This product is not intended to be used in
a critical life support application. Failure to
adhere to this warning could result in
death or serious injury.
60 Hz Air-Cooled Generators
15 kW EcoGen™
Register your Generac product at:
WWW.GENERAC.COM
1-888-GENERAC
(888-436-3722)
Para español, visita: http://www.generac.com/service-support/product-support-lookup
Pour le français, visiter : http://www.generac.com/service-support/product-support-lookup
SAVE THIS MANUAL FOR FUTURE REFERENCE
Use this page to record important information about your generator set.
Model:
Serial:
Prod Date Week:
Volts:
LPV Amps:
NG Amps:
Hz:
Phase:
Controller P/N:
(000005)
WARNING
California Proposition 65. This product contains or
emits chemicals known to the state of California to
cause cancer, birth defects, and other reproductive
harm.
(000004)
WARNING
California Proposition 65. Engine exhaust and some
of its constituents are known to the state of California
to cause cancer, birth defects, and other reproductive
harm.
Record the information found on your unit data label on this
page. See General Information for the location of the unit
data label. The unit has a label plate affixed to the inside
partition, to the left of the control panel console as shown in
Figure 2-1. See Operation for directions on how to open the
top lid and remove the front panel.
When contacting an Independent Authorized Service Dealer
(IASD) about parts and service, always supply the complete
model and serial numbers of the unit.
Operation and Maintenance: Proper maintenance and care
of the generator ensures a minimum number of problems
and keeps operating expenses at a minimum. It is the
operator’s responsibility to perform all safety checks, to
make sure that all maintenance for safe operation is
performed promptly, and to have the equipment checked
periodically by an IASD. Normal maintenance, service, and
replacement of parts are the responsibility of the owner/
operator and are not considered defects in materials or
workmanship within the terms of the warranty. Individual
operating habits and usage may contribute to the need for
additional maintenance or service.
When the generator requires servicing or repairs, Generac
recommends contacting an Independent Authorized Service
Dealer for assistance. Authorized service technicians are
factory–trained and are capable of handling all service
needs.To locate the nearest Independent Authorized Service
Dealer, please visit the dealer locator at:
Consult Manual. Read and understand manual
completely before using product. Failure to
completely understand manual and product
could result in death or serious injury.
(000001)
DANGER
Indicates a hazardous situation which, if not avoided,
will result in death or serious injury.
(000002)
WARNING
Indicates a hazardous situation which, if not avoided,
could result in death or serious injury.
(000003)
CAUTION
Indicates a hazardous situation which, if not avoided,
could result in minor or moderate injury.
Section 1: Safety Rules & General Information
Introduction
Thank you for purchasing this compact, high
performance, air-cooled, engine-driven generator. It is
designed to automatically supply electrical power to
operate critical loads during a normal power source
failure.
As supplied from the factory, this generator is designed to
work in off-grid applications.
In off-grid applications as a part of an alternative energy
system, the generator starts when the inverter/battery
charger detects the normal power source voltage has
dropped below a preset level. The generator powers the
inverter, and once the voltage level of the normal power
source rises to an acceptable level, the generator is shut
down. Another off-grid application would be for use in
remote locations such as for pumping water for a village
or campground, or for livestock.
The unit is factory installed in an all-weather metal
enclosure and is intended for outdoor installation only.
The generator can be operated using either natural gas
(NG) or vapor withdrawn liquid propane (LP).
NOTE: When sized properly, this generator is suitable for
supplying typical residential loads such as induction
motors (sump pumps, refrigerators, air conditioners,
furnaces, etc.), electronic components (computer,
monitor, TV, etc.), lighting loads and microwaves, or
loads less than 10 kW or 2 hp.
The information in this manual is accurate based on
products produced at the time of publication. The
manufacturer reserves the right to make technical
updates, corrections, and product revisions at any time
without notice.
Read This Manual Thoroughly
If any portion of this manual is not understood, contact
the nearest Independent Authorized Service Dealer
(IASD) for starting, operating, and servicing procedures.
This manual must be used in conjunction with the
appropriate installation manual.
SAVE THESE INSTRUCTIONS: The manufacturer
suggests that this manual and the rules for safe operation
be copied and posted near the unit installation site.
Safety should be stressed to all operators and potential
operators of this equipment.
Owner’s Manual for 60 Hz EcoGen™ Generators1
Safety Alerts
Throughout this publication and on tags and decals
affixed to the generator, DANGER, WARNING, and
CAUTION blocks are used to alert personnel to special
instructions about a particular operation that may be
hazardous if performed incorrectly or carelessly. Observe
them carefully. Their definitions are as follows:
NOTE: Notes provide additional information important to
a procedure or component.
These safety alerts cannot eliminate the hazards they
indicate. Observing safety precautions and strict compliance with the special instructions while performing the
action or service are essential to preventing accidents.
The operator is responsible for proper and safe use of
the equipment. The manufacturer strongly recommends
that if the operator is also the owner, to read the owner’s
manual and thoroughly understand all instructions before
using this equipment. The manufacturer also strongly
recommends instructing other users to properly start and
operate the unit. This prepares them if they need to
operate the equipment in an emergency.
How to Obtain Service
Contact an IASD for assistance when the generator
requires servicing or repairs. Service technicians are
factory-trained and are capable of handling all service
needs. Please visit the dealer locator at:
www.generac.com/Service/DealerLocator/ to locate
the nearest IASD.
When contacting a dealer about parts and service,
always supply the complete model and serial numbers of
the unit as given on its data plate (decal), which is
Safety Rules & General Information
DANGER
Accidental start-up. Disconnect power and render
unit inoperable before performing service work.
Failure to do so will result in death or serious injury.
(000344)
(000190)
DANGER
Loss of life. Property damage. Installation must always
comply with applicable codes, standards, laws and
regulations. Failure to do so will result in death
or serious injury.
(000209a)
WARNING
This product is not intended to be used in
a critical life support application. Failure to
adhere to this warning could result in
death or serious injury.
WARNING
This unit is not intended for use as a prime power
source. It is intended for use as an intermediate power
supply in the event of temporary power outage only.
See individual unit specifications for required
maintenance and run times pertaining to use.
(000247)
(000130)
WARNING
Accidental Start-up. Disconnect the negative battery
cable, then the positive battery cable when working
on unit. Failure to do so could result in death
or serious injury.
(000182)
WARNING
(000187)
WARNING
(000155)
WARNING
Only a trained and licensed electrician should perform
wiring and connections to unit. Failure to follow proper
installation requirements could result in death, serious
injury, and damage to equipment or property.
(000115)
WARNING
Moving Parts. Do not wear jewelry when
starting or operating this product. Wearing
jewelry while starting or operating this product
could result in death or serious injury.
(000111)
WARNING
Moving Parts. Keep clothing, hair, and
appendages away from moving parts. Failure
to do so could result in death or serious injury.
(000108)
WARNING
Hot Surfaces. When operating machine, do not
touch hot surfaces. Keep machine away from
combustibles during use. Hot surfaces
could result in severe burns or fire.
(000146)
WARNING
Equipment and property damage. Do not alter
construction of, installation, or block ventilation for
generator. Failure to do so could result in unsafe
operation or damage to the generator.
located on the generator. See Figure 2-1 for decal
location. Record the model and serial numbers in the
spaces provided on the inside front cover of this manual.
Safety Rules
Study these SAFETY RULES carefully before installing,
operating, or servicing this equipment. Become familiar
with this owner’s manual and with the unit. The generator
can operate safely, efficiently, and reliably only if it is
properly installed, operated, and maintained. Many
accidents are caused by failing to follow simple and
fundamental rules or precautions.
The manufacturer cannot anticipate every possible
circumstance that might involve a hazard. The alerts in
this manual and on tags and decals affixed to the unit are
not all-inclusive. If using a procedure, work method, or
operating technique the manufacturer does not
specifically recommend, verify that it is safe for others
and does not render the generator unsafe.
General Hazards
2Owner’s Manual for 60 Hz EcoGen™ Generators
Safety Rules & General Information
WARNING
Risk of injury. Do not operate or service this
machine if not fully alert. Fatigue can impair the
ability to service this equipment and could result
in death or serious injury.
(000215)
WARNING
Environmental Hazard. Always recycle batteries at an
official recycling center in accordance with all local
laws and regulations. Failure to do so could result in
environmental damage, death or serious injury.
(000228)
WARNING
Injury and equipment damage. Do not use
generator as a step. Doing so could result in falling,
damaged parts, unsafe equipment operation,
and could result in death or serious injury.
(000216)
Asphyxiation. Running engines produce
carbon monoxide, a colorless, odorless,
poisonous gas. Carbon monoxide, if not
avoided, will result in death or serious injury.
(000103)
DANGER
(000178a)
Asphyxiation. Always use a battery operated carbon
monoxide alarm indoors and installed according to
the manufacturer’s instructions. Failure to do so
could result in death or serious injury.
