotor via Wire No. 9, a Field Boost Resistor (R2), a Field Boost Diode (D2), Wire No. 4, and the brushes and slip
PART OF CONTROL PANEL WIRING HARNESS
rrSM
1
• 2 3 4
Figure 9. The Field Boost Circuit
DIODE-600V., 6 AMP
RESISTOR-5 WATT. 10 OHMS
DESCRIPTION
HEAT SHRINK
BARREL LUG
PAGE 1.3-7
SECTION 1.3- MAJOR COMPONENTS
(UNITS WITH 15 INCH STATOR)
PARTI
THE REVOLVING FIELD AC GENERATOR
1
PAGE 1.3-8
PARTI THE REVOLVING FIELD AC GENERATOR
MAJOR COMPONENTS
(UNITS WITH 10 INCH STATOR)
SECTION 1.4- MAJOR COMPONENTS
(UNITS WITH 10 INCH STATOR)
1
Section 1.4
l~47.ir>r« description
■ n Rotor Assembly
n
2 3 2
4 1 5 6 7 8 9 10 11 12 2 13 14 15 1
16 1 17 18 6 19 20 1 21 22
1
1
4 16 12
4 Vibration Dampener
1 Stator Assembly 1 Rear Bearing Carrier
4
1
4
4 Capscrew 2
33
Drive Key
Dowel Pin
Blower Housing
Air Outlet Screen
Hex Head Capscrew
Lock Wasner
Flat Washer
Brush Holder
Hex Head Capscrew
Bearing Carrier Gasket
Rame Arrestor 37
Bearing Carrier Cover
Bolt
Lock Washer
Starter Assembly
Socket Head Capscrew
Lock Washer
•i'" -W'
TUFT
23 24 25 26 10
27 12 28 29 30 1 31 32 33 1 34 35 36
38 6 39 2 40 2 42 43 2 44 1 45 1
QTY
9
1
3
1
8
1 1
6 Socket Head Capscrew 1 1 Cooling Fan 1
2 Hex Nut
DESCRIPTION
Ratwasher
Engine Plate
Hex Head Capscrew Hex Head Capscrew
Hex Head Capscrew
Flywheel
Hex Head Capscrew
Spacer
Hex Head Capscrew
Lock Washer
Flexible Coupling
Drive Hub
Starter Solenoid
Hex Head Capscrew
Rat Wasner
Hex Nut
Hex Head Capscrew
DC Voltage Regulator
Starter to Starter Solenoid Ci
Figure 1. Exploded View of Generator with 10 Inch Diameter Stator
PAGE 1.4-1
SECTION 1.4- MAJOR COMPONENTS
^UNnrewmjno^mc^T^OR^^^
1
AC Generator Disassembly
BEARING CARRIER COVER:
Remove four (4) CAPSCREWS (Item 19), FLAT WASHERS (Hem 8), and LOCK WASHERS (Item 7). Then, remove the BEARING CARRIER COVER (Item
16) and the BEARING CARRIER GASKET (Item 14).
PARTI
THE REVOLVING FIELD AC GENERATOR
Remove all four long stator bolts along with washers.
Turn the large boH at center of Bearing Carrier puller until end of bolts is flush wHh the puller. Retain the puller to the Bearing Carrier with original Carrier Cover screws. Turn the large center bolt of puller until the bearing carrier Is free of the Rotor Bearing. Completely remove the Bearing Carrier.
Figure 2. Bearing Carrier Cover Removal
BRUSH HOLDERS AND BRUSHES:
Remove wires from BRUSHES (Item 12). Remove
SCREWS (Item 13) and remove BRUSH HOLDERS (Item 12) with brushes.
REAR BEARING CARRIER:
A bearing carrier puller (Figure 4) can be used to
remove the Rear Bearing Carrier. Retain the puller to the Bearing Caller using the same saews that original ly held the Bearing Carrier Cover.
Remove fasteners that retain the Bearing Carrier to
the mounting rail.
Figure 5. Removal of Mounting Rail Fasteners and
Stator Bolts
STATOR REMOVAL:
CAUTION. Use care when removing the Stator. Do NOT allow It to drop or bump the Rotor during removal.
Free the Stator from the Blower Housing and remove.
See Figure 6.
PAGE 1.4-2
I
PARTI THE REVOLVING FIELD AC GENERATOR
Figure 6. Stator Removal
BLOWER HOUSING REMOVAL:
Remove the capscrews that retain the Blower Hous
ing to the Engine Plate, along with flat washers, lock washers and hex nuts. Note positions of longer and shorter screws, for reassembly.
