Generac QT 65, QT 75, QT 55 User Manual

Diagnostic Repair Manual
Diagnostic Repair Manual
For more information
www.guardiangenerators.com
QUIETPACT
®
55/65/75
Model 4702, 4703, 4707, 4705, 4706, 4707
SAFETY
Throughout this publication, "DANGER!" and "CAUTION!" blocks are used to alert the mechanic to special instructions concerning a particular service or operation that might be hazardous if performed incorrectly or carelessly. PAY CLOSE ATTENTION TO THEM.
DDAANNGGEERR!! UUNNDDEERR TTHHIISS HHEEAADDIINNGG WWIILLLL BBEE FFOOUUNNDD SSPPEECCIIAALL IINNSSTTRRUUCCTTIIOONNSS WWHHIICCHH,, IIFF NNOOTT CCOOMMPPLLIIEEDD WWIITTHH,, CCOOUULLDD RREESSUULLTT IINN PPEERRSSOONNAALL IINNJJUURRYY OORR DDEEAATTHH..
CCAAUUTTIIOONN!! UUnnddeerr tthhiiss hheeaaddiinngg wwiillll bbee ffoouunndd ssppeecciiaall iinnssttrruuccttiioonnss wwhhiicchh,, iiff nnoott ccoommpplliieedd wwiitthh,, ccoouulldd rreessuulltt iinn ddaamm-- aaggee ttoo eeqquuiippmmeenntt aanndd//oorr pprrooppeerrttyy..
These "Safety Alerts" alone cannot eliminate the hazards that they signal. Strict compliance with these spe­cial Instructions plus "common sense" are major accident prevention measures.
NOTICE TO USERS OF THIS MANUAL
This SERVICE MANUAL has been written and published by Generac to aid our dealers' mechanics and com­pany service personnel when servicing the products described herein.
It is assumed that these personnel are familiar with the servicing procedures for these products, or like or similar products manufactured and marketed by Generac. That they have been trained in the recommended servicing procedures for these products, including the use of common hand tools and any special Generac tools or tools from other suppliers.
Generac could not possibly know of and advise the service trade of all conceivable procedures by which a service might be performed and of the possible hazards and/or results of each method. We have not under­taken any such wide evaluation. Therefore, anyone who uses a procedure or tool not recommended by Generac must first satisfy himself that neither his nor the products safety will be endangered by the service procedure selected.
All information, illustrations and specifications in this manual are based on the latest product information available at the time of publication.
When working on these products, remember that the electrical system and engine ignition system are capa­ble of violent and damaging short circuits or severe electrical shocks. If you intend to perform work where electrical terminals could be grounded or touched, the battery cables should be disconnected at the battery.
Any time the intake or exhaust openings of the engine are exposed during service, they should be covered to prevent accidental entry of foreign material. Entry of such materials will result in extensive damage when the engine Is started.
During any maintenance procedure, replacement fasteners must have the same measurements and strength as the fasteners that were removed. Metric bolts and nuts have numbers that indicate their strength. Customary bolts use radial lines to indicate strength while most customary nuts do not have strength mark­ings. Mismatched or incorrect fasteners can cause damage, malfunction and possible injury.
REPLACEMENT PARTS
Components on Generac recreational vehicle generators are designed and manufactured to comply with Recreational Vehicle Industry Association (RVIA) Rules and Regulations to minimize the risk of fire or explo­sion. The use of replacement parts that are not in compliance with such Rules and Regulations could result in a fire or explosion hazard. When servicing this equipment, It is extremely important that all components be properly installed and tightened. If Improperly Installed and tightened, sparks could Ignite fuel vapors from fuel system leaks.
TTaabbllee ooff CCoonntteennttss
Page 1
SSAAFFEETTYY ........................................................ IINNSSIIDDEE FFRROONNTT CCOOVVEERR
SSEECCTTIIOONN 11::
GGEENNEERRAATTOORR FFUUNNDDAAMMEENNTTAALLSS ............................................ 33--77
MAGNETISM ................................................................ 3
ELECTROMAGNETIC FIELDS .................................... 3
ELECTROMAGNETIC INDUCTION .............................. 3
A SIMPLE AC GENERATOR ........................................ 4
A MORE SOPHISTICATED AC GENERATOR ............ 4
FIELD BOOST .............................................................. 6
GENERATOR AC CONNECTION SYSTEM ................ 6
SSEECCTTIIOONN 22::
MMAAJJOORR GGEENNEERRAATTOORR CCOOMMPPOONNEENNTTSS ........................ 88--1111
ROTOR ASSEMBLY ...................................................... 8
STATOR ASSEMBLY .................................................... 8
BRUSH HOLDER .......................................................... 9
BATTERY CHARGE COMPONENTS .......................... 9
EXCITATION CIRCUIT COMPONENTS ...................... 9
CRANKCASE BREATHER .......................................... 10
SSEECCTTIIOONN 33::
IINNSSUULLAATTIIOONN RREESSIISSTTAANNCCEE TTEESSTTSS ............................ 1122--1144
EFFECTS OF DIRT AND MOISTURE ........................ 12
INSULATION RESISTANCE TESTERS ...................... 12
DRYING THE GENERATOR ...................................... 12
CLEANING THE GENERATOR .................................. 12
STATOR INSULATION RESISTANCE ........................ 13
TESTING ROTOR INSULATION ................................ 14
THE MEGOHMMETER .............................................. 14
SSEECCTTIIOONN 44::
MMEEAASSUURRIINNGG EELLEECCTTRRIICCIITTYY .................................................... 1155--1177
METERS ...................................................................... 15
THE VOM .................................................................... 15
MEASURING AC VOLTAGE ...................................... 15
MEASURING DC VOLTAGE ...................................... 15
MEASURING AC FREQUENCY ................................ 16
MEASURING CURRENT ............................................ 16
MEASURING RESISTANCE ...................................... 16
ELECTRICAL UNITS .................................................. 17
OHM’S LAW ................................................................ 17
SSEECCTTIIOONN 55::
EENNGGIINNEE DDCC CCOONNTTRROOLL SSYYSSTTEEMM ................................ 1188--2266
INTRODUCTION ........................................................ 18
OPERATIONAL ANALYSIS .................................. 18-23
ENGINE CONTROLLER CIRCUIT BOARD ................ 24
BATTERY .................................................................... 24
7.5 AMP FUSE ............................................................ 25
FUEL PRIMER SWITCH ............................................ 25
START-STOP SWITCH .............................................. 25
STARTER CONTACTOR RELAY
& STARTER MOTOR ................................................ 26
SSEECCTTIIOONN 66::
TTRROOUUBBLLEESSHHOOOOTTIINNGG FFLLOOWWCCHHAARRTTSS ........................................ 2277--3377
IF PROBLEM INVOLVES AC OUTPUT ...................... 27
PROBLEM 1 ­VOLTAGE & FREQUENCY ARE BOTH
HIGH OR LOW ............................................................ 27
PROBLEM 2 ­GENERATOR PRODUCES ZERO VOLTAGE OR
RESIDUAL VOLTAGE (5-12 VAC) ........................ 28-29
PROBLEM 3 -
NO BATTERY CHARGE OUTPUT .............................. 29
PROBLEM 4 ­EXCESSIVE VOLTAGE/FREQUENCY DROOP
WHEN LOAD IS APPLIED .......................................... 30
PROBLEM 5 ­PRIMING FUNCTION DOES NOT WORK
(GASOLINE MODELS) ................................................ 30
PROBLEM 6 -
ENGINE WILL NOT CRANK ...................................... 31
PROBLEM 7 ­ENGINE CRANKS BUT WILL NOT START
(GASOLINE UNITS) .................................................... 32
PROBLEM 7 ­ENGINE CRANKS BUT WILL NOT START
(LP UNITS) .................................................................. 33
PROBLEM 8 ­ENGINE STARTS HARD AND RUNS ROUGH
(GASOLINE UNITS) .................................................... 34
PROBLEM 8 ­ENGINE STARTS HARD AND RUNS ROUGH
(LP UNITS) .................................................................. 34
PROBLEM 9 -
ENGINE STARTS THEN SHUTS DOWN .................. 36
PROBLEM 10 -
7.5 AMP (F1) FUSE BLOWING .................................. 37
SSEECCTTIIOONN 77::
DDIIAAGGNNOOSSTTIICC TTEESSTTSS ............................................................................ 3388--6677
INTRODUCTION ........................................................ 38
TEST 1 -
Check No-Load Voltage And Frequency ...................... 38
TEST 2 -
Check Engine Governor .............................................. 38
TEST 3 -
Test Excitation Circuit Breaker .................................... 39
TEST 4 -
Fixed Excitation Test/Rotor Amp Draw ........................ 39
TEST 5 -
Wire Continuity ............................................................ 40
TEST 6 -
Check Field Boost ........................................................ 41
TEST 7 -
Test Stator DPE Winding.............................................. 41
TEST 8 -
Check Sensing Leads/Power Windings ...................... 42
