
LISTED
O Manual
,10, 12, 14, 16, 17 & Air-cooled,
Automatic Standby Generators
DO NOT LiFT UNiT BY ROOF!
z_ Not intended for use as Primary Power in place of utility Z_
DEADLY EXHAUST FUMES. OUTDOOR iNSTALLATiON ONLY!
or in life-support applications.

iNTRODUCTiON
Thank you for purchasing this compact, high per-
formance, air-cooled, engine-driven generator. It is
designed to automatically supply electrical power to
operate critical loads during a utility power failure.
This unit is factory installed in an all-weather, metal
enclosure that is intended exclusively for outdoor
installation. This generator will operate using either
vapor withdrawn liquid propane (LP) or natural gas
(NG).
NOTE:
This generator is suitable for supplying typical
residential loads such as Induction Motors (sump
pumps, refrigerators, air conditioners, furnaces,
etc.), Electronic Components (computer, monitor,
TV, etc.), Lighting Loads and Microwaves.
@ READ THIS MANUAL THOROUGHLY
If any portion of this manual is not understood, con-
tact the nearest Dealer for starting, operating and
servicing procedures.
Throughout this publication, and on tags and decals
affixed to the generator, DANGER, WARNING,
CAUTION and NOTE blocks are used to alert person-
nel to special instructions about a particular opera-
tion that may be hazardous if performed incorrectly
or carelessly. Observe them carefully. Their defini-
tions are as follows:
After this heading, read instructions that, if not
strictly complied with, wi[[ result in serious person-
al injury, including death, in addition to property
damage.
-_ WARN|NG _k-
After this heading, read instructions that, if not
strictly complied with, may result in serious person-
al injury or property damage.
& CAUTIONA-
After this heading, read instructions that, if not
strictly complied with, could result in damage to
equipment and/or property.
NOTE:
After this heading, read explanatory statements
that require special emphasis.
These safety warnings cannot eliminate the haz-
ards that they indicate. Common sense and strict
compliance with the special instructions while
performing the service are essential to preventing
accidents.
Four commonly used safety symbols accompany the
DANGER, WARNING and CAUTION blocks. The type
of information each indicates follows:
This symbol points out potential explosion haz-
ard.
Z_ This symbol points out potential fire hazard.
/_ This symbol points out potential electrical shock
hazard.
The operator is responsible for proper and safe use
of the equipment. The manufacturer strongly recom-
mends that the operator read this Owner's Manual
and thoroughly understand all instructions before
using this equipment. The manufacturer also strong-
ly recommends instructing other users to properly
start and operate the unit. This prepares them if they
need to operate the equipment in an emergency.
@ CONTENTS
This manual contains pertinent owner's information
for these models:
. 7 kW NG, 8 kW LR single-cylinder GH-410 Engine
. 9 kW NG, 10 kW LR V-twin GT-530 Engine
. 12 kW NG, 12 kW LR V-twin GT-990 Engine
. 13 kW NG, 14 kW LR V-twin GT-990 Engine
. 16 kW NG, 16 kW LR V-twin GT-990 Engine
. 16 kW NG, 17 kW LR V-twin GT-990 Engine
. 18 kW NG, 20 kW LR V-twin GT-999 Engine
@ OPERATION AND MAINTENANCE
It is the operator's responsibility to perform all safety
checks, to make sure that all maintenance for safe
operation is performed promptly, and to have the
equipment checked periodically by a Dealer. Normal
maintenance service and replacement of parts are the
responsibility of the owner/operator and, as such, are
not considered defects in materials or workmanship
within the terms of the warranty. Individual operating
habits and usage contribute to the need for mainte-
nance service.
Proper maintenance and care of the generator ensures
a minimum number of problems and keep operating
expenses at a minimum. See a Dealer for service aids
and accessories.
@ HOW TO OBTAIN SERVICE
When the generator requires servicing or repairs,
contact a Dealer for assistance. Service technicians
are factory-trained and are capable of handling all
service needs.
When contacting a Dealer about parts and service,
always supply the complete model number and serial
number of the unit as given on its data decal, which is
located on the generator. See section "The Generator"
for decal location.
Model No. Serial No.
/_ This symbol points out important safety infor-
mation that, if not followed, could endanger
personal safety and/or property of others.

