Proper service and repair is important to the safe, economicai and reliabie operation
of ali recreationai vehicie and industrial mobile generators. Troubleshooting, testing
and servicing procedures recommended by Generac and described in this manual are
effective methods of performing such operations. Some of these operations or proce
dures may require the use of specialized equipment. Such equipment should be used
when and as recommended.
It is important to note that the manual contains various DANGER, CAUTION and
NOTE blocks. These should be read carefully in order to minimize the risk of personal
injury or to prevent improper methods or practices from being used which could damage
equipment or render it unsafe. These DANGER, CAUTION and NOTE blocks are not
exhaustive. Generac could not possibly know, evaluate and advise the recreational
vehicle trade of all conceivable ways in which operations described in this manual might
be accomplished, or the possible hazardous consequences of each way. Consequently,
Generac has not taken any such broad evaluation. Accordingly, anyone who uses any
troubleshooting, testing or service procedure that is not recommended by Generac must
first satisfy himself that neither his nor the equipment’s safety will be jeopardized by the
procedure or method he selects.
TABLE OF CONTENTS
#
SERVICE
MANUAL
NP and IM Series
RECREATIONAL
VEHICLE &
INDUSTRIAL
MOBILE
AC
PART
TITLE
THE REVOLVING FIELD AC GENERATOR
ENGINE MECHANICAL
ENGINE LUBRICATION AND COOLING
SYSTEM
ENGINE FUEL SYSTEM
ENGINE ELECTRICAL SYSTEM
ELECTRICAL DATA
GENERATORS
Liquid-Cooled
Diesel Engine Models
Parti
THE REVOLVING
FIELD
AC
GENERATOR
NP and IM Series
RECREATIONAL
VEHICLE &
INDUSTRIAL
MOBILE
SECTION
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8
1.9
TABLE OF CONTENTS
TITLE
Introduction
How a Generator Works
Major Components
(Units with 15 inch Stator)
Major Components
(Units with 10 Inch Stator)
Introduction to Troubleshooting
Troubleshooting
(Units with 15 Inch Stator)
Troubleshooting
(Units with 10 Inch Stator)
Insulation Resistance Tests
Operational Tests & Adjustments
AC GENERATORS
Liquid-Cooled Diesel Engine Models
PARTI
THE REVOLVING FIELD AC GENERATOR
INTRODUCTION
SECTION 1.1
INTRODUCTION
Section 1.1
Service Manual Familiarization
This SERVICE MANUAL is divided into six (6)
PARTS. Each PART consists of two or more SEC
TIONS. In turn, each SECTION is divided into SUB
SECTIONS.
At the front of the manual is a main TABLE OF
CONTENTS divider page which lists the titles of Parts
1 through 6.
Each PART of the manual is also identified by a
divider page which Identifies the SECTIONS that make
up that PART.
PMes are numbered so as to identify the PART
and SECTION, as well as the specific page number.
For example, "Page 2.1-3" indicates Page 3 of Part 2,
Section 1. This type of numbering system permits indi
vidual Sections of the manual to be kept current without
affecting the entire manual.
Contents of Manual
Part 1 - The Revolving Field AC Generator
Section 1.1- Introduction
Section 1.2- How a Generator Works
Section 1.3- Major Components (Units with 15 inch
Stator)
Section 1.4- Major Components (Units with 10 inch
Stator)
Section 1.5- Introduction to Troubleshooting
Section 1.6- Troubleshooting (Units with 15 inch
Stator)
Section 1.7- Troubleshooting (Units with 10 inch
Stator)
Section 1.8- Insulation Resistance Tests
Section 1.9- Operational Tests & Adjustments
Part 2- Engine Mechanical
Section 2.1- Engine Specifications & Charts
Section 2.2- General Information
Section 2.3- Engine Disassembly
Section 2.4- Disassembly and Inspection
Section 2.5- Engine Reassembly
Part 3- Engine Lubrication & Cooling System
Section 3.1- Engine Lubrication System
Section 3.2- Water Pump and Thermostat
Section 3.3- Cooling and Ventilating Air
Section 3.4- Periodic Maintenance
Part 4- Engine Fuel System
Section 4.1- Introduction to the Diesel Fuel System
Section 4.2- Fuel Pump
Section 5.1- Introduction to DC Control Systems
Section 5.2- Engine Cranking System
Section 5.3- Battery Charge System
Section 5.4- Preheat System
Section 5.5- Engine Protective Systems
Section 5.6- Remote Radiator Fan (Model 9319)
Section 5.7- Remote Panels
Section 5.8- Troubleshooting Row Charts
Section 5.9- Troubleshooting Test Procedures
Part 6- Electrical Data
Page 6.1-1- Resistances of Rotors & Stators
Page 6.1-1- Index to Wiring Diagrams and Eiectrical
Schematics
Identifying Units By Stator Diameter
Throughout the Manual, generators are identified
as having either a "15 inch" ora "10 inch" stator. These
numbers refer to the DIAMETER of the stator can
laminations. See Figures 1 and 2 on next page.
In addition to the diameter and construction of the
stator assembly, the following differences exist be
tween units with 10 inch stator and those having a 15
inch stator:
1. Units with 15 inch stator laminations are equipped
with a Part No. 67680 Voitage Regulator.
a. This type of Voltage Regulator mounts three advi
sory lamps (LED’s) which greatly simplify trouble
shooting.
b. The 67680 R^ulator requires a sensing voltage
of 240 volts AC. To provide the required 240 volts, a
step-up transformer (120 to 240 VAC) is used.
2. Units with 10 inch stator laminations are equipped
with a Part No. 81918 Voltage Regulator.
a. The 81918 Regulator mounts a single lamp (LED)
which remains on as long as sensing voltage is
available.
b. The 81918 Regulator requires a sensing voitage
of 120 volts AC and the step-up transformer is NOT
required.
Three Different Engine DC Control Sys
tems
The NP/IM series generators maybe equipped with
any one of three different kiinds of engine DC control
systems. For convenience, the three different DC sys
tems have been arbitrarily identified as Type 1, Type 2
and Type 3.
Refer to Part 5. "ENGINE ELECTRICAL SYS
TEM", for a description Type 1, 2 and 3 DC control
systems.
PAGE 1.1-1
SECTION 1.1
INTRODUCTION
PARTI
THE REVOLVING FIELD AC GENERATOR
Figure 2. Typical 10 Inch Stator
PAGE 1.1-2
PARTI
THE REVOLVING FIELD AC GENERATOR
HOW A GENERATOR WORKS
SECTION 1.2
HOW A GENERATOR WORKS
1
Section i.2
It has long been known that a relationship exists
General
between magnetism and electricity. The revolving field
generator (or alternator) depends on this relationship
for its operation. In order to diagnose problems and
repair a generator, the service technician must under
stand this relationship.
Why Generators Produce Electricity.
