Loss of life. This product is not intended to
be used in a critical life support application.
Failure to adhere to this warning could result
in death or serious injury.
Generac PWRcell™ Inverters
XVT076A03
XVT114G03
009954
Register your Generac product at:
https://pwrfleet.generac.com
1-888-GENERAC
RegisteryourGeneracproductat:
Para español, visita:
Pour le français, visiter: http://www.generac.com/service-support/product-support-lookup
Use this page to record important information about your Generac Product
(000393a)
WARNING
CANCER AND REPRODUCTIVE HARM
www.P65Warnings.ca.gov.
Record the information found on your unit data label on this page. See Serial Number Location.
When contacting an Independent Authorized Service Dealer (IASD) or Generac Customer Service, always supply the complete
model number and serial number of the unit.
Table 1: PWRcell Inverter Important Information
Unit Model Number
Unit Serial Number
Date Purchased
Commissioning Date
ii Installation Manual for Generac PWRcell Inverter
Current Transformers (CTs) .............................20
Other Accessories .............................................24
Owner’s Manual for Generac PWRcell Inverteriii
Page 4
This page intentionally left blank.
iv Owner’s Manual for Generac PWRcell Inverter
Page 5
Safety Rules & General Information
(000100a)
Consult Manual. Read and understand manual
completely before using product. Failure to
completely understand manual and product
could result in death or serious injury.
WARNING
(000001)
DANGER
Indicates a hazardous situation which, if not avoided,
will result in death or serious injury.
(000002)
WARNING
Indicates a hazardous situation which, if not avoided,
could result in death or serious injury.
(000003)
CAUTION
Indicates a hazardous situation which, if not avoided,
could result in minor or moderate injury.
Section 1: SafetyRules & General Information
Introduction
Thank you for purchasing a Generac PWRcell™ product.
The Generac PWRcell inverter is a storage-ready
inverter that connects to the PV Link™ optimizers and
PWRcell batteries to form the Generac PWRcell system.
This manual provides instructions for installing the
PWRcell inverter, including mounting, wiring, and battery
integration information. The companion document to this
installation manual is the Generac PWRcell Inverter
Owner’s Manual. See the owner’s manual for complete
information on programming and configuring the
PWRcell inverter.
The information in this manual is accurate based on
products produced at the time of publication. The
manufacturer reserves the right to make technical
updates, corrections, and product revisions at any time
without notice.
Read This Manual Thoroughly
Throughout this publication, and on tags and decals
affixed to the unit, DANGER, WARNING, CAUTION, and
NOTE blocks are used to alert personnel to special
instructions about a particular operation that may be
hazardous if performed incorrectly or carelessly. Observe
them carefully. Alert definitions are as follows:
If any section of this manual is not understood, contact
the nearest Independent Authorized Service Dealer
(IASD) or Generac Customer Service at 1-888-436-3722
(1-888-GENERAC), or visit www.generac.com for assis-
tance. The owner is responsible for correct maintenance
and safe use of the unit.
This manual must be used in conjunction with all other
supporting product documentation supplied with the
product.
SAVE THESE INSTRUCTIONS for future reference. This
manual contains important instructions that must be followed during placement, operation, and maintenance of
the unit and its components. Always supply this manual
to any individual that will use this unit, and instruct them
on how to correctly start, operate, and stop the unit in
case of emergency.
Safety Rules
The manufacturer cannot anticipate every possible circumstance that might involve a hazard. The alerts in this
manual, and on tags and decals affixed to the unit, are
not all inclusive. If using a procedure, work method, or
operating technique that the manufacturer does not specifically recommend, verify that it is safe for others and
does not render the equipment unsafe.
Installation Manual for Generac PWRCell Inverter1
NOTE: Notes contain additional information important to
a procedure and will be found within the regular text of
this manual.
These safety alerts cannot eliminate the hazards that
they indicate. Common sense and strict compliance with
the special instructions while performing the action or
service are essential to preventing accidents.
How to Obtain Service
For assistance, contact the nearest Independent Authorized Service Dealer (IASD) or Generac Customer Service at 1-888-436-3722 (1-888-GENERAC), or visit
www.generac.com.
When contacting an IASD or Generac Customer Service,
always supply the complete model and serial number of
the unit as given on its data decal located on the unit.
Record the model and serial numbers in the spaces provided on the front cover of this manual.
Page 6
Safety Rules & General Information
(000188)
DANGER
Electrocution. Do not wear jewelry while
working on this equipment. Doing so will
result in death or serious injury.
(000191)
DANGER
Automatic start-up. Disconnect utility power and
render unit inoperable before working on unit.
Failure to do so will result in death or serious injury.
(000187)
WARNING
Electrocution. Potentially lethal voltages are generated
by this equipment. Render the equipment safe before
attempting repairs or maintenance. Failure to do so
could result in death or serious injury.
Risk of injury. Do not operate or service this machine
if not fully alert. Fatigue can impair the ability to
operate or service this equipment and could result in
death or serious injury.
(000215a)
WARNING
(000209b)
WARNING
Loss of life. This product is not intended to
be used in a critical life support application.
Failure to adhere to this warning could result
in death or serious injury.
(000640)
WARNING
Equipment damage. Connecting inverter to electric utility
grid must only be done after receiving prior approval
from utility company. Failure to do so could result in
equipment or property damage.
(000155a)
WARNING
Electric shock. Only a trained and licensed electrician
should perform wiring and connections to unit. Failure to
follow proper installation requirements could result in death,
serious injury, and equipment or property damage.
(000182a)
WARNING
Equipment damage. Only qualified service personnel may
install, operate, and maintain this equipment. Failure to
follow proper installation requirements could result in death,
serious injury, and equipment or property damage.
Equipment damage. Connect only to REbus-compatible
devices to the DC bus. Never connect to any other DC
power source. Connecting to other DC power sources
could result in equipment damage.
(000598a)
CAUTION
General Hazards
• Connecting the PWRcell inverter to the electric util-
ity grid must only be done after receiving prior
approval from the utility company.
• Only competent, qualified personnel should install,
operate, and service this equipment. Strictly comply to local, state, and national electrical and building codes. When using this equipment, comply with
regulations established by the National Electrical
Code (NEC), CSA Standard; the Occupational
Safety and Health Administration (OSHA), or the
local agency for workplace health and safety.
• Protection against lightning surges in accordance
with local electric codes is the responsibility of the
installer.
NOTE: Lightning damage is not covered by warranty.
• Never work on this equipment while physically or
mentally fatigued.
• Any voltage measurements should be performed
with a meter that meets UL3111 safety standards,
and meets or exceeds overvoltage class CAT III.
2Installation Manual for Generac PWRCell Inverter
Page 7
Electrical Hazards
(000104)
DANGER
Electrocution. Water contact with a power
source, if not avoided, will result in death
or serious injury.
(000604)
Electrocution. PWRcell Battery front cover should
be removed by a qualified technician only.
Removing the front cover could result in death,
serious injury, equipment or property damage.
DANGER
(000145)
DANGER
Electrocution. In the event of electrical accident,
immediately shut power OFF. Use non-conductive
implements to free victim from live conductor. Apply
first aid and get medical help. Failure to do so will
result in death or serious injury.
(000599)
Electrocution. Turn battery disconnect OFF and
de-energize REbus before touching terminals.
Failure to do so will result in death, serious injury,
equipment and property damage.
DANGER
(000152)
DANGER
Electrocution. Verify electrical system is
properly grounded before applying power.
Failure to do so will result in death or serious
injury.
Safety Rules & General Information
Installation Manual for Generac PWRCell Inverter3
Page 8
Safety Rules & General Information
This page intentionally left blank.
4Installation Manual for Generac PWRCell Inverter
Page 9
General Information
Section 2: General Information
Specifications
DescriptionUnitsXVT076A03XVT114G03
Max. cont. grid-tied AC power @ 122°F (50ºC)kW7.611.4
Max. cont. islanded AC power @ 104°F (40°C)
with single 6 module battery cabinet
Max. cont. islanded AC power @ 104°F (40°C)
with 2 battery cabinets (8 modules minimum)
Max. cont. Islanded AC power @ 122°F (50°C)kW8.8Range 7.5 to 8.8*
Peak motor starting current (2 sec)A rms50
Normal output frequency ACHz60
Grid Voltage Line to Neutral (L-N)VAC120
Grid Voltage Line to Line (L-L)VAC240208
Peak efficiency%97.397.7
CEC weighted efficiency%96.597.5
AC terminals wire sizeAWG14 to 6
DC terminals wire sizeAWG18 to 6
STOP terminals wire sizeAWG28 to 16
Weightlb (kg)62.7 (28.4)
Thermal management-forced convection
Weatherization rating-NEMA Type 3R
Enclosure Material-powder-coated steel
1
kW9.09.0
kW11.0Range 9.6 to 11.0*
DescriptionUnitsMinNominalMax
REbus voltageV dc360380420
REbus current
REbus Input short circuit current
REbus Input source backfeed current to input source V dc30
Output power factor rating AC-1
Operating voltage range AC, XVT076A03 (L-N)V rms108 120130
Operating voltage range AC, XVT076A03 (L-L)
Operating voltage range AC, XVT114G03 (L-N)V rms108120130
Operating output voltage range AC, XVT114G03 (L-L)V rms184208228
Continuous output current AC grid-tiedA rms32
PCS controlled current grid-tiedA rms32
Continuous output current AC islandedA rms42
Output fault current durationA / ms50 / 2,000
Full Power operating ambient temperature range
Utility interconnection voltage and frequency trip limits and trip
times
Trip voltage and frequency limits
Trip voltage accuracy
Trip time accuracy
1
Peak performance
2
Inverter limits its REbus current to adhere to its AC power rating. Total REbus current capability from multiple REbus
sources may safely exceed this value as the inverter safely limits the amount utilized.
3
Rating for one DC input. Four total.
4
Includes ambient temperature rising from inverter operation.
* In Island mode XVT114G03 Protected loads only supply 2 phases 120 VAC L-N, 208 L-L which results in lower power than in
grid tied 3 phase mode. The low value of the range is for full L-L loading while high value of the range is full L-N loading.
3
4
V dc
V dc30
V rms216240260
°F (°C)-4 (-20)+122 (+50)
See
Voltage and Frequency Trip Thresholds for more
information.
%2% +/- 2 cycles
30
2
Installation Manual for Generac PWRcell Inverter5
Page 10
General Information
B
A
C
Serial Number Location
Refer to Figure 2-2 to locate unit serial number (D).
Record the information from this tag in Table 1: PWRcell
Inverter Important Information on the inside front cover
of this manual.