WARNING
(000146)
WARNING
Equipment and property damage. Do not alter
construction of, installation, or block ventilation for
generator. Failure to do so could result in unsafe
operation or damage to the generator.
(000144)
DANGER
Electrocution. Contact with bare wires,
terminals, and connections while generator
is running will result in death or serious injury.
(000150)
DANGER
Electrocution. Never connect this unit to the electrical
system of any building unless a licensed electrician
has installed an approved transfer switch. Failure to
do so will result in death or serious injury.
(000188)
DANGER
Electrocution. Do not wear jewelry while
working on this equipment. Doing so will
result in death or serious injury.
(000104)
DANGER
Electrocution. Water contact with a power
source, if not avoided, will result in death
or serious injury.
(000145)
DANGER
Electrocution. In the event of electrical accident,
immediately shut power OFF. Use non-conductive
implements to free victim from live conductor. Apply
first aid and get medical help. Failure to do so will
result in death or serious injury.
Electrical Hazards
DANGER
Electrical backfeed. Use only approved switchgear to
isolate generator from the normal power source.
Failure to do so will result in death, serious injury,
and equipment damage.
(000237)
• Inspect the generator regularly, and contact the
nearest IASD for parts needing repair or
replacement.
Exhaust Hazards
DANGER
Electrocution. Verify electrical system is
properly grounded before applying power.
Failure to do so will result in death or serious
injury.
(000152)
The generator must be installed and operated
•
outdoors only.
Owner’s Manual for 60 Hz EcoGen™ Generators3
Safety Rules & General Information
WARNING
Fire hazard. Do not obstruct cooling and
ventilating airflow around the generator. Inadequate
ventilation could result in fire hazard, possible
equipment damage, death or serious injury.
(000217)
WARNING
Fire and explosion. Installation must comply
with all local, state, and national electrical
(000218)
building codes. Noncompliance could result in unsafe
operation, equipment damage, death or serious injury.
WARNING
Fire hazard. Use only fully-charged fire
(000219)
extinguishers rated “ABC” by the NFPA. Discharged or
improperly rated fire extinguishers will not extinguish
electrical fires in automatic standby generators.
(000100a)
WARNING
Consult Manual. Read and understand manual
completely before using product. Failure to
completely understand manual and product
could result in death or serious injury.
WARNING
to use required safety equipment could result
in death or serious injury.
(000257)
Electrocution. Refer to local codes and
standards for safety equipment required when
working with a live electrical system. Failure
(000147)
WARNING
Risk of Fire. Unit must be positioned in a
manner that prevents combustible material
accumulation underneath. Failure to do so
could result in death or serious injury.
(000192)
DANGER
(000151)
DANGER
Connection of fuel source must be done by a qualified
professional technician or contractor. Incorrect installation
of this unit will result in death, serious injury, and damage
to equipment and property damage.
(000174)
DANGER
Risk of fire. Allow fuel spills to completely dry
before starting engine. Failure to do so will
result in death or serious injury.
(000110)
WARNING
Risk of Fire. Hot surfaces could ignite
combustibles, resulting in fire. Fire could
result in death or serious injury.
Fire Hazards
Explosion Hazards
Comply with regulations the Occupational Safety
•
and Health Administration (OSHA) has
established. Also verify that the generator is
installed in accordance with the manufacturer’s
instructions and recommendations. Following
proper installation, do nothing that might alter a
safe installation and render the unit in
noncompliance with the aforementioned codes,
standards, laws, and regulations.
4Owner’s Manual for 60 Hz EcoGen™ Generators
Section 2: General Information
(000111)
WARNING
Moving Parts. Keep clothing, hair, and
appendages away from moving parts. Failure
to do so could result in death or serious injury.
General Information
EcoGen Operating Principle
Benefits
The 15 kW EcoGen generator brings exciting new
technology to the Home Standby generator product. The
generator is significantly more fuel-efficient than constant
speed generators at normal loads, provides premium
power quality, and is significantly quieter while operating
at normal loads.
• Quieter operation - 3 dB with improved tonal qualities
under normal loads
• Cleanest Standby power available with 1.5% THD
• Significant fuel savings: more fuel efficient under
normal loads
• Lower operating speed of 2700 rpm at low loads
• Tuned exhaust system to further lower sound levels
• Variable Speed / Constant Frequency operation
How It Works
In an off-grid solution, the generator is an important
source of backup power when other resources are
insufficient for the demand, improving overall system
reliability.
2.This is fed to the inverter charger and then on to
the battery bank.
3.The inverter takes DC power from the battery bank,
converts it to AC, and then sends the current to the
AC electrical panel.
4.If there is no solar or wind gain and the battery
bank level drops below a preset threshold, the
inverter automatically signals the generator to start.
5.The generator feeds AC power to the inverter,
which in turn sends power to the electric panel and
recharges the battery bank to an acceptable level.
During startup, as the engine speed increases to 3600
RPM, the Automatic Voltage Regulator (AVR) electronics
perform a self test involving an overall system check of
the unit. If a fault is detected, the unit shuts down and
displays an alarm.
Normal Running
The engine operates between 2700 RPM–3600 RPM
depending on the attached load. When the load
increases or decreases, the speed increases or
decreases accordingly.
Small Load Changes
The system is designed to maintain the current engine
speed for small load changes. Larger load changes result
in a change in engine speed to appropriately handle the
load.
Large Load (Not Overload)
The engine always runs at a speed appropriate for the
attached load. Typical loads up to 10 kW or 2 hp can be
wired directly. The engine speed remains at 3600 RPM
for a programmable time (20 minutes default) and then
decreases to the speed appropriate for the attached load.
The programmable time can be changed by the dealer to
prevent annoying increases and decreases in engine
speed if large loads turn on and off frequently.
If natural gas is the selected fuel type, then all loads up to
9 kW can be wired directly.
Automatic Voltage Regulator (AVR) Cooling Fans
The system is equipped with two fans to cool the AVR
electronics. The primary fan is powered by AC during
operation. The secondary fan is powered by 12V DC
through the controller. The fans are monitored during
operation and if a failure occurs, an alarm is displayed.
Startup
When the generator starts, the engine speed gradually
increases to 3600 RPM to produce maximum power. This
ensures that there is sufficient power to carry the load on
start-up. The engine RPM then gradually decreases to a
speed appropriate for the attached load.
For example, if there is no load, the engine speed
decreases to approximately 2700 RPM. The time it takes
to decrease to 2700 RPM is approximately 4–5 minutes.
Since the ramp rate is linear, less time would be required
for it to decrease to only 3400 RPM.
Owner’s Manual for 60 Hz EcoGen™ Generators5
The secondary fan continues to operate for up to 80
minutes after the generator is shut down. Proper cooling
must occur before removing battery connections for
maintenance or other service activity.
NOTE: The AVR cooling air inlet includes a filter. Verify
the filter is installed and properly seated at time the unit is
installed. Check the filter at regular maintenance intervals
to verify proper airflow.
General Information
003603
R
D
F
C
E
G
R
H
J
L
K
M
B
N
O
P
Q
A
The Generator
Figure 2-1. Components and Control Locations
A.AVRE.Control PanelJ.Oil TankN.Sediment Trap
B.AVR Fil terF.Battery Compartment
C.Main Line Circuit Breaker (Generator
D.Airbox with Air CleanerH.Status LED IndicatorsM.Composite BaseR.Lock with Cover
Disconnect)
K.Oil Fill Cap/Oil dip
(Battery not supplied)
G.Exhaust EnclosureL.Oil FilterP.Q.Fuel Inlet
stick
O.Fuel Regulator
Data Plate Location
6Owner’s Manual for 60 Hz EcoGen™ Generators
General Information
Specifications
Generator
Model15 kW EcoGen
Rated Voltage240
Rated Maximum Load
Current (Amps) at 240 Volts
(LP and NG)*
Main Circuit Breaker70 Amp
Phase1
Rated AC Frequency60 Hz
Battery Requirement
Unit Weight in Lbs. (kilos)471 (213.6)
EnclosureAluminum
Normal Operating RangeThis unit is tested in accordance to UL 2200 standards with an operating
These generators are rated in accordance with UL 2200, Safety Standard for Stationary Engine Generator
Assemblies, and CSA-C22.2 No. 100-04 Standard for Motors and Generators.
62.5
12 Volts, Group 26R 540 CCA Minimum or Group 35AGM 650 CCA Minimum
temperature of -20º F (-29º C) to 122º F (50º C). For areas where temperatures fall
below 32º F (0º C) a cold weather kit is recommended. When operated above 77º
F (25º C) there may be a decrease in engine power. Please reference the engine
specifications section.