Table of Contents
Air-cooled Generators
NTS
introduction ........................ inside Front Cover
Read This Manual Thoroughly ........................ IFC
Contents .......................................................... IFC
Operation and Maintenance ............................ IFC
How to Obtain Service ..................................... IFC
Table of Contents ...............................................1
Safety Rules ......................................................... 2
Standards Index .................................................. 3
Section 1 - General information ................... 4
1.1
Unpacking/Inspection .................................... 4
1.2
Protection Systems ........................................ 4
1.3
NEC Requirement for Arc Fault Circuit
Interruption Breaker for Bedrooms ............... 4
1.4
Emission Information .................................... 5
1.5
The Generator ............................................... 6
1.6
Specifications ................................................ 7
1.7
System Set LED ............................................ 8
1.8
Fuel Requirements and Recommendations .... 8
1.9
Fuel Consumption ......................................... 8
1.10
Reconfiguring the Fuel System ....................... 9
1.11
Location ...................................................... 10
1.12
Battery Requirements .................................. 11
1.13
Battery Installation ...................................... 11
1.14
The Battery .................................................. 12
1.15
Battery Charger ........................................... 12
Section 3 - Operation .....................................16
3.1 Control Panel Interface ................................ 16
3.2 Automatic Transfer Operation ..................... 17
3.3 Sequence of Automatic Operation ................ 18
3.4 Manual Transfer Operation ......................... 19
3.5 Side Compartment (V-twin Only) ................. 20
3.6 Protection Systems ...................................... 20
Section 4 - Maintenance .............................. 22
4.1 Fuse ............................................................. 22
4.2 Checking the Engine Oil Level ..................... 22
4.3 Changing the Engine Oil .............................. 23
4.4 Changing the Engine Air Cleaner ................. 23
4.5 Spark Plug(s) .............................................. 24
4.6 Battery Maintenance .................................... 25
4.7 Adjusting GH-410/GT-530/990/999
Valve Clearance ............................................ 25
4.8
Cooling System ............................................ 26
4.9
Attention After Submersion ......................... 26
4.10
Corrosion Protection ................................... 27
4.11
Out of Service Procedure ............................. 27
4.12
Service Schedule ......................................... 28
Section 5 - Troubleshooting ........................ 29
5.1 Troubleshooting Guide ................................ 29
Section 6 - Appendix .....................................30
6.1 Menu System Navigation ............................. 30
Section 2 - Post installation Start-up
and Adjustments ........................13
2.1 Before Initial Startup ................................... 13
2.2 Check Transfer Switch Operation ................ 13
2.3 Electrical Checks ......................................... 13
2.4 Generator Tests Under Load ....................... 14
2.5 Checking Automatic Operation .................... 14
2.6 Engine Governor Adjustment ...................... 15
2.7 Voltage Regulator Adjustment ...................... 15
Section 7 - Notes ............................................ 32
Section 8 - installation Diagrams .............. 33
Section 9 - Warranty ...................................... 36

SAFETYRULES
iMPORTANT SAFETYiNSTRUCTiONS
Air-cooled Generators
_ SAVE THESE INSTRUCTIONS - The,manufacturer suggests that these rules for safe operation
be copied and posted near the unit s installation site. Safety should be stressed to all opera-
tots and potential operators of this equipment.
A GENERALHAZARDSA
. For safety reasons, the manufacturer recommends
that the installation, initial start-up and main-
tenance of this equipment is carried out by a
Dealer.
. The engine exhaust fumes contain carbon monox-
ide, which can be DEADLY. This dangerous gas, if
breathed in sufficient concentrations, can cause
unconsciousness or even death. Do NOT alter or
add to the exhaust system or do anything that
Study these SAFETY RULES carefully before install-
ing, operating or servicing this equipment. Become
familiar with this Owner's Manual and with the
unit. The generator can operate safely, efficiently and
reliably only if it is properly installed, operated and
maintained. Many accidents are caused by failing to
follow simple and fundamental rules or precautions.
The manufacturer cannot anticipate every possible
circumstance that might involve a hazard. The warn-
ings in this manual, and on tags and decals affixed
to the unit are, therefore, not all-inclusive. If using
a procedure, work method or operating technique
the manufacturer does not specifically recommend,
ensure that it is safe for others. Also make sure the
procedure, work method or operating technique uti-
lized does not render the generator unsafe.
/_ Despite the safe design of this generator,
operating this equipment imprudently, neglecting
its maintenance or being careless can cause
possible injury or death. Permit only responsible
and capable persons to operate or maintain this
equipment.
/_ Potentially lethal voltages are generated by
these machines. Ensure all steps are taken to
render the machine safe before attempting to
work on the generator.