Unit Dimensions
009955
Figure 2-1. Unit Dimension
A
24-3/4 in (628 mm)
B
19-3/8 in (491 mm)
C
8-3/8 in (214 mm)
Component Locations
A
B
Figure 2-2. Component Locations
AControl Panel
BIntake Filter
CExhaust Vent
DSerial Number Tag
C
D
009654
About PWRcell Inverters
The PWRcell inverter connects to PV Link™ optimizers
and PWRcell batteries to form the PWRcell system for
grid-interactive solar-plus-storage.
Upon the loss of grid power, PWRcell inverters
disconnect from the grid and provide AC power to
support protected loads when configured to do so. This
capability is referred to as islanding.
All PWRcell products use the REbus™ 380 VDC
nanogrid to connect to each other. The REbus nanogrid
automates the flow of power to enable plug-and-play
setup and operation of PWRcell equipment. For more
information about REbus, visit www.generac.com.
In Figure 2-3 PWRcell inverter (E) is directly connected
to PV Link optimizers (B) and PWRcell battery (C) on DC
(REbus) lines (D). To the right of the inverter are AC
lines: 120/240 VAC for grid and home loads (G) and
protected loads (H).
6Installation Manual for Generac PWRcell Inverter
Page 11
General Information
.
A
B
B
B
A Solar PanelsDREbusGLoads
B PV Link EPWRcell InverterHProtected Loads
C PWRcell BatteryFGrid
Inverter Control Panel
A
C
REbusInverter
B
F
C
D
D
E
Figure 2-3. Generac PWRcell System Example
REbus Status LED
REbus Status LED (C) communicates REbus nanogrid
status through LED color.
• Green – all devices are functioning normally and
are generating power on REbus.
D
• Yellow – no PV Links are generating power from
PV on Rebus.
• Red – one or more REbus device has a fault that
requires attention before operation will continue.
NOTE: A red LED can also indicate a fault with the
Internet
G
REbus wiring itself. See display (A) for more information
about the specific fault detected.
F
G
H
009893
Shutdown
E
(hold)
Figure 2-4. Inverter Control Panel
009894
Inverter LED
Inverter LED (D) communicates the status of the utility
grid and / or inverter through LED color and state.
• Green – utility is connected and within normal
ALCD Display
BNavigation Keys
CREbus Status LED
DInverter LED
EShutdown
FShutdown LED
GInternet LED
See Figure 2-4. The PWRcell system is controlled
through the PWRcell inverter control panel. The inverter
control panel is used for adjusting system settings and for
interacting with devices.
Installation Manual for Generac PWRcell Inverter7
operational voltage and frequency.
• Yellow – utility grid is not within normal conditions
and the inverter is in a waiting state. User
intervention typically is not required. The inverter
will restart as soon as the utility grid returns to
normal conditions.
• Red – a serious fault with the utility grid or inverter
has been detected and user attention is required
before the unit will resume operation. See display
(A) for more information about the fault detected.
• No light – the inverter is disabled, islanded, or
powered off.
Page 12
General Information
(000600)
DANGER
Electrocution. Initiate a system-wide shutdown and turn the
PWRcell DC Disconnect Switch OFF on all connected
batteries before performing service. Failure to do so will
result in death, serious injury, or equipment and property
damage.
Internet LED
Internet LED (G) is illuminated when the inverter is
connected to a router and has an IP address.
A blue Internet LED does not mean that the inverter has
a connection to the Generac server.
Shutdown Mode
NOTE: A loss of grid power will not de-energize REbus
in a PWRcell system configured to island with enabled
energy storage.
Shutdown button (E) activates a transition to shutdown
system mode.
Disabled PWRcell equipment limits output voltages to a
safe level for servicing. See Rapid Shutdown for more
information.
NOTE: The AC section of the inverter will still be
energized unless the building AC disconnect or main
service breaker is shut off.
To enter shutdown, press and hold shutdown button (E).
In shutdown mode:
• PWRcell inverter will stop sourcing power to
REbus, and immediately disable all communicating
power sources on REbus by sending a systemwide system mode change signal.
NOTE: Successful signal transmission relies upon
proper configuration of PLM channels across REbus
devices (PV Links and Batteries).
• Shutdown LED (F) will illuminate.
• Inverter screen (A) will display REbus DC bus volt-
age and text indicting shutdown mode has been
initiated.
8Installation Manual for Generac PWRcell Inverter
Page 13
Section 3: Location and Compliance
(000190)
DANGER
Loss of life. Property damage. Installation must
always comply with applicable codes, standards, laws
and regulations. Failure to do so will result in death
or serious injury.
WARNING
Electrocution. Refer to local codes and standards for
safety equipment required when working with a live
electrical system. Failure to use required safety
equipment could result in death or serious injury.
(000257)
(000182a)
WARNING
Equipment damage. Only qualified service personnel may
install, operate, and maintain this equipment. Failure to
follow proper installation requirements could result in death,
serious injury, and equipment or property damage.
Location and Compliance
Location
When installing the PWRcell inverter, consider the following:
• The unit can be installed in indoor or outdoor loca-
tions.
• The inverter installation location must meet the
working space requirements in NEC Article 110.26.
Compliance
Note on DC Wiring and the NEC
Some electricians or installers may be unfamiliar with DC
wiring in a residential setting. Note the following:
• NEC 690.31 for DC PV circuits in buildings
• NEC 215.12(C)(2) for correct DC wiring identifica-
tion
Always adhere to applicable codes when marking and
installing DC conductors. See
ing Coloring Convention. Mark or flag all conductors for
their polarity as appropriate.
• It is recommended that REbus (+) conductors NOT
be green, white, gray, blue, or black.
• It is recommended REbus (-) conductors NOT be
green, white, gray, or red.
Table 3-1. REbus DC Wiring Coloring Convention
WireColor
REbus + (RE+)Red
REbus - (RE-)Black or Blue
Ground (GND)Green
Table 3-1: REbus DC Wir-
Follow all instructions included in this manual and use
appropriate practices for all product wiring and installation.
Rapid Shutdown
The PWRcell Inverter is equipped with four DC disconnects to initiate the Photovoltaic Rapid Shutdown System
(PVRSS). Each disconnect switch can be used to initiate
Rapid Shutdown in compliance with NEC 690.12 for all
PV Link and SnapRS units connected to that disconnect.
NOTE: If an additional DC disconnect is added, ensure
the disconnect switch is DC rated for a minimum of 30
amperes, 450 volts.
To initiate the PVRSS:
• Open the inverter lid.
• Locate the four DC disconnects to the left of the
Generac Power Core.
• Turn all disconnects with connected PV sources to
the “off” position.
• PV Links will open all SnapRS devices within 30
seconds controlling all PV conductors within the
array to less than 80V, and all conductors leaving
the array to below 30V.
NOTE: Where the DC disconnect(s) in the inverter are
used as the Rapid Shutdown initiation device, proper
labeling is required for the exterior of the inverter lid to
indicate to first responders where to initiate Rapid Shutdown.
Installation Manual for Generac PWRcell Inverter 9
Page 14
Location and Compliance
Voltage and Frequency Trip Thresholds
This unit or system is provided with fixed trip limits and
shall not be aggregated above 30 kW on a single point of
common connection.
All PWRcell inverters are shipped from the factory in
compliance with all UL1741 requirements, including
IEEE1547. If permission to operate (PTO) is dependent
on compliance to a specific utility standard, follow the
steps covered in Installer Configuration Tool section in
this manual.
Table 3-2. Voltage Trip and Frequency Thresholds
Voltage Trip ThresholdsFrequency Trip Thresholds
Voltage Trip Thresholds
See Table 3-2 for the default fixed voltage trip setpoints.
All over voltage and under voltage trip conditions result in
a 300-second restart delay time after the trip threshold
has been exceeded for the listed number of cycles.
Frequency Trip Thresholds
See Table 3-2 for the default fixed frequency trip set-
points. All over frequency and under frequency trip conditions result in a 300-second restart delay time after the
trip threshold has been exceeded for the listed number of
cycles.
Threshold
OV1110120OF10.5120
OV212010OF226
OV31301OF31.30
OV4999*1OF40**1
UV188120UF10.5120
UV25010UF2210
UV3999*1UF30**1
UV4999*1UF40**1
*Value of 999 indicates a disabled threshold for voltage trips
**Value of zero indicates a disabled threshold for frequency trips
Threshold
(% of nominal)
No. of CyclesThreshold
Hz Over/
Under Nominal
No. of Cycles
10Installation Manual for Generac PWRcell Inverter
Page 15
Section 4: Installing PWRcell Inverter
4 in
(10.16 cm)
28 in
(71.15 cm)
8 in
(20.32 cm)
28-1/2 in
(72.4 cm)
36 in
(91.44 cm)
8 in
(20.32 cm)
19-1/4 in
(48.9 cm)
8-1/2 in
(21.6 cm)
20 in
(50.8 cm)
8 in
(20.32 cm )
24-1/2 in
(62.23 cm)
16 in
(40.64 cm)
1-1/2 in
(3.81 cm)
2-3/8 in
(6.03 cm)
PWRcell Inverter Dimensions and Mounting Clearances
Installing PWRcell Inverter
Figure 4-1. PWRcell Inverter Dimensions and Mounting Clearances
Mounting Bracket Dimensions
Figure 4-2. Mounting Bracket Dimensions
010508
009990
Installation Manual for Generac PWRcell Inverter11
Page 16
Installing PWRcell Inverter
(000641a)
CAUTION
Equipment damage. Mount inverter to a strong, stable surface.
Never mount to drywall, plaster, or other non-structural wall
treatments. Failure to mount inverter to a strong, stable surface
could result in equipment or property damage.
Mounting the Inverter
1. Verify mounting location adheres to the following
requirements:
• Location must meet all PWRcell inverter
requirements listed in Section 3 of this manual.
See Location and Compliance for more
information.
• Inverter must be mounted upright on a vertical wall.
• Never obstruct intake or exhaust vents.
• Never allow water to enter intake or exhaust vents.
• Observe all mounting clearances. See PWRcell
Inverter Dimensions and Mounting Clearances.
2. Secure mounting bracket mounting surface
through mounting holes.
• Fasteners must adequately secure the 62.7 lbs
(28.4 kg) inverter weight to the wall.
• Fasteners must be suitable for the mounting
surface.
• Fasteners must engage at least two studs or other
structural members.
• Mounting bracket has clearance holes for 1/4 in
fasteners with slots to accommodate different stud
spacings.
3. See Figure 4-3. Insert mounting bracket tabs (A)
into inverter body slot (B).
NOTE: Figure 4-3 is for illustration purposes only.