TEST 9 -
Check Brush Leads ...................................................... 43
TEST 10 -
Check Brushes & Slip Rings ........................................ 43
TEST 11 -
Check Rotor Assembly ................................................ 44
TEST 12 -
Check Main Circuit Breaker .......................................... 44
TEST 13 -
Check Load Voltage & Frequency ................................ 45
TEST 14 -
Check Load Watts & Amperage .................................. 45
TEST 15 -
Check Battery Charge Output ...................................... 45
TEST 16 -
Check Battery Charge Rectifier .................................... 45
TEST 17 ­Check Battery Charge Windings/
Battery Charge Resistor .............................................. 46
TEST 18 -
Try Cranking the Engine .............................................. 47
TEST 19 -
Test Primer Switch........................................................ 47
TEST 20 -
Check Fuel Pump ........................................................ 48
TEST 21 -
Check 7.5 Amp Fuse .................................................... 49
TEST 22 -
Check Battery & Cables................................................ 49
TEST 23 -
Check Power Supply to Circuit Board .......................... 49
TEST 24 -
Check Start-Stop Switch .............................................. 50
TEST 25 -
Check Power Supply to Wire 56 .................................. 51
TEST 26 -
Check Starter Contactor Relay .................................... 51
TEST 26A -
Check Starter Contactor .............................................. 52
TEST 27 -
Check Starter Motor .................................................... 52
TEST 28 -
Check Fuel Supply........................................................ 54
TEST 29 -
Check Wire 14 Power Supply ...................................... 56
TEST 30 -
Check Wire 18 .............................................................. 56
TEST 31 ­Check Fuel Solenoid
(Gasoline Models) ........................................................ 57
TEST 32 -
Check Ignition Spark .................................................... 57
TEST 33 -
Check Spark Plugs ...................................................... 59
TEST 34 -
Check and Adjust Ignition Magnetos .......................... 59
TEST 35 -
Check Valve Adjustment .............................................. 61
TEST 36 -
Check Carburetion ...................................................... 62
TEST 37 -
Check Choke Solenoid ................................................ 62
TEST 38 ­Check Engine / Cylinder Leak Down Test /
Compression Test ........................................................ 64
TEST 39 -
Check Oil Pressure Switch .......................................... 65
TEST 40 -
Test Oil Temperature Switch ........................................ 65
TEST 41 -
Test Choke Heater ...................................................... 66
TEST 42 -
Check LPG Fuel Solenoid ............................................ 66
SSEECCTTIIOONN 88::
AASSSSEEMMBBLLYY ........................................................................................................ 6688--7700
MAJOR DISASSEMBLY .............................................. 68
Enclosure/Panel Removal ........................................68
Stator Removal ........................................................ 68
Rotor Removal ........................................................ 68
Belt Tensioning ........................................................ 69
Engine Removal ...................................................... 69
Startor Removal ...................................................... 69
Flywheel/Magneto Removal .................................... 70
SSEECCTTIIOONN 99::
EEXXPPLLOODDEEDD VVIIEEWWSS // PPAARRTT NNUUMMBBEERRSS ................ 7722--8833
BASE & PULLEY DRAWING ............................................ 72
ENCLOSURE DRAWING ................................................ 74
SHEET METAL DRAWING .......................................... 76
CONTROL PANEL DRAWING .................................... 78
760 V-TWIN ENGINE DRAWING ................................ 80
LP REGULATOR DRAWING ...................................... 82
SSEECCTTIIOONN 1100::
SSPPEECCIIFFIICCAATTIIOONNSS && CCHHAARRTTSS................................................ 8844--8866
MAJOR FEATURES AND DIMENSIONS .................... 84
GENERATOR SPECIFICATIONS .............................. 85
NOMINAL RESISTANCES OF
GENERATOR WINDINGS AT 68°F ............................ 85
ENGINE SPEEDS AND
VOLTAGE SPECIFICATIONS .................................... 86
TORQUE SPECIFICATIONS ...................................... 86
SSEECCTTIIOONN 1111::
EELLEECCTTRRIICCAALL DDAATTAA ................................................................................ 8888--8899
ELECTRICAL SCHEMATIC AND
WIRING DIAGRAM ...................................................... 88
Page 2
TTaabbllee ooff CCoonntteennttss
SSeeccttiioonn 11
GGEENNEERRAATTOORR FFUUNNDDAAMMEENNTTAALLSS
MAGNETISM
Magnetism can be used to produce electricity and electricity can be used to produce magnetism.
Much about magnetism cannot be explained by our present knowledge. However, there are certain pat­terns of behavior that are known. Application of these behavior patterns has led to the development of gen­erators, motors and numerous other devices that uti­lize magnetism to produce and use electrical energy.
See Figure 1-1. The space surrounding a magnet is permeated by magnetic lines of force called “flux”. These lines of force are concentrated at the magnet's north and south poles. They are directed away from the magnet at its north pole, travel in a loop and re­enter the magnet at its south pole. The lines of force form definite patterns which vary in intensity depend­ing on the strength of the magnet. The lines of force never cross one another. The area surrounding a magnet in which its lines of force are effective is called a “magnetic field”.
Like poles of a magnet repel each other, while unlike poles attract each other.
Figure 1-1. – Magnetic Lines of Force
ELECTROMAGNETIC FIELDS
All conductors through which an electric current Is flowing have a magnetic field surrounding them. This field is always at right angles to the conductor. If a compass is placed near the conductor, the compass needle will move to a right angle with the conductor. The following rules apply:
• The greater the current flow through the conductor, the stronger the magnetic field around the conductor.
• The increase in the number of lines of force is directly proportional to the increase in current flow and the field is distributed along the full length of the conductor.
• The direction of the lines of force around a conduc­tor can be determined by what is called the “right hand rule”. To apply this rule, place your right hand around the conductor with the thumb pointing in the direction of current flow. The fingers will then be pointing in the direction of the lines of force.
NOTE: The “right hand rule” is based on the “cur­rent flow” theory which assumes that current flows from positive to negative. This is opposite the “electron” theory, which states that current flows from negative to positive.
Figure 1-2. – The Right Hand Rule
ELECTROMAGNETIC INDUCTION
An electromotive force (EMF) or voltage can be pro­duced in a conductor by moving the conductor so that it cuts across the lines of force of a magnetic field.
Similarly, if the magnetic lines of force are moved so that they cut across a conductor, an EMF (voltage) will be produced in the conductor. This is the basic principal of the revolving field generator.
Figure 1-3, below, illustrates a simple revolving field generator. The permanent magnet (Rotor) is rotated so that its lines of magnetic force cut across a coil of wires called a Stator. A voltage is then induced into the Stator windings. If the Stator circuit is completed by connecting a load (such as a light bulb), current will flow in the circuit and the bulb will light.
Figure 1-3. – A Simple Revolving Field Generator
Page 3
SSeeccttiioonn 11 GGEENNEERRAATTOORR FFUUNNDDAAMMEENNTTAALLSS
A SIMPLE AC GENERATOR
Figure 1-4 shows a very simple AC Generator. The generator consists of a rotating magnetic field called a ROTOR and a stationary coil of wire called a STA­TOR. The ROTOR is a permanent magnet which con­sists of a SOUTH magnetic pole and a NORTH mag­netic pole.
As the MOTOR turns, its magnetic field cuts across the stationary STATOR. A voltage is induced Into the STATOR windings. When the magnet's NORTH pole passes the STATOR, current flows in one direction. Current flows in the opposite direction when the mag­net's SOUTH pole passes the STATOR. This con­stant reversal of current flow results in an alternating current (AC) waveform that can be diagrammed as shown in Figure 1-5.
The ROTOR may be a 2-pole type having a single NORTH and a single SOUTH magnetic pole. Some ROTORS are 4-pole type with two SOUTH and two NORTH magnetic poles. The following apply:
1. The 2-pole ROTOR must be turned at 3600 rpm to produce an AC frequency of 60 Hertz, or at 3000 rpm to deliver an AC fre­quency of 50 Hertz.
