Generac XT8000E User Manual

Owner’s Manual
XT8000E Series Portable Generator
* *
*
Reference all appropriate documentation. This manual should remain with the unit.
NOT INTENDED FOR USE IN CRITICAL LIFE SUPPORT APPLICATIONS.
DEADLY EXHAUST FUMES! USE OUTSIDE, ONLY, FAR AWAY FROM WINDOWS, DOORS AND VENTS!
WARNING!
California Proposition 65
Engine exhaust and some of its constituents are known to the state of California to cause cancer,
birth defects, and other reproductive harm.
WARNING!
California Proposition 65
This product contains or emits chemicals known to the state of California to cause cancer,
birth defects, and other reproductive harm.
ii

Table of Contents

MODEL DATA DECAL

Unit Information

Unit Information ..........................................................iii
Frequently Asked Questions .................................... iv
Section 1 - Safety ........................................................1
1.1 Read This Manual Thoroughly................................ 1
1.2 Safety Rules............................................................ 1
Section 2 - General Information.................................5
2.1 Unpacking ...............................................................5
2.2 Assembly ................................................................ 5
2.3 Emissions Information.............................................6
2.4 Product Specifications ............................................7
2.5 Know The Generator...............................................7
2.6 Before Starting the Generator............................... 10
Section 3 - Operation................................................13
3.1 How To Use The Generator.................................. 13
3.2 Generator Loads ................................................... 14
3.3 Wattage Reference Guide ....................................14
3.4 Starting The Generator (Electric Start) ................. 14
3.5 Starting The Generator (Manual/Recoil)
Starting ..................................................................15
3.6 Stopping The Generator ....................................... 15
3.7 Low Oil Level Shutdown System .......................... 15
Use this page to record important information about your generator set.
Record the information found on your unit data label on this page. The location of the unit data label is shown here.
When contacting an Authorized Service Dealer about parts and service, always supply the complete model number and serial number of the unit.
Section 4 - Maintenance ........................................... 17
4.1 General Recommendations ..................................17
4.2 Generator Cleaning...............................................17
4.3 Service Intervals ...................................................17
4.4 Generator Storage ................................................22
Section 5 - Troubleshooting .................................... 23
5.1 Troubleshooting Guide..........................................23
5.2 Replacement Service Parts ..................................24
MODEL NO:
SERIAL NO:
Operation and Maintenance: Proper maintenance and care of the generator ensures a minimum number of problems and keep operating expenses at a minimum. It is the operator’s responsibility to perform all safety checks, to make sure that all maintenance for safe opera­tion is performed promptly, and to have the equipment checked periodically by an Authorized Service Dealer. Normal maintenance, service and replacement of parts are the responsibility of the owner/operator and, as such, are not considered defects in materials or workmanship within the terms of the warranty. Individual operating hab­its and usage may contribute to the need for additional maintenance or service.
When the generator requires servicing or repairs, contact an Authorized LOWES Service Dealer for assistance. Authorized service technicians are factory-trained and are capable of handling all service needs.
iii

Frequently Asked Questions

Q: What oil can I use if I am out of the recommended
oil and need to operate my generator?
A: In an emergency, oil with an API rating of SH, SJ, SK,
CF-4, CG-4, ILSAC, GF-1, GF-2 or GF-4 can be used. It can be mineral, semi-synthetic or synthetic. Any of the following viscosities are permissible: SAE 5W-30, 10W-30, 10W-40, 20W-50, 30 or 40 weight.
Change the oil as soon as possible using genuine
Generac oil as per the Owner’s Manual recommendations.
Q: What needs to be done to the fuel before
extended storage?
A: First treat the remaining gasoline in the fuel tank with
a commercially available fuel stabilizer. Now the fuel can either be drained, or left in the tank after following proper treatment procedures. When working with flammable gasoline, exercise all appropriate cautions and warnings contained in this
Owner’s Manual. The sections on
Generator
Storage and Long Term Storage detail
proper storage procedures, including fuel storage treatment.
Q: How often do I have to charge the generator’s
battery?
A: If the starter will not turn the engine over, charge the
battery using the charger provided with your generator. The charger should be connected for no longer than 48 hours. Charging procedures are
covered in the Owner’s Manual.
Q: What is the proper fuel to use?
A: Regular UNLEADED gasoline is the recommended
fuel. Do not use gasoline with an ethanol concentration greater than 10%. Do not use E85 gasoline or mix oil with gasoline. PREMIUM grade fuel can be used, but is not required.
Q: What do the “red” and “blue” colored dots on the
extension cord receptacles mean?
A: The extension cord outlets have red and blue colored
dots at the receptacle outlet ends. These indicate the need to balance the loads on the generator when adding electrical devices. For example, if adding two
electrical devices, plug one into a red outlet and the other into a blue outlet rather than two red or two blue outlets. This will help balance the loads applied to the generator.
Battery Charging section of this
Q: Can I operate the generator in the rain?
A: Portable generators should never be run inside an
enclosed space. However, portable generators are intended to be used during extreme weather and for the sensitive electronics on them, it is best if some sort of open covering can be used to protect it from direct rain or snow. Great options would be a car port or boat canopy with 4 open sides or a tarp overhang from a tree. It is very important to provide adequate ventilation for the generator, so any sort of protection should be at least 5 feet from any side including the top of the unit, while in use. If protection is not available, the unit can be used in rain or snow, preferably with the muffler facing away from the direction the wind/rain/snow is coming from. Additionally, a portable generator should always be stored inside when not in use to prevent unnecessary wear and tear. BE ADVISED, the generator should NEVER be used in any enclosed space including, without limitation, a shed, home, garage, trailer or vehicle, even if the doors are left open, as this can damage the engine and can be a serious fire hazard and carbon monoxide risk.
Q: How do I adjust the valve clearance?
A: Valve clearance adjustment is critical to proper
engine operation and requires special tools and training. Instructions are covered in the
Clearance Adjustment
publication. However, if you are uncomfortable performing this service procedure, have your dealer maintain the generator’s valve clearance at the intervals specified.
section of this
Valve
iv
Q: How long can I operate the generator? Does it
need a “rest” or “break”?
A: Your generator can be operated almost indefinitely.
Most important is maintaining a proper oil level. Each time you add fuel, turn the generator off and check the oil level and add oil, if necessary, to keep the level at the upper mark on the dipstick. See the
Checking Oil Level and Adding Fuel sections
for instructions on adding oil and fuel.
Q: Is there anything special I need to do or unplug
my electrical devices before turning the generator off?
A: Yes, remove all loads BEFORE turning the generator
off. Do this by turning off appliances, lights and items being powered by the generator. Then unplug the items from the generator’s receptacles before allowing the generator to cool and turning the generator off. NEVER turn the generator off while
loads are applied. Refer to the section of the Owner’s Manual for complete instructions on adding and removing electrical devices.
Generator Loads
Q: The Hourmeter said it was time to service the air
filter. After the service has been performed, does anything need to be done to the Hourmeter?
A: The Hourmeter will alert the owner continuously for
one hour before until one hour after scheduled maintenance has been reached. Oil changes (at 100 hours) or air filter servicing (at 200 hours).
As hours of operation continue to accumulate, the
hourmeter will automatically reset itself until the next 100 or 200 hour service interval is reached. See the
Hourmeter section for additional information.
Some generators have a reset button that allows the
operator to move between maintenance intervals and reset intervals by holding the reset button for 9 seconds. NOTE: not all generator models have the reset button feature.
Q: The generator’s battery will no longer accept a
charge. What is the procedure for replacing with a new battery?
A: Battery replacement procedures can be found in the
Battery Replacement section of this Owner’s
Manual.
Q: If the generator is being used during an outage,
how do I connect or disconnect electrical devices?
A: NEVER start or stop the generator’s engine with
electrical devices plugged into the generator AND those devices turned on. It is important that electrical devices, that are turned on, NOT be connected to the generator before it is operating.
With the generator turned OFF, only connect elec­trical devices that are turned OFF. The generator should never be started or stopped when electrical devices or appliances that are drawing electrical power are connected.
With the generator turned ON, electrical devices
that are turned ON or OFF may be connected.
v
This page intentionally left blank.
vi
*
$
!
+

Section 1 Safety

Thank you for purchasing this model by Generac Power Systems, Inc. This model is a compact, high perfor­mance, air-cooled, engine driven generator designed to supply electrical power to operate electrical loads where no utility power is available or in place of utility due to a power outage.