SECTION 1.4- MAJOR COMPONENTS
(UNITS WITH 10 INCH STATOR)
1
ENGINE PLATE REMOVAL:
Remove starter retaining bolts and remove starter.
Remove bolts that retain the engine plate. Remove the engine plate.
ROTOR REMOVAL;
Remove capscrews and washers that retain the Cou
pling Plate to the Ring Gear. Remove Rotor, Cooling Fan, Drive Hub and Coupling Plate as a unit.
If desired, the Cooling Fan, Drive Hub and Coupling
Plate may be removed from the Rotor.
Components Inspection and Testing
GENERAL;
Follovving disassembly, generator components should be cleaned, dryed and inspected or tested. Never reassemble a generator with defective or damaged parts. Store parts In a dean, dry area.
PAGE 1.4-3
SECTION 1.4- MAJOR COMPONENTS (UNITS WITH 10 INCH STATOR)
Components Inspection
REAR BEARING COVER AND GASKET:
Clean the Beeuing Cover in a suitable non-flammable commercial cleaner. Blow dry with compressed air. Inspect the Cover for obvious damage, clogged air slots, etc. Replace, if necessary. Inspect gasket, replace if damaged or defective.
REAR BEARING CARRIER;
The Rear Bearing Carrier is an aluminum casting.
Clean the casting and blow dry with air. Inspect carefully
for cracks, damage. An insert is pressed into the Bear ing Carrier center bore, to accommodate the Rotor bearing. Use an inside micrometer to check the inside diameter of the insert. Replace the Bearing Carrier if the insert inside diameter is not within the following:
PARTI
THE REVOLVING FIELD AC GENERATOR
J
and Testing (Continued)
the Rotor with dry, heated airfor several hours. DO NOT
EXCEED 185* F. (85* C.). if Insulation resistance is still
low after drying, replace the Rotor Assembly.
FAN AND RING GEAR ASSEMBLY:
The FAN, DRIVE HUB, COUPLING PLATE and RING GEAR are assembled and balanced as a unit. Clean and inspect parts, replace the entire assembly if necessary.
BRUSH HOLDER AND BRUSHES:
Inspect both brush holders and both sets of brushes. Look for cracks, excessive wear, cracks, chipping, etc. Replace any damaged brush holder. Brushes should be replaced as a complete set
2.834-2.836 inches (71.996-72.012mm)
STATOR ASSEMBLY:
Clean the stator can exterior surfaces with a soft brush or cloth. Use clean, dry low pressure air (25 psi maximum) to clean the stator. Use an ohmmeter to test the resistance of Stator AC power and excitation wind ings. Use an insulation resistance tester (megohmmeter or Hi-Pot tester) to check condition of Stator insulation (see Section 1.8). If Stator insulation fails the test, the
Stator may be dried by blowing warm, dry air across it for several hours. DO NOT EXCEED 185* F. (85* C.). If
insulation resistance is still low after drying, replace the
Stator.
BLOWER HOUSING:
Clean with a commercial solvent that is suitable for
use with aluminum. Inspect the Housing carefully for cracks, damage, etc. Replace, if necessary.
ROTOR ASSEMBLY:
Clean with dry, low pressure air (25 psi maximum).
Test Rotor winding resistance with an ohmmeter. Check
Rotor bearing for binding, seizing, roughness. If the
bearing is defective, replace the Rotor assembly. In spect the keyway in the tapered shaft for wear, damage.
If slip rings are dull or tarnished, clean with fine
sandpaper. Use an insulation resistance tester
(megohmmeter or Hi-Pot tester) to test for insulation
breakdown (see Section 1.8). If resistance is low, dry
Inspect brush leads No. 1 and 4. Replace any
damaged or defective brush lead.
Generator Reassembly
Reassemble the generator in the reverse order of disassembly. The reassembly process requires a great deal of care. All components must be properly aligned and retained. Tighten all fasteners to the recommended torque values. Following reassembly, perform an opera tional test of the unit.
Components In Generator Control Panel
INTRODUCTION:
The following AC generator components are
mounted on or housed in the generator control panel:
Voltage Regulator Assembly. □ An AC Circuit Breaker (CB1 and CB2). □ Exdtation Circuit Breaker (CB4). □ A field boost circuit.