/_ Parts of the generator are rotating and/or hot
during operation. Exercise care near running
generators.
might render the system unsafe or in noncompli-
ance with applicable codes and standards.
. Keep hands, feet, clothing, etc., away from drive
belts, fans, and other moving or hot parts. Never
remove any drive belt or fan guard while the unit
is operating.
. Adequate, unobstructed flow of cooling and venti-
lating air is critical to correct generator operation.
Do not alter the installation or permit even partial
blockage of ventilation provisions, as this can seri-
ously affect safe operation of the generator. The
generator MUST be installed outdoors.
* When working on this equipment, remain alert
at all times. Never work on the equipment when
physically or mentally fatigued.
. Inspect the generator regularly, and contact the
nearest Dealer for parts needing repair or replace-
ment.
. Before performing any maintenance on the gen-
erator, disconnect its battery cables to prevent
accidental start up. Disconnect the cable from the
battery post indicated by a NEGATIVE, NEG or
(-) first, then remove the POSITIVE, POS or (+)
cable. When reconnecting the cables, connect the
POSITIVE cable first, the NEGATIVE cable last.
. Never use the generator or any of its parts as a
step. Stepping on the unit can stress and break
parts, and may result in dangerous operating con-
ditions from leaking exhaust gases, fuel leakage,
oil leakage, etc.
2

iMPORTANT SAFETY iNSTRUCTiONS
Air-cooled Generators
SAFETYRULES
ELECTRICAL HAZARDS
* All generators covered by this manual produce
dangerous electrical voltages and can cause fatal
electrical shock. Utility power delivers extremely
high and dangerous voltages to the transfer switch
as does the standby generator when it is in opera-
tion. Avoid contact with bare wires, terminals,
connections, etc., while the unit is running. Ensure
all appropriate covers, guards and barriers are in
place, secured and/or locked before operating the
generator. If work must be done around an oper-
ating unit, stand on an insulated, dry surface to
reduce shock hazard.
* Do not handle any kind of electrical device while
standing in water, while barefoot, or while hands or
feet are wet. DANGEROUS ELECTRICAL SHOCK
MAY RESULT.
. The National Electrical Code (NEC) requires the
frame and external electrically conductive parts of
the generator to be connected to an approved earth
ground. Local electrical codes also may require
proper grounding of the generator electrical system.
* After installing this home standby electrical sys-
tem, the generator may crank and start at any
time without warning. When this occurs, load cir-
cuits are transferred to the STANDBY (generator)
power source. To prevent possible injury if such a
start and transfer occur, always set the generator's
AUTO/OFF/MANUAL switch to its OFF position
before working on equipment and remove the 15A
fuse from the generator control panel.
* In case of accident caused by electric shock, imme-
diately shut down the source of electrical power. If
this is not possible, attempt to free the victim from
the live conductor. AVOID DIRECT CONTACT WITH
THE VICTIM. Use a nonconducting implement,
such as a dry rope or board, to free the victim from
the live conductor. If the victim is unconscious,
apply first aid and get immediate medical help.
* Never wear jewelry when working on this equip-
ment. Jewelry can conduct electricity resulting in
electric shock, or may get caught in moving com-
ponents causing injury.
FiREHAZARDS/g,
* For fire safety, the generator must be installed and
maintained properly. Installation must always
comply with applicable codes, standards, laws
and regulations. Adhere strictly to local, state
and national electrical and building codes. Comply
with regulations the Occupational Safety and
Health Administration (OSHA) has established.
Also, ensure that the generator is installed in
accordance with the manufacturer's instructions
and recommendations. Following proper installa-
tion, do nothing that might alter a safe installation
and render the unit in noncompliance with the
aforementioned codes, standards, laws and regu-
lations.
* Keep a fire extinguisher near the generator at all
times. Extinguishers rated 'TkBC" by the National
Fire Protection Association are appropriate for
use on the standby electric system. Keep the extin-
guisher properly charged and be familiar with its
use. Consult the local fire department with any
questions pertaining to fire extinguishers.
EXPLOSION HAZARDS
Do not smoke around the generator. Wipe up any
fuel or oil spills immediately. Ensure that no com-
bustible materials are left in the generator com-
partment, or on or near the generator, as FIRE or
EXPLOSION may result. Keep the area surround-
ing the generator clean and free from debris.