1.1 — READ THIS MANUAL THOROUGHLY

If any portion of this manual is not understood, contact the nearest Authorized Dealer for starting, operating and servicing procedures.
The operator is responsible for proper and safe use of the equipment. We strongly recommend that the operator read this manual and thoroughly understand all instruc­tions before using the equipment. We also strongly rec­ommend instructing other users to properly start and operate the unit. This prepares them if they need to oper­ate the equipment in an emergency.
The generator can operate safely, efficiently and reliably only if it is properly located, operated and maintained. Before operating or servicing the generator:
• Become familiar with and strictly adhere to all local, state and national codes and regulations.
• Study all safety warnings in this manual and on the product carefully.
Become familiar with this manual and the unit before use. The manufacturer cannot anticipate every possible cir-
cumstance that might involve a hazard. The warnings in this manual, and on tags and decals affixed to the unit are, therefore, not all inclusive. If using a procedure, work method or operating technique that the manufacturer does not specifically recommend, ensure that it is safe for others. Also make sure the procedure, work method or operating technique utilized does not render the genera­tor unsafe.
THE INFORMATION CONTAINED HEREIN WAS BASED ON MACHINES IN PRODUCTION AT THE TIME OF PUBLICATION. GENERAC RESERVES THE RIGHT TO MODIFY THIS MANUAL AT ANY TIME.
Save these instructions for future reference. If you loan this device to someone, ALWAYS loan these instructions to the individual as well.

1.2 — SAFETY RULES

Throughout this publication, and on tags and decals affixed to the generator, DANGER, WARNING, CAUTION and NOTE blocks are used to alert personnel to special instructions about a particular operation that may be haz­ardous if performed incorrectly or carelessly. Observe them carefully. Their definitions are as follows:
INDICATES A HAZARDOUS SITUATION OR ACTION WHICH, IF NOT AVOIDED, WILL RESULT IN DEATH OR SERIOUS INJURY.
Indicates a hazardous situation or action which, if not avoided, could result in death or serious injury.
Indicates a hazardous situation or action which, if not avoided, could result in minor or moderate injury.
NOTE:
Notes contain additional information important to a
procedure and will be found within the regular text
body of this manual.
These safety warnings cannot eliminate the hazards that they indicate. Common sense and strict compliance with the special instructions while performing the action or service are essential to preventing accidents.
Four commonly used safety symbols accompany the DANGER, WARNING and CAUTION blocks. The type of information each indicates is as follows:
This symbol points out important safety infor­mation that, if not followed, could endanger personal safety and/or property of others.
This symbol points out potential explosion hazard.
This symbol points out potential fire hazard.
This symbol points out potential electrical shock hazard.
XT8000E Series Portable Generator 1
1.2.1 — General Hazards
• NEVER operate in an enclosed area, in a vehicle, or indoors EVEN IF doors and windows are open.
• For safety reasons, the manufacturer recommends that the maintenance of this equipment is carried out by an Authorized Dealer. Inspect the generator regu­larly, and contact the nearest Authorized Dealer for parts needing repair or replacement.
• Operate generator only on level surfaces and where it will not be exposed to excessive moisture, dirt, dust or corrosive vapors.
• Keep hands, feet, clothing, etc., away from drive belts, fans, and other moving parts. Never remove any fan guard or shield while the unit is operating.
• Certain parts of the generator get extremely hot during operation. Keep clear of the generator until it has cooled to avoid severe burns.
• Do NOT operate generator in the rain.
• Do not alter the construction of the generator or change controls which might create an unsafe operat­ing condition.
• Never start or stop the unit with electrical loads con­nected to receptacles AND with connected devices turned ON. Start the engine and let it stabilize before connecting electrical loads. Disconnect all electrical loads before shutting down the generator.
• Do not insert objects through unit’s cooling slots.
• When working on this equipment, remain alert at all times. Never work on the equipment when physically or mentally fatigued.
• Never use the generator or any of its parts as a step. Stepping on the unit can stress and break parts, and may result in dangerous operating conditions from leaking exhaust gases, fuel leakage, oil leakage, etc.
1.2.2 — Exhaust & Location Hazards
Never operate in an enclosed area or indoors! NEVER use in the home, in a vehicle, or in partly enclosed areas such as garages, EVEN IF doors and windows are open! ONLY use outdoors and far from open windows, doors, vents, and in an area that will not accumulate deadly exhaust.
• The engine exhaust fumes contain carbon monoxide, which you cannot see or smell. This poisonous gas, if breathed in sufficient concentrations, can cause unconsciousness or even death.
• Adequate, unobstructed flow of cooling and ventilating air is critical to correct generator operation. Do not alter the installation or permit even partial blockage of ventilation provisions, as this can seriously affect safe operation of the generator. The generator MUST be operated outdoors.
• This exhaust system must be properly maintained. Do nothing that might render the exhaust system unsafe or in noncompliance with any local codes and/or stan­dards.
• Always use a battery operated carbon monoxide alarm indoors, installed according to the manufactur­ers instructions.
• If you start to feel sick, dizzy, or weak after the genera­tor has been running, move to fresh air IMMEDI­ATELY. See a doctor, as you could have carbon monoxide poisoning.
2 XT8000E Series Portable Generator
1.2.3 — Electrical Hazards
• The generator produces dangerously high voltage when in operation. Avoid contact with bare wires, ter­minals, connections, etc., while the unit is running, even on equipment connected to the generator. Ensure all appropriate covers, guards and barriers are in place before operating the generator.
• Never handle any kind of electrical cord or device while standing in water, while barefoot or while hands or feet are wet. DANGEROUS ELECTRICAL SHOCK
MAY RESULT.
• The National Electric Code (NEC) requires the frame and external electrically conductive parts of the gener­ator be properly connected to an approved earth ground. Local electrical codes may also require proper grounding of the generator. Consult with a local elec­trician for grounding requirements in the area.
• Use a ground fault circuit interrupter in any damp or highly conductive area (such as metal decking or steel work).
• Do not use worn, bare, frayed or otherwise damaged electrical cord sets with the generator.
• Before performing any maintenance on the generator, disconnect the engine starting battery (if equipped) to prevent accidental start up. Disconnect the cable from the battery post indicated by a NEGATIVE, NEG or (–) first. Reconnect that cable last.
• In case of accident caused by electric shock, immedi­ately shut down the source of electrical power. If this is not possible, attempt to free the victim from the live conductor. AVOID DIRECT CONTACT WITH THE VICTIM. Use a non-conducting implement, such as a rope or board, to free the victim from the live conduc­tor. If the victim is unconscious, apply first aid and get immediate medical help.
1.2.4 — Fire Hazards
• Gasoline is highly FLAMMABLE and its vapors are EXPLOSIVE. Never permit smoking, open flames, sparks or heat in the vicinity while handling gasoline.
• Never add fuel while unit is running or hot. Allow engine to cool completely before adding fuel.
Never fill fuel tank indoors. Comply with all laws regulating storage and handling of gasoline.
Do not overfill the fuel tank. Always allow room for fuel expansion. If tank is over-filled, fuel can overflow onto a hot engine and cause FIRE or an EXPLOSION. Never store generator with fuel in tank where gasoline vapors might reach an open flame, spark or pilot light (as on a furnace, water heater or clothes dryer). FIRE or EXPLOSION may result. Allow unit to cool entirely before storage.
• Wipe up any fuel or oil spills immediately. Ensure that no combustible materials are left on or near the gener­ator. Keep the area surrounding the generator clean and free from debris and keep a clearance of five (5) feet on all side to allow for proper ventilation of the generator.
• Do not insert objects through unit’s cooling slots.
Never operate the generator if connected electrical devices overheat, if electrical output is lost, if engine or generator sparks or if flames or smoke are observed while unit is running.
• Keep a fire extinguisher near the generator at all times.
NOTE:
California CARB models only are equipped with a
spark arrestor muffler. The spark arrestor must be
maintained in effective working order by the owner/
operator. In the state of California, a spark arrestor is
required by law (Section 4442 of the Public
Resources Code). Other states may have similar
laws. Federal laws apply on federal lands.
1.2.5 — Standards Index
1. National Fire Protection Association (NFPA) 70: The NATIONAL ELECTRIC CODE (NEC) available from www.nfpa.org
2. National Fire Protection Association (NFPA) 5000: BUILDING CONSTRUCTION AND SAFETY CODE available from www.nfpa.org
3. International Building Code available from www.iccsafe.org
4. Agricultural Wiring Handbook available from www.rerc.org , Rural Electricity Resource Council P.O. Box 309 Wilmington, OH 45177-0309
5. ASAE EP-364.2 Installation and Maintenance of Farm Standby Electric Power available from www.asabe.org, American Society of Agricultural & Biological Engineers 2950 Niles Road, St. Joseph, MI 49085
This list is not all inclusive. Check with the Authority Hav­ing Local Jurisdiction (AHJ) for any local codes or stan­dards which may be applicable to your jurisdiction.
XT8000E Series Portable Generator 3
4 XT8000E Series Portable Generator
This page intentionally left blank.
C
D
B
A