In addition to the above AC generator components
housed in the control panel, aTHERMAL PROTECTOR is physicaliy imbedded in the wire windings of the Stator Assembly.
Other components are housed in the control panel,
as well. However, these components are part of the engine's DC control system and will be discussed in PART 5, "ENGINE ELECTRICAL SYSTEM".
PAGE 1.4-4
PARTI
THE REVOLVING FIELD AC GENERATOR
Components in Generator Control Panel (Continued)
SECTION 1.4- MAJOR COMPONENTS
1
THE AC VOLTAGE REGULATOR:
The VoKage Regulator used on units with 10 inch stator is shown In Figure 10. The Regulator has a single red lamp (LED) which will remain on during operation as long as stator AC power winding "sensing* voitage is avaiiabie. Three sets of leads connect to the Regulator
terminals as follows:
D Unregulated AC output from the stator excitation
winding connect to the two terminals indicated by "DPE*.
Sensing (actual) voltage signals from the stator
AC power windings are delivered to the Regulator terminals indicated by "SEN".
Rectified and regulated (DC) current Is delivered
to the Rotor winding from Regulator terminals Indicated by a"+" and
The Regulator provides over-voltage protection. On loss of "sensing", the Regulator will shut down and regulated excitation current to the Rotor will terminate.
A single adjustment potentiometer permits the gener
ator's AC output voltage to be adjusted. Perform this adjustment with the engine running at no-load and with
AC frequency at 62 Hertz (1860 rpm). At 62 Hertz, set the line-to-neutral AC output voltage to 124 volts AC; or the line-to-line AC output voltage to 248 volts AC.
AC CIRCUIT BREAKERS:
Two AC output circuit breakers (CB1 and CB2) are provided, one for each line of the 240 volts AC output circuit. The trip rating of these breakers depends on the rated maximum amperage capacity of the generator. Units rated at 8000 watts (8.0 kW) are equipped with AC breakers rated at 35 amperes.
Schematic
Pictorial
11
SEE FIGURES 4 & 5 ON PAGE 1.5-2 FOR WIRING CONNECTIONS
Figure 11. AC Output Circuit Breakers
EXCITATION CIRCUIT BREAKER (CB4):
An AC circuit breaker, rated 5 amperes, is electrically connected in series with Wires No. 2 and 2A betwen the stator excitation winding and the Voltage Regulator. If the breaker should trip (open) due to an overload, loss of excitation current to the Rotor will occur. Generator AC output voltage will then decrease to a value that is commensurate with Rotor residual magnetism (about 2 to 7% of the unit's rated voltage). The breaker is self resetting and cannot be reset manually.
Figure 12. Excitation Circuit Breaker
PAGE 1.4-5
SECTION 1.4- MAJOR COMPONENTS (UNITS WITH 10 INCH STATOR)
1
Components In Generator Control Panel (Continued)
FIELD BOOST CIRCUIT
During engine cranking, an engine controi circuit board deiivers battery voltage to the Rotor windings. This "Field Boost" current is delivered to the Rotor via Wire 4A, a field boost resistor, and Wire 4. The Field Boost feature provides the following benefits:
□ In effect, field boost current "flashes the field" on
every engine startup. Thus, if Rotor residual magne tism was lost for any reason, it would be restored by the act of "flashing the field" during cranking.
□ Approximately 4-8 volts AC output from the stator
excitation winding is needed to turn the voltage reg ulator on. Reid boost current builds Rotor magnetism early which, in turn, develops voltage early during startup. The result of field boost is an early "pickup"
voltage in the stator windings.
THERMAL PROTECTOR:
Refer to " THERMAL PROTECTOR' on Page 1.3-7.
PARTI
THE REVOLVING FIELD AC GENERATOR
PAGE 1.4-6
PARTI
THE REVOLVING FIELD AC GENERATOR
Section 1.5

INTRODUCTION TO TROUBLESHOOTING

DANGER: GENERATORS PRODUCE EXTREMELY HIGH AND DANGEROUS VOLTAGES. CONTACT WITH LIVE WIRES OR TERMINALS WILL RESULT
IN HAZARDOUS AND POSSIBLY FATAL ELECTRI-
<CAL SHOCK. ONLY PERSONNEL WHO HAVE
BEEN TRAINED IN THE SERVICING AND REPAIR OF RV GENERATORS SHOULD ATTEMPT TO TROUBLESHOOT, TEST OR REPAIR THESE GEN ERATORS.