Generators produce an electrical current flow be
cause of the following laws of magnetic induction:
□ When a magnetic field is moved so that it cuts across
a conductor, a voltage and current flow are induced
into the conductor.
□ When current flows through a conductor, a magnetic
field is created around that conductor.
MAGNETIC FIELD CREATES A VOLTAGE;
See Figure 1. When a wire, or coil of wire, is moved
through a magnetic field, an electromotive force (EMF)
or voltage is induced into the wire. Conversely, move
ment of the magnetic field so that its lines of flux cut
across the wire will induce a voltage into the wire. If the
ends of the wire are connected to form a complete
circuit, current will flow in the wire. The direction in
which the current flows depends on the polarity of the
magnetic field and the direction in which the magnet is
moved.
11
Z-
oCOIi
K
11
Figure 1. Magnetism Creates Electricity
Figure 2. Current Flow Creates a Magnetic Field
------
CURRENT FLOW CREATES A MAGNETIC FIELD:
See Rgure 2. Current flow through a wire or coil of
wire will create a magnetic field around the wire. The
strength of the magnetic field depends on the amount
of current flow and the number of loops or coils in the
wire. The direction (polarity) of the magnetic field de
pends on the direction of current flow through the wire.
A Simple AC Generator
See Figure 3. In the simple generator shown, the
revolving magnetic field (Rotor) is a permanent mag
net. As the magnet rotates, its magnetic lines of flux cut
across a stationary coil of wire called a STATOR. If the
stator circuit is completed (by adding a load such as the
light bulb), current will flow through the circuit.
A More Sophisticated Generator
In Figure 4, direct current (DC) is delivered to the
ROTOR coil through CARBON BRUSHES and SLIP
RINGS, to create a magnetic field around the ROTOR.
The greater the current flow through the ROTOR wind
ings, the stronger the magnetic field around the
ROTOR. The ROTOR’S magnetic field cuts across the
stationary STATOR windings, to induce a voltage into
those windings, with the induced voltage proportional
to the strength of the ROTOR’S magnetic field.
STATOR
Û. T 1«V.
üэ”r^
¿»V.
< o
z
UJ-
a.
oc
u 3
ou
Figure 4. A More Sophisticated Generator
BRUSHES
RINGS
PAGE 1.2-1
SECTION 1.2
HOW A GENERATOR WORKS
Operational Analysis- Units with 10 inch Stator Laminations
NOTE: See "IDENTIFYING UNITS BY STATOR DIAMETER" on Page 1.1-1.
PARTI
THE REVOLVING FIELD AC GENERATOR
1
Generator Operation may be briefly described as
follows:
CZl The ROTOR is attached to the engine PTO shaft
and rotates at the same speed as the engine.
□ As the Rotor turns, its magnetic lines of flux cut
across the stationary coils of (a) a stator excitation
winding and (b) dual stator AC power windings. A
voltage is induced into these stationary windings.
□ Current flow from the Stator excitation winding is
delivered to the Voltage Regulator as unregulated
alternating current.
□ Current flow from the Stator AC power windings is
delivered to connected electrical loads.
□ Sensing leads deliver a signal of ACTUAL power
winding output voltage to the Voltage Regulator,
from the Stator AC power windings.
□ The Voltage Regulator electronically compares the
ACTUAL power winding voltage to a REFERENCE
voltage which was pre-set.
□ If the ACTUAL power winding voltage is less than the
Regulator’s REFERENCE voltage. Regulator action
will (a) change the excitation winding output to direct
current (DC), and (b) increase the excitation current
flow to the Rotor.
□ If the ACTUAL power winding voltage is more than
the Regulator’s REFERENCE voltage, regulator ac
tion will (a) change the excitation current to direct
current, and (b) decrease excitation current to the
Rotor.
□ The regulated direct current flow to the Rotor is
delivered via brushes and slip rings.
□ A regulated voltage is induced into the Stator AC
power windings as the Voltage Regulator acts to
maintain an ACTUAL voltage as close as possible to
an adjusted REFERENCE voltage.
A = EXCITATION WINDING
B = STATOR AC POWER WINDING
C = STATOR AC POWER WINDING
CB1 = MAIN CIRCUIT BREAKERS
Figure 5. Operating Diagram- Units with 10 Inch Stator Laminations
PART 1
THE REVOLVING FIELD AC GENERATOR
Operational Analysis- Units with 15 Inch Stator Laminations
Some differences exist between generator models
having a 10 inch diameter stator and those with a 15
inch diameter Stator. You may wish to review "IDENTI
FYING UNITS BY STATOR DIAMETER" on Page 1:1-
1.
Figure 6 is an Operating Diagram for NF eries
generators with a 15* inch diameter stator. T units
are equipped with a Part No. 67680 voltagi n rewhich requires 240 volts AC sensing. Tf ram,
SENSING TRANSFORMER serves to itor’s
stator’s line-to-neutral sensing voltage to 24 ts.
SECTION 1.2
HOW A GENERATOR WORKS
1
Figure 7. Voltage Regulator Part No. 67680
m
A = EXCITATION WINDING
B = STATOR AC POWER WINDING
C = STATOR AC POWER WINDING
CB1 = MAIN CIRCUIT BREAKERS
CB4 = EXCITATION CIRCUIT BREAKER
TP = THERMAL PROTECTOR
Operating Diagram- Units with 15 Inch Diameter Stator Laminations
PAGE 1.2-3
SECTION 1.2
HOW A GENERATOR WORKS
PARTI
THE REVOLVING FIELD AC GENERATOR
1
PAGE 1.2-4
PARTI
THE REVOLVING FIELD AC GENERATOR
MAJOR COMPONENTS
(UNITS WITH 15 INCH DIAMETER STATOR)
SECTION 1.3- MAJOR COMPONENTS
(UNITS WITH 15 INCH STATOR)
1
Section 1.3
ITEM
QTYDESCRIPTION
1
24
3
41Rear Bearing Carrier
5
61
71
810
96
104Hex Head Flanged Bolt
114Screw
12
131Flexible Coupling
14
151Flywheel
16
171Air Ring Baffle
184Vibration Mount
196
202Socket Head Capscrew
4Taptite Screw
4Stud
1
4
1
4Hex Head Capscrew
Taptite Screw
Rotor Bearing
Rotor Assembly
Stator Assembly
Hex Head Capscrew
Lockwasner
Lockwasher
Fan Ring
Flatwasher
»
2®
ITEM
21
22
23
24
25
26
278Lockwasher
28
29
30
31
324
33
344
35
36
371
38
39
40
QTY
■ 1
DESCRIPTION
1
1
4'
2
2
2
6
4
2
2
4
1
1
4
2
Battery Cable Boot
Starter Motor
Engine Adapter
Hex Head Capscrew
Vibration Isolator
Flatwasher
Hex Head Screw
Hex Nut
Brush
Brush Holder
Screw
Brush Cover
stud
Flanged Nut
Red Starter Cable
Lockwasher
Hex Nut
Lockwasher
Hex Head Capscrew
Figure 1. Exploded View of AC Generator with 15 Inch Stator
PAGE 1.3-1
SECTION 1.3- MAJOR COMPONENTS
(UNITS WITH 15 INCH STATOR)
1
AC Generator Disassembly
BRUSH ACCESS AND REMOVAL Figures 1 & 2);
See Rgure 1. Remove the TAPTITE SCREWS
(Item 2) that retain the two BRUSH COVERS (Item 33)
to the REAR BEARING CARRIER (Item 4). Remove
the BRUSH COVERS (Item 33) to gain access to the
BRUSH HOLDERS (Item 31).