Section 2 General Information

2.1 — UNPACKING

• Remove all packaging material.
• Remove separate items.
• Remove the generator from carton.
2.1.1 — Documents and Accessories
(not shown)
Check all contents. If any parts are missing or damaged, call 1-888-77LOWES.
• Product Registration Card
• Warranty and Emission Sheets
• 1 - Owner’s Manual
• 1 - Quart Oil - SAE 30W
• 1 - 20 ft. Extension Cord
• 1 - Battery Charger
• 1 - Oil Funnel
2.1.2 — Loose Components
• 1 - Hardware Bag (containing the following): — 2 - Cotter Pins
— 2 - Washers (B) — 2 - Never-Flat Wheels (C) — 2 - Axle Pins (D) — 2 - Frame Foot Assembly (E) — 4 - Hex Flanged Nuts (M8) (F) — 4 - Hex Bolts (M8) (G) — 1 - Gasket (H) — 1 - Control Guard (J) — 4 - Allen Screw (4 mm) (K) — 1 - Handle Assembly (L) (not in hardware bag) — 2 - Hex Bolt (M8 X 55 mm) (M) — 4 - Washer, Nylon (N) — 2 - Nut, Hex Lock (P) — 1 - Allen Hex Wrench (4 mm) (not shown)
(A)

2.2 — ASSEMBLY

The generator requires some assembly prior to usage. If problems arise when assembling the generator, call 1­888-77LOWES.
2.2.1 — Required Tools
— 1 - Ratchet wrench — 1 - 13 mm socket — 2 - 8 mm wrenches — 1 - 13 mm wrench — 1 - Needle nosed pliers
2.2.2 — Installing Wheels
NOTE:
The wheels are not intended for over-the-road use.
1. Install the Wheels as follows (Figure 2-1): — Slide the Axle Pin through the Wheel, Wheel
Bracket on the frame and a 5/8" Flat Washer.
— Insert the Cotter Pin through the Axle Pin. Use the
needle nosed pliers to bend open to lock in place.
Figure 2-1. Wheel Assembly
2.2.3 — Installing Frame Feet and Control
Guard
2. Install the Frame Foot Assemblies as shown (Figure 2-2).
— Slide the M8 Hex Bolts through the holes in the
Frame Rail.
— Slide the Frame Foot onto the Hex Head Bolts.
Then install the Locking Flange Nuts. Tighten securely using a ratchet, 13 mm socket and 13 mm wrench.
3. Install the Gasket and Control Guard (Figure 2-2). — Place the Gasket and Control Guard in place
against the side panel opening. While holding the Gasket and Control Guard, install the four retain­ing screws. Thread all screws loosely before final tightening any of them. Final tighten securely with the 4 mm Allen wrench (provided).
XT8000E Series Portable Generator 5
J
G
K
F
E
H
N
P
M
L
L
+
_
POSITIVENEGATIVE
Figure 2-2. Control Guard and Frame Foot
Assemblies
2.2.4 — Installing Handle
1. Place the handle brackets between the frame tabs as shown. Place a flat washer on the inside of each frame tab (Figure 2-3).
2. Slide bolts through the handle brackets, washers and
tabs.
3. Place a nut on each bolt and tighten securely using a
ratchet, 13 mm socket and 13 mm wrench.
2.2.5 — Battery Cables
NOTE:
The battery shipped with the generator has been fully charged. The positive and negative cables are NOT connected and must be attached prior to operation.
The NEGATIVE (black) (-) battery cable should:
1. Always be DISCONNECTED FIRST.
2. Always be CONNECTED LAST.
Use two 8 mm wrenches to tighten battery hardware.
Figure 2-4. Battery Connections
NOTE:
A battery may lose some of its charge when not in use for prolonged periods of time. If the battery is unable to crank the engine, plug in the 12V charger included in the accessory box (see the Charging a Battery - Section 4: Maintenance). RUNNING THE GENERATOR DOES NOT CHARGE THE BATTERY.

2.3 — EMISSIONS INFORMATION

The Environmental Protection Agency (and California Air Resource Board for generators certified to CA standards) requires that this generator comply with exhaust and evaporative emission standards. Locate the emissions compliance decal on the engine to determine what stan­dards the generator meets, and to determine which war­ranty applies. This generator is certified to operate on gasoline. The emission control system includes the fol­lowing components (if equipped):
Figure 2-3. Handle
6 XT8000E Series Portable Generator
• Air Induction System — Intake Pipe / Manifold
— Air Cleaner
•Fuel System — Carburetor/Mixer Assembly
— Fuel Regulator
• Ignition System
4
1
3
5
8
7
2
6
— Spark Plug — Ignition Module
• Exhaust System — Exhaust Manifold
— Muffler — Pulsed Air Valve — Catalyst