2. The 4-pole ROTOR must operate at 1800 rpm to deliver a 60 Hertz AC frequency or at 1500 rpm to deliver a 50 Hertz AC frequency.
Figure 1-4. – A Simple AC Generator
Figure 1-5. – Alternating Current Sine Wave
A MORE SOPHISTICATED AC GENERATOR
Figure 1-6 represents a more sophisticated genera­tor. A regulated direct current is delivered into the ROTOR windings via carbon BRUSHES AND SLIP RINGS. This results in the creation of a regulated magnetic field around the ROTOR. As a result, a reg­ulated voltage is induced into the STATOR. Regulated current delivered to the ROTOR is called “EXCITATION” current.
Figure 1-6. – A More Sophisticated Generator
See Figure 1-7 (next page). The revolving magnetic field (ROTOR) is driven by the engine at a constant speed. This constant speed is maintained by a mechanical engine governor. Units with a 2-pole rotor require an operating speed of 3600 rpm to deliver a 60 Hertz AC output. Engine governors are set to maintain approximately 3720 rpm when no electrical loads are connected to the generator.
Page 4
SSeeccttiioonn 11
GGEENNEERRAATTOORR FFUUNNDDAAMMEENNTTAALLSS
NOTE: AC output frequency at 3720 rpm will be about 62 Hertz. The “No-Load” is set slightly high to prevent excessive rpm, frequency and voltage droop under heavy electrical loading.
Generator operation may be described briefly as fol­lows:
1. Some “residual” magnetism is normally present in the Rotor and is sufficient to induce approximately 7 to 12 volts AC Into the STATOR's AC power windings.
2. During startup, an engine controller circuit board delivers bat­tery voltage to the ROTOR, via the brushes and slip rings.
a. The battery voltage is called “Field Boost”. b. Flow of direct current through the ROTOR
increases the strength of the magnetic field above that of “residual” magnetism alone.
3. “Residual” plus “Field Boost” magnetism induces a voltage into the Stator excitation (DPE), battery charge and AC Power windings.
4. Excitation winding unregulated AC output is delivered to an electronic voltage regulator, via an excitation circuit breaker.
a. A “Reference” voltage has been preset into
the Voltage Regulator.
b. An “Actual” (“sensing”) voltage is delivered
to the Voltage Regulator via sensing leads from the Stator AC power windings.
c. The Regulator “compares” the actual (sens-
ing) voltage to its pre-set reference voltage.
(1) If the actual (sensing) voltage is greater than the pre-set reference voltage, the Regulator will decrease the regulated cur­rent flow to the Rotor.
(2) If the actual (sensing) voltage is less than the pre-set reference voltage, the Regulator will increase the regulated cur­rent flow to the Rotor.
(3) In the manner described, the Regulator maintains an actual (sensing) voltage that is equal to the pre-set reference voltage.
NOTE: The Voltage Regulator also changes the Stator excitation windings alternating current (AC) output to direct current (DC).
5. When an electrical load is connected across the Stator power windings, the circuit is completed and an electrical current will flow.
6. The Rotor's magnetic field also induces a voltage Into the Stator battery charge windings.
a. Battery charge winding AC output is deliv-
ered to a battery charge rectifier (BCR) which changes the AC to direct current (DC).
b. The rectified DC is then delivered to the unit
battery, to maintain the battery in a charged state.
c. A 1 ohm, 25 watt Resistor is installed in
series with the grounded side of the battery charge circuit.
Page 5
Figure 1-7. – Generator Operating Diagram
SSeeccttiioonn 11 GGEENNEERRAATTOORR FFUUNNDDAAMMEENNTTAALLSS
FIELD BOOST
When the engine is cranked during startup, the engine's starter contactor is energized closed. Battery current is then delivered to the starter motor and the engine cranks.
Closure of the starter contactor contacts also delivers battery voltage to Pin 13 of an Engine Controller cir­cuit board. The battery current flows through a 47 ohm, 2 watt resistor and a field boost diode, then to the Rotor via brushes and slip rings. This is called “Field Boost” current.
Field boost current is delivered to the Rotor only while the engine is cranking. The effect is to “flash the field” every time the engine is cranked. Field boost current helps ensure that sufficient “pickup” voltage is avail­able on every startup to turn the Voltage Regulator on and build AC output voltage.
NOTE: Loss of the Field Boost function may or may not result in loss of AC power winding out­put. If Rotor residual magnetism alone is suffi­cient to turn the Regulator on loss of Field Boost may go unnoticed. However, If residual magnet­ism alone Is not enough to turn the Regulator on, loss of the Field Boost function will result In loss of AC power winding output to the load. The AC output voltage will then drop to a value commen­surate with the Rotor's residual magnetism (about 7-12 VAC).
GENERATOR AC CONNECTION SYSTEM
These air-cooled generator sets are equipped with dual stator AC power windings. These two stator wind­ings supply electrical power to customer electrical loads by means of a dual 2-wire connection system.
Generators may be installed to provide the following outputs:
1. 120 VAC loads only — one load with a maximum total wattage requirement equal to the generator’s rated power output (in watts), and 120V across the generator output terminals. Figure
1.8, page 7, shows the generator lead wire connections for 120VAC ONLY.
2. 120/240 VAC loads — one load with a maximum total wattage requirement equal to the generator’s rated power output, and 240V across the generator output terminals; or two separate loads, each with a maximum total wattage requirement equal to half of the generator’s rated power output (in watts), and 120V across the generator output terminals. Figure 1.9 on page 7, shows the generator lead wire connections for 120/240 VAC loads.
You can use your generator set to supply electrical power for operating one of the following electrical loads:
• QUIETPACT 55G & LP: 120 and/or 240 volts, sin­gle phase, 60 Hz electrical loads. These loads can require up to 5500 watts (5.5 kW) of total power, but cannot exceed 45.8 AC amperes of current at 120 volts or exceed 22.9 AC amperes at 240 volts.
• QUIETPACT 65G & LP: 120 and/or 240 volts, sin­gle phase, 60 Hz electrical loads. These loads can require up to 6500 watts (6.5 kW) of total power, but cannot exceed 54.1 AC amperes of current at 120 volts or exceed 27 AC amperes at 240 volts.
• QUIETPACT 75G & LP: 120 and/or 240 volts, sin­gle phase, 60 Hz electrical loads. These loads can require up to 7500 watts (7.5 kW) of total power, but cannot exceed 62.5 AC amperes of current at 120 volts or exceed 31.2 AC amperes at 240 volts.
CCAAUUTTIIOONN!! DDoo nnoott oovveerrllooaadd tthhee ggeenneerraattoorr.. SSoommee iinnssttaallllaattiioonnss mmaayy rreeqquuiirree tthhaatt eelleeccttrriiccaall llooaaddss bbee aalltteerrnnaatteedd ttoo aavvooiidd oovveerrllooaaddiinngg.. AAppppllyyiinngg eexxcceess-- ssiivveellyy hhiigghh eelleeccttrriiccaall llooaaddss mmaayy ddaammaaggee tthhee ggeenn-- eerraattoorr aanndd mmaayy sshhoorrtteenn iittss lliiffee.. AAdddd uupp tthhee rraatteedd wwaattttss ooff aallll eelleeccttrriiccaall lliigghhttiinngg,, aapppplliiaannccee,, ttooooll aanndd mmoottoorr llooaaddss tthhee ggeenneerraattoorr wwiillll ppoowweerr aatt oonnee ttiimmee.. TThhiiss ttoottaall sshhoouulldd nnoott bbee ggrreeaatteerr tthhaann tthhee wwaattttaaggee ccaappaacciittyy ooff tthhee ggeenneerraattoorr.. IIff aann eelleeccttrriiccaall ddeevviiccee nnaammeeppllaattee ggiivveess oonnllyy vvoollttss aanndd aammppss,, mmuullttiippllyy vvoollttss ttiimmeess aammppss ttoo oobbttaaiinn wwaattttss ((vvoollttss xx aammppss == wwaattttss)).. SSoommee eelleeccttrriicc mmoottoorrss rreeqquuiirree mmoorree wwaattttss ooff ppoowweerr ((oorr aammppss ooff ccuurrrreenntt)) ffoorr ssttaarrttiinngg tthhaann ffoorr ccoonnttiinnuuoouuss ooppeerraattiioonn..