See Figure 2, below. Remove Wires No. 1 and 4
from the BRUSHES in both BRUSH HOLDERS. Re
move the TAPTITE SCREWS that retain the BRUSH
HOLDERS to the REAR BEARING CARRIER. Re
move both BRUSH HOLDERS, along with the
BRUSHES
PARTI
THE REVOLVING FIELD AC GENERATOR
To remove the FLEXIBLE COUPLING (Item 13)
from the ROTOR (Item 6), remove four HEX HEAD
FLANGED BOLTS (Item 10).
FLYWHEEL REMOVAL (Figure 1):
Remove four SCREWS (Item 11) and
LOCKWASHERS (Item 12). Then, remove FLY
WHEEL (Item 15). If desired, the FAN RING (Item 14)
can be removed by removing HEX HEAD
CAPSCREWS (Item 8) and LOCKWASHERS (Item 9).
ENGINE ADAPTER REMOVAL (Figure 1);
To remove AIR RING BAFFLE (Item 17), remove
CAPSCREWS (Item 8) that retain It to the ENGINE
ADAPTER (Item 23).
Support the engine and remove all fasteners that
retain the ENGINE ADAPTER to the BASE ASSEM
BLY. Remove HEX HEAD CAPSCREWS (Item 40) and
LOCKWASHERS (Item 27). Finally, remove the EN
GINE ADAPTER.
Components Inspection and Testing
REAR BEARING CARRIER REMOVAL (Figure 1):
Remove HEX NUTS (Item 29), LOCKWASHERS
(Item 27) and STUDS (Item 3) that retain the REAR
BEARING CARRIER (Item 4). To free the REAR
BEARING CARRIER (Item 4) from the ROTOR BEAR
ING (Item 5), use a soft mallet to tap around the outer
periphery of the BEARING CARRIER. Continue tap
ping until the BEARING CARRIER is free of the bear
ing.
STATOR REMOVAL (Figure 1):
The STATOR (Item 7) is "sandwiched" between the
ENGINE ADAPTER (Item 23) and the REAR BEARING
CARRIER (Item 4). Carefully remove the STATOR
(Item 7). DO NOT PERMIT THE STATOR TO DROP
OR BUMP THE ROTOR DURING REMOVAL.
ROTOR REMOVAL (Figure 1):
Remove the four FLANGED NUTS (Item 35) from
STUDS (Item 34). The ROTOR (Item 6), with FLEXI
BLE COUPLING (Item 13) attached, can now be pulled
free of the FLYWHEEL (Item 15).
GENERAL;
Following disassembly, generator components
should be cleaned, dryed and inspected or tested.
Never reassemble a generator having defective parts.'
Keep major parts separated and keep the mounting
hardware along with the parts they are used with. Store
parts in a clean, dry area where condensation, dirt, or
moisture will not damage them.
REAR BEARING CARRIER:
The Rear Bearing Carrier (Figure 1, Item 4) is an
aluminum casting. Clean the casting and blow dry with
air. Inspect carefully for cracks, obvious damage. An
insert has been pressed into the Carrier center bore, to
accommodate the Rotor Bearing. Replace the Rear
Bearing Carrier if the center bore diameter is not within
the following dimensions:
BEARING CARRIER CENTER BORE
2.9527-2.9533 Inches (74.999-75.014mm)
ROTOR BEARING:
The rotor bearing is a prelubricated and sealed ball
bearino that requires no additional lubrication for the
life of the bearing. Spin the Rotor bearing by hand and
check it for binding, seizing, roughness, etc. If the
bearing is defective, it must be replaced.
The bearing may be removed from the Rotor shaft
using a bearing puller. A new bearing can then be
pressed onto the shaft. Exert pressing force on the
bearing inner race only- NEVER on the bearing outer/'"~^^
race.
PAGE 1.3-2
PART 1
THE REVOLVING FIELD AC GENERATOR
SECTION 1.3- MAJOR COMPONENTS
(UNITS WITH 15 INCH STATOR)
1
Components Inspection and Testing
(Continued)
ROTOR ASSEMBLY;
Clean the Rotor with dry, low pressure air (25 psi
or less). If the slip rings are dirty or tarnished, clean
them with fine sandpaper. Inspect the Rotor for dam
age.
Check the resistance of Rotor windings with a
volt-ohm-milliammeter (VOM). Refer to Section 1.6,
"TROUBLESHOOTING (UNITS WITH 15 INCH STA
TOR)".
Use an Insulation resistance tester, megohmmeter,
or Hi-Pot tester to test the resistance of Rotor insula
tion. See Section 1.8,
TESTSr.
If the Insulation resistance is low, dry the Rotor with
warm, dry air. DO NOT EXCEED 185* F. (85’ C.). If
resistance is still low after drying, replace the Rotor
Assembly.
STATOR ASSEMBLY:
Clean the Stator Assembly in the same manner as
the Rotor was cleaned. Inspect ther Stator for damage.
Use a VOM to check Stator windings resistance
(see Section 1.6).
Check the insulation resistance of Stator windings,
as outlined in Section 1.8.
FLEXIBLE COUPLING:
Carefully inspect the Flexible Coupling (Figure 1,
Item 13) for damage, cracking. Check mounting holes
on couplino for elongation and damage. Replace the
Coupling, if it is damaged.
FAN RING AND AIR RING BAFFLE:
Inspect the Fan Ring (Figure 1, Item 14) and the
Air Ring Baffle (Item 17) for damage, cracking. Re
place, if damaged.
•INSULATION RESISTANCE
Reassemble the generator In the reverse order of
Generator Reassembly
disassembly. The reassembly process requires a great
deal of care. Components must be properly aligned and
retained. Tighten all fasteners to the recommended
torque values (see Part 6, "SPECIFICATIONS AND
CHARTS"). Following reassembly, perform an opera
tional test of the unit (Section 1.9).
Components In Generator Control Panel
INTRODUCTION:
Rgure 3 (next page) Is an exploded view of the
generator control panel. The Panel houses or mounts
several Important AC generator components, as well
as components that are part of the engine DC electrical
systems.