Gaseous fluids such as natural gas and liquid pro-
pane (LP) gas are extremely EXPLOSIVE. Install
the fuel supply system according to applicable
fuel-gas codes. Before placing the home standby
electric system into service, fuel system lines must
be properly purged and leak tested according to
applicable code. After installation, inspect the fuel
system periodically for leaks. No leakage is permit-
ted.
• STANDARDS iNDEX
In the absence of pertinent standards, codes, regu-
lations and laws, the published information listed
below may be used as installation guide for this
equipment.
1. NFPA No. 37, STATIONARY COMBUSTION
ENGINES AND GAS TURBINES, available from
the National Fire Protection Association, 470
Atlantic Avenue, Boston, MA 02210.
2. NFPA No. 76A, ESSENTIAL ELECTRICAL
SYSTEMS FOR HEALTH CARE FACILITIES,
available same as Item 1.
3. NFPA No. 54, NATIONAL FUEL GAS CODE,
available same as Item 1.
4. NFPA No. 58, AMERICAN NATIONAL STANDARD
FOR STORAGE AND HANDLING OF LIQUEFIED
PETROLEUM GAS, available same as Item 1.
5. NFPA No. 70, NFPA HANDBOOK OF NATIONAL
ELECTRIC CODE, available same as Item 1.
6. Article X, NATIONAL BUILDING CODE, available
from the American Insurance Association, 85
John Street, New York, N.Y. 10038.
7. AGRICULTURAL WIRING HANDBOOK, avail-
able from the Food and Energy Council, 909
University Avenue, Columbia, MO 65201.
8. ASAE EP-3634, INSTALLATION AND
MAINTENANCE OFFARM STANDBYELECTRICAL
SYSTEMS, available from the American Society
of Agricultural Engineers, 2950 Niles Road, St.
Joseph, MI 49085.
9. NFPA No. 30, FLAMMABLE AND COMBUSTIBLE
LIQUIDS CODE, available same as Item 1.
3

" GENERAL "
INFORMATON
/_ Only qualified electricians or contractors should
attempt such installations, which must comply
strictly with applicable codes, standards and regu-
lations.
Air-cooled Generators
1.1 UNPACKING/INSPECTION
After unpacking, carefully inspect the contents for
damage.
. This standby generator set is ready for installa-
tion with a factory supplied and pre-mounted base
pad and has a weather protective enclosure that is
intended for outdoor installation only.
. This UL listed standby generator set may be pack-
aged with an automatic transfer switch with built
in load center. The combination transfer switch
and load center is pre-wired with a two foot and
30 foot conduit. Circuit breakers for emergency
circuit connections are included (if equipped).
. This UL listed, 2-pole switch is rated at 100 or 200
AC amperes at 250 volts maximum. The 100 Amp
transfer switch is for indoor use only. The 200
Amp transfer switch is for indoor/outdoor use
(if equipped).
-,_ WARNING _-
/_ if this generator is used to power electrical load
circuits normally powered by a utility power
source, it is required by code to install a transfer
switch. The transfer switch must effectively isolate
the electrical system from the utility distribution
system when the generator is operating (NEC 700,
701 & 702). Failure to isolate an electrical system
by such means will result in damage to the gen-
erator and also may result in injury or death to
utility power workers due to backfeed of electrical
energy.
If any loss or damage is noted at time of delivery, have
the person(s) making the delivery note all damage on
the freight bill or affix their signature under the con-
signor's memo of loss or damage.
If a loss or damage is noted after delivery, separate
the damaged materials and contact the carrier for
claim procedures.
"Concealed damage" is understood to mean damage
to the contents of a package that is not in evidence at
the time of delivery, but is discovered later.
To properly open the roof, press down on the cen-
ter top lip and release the latch. If pressure is not
applied from the top, the roof may appear stuck.
Always verify that the side lock is unlocked before
attempting to lift the roof.
Section 1 - Genera[ information
1.2 PROTECTION SYSTEMS
Unlike an automobile engine, the generator may have
to run for long periods of time with no operator pres-
ent to monitor engine conditions. For that reason,
the engine is equipped with the following systems
that protect it against potentially damaging condi-
tions:
1. Low Oil Pressure Sensor
2. High Temperature Sensor
3. Overcrank
4. Overspeed
5. RPM Sensor
6. Low Battery
There are readouts on the control panel to notify
personnel that one of these failures has occurred.
There is also a System Set LED (single cylinder) or a
Status message on the display (V-twins) that displays
when all of the conditions described in the "System
Set LED" section are true.