LINE BREAKERS (120 VOLTS ONLY): Protects generator’s AC output circuit against
overload, i.e., prevents unit from exceeding wattage/amperage capacity. The circuit breaker rat­ings are as follows:
Page 6
MMooddeell CCiirrccuuiitt BBrreeaakkeerr 11 CCiirrccuuiitt BBrreeaakkeerr 22
QuietPact 55 30A 20A
QuietPact 65 30A 30A
QuietPact 75 35A 35A
SSeeccttiioonn 11
GGEENNEERRAATTOORR FFUUNNDDAAMMEENNTTAALLSS
Figure 1-8. – Connection for 120 Volts Only
RECONNECTION FOR DUAL VOLTAGE OUTPUT: When connected for dual voltage output, Stator out-
put leads 11P and 44 form two “hot” leads (T1- Red and T3- Black). The junction of leads 22P and 33 form the “Neutral” line (T2- White).
For dual voltage output, the “Neutral” line remains grounded.
NOTE: For units with two 30 amp or two 35 amp main breakers, the existing breakers may be re­used when reconnecting for dual voltage output. However, on units with a 30 amp and a 20 amp main breaker, you may wish to install a 2-pole breaker that is rated closer to the unit’s rated capacity (use two 25 amp main breakers).
Figure 1-9 - Connection for 120/240 Volts
NOTE: If this generator has been reconnected for dual voltage AC output (120/240 volts), the replacement line breakers should consist of two separate breakers with a connecting piece between the breaker handles (so that both break­ers operate at the same time). If the unit is recon­nected for dual voltage, it is no longer RVIA listed.
Page 7
SSeeccttiioonn 22 MMAAJJOORR GGEENNEERRAATTOORR CCOOMMPPOONNEENNTTSS
ROTOR ASSEMBLY
The Rotor is sometimes called the “revolving field”, since it provides the magnetic field that induces a voltage into the stationary Stator windings. Slip rings on the Rotor shaft allow excitation current from the voltage regulator to be delivered to the Rotor wind­ings. The Rotor is driven by the engine at a constant speed through a pulley and belt arrangement.
All generator models in this manual utilize a 2-pole Rotor, i.e., one having a single north and a single south pole. This type of Rotor must be driven at 3600 rpm for a 60 Hertz AC output, or at 3000 rpm for a 50 Hertz output.
Slip rings may be cleaned. If dull or tarnished, clean them with fine sandpaper (a 400 grit wet sandpaper is recommended). DO NOT USE ANY METALLIC GRIT OR ABRASIVE TO CLEAN SLIP RINGS.
STATOR ASSEMBLY
The Stator is “sandwiched” between the upper and lower bearing carriers and retained in that position by four Stator studs. Windings Included in the Stator assembly are (a) dual AC power windings, (b) an excitation or DPE winding, and (c) a battery charge winding. A total of eleven (11) leads are brought out of the Stator as follows:
1. Four (4) Stator power winding output leads (Wires No. 11P, 22P, 33 and 44). These leads deliver power to connected elec­trical loads.
2. Stator Power winding “sensing” leads (11S and 22S). These leads deliver an “actual voltage signal to the electronic Voltage Regulator.
Page 8
Figure 2-1. Exploded View of Generator
SSeeccttiioonn 22
MMAAJJOORR GGEENNEERRAATTOORR CCOOMMPPOONNEENNTTSS
3. Two excitation winding output leads (No. 2 and 6). These leads deliver unregulated excitation current to the voltage regulator.
4. Three (3) battery charge output leads (No. 55, 66 and 77).
Figure 2-2. – Stator Output Leads
BRUSH HOLDER
The brush holder is retained in the rear bearing carri­er by two M5 screws. It retains two brushes, which contact the Rotor slip rings and allow current flow from stationary parts to the revolving Rotor. The posi­tive (+) brush is located nearest the Rotor bearing.
Figure 2-3. – Brush Holder
BATTERY CHARGE COMPONENTS
The Stator incorporates dual battery charge windings. A battery charge rectifier (BCR) changes the AC out­put of these windings to direct current (DC). Battery charge winding output is delivered to the unit battery
via the rectifier, a 7.5 amp fuse and Wire No. 13. A 1 ohm, 25 watt resistor is connected in series with the grounded side of the circuit.
Figure 2-4. – Battery Charge Circuit
EXCITATION CIRCUIT COMPONENTS
GENERAL: During operation, the Rotor's magnetic field induces a
voltage and current flow into the Stator excitation winding. The resultant AC output is delivered to a voltage regulator via an excitation circuit breaker (CB3).
Figure 2-5. – Schematic: Excitation Circuit
EXCITATION CIRCUIT BREAKER: The excitation circuit breaker (CB3) is self-resetting
and cannot be reset manually. Should the breaker open for any reason, excitation current flow to the
Page 9
SSeeccttiioonn 22 MMAAJJOORR GGEENNEERRAATTOORR CCOOMMPPOONNEENNTTSS
Rotor will be lost. The unit’s AC output voltage will then drop to a value commensurate with the Rotor's residual magnetism (about 7-12 VAC).
Figure 2-6. – Excitation Circuit Breaker
VOLTAGE REGULATOR: Six (6) leads are connected to the voltage regulator
as follows:
• Two (2) SENSING leads deliver ACTUAL AC out­put voltage signals to the regulator. These are Wires No. 11S and 22S.
• Two (2) leads (4 and 0K) deliver the regulated direct current to the Rotor, via brushes and slip rings.
• Two (2) leads (No. 6 and 2A) deliver Stator excita­tion winding AC output to the regulator.
Figure 2-7. – Voltage Regulator
The regulator mounts a “VOLTAGE ADJUST” poten­tiometer, used for adjustment of the pre-set REFER­ENCE voltage. A lamp (LED) will turn on to indicate that SENSING voltage is available to the regulator and the regulator is turned on.
ADJUSTMENT PROCEDURE: With the frequency set at 62.5 Hertz and no load on
the generator, slowly turn the voltage adjust pot on the voltage regulator until 124 VAC is measured. If voltage is not adjustable, proceed to Section 6 ­Troubleshooting; Problem 2.
NOTE: If, for any reason, sensing voltage to the regulator is lost, the regulator will shut down and excitation output to the Rotor will be lost. The AC output voltage will then drop to a value that is commensurate with Rotor residual magnetism (about 7-12 VAC). Without this automatic shut­down feature, loss of sensing (actual) voltage to the regulator would result in a “full field” or “full excitation” condition and an extremely high AC output voltage.
NOTE: Adjustment of the regulator's “VOLTAGE ADJUST” potentiometer must be done only when the unit is running at its correct governed no-load speed. Speed is correct when the unit's no-load AC output frequency is about 62.5 Hertz. At the stated frequency, AC output voltage should be about 124 volts.
CRANKCASE BREATHER
Figure 2-8. – Crankcase Breather
DESCRIPTION: The crankcase breather is equipped with a reed valve
to control and maintain a partial vacuum in the crankcase. The breather is vented to the intake
Page 10
SSeeccttiioonn 22
MMAAJJOORR GGEENNEERRAATTOORR CCOOMMPPOONNEENNTTSS
elbow. The breather chamber contains a removable oil vapor collector. Oil vapor is condensed on the col­lector material and drains back into the crankcase, which minimizes the amount of oil vapor entering the breather.
CHECK BREATHER:
1. Disconnect breather tube and remove four screws and breather. Discard gasket.
2. Check to see that reed valve is not deformed (Figure 2-8).
Note: Reed valve must form a complete seal around vent hole.
3. Remove oil vapor collector and retainer.
4. Check collector for deterioration and replace if necessary.
INSTALL BREATHER:
1. Install oil vapor collector and retainer.
Note: Push oil vapor collector and retainer in until it bottoms.
2. Install breather with new gasket (Figure 2-8).
a. Torque screws to 5-8 ft-lbs.
3. Assemble breather tube to intake elbow.
Page 11
CONTROL PANEL COMPONENT IDENTIFICATION
Figure 2-9. – Control Panel Components
SSeeccttiioonn 33 IINNSSUULLAATTIIOONN RREESSIISSTTAANNCCEE TTEESSTTSS
EFFECTS OF DIRT AND MOISTURE
Moisture and dirt are detrimental to the continued good operation of any generator set.