ENGINE ELECTRICAL SYSTEM COMPONENTS;
The Control Panel houses the following compo
nents that are part of the engine electrical system. For
Information on these components, refer to Part 5 of this
Manual, "ENGINE ELECTRICAL SYSTEM".
□ The 14 and 30 amp Fuses (Items 4 and 5).
□ The 10 amp DC Circuit Breaker (Item 6).
□ The two 12 volts DC Relays (Items 7 and 8).
□ The DC Voltage Regulator (Item 13).
□ Engine Control Circuit Board (Item 39).
□ Hourmeter (Item 23).
□ Start-Stop Switch (Item 24).
□ Preheat Switch (Item 25).
AC GENERATOR COMPONENTS:
The following components, housed in the control
panel, are major generator components and will be
discussed in this Section and Sub-Section.
□ Excitation Circuit Breaker (Item 11).
□ AC Voltage Regulator (Item 14).
□ The Sensing Transformer (Item 15).
□ AC Circuit Breaker (Item 16).
FLYWHEEL;
Clean the flywheel. Inspect for damage, cracks,
wear, etc. Replace, if necessary.
ENGINE ADAPTER;
Clean the Engine Adapter (Figure 1, Item 23).
Inspect the Adapter carefully for damage, wear, crack
ing, etc. Replace, if necessary.
BRUSH HOLDERS AND BRUSHES:
Inspect Brush Holders and Brushes for damage,
cracking, chipping, excessive wear, etc. Replace any
defective or damaged part. Brushes must always be
replaced in complete sets.
In addition to the above components, a THERMAL
PROTECTOR is physically imbedded in the wire wind
ings of the Stator Assembly. A discussion of this com
ponent will also be included in this Section.
EXCITATION CIRCUIT BREAKER;
The excitation circuit breaker is housed in the con
trol panel and connected in series with .the Stator
Excitation winding output to the Voltage Regulator.
If this Breaker should open, loss of unregulated
excitation current to the Regulator will occur. The Reg
ulator will then shut down and loss of regulated excita
tion current to the Rotor will occur. Generator AC output
will then be proportional to Rotor residual magnetism
only (about 2-7% of rated voltage).
PAGE 1.3-3
SECTION 1.3- MAJOR COMPONENTS
(UNITS WITH 15 INCH STATOR)
PARTI
THE REVOLVING FIELD AC GENERATOR
1
ITEM
QTY
1
2*
3*1
4*
5*
6*
r1
8*
9
101
11**1
12
13*
14“
15“
16
17
18
19
201
211
222
* See Part 5,
2
1
1
1
1
1
1
EXCITATION CIRCUIT BREAKER
1
1
1
1
1
4
4
1
'* Part of AC generator circuit, Included in this Section.
Control Panel Box
DC VOLTAGE REGULATOR
AC VOLTAGE REGULATOR
SENSING TRANSFORMER
AC CIRCUIT BREAKER
Pan Head Screw
Lockwasher
Lockwasher
Control Panel
Panel Decal
Pan Head Screw
ITEM
23*1
24*1
25*
262
27
28
29
30
31
321
33
34
35
36
374
39*
40
41
422
441
45
46
47
48
QTY
1
2
10
8
8
•
8Pan Head Screw
8
8
4
1
6
2
1
4
4
4
DESCRIPTION
HOURMETER
START-STOP SWITCH
PREHEAT SWITCH
Hex Head Capscrew
External Lockwasher
Lockwasher
Flatwasher
Hex Head Capscrew
Customer Leeds (Not Shown).
Pan Head Screw
Lockwasher
Hex Nut
Self Tapping Screw
ENGINE CONTROL CIRCUIT
Spacer Tlut
BOARD
Lockwasher
Hex Nut
Hex Head Capscrew
Panel Wiring Harness
Engine Wire Harness
Vibration Dampener
Hex Nut
Flatwasher
Figure 3. Exploded View of Control Panel
/ 13
PAGE 1.3-4
PARTI
THE REVOLVING FIELD AC GENERATOR
Components In Generator Control Panel (Continued)
AC VOLTAGE REGULATOR:
The Voltage Regulator is powered by stator excitation
winding AC output. Approximately 4 to 8 volts is required
from that power source to turn the regulator on.
The Regulator is equipped with three (3) lamps
(LED’s or "light emitting diodes). See Figure 5. These
lamps are normally on during operation with no faults in
the system. The green EXCITATION lamp and the red
REGULATOR lamp are both turned on by stator excita
tion winding output. If, for any reason, stator excitation
winding output were to be reduced, the two lamps would
begin to dim. Finally, at some mid-point voltage and
current, the two lamps will no longer glow visibly.
SECTION 1.3- MAJOR COMPONENTS
(UNITS WITH 15 INCH STATOR)
1
NOTE: Sensing input to the Regulator Is actually taken
from Hne-to-neutra! stator leads and Is about 120 volts
AC. However, this voltage Is boosted to about 240 volts
AC by the action of a sensing transformer.
The following facts apply to Voltage Regulator opera
tion:
1. The Regulator will shut down on occurence of one or
more of the following conditions:
a. Loss of sensing voltage.
b. Loss of stator excitation voltage Input to the
Regulator.
c. Loss of circuit reference.
NOTE: The term "circuit reference" refers to voltage
regulator settings. The Regulator "regulates" excitation
winding current flow to the Rotor windings in order to
maintain a sensing (actual) voltage that Is commen
surate with a preset "reference" voltage. The reference
voltage is adjustable within a 20 percent range at the
Regulator. Voltage regulation Is accomplished by
electronically maintaining an ACTUAL voltage that Is
very close to the Regulator's preset REFERENCE volt
age.
The yellow SENSING lamp Is powered by sensing
input to the Regulator from the stator AC power wind
ings. The brightness of this lamp (LED) will depend on
available sensing voltage.
2. During generator operation, all three Regulator lamps
should be ON.
a. REGULATOR lamp ON Indicates the Regulator is
functioning normally.
b. SENSING lamp ON indicates that normal sensing
voltage Is available to the Regulator.
c. EXCITATION lamp ON Indicates that unregulated
excitation winding output Is available to the
Regulator.
3. If the red REGULATOR lamp is OUT, a Voltage
Regulator fault exists or the Regulator has shut down
due to occurence of one or more Regulator shutdown
conditions. See Step 1 above for conditions that will
result in Regulator shutdown.
a. Expect to see a generator AC output voltage that
is commensurate with the Rotor’s residual mag
netism.
b. Rotor residual magnetism will supply approximate
ly 2 to 7 percent of the unit’s rated voltage.
NOTE: "Residual" magnetism Is that magnetism that Is
normally always present In the Rotor. The Rotor may be
considered a "permanent magnet".