1.3 NEC REQUIREMENTFORARC
FAULTCIRCUITiNTERRUPTION
BREAKER FOR BEDROOMS
In 2001, the National Electric Code (NEC) intro-
duced a requirement for new construction. This new
requirement indicates the need for Arc Fault Circuit
Interrupters to be used to protect the complete
branch circuit that feeds a dwelling bedroom. The
actual NEC requirement is indicated below.
@ 1.3.1 SECTION 110.11 ARC FAUET CIRCUIT
INTERRUPTER PROTECTION
1. Definition: An arc fault circuit interrupter is a
device intended to provide protection from the
effects of arc faults by recognizing characteristics
unique to arcing and by functioning to de-ener-
gize the circuit when an arc fault is detected.
2. Dwelling Unit Bedrooms: All branch circuits that
supply 125 volt, single-phase, 15 and 20 ampere
outlets installed in dwelling unit bedrooms shall
be protected by an arc fault circuit interrupter
listed to provide protection of the entire branch
circuit.
Section 210.12 requires that AFCI protection be
provided on branch circuits that supply outlets
(receptacle, lighting, etc.) in dwelling bedrooms. The
requirement is limited to 15 and 20 ampere, 125
volt circuits. There is no prohibition against provid-
ing AFCI protection on other circuits or in locations
other than bedrooms. Because circuits are often
shared between a bedroom and other areas such as
closets and hallways, providing AFCI protection on
the complete circuit would comply with 210.12.
4

Section 1 - General information
Air-cooled Generators
GENERAL
NFORMATON
If during the installation of the home standby system
the decision is made to provide back up power to a
bedroom branch circuit, then the circuit breaker in
the transfer switch should be replaced with an Arc
Fault Circuit Interrupter.
It is most important that breakers only be switched
like for like. For instance, if replacing a 15A breaker,
it MUST be replaced with a 15A AFCI breaker.
Likewise, a 20A breaker MUST be replaced with a
20A AFCI.
These AFCI breakers are available at the nearest
hardware store.
Siemens Item #
Ql15AF
Q120AF
Description
15A Single Pole AFCI
20A Single Pole AFCI
1.4 EMISSION INFORMATION
The Environmental Protection Agency requires that
this generator complies with exhaust emission stan-
dards. This generator is certified to meet the appli-
cable EPA emission levels. Additional information
regarding the requirements set by the EPA is as fol-
lows:
The generator is certified for use as a stationary
engine for standby power generation. Any other use
may be a violation of federal and/or local laws. It is
important that to follow the maintenance specifica-
tions in the "Maintenance" section to ensure that the
engine complies with the applicable emission stan-
dards for the duration of the engine's life. This engine
is certified to operate on Liquid Propane fuel and
pipeline Natural Gas. The emission control system
on the generator consists of the following:
. Fuel Metering System
Carburetor/mixer assembly
Fuel regulator
Air Induction System
Intake pipe/manifold
Air cleaner
Ignition System
Spark plug
Ignition module
The Emissions Compliance Period referred to on the
Emissions Compliance Label indicates the number of
operating hours for which the engine has been shown
to meet Federal emission requirements. See the table
below to determine the compliance period for the
generator. The displacement of the generator is listed
on the Emissions Compliance Label.
Displacement Category Compliance Period
A 300 Hours
< 66 ce B 125 Hours
C 50 Hours
> 66 cc -
< 225 cc
> 225 ce B
A
B
C
A
C
500 Hours
250 Hours
125 Hours
1000 Hours
500 Hours
250 Hours
5

" GENERAL "
INFORMATON
Air-cooled Generators
1.5 THE GENERATOR
Section | - General information
Figure 1.1 - 8kW, Single Cylinder, GH-410 Engine
(door removed)
Roof Latch
L
Exhaust -_.
Enclosure
'b
Oil
Dipstick
Data Label Control
(see sample) Panel
\
\
\- J
Jio i
I
Composite Base Battery Compartment
Oil Filter
Circuit
J _ Breaker
2 iI !