If moisture is allowed to remain in contact with the Stator and Rotor windings, some of the moisture will be retained in voids and cracks of the winding Insulation. This will result in a reduced Insulation resistance and, eventually, the unit's AC output will be affected.
Insulation used in the generator is moisture resistant. However, prolonged exposure to moisture will gradu­ally reduce the resistance of the winding insulation.
Dirt can make the problem worse, since it tends to hold moisture Into contact with the windings. Salt, as from sea air, contributes to the problem since salt can absorb moisture from the air. When salt and moisture combine, they make a good electrical conductor.
Because of the detrimental affects of dirt and mois­ture, the generator should be kept as clean and as dry as possible. Rotor and Stator windings should be tested periodically with an insulation resistance tester (such as a megohmmeter or hi-pot tester).
If the Insulation resistance is excessively low, drying may be required to remove accumulated moisture. After drying, perform a second insulation resistance test. If resistance is still low after drying, replacement of the defective Rotor or Stator may be required.
INSULATION RESISTANCE TESTERS
Figure 3-1 shows one kind of hi-pot tester. The tester shown has a “Breakdown” lamp that will glow during the test procedure to indicate an insulation break­down in the winding being tested.
Figure 3-1. – One Type of Hi-Pot Tester
DDAANNGGEERR!! IINNSSUULLAATTIIOONN RREESSIISSTTAANNCCEE TTEESSTTEERRSS SSUUCCHH AASS HHII--PPOOTT TTEESSTTEERRSS AANNDD MMEEGGOOHHMMMMEETTEERRSS AARREE AA SSOOUURRCCEE OOFF HHIIGGHH AANNDD DDAANNGGEERROOUUSS EELLEECCTTRRIICCAALL VVOOLLTTAAGGEE.. FFOOLLLLOOWW TTHHEE TTEESSTTEERR MMAANNUUFFAACCTTUURREERR''SS IINNSSTTRRUUCCTTIIOONNSS CCAARREEFFUULLLLYY.. UUSSEE CCOOMMMMOONN SSEENNSSEE TTOO AAVVOOIIDD DDAANNGGEERROOUUSS EELLEECCTTRRII-- CCAALL SSHHOOCCKK
DRYING THE GENERATOR
GENERAL: If tests indicate the insulation resistance of a winding
is below a safe value, the winding should be dried before operating the generator. Some recommended drying procedures Include (a) heating units and (b) forced air.
HEATING UNITS: If drying is needed, the generator can be enclosed in
a covering. Heating units can then be installed to raise the temperature about 15°-18° F. (8°-10° C.) above ambient temperature.
FORCED AIR: Portable forced air heaters can be used to dry the
generator. Direct the heated air into the generator’s air intake openings. Remove the voltage regulator and run the unit at no-load. Air temperature at the point of entry into the generator should not exceed 150° F. (66° C.).
CLEANING THE GENERATOR
GENERAL: The generator can be cleaned properly only while it is
disassembled. The cleaning method used should be determined by the type of dirt to be removed. Be sure to dry the unit after it has been cleaned.
NOTE: A shop that repairs electric motors may be able to assist you with the proper cleaning of gen­erator windings. Such shops are often experi­enced In special problems such as a sea coast environment, marine or wetland applications, mining, etc.
USING SOLVENTS FOR CLEANING: If dirt contains oil or grease a solvent is generally
required. Only petroleum distillates should be used to clean electrical components. Recommended are safety type petroleum solvents having a flash point greater than 100° F. (38° C.).
Page 12
SSeeccttiioonn 33
IINNSSUULLAATTIIOONN RREESSIISSTTAANNCCEE TTEESSTTSS
CCAAUUTTIIOONN!!:: SSoommee ggeenneerraattoorrss mmaayy uussee eeppooxxyy oorr ppoollyyeesstteerr bbaassee wwiinnddiinngg vvaarrnniisshheess.. UUssee ssoollvveennttss tthhaatt wwiillll nnoott aattttaacckk ssuucchh mmaatteerriiaallss..
Use a soft brush or cloth to apply the solvent. Be care­ful to avoid damage to wire or winding insulation. After cleaning, dry all components thoroughly using mois­ture-free, low-pressure compressed air.
DDAANNGGEERR!!:: DDOO NNOOTT AATTTTEEMMPPTT TTOO WWOORRKK WWIITTHH SSOOLLVVEENNTTSS IINN AANNYY EENNCCLLOOSSEEDD AARREEAA.. PPRROO-- VVIIDDEE AADDEEQQUUAATTEE VVEENNTTIILLAATTIIOONN WWHHEENN WWOORRKKIINNGG WWIITTHH SSOOLLVVEENNTTSS.. WWIITTHHOOUUTT AADDEE-- QQUUAATTEE VVEENNTTIILLAATTIIOONN,, FFIIRREE,, EEXXPPLLOOSSIIOONN OORR HHEEAALLTTHH HHAAZZAARRDDSS MMAAYY EEXXIISSTT .. WWEEAARR EEYYEE PPRROOTTEECCTTIIOONN.. WWEEAARR RRUUBBBBEERR GGLLOOVVEESS TTOO PPRROOTTEECCTT TTHHEE HHAANNDDSS..
CLOTH OR COMPRESSED AIR: For small parts or when dry dirt is to be removed, a
dry cloth may be satisfactory. Wipe the parts clean, then use low pressure air at 30 psi (206 Kpa) to blow dust away.
BRUSHING AND VACUUM CLEANING: Brushing with a soft bristle brush followed by vacuum
cleaning is a good method of removing dust and dirt. Use the soft brush to loosen the dirt, then remove it with the vacuum.
STATOR INSULATION RESISTANCE
GENERAL: Insulation resistance is a measure of the Integrity of
the insulating materials that separate electrical wind­ings from the generator's steel core. This resistance can degrade over time due to the presence of conta­minants, dust, dirt, grease and especially moisture).
The normal Insulation resistance for generator wind­ings is on the order of “millions of ohms” or “megohms”.
When checking the insulation resistance, follow the tester manufacturer's Instructions carefully. Do NOT exceed the applied voltages recommended in this manual. Do NOT apply the voltage longer than one (1) second.
CCAAUUTTIIOONN!!:: DDOO NNOOTT ccoonnnneecctt tthhee HHii--PPoott TTeesstteerr oorr MMeeggoohhmmmmeetteerr tteesstt lleeaaddss ttoo aannyy lleeaaddss tthhaatt aarree rroouutteedd iinnttoo tthhee ggeenneerraattoorr ccoonnttrrooll ppaanneell.. CCoonnnneecctt tthhee tteesstteerr lleeaaddss ttoo tthhee SSttaattoorr oorr RRoottoorr lleeaaddss oonnllyy..
STATOR SHORT-TO-GROUND TESTS: See Figure 3-2. To test the Stator for a short-to-
ground condition, proceed as follows:
1. Disconnect and Isolate all Stator leads as follows:
a. Disconnect sensing leads 11S and 22S
from the voltage regulator.
b. Disconnect excitation winding lead No. 6
from the voltage regulator.
c. Disconnect excitation lead No. 2 from the
excitation circuit breaker (CB3).
d. Disconnect battery charge winding leads
No. 66 and 77 from the battery charge recti­fier (BCR).
e. Disconnect battery charge winding lead No.
55 from the battery charge resistor (R1).
f. At the main circuit breakers, disconnect AC
power leads No. 11P and 33.
g. At the 4-tab ground terminal (GT), discon-
nect Stator power leads No. 22P and 44.
2. When all leads have been disconnected as outlined in Step 1 above, test for a short-to-ground condition as follows:
a. Connect the terminal ends of all Stator
leads together (11S, 22S, 11P, 22P, 33, 44, 2,6, 55, 66, 77).
b. Follow the tester manufacturer's instructions
carefully. Connect the tester leads across all Stator leads and to frame ground on the Stator can. Apply a voltage of 1500 volts. Do NOT apply voltage longer than one (1) second.
If the test Indicates a breakdown in Insulation, the Stator should be cleaned, dried and re-tested. If the winding fails the second test (after cleaning and dry­ing), replace the Stator assembly.
TEST BETWEEN ISOLATED WINDINGS:
1. Follow the tester manufacturer's instructions carefully. Connect the tester test leads across Stator leads No. 11P and 2. Apply a voltage of 1500 volts- DO NOT EXCEED 1 SECOND.
2. Repeat Step 1 with the tester leads connected across the fol­lowing Stator leads:
a. Across Wires No. 33 and 2. b. Across Wires No. 11P and 66. c. Across Wires No. 33 and 66. d. Across Wires No. 2 and 66.