Tools and Test Equipment
An RV generator service technician shouid have a
weii stocked tool box that is fiiied with a good seiection
of common hand tools. The tool box should contain combination wrenches and socket wrenches in both standard and metric sizes. Also, a good nut driver set is recommended.
SECTION 1.5
INTRODUCTION TO TROUBLESHOOTING
1
Figure 1. Typical Volt-Ohm-Mllllamm eter (VOM)
The following test equipment is recommended:
An accurate volt-ohm-milliammeter (VOM),
preferably a precise digital type.
A good AC frequency meter.
D An insulation resistance tester (megohmmeter or
Hi-Pot tester).
O A load bank or some means of applying a known
electrical load to the generator.
Volt-Ohm>Milllammeter (VOM)
If desired, three separate meters may be used, i.e., a voltmeter, ohmmeter and ammeter. Recommended is an accurate digital type VOM having a ’Diode Check' mode.
The service technician must be familiar with his VOM
and must know how to use it. He must also be familiar
with generator electrical circuits and must be able to
read electrical vriring diagrams and schematics.
Frequency Meter
The generator’s AC output frequency must be known
if engine governed speed Is to be property adjusted. See "ROTOR ROTATIONAL SPEED’ in this section.
Figure 2. One Kind of AC Frequency Meter
Testing Insulation Resistance
Insulation resistance Is a measurement of the In
tegrity of the Insulating materials that separate the electrical windings from the generator’s steel core. This resistance can degrade over time due to contaminants such as dust, dirt, grease and especially moisture.
Information on Insulation resistance test can be found
in Section 1.8, "INSULATION RESISTANCE TESTS'.
PAGE 1.5-1
SECTION 1.5
INTRODUCTION TO TROUBLESHOOTING
Rotor Rotational Speed
"NP" series generators are equipped with a 4-pole Rotor. That is, the Rotor has two south magnetic poles
and two north magnetic poles. A 4-pole Rotor must be operated at 1800 rpm to obtain a 60 Hertz AC output frequency. The following formulas apply when calculat ing frequency, rpm and number of Rotor poles:
Hertz = RPM X No. of Rotor Poles
2x 60
RPM = 2 X 60 X Hertz
No. of Rotor Poles
PART 1
THE REVOLVING FIELD AC GENERATOR
L
A second alternative Is to connect the wiring to supply
120 volts AC only (Figure 5). When this connectior method Is used, a jumper wire must be connected between the two main circuit breakers (CB1 and CB2), as shown.
No. of = Poles
2 X 60 X Hertz
RPM
Voltage and Frequency
The generator's solid state Voltage Regulator will maintain an AC output voltage that is at a fixed ratio to frequency. For example, at a frequency of 60 Hertz, AC output voltage will be maintained at about 120/240 volts (plus or minus 2%). Should frequency drop to 30 Hertz, voltage will decrease proportionally to about 60/120
volts.
For generators rated 120/240 volts, the engine gover
nor should be set to maintain a NO-LOAD frequency of about 60.5-63.5 Hertz. The Voltage Regulator should then be set to maintain a voltage of about 121-127 volts
(line-to-neutral); or 242-254 volts (line-to-line).
Stator AC Connection Systems
1-PHASE, DUAL WINDING TYPE:
Some NP/IM series generators have dual AC
power windings (Figure 3). Each winding supplies a
120 volts AC output. When the two windings are con
nected in series (Figure 4), a 240 volts AC output results.
When installed, the unit may have ben connected to supply a dual voltage output (120 and/or 240 volts). This is shown In Figure 4. A 3-wire connection system Is used. Stator leads No. 11 and 44 form the two "hot" leads; the Junction of stator leads 22 and 33 form the "Neutral" lead. Notice the "Neutral" line is grounded.
Figure 3. The Dual Stator AC Power Windings
nnrowi fWtrCPi
,, 22 33 44
)CB. ‘f CBzS
T2
-120 V.----------------^
T1 (RED)
Figure 4. Connected for Dual Voltage AC Output
11
(WHnE)
■ 24-3V.
22 33 1
------------------------------------
L 1
K
T
-------------
T3 (BLACK)
-----------------
120V.