Engine
Model15 kW EcoGen
Type of EngineG-Force 1000 Series
Number of Cylinders2
Displacement999 cc
Cold Valve Clearance0.002”-0.004” (0.05 mm - 0.1 mm)
Cylinder BlockAluminum w/Cast Iron Sleeve
Recommended Spark
Plug
Spark Plug Gap0.040 in. (1.02 mm)
Starter12 VDC
Oil Capacity Including
Filter
Recommended Oil FilterPart #070185E
Recommended Air FilterPart #0J8478
Maximum wattage and current is subject to and limited by such factors as fuel BTU/joules content, ambient
temperature and altitude. Maximum power decreases about 3.5 percent for each 1,000 feet (304.8 meters) above
sea level, and also will decrease about 1 percent for each 10° F (6º C) above 60º F (15º C) ambient temperature.
RC12YC
Approx. 3.75 Quarts / 3.55 Liters
The specification sheet for this generator was included in
the documentation provided with the unit at the time of
purchase. For additional copies, consult your local
Independent Authorized Service Dealer.
Owner’s Manual for 60 Hz EcoGen™ Generators7
General Information
(000105)
DANGER
Explosion and Fire. Fuel and vapors are
extremely flammable and explosive. Add fuel
in a well ventilated area. Keep fire and spark
away. Failure to do so will result in death
or serious injury.
Protection Systems
The generator may need to run for long periods of time
with no operator present to monitor the engine/generator
conditions. The generator is equipped with protection
systems to automatically shut down the unit to protect
against potentially damaging conditions. Some of these
systems include:
Alarms:
• High Temperature
• Low Oil Pressure
• Overcrank
• Overspeed
• Overvoltage
• Undervoltage
• Underspeed
• RPM Sensor Loss
• Controller Fault
• Wiring Error
• Fuse Problem
• Stepper Overcurrent
• Overload
Warnings:
• Charger Warning
• Charger Missing AC
• USB Warning
• Download Failure
• Low Battery
• Battery Problem
The control panel contains a display which alerts the
operator when a fault condition occurs. The above list is
not all inclusive. See Operation for more information
about alarms and control panel operation.
NOTE: A warning will indicate a condition on the
generator that should be addressed, but will not shut the
generator down. An alarm will shut the generator down to
protect the system from any damage. In the event of an
alarm, an owner can clear the alarm and restart the
generator prior to contacting an IASD. If the intermittent
issue occurs again, contact an IASD.
Emission Information
The United States Environmental Protection Agency (US
EPA) (and California Air Resources Board (CARB), for
engines/equipment certified to California standards)
requires that this engine/equipment complies with
exhaust and evaporative emissions standards. Locate
the emissions compliance decal on the engine to
determine applicable standards. For emissions warranty
information, please reference the included emissions
warranty. Follow the maintenance specifications in
Maintenance to ensure that the engine complies with the
applicable emissions standards for the duration of the
product’s life.
This generator is certified to operate on Liquid Propane
Vapor fuel or pipeline Natural Gas.
The Emission Control System code is EM (Engine
Modification). The Emission Control System on this
generator consists of the following:
SystemComponents
Air Induction
Fuel Metering
Ignition
Exhaust
- Intake Manifold
- Air Cleaner
- Carburetor and Mixer Assembly
- Fuel Regulator
- Spark Plug
- Ignition Module
- Exhaust Manifold
- Muffler
Fuel Requirements
The engine has been fitted with a dual fuel carburetion
system. The unit will run on natural gas or LP gas
(vapor), but it has been factory set to run on natural gas.
The fuel system will be configured for the available fuel
source during installation.
Recommended fuels should have a BTU content of at least
1000 BTUs per cubic foot (37.26 megajoules per cubic
meter) for natural gas, or at least 2500 BTUs per cubic foot
(93.15 megajoules per cubic meter) for LP gas (vapor).
NOTE: If converting to LP gas from natural gas, a
minimum LP tank size of 250 gal (946 L) is
recommended. See the installation manual for complete
procedures and details.
Battery Requirements
12 volts, Group 26R-540CCA minimum or Group 35AGM650CCA minimum (not included with unit.) See
Maintenance
for proper battery maintenance procedures.
Battery Charger
The battery charger is integrated into the control panel
module in all models. It operates as a smart charger,
which ensures output charging levels are safe and
continuously optimized to promote maximum battery life.
Engine Oil Requirements
See Engine Oil Requirements in the Maintenance
section for proper oil viscosity.
8Owner’s Manual for 60 Hz EcoGen™ Generators
General Information
Activating the Generator
The generator should be activated upon initial start-up.
See the installation manual for complete instructions.
Replacement Parts
Description15 kW EcoGen
26R Exide Battery0H34215
Spark Plug0G0767A
Oil Filter070185E
Air Filter0J8478
Control Panel Fuse0D7178T
AVR Air filter0K3054
Rotor Brushes0J8318
Accessories
NOTE: Performance enhancing accessories are available for air-cooled generators. Contact an IASD or visit
www.generac.com for additional information on replacement parts, accessories, and extended warranties. See also
http://www.ordertree.com/generac/air-cooled-homestandby-generators/.
Accessory Description
Cold Weather Accessories*—
• Battery Pad Warmer
• Oil Warmer
• Breather Warmer
* each sold separately
Scheduled Maintenance Kit Includes all pieces necessary to perform maintenance on the generator along with oil
Touch-Up Paint Kit Very important to maintain the look and integrity of the generator enclosure. This kit includes
Wireless Local Monitor The Wireless Local Monitor is completely wireless and battery powered, and provides owners
• Recommended in areas where temperatures fall below 0 °F (-18 °C).
(Not necessary for use with AGM-style batteries)
• Recommended in areas where temperatures fall below 0 °F (-18 °C).
• Recommended in areas where heavy icing occurs.
recommendations.
touch-up paint and instructions.
with instant generator status updates without ever leaving the house. Status lights (red,
yellow, and green) alert owners when the generator needs attention. Magnetic backing
permits refrigerator mounting and gives a 600 ft (183 m) line of sight communication.
Owner’s Manual for 60 Hz EcoGen™ Generators9
General Information
This page intentionally left blank.
10Owner’s Manual for 60 Hz EcoGen™ Generators
Section 3: Operation
Accidental start-up. Disconnect power and render
unit inoperable before performing service work.
Failure to do so will result in death or serious injury.
(000344)
001797
A
A
B
D
C
Operation
Site Prep Verification
The generator must be installed so that airflow into and
out of the generator is not impeded. Verify that all shrubs
or tall grasses within 3 ft (0.91 m) of the intake and
discharge louvers on the sides of the enclosure have
been removed. Install the generator on high ground
where water levels will not rise and endanger it. This unit
should not operate in or be subjected to standing water.
Verify that all potential water sources such as water
sprinklers, roof run-off, rain gutter downspouts, and sump
pump discharges are directed away from the generator
enclosure.
DANGER
Generator Enclosure
The lid will be locked. A set of keys is attached to the
intake side of the generator.
1. Cut the plastic bag to remove the keys.
2. Use the keys to open the lid of the generator.
NOTE: The enclosed keys provided with this unit are
intended for service personnel use only.
Opening the Lid
Two locks secure the lid—one on each side (A in Figure
3-1). Open the protective rubber cap to access the
keyhole, and press down on the lid above the side lock
and unlock the latch to properly open the lid.
Repeat for the other side. The lid may appear stuck if
pressure is not applied from the top.
NOTE: Always verify that the side locks are unlocked
before attempting to lift the lid.
Removing the Front Access Panel
Remove the front access panel by lifting it straight up and
out once the lid is open.
Always lift the front access panel straight up before
pulling it away from the enclosure (B and C in Figure 3-
1). Do not pull the panel away from the enclosure before
lifting up (D in Figure 3-1).
Figure 3-1. Side Lock Location and Front Panel Removal
Owner’s Manual for 60 Hz EcoGen™ Generators11
Operation
002961
A
B
D
C
001810
B
A
001791
B
C
A
Intake Side Panel Removal
See Figure 3-2. The intake side panel (A) must be
removed to access the battery compartment, fuel
regulator, and sediment trap.
1. Raise the lid and remove the front panel.
2. Use an Allen wrench to remove two mounting
screws (B) and the L-bracket screw (C).
Figure 3-2. Intake Side Panel Removal
Main Line Circuit Breaker (Generator
Disconnect)
3. Lift the intake panel up and away from the
generator.
NOTE: Always lift the intake side panel straight up
before pulling away from enclosure. Do not pull the panel
away from the enclosure before lifting up (D).
LED Indicator Lights
This is a 2-pole breaker rated according to relevant
specifications. See “A” in Figure 3-3.
The breaker can be locked in the OFF (OPEN) position
for security. Use an appropriately-sized padlock (not
included) with a shackle long enough to pass through
both lock tabs (B).
Figure 3-3. Main Breaker
NOTE: DO NOT lock out the MLCB during normal
generator operation. Doing so will compromise automatic
standby functionality.