If a breakdown in the insulation between isolated windings is indicated, clean and dry the Stator. Then, repeat the test. If the Stator fails the second test, replace the Stator assembly.
Page 13
SSeeccttiioonn 33 IINNSSUULLAATTIIOONN RREESSIISSTTAANNCCEE TTEESSTTSS
TEST BETWEEN PARALLEL WINDINGS: Connect the tester leads across Stator leads No. 11P
and 33. Apply a voltage of 1500 volts. If an insulation breakdown is indicated, clean and dry the Stator. Then, repeat the test between parallel windings. If the Stator fails the second test, replace it.
Figure 3-2. – Stator Leads
TESTING ROTOR INSULATION
To test the Rotor for insulation breakdown, proceed as follows:
1. Disconnect wires from the Rotor brushes or remove the brush holders with brushes.
2. Connect the tester positive (+) test lead to the positive (+) slip ring (nearest the Rotor bearing). Connect the tester negative (-) test lead to a clean frame ground (like the Rotor shaft).
Figure 3-3. – Rotor Test Points
3. Apply 1000 volts. DO NOT APPLY VOLTAGE LONGER THAN 1 SECOND.
If an insulation breakdown is indicated, clean and dry the Rotor then repeat the test. Replace the Rotor if it fails the second test (after cleaning and drying).
THE MEGOHMMETER
GENERAL: A megohmmeter, often called a “megger”, consists of
a meter calibrated in megohms and a power supply. Use a power supply of 1500 volts when testing Stators; or 1000 volts when testing the Rotor. DO NOT APPLY VOLTAGE LONGER THAN ONE (1) SECOND.
TESTING STATOR INSULATION: All parts that might be damaged by the high megger
voltages must be disconnected before testing. Isolate all Stator leads (Figure 3-2) and connect all of the Stator leads together. FOLLOW THE MEGGER MANUFACTURER'S INSTRUCTIONS CAREFULLY.
Use a megger power setting of 1500 volts. Connect one megger test lead to the junction of all Stator leads, the other test lead to frame ground on the Stator can. Read the number of megohms on the meter.
MINIMUM INSULATION
GENERATOR RATED VOLTS
RESISTANCE =
__________________________
+1
(in “Megohms”)
1000
The MINIMUM acceptable megger reading for Stators may be calculated using the following formula:
EXAMPLE: Generator is rated at 120 volts AC. Divide “120” by “1000” to obtain “0.12”. Then add “1” to obtain “1.12” megohms. Minimum Insulation resistance for a 120 VAC Stator Is 1.12 megohms.
If the Stator insulation resistance is less than the cal­culated minimum resistance, clean and dry the Stator. Then, repeat the test. If resistance is still low, replace the Stator.
Use the Megger to test for shorts between isolated windings as outlined “Stator Insulation Resistance”.
Also test between parallel windings. See “Test Between Parallel Windings”on this page.
TESTING ROTOR INSULATION: Apply a voltage of 1000 volts across the Rotor posi-
tive (+) slip ring (nearest the rotor bearing), and a clean frame ground (i.e. the Rotor Shaft). DO NOT EXCEED 1000 VOLTS AND DO NOT APPLY VOLT­AGE LONGER THAN 1 SECOND. FOLLOW THE MEGGER MANUFACTURER'S INSTRUCTIONS CAREFULLY.
RROOTTOORR MMIINNIIMMUUMM IINNSSUULLAATTIIOONN RREESSIISSTTAANNCCEE::
11..55 mmeeggoohhmmss
Page 14
SSeeccttiioonn 44
MMEEAASSUURRIINNGG EELLEECCTTRRIICCIITTYY
METERS
Devices used to measure electrical properties are called meters. Meters are available that allow one to measure (a) AC voltage, (b) DC voltage, (c) AC fre­quency, and (d) resistance In ohms. The following apply:
To measure AC voltage, use an AC voltmeter. To measure DC voltage, use a DC voltmeter. Use a frequency meter to measure AC frequency In
“Hertz” or “cycles per second”..
Use an ohmmeter to read circuit resistance, in
“ohms”.
THE VOM
A meter that will permit both voltage and resistance to be read is the “volt-ohm-milliammeter” or “VOM”.
Some VOM's are of the “analog” type (not shown). These meters display the value being measured by physically deflecting a needle across a graduated scale. The scale used must be Interpreted by the user.
“Digital” VOM's (Figure 4-1) are also available and are generally very accurate. Digital meters display the measured values directly by converting the values to numbers.
NOTE: Standard AC voltmeters react to the AVER­AGE value of alternating current. When working with AC, the effective value is used. For that rea­son a different scale is used on an AC voltmeter. The scale is marked with the effective or “rms” value even though the meter actually reacts to the average value. That is why the AC voltmeter will give an Incorrect reading if used to measure direct current (DC).
Figure 4-1. – Digital VOM
MEASURING AC VOLTAGE
An accurate AC voltmeter or a VOM may be used to read the generator's AC output voltage. The following apply:
1. Always read the generator's AC output voltage only at the unit's rated operating speed and AC frequency.
2. The generator's voltage regulator can be adjusted for correct output voltage only while the unit is operating at its correct rated speed and frequency.
3. Only an AC voltmeter may be used to measure AC voltage. DO NOT USE A DC VOLTMETER FOR THIS PURPOSE.
DDAANNGGEERR!!:: RRVV GGEENNEERRAATTOORRSS PPRROODDUUCCEE HHIIGGHH AANNDD DDAANNGGEERROOUUSS VVOOLLTTAAGGEESS.. CCOONNTTAACCTT WWIITTHH HHIIGGHH VVOOLLTTAAGGEE TTEERRMMIINNAALLSS WWIILLLL RREESSUULLTT IINN DDAANNGGEERROOUUSS AANNDD PPOOSSSSIIBBLLYY LLEETTHHAALL EELLEECCTTRRIICCAALL SSHHOOCCKK..
MEASURING DC VOLTAGE
A DC voltmeter or a VOM may be used to measure DC voltages. Always observe the following rules:
1. Always observe correct DC polarity.
a. Some VOM's may be equipped with a polar-
ity switch.
b. On meters that do not have a polarity
switch, DC polarity must be reversed by reversing the test leads.
2. Before reading a DC voltage, always set the meter to a higher voltage scale than the anticipated reading. if in doubt, start at the highest scale and adjust the scale downward until correct readings are obtained.
3. The design of some meters is based on the “current flow” theo­ry while others are based on the “electron flow” theory.
a. The “current flow” theory assumes that
direct current flows from the positive (+) to the negative (-).
b. The “electron flow” theory assumes that
current flows from negative (-) to positive (+).
NOTE: When testing generators, the “current flow” theory is applied. That is, current is assumed to flow from positive (+) to negative (-).
Page 15
SSeeccttiioonn 44 MMEEAASSUURRIINNGG EELLEECCTTRRIICCIITTYY
MEASURING AC FREQUENCY
The generator's AC output frequency is proportional to Rotor speed. Generators equipped with a 2-pole Rotor must operate at 3600 rpm to supply a frequen­cy of 60 Hertz. Units with 4-pole Rotor must run at 1800 rpm to deliver 60 Hertz.
Correct engine and Rotor speed is maintained by an engine speed governor. For models rated 60 Hertz, the governor is generally set to maintain a no-load frequency of about 62 Hertz with a corresponding out­put voltage of about 124 volts AC line-to-neutral. Engine speed and frequency at no-load are set slight­ly high to prevent excessive rpm and frequency droop under heavy electrical loading.
MEASURING CURRENT
To read the current flow, in AMPERES, a clamp-on ammeter may be used. This type of meter indicates current flow through a conductor by measuring the strength of the magnetic field around that conductor. The meter consists essentially of a current trans­former with a split core and a rectifier type instrument connected to the secondary. The primary of the cur­rent transformer is the conductor through which the current to be measured flows. The split core allows the Instrument to be clamped around the conductor without disconnecting it.
Current flowing through a conductor may be mea­sured safely and easily. A line-splitter can be used to measure current in a cord without separating the con­ductors.
Figure 4-2. – Clamp-On Ammeter
Figure 4-3. – A Line-Splitter
NOTE: If the physical size of the conductor or ammeter capacity does not permit all lines to be measured simultaneously, measure current flow in each individual line. Then, add the Individual readings.