B
A
009991
Figure 4-3. Mounting Inverter onto Bracket
4. See Figure 4-4. Secure the bottom of the inverter
to wall with two fasteners through mounting holes
(C). Holes are spaced at 11 1/4 in from each other.
Use anchors or blocking as needed.
C
009992
Figure 4-4. Mounting Holes
12Installation Manual for Generac PWRcell Inverter
Page 17
Section 5: Electrical Connections
PWRcell Inverter Wiring Compartment
A
Electrical Connections
H
F
D
B
C
E
G
M
N
I
K
L
J
Figure 5-1. PWRcell Inverter Wiring Compartment
APWRcell DC Disconnects HAuthorized Generac Personnel Only
FAutomatic Transfer Switches (ATS) Accessory Port MGrounding Bar
GREbus Beacon PortN RGM PWR Gen Inhibit
011235
Installation Manual for Generac PWRCell Inverter13
Page 18
Electrical Connections
(000600)
DANGER
Electrocution. Initiate a system-wide shutdown and turn the
PWRcell DC Disconnect Switch OFF on all connected
batteries before performing service. Failure to do so will
result in death, serious injury, or equipment and property
damage.
(000642)
DANGER
Electrocution. Verify all system voltages are safe before
wiring. Disconnect all AC and DC sources of power before
touching terminals. Failure to ensure no dangerous
voltages are present on conductors and terminals before
wiring will result in death or serious injury.
Accessing Wiring Compartment
See
Figure 5-2. To access the wiring compartment:
1. Initiate an inverter shutdown.
2. Open all PWRcell DC disconnects (A). Verify DC
voltage reported on LCD screen has dropped to
below 10VDC.
3. Disconnect AC Grid source from inverter. Wait for
Inverter LCD screen to turn off.
4.
Open inverter front cover by lifting the bottom to
horizontal (B) and pushing inward (C).
5. Locate wiring compartment cover (D).
6. Remove five M4X10 screws (E) and wiring
compartment cover.
7. Verify all PWRcell DC and AC terminals are below
10V, using a multi-meter.
• Install reducing washers to accommodate smaller
conduit sizes.
• Install rain-tight or wet locations hubs in
compliance with UL514B.
Table 5-3. Combination Knockout Size and Quantity
Combination Knockout SizeQuantity
3/4 in X 1 in6
1/2 in X 3/4 in7
0.575 in use only for LTE Modem Antenna1
C
B
A
E
D
010238
Figure 5-2. Wiring Compartment
Knockout Dimensions and Locations
NOTE: All knockouts are combination knockouts, except
for the 1/4 in trade knockout at the top of the left side
which is intended only for mounting an optional LTE
modem antenna.
See Figure 5-3 for knockout locations and Table 5-3 for
available knockout sizes and quantities.
When using knockouts:
14Installation Manual for Generac PWRCell Inverter
Page 19
Electrical Connections
42 mm
1-21/32 in
50 mm
1-31/32 in
137 mm
5-13/32 in
97 mm
3-13/16 in
140 mm
5-17/32 in
2-13/16 in
72 mm
56 mm
2-7/32 in
40 mm
1-19/32 in
552 mm
21-23/32 in
50 mm
1-31/32 in
45 mm
1-3/4 in
55 mm
2-5/32 in
55 mm
2-5/32 in
26 mm
1 in
58 mm
2-9/32 in
62 mm
2-7/16 in
50 mm
1-31/32 in
48 mm
1-7/8 in
55 mm
2-5/32 in
55 mm
2-5/32 in
35 mm
1-3/8 in
10 mm
13/32 in
28 mm
1-3/32 in
(000642)
DANGER
Electrocution. Verify all system voltages are safe before
wiring. Disconnect all AC and DC sources of power before
touching terminals. Failure to ensure no dangerous
voltages are present on conductors and terminals before
wiring will result in death or serious injury.
(000599)
Electrocution. Turn battery disconnect OFF and
de-energize REbus before touching terminals.
Failure to do so will result in death, serious injury,
equipment and property damage.
DANGER
Wiring Guidelines
Figure 5-3. Knockout Locations
• Proper installation techniques must be employed to
restrain service loops and to separate AC, DC and
isolated circuits.
• All conductors must be rated for at least 420 V.
• Always use wiring methods in accordance with
National Electrical Code (ANSI/NFPA 70) or other
applicable codes.
• Field terminals are for copper conductors only.
• Do not use field wiring leads smaller than 18 AWG.
• All field installed conductors within the unit are
sized in compliance with NEC Article 310.
• Torque all terminals as specified in Table 5-4.
011234
• The inverter shall be installed in accordance with
NEC Article 705.
Installation Manual for Generac PWRCell Inverter15
Page 20
Electrical Connections
(000607a)
Equipment damage. Never connect REbus conductors
to ground. Connecting REbus conductors to ground
could result in equipment or property damage.
CAUTION
Table 5-4. Terminal Torques
Wiring TerminalTorque
AC terminals13.3 to 15.9 in-lb (1.5 to 1.8 Nm)
DC terminals12 in-lb (1.35 Nm)
Ground terminals4 to 6 AWG: 45 in-lb (5 Nm)
8 AWG: 40 in-lb (4.5 Nm)
10 to 14 AWG: 35 in-lb (4 Nm)
STOP terminals1.9 to 2.2 in-lb (0.22 to 0.25 Nm)
Grounding Bar Wiring
• Bond the inverter enclosure to the equipment
grounding conductor of the normal power source
power feeder.
• The grounding bar provides central grounding for
up to 8 conductors.
• Input and output circuits are isolated from the
enclosure.
• The neutral conductor is not bonded to the
equipment ground terminal bar within the
enclosure.
• The inverter and its connected PV and battery
sources are not separately derived systems.
• DC system grounding is critical for REbus
communications. REbus grounding wires are used
as communications wires. Ensure the following
REbus devices have a low resistance wired
connection back to the inverter grounding terminal
bar:
– PV Link
– PWRcell batteries
• Torque all terminals as specified in Table 5-5.
Table 5-5. Grounding Bar Wiring Terminal
Specifications
Wire Size (AWG)Torque
4-645 in-lb (5 Nm)
840 in-lb (4.5 Nm)
1030 in-lb (4 Nm)
16Installation Manual for Generac PWRCell Inverter
Page 21
DC Wiring
DANGER
Electrocution. Never touch terminals when
inverter and PWRcell DC disconnects are ON.
Doing so will result in death or serious injury.
(000646)
Equipment damage. Obey polarity markings when
connecting REbus devices. Reverse-polarizing DC
circuits could result in equipment or property damage.
WARNING
(000645)
WARNING
Equipment damage. Do not connect raw, unregulated
battery output to inverter. Connect only REbus-compatible
batteries. Connecting batteries that are not REbuscompatible could result in equipment or property damage.
Equipment damage. Do not connect PV string output
directly to inverter. PV must be connected via Generac
PWRcell PV Link. Connecting PV output directly to inverter
could result in equipment or property damage.
CAUTION
(000644a)
(000647a)
CAUTION
Equipment damage. Connect only one wire to each
DC wiring terminal. Doubling wires on a terminal
could result in equipment or property damage.
Equipment damage. Connect only to REbus-compatible
devices to the DC bus. Never connect to any other DC
power source. Connecting to other DC power sources
could result in equipment damage.
(000598a)
CAUTION
N1
L1
L2
N
Protcd.
L3
(3p)
L1
Protcd.
L2
Protcd.
Electrical Connections
Table 5-6. DC Wiring Terminal Specifications
(000686a)
Wire Size
18-6 AWG
(.75-10 mm)
Terminal
Temp Range
-40 to 266ºF
(-40 to 130ºC)
Wire Min
Temp Rating
194ºF
90ºC
Torque
12 in-lb
(1.35 Nm)
AC Wiring
NOTE: The installer is responsible for providing sufficient
overcurrent protection for the AC grid wiring terminals.
The conductors and overcurrent protection device shall
be sized in accordance with NEC Article 705 for the utility
power connection. All other conductors shall be sized in
accordance with NEC Article 310 and all other applicable
NEC Articles.This system is equipped with a power
control system (PCS). The PCS controlled AC grid
conductors shall be protected with a suitably rated
overcurrent device appropriately sized for the conductor
ampacity.
• See Figure 5-4. The PWRcell inverter is equipped
with four AC grid connection terminals and three
protected loads terminals.
• Use the top four terminals (A) for connection to the
utility grid.
NOTE: Disable REbus before returning PWRcell DC
disconnects to ON position.
• Connect all REbus devices to the REbus bi-
directional DC terminals.
• Each terminal is protected by a 30 A two-pole
circuit disconnect.
• PWRcell DC disconnects indicate state and may
be used to disconnect DC circuits.
• PWRcell DC disconnects disconnect both
ungrounded DC conductors simultaneously.
• Torque all terminals as specified in Table 5-6.
Installation Manual for Generac PWRCell Inverter17
NOTE: Use L3 terminal (B) with 3-phase inverters only.
• Use the bottom three terminals (C) for protected
loads output. See Protected Load.
A
B
C
009996
Figure 5-4. AC Wiring Terminals
• Torque all terminals as specified in Table 5-7.
Table 5-7. AC Wiring Terminal Specifications
Wire Size
Terminal Temp RangeUp to 248ºF (120ºC)
Wire Min Temp Rating194ºF (90ºC)
Torque
10 to 6 AWG
2
(5.26 mm
13.3 in-lb to 15.9 in-lb
(1.5 Nm to 1.8 Nm)
to 13.3 mm2)
Page 22
Electrical Connections
(000648a)
CAUTION
Equipment damage. Never connect protected loads
terminals to other sources of power, including any other
inverter, the utility grid, or a generator. Doing so could
result in equipment or property damage.
(000649a)
CAUTION
Equipment damage. Never connect protected loads
output from inverters in parallel. Doing so could result
in equipment or property damage.
Protected Load
For systems equipped with energy storage, the inverter’s
protected loads terminals provide power during a grid
outage.
NOTE: The protected loads terminals can only provide
two phases of power in a three-phase system.
See Figure 5-5. By default, the grid powers any
protected loads connected to the inverter protected loads
terminals. The PWRcell Inverter is configured to pass
grid power from AC grid terminals through to the
protected loads terminals. This includes when the
inverter is disabled. During a grid outage, internal relays
inside the inverter isolate the AC grid connection and the
inverter powers the protected loads only using PV array
and battery power. This transition takes place in a
fraction of a second.
NOTE: To create a protected loads panel, connect the
circuits that require backup to a subpanel. Connect this
subpanel to the protected loads terminals.
• The protected loads output can provide on the
order of 8 kW of continuous power. See
Specifications for exact values.
• The inverter can surge up to 50 A for motor starting
capabilities.