2.4 — PRODUCT SPECIFICATIONS

2.4.1 — Generator Specifications
Rated Power ........................................................... 8 kW
Surge Power .........................................................10 kW
Rated AC Voltage............................................... 120/240
Rated AC Load
Current @ 240V ........................................ 33.3 Amps**
Current @ 120V ........................................ 66.6 Amps**
Rated Frequency ............................. 60 Hz @3600 RPM
Phase.........................................................Single Phase
Operating Temperature Range ... 0° F (-17° C) to 110° F (43° C)*
* Operating temperature range: 0° F (-18° C) to 104° F (40° C). When
operated above 77° F (25° C) there may be a decrease in power.
** Maximum wattage and current are subject to, and limited by, such
factors as fuel Btu content, ambient temperature, altitude, engine condition, etc.. Maximum power decreases about 3.5% for each 1,000 feet above sea level; and will also decrease about 1% for each 10° F (-12.2° C) above 60° F (16° C) ambient temperature.
2.4.2 — Engine Specifications
Displacement ........................................................ 420 cc
Spark Plug Type ................................... Champion N9YC
Spark Plug Gap ....... 0.028-0.031 inch or (0.70-0.80 mm)
Fuel Capacity ................................7.5 gallons/ 28.4 liters
Oil Type................................................see Section 2.6.1
Oil Capacity..................................1.06 Quarts (1.0 liters)
Run Time at 50% Load ..................................... 11 Hours

2.5 — KNOW THE GENERATOR

Compare the generator to Figures 2-5 through 2-7 to become familiarized with the locations of various controls and adjustments.
Read the Owner’s Manual and Safety Rules before operating this generator.
1. 120/240 Volt AC, 30 Amp, Locking Receptacle – Supplies electrical power for the operation of 120 and/or 240 Volt AC, 30 Amp, single-phase, 60 Hz electrical lighting, appliance, tool and motor loads.
2. Hourmeter - Tracks hours of operation to perform
required maintenance.
3. Circuit Breakers (AC) – A 2-pole circuit breaker pro-
tects the rated output of the 30 Amp Twistlock outlet. Each duplex receptacle is provided with a push-to­reset circuit breaker to protect against electrical over­load.
4. 120 Volt AC, 20 Amp GFCI Duplex Outlets – Sup-
plies electrical power for the operation of 120 Volt AC, 20 Amp, single-phase, 60 Hz, electrical lighting, appliance, tool and motor loads. It also provides pro­tection with an integral Ground Fault Circuit Inter­rupter, complete with a press to “Test” and “Reset” button.
5. Off/Run/Start Switch – Controls the operation of the
generator.
6. Battery Charger Input – Permits recharging of the
battery. A 12 volt charger is included. A 1.50 Amp in­line fuse is located behind the control panel to protect the battery when charging.
7. Powerbar – Indicates the amount of power being
used from the generator. Each section is approxi­mately 20%.
8. Idle Control Switch – operates the engine at normal
(high) rpm when there is an electrical load present and automatically reduces the engine to a lower rpm when a load is not present. The system can also be turned off to operate the engine at a higher rpm at all times.
XT8000E Series Portable Generator 7
Figure 2-5. Control Panel
Figure 2-6. Generator Controls
9
11
12
13
10
14
17
16
15
18
23
24
25
20
21
22
19
OIL DRAIN PLUG
24
23
9. Grounding Location - Ground the generator to an approved earth ground here. See “Grounding the Generator” for details.
10. Spark Arrestor - Reduces fire hazards by containing sparks. (California CARB models only)
11. Muffler – Quiets the engine.
12. Fuel Cap - Remove to fill fuel tank.
13. Recovery Hose - vapor tube between roll over valve and the engine.
14. Carbon Canister - California CARB models only.
15. Choke Lever - Used when starting a cold engine.
16. Air Filter - Filters into air as it is drawn into the engine.
17. Recoil Starter – Used to start engine manually.
18. Fuel Valve - Turns fuel supply on and off.
19. Handle – Used to transport generator.
20. Fuel Gauge - Shows fuel level in tank.
21. Roll Over Valve - Passes fuel vapors to the engine.
22. Fuel Tank - holds fuel supply.
23. Oil Drain - Drain plug for removing used oil from the crankcase.
24. Oil Fill/Dipstick - Check oil level and add oil here.
25. Battery - Provides power for electric starter.
DIPSTICK / FILL OPENING
Figure 2-7. Oil Drain/Fill
8 XT8000E Series Portable Generator
2.5.1 — Connection Plugs
4
1
BLUE DOTS RED DOTS
2.5.1.1 — 120 VAC, 20 Amp, GFCI Duplex
Receptacle
This is a 120 Volt outlet protected against overload by a 20 Amp push-to-reset circuit breaker (Figure 2-8). Use each socket to power 120 Volt AC, single phase, 60 Hz electrical loads requiring up to a combined 2400 watts (2.4 kW) or 20 Amps of current. Use only high quality, well-insulated, 3-wire grounded cord sets rated for 125 Volts at 20 Amps (or greater).
Keep extension cords as short as possible, preferably less than 15 feet long, to prevent voltage drop and possi­ble overheating of wires.
Use this receptacle to operate 120 Volt AC, 60 Hz, single phase loads requiring up to 3600 watts (3.6 kW) of power at 30 Amps or 240 Volt AC, 60 Hz, single phase loads requiring up to 7,200 watts of power. The outlet is pro­tected by a 30 Amp circuit breaker.
2.5.2 — Extension Cord
Your generator comes with a 20 foot extension cord for connecting appliances and other electrical devices to the generator.
NOTE:
Never start or stop the engine with electrical devices plugged into generator and devices turned on.
The colored dots on the extension cord are indicators for evenly applying the loads to the generator. For example, if two electrical devices are plugged in, place one into a red labeled outlet and the other into a blue labeled outlet, rather than two red or two blue outlets (Figure 2-10).
Figure 2-8. 120 Volt AC, 20 Amp, Duplex
Receptacle
2.5.1.2 — 120/240 VAC, 30 Amp Locking Receptacle
Use a NEMA L14-30 Plug with this receptacle (rotate to lock/unlock). Connect the supplied 4-wire grounded cord set to the plug and to the desired load. The cord set should be rated for 250 Volts AC at 30 Amps (or greater).
Figure 2-9. 120/240 VAC, 30 Amp Receptacle
Figure 2-10. Extension cord
2.5.3 — Hourmeter
The Hourmeter tracks hours of operation for scheduled maintenance (Figure 2-11).
There will be a "CHG OIL" message every 100 hours. The message will flash one hour before and one hour after each 100 hour interval, providing a two hour window to perform service.
This message will actually begin flashing at 99 hours and disable itself at 101 hours again, providing a two hour window to perform the service.
Every 200 hours the "SVC" icon on the lower left hand corner of the display will flash. The message will flash one hour before and one hour after each 200 hour inter­val providing a two hour window to perform service.
XT8000E Series Portable Generator 9
Figure 2-11. Hourmeter
HOUR GLASS GRAPHIC
RESET BUTTON (IF EQUIPPED)
0000.0
2
8
*
FULL
ADD
24
When the hour meter is in the Flash Alert mode, the maintenance message will always alternate with elapsed time in hours and tenths. The hours will flash four times, then alternate with the maintenance message four times until the meter resets itself.
• 100 hours - CHG OIL — Oil Change Interval (Every 100 hrs)
• 200 hours - SVC — Service Air Filter (Every 200 hrs)
NOTE:
The hour glass graphic will flash on and off when the engine is running. This signifies that the meter is tracking hours of operation.
2.6 — BEFORE STARTING THE
ENERATOR
G
Prior to operating the generator:
• Engine oil will need to be added.
• Fill the fuel tank with unleaded fuel.
• Battery cables will need to be connected.
2.6.1 — Adding Engine Oil
The generator has been shipped WITHOUT oil. All oil should meet minimum American Petroleum Institute (API) Service Class SJ, SL or better. Use no special addi­tives. Select the oil's viscosity grade according to the expected operating temperature (also see chart).
• Above 40° F (4.4° C), use SAE 30
• Below 40° F (4.4° C) and down to 10° F (-12.2° C), use SAE 10W-30
• All temperatures, use synthetic SAE 5W-30
2.5.4 — Idle Control Switch
In the ON position, the engine will operate at the normal 3,600 rpm to meet the demands of any loads applied. When no loads are applied, the idle control system slows the engine rpm to conserve fuel and lower noise levels. Applying a load brings the engine speed back to normal automatically.
With the switch in the OFF position, the low speed sys­tem is disabled and the engine runs at a constant 3,600 rpm, with or without a load.
Figure 2-12. Idle Control Switch
Any attempt to start the engine before it has been properly serviced with the recommended oil may result in an engine failure.
1. Place generator on a level surface (not to exceed 15° in any direction).
2. Clean area around oil fill and remove oil fill cap/dip­stick.
3. Wipe dipstick clean (Figure 2-13).
4. Slowly fill engine with oil through the oil fill opening. Stop filling occasionally to check oil level. Fill until the level is at the upper mark on the dipstick. Be careful
not to over fill.
10 XT8000E Series Portable Generator
Figure 2-13. Oil Fill/Dipstick
5. Install oil fill cap and finger tighten securely.
$
$
DO NOT FILL
ABOVE LIP!
1212
6. Check engine oil level before starting each time thereafter.
2.6.2 — Adding Fuel
Never fill fuel tank indoors. Never fill fuel tank when engine is running or hot. Avoid spilling gasoline on a hot engine. Allow engine to cool entirely before filling fuel tank.
DO NOT light a cigarette or smoke when filling the fuel tank.
Do not overfill the fuel tank. Always leave room for fuel expansion. If the fuel tank is overfilled, fuel can overflow onto a hot engine and cause FIRE or EXPLOSION. Wipe up any spilled fuel immediately.
Use the following instructions for adding gasoline:
Use regular UNLEADED gasoline with the generator engine. Do not mix oil with gasoline.
Do not use gasoline with more than 10% alcohol such as E85 or ethanol.
Clean area around fuel fill cap, remove cap. Slowly add unleaded gasoline to fuel tank. Be careful
not to overfill (Figure 2-14). Install fuel cap and wipe up any spilled gasoline.
Figure 2-14. Fuel Fill Level
IMPORTANT: It is important to prevent gum deposits
from forming in fuel system parts such as the carburetor, fuel hose or tank during storage. Alcohol-blended fuels (called gasohol, ethanol or methanol) can attract mois­ture, which leads to separation and formation of acids during storage. Acidic gas can damage the fuel system of an engine while in storage. To avoid engine problems, the fuel system should be emptied or treated with a com­mercially available fuel stabilizer before storage of 30 days or longer. See the "Storage" section. Never use engine or carburetor cleaner products in the fuel tank as permanent damage may occur.
XT8000E Series Portable Generator 11
12 XT8000E Series Portable Generator
This page intentionally left blank.
* *
* *
*
GROUNDING LOCATION