PAGE 1.3-5
SECTION 1.3- MAJOR COMPONENTS
(UNITS WITH 15 INCH STATOR)
1
Components In Generator Control Panel (Continued)
AC VOLTAGE REGULATOR (CONT’D):
4. If the green EXCITATION lamp goes out, loss of
stator excitation winding output to the Regulator has
occured.
a. Loss of excitation winding output will result in
Regulator shutdown. The red REGULATOR lamp will
then go out, as well.
b. Under this condition, look for a generator AC output
voltage that is commensurate with residual Rotor
magnetism (about 2-7% of rated volts).
c. When the REGULATOR and EXCITATION lamps
are both out, the excitation circuit from the stator
excitation windings to the voltage regulator Is suspect
(inclusive).
5. Should the yellow SENSING lamp go out, loss of
sensing voltage to the Regulator has occured.
a. Loss of sensing may cause the Regulator to shut
down. Both the SENSING lamp and the
REGULATOR lamp will then go out.
b. Generator AC output voltage will then be commen
surate with Rotor residual magnetism (2-7% of rated
volts).
c. Look for a fault in the sensing circuit.
6. If all three lamps go out, look for a fault that might
cause both sensing and excitation to fail.
a. Look for dirty or corroded slip rings, bad brushes,
defective Rotor.
b. Look for open circuit in Wires No. 1 and/or 4.
7. If the red REGULATOR lamp flashes, the
Regulator’s STABILITY potentiometer requires ad
justment.
PART 1
THE REVOLVING FIELD AC GENERATOR
AC CIRCUIT BREAKER:
The AC circuit breaker protects the unit against cur
rent overload by opening the AC output circuit in the
event the generator’s current (amperage) capacity is,/'”^
exceeded. The amperage at which the breaker will trip
(open) is the breaker’s trip rating.
SENSING TRANSFORMER:
The Part No. 67680 Voltage Regulator requires a
"line-to-line" sensing voltage (240 volts) for proper
operation. However, the sensing Is taken from "line-toneutral" Wires No. 11 and 22 (120 volts). For that
reason, the primary coil of a sensing transformer is
connected in series with the sensing leads. The sensing
transformer is a "step-up" type. That is, 120 volts AC in
its primary coil will induce 240 volts into its secondary
coil. It is the secondary coil voltage that is delivered to
the regulator as sensing voltage.
The sensing transformer is housed in the generator
control panel and is used on generator’s with the Part
No. 67680 Voltage Regulator and with 15 inch diameter
stator laminations.
The sensing transformer Is shown pictorially and
schematically in Figure 6.
PAGE 1.3-6
The AC circuit breaker used on any specific generator
model will depend on the rated current (amperage)
capacity of that model.
PART 1
THE REVOLVING FIELD AC GENERATOR
Thermal Protector !
A Thermal Protector is physically imbedded in the
wire windings of the Stator and electrically connected In
series with the excitation winding output leads to the
Regulator. The device is a normally-closed (N.C.),
temperature sensitive switch. The switch contacts will
open when stator temperatures exceed a safe level. The
switch is self resetting. That Is, it will re-dose when
stator temperatures decrease to a safe level.
If the switch contacts should op>en, excitation winding
AC output to the Voltage Regulator will be terminated
and the Regulator’s green EXCITATION lamp will go
out. Since the Regulator cannot op>erate without excita
tion winding output, the red REGULATOR lamp will also
go out. Generator AC output voltage will then drop to a
value commensurate with the Rotor’s residual mag
netism.
If the Thermal Protector contacts open during opera
tion due to a stator overtemperature condition, the
cause of the overtemperature condition must be found
and corrected. High Internal stator temperatures can be
caused by any one of the following:
SECTION 1.3- MAJOR COMPONENTS
(UNITS WITH 15 INCH STATOR
1
rings. The direct current (approximately 9-10 volts DC)
flows through the Rotor windings, the negative (-) slip
ring and brush, and to ground.
Field boost current creates a magnetic field strength
that is additive to the Rotor’s residual magnetism. The
Increased magnetic field strength during engine crank
ing provides an early "pickup* voltage In the stator. The
Regulator is turned on more quickly and AC output
occurs sooner. In effect, field boost current "flashes the
field" on every startup.
Failure of the field boost system nr^y or may not result
In a reduction of AC output to that produced by residual
Rotor magnetism. If residual magnetism Is adequate to
turn the Regulator on and provide the required pickup
voltage, the generator will operate normally with or
without field boost. However, if residual magnetism Is
not adequate, generator AC output will not build and will
be comrr^nsurate with Rotor residual magnetism.
D Insufficient cooling air flow into the generator
interior. Look for blockage of cooling air inlet/outlet openings, air openings that are too small,
ambient temperatures that are too high, etc.
□ Exceeding the wattage/amperage capacity of the
generator. If the unit is overloaded for a period of
time, internal stator temperatures can rise quickly
and cause the Thermal Protector contacts to
open.
D A shorted condition in the generator stator wind
ings or in an electrical load connected to the
generator’s AC output.
The Thennal Protector is not accessible and cannot
be removed and replaced. If the device has failed open,
it can be bypassed by connecting excitation lead No. 2
to a bypass lead (Wire No. 5). Once the device has been
bypassed, stator overtemperature protection Is no
longer available.
Field Boost
When the generator engine Is cranked, direct current
(DC) Is delivered to the Rotor windings. The cunent flow
is provided by the action of an Engine Control circuit
board housed In the control panel and Is delivered to the
Rotor via Wire No. 9, a Field Boost Resistor (R2), a Field
Boost Diode (D2), Wire No. 4, and the brushes and slip
PART OF CONTROL PANEL
WIRING HARNESS
rrSM
1
• 2
3
4
Figure 9. The Field Boost Circuit
DIODE-600V., 6 AMP
RESISTOR-5 WATT. 10 OHMS
DESCRIPTION
HEAT SHRINK
BARREL LUG
PAGE 1.3-7
SECTION 1.3- MAJOR COMPONENTS
(UNITS WITH 15 INCH STATOR)
PARTI
THE REVOLVING FIELD AC GENERATOR
1
PAGE 1.3-8
PARTI
THE REVOLVING FIELD AC GENERATOR
MAJOR COMPONENTS
(UNITS WITH 10 INCH STATOR)
SECTION 1.4- MAJOR COMPONENTS
(UNITS WITH 10 INCH STATOR)
1
Section 1.4
l~47.ir>r«description
■ nRotor Assembly
n
2
32
41
5
6
7
8
9
10
11
122
13
14
151
161
17
186
19
201
21
22
1
1
4
16
12
4Vibration Dampener
1Stator Assembly
1Rear Bearing Carrier
4
1
4
4Capscrew
2
33
Drive Key
Dowel Pin
Blower Housing
Air Outlet Screen
Hex Head Capscrew
Lock Wasner
Flat Washer
Brush Holder
Hex Head Capscrew
Bearing Carrier Gasket
Rame Arrestor37
Bearing Carrier Cover
Bolt
Lock Washer
Starter Assembly
Socket Head Capscrew
Lock Washer
•i'" -W'
TUFT
23
24
25
2610
2712
28
29
301
31
32
331
34
35
36
386
392
402
42
432
441
451
QTY
9
1
3
1
8
1
1
6Socket Head Capscrew
1
1Cooling Fan
1
2Hex Nut
DESCRIPTION
Ratwasher
Engine Plate
Hex Head Capscrew
Hex Head Capscrew
Hex Head Capscrew
Flywheel
Hex Head Capscrew
Spacer
Hex Head Capscrew
Lock Washer
Flexible Coupling
Drive Hub
Starter Solenoid
Hex Head Capscrew
Rat Wasner
Hex Nut
Hex Head Capscrew
DC Voltage Regulator
Starter to Starter Solenoid Ci
Figure 1. Exploded View of Generator with 10 Inch Diameter Stator
PAGE 1.4-1
SECTION 1.4- MAJOR COMPONENTS
^UNnrewmjno^mc^T^OR^^^
1
AC Generator Disassembly
BEARING CARRIER COVER:
Remove four (4) CAPSCREWS (Item 19), FLAT
WASHERS (Hem 8), and LOCK WASHERS (Item 7).