MEASURING RESISTANCE
The volt-ohm-milliammeter may be used to measure the resistance in a circuit. Resistance values can be very valuable when testing coils or windings, such as the Stator and Rotor windings.
When testing Stator windings, keep in mind that the resistance of these windings is very low. Some meters are not capable of reading such a low resis­tance and will simply read “continuity”.
If proper procedures are used, the following condi­tions can be detected using a VOM:
A “short-to-ground” condition in any Stator or Rotor
winding.
Shorting together of any two parallel Stator wind-
ings.
Shorting together of any two isolated Stator wind-
ings.
An open condition in any Stator or Rotor winding.
Component testing may require a specific resistance value or a test for “infinity” or “continuity.” Infinity is an OPEN condition between two electrical points, which would read as no resistance on a VOM. Continuity is a closed condition between two electrical points, which would be indicated as very low resistance or “ZERO” on a VOM.
Page 16
SSeeccttiioonn 44
MMEEAASSUURRIINNGG EELLEECCTTRRIICCIITTYY
ELECTRICAL UNITS
AMPERE: The rate of electron flow in a circuit is represented by
the AMPERE. The ampere is the number of electrons flowing past a given point at a given time. One AMPERE is equal to just slightly more than six thou­sand million billion electrons per second.
With alternating current (AC), the electrons flow first in one direction, then reverse and move in the oppo­site direction. They will repeat this cycle at regular intervals. A wave diagram, called a “sine wave” shows that current goes from zero to maximum posi­tive value, then reverses and goes from zero to maxi­mum negative value. Two reversals of current flow is called a cycle. The number of cycles per second is called frequency and is usually stated in “Hertz”.
VOLT: The VOLT is the unit used to measure electrical
PRESSURE, or the difference in electrical potential that causes electrons to flow. Very few electrons will flow when voltage is weak. More electrons will flow as voltage becomes stronger. VOLTAGE may be consid­ered to be a state of unbalance and current flow as an attempt to regain balance. One volt is the amount of EMF that will cause a current of 1 ampere to flow through 1 ohm of resistance.
Figure 4-4. – Electrical Units
OHM: The OHM is the unit of RESISTANCE. In every circuit
there is a natural resistance or opposition to the flow of electrons. When an EMF is applied to a complete circuit, the electrons are forced to flow in a single direction rather than their free or orbiting pattern. The resistance of a conductor depends on (a) its physical makeup, (b) its cross-sectional area, (c) its length, and (d) its temperature. As the conductor's tempera­ture increases, its resistance increases in direct pro­portion. One (1) ohm of resistance will permit one (1) ampere of current to flow when one (1) volt of electro­motive force (EMF) is applied.
OHM'S LAW
A definite and exact relationship exists between VOLTS, OHMS and AMPERES. The value of one can be calculated when the value of the other two are known. Ohm's Law states that in any circuit the current will increase when voltage increases but resistance remains the same, and current will decrease when resistance Increases and voltage remains the same.
Figure 4-5.
If AMPERES is unknown while VOLTS and OHMS are known, use the following formula:
AMPERES =
VOLTS
OHMS
If VOLTS is unknown while AMPERES and OHMS are known, use the following formula:
VOLTS = AMPERES x OHMS
If OHMS is unknown but VOLTS and AMPERES are known, use the following:
OHMS
=
VOLTS
AMPERES
Page 17
SSeeccttiioonn 55 EENNGGIINNEE DDCC CCOONNTTRROOLL SSYYSSTTEEMM
INTRODUCTION
The engine DC control system includes all com­ponents necessary for the operation of the engine. Operation includes rest, priming, crank­ing, starting, running and shutdown. The system is shown schematically.
OPERATIONAL ANALYSIS
CIRCUIT CONDITION- REST:
Battery voltage is available to the engine controller cir­cuit board (PCB) from the unit BATTERY and via (a) the RED battery cable, Wire 13, a 7.5 amp FUSE (F1), Wire 15 and circuit board Terminal J3. However, circuit board action is holding the circuit open and no action can occur.
Battery output is available to the contacts of a STARTER CONTACTOR (SC) and STARTER CON­TACTOR RELAY (SCR), but the contacts are open.
Battery voltage is also delivered to the FUEL PRIMER SWITCH (SW2). The switch is open and the circuit is incomplete.
Battery voltage is also available to the REMOTE FUEL PRIMER SWITCH. The switch is open and the circuit is incomplete.
Page 18
SSeeccttiioonn 55
EENNGGIINNEE DDCC CCOONNTTRROOLL SSYYSSTTEEMM
Page 19
CIRCUIT CONDITION- PRIMING:
When the FUEL PRIMER SWITCH (SW2) or the REMOTE PANEL FUEL PRIMER is closed by the oper­ator, battery voltage is delivered across the closed switch contacts and to the FUEL PUMP (FP) via Wire 14A. The FUEL SOLENOID (FS) will be energized via Wire 14 during cranking and running.
SSeeccttiioonn 55 EENNGGIINNEE DDCC CCOONNTTRROOLL SSYYSSTTEEMM
Page 20
CIRCUIT CONDITION- CRANKING:
When the START-STOP-SWITCH (SW1)or REMOTE PANEL START SWITCH is held at “START” position, Wire 17 from the Engine controller circuit board is con­nected to frame Ground. Circuit board action will then deliver battery voltage to a STARTER CONTACTOR RELAY (SCR) via wire 56, and to a automatic CHOKE SOLENOID (CS) via Wire 90.
When battery voltage energizes the STARTER CON­TACTOR RELAY (SCR), Its contacts close and battery output is delivered to the STARTER CONTACTOR (SC) via Wire 16. The STARTER CONTACTOR (SC) ener­gizes and its contacts close, battery output is delivered to the STARTER MOTOR (SM) via Wire 16.The STARTER MOTOR energizes and the engine cranks.
When the STARTER CONTACTOR RELAY (SCR) closes, Battery voltage is also delivered to the circuit board pin location J1-13 via Wire 16. This voltage is reduced and used for field boost and is outputted from pin location J1-9.
While cranking, the CHOKE SOLENOID (CS) is ener­gized cyclically by circuit board action (two seconds on, two seconds off).
Also while cranking, circuit board action energizes CIRCUIT BOARD TERMINAL J2 and delivers battery voltage to the Wire 14/14A circuit. This energizes the FUEL PUMP (FP) ,FUEL SOLENOID (FS) and CHOKE HEATER (CH) and optional light or hourmeter in remote panel.
Circuit board action holds open Wire 18A to common ground. The Magneto will induce a spark during cranking.
SSeeccttiioonn 55
EENNGGIINNEE DDCC CCOONNTTRROOLL SSYYSSTTEEMM
Page 21
CIRCUIT CONDITION-RUNNING:
With the FUEL PUMP (FP) and FUEL SOLENOID (FS) operating and ignition occurring, the engine should start, and the START-STOP SWITCH (SW1) is released.
A voltage is induced into the Stator's BATTERY CHARGE WINDING. This voltage is delivered to the ENGINE CONTROLLER BOARD (PCB) via Wire 66 to prevent STARTER MOTOR engagement above a cer­tain rpm.
Circuit board action terminates DC output to the STARTER CONTACTOR RELAY (SCR), which then de-energizes to end cranking. Circuit board action ter­minates DC output to the CHOKE SOLENOID (CS). The choke will go to a position determined by the CHOKE HEATER (CH).
The LOW OIL PRESSURE SWITCH (LOP) is nor­mally closed. After start-up, engine oil pressure will open the LOP.
SSeeccttiioonn 55 EENNGGIINNEE DDCC CCOONNTTRROOLL SSYYSSTTEEMM
Page 22
CIRCUIT CONDITION- SHUTDOWN:
Setting the START-STOP SWITCH (SW1) or the REMOTE PANEL START-STOP SWITCH to its “STOP” position connects the Wire 18 circuit to frame ground. Circuit board action then closes the circuit to Wire 18A, grounding the ignition magneto. Circuit board action de-energizes DC output to Terminal J2. The FUEL PUMP (FP), FUEL SOLENOID (FS) and CHOKE HEATER (CH) are de-energized by the loss of DC to Wire 14. Ignition and fuel flow terminate and the engine shuts down.
SSeeccttiioonn 55
EENNGGIINNEE DDCC CCOONNTTRROOLL SSYYSSTTEEMM
Page 23
CIRCUIT CONDITION- FAULT SHUTDOWN: The engine mounts a HIGH OIL TEMPERA-
TURE SWITCH (HTO) and a LOW OIL PRES­SURE SWITCH (LOP).