Section 3 Operation

3.1 — HOW TO USE THE GENERATOR

See the "To Start the Engine" section for how to safely start and stop the generator and how to connect and dis­connect loads. If there are any problems operating the generator, please call 1-888-77LOWES.
Never operate in an enclosed area or indoors! NEVER use in the home, in a vehicle, or in partly enclosed areas such as garages, EVEN IF doors and windows are open! ONLY use out­doors and far from open windows, doors, vents, and in an area that will not accumulate deadly exhaust. The engine exhaust fumes contain carbon monoxide, which you cannot see or smell. This poisonous gas, if breathed in sufficient con­centrations, can cause unconsciousness or even death. Adequate, unobstructed flow of cooling and ventilating air is critical to correct generator operation. Do not alter the installation or per­mit even partial blockage of ventilation provi­sions, as this can seriously affect safe operation of the generator. The generator MUST be operated outdoors. This exhaust system must be properly main­tained. Do nothing that might render the exhaust system unsafe or in noncompliance with any local codes and/or standards. Always use a battery operated carbon monox­ide alarm indoors, installed according to the manufacturer's instructions.
3.1.1 — Grounding The Generator When Used As A Portable
This generator has an equipment ground that connects the generator frame components to the ground terminals on the AC output receptacles (see NEC 250.34 (A) for explanation). This allows the generator to be used as a portable without grounding the frame of the generator as specified in NEC 250.34.
Figure 3-1. Grounding the Generator
3.1.1.1 — Special Requirements
There may be Federal or State Occupational Safety and Health Administration (OSHA) regulations, local codes, or ordinances that apply to the intended use of the gener­ator.
Please consult a qualified electrician, electrical inspector, or the local agency having jurisdiction:
• In some areas, generators are required to be regis­tered with local utility companies.
• If the generator is used at a construction site, there may be additional regulations which must be observed.
3.1.2 — Connecting The Generator To A Building’s Electrical System
When connecting directly to a building’s electrical sys­tem, it is recommended that a manual transfer switch is used. Connections for a portable generator to a building’s electrical system must be made by a qualified electrician and in strict compliance with all national and local electri­cal codes and laws.
XT8000E Series Portable Generator 13

3.2 — GENERATOR LOADS

+
Overloading a generator in excess of its rated wattage capacity can result in damage to the generator and to connected electrical devices. Observe the following to prevent overloading the unit:
• Add up the total wattage of all electrical devices to be connected at one time. This total should NOT be greater than the generator's wattage capacity.
• The rated wattage of lights can be taken from light bulbs. The rated wattage of tools, appliances and motors can usually be found on a data label or decal affixed to the device.
• If the appliance, tool or motor does not give wattage, multiply volts times ampere rating to determine watts (volts x amps = watts).
• Some electric motors, such as induction types, require about three times more watts of power for starting than for running. This surge of power lasts only a few seconds when starting such motors. Make sure to allow for high starting wattage when selecting electri­cal devices to connect to the generator:
1. Figure the watts needed to start the largest motor.
2. Add to that figure the running watts of all other con­nected loads.
The Wattage Reference Guide is provided to assist in determining how many items the generator can operate at one time.
NOTE:
All figures are approximate. See data label on appli­ance for wattage requirements.
Electric Nail Gun . . . . . . . . . . . . . . . . . . . . . . . . . . .1200
Electric Range (per element). . . . . . . . . . . . . . . . . .1500
Electric Skillet . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1250
*Freezer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .700
*Furnace Fan (3/5 HP) . . . . . . . . . . . . . . . . . . . . . . .875
*Garage Door Opener . . . . . . . . . . . . . . . . . . 500 to 750
Hair Dryer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1200
Hand Drill. . . . . . . . . . . . . . . . . . . . . . . . . . . 250 to 1100
Hedge Trimmer . . . . . . . . . . . . . . . . . . . . . . . . . . . . .450
Impact Wrench . . . . . . . . . . . . . . . . . . . . . . . . . . . . .500
Iron . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1200
*Jet Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .800
Lawn Mower . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1200
Light Bulb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .100
Microwave Oven . . . . . . . . . . . . . . . . . . . . . 700 to 1000
*Milk Cooler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1100
Oil Burner on Furnace . . . . . . . . . . . . . . . . . . . . . . . .300
Oil Fired Space Heater (140,000 Btu) . . . . . . . . . . . .400
Oil Fired Space Heater (85,000 Btu) . . . . . . . . . . . . .225
Oil Fired Space Heater (30,000 Btu) . . . . . . . . . . . . .150
*Paint Sprayer, Airless (1/3 HP) . . . . . . . . . . . . . . . .600
Paint Sprayer, Airless (hand-held). . . . . . . . . . . . . . .150
Radio. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 to 200
*Refrigerator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .700
Slow Cooker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .200
*Submersible Pump (1-1/2 HP) . . . . . . . . . . . . . . . .2800
*Submersible Pump (1 HP) . . . . . . . . . . . . . . . . . . .2000
*Submersible Pump (1/2 HP) . . . . . . . . . . . . . . . . .1500
*Sump Pump . . . . . . . . . . . . . . . . . . . . . . . . 800 to 1050
*Table Saw (10") . . . . . . . . . . . . . . . . . . . . 1750 to 2000
Television. . . . . . . . . . . . . . . . . . . . . . . . . . . . 200 to 500
Toaster. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1000 to 1650
Weed Trimmer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .500
* Allow 3 times the listed watts for starting these devices.