NOTE: Actual power output for protected loads during a
grid outage will depend on system sizing for batteries and
solar array.
NOTE: Backup power ratings are separate from the
power ratings for PWRcell inverters while grid connected-
7.6kW and 11.4kW respectively.
A
B
B
G
APV Array
BPWRcell Inverter
CProtected Loads Panel
DProtected Loads Disconnect
EAC Main Panel
E
FPWRcell Battery
GUtility
F
C
D
009997
Figure 5-5. Single Inverter Backup Installation with Protected Loads Panel
18Installation Manual for Generac PWRCell Inverter
Page 23
Electrical Connections
NOTE: See Figure 5-6. On systems that do not include battery storage but battery storage is expected in the future,
install a protected loads panel during inverter installation. The protected loads panel will be fed by the grid while the
system operates in Grid Tie mode.
A
B
G
APV Array
BPWRcell Inverter
CProtected Loads Panel
DProtected Loads Disconnect
EAC Main Panel
C
E
GUtility
D
Figure 5-6. Configuration for Adding Batteries Later
009998
Installation Manual for Generac PWRCell Inverter19
Page 24
Electrical Connections
(000732)
Equipment damage. Only connect CTs provided by
Generac. Never connect to any other CTs. Connecting
to other CTs could result in equipment damage.
CAUTION
Connecting Ethernet
IMPORTANT NOTE: Generac requires all PWRcell
system components to be connected to the Internet
and to maintain such connection throughout the warranty period. Internet connectivity is established via
the PWRcell inverter. By installing the PWRcell
inverter and connecting it to the Internet, Customer
agrees that Generac may remotely monitor the use
and condition of the system and update the system's
software and firmware, as necessary, without further
notice. If the PWRcell system loses Internet connection for an extended period, Generac may not be able
to provide important remote upgrades. In such
cases, Generac may not be able to honor the full warranty.
• See PWRcell Inverter Wiring Compartment for
the Inverter Ethernet jack location.
• Use an appropriate cord grip or strain-relief
connector when running Ethernet cable with a
conduit.
• Inverters connected by a router to a DHCP network
will automatically detect settings.
• For manual IP setup, see Manually Configuring
IP Settings.
NOTE: It is the installer’s responsibility to verify the
Internet connection is reliable and secure. Generac
recommends using a hardwired connection to provide
Internet connectivity. Generac does not support using
any wireless or power line carrier network devices. Use
these devices at your own discretion.
NOTE: Ethernet cable run must be dedicated for the
inverter. This cable may not be daisy-chained to another
device, including another PWRcell inverter.
Current Transformers (CTs)
Current transformers (CTs) are required to use the Self
Supply mode and to enable Import / Export Limiting
capability. CTs are also required where setting a specific
ESS Grid Usage Mode. CTs also allow the inverter to
provide information on utility consumption through the
PWRcell inverter control panel and the PWRview
monitoring app.
Connecting Current Transformers
•
See Figure 5-7. Install CTs around the main
service conductors between the service meter and
point of interconnection with subsequent service
entrance panel/device.
• Install one current transformer per phase:
– Install two CTs for split phase grids.
– Install three CTs for three-phase grids.
G
A
B
H
APV Array
BPWRcell Inverter
CProtected Loads Panel
DProtected Loads Disconnect
D
E
EAC Main Panel
FPWRcell Battery
GCurrent Transformers (CTs)
HUtility
F
C
Figure 5-7. Connecting Current Transformers (CTs)
20Installation Manual for Generac PWRCell Inverter
009997
Page 25
Electrical Connections
NA
NA
CT2 ‒
CT1 ‒
CT1+
CT2+
CT3 ‒
CT3+
ATS
CTs
Connecting CTs to the Inverter
1. See Figure 5-8. Connect CT leads to RJ-45 Break-
out Adapter’s (M) push terminals according to the
label on the breakout adapter.
NOTE: Use yellow lead for CTx+ and use green lead for
CTx-.
M
Figure 5-8. RJ-45 Breakout Adapter
NOTE: RJ-45 Breakout Adapter is included in the
Generac PWRcell Kit.
NOTE: If the RJ-45 Breakout Adapter is not available,
the CT leads can be wired to a Category 5 (Cat 5) cable.
Use Table 5-8 to wire CTs directly to stripped Cat 5 wire.
Table 5-8. CT RJ-45 Pinout
Pin
1White / GreenWhite / OrangeCT3+
2GreenOrangeCT3-
3White/OrangeWhite / GreenCT2+
4BlueBlueCT1+
5White / BlueWhite / BlueCT1-
6OrangeGreenCT2-
7White / BrownWhite / BrownNot Used
8BrownBrownNot Used
Wire Color
(T-568A)
2. See Figure 5-9. Connect Cat 5 cable to CT input
jack (H).
NOTE: The connection between the RJ-45 breakout
adapter and the inverter is made using a widely available
installer supplied Cat 5 style cable.
Wire Color
(T-568B)
Value
010222
• CT input jack is a double-stacked RJ-45 jack.
• Either the top or bottom port may be used.
• Both jacks may be used when multiple sets of
CTs are required.
:
I
H
J
K
L
010001
Figure 5-9. Accessory Ports
HCurrent Transformers (CTs) Accessory Port (RJ-45)
IAutomatic Transfer Switches (ATS) Accessory Port
(RJ-45)
JREbus Beacon Port (USB-B)
KAuthorized Generac Personnel Only
LSTOP Terminals
NOTE: When setting an ESS Grid Usage Mode other
than the default unrestricted mode, attach the label
packaged with the CTs to the inverter.
Connecting Multiple Sets of CTs
When installing CTs, local factors may require multiple
sets of CTs to fully measure the utility power being sent to
the building.
For 4-wire, 120 / 240 VAC, split-phase service:
• Use two pairs of CTs to measure the service. Use
each pair of CTs to measure a pair of service
conductors / feeders within the main panel.
• Use both RJ-45 jacks with two Cat 5 cables.
• Connect CT1 from both cables to the same phase
and CT2 cable from both cables to the second
phase.
• See Table 5-9: Multiple CT Connection. Connect
Cat 5 cables from the adapters into the two CT
accessory ports at the inverter.
NOTE: Make sure to use the same pinout and
connections.
Table 5-9. Multiple CT Connection
Service
CT
1-1L1-114 and 5Front Port
1-2L2-113 and 6Front Port
2-1L1-224 and 5Back Port
2-2L2-223 and 6Back Port
Phase and
Wire Adapter
Adapter Adapter
Pins
CT Port
Row
Values
Installation Manual for Generac PWRCell Inverter21
Page 26
Electrical Connections
Connecting CTs to Multiple PWRcell Systems/
Inverters
When an installation has multiple PWRcell inverter
systems, either:
• Run a set of CTs for each inverter.
• Run a set of CTs to one inverter and then run a Cat
5 cable from the spare CT port within that inverter
to any CT port within another inverter.
When running separate sets of CTs for each inverter, the
load value displayed on each inverter screen will be the
total load measured by the CTs.
When daisy-chaining multiple inverters, the total
measured value is shared evenly across the inverters. In
other words, the load value measured and acted upon by
each inverter is inversely proportional to the number of
inverters seeing the signal.
Example: The CT measured load displayed on three
inverters which daisy chain the signal from the first
inverter to the second inverter and the second to the
third inverter, will be one-third of the total load seen.
NOTE: Daisy-chaining CTs across multiple inverters for
distributed load-share is most applicable when each
inverter has a battery attached. Otherwise, this
configuration may not be necessary or desirable.
– CT3 must be connected to line 3 (for three phase
applications).
– All CTs must be orientated in the same relative
direction.
– In certain scenarios, additional setpoint modifi-
cations may need to be made. See Table 5-10:
CT Setpoints for more information.
To daisy-chain a CT signal:
1. Connect and calibrate a set of CTs to the first
inverter. See CT Calibration for more information.
2. Run a new Cat 5 cable between the spare CT
accessory port of the first inverter to either CT
accessory port on the second inverter.
NOTE: Running a new Cat 5 cable between inverter CT
ports prior to calibration in Step 1 may cause calibration
issues.
CT Calibration
•
Install CTs before powering ON the inverter.
• The inverter automatically detects CTs when
turned ON.
• Once CTs are detected, a utility pole symbol will
appear on the lower right corner of the home
screen power flow diagram. Verify operation by
noting power flow.
– To calibrate CTs, navigate to the inverter device
page, access the sub-menu, and select the Calibrate CTs option. When the CT calibration process has been successfully completed, the
inverter LCD screen will provide feedback showing ct cal success. Otherwise, the screen will
show ct cal = X, where the value of X can be
found in Table 5-11: Automatic Detection
Troubleshooting Table.
– CT2 must be connected to Line 2.
22Installation Manual for Generac PWRCell Inverter
Page 27
Electrical Connections
Table 5-10. CT Setpoints
SetpointBehaviorDefaultUnits
CalOverride
•Overrides CT calibration.
OFFN/A
•When set to OFF, the inverter detects the CTs number and direction of
CTs.
•A value of ON assumes a specific orientation and direction of CTs.
CTTurnsRatio
•Turns ratio of the CTs installed.
1,500 Turns
•Default turns ratio of 1,500 is compatible with included clamp type CTs
•If installation restriction requires larger accessory CTs, set point shall be
adjusted to 3,000. Verify turn ratio of CTs before modifying this setting.
ct cal = 10x8061Line 1 doesn’t have a valid CT calibrationCheck wiring and CT integrity
ct cal = 20x8062Line 2 doesn’t have a valid CT calibrationCheck wiring and CT integrity
ct cal = 30x8063Line 1 & 2 don’t have a valid CT calibrationCheck wiring and CT integrity
ct cal = 40x8064Line 3 doesn’t have a valid CT calibrationCheck wiring and CT integrity
ct cal = 50x8065Line 1 & 3 don’t have a valid CT calibrationCheck wiring and CT integrity
ct cal = 60x8066Line 2 & 3 don’t have a valid CT calibrationCheck wiring and CT integrity
ct cal = 70x8067Line 1 & 2 & 3 don’t have a valid CT calibrationCheck wiring and CT integrity
ct cal = 90x8069
ct cal = A0x806A
ct cal = B0x806B
Line 1 has multiple CTs on it (or a CT is on the
neutral wire)
Line 2 has multiple CTs on it (or a CT is on the
neutral wire)
Lines 1 and 2 have multiple or missing CTs on
them (or a CT is on the neutral wire)
Check wiring and CT integrity
Check wiring and CT integrity
Check wiring and CT integrity
ct cal = C0x806C
ct cal = D0x806D
ct cal = E0x806E
ct cal = F0x806F
ct cal success0x8070Calibration was successfulCheck wiring and CT integrity
Line 3 has multiple CTs on it (or a CT is on the
neutral wire)
Lines 1 & 3 have multiple or missing CTs on them
(or a CT is on the neutral wire)
Lines 2 & 3 have multiple or missing CTs on them
(or a CT is on the neutral wire)
Lines 1 & 2 & 3 have multiple or missing CTs on
them (or a CT is on the neutral wire)
Check wiring and CT integrity
Check wiring and CT integrity
Check wiring and CT integrity
Check wiring and CT integrity
Installation Manual for Generac PWRCell Inverter23
Page 28
Electrical Connections
Other Accessories
Revenue Grade Meter (RGM) Kit
A Generac PWRview Meter is an optional accessory for
the PWRcell Inverter and may be factory or field installed.