Then, remove the BEARING CARRIER COVER (Item
16) and the BEARING CARRIER GASKET (Item 14).
PARTI
THE REVOLVING FIELD AC GENERATOR
Remove all four long stator bolts along with washers.
Turn the large boH at center of Bearing Carrier puller
until end of bolts is flush wHh the puller. Retain the puller
to the Bearing Carrier with original Carrier Cover
screws. Turn the large center bolt of puller until the
bearing carrier Is free of the Rotor Bearing. Completely
remove the Bearing Carrier.
Figure 2. Bearing Carrier Cover Removal
BRUSH HOLDERS AND BRUSHES:
Remove wires from BRUSHES (Item 12). Remove
SCREWS (Item 13) and remove BRUSH HOLDERS
(Item 12) with brushes.
REAR BEARING CARRIER:
A bearing carrier puller (Figure 4) can be used to
remove the Rear Bearing Carrier. Retain the puller to
the Bearing Caller using the same saews that original
ly held the Bearing Carrier Cover.
Remove fasteners that retain the Bearing Carrier to
the mounting rail.
Figure 5. Removal of Mounting Rail Fasteners and
Stator Bolts
STATOR REMOVAL:
CAUTION. Use care when removing the Stator. Do
NOT allow It to drop or bump the Rotor during
removal.
Free the Stator from the Blower Housing and remove.
See Figure 6.
PAGE 1.4-2
I
PARTI
THE REVOLVING FIELD AC GENERATOR
Figure 6. Stator Removal
BLOWER HOUSING REMOVAL:
Remove the capscrews that retain the Blower Hous
ing to the Engine Plate, along with flat washers, lock
washers and hex nuts. Note positions of longer and
shorter screws, for reassembly.
SECTION 1.4- MAJOR COMPONENTS
(UNITS WITH 10 INCH STATOR)
1
ENGINE PLATE REMOVAL:
Remove starter retaining bolts and remove starter.
Remove bolts that retain the engine plate. Remove the
engine plate.
ROTOR REMOVAL;
Remove capscrews and washers that retain the Cou
pling Plate to the Ring Gear. Remove Rotor, Cooling
Fan, Drive Hub and Coupling Plate as a unit.
If desired, the Cooling Fan, Drive Hub and Coupling
Plate may be removed from the Rotor.
Components Inspection and Testing
GENERAL;
Follovving disassembly, generator components
should be cleaned, dryed and inspected or tested.
Never reassemble a generator with defective or
damaged parts. Store parts In a dean, dry area.
PAGE 1.4-3
SECTION 1.4- MAJOR COMPONENTS
(UNITS WITH 10 INCH STATOR)
Components Inspection
REAR BEARING COVER AND GASKET:
Clean the Beeuing Cover in a suitable non-flammable
commercial cleaner. Blow dry with compressed air.
Inspect the Cover for obvious damage, clogged air slots,
etc. Replace, if necessary. Inspect gasket, replace if
damaged or defective.
REAR BEARING CARRIER;
The Rear Bearing Carrier is an aluminum casting.
Clean the casting and blow dry with air. Inspect carefully
for cracks, damage. An insert is pressed into the Bear
ing Carrier center bore, to accommodate the Rotor
bearing. Use an inside micrometer to check the inside
diameter of the insert. Replace the Bearing Carrier if the
insert inside diameter is not within the following:
PARTI
THE REVOLVING FIELD AC GENERATOR
J
and Testing (Continued)
the Rotor with dry, heated airfor several hours. DO NOT
EXCEED 185* F. (85* C.). if Insulation resistance is still
low after drying, replace the Rotor Assembly.
FAN AND RING GEAR ASSEMBLY:
The FAN, DRIVE HUB, COUPLING PLATE and
RING GEAR are assembled and balanced as a unit.
Clean and inspect parts, replace the entire assembly if
necessary.
BRUSH HOLDER AND BRUSHES:
Inspect both brush holders and both sets of brushes.
Look for cracks, excessive wear, cracks, chipping, etc.
Replace any damaged brush holder. Brushes should be
replaced as a complete set
2.834-2.836 inches (71.996-72.012mm)
STATOR ASSEMBLY:
Clean the stator can exterior surfaces with a soft
brush or cloth. Use clean, dry low pressure air (25 psi
maximum) to clean the stator. Use an ohmmeter to test
the resistance of Stator AC power and excitation wind
ings. Use an insulation resistance tester (megohmmeter
or Hi-Pot tester) to check condition of Stator insulation
(see Section 1.8). If Stator insulation fails the test, the
Stator may be dried by blowing warm, dry air across it
for several hours. DO NOT EXCEED 185* F. (85* C.). If
insulation resistance is still low after drying, replace the
Stator.
BLOWER HOUSING:
Clean with a commercial solvent that is suitable for
use with aluminum. Inspect the Housing carefully for
cracks, damage, etc. Replace, if necessary.
ROTOR ASSEMBLY:
Clean with dry, low pressure air (25 psi maximum).
Test Rotor winding resistance with an ohmmeter. Check
Rotor bearing for binding, seizing, roughness. If the
bearing is defective, replace the Rotor assembly. In
spect the keyway in the tapered shaft for wear, damage.
If slip rings are dull or tarnished, clean with fine
sandpaper. Use an insulation resistance tester
(megohmmeter or Hi-Pot tester) to test for insulation
breakdown (see Section 1.8). If resistance is low, dry
Inspect brush leads No. 1 and 4. Replace any
damaged or defective brush lead.
Generator Reassembly
Reassemble the generator in the reverse order of
disassembly. The reassembly process requires a great
deal of care. All components must be properly aligned
and retained. Tighten all fasteners to the recommended
torque values. Following reassembly, perform an opera
tional test of the unit.