3.3 — WATTAGE REFERENCE GUIDE

Device. . . . . . . . . . . . . . . . . . . . . . . . . . . Running Watts
*Air Conditioner (12,000 Btu) . . . . . . . . . . . . . . . . . 1700
*Air Conditioner (24,000 Btu) . . . . . . . . . . . . . . . . . 3800
*Air Conditioner (40,000 Btu) . . . . . . . . . . . . . . . . . 6000
Battery Charger (20 Amp) . . . . . . . . . . . . . . . . . . . . 500
Belt Sander (3") . . . . . . . . . . . . . . . . . . . . . . . . . . . 1000
Chain Saw . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1200
Circular Saw (6-1/2") . . . . . . . . . . . . . . . . . .800 to 1000
*Clothes Dryer (Electric) . . . . . . . . . . . . . . . . . . . . 5750
*Clothes Dryer (Gas) . . . . . . . . . . . . . . . . . . . . . . . . 700
*Clothes Washer. . . . . . . . . . . . . . . . . . . . . . . . . . . 1150
Coffee Maker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1750
*Compressor (1 HP) . . . . . . . . . . . . . . . . . . . . . . . . 2000
*Compressor (3/4 HP) . . . . . . . . . . . . . . . . . . . . . . 1800
*Compressor (1/2 HP) . . . . . . . . . . . . . . . . . . . . . . 1400
Curling Iron. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 700
*Dehumidifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 650
Disc Sander (9") . . . . . . . . . . . . . . . . . . . . . . . . . . . 1200
Edge Trimmer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 500
Electric Blanket. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 400
14 XT8000E Series Portable Generator

3.4 — STARTING THE GENERATOR (ELECTRIC START)

Never start or stop engine with electrical devices plugged into the receptacles AND devices turned on.
1. To start the engine, turn the fuel valve to the ON posi-
tion (Figure 3-2).
2. Move the choke lever to the START position (Figure
3-3).
3. Press and hold the off/run/start switch in the START
position. The engine will crank and attempt to start. When the engine starts, release the switch to the RUN position.
4. When the engine starts, move the choke lever to the
CHOKE LEVER
LEFT = CHOKE (START)
RIGHT = RUN
RUN position. If engine falters, move choke lever back to the START position until the engine runs smoothly and then return it to the RUN position.
5. This generator is also equipped with a manual recoil starter which may be used if the battery is dis­charged.
Figure 3-2. Fuel Valve
5. When the engine starts, move the choke lever until the engine runs smoothly and then fully to the RUN position. If engine falters, pull choke lever back to START until the engine runs smoothly and then return to the RUN position.
NOTE:
If engine fires, but does not continue to run, move
the choke lever to “Start” and repeat starting instruc-
tions.
IMPORTANT: Do not overload the generator. Also, do
not overload individual panel receptacles. These outlets are protected against overload with push-to-reset-type circuit breakers. If amperage rating of any circuit breaker is exceeded, that breaker opens and electrical output to that receptacle is lost. Read “Generator Loads” carefully.

3.6 — STOPPING THE GENERATOR

NOTE:
NEVER start or stop the engine with electrical devices plugged in and turned on.
1. Shut off all loads, then unplug the electrical loads
from the generator’s panel receptacles or extension cord.
2. Let the engine run at no-load for several minutes to stabilize the internal temperatures of the engine and generator.
3. Move the off/run/start switch to the OFF position.
4. Close the fuel valve.

3.5 — STARTING THE GENERATOR (MANUAL/RECOIL) STARTING

1. To start the generator, put the off/run/start switch in
the ON position.
2. Turn the fuel valve to the ON position.
3. Move the choke lever to the START position.
4. Firmly grasp the recoil handle and pull slowly until
increased resistance is felt. Pull rapidly up and away to start engine.
Figure 3-3. Choke
3.7 — LOW OIL LEVEL SHUTDOWN
YSTEM
S
The engine is equipped with a low oil level sensor that shuts down the engine automatically when the oil level drops below a specified level. If the engine shuts down by itself and the fuel tank has sufficient fuel, check engine oil level.
XT8000E Series Portable Generator 15
This Page Intentionally Left Blank
16 XT8000E Series Portable Generator
*

Section 4 Maintenance

4.1 — General Recommendations

The warranty of the generator does not cover items that have been subjected to operator abuse or negligence. To receive full value from the warranty, the operator must maintain the generator as instructed in this manual.
Some service procedures will be performed periodically to properly maintain the generator.
All service procedures in the Maintenance section of this manual should be made at the intervals indicated. Follow the intervals in the “Service Interval Table 4-1”.

4.2 — Generator Cleaning

Generator cleaning consists of keeping the unit clean and dry. Operate and store the unit in a clean dry envi­ronment where it will not be exposed to excessive dust, dirt, moisture or any corrosive vapors. Cooling air slots in the generator must not become clogged with snow, leaves, or any other foreign material. Check the cleanli­ness of the generator frequently and clean when dust, dirt, oil, moisture or other foreign substances are visible on its exterior surface.
4.2.1 — Generator Cleaning
• Use a damp cloth to wipe exterior surfaces clean.
• A soft, bristle brush may be used to loosen caked on dirt, oil, etc.
• A vacuum cleaner may be used to pick up loose dirt and debris.
• Low pressure air (not to exceed 25 psi/1.72 bar) may be used to remove dirt. Inspect cooling air slots and openings on the generator. These openings must be kept clean and unobstructed.
NOTE:
DO NOT use a garden hose to clean generator. Water can enter the engine fuel system and cause prob­lems. In addition, if water enters the generator through cooling air slots, some water will be retained in voids and crevices of the rotor and stator winding.