When installed at the bottom of the wiring cabinet, it also
uses additional CTs that are provided. Complete
installation instructions are included with the RGM kit.
Order part number: PCRGM1.
PWRcell ATS
A Generac PWRcell ATS can be integrated into the
PWRcell installation to facilitate alternate backup power
configurations. Refer to the PWRcell ATS manual for
additional information regarding configurations and
installation instructions.
A
F
E
G
C
Figure 5-10. Accessory Ports
D
B
011236
LTE Modem
An LTE Wireless phone Modem is an optional accessory
that can provide low bandwidth Internet connectivity if
there is no hardwired Internet connected or if it is
temporarily unavailable. The modem will be located in
the upper left area in the inverter enclosure in proximity
to the Rebus Beacon. The modem uses an antenna that
gets mounted top left exterior of the enclosure through
the 1/4 in trade knockout. The power cable is prewired in
the inverter enclosure. When no LTE Modem is installed,
the power cable will be left unconnected and safely
secured. Complete installation instructions are included
in the LTE Modem Kit. Order part number: PCLTE1.
Technical Service Connection
Service RJ-11 jack (C) is for use by authorized Generac
personnel only. Never connect any device to this jack
without direct instructions from Generac Technical
Service.
AREbus Beacon USB-B Jack
BSTOP Terminals
CAuthorized Generac Personnel Only
DRGM PWR Gen Inhibit
EAutomatic Transfer Switches (ATS) Accessory Port
FCurrent Transformers (CTs)
GLTE Modem Power Connector
Load Management Options
Load management systems are designed to work
together to prevent the PWRcell system from being
overloaded by large appliance loads. Load management
options for PWRcell include the PWRcell ATS Controller
and Smart Management Module (SMM).
When utilizing these load management solutions be sure
to turn on the “EnaLoadShed” setpoint to on. This
setpoint is accessible through the Mod. Settings menu
via the inverter device page as shown in Figure 5-11.
011980
Figure 5-11. Mod Settings Menu
If this setpoint is not set to on, the devices will not
operate correctly with the system. In addition, be sure to
thoroughly read and understand each load management
device manual before installation.
24Installation Manual for Generac PWRCell Inverter
Page 29
Section 6: Commissioning and Setup
REGISTER YOUR SYSTEM
Go to
https://pwrfleet.generac.com/
to register
or scan the code above.
SERIAL NUMBER:
REGISTRATION CODE:
PEEL AWAY
XXXXX-XXXXX
RRRR-RRRR
Commissioning and Setup
System Configuration
The PWRcell system is a flexible, highly customizable
system that can be configured in a number of ways to
meet customer need. Correct system configuration
requires selecting the right equipment and the correct
system mode for the system. See the Generac PWRcell
Inverter Owner’s Manual for information on system
modes and other user-configurable settings.
General Information
All REbus devices are configured and controlled through
the Generac PWRcell Inverter. Connected devices will
appear on the LCD display.
NOTE: See Commissioning Multiple Inverter Sys-
tems for instructions on commissioning multiple inverter
systems.
Commissioning the System
NOTE: See the Generac PWRcell Commissioning Quick
Start Guide for more information.
Before powering up the system for the first time:
• Verify AC voltage is within the specified range for
system configuration.
– 240 V split-phase (108-130 VAC Line to Neutral)
– 208 V 3-phase (108-130 VAC Line to Neutral)
• Verify all wiring terminations are tight and secure.
• Verify DC wiring field terminations are secure and
polarity is correct.
• Verify DC disconnects for all connected devices
are turned ON.
Commissioning consists of seven steps:
1. Register system.
2. Energize the PWRcell inverter with AC power.
3. Select Inverter system mode.
4. Configure inverter settings.
5. Select inverter compliance setting (optional).
6. Select ESS Grid Usage Mode (optional).
7. Enable REbus devices.
8. Test islanding.
NOTE: Registering an inverter automatically registers all
REbus system components connected to that inverter.
Every REbus-enabled device can be monitored from the
PWRfleet fleet management platform and the
PWRview™ online monitoring system and mobile app.
To register a system for PWRview monitoring:
1. See Figure 6-1. Locate the serial number and reg-
istration code on the registration decal on the front
of the inverter. This information will be required for
registration.
2. Navigate to
using a mobile device scan the registration label
QR code.
3. Follow the on-screen prompts to complete the
profile.
.
https://pwrfleet.generac.com or if
Registration
NOTE: If the system will not be connected to the Inter-
net, installer will not be able to take advantage of PWRfleet, the home owner will not have access to the
PWRview app, and warranty will be limited to five years.
Contact Generac at 1-888-ACTIVATE to complete the
registration.
Installation Manual for Generac PWRCell Inverter25
Figure 6-1. Registration Decal
009984
Page 30
Commissioning and Setup
Safety Shutdown
System ModeMenu
Self Supply
Clean Backup
< EXIT SCROLL > NEXT • SELECT
Grid Tie *
Safety Shutdown
System ModeMenu
Clean Backup
< EXIT SCROLL > NEXT • SELECT
Grid Tie *
Self Supply
SA
System ModeMenu
GRd. Settings
SElibrate CTs
CLEPn: 00010003XXXX
< EXIT SCROLL > NEXT • SELECT
Enable
CancelConfirm
Connecting PWRcell Inverter to AC
Power
Turn ON main AC backfeed to power-up the inverter.
See Figure 6-2. On power-up, the home screen will
appear on the control panel LCD with the operational
mode listed at the top of the home screen.
010006
Figure 6-2. Inverter Power-Up
NOTE: If there is no grid power at the site and the system includes a PWRcell battery, blackstart can be used
to start the system from the battery. See the Generac
PWRcell Battery Owner’s manual for information on
blackstarting a system.
3. See Figure 6-4. Use the up and down arrows to
highlight the desired mode and press the center
button to select.
009967
Figure 6-4. Selecting System Modes (2 of 4)
4. Arrow right and press the center button to select
Confirm.
5. See Figure 6-5. Arrow right and press the center
button to select Confirm.
Selecting Inverter System Mode
NOTE: See the Generac PWRcell Inverter Owner’s
Manual for more information on system mode options.
To select a system mode:
1. See Figure 6-2. While viewing the home screen
press the center button.
2. See Figure 6-3. A list of system modes will be
displayed with the current mode marked with an
asterisk.
NOTE: The list of modes may not include all those
shown in Figure 6-3.
Figure 6-3. Selecting System Modes (1 of 4)
011139
Figure 6-5. Selecting System Modes (3 of 4)
6. See Figure 6-6. Verify the mode listed at the top of
the home screen is the desired mode.
009968
Figure 6-6. Selecting System Modes (4 of 4)
009966
26Installation Manual for Generac PWRCell Inverter
Page 31
Commissioning and Setup
Configuring Inverter Settings
Configuring Systems with PWRcell Batteries
Systems with a PWRcell battery must have the EnaIslanding setpoint set to ON in order to provide backup
power during a grid outage. This setpoint is accessible
through the Mod. Settings menu via the inverter device
page. The default value for this setting from the factory is
ON.
Verify the PWRcell inverter protected loads disconnect is
in the ON position.
Verify the Battery Disconnect on the PWRcell battery is
ON.
NOTE: Reference the PWRcell Battery Owner's Manual
for advanced battery settings.
Adjusting Inverter Settings
1. See Table 1. Navigate to the inverter device page
using the right arrow key (next page right of the
home screen).
2. Push the center button.
3. Select Mod. Settings using the down arrow to scroll
and the center button to select.
4. Scroll through the settings using the up/down
arrow keys.
5. Use the center button to select a setting.
6. Use the up/down arrow keys to change the value of
a setting.
7. Use the center button to deselect a setting.
8. Scroll down and save all changes before exiting
the Mod. Settings menu.
9. Select Mod. Settings again to verify changes were
saved.
Table 1 - Adjusting Inverter Settings
SetpointRangeDefaultDescription
Channel for REbus communications. All devices in a system must use
PLM_Channel0 – 121
the same channel (except REbus Beacon). Do not set equipment to
channel 0 unless performing
Multiple Inverter System Commis-
sioning Procedure
.
TargMaxImprtP-30,000 to +30,000 Watts0
TargMinImprtP-30,000 to +30,000 Watts0
EnaIslandingon / offonAllows system to island, providing backup power during a grid outage.
EnaExtTransferon / offoff
ExtTransVolt50 – 200 Volts95
ExtTransTime1 – 360 Seconds15
Export Overrideon / offoff
PLM_Disableon / offoff
CalOverrideon / offoff
CTTurnsRatio1,500 – 3,000 Turns1,500Allows a different turns ratio to be set for specific CTs.
Maximum Threshold for importing power before the battery will dis-
charge in Self-Supply Mode to offset.
Minimum power import maintained by charging the battery from the grid
in Supply Mode.
Turn on if an external automatic transfer switch (ATS) has been installed
to operate with the Inverter.
Minimum voltage from the utility that must be present for the inverter to
reconnect an ATS back to the grid.
Length of time the inverter will wait to trigger an ATS to reconnect to the
utility upon sensing grid voltage return.
Formerly called Zero Export, this setting will inhibit the PWRcell system
from exporting power to the grid.
This setting will disable the power line communications coming from the
inverter.
Overrides inverter logic for automatic detection of included Generac cur-
rent transformers (CTs).
EnaLoadShedon / offoffTurn on if PWRcell ATS Controller or SMM devices have been installed.
Installation Manual for Generac PWRCell Inverter27
Page 32
Commissioning and Setup
(000627a)
DANGER
Electrocution. Never enable any device during an
installation or while wires are exposed. Doing so
will result in death, serious injury, or equipment or
property damage.
Inverter
PWRcell 2P Inv.