Figure 3-4. LED Indicator Lights
See Figure 3-4. Three LEDs are visible behind a
translucent lens on the generator side panel. These
LEDs indicate the operating status of the generator.
• Green LED “Ready” light (A) is illuminated when
the control panel button is in the AUTO position.
The LED flashes when the connected load is
running under generator power.
• Red LED “Alarm” light (B) is illuminated when the
generator is OFF or a fault is detected. Contact an
IASD.
• Yellow LED “Maintenance” light (C) is illuminated
when scheduled maintenance is due.
NOTE: Yellow Maintenance or Warning LED may be on
at the same time as either the Red or Green LED.
12Owner’s Manual for 60 Hz EcoGen™ Generators
Operation
001798
A
B
Control Panel Interface
See Figure 3-5. The control panel interface (A) is located
under the lid of the enclosure. Verify that both the left and
right side locks are unlocked before attempting to lift the
lid of the enclosure. Open the lid as directed in Opening
the Lid.
The 7.5A fuse is located beneath the rubber cover (B) to
the right of the control panel.
Verify that both the left and right side locks are securely
out of the way before closing the unit.
Figure 3-5. Generator Control Panel
Using the AUTO/OFF/MANUAL
Interface
Button Description of Operation
This button activates fully automatic system
operation.
The Green LED on this button will flash if
AUTO
OFF
MANUAL
running in Automatic mode and the connected
loads are running under generator power.
Transfer to standby power occurs if remote two
wire start is ON (CLOSED).
This button shuts down the engine and
prevents automatic operation of the unit.
This button cranks and starts the generator.
The blue LED on this button will flash if running
in manual mode and the connected loads are
running under generator power.
NOTE: Damage caused by mis-wiring of the
interconnect wires is not warrantable.
Interface Menu Displays
All appropriate panels must be in place during any
operation of the generator. This includes operation by a
servicing technician while conducting troubleshooting
procedures.
USB Port for Firmware Updates
A USB Port is located beneath the rubber cover (B) and
is provided for firmware updates. Firmware updates must
be performed by an IASD.
NOTE: The USB port is intended for use with a USB
flash drive only. The USB port is not intended for
charging or powering any device such as phones or LED
lights. Do not connect any consumer electronics to the
USB port.
The LCD Panel
Feature Description
Default page that is displayed if no buttons are
pressed for 60 seconds. Normally shows
current status message and the current date
and time. The highest priority active alarm/
warning is automatically posted on this page,
HOME
page
To get to the MENU, use the ESCAPE button from any page. You may need to press the ESCAPE button several times
before reaching the MENU page. Navigate to the desired menu by using the
displayed and flashing, press the ENTER button.
↑/↓ buttons. When the desired menu is
14Owner’s Manual for 60 Hz EcoGen™ Generators
Figure 3-6. Navigation Menu
UP ARROW =
+
DOWN ARROW = -
MAINT
DEALER
EXAMPLE:
Inspect Battery 200 RnHr or 12/27/13
and
Next Maintenance 200 RnHr or 12/27/13
Current Date/Time
02/14/13 07:40
ESC
ESC
ENTER
ENTER
ESCENTER
ESC
ESCESC
ENTER
ESC
MAINT
:
Maint. Log
Run Hrs
Scheduled
Select Month (1-12)
- 2 +
Run Hours (H)
0.0
ENTER
Select Date (1-31)
- 13 +
ENTER
Select Year (0-99)
- 13 +
ENTER
ENTER
Access Requires Password
"Current:V XXXX "
"USB: V XXXX"
"Are You Sure?"
"- Yes or No +"
ESC
ENTER
ESCENTER
ESCENTER
Select “Yes” then Press “Enter” to continue or Press
“ESCAPE” to escape out of updating.
During update process the Blue “Manual” light
flashes, then the Green “Auto” light flashes.
Sequence does this twice. When update is complete
the unit returns to Install Wizard menu.
When the controller powers up the very first screen
displays the version number for a few seconds.
When update is complete remove Thumb Drive, then
follow the Install Wizard Menu.
- 1 thru 50 +
"Battery Maintained"
"Schedule A Serviced"
"Schedule B Serviced"
NOTE: The battery charger is integrated into the control
module in all models.
The battery charger operates as a smart charger that
verifies:
• Will not transfer to generator if MLCB (generator disconnect) is OFF (OPEN).
MANUAL
• Will transfer to generator if MLCB (generator disconnect) is ON (CLOSED).
• Will start and run when remote two-wire start is ON (CLOSED).
AUTO
• The generator will shut down if the OFF button is pressed or a shutdown alarm is present.
• Once remote two-wire start is OFF (OPEN), the generator will shut down immediately (a
selectable cool down is provided; default is no cool down)
Automatic Sequence of
Operation
Cranking
The system will control the cyclic cranking as follows:
• 16 second crank, seven (7) second rest, 16 second
crank, seven (7) second rest, followed by three (3)
additional cycles of seven (7) second cranks followed
by seven (7) second rests.
Cold Smart Start
The Cold Smart Start feature monitors the ambient
temperature and adjusts the warm-up delay upon start up
in AUTO mode based on prevailing conditions.
The generator will startup with the normal warm-up delay
of 5 seconds if the ambient temperature is at or above
the fixed temperature.
A check for proper output voltage build up will be
performed when the generator engine is started.
If some condition impedes normal voltage creation, such
as frost crystals or dust/dirt preventing a good electrical
connection, the start sequence will be interrupted so that
a cleaning cycle of the internal electrical connections can
be attempted.
The cleaning cycle is an extended warming up period
which lasts for several minutes while the normal
generator voltage output is determined to be low. During
this cycle, the generator controller will display “Warming
Up” on the display screen.
The generator controller display will show “Under
Voltage” if the cleaning cycle fails to clear the obstruction.
After several minutes, the alarm message can be
cleared, and the generator restarted.
If the problem persists, make no further attempts to start.
Contact an IASD.
• output is continually optimized to promote
maximum battery life.
• charging levels are safe.
NOTE: A warning is displayed on the LCD when the
battery needs service.
Shutting Generator Down While
Under Load Or During An
Extended Run
Proceed as follows to turn the generator off during an
extended run to perform maintenance or conserve fuel:
To turn the generator OFF (while running in
AUTO and online):
1. Turn the MLCB (generator disconnect) on the gen-
erator to OFF (OPEN).
2. Allow generator to run approximately 1 minute for
proper cooling.
3. Press the OFF button on the controller.
To turn the generator back ON:
1. Put the generator into AUTO and allow to start and
warm-up for a few minutes.
2. Set the MLCB (generator disconnect) on the
generator to ON (CLOSED).
The system is now in automatic mode. The connected
loads can be engaged.
16Owner’s Manual for 60 Hz EcoGen™ Generators
Section 4: Maintenance
(000182)
WARNING
002389
Maintenance
Maintenance
Regular maintenance will improve performance and
extend engine/equipment life. Generac Power Systems,
Inc. recommends that all maintenance work be
performed by an Independent Authorized Service Dealer
(IASD). Regular maintenance, replacement, or repair of
the emissions control devices and systems may be
performed by any repair shop or person of the owner’s
choosing. To obtain emissions control warranty service
free of charge, the work must be performed by an IASD.
See the emissions warranty.
Preparing for Maintenance
Before performing any maintenance, proceed as follows
to prevent the generator from accidental startup:
1. Open lid, turn the generator off and allow the
engine to cool. Verify that the unit is OFF.
Performing Scheduled
Maintenance
It is important to perform maintenance as specified in the
Service Schedule for proper generator operation. Check
the engine oil level, change the oil filter, and adjust the
valve lash after the first 25 hours of operation.
Emissions-critical maintenance must be performed as
scheduled in order for the emissions warranty to be valid.
Emissions-critical maintenance consists of servicing the
air filter and spark plugs in accordance with the Service
Schedule.
The controller will prompt for Schedule A or Schedule B
maintenance to be performed. Schedule A maintenance
consists of the oil, oil filter, and battery check. Schedule B
maintenance includes the oil, oil filter, battery check, air
cleaner, spark plug(s), and valve clearance.
Since most maintenance alerts will occur at the same
time (most have two year intervals), only one will appear
on the control panel display at a time. Once the first alert
is cleared, the next active alert will be displayed.
NOTE: Allow the AVR to cool down before removing the
7.5 amp fuse to prevent damage to the AVR. The cool
down may take up to 80 minutes.
2. With the generator shut down, remove the front
panel.
3. Remove the 7.5 amp fuse from the control panel.
4. Remove the intake side panel. (See Intake Side
Panel Removal.)
5. See Figure 4-1. Disconnect the white battery
charger cable.