4.3 — Service Intervals

Follow the service interval table to perform scheduled maintenance. More frequent service is required when operating in adverse conditions as noted below.
Never insert any object or tool through the air cooling slots, even if the engine is not running.
Table 4-1: Service Intervals
OPERATION INTERVAL FREQUENCY
Oil Level Check Prior to every use/or every 24 hours of operation Oil Change (break-in) After initial 30 hours of operation Oil Change Every 100 hours of operation and/or annually Spark Plug Replacement Every 200 hours of operation and/or annually Air Filter Service Every 200 hours of operation and/or annually Spark Arrestor Service Annually Valve Clearance Adjustment (break-in) After 50 hours of operation Valve Clearance Adjustment Every 300 hours of operation Fuel Filter Replacement Every 500 hours of operation and/or annually Battery Charging Every 3 months or if starter will not turn engine Battery Replacement If it no longer accepts a charge Storage If not used for 30 days or more/ long term
XT8000E Series Portable Generator 17
4.3.1 — Engine Maintenance
+
*
OIL DRAIN PLUG
24
23
FULL
ADD
24
SPARK PLUG LOCATION
When working on the generator, always dis­connect spark plug wire from spark plug and keep wire away from spark plug.
4.3.2 — Oil Level Check
See the “Before Starting the Generator” section for infor­mation on Adding and checking the oil level. The oil level should be checked before each use, or at least every eight hours of operation. Keep the oil level maintained. See Figure 4-1 for the dipstick and oil fill location.
4.3.3 — Oil Change
Change the oil after the first 30 hours and every 100 hours thereafter. If running this unit under dirty or dusty conditions, or in extremely hot weather, change the oil more often.
Hot oil may cause burns. Allow engine to cool before draining oil. Avoid prolonged or repeated skin exposure with used oil. Thor­oughly wash exposed areas with soap.
Use the following instructions to change the oil after the engine cools down:
1. Clean area around oil drain plug. See Figure 4-1.
2. Remove oil drain plug from engine and oil fill plug to drain oil completely into a suitable container.
3. When oil has completely drained, install oil drain plug and tighten securely.
4. Fill engine with recommended oil. (See “Before Start­ing the Generator” for oil recommendations).
5. Fill to the upper level on the dipstick. See Figure 4-2.
6. Dispose of used oil at a proper collection center.
Figure 4-2. Oil Fill/Dipstick
4.3.4 — Spark Plug Replacement
Use a Champion N9YC spark plug or equivalent.
Replace the plug every 200 hours.
1. Stop the engine and shut off the fuel valve. Allow the engine to cool.
2. Remove the spark plug boot from the plug and clean that area of the cylinder head. The spark plug is located on the side of the generator shown in Figure 4-3.
3. Use a 13/16 in. (21mm) spark plug tool to remove the spark plug.
4. Set the new spark plug’s gap to 0.028-0.031 in. (0.70-0.80 mm). See Figure 4-4.
5. Install the correctly gapped spark plug into the cylin­der head and torque to 18-21.6 ft./lbs./24.4-29.3 Nm.
6. Reconnect the spark plug wire.
DIPSTICK / FILL OPENING
Figure 4-3. Spark Plug Location
Figure 4-1. Oil Drain Plug
18 XT8000E Series Portable Generator
Figure 4-4. Spark Plug Gap
AIR FILTER COVER
AIR FILTER
SCREW
16
!
CONE
SCREEN
CLAMP
MUFFLER
10
4.3.5 — Air Filter Service
The engine will not run properly and may be damaged if using a dirty air filter. Clean the air filter every 50 hours or annually (Figure 4-5). Clean or replace more often if operating under dusty conditions.
1. Remove air filter cover retaining screw and cover.
2. Wash in soapy water. Squeeze filter dry in clean cloth (DO NOT TWIST).
3. Clean air filter cover before re-installing it.
4. Tighten air filter cover screw securely.
NOTE:
To order a new air filter, please call 1-888-77LOWES.
If using the generator on any forest-covered, brush-covered or grass-covered unimproved land, it must be equipped with a spark arrestor. The spark arrestor must be maintained in good condition by the owner/operator.
Clean and inspect the spark arrestor when the engine is at ambient temperature as follows:
1. Remove the spark arrestor screen from the muffler by loosening the clamp and removing the screw.
2. Inspect screen and replace if torn, perforated or oth­erwise damaged. DO NOT USE a defective screen. If screen is not damaged, clean it with commercial sol­vent.
3. Replace the spark arrestor and secure with the clamp and screw.
Figure 4-6. Spark Arrestor Screen
4.3.7 — Valve Clearance Adjustment
• Intake - 0.006 ± 0.0008 in. (0.15 ± 0.02 mm) (cold) Exhaust - 0.008
• After the first 50 hours of operation, check the valve clearance in the engine and adjust if necessary.
Important: If feeling uncomfortable about doing this
Figure 4-5. Air Filter
4.3.6 — Spark Arrestor Service (California CARB models only)
If the engine exhaust muffler has a spark arrestor screen (Figure 4-6). Inspect and clean the screen at least annu­ally. If unit is used regularly, inspect and clean more often.
XT8000E Series Portable Generator 19
procedure or the proper tools are not available, please take the generator to the nearest service cen­ter to have the valve clearance adjusted. This is a very important step to ensure longest life for the engine.
To check valve clearance:
1. Make sure the engine is at room temperature (60° - 80° F/ 15.55° - 26.66° C).
2. Make sure that the spark plug wire(s) is removed from the spark plug and out of the way. Remove spark plug(s).
± 0.0008 in. (0.20 ± 0.02 mm) (cold)
NOTE:
3. Remove the six screws attaching the valve cover(s).
FUEL FILTER LOCATION
FUEL FILTER LOCATION
FUEL FILTER LOCATION
4. Make sure the piston is at Top Dead Center (TDC) of its compression stroke (both valves closed). To get the piston at TDC, pull the recoil handle slowly while watching the piston through the spark plug hole. The piston should move up and down. The piston is at TDC when it is up as high as it can go.
5. Insert a 0.006 in. (0.15 mm) feeler gauge, for intake clearance, between the intake rocker arm and valve stem. Insert a 0.008 in. (0.20 mm) feeler gauge, for exhaust clearance, between the exhaust rocker arm and valve stem. Correct clearance is when a slight drag is felt when sliding the gauge back and forth. If the clearance is either excessively loose or tight the rocker arms will need adjusting.
To adjust valve clearance:
1. Hold the rocker arm pivot with a wrench and loosen the pivot lock nut (Figure 4-7).
NOTE:
The rocker arm jam nut must be held in place as the pivot ball stud is turned.
2. Loosen the rocker arm pivot and turn the rocker arm pivot to obtain the specified valve clearance. The desired clearance for intake and exhaust valves is the same.
3. Hold the rocker pivot with a wrench and tighten the lock nut to 69 ft./lbs. (7.8 Nm).
4. Install new valve cover gasket.
NOTE:
4.3.8 — Fuel Filter Replacement
The fuel filter replacement should take place every 500 hours of operation and/or annually (Figure 4-8).
1. Turn fuel valve off.
2. Using a pliers, squeeze the clamp and slide the clamp back from the fuel valve and remove the hose from fuel valve fitting.
3. Slide both clamps away from the fuel filter fittings Clamps can be reused.
4. Remove the short hose from the fuel filter. Then remove the filter from the longer hose.
5. Place the new filter on the longer hose. The larger end of the filter (with the red dot) must face towards the fuel valve. Position the clamp on the filter fitting.
6. Place the short length of hose on the filter. Then the other end on the fuel valve.
7. Place both clamps back onto the fittings of the filter and fuel valve.
Start all six screws before tightening or it will not be possible to get all the screws in place.
5. Re-attach the valve cover. Torque fasteners to 20-48 in./lbs. / 2.3-5.4 Nm. Torque fasteners in a cross pat­tern.
Figure 4-7. Valve Clearance Adjustment
6. Re-attach the spark plug boot to the spark plug.
Figure 4-8. Fuel Filter Location
4.3.9 — Battery Charging
The charging port is protected by a 1.50 Amp replaceable in-line fuse. If the charger is not recharging the battery, check the fuse. Replacement fuses can be obtained at your dealer.
1. The battery charger fuse is located behind the control panel as shown in Figure 4-9. It is secured with a rub­ber coated clamp.
2. The two halves of the fuse holder pull apart. Remove the broken fuse.
3. Install a new replacement fuse and push the halves of the fuse holder together.
4. Route all wires away from any engine components and secure them, as before, with the rubber coated clamp.
20 XT8000E Series Portable Generator
Figure 4-9. Battery Charger Fuse
INLINE FUSE
LOCATION
$
+
_
POSITIVENEGATIVE
.
Storage batteries give off explosive hydrogen gas while recharging. An explosive mixture will remain around the battery for a long time after it has been charged. The slightest spark can ignite the hydrogen and cause an explosion. Such an explosion can shatter the battery and cause blindness or other serious injury.
Do not permit smoking, open flame, sparks or any other source of heat around a battery. Wear protective goggles, rubber apron and rubber gloves when working around a battery. Battery electrolyte fluid is an extremely corrosive sulfuric acid solution that can cause severe burns. If spill occurs flush area with clear water immediately.
NOTE:
The battery shipped with the generator has been fully charged. A battery may lose some of its charge when not in use for prolonged periods of time. If the battery is unable to crank the engine, plug in the 12V charger included in the accessory box. RUNNING THE GENERATOR DOES NOT CHARGE THE BATTERY.
NOTE:
Do not use the battery charger for more than 48
hours at one charge. Charge the battery at least once
every 3 months.
4.3.10 — Battery Replacement
When the battery will no longer accept a charge, replace­ment is necessary. The battery is needed to use the elec­tric starter.
NOTE:
The battery shipped with the generator has been fully charged. A battery may lose some of its charge when not in use for prolonged periods of time. If the battery is unable to crank the engine, plug in the 12V charger included in the accessory box (see the Charging the Battery section). RUNNING THE GENERATOR DOES NOT CHARGE THE BATTERY.
The battery shipped with the generator has been provided fully charged. To replace the battery, see Figure 4-10.
1. Disconnect and remove the battery mounting hard-
ware (8mm) and BLACK wire from the battery’s NEGATIVE (-) terminal.
2. Move the red protective boot and disconnect the bat-
tery mounting hardware (8mm) and RED wire from the battery’s POSITIVE (+) terminal.
3. Remove the two screws and bracket from the battery
tray. Remove the battery.
4. Place the new battery in the tray. Secure with the
bracket and two mounting screws. Tighten screws securely.
5. Reconnecting the RED wire to the POSITIVE (+) ter-
minal and the BLACK wire to the NEGATIVE (-) ter­minal.
Use battery charger plug to keep the battery charged and ready for use. Battery charging should be done in a dry location.
1. Plug charger into “Battery Charger Input” jack (6), located on the control panel (Figure 2-5). Plug wall receptacle end of the battery charger into a 120 Volt AC wall outlet.
2. Unplug battery charger from wall outlet and control panel jack when generator is going to be in use.
Figure 4-10. Battery Mounting Hardware
XT8000E Series Portable Generator 21
NOTE:
*
*
*
Your generator can still be operated using the recoil starter.