j Air Filter
I Fuel Inlet
(back)
Fuel
Regulator
Figure 1.2 - IOkVV, V-twin, GT-530 Engine
(door removed)
Roof Latch
Oil Data Label Control _F
Dipstick (see sample) Panel
Exhaust .__
Enclosure
Composite Base Oil Filter Battery Compartment
Circuit
jBreaker
_i- Air
Filter
1Fuel Inlet
(back)
Fuel
Regulator
Exhaust
Enclosure
Figure 1.3- 12, 14, 16, 17 and 20kW, V-twin,
GT-990/GT-999 Engine (door removed)
RoofLatch
1
CircuitBreakers
(All17&20kW)
/
1_
j-Fuel Inlet
C
_ Fuel
: j
/
CompositeBase
OilFilter
Battery Compartment
GFClOutlet
(back)
Regulator
Data Label Sample
MODEL
SERIAL
VOLTS
AMPS
1 PH, 60 Hz, RPM ,3600
RAINPROOF ENCLOSURE FITTEE
CLASS H INSULATION
RATED AMBIENT TEMP - 25°(
FOR STANDBY SERVICE
IItI!UTR_L FLQ_TINQ
MAX LOAD UNBALANCE-50%
WHITEWATER, WIS
MADE IN U,S.A,
1
6

Section 1 - General information
Air-cooled Generators
GENERAL
NFORMATON
1.6 SPECiFiCATiONS
• 1.6.1 GENERATOR
Model 8kW 10kW 12kW 14kW 16kW 17kW 20kW
Rated Maximum 7,000 NG 9,000 NG 12,000 NG 13,000 NG 16,000 NG 16,000 NG 18,000 NG
Power Capacity (Watts*) 8,000 LP 10,000 LP 12,000 LP 14,000 LP 16,000 LP 17,000 LP 20,000 LP
Rated Voltage 120/240
Rated Maximum Load Current (Amps)
120 Volts** (NG/LP) 58.3/66.6 75.0/83.3 100.0/100.0 108.3/116.6 133.3/133.3 133.3/141.6 150.0/166.6
240 Volts (NG/LP) 29.2/33.3 37.5/41.6 50.0/50.0 54.2/58.3 66.6/66.6 66.6/70.8 75.0/83.3
Main Circuit Breaker 35 Amp 45 Amp 50 Amp 60 Amp 65 Amp 65 Amp 100 Amp
Circuits*** 50A, 240V 1 1 1
40A, 240V 1 1 1 1
30A, 240V 1 1 1
20A, 240V 1 1 1 1
20A, 120V 1 3 3 4 5 5
15A, 120V 5 3 5 4 5 5
Phase 1
Number of Rotor Poles 2
Rated AC Frequency 60 Hz
Battery Requirement Volts and 350 Group 26R, 12 Volts and 525 CCA Mininmm
Weight (unit only in lbs.) 340 387 439 439 439 455/421 450
Enclosure Steel Steel Steel Steel Steel Steel/Aluminum Aluminum
Normal Operating Range -20 ° F (-28.8 ° C) to 77 ° F (25 ° C)
* Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power and condition,
etc. Maximum power decreases about 3.5 percent for each 1,000 %et above sea leveh and also will decrease about 1 percent for each 6 C (10 F) above 16 C
(60 F) ambient temperature.
** Load current values shown for 120 volts are maximum TOTAL values for two separate circuits. The maximum current in each circuit must not exceed the
value stated for the 240 volts.
*** Circuits to be moved must be protected by same size breaker. For example, a 15 amp circuit in the main panel must be a 15 amp circuit in the trans%r
switch.
Group 26R, 12
CCA Minimum
ld_.1 ENGINE
Model 8 kW I0 kW 12/14/16/17 kW 20 kW
Type of Engine GH-410 GT-530 GT-990 GT-999
Number of Cylinders 1 2 2 2
Rated Horsepower @ 3,600 rpm 14.8 18 32 36
Displacement 410cc 530cc 992cc 999cc
Cylinder Block Aluminum w/Cast Iron Sleeve
Valve Arrangement Overhead Valves
Ignition System Solid-state w/Magneto
Recommended Spark Plug RC 14YC BPR6HS RC 14YC RC 12YC
Spark Plug Gap 0.76 mm (0.030 inch) 0.76 mm (0.030 inch) 1.02 mm (0.040 inch) 0.76 mm (0.030 inch)
Compression Ratio 8.6:1 9.5:1 9.5:1 9.5:1
Starter 12 VDC
Oil Capacity Including Filter Approx. 1.5 Qts Approx. 1.7 Qts Approx. 1.7 Qts Approx. 1.7 Qts
Recommended Oil Filter Part # 070185F
Recommended Air Filter Part # 0G3332 Part # 0E9581 Part # 0C8127 Part # 0G5894
Operating RPM 3,600
7

° GENERAL °
INFORMATION
Section ] - General information
Air-cooled Generators
1.7 SYSTEMSETLED
The "System Set" LED (single cylinder) or "Ready to
Run" on the display (v-twin) is ready when all of the
following conditions are true:
1. The AUTO/OFF/MANUAL switch is set to the
AUTO position.