2.4Wh
248V
0W
-02
Disabled
AC Power:
AC Voltage:
E-total:
Enable
PWRcell 2P Inv.Menu
Mod. Settings
Calibrate CTs
RCPn: 000100073212
< EXIT SCROLL > NEXT • SELECT
Selecting Inverter Compliance Setting
(optional)
By default, all Generac PWRcell Inverters ship in compliance with UL 1741, including IEEE 1547. If the system
needs to be configured to comply with a different grid
interconnection standard, activate the new configuration
before proceeding via the Installer Configuration Tool.
See Installer Configuration Tool for more information.
Selecting ESS Grid Usage Mode
(Optional)
By default, all Generac PWRcell Inverters ship without
restrictions on how the PWRcell battery (ESS) may be
charged from, or supply power to, an interconnected utility grid. If the system needs to be configured to comply
with specific utility interconnection requirements, a different ESS Grid Usage Mode may be selected.
An ESS Grid Usage Mode is set through the Installer
Configuration Tool.
NOTE: The ESS Grid Usage Mode is one-time settable
and, therefore, once set cannot be changed by an
installer without support from Generac Power Systems.
Enabling REbus Devices
NOTE: All PWRcell devices are enabled and configured
individually through the PWRcell inverter control panel.
Following installation, the inverter must be enabled
before all other REbus devices.
To enable the inverter:
1. See Figure 6-7. Use the right arrow key to scroll
the inverter device page.
2. Verify inverter status reads disabled.
NOTE: There is no time allowance provided to further
change this mode after it is set.
There are two ESS Grid Usage Modes for PWRcell
equipment: Zero Import and Export Limiting.
Zero Import mode (CRD200 Export Only compliance)
allows the battery to export power to a connected utility
grid but will not allow the battery to be charged from the
utility grid. In this mode, the battery will only be charged
by a connected REbus source such as a PV Link. Power
from the battery can supply all local loads as well as supplying power to a utility (when connected). See Setting
for Import/Export Compliance for more information.
Export Limiting mode allows the user to restrict the export
to a connected utility grid to a Export Limit value set by
the installer. When the Export Limit value is set to 0, this
mode functions as like a “Zero Export” mode (CRD200
Import Only compliance) allowing the battery to be
charged from a connected utility grid but will not allow
any REbus-connected source (either from the battery or
PV) to export power to the utility grid. Configured this
way, the battery can be charged by a connected REbus
source and / or a utility grid source but no power will be
exported to the utility.
See Setting for Import/Export Compliance for more
information.
010010
Figure 6-7. Enabling Inverter (1 of 4)
3. Press the center button.
4. See Figure 6-8. Highlight Enable and press the
center button.
009656
010011
Figure 6-8. Enabling Inverter (2 of 4)
5. See Figure 6-9. Arrow right and press center
button to Confirm.
28Installation Manual for Generac PWRCell Inverter
Page 33
Commissioning and Setup
Enable
PWRcell 2P InvMenu
Mod. Settings
Calibrate CTs
RCPn: 00010003XXXX
< EXIT SCROLL > NEXT • SELECT
Enable
CancelConfirm
Inverter
PWRcell 2P Inv.
2.4Wh
248V
-36W
-02
grid connected
AC Power:
AC Voltage:
E-total:
TOU Scheduler
REbus Beacon
disabled
To enable scheduler,
press center button
and select “Enable”.
REbus BeaconMenu
Mod. Settings
Remove Device
RCPn: 00010003XXXX
< EXIT SCROLL > NEXT • SELECT
Enable
TOU Schedule:
Time Zone:
CancelSave
1
4
Access Code:57
010012
Figure 6-9. Enabling Inverter (3 of 4)
6. See Figure 6-10. The inverter is enabled. It will
create voltage at the DC terminals and begin communicating with connected REbus devices.
NOTE: Per UL1741, the PWRcell inverter may require
five minutes upon recovery from a grid outage or islanding event before exporting power.
010013
Figure 6-10. Inverter Enabled (4 of 4)
7. Enable all other REbus devices connected to the
system by repeating steps 1-5 for each device. For
further commissioning instruction for REbus
devices, see their respective installation manuals.
010109
Figure 6-11. Configuring TOU Schedule (1 of 4)
2. See Figure 6-12. Use the up and down arrows to
highlight Mod. Settings and press the center button
to enter the settings menu.
010110
Figure 6-12. Configuring TOU Schedule (2 of 4)
3. See Figure 6-13. Use the up and down arrows to
highlight Access Code and press the center button
to select.
4. Use the up and down arrows to set the Access
Code to 57, and press the center button.
NOTE: The access code is valid for five minutes. After
five minutes, the access code must be entered again to
enable changes.
REbus Beacon Setup
REbus Beacon allows the PWRcell system to manage
energy production and storage over the course of the
day. This is called Time of Use (TOU) energy management. To take advantage of this functionality, the PWRcell
system must include a PWRcell battery and a reliable
connection to the Internet via an Ethernet connection to a
router.
NOTE: Enabling and setup of the REbus Beacon is only
required when utilized for TOU scheduling. Otherwise, do
not enable the REbus Beacon.
Configuring and Running a TOU Schedule
1. See Figure 6-11. Navigate to the Beacon device
page and press the center button to enter the
device menu.
Installation Manual for Generac PWRCell Inverter29
010111
Figure 6-13. Configuring TOU Schedule (3 of 4)
5. Use the up and down arrows to highlight TOU
Schedule and press the center button to select.
Page 34
Commissioning and Setup
TOU Schedule:
Time Zone:
Cancel
1
4
Access Code:57
Save
TOU Scheduler
REbus Beacon
SDGE
Self Supply
1h:37m
running
Next Change:
To:
Schedule:
TOU Scheduler
REbus Beacon
SDGE
Self Supply
1h:37m
Priority Backup
Next Change:
To:
Schedule:
6. Use the up and down arrows to adjust the TOU
Schedule. Once the desired value is set, press the
center button to exit edit mode.
NOTE: See the latest Time of Use Program Guide for
current TOU schedule values. The program guide is
available at https://www.generac.com/resources-and-
7. Set the Time Zone to the desired location based on
Table 2: Time Zone Codes. Once the desired
value is set, press the center button to exit edit
mode.
Table 2 - Time Zone Codes
Time ZoneUnits
UTC0
US / Eastern1
US / Central2
US / Mountain3
US / Pacific4
US / Alaska5
US / Hawaii6
US / Arizona7
US / Puerto Rico8
8. See Figure 6-14. To commit changes to all entries,
highlight Commit. Press the center button, then
use the arrows and center button to confirm the
choice.
010113
Figure 6-15. Running.
010114
Figure 6-16. Current System Mode.
See Figure 6-17 and Figure 6-18. On the home page,
the text above the power flow diagram will alternate
between Scheduler Active and the current system mode.
010112
Figure 6-14. Configuring TOU Schedule (4 of 4)
See Figure 6-15 and Figure 6-16. When enabled, the
LCD will alternate between a TOU Scheduler Running
Screen and a Current System Mode screen. Both
screens will display the time until the next system change
and the mode the system will change to. The TOU
Schedule name will be listed at the bottom of the device
page.
30Installation Manual for Generac PWRCell Inverter
Figure 6-17. Scheduler Active
Figure 6-18. Current Mode
010115
010116
Page 35
Commissioning and Setup
TOU Scheduler
REbus Beacon
disabled
To enable scheduler,
press center button
and select “Enable”.
Enable
Rebus BeaconMenu
Mod. Settings
Calibrate CTs
RCPn: 00010003XXXX
< EXIT SCROLL > NEXT • SELECT
Enable
CancelConfirm
TOU Scheduler
REbus Beacon
SDGE
Self Supply
1h:37m
running
Next Change:
To:
Schedule:
Enable
Rebus BeaconMenu
Mod. Settings
Calibrate CTs
RCPn: 00010003XXXX
< EXIT SCROLL > NEXT • SELECT
Disable
CancelConfirm
TOU Scheduler
REbus Beacon
disabled
To enable scheduler,
press center button
and select “Enable”.
Enabling Beacon TOU
Once the TOU Schedule is set, the scheduler will automatically enable itself and begin running. However, if the
scheduler becomes disabled for any reason, follow the
instructions below to re-enable the scheduler:
1. See Figure 6-19. Navigate to the Beacon device
page and press the center button to enter the
device menu.
010118
Figure 6-19. Enabling Beacon (1 of 2)
2. Highlight Enable and press the center button.
3. See Figure 6-20. Arrow sideways to Confirm and
press the center button.
Disabling Beacon TOU
The scheduler can be disabled at any time. To disable
the scheduler:
1. See Figure 6-21. Navigate to the Beacon device
page and press the center button to enter the
device menu.
010113
Figure 6-21. Disabling Beacon (1 of 3)
2. Highlight Disable and press the center button.
3. See Figure 6-22. Arrow sideways to Confirm and
press the center button.
Figure 6-20. Enabling Beacon (2 of 2)
Installation Manual for Generac PWRCell Inverter31
011140
010117
Figure 6-22. Disabling Beacon (2 of 3)
4. See Figure 6-23. The status line on the Beacon
device page will read Disabled.
NOTE: The system will remain in the current system
mode until the mode is changed manually or the scheduler is re-enabled.
010118
Figure 6-23. Disabling Beacon (3 of 3)
Page 36
Commissioning and Setup
TOU Scheduler
REbus Beacon
SDGE
Self Supply
1h:37m
running, overridden
Next Change:
To:
Schedule:
IP: 192.168.158.37
MAC:00:04:a3:0b:77:fc
DHCP: bound, 83285s
ARP: idle
DNS: done
ctr btn: net settings
IP Settings
Network Settings Menu
< EXIT SCROLL > NEXT • SELECT
Disable Ethernet
Temporarily Overriding the TOU Scheduler
The scheduler can be temporarily overridden at any time
without disabling it. A manual override will apply until the
next regularly scheduled system mode change.
To temporarily override the scheduler:
1. Navigate to the system home page.
2. Press the center button.
3. Select the desired temporary system mode.
NOTE: See the Generac PWRcell Inverter Owner’s
Manual for more information on system modes.
When the scheduler has been overridden:
• Temporary Override will display on the home page,
alternating with the words Scheduler Active and
the name of the current system mode.
• See Figure 6-24. Running, Overridden will display
on the Beacon device page.
NOTE: If Priority Backup mode is not listed with the other
system modes, the system installer may have removed
the mode to comply with utility rules. Some utilities do not
permit a battery to charge from the grid..
Manually Configuring IP Settings
NOTE: On networks not configured for DHCP, use the
MAC address to locate the device on the network.
To manually configure settings:
1. Disconnect and move the blue Cat 5 connector
connected to the topside of the Beacon to the RJ45 Ethernet port on the backside of the inverter
Control Panel.
2. See Figure 6-25. When step 1 is conducted properly and the inverter is receiving Internet, the
inverter control panel will have an additional device
page to configure Ethernet Settings. From the
home screen, press the left arrow key.