4.4 — Generator Storage

The unit should be started at least once every 30 days and be allowed to run at least 30 minutes. If this cannot be done and the unit must be stored for more than 30 days, use the following information as a guide to prepare it for storage.
Allow unit to cool entirely before storage.
4.4.1 — Long Term Storage
1. Treat the fuel with a commercially available fuel sta­bilizer. Operate the engine for 10-15 minutes to circu­late treated fuel into the fuel lines and carburetor. Turn the fuel valve off and run the unit until it shuts down. The fuel may be left in the tank or drained into a suitable container.
2. Drain oil from crankcase. Refill with recommended grade oil.
3. Remove spark plug and pour about 1/2 ounce (15 ml) of engine oil into the cylinder. Cover spark plug hole with rag. Pull the recoil starter several times to lubricate the piston rings and cylinder bore. A fogging agent can be used in place of oil.
NEVER cover the generator while engine and exhaust areas are warm.
Avoid spray from spark plug hole when crank­ing engine.
4. Install and tighten spark plug. Do not connect spark plug wire.
NOTE:
Allow the unit to cool completely.
5. Clean the unit’s outer surfaces. Check that cooling air slots and openings on the unit are open and unob­structed.
6. Store the unit in a clean, dry place.
4.4.2 — Other Storage Tips
• If possible, store the unit indoors and cover it to give protection from dust and dirt. BE SURE TO CLOSE
THE VALVE ON THE FUEL TANK.
• Cover the unit with a suitable protective cover that does not retain moisture.
22 XT8000E Series Portable Generator

Section 5 Troubleshooting

5.1 — Troubleshooting Guide

PROBLEM CAUSE CORRECTION
Engine is running, but no AC output is available.
Engine runs well but bogs down when loads are connected.
Engine will not start; or starts and runs rough.
1. Circuit breaker is open.
2. Poor connection or defective cord set.
3. Connected device is bad.
4. Fault in generator.
5. 120V GFCI tripped (no light).
1. Short circuit in a connected load.
2. Generator is overloaded.
3. Engine speed is too slow.
4. Shorted generator circuit.
1. Fuel Shut-off is OFF.
2. Dirty air filter.
3. Dirty fuel filter.
4. Out of fuel.
5. Spark plug wire not connected to spark plug.
6. Bad spark plug.
7. Water in fuel.
8. Low oil level.
9. Excessive rich fuel mixture.
10. Intake valve stuck open or closed.
11. Engine has lost compression.
1. Reset circuit breaker.
2. Check and repair.
3. Connect another device that is in good condition.
4. Contact Authorized Service Facility.
5. Reset 120V GFCI push button (light is on).
1. Disconnect shorted electrical load.
2. See “Don’t Overload the Generator”.
3. Contact Authorized Service Facility.
4. Contact Authorized Service Facility.
1. Turn Fuel Shut-off ON.
2. Clean or replace air filter.
3. Replace fuel filter.
4. Fill the fuel tank.
5. Connect wire to spark plug.
6. Replace spark plug.
7. Drain fuel tank and replace with fresh fuel.
8. Fill crankcase to proper level.
9. Contact Authorized Service Facility.
10. Contact Authorized Service Facility.
11. Contact Authorized Service Facility.
Engine shuts down during operation.
Engine lacks power. 1. Load is too high.
Engine “hunts” or falters. 1. Carburetor is running too rich or too lean.
XT8000E Series Portable Generator 23
1. Out of fuel.
2. Low oil level.
3. Dirty fuel filter.
4. Fault in engine.
2. Dirty air filter.
3. Dirty fuel filter.
4. Engine needs to be serviced.
2. Dirty fuel filter.
3. Governor out of adjustment?
1. Fill the fuel tank.
2. Fill crankcase to proper level.
3. Change fuel filter.
4. Contact Authorized Service Facility.
1. Reduce load (see “Don’t Overload the Generator”).
2. Clean or replace air filter.
3. Replace fuel filter.
4. Contact Authorized Service Facility.
1. Contact Authorized Service Facility.
2. Replace fuel filter.
3. Contact authorized dealer facility.

5.2 — Replacement Service Parts

Description Part No.
Oil (quart) 0G0752
Spark Plug 0G84420101
Air Filter 0G84420151
Fuel Filter 0H1326
Battery 0G9449
Battery Fuse 0K3029
Spark Arrestor
0K3857
(California only)
Maintenance Kit 005777-0
24 XT8000E Series Portable Generator
XT8000E Series Portable Generator 25
This page intentionally left blank.

Part No. 0K3177 Rev C 08/12/14 © Generac Power Systems, Inc. All rights reserved Specifications are subject to change without notice. No reproduction allowed in any form without prior written consent from Generac Power Systems, Inc.

Generac Power Systems, Inc.
S45 W29290 Hwy. 59
Waukesha, WI 53189
1-888-GENERAC (1-888-436-3722)
generac.com
Loading...