Figure 4-1. Disconnecting Battery Charger Cable
Owner’s Manual for 60 Hz EcoGen™ Generators23
Maintenance
Service Schedule
ServiceWeekly
Check Enclosure Louvers for Dirt and Debris
Check AVR and Engine Filter
Check Lines and Connections for Fuel or Oil Leaks
Check Engine Oil Level
Check Spark Plugs
Check Battery Condition
Replace AVR Filter*
Replace Engine Oil Filter and Oil in Oil Tank**
Replace Engine Air Filter
Replace Spark Plugs
Adjust Valve Clearance***
Replace Rotor Brushes****
Contact the nearest IASD for assistance if necessary.
* Replace AVR filter more frequently if operating in dusty conditions.
** Check the engine oil level and change the oil filter
*** Check/adjust valve clearance after the first 25 hours of operation.
**** Should be performed only by an Independent Authorized Service Dealer.
Every Three
Months
Every
Yea r
Schedule A
Every
Two Years
or 500 Hours
Schedule B
Every
Four Years
or 1000 Hours
NOTE: Contact an IASD or visit www.generac.com for additional information on replacement parts.
Maintenance Log
Battery inspection and charge check
Dates Performed:
Oil, oil filter, air filter, and spark plug replacement
Dates Performed:
Valve Adjustment
Dates Performed:
24Owner’s Manual for 60 Hz EcoGen™ Generators
Maintenance
(000139)
WARNING
Risk of burns. Allow engine to cool before
draining oil or coolant. Failure to do so
could result in death or serious injury.
(000210)
WARNING
Skin irritation. Avoid prolonged or repeated contact with
used motor oil. Used motor oil has been shown to cause
skin cancer in laboratory animals. Thoroughly wash
exposed areas with soap and water.
(000135)
CAUTION
Engine damage. Verify proper type and quantity of
engine oil prior to starting engine. Failure to do so
could result in engine damage.
001384
A
(000135)
CAUTION
Engine damage. Verify proper type and quantity of
engine oil prior to starting engine. Failure to do so
could result in engine damage.
Checking Engine Oil Level
Proceed as follows to check the engine oil level:
1. Turn the main line circuit breaker (MLCB) (generator disconnect) on the generator to OFF (OPEN).
2. Disengage the connected loads from the
generator.
3. Turn the generator off.
4. Press the control panel OFF button. Wait five
minutes.
2. Allow the generator to start and warm up for a few
minutes.
3. Set the generator disconnect on the generator to
ON (CLOSED).
4. The system is now operating in automatic mode.
The connected loads can now be engaged.
Engine Oil Requirements
To maintain the product warranty, the engine oil should
be serviced in accordance with the recommendations of
this manual. For your convenience, Generac
Maintenance Kits are available that include engine oil, oil
filter, air filter, spark plug(s), a shop towel, and a funnel.
These kits can be obtained from an IASD.
All Generac oil kits meet minimum American Petroleum
Institute (API) Service Class SJ, SL, or better. Do not use
special additives.
Required Oil—
Synthetic SAE 5W-30 for all temperature ranges.
Figure 4-2. Dipstick Location
5. See Figure 4-2. Remove the dipstick (A) and wipe
it dry with a clean cloth.
6. Completely insert the dipstick and again remove it.
7. Observe the oil level. The level should be at the
“FULL” mark on the dipstick.
8. If necessary, remove the oil fill cap and add oil to
the engine until the level reaches the “FULL” mark
and reinsert the dipstick and fill cap.
An Oil System Drain Pump Kit (P/N 0K3717) has been
shipped with this unit. Refer to the instructions included
with that kit for assembly and use of the Oil System Drain
Pump. If the Oil System Drain Pump has become lost, or
is unavailable, use a suitable suction pump to perform
the following oil change procedure.
EcoGen Oil System Drain Pump Kit Parts List
(Kit Part No. 0K3717)
A¾ in. Spring Clamp**
B½ in. Rubber Hose**
C½ in. Barb Hose Fitting with ¾ in. Hose Thread**
DDrill Pump
E¼ in. Barb Hose Fitting w/¾ in. Hose Thread*
F½ in. Spring Clamp*
G¼ in. Rubber Hose*
* Parts 1, 2, and 6 come assembled from the supplier.
** Parts 3, 4, and 7 come assembled from the supplier.
EcoGen Oil System Drain Pump Assembly
1. See Figure 4-4. Install the ¼ in. Hose Assembly
onto the inlet side of the Drill Pump. Twist the fitting
clockwise until it is snug. Do not over-tighten.
Figure 4-4. Pump Assembly Step 1
2. See Figure 4-5. Install the ½ in. Hose Assembly
onto the outlet side of the Drill Pump. Twist the
fitting clockwise until it is snug. Do not over-tighten.
Figure 4-5. Pump Assembly Step 2
26Owner’s Manual for 60 Hz EcoGen™ Generators
EcoGen Oil Change Procedure
(000210)
WARNING
Skin irritation. Avoid prolonged or repeated contact with
used motor oil. Used motor oil has been shown to cause
skin cancer in laboratory animals. Thoroughly wash
exposed areas with soap and water.
001387
B
A
001426
001389
001390
1. Place the MLCB to the OFF position.
2. Press the Control Panel MANUAL button to
operate the unit.
3. Verify the engine is at operating temperature by
operating the unit for a minimum of 20 minutes.
4. Press the Control Panel OFF button to shut down
the engine.
5. Allow the oil to settle for 10 minutes.
NOTE: Allowing the engine to run at operating
temperature increases engine oil viscosity so that it can
be easily drawn out of the system. Allowing the oil to
settle ensures that the oil has thoroughly drained to the
tank and that the equipment is cool enough to handle
during the procedure. Always follow proper safety
precautions when working with this equipment.
Maintenance
Figure 4-7. Attaching Drill Pump
10. See Figure 4-8. Insert the ¼ in. hose free end into
the unit’s oil tank.
6. See Figure 4-6. Remove the used oil filter (A) by
turning it counterclockwise. A towel or small
container may be used to catch any residual oil
when removing the filter.
Figure 4-6. Oil Filter and Dipstick
7. Remove the oil dipstick (B) from the tank.
8. Set a drill to spin in the clockwise direction.
9. See Figure 4-7. Attach the drill to the drive shaft of
the Drill Pump.
Figure 4-8. Drain Hose In Oil Tank
11. See Figure 4-9. Insert the ½ in. hose free end into
a suitable oil catch container. Make sure there are
no kinks or obstructions in either hose.
Figure 4-9. Draining Into Oil Catch Container
12. Spin the pump on the high speed setting of the drill.
NOTE: It may take up to 2 minutes to prime the pump.
Owner’s Manual for 60 Hz EcoGen™ Generators27
13. After oil begins pumping, draw out as much oil as
possible. A total of 2.5–3.5 quarts (2.37– 3.31 L) of
oil should be removed from the system.
14. Remove the ¼ in. hose from the tank and drain
remaining oil from the drill pump and hoses.
15. Apply a light coating of new oil to the gasket of the
new oil filter.
Maintenance
001221
A
B
001222
C
(000223)
WARNING
Electric shock. AVR maintains electrical
charge after generator shutdown. Wait five
minutes before AVR removal. Failure to do
so could result in death or serious injury.
16. Screw the new oil filter on by hand until the filter
gasket contacts the oil filter adapter. Tighten the
new oil filter ¾ to one full turn more.
17. Refill the oil tank with the proper recommended oil.
Do not fill above the full mark on the dipstick.
18. Start the engine, run for one minute and check for
leaks.
19. Stop the engine for a minimum of 10 minutes.
20. Recheck the oil level and add oil if necessary.
21. Place the MLCB to the ON position.
22. Place the unit back into service by pressing the
control panel AUTO button.
Dispose of used engine oil and oil filter at a proper
collection center.
Replacing the Engine Air Filter
1. With the generator shut down, lift the lid and
remove the front panel.
2. See Figure 4-10. Remove the cover clip (A) and
air cleaner cover (B).
6. Install the air cleaner cover and cover clip.
Replacing the AVR Filter
001219
Figure 4-12. Removing the AVR Filter Screw
Figure 4-10. Removing the Air Cleaner Cover
3. See Figure 4-11. Pull out the old air filter (C) and
discard.
Figure 4-13. Replacing the AVR Filter
1. See Figure 4-12. Remove screw to release AVR
filter housing from back panel.
2. Remove AVR filter housing.
3. See Figure 4-13. Grasp rubber lifting strap and
remove filter from filter housing.
Figure 4-11. Removing the Air Filter
4. Thoroughly clean the air cleaner enclosure of any
dust or debris.
5. Install a new air filter.
28Owner’s Manual for 60 Hz EcoGen™ Generators
4. Install new filter (See Replacement Parts), so that
edge is positioned inboard of two tabs on filter
housing.
5. Install AVR filter housing so the bottom drops into
the slots, ensuring that the rubber boot is
completely around the fan opening. Install screw to
fasten AVR filter housing to back panel and torque
to 50–96 in-lbs (6–11 Nm).