010119
Figure 6-24. Overriding Scheduler
• The countdown timer on the Beacon device page
will indicate the remaining time until the next mode
change.
After the next scheduled mode change, the scheduler will
resume normal operation.
Disabling the TOU Scheduler in Anticipation of a
Grid Outage
In the event of an impending storm and potential outage,
top off the battery by disabling the scheduler and switching the system mode to priority backup or clean backup
mode.
To disable the TOU Scheduler:
1. Navigate to the Beacon device page and disable
the scheduler. See Enabling Beacon TOU for
more information.
2. Navigate to the system home page and change the
system mode to a backup-only mode, such as Priority Backup or Clean Backup. See the Generac
PWRcell Inverter Owner’s Manual for more information on system modes.
3. Once the emergency has passed, re-enable the
scheduler. See Enabling Beacon TOU for more
information.
32Installation Manual for Generac PWRCell Inverter
Figure 6-25. Ethernet Configuration (4 of 4)
3. See Figure 6-26. Press the center button from the
Ethernet settings screen and select IP Settings.
Figure 6-26. Ethernet Configuration (1 of 2)
009981
010048
Page 37
4. See Figure 6-27. From the IP Settings menu select
IP: 192.168.158.37
MAC:00:04:a3:0b:77:fc
DHCP: bound, 83285s
ARP: idle
DNS: done
ctr btn: net settings
Manual.
Figure 6-27. Ethernet Configuration (2 of 2)
5. Adjust any of the following:
• IP
• Subnet Mask
• DNS
• Gateway
NOTE: Contact your network system administrator to
connect the PWRcell inverter to a restricted network.
6. Disconnect and move blue Cat 5 connector back to
its original RJ-45 connection port on the topside of
the Beacon.
NOTE: Beacon must retain an Internet connection in
order to use the PWRview mobile app.
Ethernet Troubleshooting
NOTE: Use a laptop or other device to verify the Internet
connection is working properly before troubleshooting.
For a successful connection the following must be valid:
• The Internet LED on the control panel must be lit.
NOTE: A lit Internet LED is a necessary, but not suffi-
cient indication of a successful connection to the PWRview server. The blue LED may be lit even if the inverter
is not connected to the server.
• A valid IP address must be displayed on the Ether-
net settings page.
To validate the connection to the server, the Ethernet settings page must be accessed. To access the Ethernet
settings page:
1. Relocate the blue Cat 5 cable connector inserted
into the RJ-45 port on the top of the Beacon to the
RJ-45 port on the backside of the inverter control
Panel.
2. Navigate the inverter control panel to access a
screen similar to Figure 6-28. When properly
installed, the inverter control panel will have an
additional device page for Ethernet Settings.
010049
Commissioning and Setup
009981
Figure 6-28. Ethernet Troubleshooting
NOTE: Ensure blue Cat 5 cable is reconnected to the
Beacon after troubleshooting is complete.
On the Ethernet settings page, the PWRview State
should read “Listen”, then a successful connection has
not been made to the PWRview server.
If the inverter does not automatically connect to the
network and begin communicating with the PWRview
server, perform the following steps:
1. Verify an Ethernet connection has been enabled by
pressing the center button on the Ethernet page
and selecting Enable Ethernet.
2. Verify the network is configured for DHCP and that
DHCP is enabled.
3. If the network is not configured for DHCP, obtain
the MAC address and contact the system
administrator for IP address assignment.
4. Input IP address under Manual settings. See
Registration.
5. Restart router and modem.
6. Contact system administrator for further
troubleshooting steps.
NOTE: It is the installer’s responsibility to make sure the
Internet connection is reliable and secure. Generac
recommends always using a hardwired connection.
Generac does not recommend or support using any
wireless or power line carrier network devices. Use these
devices at your own discretion.
Commissioning Multiple Inverter
Systems
PLM Crosstalk
NOTE: Do not energize two or more inverters before
commissioning. Energizing two or more inverters prior to
commissioning will result in crosstalk.
PWRcell inverters are manufactured with some common
default parameters. One of these default parameters is
the default Power Line Modem (PLM) channel. PWRcell
inverters use the PLM channel to communicate with and
Installation Manual for Generac PWRCell Inverter33
Page 38
Commissioning and Setup
send commands to REbus-powered devices. In this way,
a PWRcell inverter behaves like a master device. If two
or more master devices are communicating on the same
PLM channel, REbus devices become unable to respond
properly to the intended master device and the master
devices will attempt to provide control for the other, often
leading to communication and reporting issues. This is
referred to as cross-talk.
How to identify PLM Crosstalk
Cross-talk can be easily identified by navigating to the
device pages on an inverter control panel. If two inverter
device pages exist, crosstalk has occurred. Similarly, if
any REbus devices from one inverter show up on
another, crosstalk has occurred.
NOTE: To differentiate one inverter device page from
another, confirm the RCP numbers via the device page
sub-menu.
NOTE: It is recommended to keep a list of which REbus
devices are connected to specific inverters at multi-system sites.
Multiple Inverter System Pre-Commissioning
Checklist
Before commissioning multiple inverter systems, confirm
the following:
• Inverter systems (including PV Links and PWRcell
batteries) have been installed per manufacturer
instructions and to local and state code requirements.
• PWRcell batteries have their Battery Disconnect
switches in the OFF position.
• PWRcell inverters are de-energized with no volt-
age present at their AC Grid input terminals. Use
an appropriately rated multi-meter/voltmeter to verify if AC voltage is present at the AC Grid terminals.
NOTE: To determine if the inverter is de-energized,
check the inverter control panel and the system backfeed
breaker. If de-energized, the inverter control panel will be
powered off and the inverter backfeed breaker will be
OPEN.
Multiple Inverter System Commissioning
Procedure
NOTE: Throughout this process, it is important that only
one inverter is energized at any time. If two or more
inverters are energized at any point during this process,
the inverters will cross-talk. To resolve crosstalk, see
PLM Crosstalk Recovery Procedure. After resolving
crosstalk, the commissioning process will need to be
restarted for the cross-talked inverters.
1. Close the AC backfeed breaker to supply AC
power to one PWRcell Inverter AC Grid Input/Out-
put Terminals. This will allow the inverter to energize and illuminate the Inverter control panel.
2. Perform Commissioning the System steps 1-7.
3. Modify the PWRcell inverter PLM Channel to 0.
NOTE: PLM Channel 0 is a catchall channel. Only use
for inverters during programming. Do not set REbus
devices to channel 0. Do not leave inverter on channel 0.
4. Choose a channel from 2 – 12 to use as the only
number for addressing all devices on the system.
The goal is to address the system to its own unique
channel across all devices.
NOTE: Do not leave any device, including the inverter,
on channel 0 or channel 1 by the end of the process.
5. Use arrow keys to navigate to all REbus devices
(expect REbus Beacon) to change the PLM channel.
6. Access Mod. Settings for each device and change
the PLM channel to the chosen channel (step 4) for
that system. See device installation manual for
specific instructions.
7. Modify the PLM channel setpoint for the PWRcell
inverter to match the PLM channel its REbus
devices were set to in the previous step.
NOTE: Be sure to click Save at the bottom of the menu
after modifying the channel on each device.
8. De-energize inverter. Once the inverter is de-energized, repeat steps 1 – 7.
NOTE: It may take a few seconds for the inverter screen
to power off due to capacitance in the power core. Wait
until the screen goes blank before energizing the next
inverter.
9. After programming each system separately, reenergize all PWRcell inverters by closing their AC
Grid backfeed breakers, enable the inverters, and
all REbus devices.
PLM Crosstalk Recovery Procedure
For each PWRcell Inverter that has crosstalked, perform
the following procedure to clear the foreign devices from
the display after the multi-inverter system has been properly commissioned:
1. De-energize all but one inverter.
2. Access the Installer Configuration Tool using the
instructions below.
3. Navigate to the Inverter using the Installer Tool and
select PWRcell Configuration.
4. Select Clear Display to wipe the screen of that
inverter of unwanted devices from other systems
on site.
5. Follow steps 1 – 8 for Multiple Inverter System
Commissioning. See Multiple Inverter System
Commissioning Procedure for more information.
34Installation Manual for Generac PWRCell Inverter
Page 39
Commissioning and Setup
6. Proceed to next crosstalked inverter and repeat the
procedure.
Installer Configuration Tool
The Installer Configuration Tool allows configuration and
provisioning of Generac PWRcell systems from a smartphone or laptop. The interface allows installers to configure basic settings, set inverter compliance, generate a
compliance report, and understand system performance.
The interface is only available on Generac PWRcell systems with a REbus Beacon installed. Close proximity to
the Beacon is required for use. It is not possible to
access this tool remotely. 45 minutes after being activated, the Beacon’s WIFI signal will time out and may
need to be reactivated. For Beacon installation instructions, see REbus Beacon Setup.
NOTE: All PWRcell inverters come with a REbus
Beacon pre-installed.
Accessing the Installer Configuration Tool
1. Navigate to the Beacon device page on the PWR-
cell inverter control screen and press the center
button.
2. Select Installer Tool from the menu and click Confirm. This will activate the Beacon’s Wi-Fi network.
3. Use a smartphone or laptop to connect to the Wi-Fi
network SSID titled: REbus_Beacon_xxxx where
xxxx is the last 4 digits of the Beacon’s RCP number.
NOTE: The Beacon’s RCP number can be found on the
front of the Beacon located inside the inverter, as well as
on the Beacon device page through the inverter’s screen.
To find this number through the inverter’s screen press
the center button on the Beacon device page. The RCP
number will be displayed at the bottom of the menu
screen.
browser URL. The installer tool will appear in the
browser.
010981
Figure 6-29. Installer Configuration Tool
Configuring Basic PWRcell Settings
NOTE: To customize basic settings, the inverter must be
disabled. Before disabling the inverter, ensure all REbus
devices have first been disabled. Settings changes will
not be applied if the inverter is enabled.
1. Select Inverter from the Beacon menu.
NOTE: If using a smartphone, open the menu by click-
ing the hamburger icon in the upper-right corner of the
screen. Laptop users will see the menu displayed on the
left side of the screen.
2. Select PWRcell Configuration.
4. Type in the password (labeled “CODE”) for the
REbus Beacon's Wi-Fi network.
NOTE: The code for the REbus Beacon’s Wi-Fi network
is located on the back of the Beacon inside of the
inverter. The Beacon is mounted on the upper left-hand
sidewall of the inverter housing. Unstick the Beacon to
view the code labeled on the back.
NOTE: Where utility requirements contain provisions for
security against adjusting compliance settings, consider
removing code label for the Beacon after successful
commissioning.