Components In Generator Control Panel
INTRODUCTION:
The following AC generator components are
mounted on or housed in the generator control panel:
□ Voltage Regulator Assembly.
□ An AC Circuit Breaker (CB1 and CB2).
□ Exdtation Circuit Breaker (CB4).
□ A field boost circuit.
In addition to the above AC generator components
housed in the control panel, aTHERMAL PROTECTOR
is physicaliy imbedded in the wire windings of the Stator
Assembly.
Other components are housed in the control panel,
as well. However, these components are part of the
engine's DC control system and will be discussed in
PART 5, "ENGINE ELECTRICAL SYSTEM".
PAGE 1.4-4
PARTI
THE REVOLVING FIELD AC GENERATOR
Components in Generator Control Panel (Continued)
SECTION 1.4- MAJOR COMPONENTS
1
THE AC VOLTAGE REGULATOR:
The VoKage Regulator used on units with 10 inch
stator is shown In Figure 10. The Regulator has a single
red lamp (LED) which will remain on during operation
as long as stator AC power winding "sensing* voitage is
avaiiabie. Three sets of leads connect to the Regulator
terminals as follows:
D Unregulated AC output from the stator excitation
winding connect to the two terminals indicated by
"DPE*.
□ Sensing (actual) voltage signals from the stator
AC power windings are delivered to the
Regulator terminals indicated by "SEN".
□ Rectified and regulated (DC) current Is delivered
to the Rotor winding from Regulator terminals
Indicated by a"+" and
The Regulator provides over-voltage protection. On
loss of "sensing", the Regulator will shut down and
regulated excitation current to the Rotor will terminate.
A single adjustment potentiometer permits the gener
ator's AC output voltage to be adjusted. Perform this
adjustment with the engine running at no-load and with
AC frequency at 62 Hertz (1860 rpm). At 62 Hertz, set
the line-to-neutral AC output voltage to 124 volts AC; or
the line-to-line AC output voltage to 248 volts AC.
AC CIRCUIT BREAKERS:
Two AC output circuit breakers (CB1 and CB2) are
provided, one for each line of the 240 volts AC output
circuit. The trip rating of these breakers depends on the
rated maximum amperage capacity of the generator.
Units rated at 8000 watts (8.0 kW) are equipped with AC
breakers rated at 35 amperes.
Schematic
Pictorial
11
SEE FIGURES 4 & 5 ON
PAGE 1.5-2 FOR WIRING
CONNECTIONS
Figure 11. AC Output Circuit Breakers
EXCITATION CIRCUIT BREAKER (CB4):
An AC circuit breaker, rated 5 amperes, is electrically
connected in series with Wires No. 2 and 2A betwen the
stator excitation winding and the Voltage Regulator. If
the breaker should trip (open) due to an overload, loss
of excitation current to the Rotor will occur. Generator
AC output voltage will then decrease to a value that is
commensurate with Rotor residual magnetism (about 2
to 7% of the unit's rated voltage). The breaker is self
resetting and cannot be reset manually.
Figure 12. Excitation Circuit Breaker
PAGE 1.4-5
SECTION 1.4- MAJOR COMPONENTS
(UNITS WITH 10 INCH STATOR)
1
Components In Generator Control Panel (Continued)
FIELD BOOST CIRCUIT
During engine cranking, an engine controi circuit
board deiivers battery voltage to the Rotor windings.
This "Field Boost" current is delivered to the Rotor via
Wire 4A, a field boost resistor, and Wire 4. The Field
Boost feature provides the following benefits:
□ In effect, field boost current "flashes the field" on
every engine startup. Thus, if Rotor residual magne
tism was lost for any reason, it would be restored by
the act of "flashing the field" during cranking.
□ Approximately 4-8 volts AC output from the stator
excitation winding is needed to turn the voltage reg
ulator on. Reid boost current builds Rotor magnetism
early which, in turn, develops voltage early during
startup. The result of field boost is an early "pickup"
voltage in the stator windings.
THERMAL PROTECTOR:
Refer to " THERMAL PROTECTOR' on Page 1.3-7.
PARTI
THE REVOLVING FIELD AC GENERATOR
PAGE 1.4-6
PARTI
THE REVOLVING FIELD AC GENERATOR
Section 1.5
INTRODUCTION TO TROUBLESHOOTING
DANGER: GENERATORS PRODUCE EXTREMELY
HIGH AND DANGEROUS VOLTAGES. CONTACT
WITH LIVE WIRES OR TERMINALS WILL RESULT
IN HAZARDOUS AND POSSIBLY FATAL ELECTRI-
<CAL SHOCK. ONLY PERSONNEL WHO HAVE
BEEN TRAINED IN THE SERVICING AND REPAIR
OF RV GENERATORS SHOULD ATTEMPT TO
TROUBLESHOOT, TEST OR REPAIR THESE GEN
ERATORS.
Tools and Test Equipment
An RV generator service technician shouid have a
weii stocked tool box that is fiiied with a good seiection
of common hand tools. The tool box should contain
combination wrenches and socket wrenches in both
standard and metric sizes. Also, a good nut driver set is
recommended.
SECTION 1.5
INTRODUCTION TO TROUBLESHOOTING
1
Figure 1. Typical Volt-Ohm-Mllllamm eter (VOM)
The following test equipment is recommended:
□ An accurate volt-ohm-milliammeter (VOM),
preferably a precise digital type.
□ A good AC frequency meter.
D An insulation resistance tester (megohmmeter or
Hi-Pot tester).
O A load bank or some means of applying a known
electrical load to the generator.
Volt-Ohm>Milllammeter (VOM)
If desired, three separate meters may be used, i.e., a
voltmeter, ohmmeter and ammeter. Recommended is
an accurate digital type VOM having a ’Diode Check'
mode.
The service technician must be familiar with his VOM
and must know how to use it. He must also be familiar
with generator electrical circuits and must be able to
read electrical vriring diagrams and schematics.
Frequency Meter
The generator’s AC output frequency must be known
if engine governed speed Is to be property adjusted. See
"ROTOR ROTATIONAL SPEED’ in this section.
Figure 2. One Kind of AC Frequency Meter
Testing Insulation Resistance
Insulation resistance Is a measurement of the In
tegrity of the Insulating materials that separate the
electrical windings from the generator’s steel core. This
resistance can degrade over time due to contaminants
such as dust, dirt, grease and especially moisture.
Information on Insulation resistance test can be found
in Section 1.8, "INSULATION RESISTANCE TESTS'.