001220
Maintenance
(000140)
Electrical shock. Do not disconnect spark
plug wires with engine running. Doing so
could result in death or serious injury.
WARNING
(000222a)
WARNING
Moving Parts. Avoid AVR fan housing for 80
minutes after generator shutdown. Fan
operates even if fuse is removed. Rotating fan
blades could result in death or serious injury.
(000223)
WARNING
Electric shock. AVR maintains electrical
charge after generator shutdown. Wait five
minutes before AVR removal. Failure to do
so could result in death or serious injury.
000211
(000130)
WARNING
Accidental Start-up. Disconnect the negative battery
cable, then the positive battery cable when working
on unit. Failure to do so could result in death
or serious injury.
(000223)
WARNING
Electric shock. AVR maintains electrical
charge after generator shutdown. Wait five
minutes before AVR removal. Failure to do
so could result in death or serious injury.
001404
A
Maintaining the Spark Plugs
Check and replace the spark plugs as necessary.
1. With the generator shut down, lift the lid and
remove the front panel.
2. See “A” in Figure 4-12. Remove screw to release
AVR filter housing from back panel.
3. Clean the area around the base of the spark plugs
to keep dirt and debris out of the engine.
4.
Remove spark plug cables from spark plug terminals
5. Remove the spark plugs and check the condition.
Install new plugs if the old spark plugs are worn or
if reuse is questionable.
6. Clean the spark plugs by scraping or washing with
a wire brush and commercial solvent. Do not blast
the spark plugs to clean.
7. See Figure 4-14. Check spark plug gap using a
wire feeler gauge. Replace the spark plug if the
gap is not within specification as provided in
Section 2 — Specifications.
10. Install AVR filter housing.
11. Install front panel and lower the generator lid.
Valve Clearance Adjustment
Check the valve clearance after the first 25 hours of
operation, then as per recommended service interval
(See Service Schedule). Adjust if necessary.
Important: Please contact an Independent Authorized
Service Dealer for service assistance. Proper valve
clearance is essential for prolonging the life of the
engine.
Check Valve Clearance
1. Verify that engine is at ambient air temperature.
NOTE: Allow the AVR to complete its cool down before
disconnecting power, which is indicated by the green light
turning off.
.
2. See Figure 4-12. Remove screw to release AVR
filter housing from back panel. Remove AVR filter
housing.
3. See Figure 4-15. Depress external latch to
disconnect 4-pin connector (A) from AVR.
4. See Figure 4-16. Remove three screws (B) to
release AVR fan from AVR.
Figure 4-14. Checking Spark Plug Gap
8. Install the spark plugs and torque to 18.4 ft-lbs (25
Nm).
9. Attach spark plug cables to spark plug terminals.
Owner’s Manual for 60 Hz EcoGen™ Generators29
Figure 4-15. Remove AVR Fan Connector
Maintenance
001414
B
002380
C
D
E
F
Figure 4-16. Remove AVR Fan Screws
5. Remove spark plug cables from spark plug
terminals.
6. Remove spark plugs.
7. Make sure the piston is at top dead center (TDC) of
its compression stroke (both valves closed). To
move the piston to TDC, remove the intake screen
at the front of the engine to access the flywheel
nut. Use a large socket and socket wrench to
rotate the flywheel nut clockwise, which will rotate
the crankshaft. Watch the piston through the spark
plug hole. The piston should move up and down.
The piston is at TDC when it is at its highest point
of travel.
Adjust Valve Clearance
See Figure 4-17. Proceed as follows to adjust the valve
clearance:
NOTE: Allow engine to cool before adjusting valve
clearance.
1. Remove spark plug wire(s) and position wire(s)
away from plugs.
2. Remove spark plug(s).
3. Remove the four screws attaching the valve cover.
Remove and discard gasket.
4. Make sure the piston is at top dead center (TDC) of
its compression stroke (both valves closed).
5. Loosen the rocker jam nut (C) using a 13 mm
wrench.
.
Figure 4-17. Valve Clearance Adjustment
6. Turn the pivot ball stud (D) using a 10 mm Allen
wrench while checking clearance between the
rocker arm (E) and the valve stem (F) with a feeler
gauge. Adjust clearance as per Specifications.
NOTE: Hold the rocker arm jam nut in place as the pivot
ball stud is turned.
7. When valve clearance is correct, hold the pivot ball
stud (B) in place with a wrench and tighten the
rocker arm jam nut. Tighten the jam nut to 174 inlbs (19.68 Nm).
8. After tightening the jam nut, recheck valve
clearance to verify it did not change.
9. Install new valve cover gasket.
10. Install the valve cover. Tighten fasteners in a cross
pattern, torquing to 60 in-lbs (6.8 Nm).
NOTE: Start all four screws before tightening, or it will
not be possible to get all the screws in place. Verify the
valve cover gasket is in place.
11. Install spark plugs and torque to 18 ft-lbs (25 Nm).
12. Attach the spark plug wire to the spark plug.
13. Connect the AVR fan to the AVR using the three
screws.
14. Connect the 4-pin connector to the AVR.
15. Install AVR filter housing so the bottom drops into
the slots, ensuring that the rubber boot is
completely around the fan opening. Install screw to
fasten AVR filter housing to back panel and torque
to 50–96 in-lbs (6–11 Nm)
16. Repeat the process for the other cylinder if
necessary.
30Owner’s Manual for 60 Hz EcoGen™ Generators
Battery Maintenance
–
+
(000162)
WARNING
Explosion. Do not dispose of batteries in a fire.
Batteries are explosive. Electrolyte solution can cause
burns and blindness. If electrolyte contacts skin or eyes,
flush with water and seek immediate medical attention.
(000137a)
WARNING
(000164)
WARNING
Electrical shock. Disconnect battery ground
terminal before working on battery or battery
wires. Failure to do so could result in death
or serious injury.
(000138a)
WARNING
WARNING
Environmental Hazard. Always recycle batteries at an
official recycling center in accordance with all local
laws and regulations. Failure to do so could result in
environmental damage, death or serious injury.
(000228)
The battery should be regularly inspected per the
Service Schedule. Contact an IASD for assistance if
necessary.
Proceed as follows to inspect the battery:
1. Press the OFF button to shut down the generator,
then lift the lid and remove the front panel.
2. Remove the 7.5 amp fuse from the control panel.
3. Remove the intake side panel. (See Intake Side
Panel Removal.)
4. See Figure 4-1. Disconnect the white battery
charger cable.
NOTE: Allow the AVR to cool and the fan to stop before
removing the battery. Removing the battery before the
AVR has stopped can damage the AVR and injure the
operator.
5. See Figure 4-18. Inspect the battery posts and
cables for tightness and corrosion. Tighten and
clean as necessary.
Maintenance
001832
Figure 4-18. Battery Cables
6. (Unsealed batteries only): Completely disconnect
the battery. Check the battery fluid level and, if
necessary, fill with distilled water only. DO NOT
use tap water. Also, have an IASD or a qualified
service technician check the state of charge and
condition.
7. When inspection is complete, reconnect the battery
cables, the battery charger cable, reinstall the
intake side panel, and reinstall the 7.5 amp fuse.
8.
Place the controller in AUTO mode.
9.
Install the front panel and close the generator lid.
• DO NOT smoke when near the battery.
• DO NOT cause flame or spark in the battery area.
• Discharge static electricity from the body before
touching the battery by first touching a grounded
metal surface.
Cleaning the Sediment Trap
The sediment trap removes contaminants (moisture and
fine particles) from gaseous fuels before they enter the
fuel regulator. Accumulated moisture and particles must
be emptied from the sediment trap per local codes and
guidelines.
Proceed as follows to clean the sediment trap:
1. Remove the intake side panel (see Intake Side
Panel Removal).
2. Turn the generator fuel supply off.
3.
See
Figure 4-19
. Unscrew and remove the cap (A).
Owner’s Manual for 60 Hz EcoGen™ Generators31
Maintenance
001821
A
B
WARNING
Explosion. Batteries emit explosive gases.
Always disconnect negative battery cable
first to avoid spark. Failure to do so could
result in death or serious injury.
(000238)
Figure 4-19. Cleaning the Sediment Trap
4. Use a clean-out tool (not provided) to remove
accumulated moisture and particles from the cap
and body (B).
5. Wipe the inside of each component with a clean,
dry, lint-free cloth.
6. Seal the threads of the cap with appropriate
sealing compound. Install the cap and handtighten.
7. Tighten the cap with an appropriately sized pipe
wrench. DO NOT overtighten.
8. Turn the generator fuel supply on. Check for leaks
by spraying all connection points with a noncorrosive gas leak detection fluid. The solution
should not be blown away or form bubbles.