5. See Figure 6-29. Open a web browser on a smartphone or laptop and enter 10.10.10.10 for the
Installation Manual for Generac PWRCell Inverter35
Page 40
Commissioning and Setup
3. See Figure 6-30. To adjust a setting, click on it,
select the desired change, and click Submit. Any
changes selected to be made, will not be implemented unless Submit is selected at the end.
011978
Figure 6-30. PWRcell Configuration
All settings can be adjusted through the inverter’s screen
with the exception of the following two settings, which
can only be adjusted though the Installer Configuration
Tool:
• Enabled SysModes. Allows installers the option to
disable system modes, such that they cannot be
enabled through the inverter control screen. To disable a system mode, tap the checkbox to uncheck
the box for that mode. Click Submit to save.
• Clear Display. Allows installers to wipe the screen
of any unwanted devices being retained by the
memory card in the screen module. Select Clear
and click Submit. The screen will go blank and test
its LEDs. Allow time for the screen to reload before
accessing.
that may not come default to the unit installed. The software version of an inverter can be verified using the Beacon Installer Tool. To verify the inverter software version
in the Beacon Installer Tool, select the 'Common' submenu option under the “Inverter” object as shown in Fig-
ure 6-31.
011979
Figure 6-31. Verifying Inverter Software
The information populated upon selecting the 'Common'
sub-menu option lists the manufacturer, model, version,
and serial number for the inverter. The value displayed
for 'Version' contains the hardware version and software
version of the inverter displayed as the sequence of numbers separated by an underscore. Where a “H” represents the hardware version and a “S” represents the
software version, the value shown for 'Version' would be
“HHH_SSSSS”.
Setting for Import/Export Compliance
NOTE: The PWRcell Inverter must be disabled prior to
making changes to import or export settings.
Utility interconnection requirements may require the abil-
ity to restrict or limit system import or export power from/
to the Utility grid. To setup a PWRcell system to comply
with these requirements, access the PWRcell Configurations page following the instructions in Configuring Basic
PWRcell Settings through the Inverter sub-menu. Once
the configuration page loads, you may adjust import and
export settings.
Once all settings adjustments have been made, click the
“Submit Query” button at the bottom of the configuration
page. Import and Export settings are explained in detail
below.
NOTE: These settings are included in the Compliance
PDF. See Proof of Compliance section for more information.
36Installation Manual for Generac PWRCell Inverter
Page 41
Export Limiting: This option is one-time settable. To
unset Export Limiting, please contact Generac PWRcell
Technical Support. Please be aware that once set, certain Utilities may require the request to unset this setting
come from the Utility. Changing this setting from “DISABLED” to “ENABLED” via the dropdown list will limit the
inverter power export to the utility grid to the value specified for Export Limit.
Export Limit: Once set from its default value, this feature’s value can only be decreased from its current value.
Please be aware that once set, certain Utilities may
require the request to unset this setting come from the
Utility. To reset the value of this feature, please contact
Generac PWRcelll Technical Support. The units for this
feature are Watts. The value of this setting is the limit to
what the inverter can export to the grid once the ExportLimiting is enabled. To set the inverter so that it does not
export any excess power to the grid, set this value to 0.
This will enforce CRD200 Import Only Mode.
NOTE: This feature is only available for inverter firmware version 13310 or greater. See Verifying Inverter
Software Version for more details. To request a firm-
ware update for an inverter, please contact Generac
PWRcell Technical Support.
Zero Import: This option enforces CRD200 Export Only
mode and is one-time settable. Please be aware that
once set, certain Utilities may require the request to
unset this setting come from the Utility. To unset Zero
Import, please contact Generac PWRcell Technical Support. Changing the value from “DISABLED” to
“ENABLED” via the dropdown list will prevent the PWRcell batteries from importing power from the utility grid.
Commissioning and Setup
010983
Figure 6-32. Utility Compliance Configuration
NOTE: Verify the Compliance Selection field shows the
desired compliance rule after clicking Submit.
NOTE: For multi-system sites, compliance must be set
on each inverter separately through each respective Beacon.
NOTE: This feature is only available for inverter firmware
version 13310 or greater. See Verifying Inverter Soft-
ware Version for more details. To request a firmware
update for an inverter, please contact Generac PWRcell
Technical Support.
Setting Inverter Grid Compliance
NOTE: The inverter must be disabled before changing
utility compliance settings. Before disabling inverter,
ensure that all REbus devices have first been disabled.
Compliance settings changes will not be applied if
inverter is enabled.
1. To set an inverter to comply with a utility’s require-
ments, navigate to the drop-down menu in the
upper right-hand corner of the Installer Configuration Tool home page and select Inverter from the
drop-down menu.
2. See Figure 6-32Click on Utility Compliance Con-
figuration and select the appropriate utility compliance standard from the menu at the bottom of the
page. Click Submit to apply the compliance standard. The settings entered will not take effect until
the Submit button has been clicked.
Installation Manual for Generac PWRCell Inverter37
Page 42
Commissioning and Setup
Proof of Compliance
The Compliance PDF validates whether the system has
been set up to conform to a utility compliance ruleset.
Please double check the system is configured properly
by observing the ‘In compliance with’ line in the PDF. If
your utility requires proof of correct configuration, save
this PDF and send it to your utility. It is recommend you
keep a copy on file as well.
1. To generate a proof of compliance PDF, click on
the Compliance PDF tab in the navigation menu.
2. Click on Download Report.
3. A new window will open in the browser with the
report. Verify information is correct and save the
document or send via email.
Figure 6-33. Proof of Compliance
010984
38Installation Manual for Generac PWRCell Inverter
Page 43
Section 7: Maintenance
(000642)
DANGER
Electrocution. Verify all system voltages are safe before
wiring. Disconnect all AC and DC sources of power before
touching terminals. Failure to ensure no dangerous
voltages are present on conductors and terminals before
wiring will result in death or serious injury.
(000600)
DANGER
Electrocution. Initiate a system-wide shutdown and turn the
PWRcell DC Disconnect Switch OFF on all connected
batteries before performing service. Failure to do so will
result in death, serious injury, or equipment and property
damage.
Equipment damage. Never replace a fuse with a
different size or style. Doing so will void the inverter
warranty and could result in equipment or property
damage.
(000653a)
CAUTION
(000652a)
CAUTION
Equipment damage. Never remove DC fuses under
load. Removing DC fuses under load could result in
equipment or property damage.
Service
Maintenance
C
B
A
For any servicing needs, contact the nearest Independent Authorized Service Dealer (IASD), contact Generac
PWRcell Technical Support at 1-855-635-5186, or call
Generac Customer Service at 1-888-436-3722 (1-888GENERAC), or visit www.generac.com.
Accessing Wiring Compartment
To access the wiring compartment:
1. Initiate an inverter shutdown.
2. Allow DC voltage to drop to below 10VDC.
3.
See
Figure 7-1. Open all PWRcell DC Disconnects
(A). Verify DC voltage reported on LCD screen has
dropped to below 10VDC.
4. Disconnect AC Grid source from inverter. Wait for
Inverter LCD screen to turn off.
5.
Open inverter front cover by lifting the bottom to
horizontal (B) and pushing inward (C).
6. Locate wiring compartment cover (D).
7. Remove five M4X10 screws (E) and wiring
compartment cover.
8. Verify all PWRcell DC and AC terminals are below
10V
E
D
010238
Figure 7-1. Wiring Compartment
Replacing Fuses
Two main fuses are installed between the power core
and the PWRcell DC disconnects. See PWRcell Inverter
Wiring Compartment for location.
If a main fuse has blown, determine the root cause of the
issue before replacing it. For assistance, contact the
nearest Independent Authorized Service Dealer (IASD),
contact Generac PWRcell Technical Support at 1-855635-5186, or call or Generac Customer Service at 1-888436-3722 (1-888-GENERAC), or visit
www.generac.com.
Owner’s Manual for Generac PWRcell Inverter39
Page 44
Maintenance
To replace a fuse:
1. Initiate an inverter shutdown. See Shutdown
Mode for more information.
2.
See
Figure 7-1. Open all PWRcell DC Disconnects
(A). Verify DC voltage reported on LCD screen has
dropped to below 10VDC.
3. Disconnect all sources of AC and DC Power.
4. Remove wiring compartment cover. See Access-
ing Wiring Compartment.
5. See Figure 7-2. Locate DC fuse holders (B).
6. Using a multi-meter, verify all PWRcell DC and AC
terminals are below 10V.
7. Press fuse holder up and turn counterclockwise to
release.
8. Remove fuse from fuse holder and check for continuity using a multi-meter.
9. Insert replacement fuse into fuse holder.
10. Reinstall fuse holder. Turn clockwise until tight.
B
Recovery From an Error State
Error events will force the PWRcell inverter into an error
state where no DC power is exported, though voltage
may still be present on REbus from connected devices.
To recover a device from an error state, use the front
control panel to disable and then enable to device.
If the system is unable to be accessed, but is connected
to the Internet, contact Generac Technical support for
assistance in resetting an error state.
A
010018
Figure 7-2. Removing Wiring Compartment Cover
40Installation Manual for Generac PWRcell Inverter
Page 45
Troubleshooting
Section 8: Troubleshooting
General Troubleshooting
Some of the more common problems are listed in the table below. This information is intended to be a check or
verification that simple causes can be located and fixed. It does not cover all types of problems. Procedures that
require in-depth knowledge or skills should be referred to an Independent Authorized Service Dealer.
Table 8-1. General Troubleshooting Guide
ProblemPossible CauseSolution
System will not exit
Shutdown
CTs will not calibrate
No REbus Beacon device
page
Inverter isn’t connected to
server
External shutdown button
depressed
No jumper between STOP
terminals
Loose connectionCheck CT wiring.
Beacon USB cable not
connected
Beacon wrap-around cable
not connected
Inverter not connected to the
Internet
Release external shutdown button.
Verify jumper is in place between STOP terminals.
Trigger manual CT calibration from the inverter device menu.
Verify the USB cable is correctly connected to the Beacon and also
to the Beacon accessory port in the inverter wiring compartment.
Inspect exposed sections of cable for damage.
Verify the short wrap-around cable is plugged into Beacon, from one
port to the other.
Verify the inverter is connected to the Internet via a router.
If problems persist, contact the nearest Independent Authorized Service Dealer (IASD), contact Generac PWRcell
Technical Support at 1-855-635-5186, or call Generac Customer Service at 1-888-436-3722 (1-888-GENERAC).
Installation Manual for Generac PWRCell Inverter41
Page 46
Troubleshooting
This page intentionally left blank.
42Installation Manual for Generac PWRCell Inverter