2. The utility voltage being supplied to the unit is
being sensed by the PCB. If the utility sense volt-
age is not connected to the unit or if it is below
approximately 150-160 volts AC, then the system
set light will flash rapidly (8kW). This indicates
that if the AUTO/OFF/MANUAL switch is placed
in the Auto position, the generator will start.
3. No alarms are present, for example, low oil pres-
sure, high temperature, etc.
1.8 FUEL REQUIREMENTS
AND RECOMMENDATIONS
With LP gas, use only the vapor withdrawal sys-
tem. This type of system uses the vapors formed
above the liquid fuel in the storage tank.
The engine has been fitted with a fuel carburetion
system that meets the specifications of the 1997
California Air Resources Board for tamper-proof dual
fuel systems. The unit will run on natural gas or LP
gas, but it has been factory set to run on natural gas.
Should the primary fuel need to be changed to LP
gas, the fuel system needs to be reconfigured. See the
reconfiguring the Fuel System section for instructions
on reconfiguration of the fuel system.
Recommended fuels should have a Btu content of at
least 1,000 Btus per cubic foot for natural gas; or at
least 2,520 Btus per cubic foot for LP gas. Ask the
fuel supplier for the Btu content of the fuel.
Required fuel pressure for natural gas is five (5)
inches to seven (7) inches water column (0.18 to
0.25 psi); and for liquid propane, I0 inches to 12
inches of water column (0.36 to 0.43 psi). The
primary regulator for the propane supply is NOT
INCLUDED with the generator.
NOTE:
All pipe sizing, construction and layout must com-
ply with NFPA 54 for natural gas applications and
NFPA 58 for liquid propane applications. Once the
generator is installed, verify that the fuel pressure
NEVER drops below four (4) inches water column
for natural gas or I0 inches water column for liq-
uid propane.
Prior to installation of the generator, the installer
should consult local fuel suppliers or the fire mar-
shal to check codes and regulations for proper instal-
lation. Local codes will mandate correct routing of
gaseous fuel line piping around gardens, shrubs and
other landscaping to prevent any damage.
8
Special considerations should be given when install-
ing the unit where local conditions include flooding,
tornados, hurricanes, earthquakes and unstable
ground for the flexibility and strength of piping and
their connections.
Use an approved pipe sealant or joint compound on
all threaded fitting.
All installed gaseous fuel piping must be purged and
leak tested prior to initial start-up in accordance with
local codes, standards and regulations.
1.9 FUEL CONSUMPTION
Unit
7/8kW 77 140 0.94/34 1.68/62
9/10kW 102 156 1.25/46 1.93/70
12/12kW 152 215 1.53/56 2.08/76
13/14kW 156 220 1.56/58 2.30/84
16/16kW 183 261 1.59/58 2.51/91
16/17kW 183 261 1.61/59 2.57/94
18/20kW 206 294 1.89/69 2.90/106
Natural gas is in cubic feet per hour.
** LP is in gallons per hour/cubic %et per hour.
*** Vahtes given are approximate.
Verify that gas meter is capable of providing enough
fuel flow to include household appliances.
@ 1.9.1 BTU FLOW REQUIREMENTS =
BTU flow required for each unit based on 1000 BTU
per cubic foot.
. 7kW-- 140,000 BTU/Hour
. 9kW-- 156,000 BTU/Hour
. 12kW-- 215,000 BTU/Hour
. 13kW-- 220,000 BTU/Hour
. 16kW-- 261,000 BTU/Hour
. 18kW-- 294,000 BTU/Hour
Gaseous fuels such as natural gas and liquid
propane (LP) gas are highly explosive. Even the
slightest spark can ignite such fuels and cause
an explosion. No leakage of fuel is permitted.
Natural gas, which is lighter than air, tends to
collect in high areas. LP gas is heavier than air
and tends to settle in low areas.
Nat. Gas LP Vapor
1/2 Load Full Load 1/2 Load Full Load
NATURAL (;AS

Section 1 - General information
Air-cooled Generators
GENERAL
NFORMATON
NOTE:
A minimum of one approved manual shut-off valve
must be installed in the gaseous fuel supply line.