---------------------------------
1
1
T1 (RED)
^
-----------------
Figure 5. Connected for 120 Volts AC Output
■ 120V.-
120 V.
---------
T3
(BLACK)
44
------
T2
-------
-------
(WHITE)
P
»
/
r
PAGE 1.5-2
PART1 I SECTION 1.5
THE REVOLVING FIELD AC GENERATOR ■ INTRODUCTION TO TROUBLESHOOTING
Stator AC Connection Systems (Continued)
3-PHASE DELTA STATOR WINDING:
Some units may be equipped with a 3-phase delta type stator winding, shown in Figure 6. Phase rotation is L1-L2-L3. The ^Neutral* line is designated as "LO’. Generator Model No. 9422 uses this type of stator to deliver 120 volts AC (line-to-neutral); or 240 volts AC
(line-to-line).
3-PHASE. WYE-CONNECTED SYSTEM:
Figure 7 shows a 3-phase Wye-Type stator which
has 12 AC output leads that are reconnectable to
supply several voltages. Generator Model 9318 uses
this type of statorto supply 220/380 volts AC at 50 Hertz (i.e., 220 volts AC line-to-neutral; 380 volts AC line-to­line).
Figure 6. A 3-Phase Delta Stator
PAGE 1.5-3
SECTION 1.5 INTRODUCTION TO TROUBLESHOOTING
PARTI
ITHE REVOLVING FIELD AC GENERATOR
PAGE 1.5-4
PARTI
THE REVOLVING FIELD AC GENERATOR
SECTION 1.6- TROUBLESHOOTING
(UNITS WITH 15 INCH STATOR)
1
Section 1.6
TROUBLESHOOTING
(UNITS WITH 15 INCH STATOR)
Introduction
The 'Troubleshooting Flow Charts' that follow have been carefully formulated to help the technician find the cause of problems quickly and easily. Use the Charts as a guide In troubleshooting RV generator problems, to help avoid the unnecessary labor and expense of replacing parts needlessly. Test numbers in the Charts correspond to the numbered tests In the 'DETAILED INSTRUCTIONS' that follow the Flow Charts.
Problem 1- Generator Produces Zero or Residual Voltage at No-Load
REPLACE STATOR
BYPASS
THERMAL PROTECTOR
RECONNECT,
REPAIR OR REPLACE
PAGE 1.6-1
/•.'3c
SECTION 1.6- TROUBLESHOOTING (UNITS WITH 15 INCH STATOR)
Problem 1 - Generator Produces Zero or Residual Voltage at No-Load (Continued)
PART 1
THE REVOLVING FIELD AC GENERATOR
1
TEST 8- CHECK
SENSING LEADS
BAD
AT/M3
i
RECONNECT, REPAIR OR REPLACE BAD LEADS AS NECESSARY
TEST 11-TEST ROTOR WINDINGS
BAD
I
REPLACE ROTOR
---------
O.K._^ BRUSHES AND
r\ 1/ w
TEST 9-TEST
TRANSFORMER
REPLACE BAD
TRANSFORMER
TEST 12- CHECK
REPLACE BRUSHES
OR CLEAN SLIP RINGS,
AS NECESSARY
CCKICIAI/^
BAD
J
SLIP RINGS
I
I
--
rsr\r\r\^
«O.K.^
TEST 10- TEST
CTATnn An
POWER
WtNniNnft
BAD
\
REPLACE
STATOR
ASSEMBLY
TEST 13- CHECK
WIRES NO.
1 AND 4
T
BAD
I
RECONNECT,
REPAIR OR REPLACE
BADWIRE(S)
TEST 14- TEST
FIELD
BOOST
BAD
»
REPAIR BAD WIRE(S) OR
REPLACE BAD
PART(S)
Problem 2- Generator Produces Low Voltage and Frequency at No-Load
(Greater than Residual Voltage)
TESTIS- CHECK
VOLTAGE AND FREQUENCY
FREQUENCY GOOD,
VOLTAGE IS LOW
NOTE: A shorted stator winding can cause rpm, frequency and voltage to droop excessively In the same manner as when the unit’s wattage/amperage capacity Is exceeded.
BOTH
__ AREbh^
LOW
TEST 17-CHECK
AND ADJUST
VOLTAGE
REGULATOR
TEST 16-ADJUST
ENGINE
GOVERNOR
LOW VOLTAGE
, AND/OR LOW FREQUENCY!
CONDITION
IS NOT CORRECTED
FREQUENCY AND I VOLTAGE GOOD-
AFTER ADJUSTMENT
^1 STOP TESTS
GOTO
PROBLEM 1
PAGE 1.6-2
Loading...
+ 122 hidden pages