PAGE 1.5-1
SECTION 1.5
INTRODUCTION TO TROUBLESHOOTING
Rotor Rotational Speed
"NP" series generators are equipped with a 4-pole
Rotor. That is, the Rotor has two south magnetic poles
and two north magnetic poles. A 4-pole Rotor must be
operated at 1800 rpm to obtain a 60 Hertz AC output
frequency. The following formulas apply when calculat
ing frequency, rpm and number of Rotor poles:
Hertz = RPM X No. of Rotor Poles
2x 60
RPM = 2 X 60 X Hertz
No. of Rotor Poles
PART 1
THE REVOLVING FIELD AC GENERATOR
L
A second alternative Is to connect the wiring to supply
120 volts AC only (Figure 5). When this connectior
method Is used, a jumper wire must be connected
between the two main circuit breakers (CB1 and CB2),
as shown.
No. of =
Poles
2 X 60 X Hertz
RPM
Voltage and Frequency
The generator's solid state Voltage Regulator will
maintain an AC output voltage that is at a fixed ratio to
frequency. For example, at a frequency of 60 Hertz, AC
output voltage will be maintained at about 120/240 volts
(plus or minus 2%). Should frequency drop to 30 Hertz,
voltage will decrease proportionally to about 60/120
volts.
For generators rated 120/240 volts, the engine gover
nor should be set to maintain a NO-LOAD frequency of
about 60.5-63.5 Hertz. The Voltage Regulator should
then be set to maintain a voltage of about 121-127 volts
(line-to-neutral); or 242-254 volts (line-to-line).
Stator AC Connection Systems
1-PHASE, DUAL WINDING TYPE:
Some NP/IM series generators have dual AC
power windings (Figure 3). Each winding supplies a
120 volts AC output. When the two windings are con
nected in series (Figure 4), a 240 volts AC output
results.
When installed, the unit may have ben connected to
supply a dual voltage output (120 and/or 240 volts). This
is shown In Figure 4. A 3-wire connection system Is
used. Stator leads No. 11 and 44 form the two "hot"
leads; the Junction of stator leads 22 and 33 form the
"Neutral" lead. Notice the "Neutral" line is grounded.
Figure 3. The Dual Stator AC Power Windings
nnrowi fWtrCPi
,, 22 33 44
)CB. ‘f CBzS
T2
-120 V.----------------^
T1
(RED)
Figure 4. Connected for Dual Voltage AC Output
11
(WHnE)
■ 24-3V.
22 33 1
------------------------------------
L 1
K—
T
-------------
T3
(BLACK)
I«
-----------------
120V.
---------------------------------
1
1
T1
(RED)
^
-----------------
Figure 5. Connected for 120 Volts AC Output
■ 120V.-
120 V.
---------
T3
(BLACK)
44
------
T2
-------
-------
(WHITE)
P
»
/
r
PAGE 1.5-2
PART1 I SECTION 1.5
THE REVOLVING FIELD AC GENERATOR ■ INTRODUCTION TO TROUBLESHOOTING
Stator AC Connection Systems (Continued)
3-PHASE DELTA STATOR WINDING:
Some units may be equipped with a 3-phase delta
type stator winding, shown in Figure 6. Phase rotation
is L1-L2-L3. The ^Neutral* line is designated as "LO’.
Generator Model No. 9422 uses this type of stator to
deliver 120 volts AC (line-to-neutral); or 240 volts AC
(line-to-line).
3-PHASE. WYE-CONNECTED SYSTEM:
Figure 7 shows a 3-phase Wye-Type stator which
has 12 AC output leads that are reconnectable to
supply several voltages. Generator Model 9318 uses
this type of statorto supply 220/380 volts AC at 50 Hertz
(i.e., 220 volts AC line-to-neutral; 380 volts AC line-toline).
Figure 6. A 3-Phase Delta Stator
PAGE 1.5-3
SECTION 1.5
INTRODUCTION TO TROUBLESHOOTING
PARTI
ITHE REVOLVING FIELD AC GENERATOR
PAGE 1.5-4
PARTI
THE REVOLVING FIELD AC GENERATOR
SECTION 1.6- TROUBLESHOOTING
(UNITS WITH 15 INCH STATOR)
1
Section 1.6
TROUBLESHOOTING
(UNITS WITH 15 INCH STATOR)
Introduction
The 'Troubleshooting Flow Charts' that follow have been carefully formulated to help the technician find the
cause of problems quickly and easily. Use the Charts as a guide In troubleshooting RV generator problems, to help
avoid the unnecessary labor and expense of replacing parts needlessly. Test numbers in the Charts correspond to
the numbered tests In the 'DETAILED INSTRUCTIONS' that follow the Flow Charts.
Problem 1- Generator Produces Zero or Residual Voltage at No-Load
REPLACE
STATOR
BYPASS
THERMAL PROTECTOR
RECONNECT,
REPAIR OR REPLACE
PAGE 1.6-1
/•.'3c
SECTION 1.6- TROUBLESHOOTING
(UNITS WITH 15 INCH STATOR)
Problem 1 - Generator Produces Zero or Residual Voltage at No-Load (Continued)
PART 1
THE REVOLVING FIELD AC GENERATOR
1
TEST 8- CHECK
SENSING LEADS
BAD
AT/M3
i
RECONNECT, REPAIR OR
REPLACE BAD LEADS AS
NECESSARY
TEST 11-TEST
ROTOR
WINDINGS
BAD
I
REPLACE ROTOR
---------
O.K._^BRUSHES AND
r\ 1/ w
TEST 9-TEST
TRANSFORMER
REPLACE BAD
TRANSFORMER
TEST 12- CHECK
REPLACE BRUSHES
OR CLEAN SLIP RINGS,
AS NECESSARY
CCKICIAI/^
BAD
J
SLIP RINGS
I
I
--
rsr\r\r\^
«O.K.^
TEST 10- TEST
CTATnn An
POWER
WtNniNnft
BAD
\
REPLACE
STATOR
ASSEMBLY
TEST 13- CHECK
WIRES NO.
1 AND 4
T
BAD
I
RECONNECT,
REPAIR OR REPLACE
BADWIRE(S)
TEST 14- TEST
FIELD
BOOST
BAD
»
REPAIR BAD
WIRE(S) OR
REPLACE BAD
PART(S)
Problem 2- Generator Produces Low Voltage and Frequency at No-Load
(Greater than Residual Voltage)
TESTIS- CHECK
VOLTAGE AND
FREQUENCY
FREQUENCY GOOD,
VOLTAGE IS LOW
NOTE: A shorted stator winding can cause rpm, frequency and voltage to droop excessively In the same
manner as when the unit’s wattage/amperage capacity Is exceeded.
BOTH
__ AREbh^
LOW
TEST 17-CHECK
AND ADJUST
VOLTAGE
REGULATOR
TEST 16-ADJUST
ENGINE
GOVERNOR
LOW VOLTAGE
, AND/OR LOW FREQUENCY!
CONDITION
IS NOT CORRECTED
FREQUENCY AND
I VOLTAGE GOOD-
AFTER ADJUSTMENT
^1 STOP TESTS
GOTO
PROBLEM 1
PAGE 1.6-2
Loading...
+ 122 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.