The valve must be easily accessible, Local codes
determine the proper location.
l.lO RECONFIGURINGTHE
FUELSYSTEM
O 1.10.1 8 KW 410CC ENGINE
To reconfigure the fuel system from NG to LR follow
these steps (Figure 1.4):
NOTE:
The primary regulator for the propane supply is
NOT INCLUDED with the generator, A fuel pres-
sure of I0 to 12 inches of water column (0,36 to
0.43 psi) to the fuel inlet of the generator MUST
BE SUPPLIED,
1. Turn off the main gas supply (if connected).
2. Open the roof and remove the door.
3. Remove the battery (if installed).
4. Take the plastic T-handle fuel selector in the poly
bag supplied with the generator.
5. Locate the selector knob on the air box cover,
behind the yellow air filter door and power
bulge. The unit comes from the factory in the NG
(Natural Gas) position. Grasping the T-handle,
insert the pin end into the hole in the selector
knob and pull out to overcome spring pressure
and then twist clockwise 90 degrees and allow
the selector to return in once aligned with the LP
(Liquid Propane) position.
6. Save this tool with the Owner's Manual.
7. Install the battery, door and close the roof.
8. Reverse the procedure to convert back to natural
gas.
Figure 1.4 - Fuel Selector
NOTE:
Use an approved pipe sealant or joint compound
on all threaded fittings to reduce the possibility
of leakage,
0 1.10.2 10, 12, 14, 16, 17 AND 20KW, V=TWIN
ENGINES
To reconfigure the fuel system from NG to LR follow
these steps:
NOTE:
The primary regulator for the propane supply is
NOT INCLUDED with the generator, A fuel pres-
sure of I0 to 12 inches of water column (0,36 to
0.43 psi) to the fuel inlet of the generator MUST
BE SUPPLIED.
1. Open the roof.
2. For 10kW units: Loosen clamp and slide back
the air inlet hose.
* Slide fuel selector on carburetor out towards the
back of the enclosure (Figures 1.5 and 1.6).
* Return the inlet hose and tighten clamp secure-
ly.
For 12, 14, 16, 17 and 20kW units: remove the air
cleaner cover.
* Slide the selector lever out towards the back of
the enclosure (Figures 1.7 and 1.8).
* Return the air cleaner cover and tighten the two
thumb screws.
Figure 1.5 - lOkW, GT=530 (inlet Hose Slid Back)
FuelSelection
Lever- "in"
Positionfor
NaturalGas
Fuel
3. Close the roof.
4. Reverse the procedure to convert back to natural
gas.
9

o o o
GENERAL
NFORMATON
Section 1 - General information
Air-cooled Generators
Figure 1.6 - lOkW, GT-530 (Inlet Hose Slid Back)
Figure 1.7- 12, 14, 16, 17, & 20kW,
GT-990/GT-999 (Airbox Cover Removed)
Figure 1.8- 12, 14, 16, 17, & 20kW,
GT-990/GT-999 (Airbox Cover Removed)
1.11 LOCATION
• 1.11.1 GENERATOR
Install the generator set, in its protective enclosure,
outdoors, where adequate cooling and ventilating air
is always available (Figure 1.9). Consider these fac-
tors:
. The installation of the generator must comply
strictly with NFPA 37, NFPA 54, NFPA 58, and
NFPA 70 standards.
* Install the unit where air inlet and outlet open-
ings will not become obstructed by leaves, grass,
snow, etc.. If prevailing winds will cause blowing
or drifting, consider using a windbreak to protect
the unit.
* Install the generator on high ground where water
levels will not rise and endanger it.
* Allow sufficient room on all sides of the generator
for maintenance and servicing. This unit must be
installed in accordance with current applicable
NFPA 37 and NFPA 70 standards; as well as any
other federal, state and local codes for minimum
distances from other structures. DO NOT install
under wooden decks or structures unless there is
at least four (4) feet of clearance above the genera-
tor, three (3) feet of clearance on sides and front,
and 18 inches of clearance at back of unit.
* Install the unit where rain gutter down spouts,
roof run-off, landscape irrigation, water sprinklers
or sump pump discharge does not flood the unit
or spray the enclosure, including any air inlet or
outlet openings.
* Install the unit where services will not be affected
or obstructed, including concealed, underground
or covered services such as electrical, fuel, phone,
air conditioning or irrigation.
* Where strong prevailing winds blow from one
direction, face the generator air inlet openings to
the prevailing winds.
to
Figure 1.9 - Generator Clearances