9. Install the intake side panel.
Remove From, and Return To
Service Procedure
Remove From Service
If the generator will be out of service longer than 90 days,
proceed as follows to prepare the generator for storage:
1. Start the engine and let it warm up.
2. Close the fuel shutoff valve in the fuel supply line
and allow the engine to stop.
3. Once the engine has stopped, set the generator
MLCB (generator disconnect) to OFF (OPEN).
4. Disengage the connected loads to the generator.
5. See Figure 4-1. Remove battery charger AC input
T1/Neutral cable (has white sleeve) at controller.
NOTE: Allow the AVR to cool and the fan to stop before
removing the battery. Removing the battery before the
AVR has stopped can damage the AVR and injure the
operator.
6. Remove the 7.5 amp fuse from the generator’s
control panel.
7. Disconnect the battery cables. Remove the
negative cable first.
Attention After Submersion
DO NOT start or operate the generator if it has been
submerged in water. Have an IASD thoroughly clean, dry,
and inspect the generator following any submersion in
water. If the structure (home) has been flooded, it should
be inspected by a certified electrician to verify there won’t
be any electrical problems during generator operation or
when connected loads are engaged.
Corrosion Protection
Regular scheduled maintenance should be conducted to
perform a visual inspection of the unit for corrosion.
Inspect all metal components of the generator, including
the base frame, brackets, alternator can, the entire fuel
system (inside and outside of the generator), and
fastener locations. If there is corrosion found on
generator components (e.g. regulator, engine/alternator
mounts, fuel plenum, etc.), replace parts as necessary.
Periodically wash and wax the enclosure using
automotive type products. Do not spray the unit with a
hose or power washer. Use warm, soapy water and a soft
cloth. Frequent washing is recommended in salt water/
coastal areas. Spray engine linkages with a light oil such
as WD-40.
32Owner’s Manual for 60 Hz EcoGen™ Generators
8. Drain the oil completely while the engine is still
warm, and then refill the oil tank with oil.
9. Attach a tag to the engine indicating the viscosity
and classification of the new oil in the oil tank.
10. Remove the spark plug(s) and spray a fogging
agent into the spark plug(s) threaded openings.
Reinstall and tighten the spark plug(s) to
specification.
11. Remove the battery and store it in a cool, dry room
on a wooden board.
12. Clean and wipe down the entire generator.
Return to Service
Proceed as follows to return the unit to service after
storage:
1. Verify the connected loads are disengaged.
2. Check the tag on the engine for oil viscosity and
classification. Drain and refill with proper oil, if
necessary.
3. Check the state of the battery. (Unsealed batteries
only) Fill all cells of unsealed batteries to the
proper level with distilled water. DO NOT use tap
water. Recharge the battery to 100% state of
charge. Replace the battery if it will not maintain a
charge.
4. Clean and wipe down the entire generator.
5. Verify that the 7.5 amp fuse is removed from the
generator control panel.
6. Reconnect the battery. Observe battery polarity.
Damage may occur if the battery is connected
incorrectly. Install positive cable first.
7. Reconnect the battery charger AC input T1/Neutral
cable (white sleeve) at controller.
8. Open the fuel shutoff valve.
9. Insert the 7.5 amp fuse into the generator control
panel.
10. Press the MANUAL button to start the unit. Allow
the unit to warm up for a few minutes.
11. Complete the Installation Wizard information.
12. Press the control panel OFF button to stop the unit.
13. Engage the connected loads to the generator.
14. Set the control panel to AUTO.
The generator is ready for service.
Maintenance
NOTE: The current date and time must be reset when a
battery is dead or has been disconnected.
Generator is set to
OFF, but the engine
continues to run.
1. Blown fuse.
2. Loose, corroded, or defective battery cables.
3. Defective starter contact.
4. Defective starter motor.
5. Discharged battery.
1. No fuel.
2. Defective fuel solenoid (FS).
3. Open Wire 14 from controller.
4. Defective spark plug(s).
5. Valve clearance out of adjustment.
6. Fuel pressure too high
1. Air cleaner plugged or damaged.
2. Defective spark plug(s).
3. Incorrect fuel pressure.
4. Fuel selector in wrong position.
5. Valve(s) out of adjustment.
6. Internal engine issue.
1. Controller wired incorrectly.
2. Defective control board.
1. Correct short circuit condition by replacing 7.5
amp fuse in generator control panel. Contact an
Independent Authorized Service Dealer (IASD) if
fuse continues to blow.
2. Tighten, clean, or replace as necessary.*
3. *See #2.
4. *See #2.
5. Charge or replace battery.
1. Replenish fuel / turn on fuel valve.
2. *
3. *
4. Clean; check gap; replace plug(s) if necessary.
5. Reset valve clearance.
6. Verify proper fuel pressure
1. Check and clean air cleaner.
2. Clean; check gap; replace plug(s) as needed.
3. Confirm fuel pressure to regulator is 10–12 in
water column (19–22 mm Hg) for LP, and 3.5–7.0
in water column (9–13 mm Hg) for natural gas.
4. Turn fuel conversion valve to correct position.
5. Adjust valve clearance.
6. *
1. *
2. *
No AC output from
generator.
1. Main line circuit breaker (MLCB) (generator disconnect) is OFF (OPEN).
2. Generator internal failure.
3. Engine may be warming up. Refer to
Smart Start
No transfer to generator power after
startup.
Unit consumes
large amounts of oil.
* Contact an IASD for assistance.
1. MLCB (generator disconnect) is OFF (OPEN).
2. Engine may be warming up. Refer to
Smart Start
1. Excessive engine oil.
2. Defective engine breather.
3. Improper type or viscosity of oil.
4. Damaged gasket, seal, or hose.
5. Restricted air filter.
1. Reset generator disconnect to ON (CLOSED).
2. *
Cold
.
Cold
.
3. Check the controller screen to verify status.
1. Reset generator disconnect to ON (CLOSED).
2. Check the controller screen to verify status.
1. Adjust oil to proper level.
2. *
Engine Oil Requirements.
3. See
4. Check for oil leaks.
5. Replace air filter.
Owner’s Manual for 60 Hz EcoGen™ Generators35
Troubleshooting / Quick Reference Guide
Quick Reference Guide
To clear an active alarm, press the OFF button, the ENTER button, and then press AUTO. If the alarm reoccurs,
contact an IASD.
Active AlarmLEDProblemThings to CheckSolution
NONE
HIGH
TEMPERATURE
OVERLOAD
REMOVE LOAD
RPM SENSE LOSSRED
NOT ACTIVATEDNONE
NONEGREEN
LOW OIL
PRESSURE
RPM SENSE LOSSRED
FLASHING
GREEN
RED
RED
RED
Unit running in AUTO but
no power at L1 and L2.
Unit shuts down during
operation.
Unit shuts down during
operation.
Unit was running and
shut down, attempts to
restart.
Unit will not start in
AUTO with remote start
signal.
Unit will not start in
AUTO with remote start
signal.
Unit will not start in
AUTO with remote start
signal.
Unit will not start in
AUTO with remote start
signal.
Check MLCB.Check MLCB. If it is ON, contact an IASD.
Check the LEDs /
screen for alarms.
Check the LEDs /
screen for alarms.
Check the LEDs /
screen for alarms.
Check if screen says
unit not activated.
Check screen for start
delay countdown.
Check the LEDs /
screen for alarms.
Check the LEDs /
screen for alarms.
Check ventilation around the generator,
intake, exhaust, and rear of generator. If no
obstructions are present, contact an IASD.
Clear alarm and remove household loads
from the generator. Put in AUTO and
restart.
Clear alarm and remove household loads
from the generator. Put into AUTO and
restart. If generator does not start, contact
an IASD.
Refer to “Activation” in installation manual.
If the startup delay is greater than
expected, contact an IASD to adjust.
Check oil level and add oil as needed. If oil
level is correct, contact an IASD.
Clear alarm. Using the control panel, check
the battery by navigating to the BATTERY
MENU option from the MAIN MENU. If battery condition displays GOOD, contact an
IASD. If control panel displays CHECK
BATTERY, replace the battery.
Unit will not start in
OVERCRANKRED
LOW VOLTS
REMOVE LOAD
FUSE PROBLEMRED
OVERSPEEDRED
UNDERVOLTAGERED
36Owner’s Manual for 60 Hz EcoGen™ Generators
RED
AUTO with remote start
signal.
Unit will not start in
AUTO with remote start
signal.
Unit will not start in
AUTO with remote start
signal.
Unit will not start in
AUTO with remote start
signal.
Unit will not start in
AUTO with remote start
signal.
Check the LEDs /
screen for alarms.
Check the LEDs /
screen for alarms.
Check the LEDs /
screen for alarms.
Check the LEDs /
screen for alarms.
Check the LEDs /
screen for alarms.
Check fuel line shutoff valve is ON. Clear
alarm. Start the unit in MANUAL. If it does
not start, or starts and runs rough, contact
an IASD.
Clear alarm and remove household loads
from the generator. Put in AUTO and
restart.
Check the 7.5 amp fuse. If it is blown,
replace it with an ATO 7.5 amp fuse. If the
fuse is intact, contact an IASD.
Contact an IASD.
Contact an IASD.
Troubleshooting / Quick Reference Guide
Active AlarmLEDProblemThings to CheckSolution
UNDERSPEEDRED
STEPPER
OVERCURRENT
MISWIRERED
OVERVOLTAGERED
LOW BATTERYYELLOW
BATTERY
PROBLEM
CHARGER
WARNING
RED
YELLOW
YELLOW
Unit will not start in
AUTO with remote start
signal.
Unit will not start in
AUTO with remote start
signal.
Unit will not start in
AUTO with remote start
signal.
Unit will not start in
AUTO with remote start
signal.
Yellow LED illuminated in
any state.
Yellow LED illuminated in
any state.
Yellow LED illuminated in
any state.
Check the LEDs /
screen for alarms.
Check the LEDs /
screen for alarms.
Check the LEDs /
screen for alarms.
Check the LEDs /
screen for alarms.
Check the screen for
additional information.
Check the screen for
additional information.
Check the screen for
additional information.
Contact an IASD.
Contact an IASD.
Contact an IASD.
Contact an IASD.
Clear alarm. Using the control panel, check
the battery by navigating to the BATTERY
MENU option from the MAIN MENU. If battery condition displays GOOD, contact an
IASD. If control panel displays CHECK
BATTERY, replace the battery.
Contact an IASD.
Contact an IASD.
SERVICE AYELLOW
SERVICE BYELLOW
INSPECT BATTERY YELLOW
Yellow LED illuminated in
any state.
Yellow LED illuminated in
any state.
Yellow LED illuminated in
any state.
Check the screen for
additional information.
Check the screen for
additional information.
Check the screen for
additional information.
Perform SERVICE A maintenance. Press
ENTER to clear.
Perform SERVICE B maintenance. Press
ENTER to clear.
Inspect battery. Press ENTER to clear.
Owner’s Manual for 60 Hz EcoGen™ Generators37
Troubleshooting / Quick Reference Guide
AVR Troubleshooting
Table 5-1. AVR Troubleshooting
Ecode/Active
LED ProblemThings to
Alarm
1048 VSCF Overload REDUnit shuts down
during operation.
1049 VSCF Overload REDUnit shuts down
during operation.
1051 VSCF High
Battery
1052 VSCF DC
Overvoltage
1053 VSCF Gate
Fault
1054 VSCF IGBT
Overtemp.
1055 VSCF Phase
Error
1056 VSCF
Undervoltage
YELLOWYellow LED
illuminated in any
state.
REDUnit shuts down
during operation.
REDUnit shuts down
during operation
or starting.
REDUnit shuts down
during operation
or starting.
REDUnit shuts down
during starting.
REDUnit shuts down
during operation
or starting.
Check
Check the
LEDs/Screen
for alarms.
Check the
LEDs/Screen
for alarms.
Check the
LEDs/Screen
for alarms.
Check the
LEDs/Screen
for alarms.
Check the
LEDs/Screen
for alarms.
Check the
LEDs/Screen
for alarms.
Check the
LEDs/Screen
for alarms.
Check the
LEDs/Screen
for alarms.
Possible Causes/Solution
Alternator, AVR or wiring is damaged.
Contact servicing dealer.
Generator output is shorted or severely overloaded.
Identify and clear the overload, and then restart.
Voltage supply to the AVR is high. If an external battery
charger is in use, contact installing dealer to correct
installation. If an external battery charger is NOT in use,
contact servicing dealer.
Probable causes are:
1) The generator was temporarily overloaded.
2) The output was temporarily shorted. Try to restart the
unit.
AVR is damaged. Contact servicing dealer.
Probable causes are:
1) Replace AVR filter. Inspect fan.
2) Intake or exhaust air path is blocked. Check intake and
exhaust.
3) The BIG fan is not running (Note: only runs when the
engine is running). KEEP FINGERS AWAY FROM FAN
HOUSING- PERSONAL INJURY CAN OCCUR IF FAN IS
RUNNING. Contact servicing dealer.
4) Air leak in AVR enclosure. Contact servicing dealer.
5) Engine running too hot. Inspect air intake and exhaust.
6) Ambient temperature has risen above 60º F. Derate the
generator output per specifications.
An incorrect voltage and frequency has been detected
during starting. Probable causes are:
1) Alternator damage. Contact servicing dealer.
2) Generator has started into a severe load. Manually
operate generator breaker and try to restart unit. If
problem persists, remove load and attempt to restart unit
again.
3) The engine may not be reaching its prescribed speed.
Proceed as follows:
• Verify stepper motor is moving and linkage is free.
• Verify stepper motor is plugged in.
• Verify gas pressure is within specified limits.
The generator output voltage is too low. Probable causes
are:
1) The load is too large. Remove load and attempt to
restart unit.
2) Alternator or AVR damage. Contact servicing dealer.
38Owner’s Manual for 60 Hz EcoGen™ Generators
Troubleshooting / Quick Reference Guide
Table 5-1. AVR Troubleshooting
Ecode/Active
LED ProblemThings to
Alarm
1057 VSCF
Overvoltage
1058 VSCF DC
Undervoltage
1059 VSCF
Field Loss
1061 VSCF
Field Loss
1060 Big Fan Failure REDUnit shuts down
1065 Overfrequency REDUnit shuts down
1066 VSCF Speed
mismatch
1070 Small fan
failure
REDUnit shuts down
during operation
or starting.
REDUnit shuts down
during operation
or starting.
REDUnit shuts down
during starting.
REDUnit shuts down
during operation.
during operation.
during operation.
REDUnit shuts down
during Operation
or starting.
YELLOW“Small fan failure”
is displayed. If
unit was running
in AUTO, it will
continue to run for
80 minutes to cool
electronics
without fan.
Check
Check the
LEDs/Screen
for alarms.
Check the
LEDs/Screen
for alarms.
Check the
LEDs/Screen
for alarms.
Check the
LEDs/Screen
for alarms.
Check the
LEDs/Screen
for alarms.
Check the
LEDs/Screen
for alarms.
Check the
LEDs/Screen
for alarms.
Check the
LEDs/Screen
for alarms.
Possible Causes/Solution
Probable causes are:
1) The generator has been overloaded. Remove load and
attempt to restart unit.
2) Generator has started into a severe load. Manually
operate generator breaker and try to restart unit. If
problem persists, remove load and attempt to restart unit
again.
The DPE winding supplies this voltage.
1) Alternator damage. Contact servicing dealer.
Unit detects no output voltage while starting.
1) Alternator damage. Contact servicing dealer.
Unit detects loss of output voltage while running.
1) Alternator damage. Contact servicing dealer.
This alarm occurs when the AVR electronics temperature
exceeds 70 C. Possible causes are:
1) AVR filter faulty. Replace AVR filter.
2) Intake or exhaust air path is blocked. Check intake and
exhaust.
3) The BIG fan is not running (Note: only runs when the
engine is running). KEEP FINGERS AWAY FROM FAN
HOUSING- PERSONAL INJURY CAN OCCUR IF FAN IS
RUNNING. Contact servicing dealer.
4) Air leak in AVR enclosure. Contact servicing dealer.
5) Engine running too hot. Inspect air intake and exhaust.
6) Ambient temperature has risen above 60º F. Derate the
generator output per specifications.
If message is displayed when generator is stopped, also
check SMALL fan. Small fan RUNS for 80 minutes after
generator is stopped and keeps electronics cool during
heat soak.
Probable causes are:
1) Overload. Remove load and attempt to restart unit.
2) RPM sensor has failed. Contact servicing dealer.
3) Stepper motor problem. Contact servicing dealer.
1) Fuel problem (pressure loss). Check fuel supply and
attempt to restart unit.
2) Large overload. Remove load and attempt to restart
unit.
3) Throttle or engine problem. Contact servicing dealer.
Small fan current incorrect. Probable causes are:
1) Fan wiring or mechanical problem. Contact servicing
dealer.
2) Air path is blocked. Check AVR filter.
KEEP FINGERS AWAY FROM FAN HOUSING-
PERSONAL INJURY CAN OCCUR IF FAN IS RUNNING.
Owner’s Manual for 60 Hz EcoGen™ Generators39
Troubleshooting / Quick Reference Guide
AVR Diagnostics
Table 5-2. AVR Diagnostics
SymptomPossible Causes
Generator stalls when large load is
supplied.
Output voltage is low/high.Voltage calibration incorrect. Contact servicing dealer.
Generator does not pull full power.Current calibration incorrect. Contact servicing dealer.
Total load is too big for the generator. Loads must be less than 10 kW or 2 hp when
operating under 3600 rpm.Contact installing dealer to correct installation.