Should engine oil temperature exceed a pre­set value, the switch contacts will close. Wire 85 from the circuit board will connect to frame ground. Circuit board action will then initiate a shutdown.
Should engine oil pressure drop below a safe pre-set value, the switch contacts will close. On contact closure, Wire 85 will be connected to frame ground and circuit board action will initiate an engine shutdown.
The circuit board has a time delay built into it for the Wire 85 fault shutdowns. At STARTUP ONLY the circuit board will wait approximately 6 seconds before looking at the Wire 85 fault shutdowns. Once running after the 6 second time delay, grounding Wire 85 thru either switch will cause an immediate shutdown.
SSeeccttiioonn 55 EENNGGIINNEE DDCC CCOONNTTRROOLL SSYYSSTTEEMM
ENGINE CONTROLLER CIRCUIT BOARD
GENERAL: The engine controller board is responsible for crank-
ing, startup, running and shutdown operations. The board interconnects with other components of the DC control system to turn them on and off at the proper times. It is powered by fused 12 VDC power from the unit battery.
CIRCUIT BOARD CONNECTIONS: The circuit board mounts a 15-pin receptacle (J1) and
two single pin terminals (J2 and J3, see Figure 5.3). Figure 5-2 shows the 15-pin receptacle (J1), the asso­ciated wires and the function(s) of each pin and wire.
PPIINN WWIIRREE FFUUNNCCTTIIOONN
1 56 Delivers 12 VDC to Starter Contactor (SC)
while cranking only.
290
Delivers 12 VDC to Choke Solenoid coil while cranking only. (Two seconds ON, Two seconds OFF)
3 Not used.
4 18A Grounds Magneto for Shutdown.
5 Not used.
6 17 To Start-Stop switch. When wire is grounded
by setting Start-Stop switch to “START”, engine will crank.
7 17 To Start-Stop switch on optional Remote
Panel.
8 Not used.
9 4 Field Boost DC to Voltage Regulator and to
Rotor windings.
10 66 Starter Lockout. Prevents cranking while
engine is running.
11 85 Fault shutdown circuit. When grounded by clo-
sure of High Oil Temperature or Low Oil Pressure Switch engine will shut down.
12 0 Common Ground.
13 16 12 VDC Input to Field Boost circuit while
cranking only.
14 18 To Start-Stop switch. When grounded by set-
ting Switch to “STOP” engine shuts down.
15 18
To Start-Stop Switch on optional Remote Panel.
Figure 5-2. – Receptacle J1
In addition to the 15-pin receptacle (J1), the circuit board is equipped with two single pin terminals (J2 and J3). These terminals may be identified as follows:
1. Wire 14 connects to Terminal J2. During cranking and running, the circuit board delivers battery voltage to the Wire 14 circuit for the following functions:
a. To operate the electric Fuel Pump (FP). b. To energize the Fuel Solenoid. c. To operate the Choke Heater. d. To the Remote Wire Harness to operate an
hourmeter or a light.
2. Wire 15 connects to Terminal J3. This is the power supply (12 VDC) for the circuit board and the DC control system.
Figure 5-3. – Engine Controller Circuit Board
BATTERY
RECOMMENDED BATTERY: When anticipated ambient temperatures will be con-
sistently above 32° F. (0° C.), use a 12 volts automo­tive type storage battery rated 70 amp-hours and capable of delivering at least 400 cold cranking amperes.
If ambient temperatures will be below 32° (0° C.), use a 12 volt battery rated 95 amp-hours and having a cold cranking capacity of 400 amperes.
BATTERY CABLES: Use of battery cables that are too long or too small in
diameter will result in excessive voltage drop. For best cold weather starting, voltage drop between the battery and starter should not exceed 0.12 volt per 100 amperes of cranking current.
Select the battery cables based on total cable length and prevailing ambient temperature. Generally, the longer the cable and the colder the weather, the larg­er the required cable diameter.
Page 24
SSeeccttiioonn 55
EENNGGIINNEE DDCC CCOONNTTRROOLL SSYYSSTTEEMM
The following chart applies:
CCAABBLLEE LLEENNGGTTHH ((IINN FFEEEETT)) RREECCOOMMMMEENNDDEEDD CCAABBLLEE SSIIZZEE
0-10 No. 2 11-15 No. 0 16-20 No. 000
EFFECTS OF TEMPERATURE: Battery efficiency is greatly reduced by a decreased
electrolyte temperature. Such low temperatures have a decided numbing effect on the electrochemical action. Under high discharge rates (such as crank­ing), battery voltage will drop to much lower values in cold temperatures than in warmer temperatures. The freezing point of battery electrolyte fluid is affected by the state of charge of the electrolyte as indicated below:
SSPPEECCIIFFIICC GGRRAAVVIITTYY FFRREEEEZZIINNGG PPOOIINNTT
1.220 -35° F. (-37° C.)
1.200 --20° F. (-29° C.)
1.160 0° F. (-18° C.)
ADDING WATER: Water is lost from a battery as a result of charging
and discharging and must be replaced. If the water is not replaced and the plates become exposed, they may become permanently sulfated. In addition, the plates cannot take full part in the battery action unless they are completely immersed in electrolyte. Add only DISTILLED WATER to the battery. DO NOT USE TAP WATER.
NOTE: Water cannot be added to some “mainte­nance-free” batteries.
CHECKING BATTERY STATE OF CHARGE: Use an automotive type battery hydrometer to test the
battery state of charge. Follow the hydrometer manu­facturer's instructions carefully. Generally, a battery may be considered fully charged when the specific gravity of its electrolyte is 1.260. If the hydrometer used does not have a “Percentage of Charge” scale, compare the readings obtained with the following:
SSPPEECCIIFFIICC GGRRAAVVIITTYY PPEERRCCEENNTTAAGGEE OOFF CCHHAARRGGEE
1.260 100%
1.230 75%
1.200 50%
1.170 25%
CHARGING A BATTERY: Use an automotive type battery charger to recharge a
battery. Battery fluid is an extremely corrosive, sulfu­ric acid solution that can cause severe burns. For that reason, the following precautions must be observed:
The area in which the battery is being charged must
be well ventilated. When charging a battery, an explosive gas mixture forms in each cell.
Do not smoke or break a live circuit near the top of
the battery. Sparking could cause an explosion.
Avoid spillage of battery fluid. If spillage occurs,
flush the affected area with clear water immediately.
Wear eye protection when handling a battery.
7.5 AMP FUSE
This panel-mounted Fuse protects the DC control circuit against overload and possible damage. If the Fuse has melted open due to an overload, nei­ther the priming function nor the cranking function will be available.
FUEL PRIMER SWITCH
Following generator installation and after the unit has been idle for some time, the fuel supply line may be empty. This condition will require a long cranking peri­od before fuel can reach the carburetor. The Fuel Primer Switch, when actuated to its “PRIME” position will deliver battery voltage across the closed switch contacts to the Fuel Pump (FP) to turn the Pump on. Pump action will then draw fuel from the supply tank to prime the fuel lines and carburetor.
Figure 5-5. – Primer Switch
START-STOP SWITCH
The Start-Stop Switch allows the operator to control cranking, startup and shutdown. The following wires connect to the Start-Stop Switch:
1. Wire No. 17 from the Engine Controller circuit board. This Is the CRANK and START circuit. When the Switch is set to 'START”, Wire 17 is connected to frame ground via Wire OB.
a. With wire 17 grounded, a Crank Relay on
the circuit board energizes and battery volt-
Page 25
Figure5-4
SSeeccttiioonn 55 EENNGGIINNEE DDCC CCOONNTTRROOLL SSYYSSTTEEMM
age is delivered to the Starter Contactor Relay via Wire 56.The Starter Contactor Relay energizes, its contacts close and the Starter Contactor is energized via wire 16. Its contacts close and the engine cranks.
b. With Wire 17 grounded, a Run Relay on the
circuit board energizes and battery voltage is delivered to the Wire 14 circuit. Battery voltage is delivered to the Fuel Pump, Fuel Solenoid, Choke Heater and the Remote Harness.
2.Wire 18 from the Engine Controller board. This Is the ENGINE STOP circuit. When the Start-Stop Switch is set to “STOP”, Wire 18 is connected to frame ground via Wire No. 0B. Circuit board action then opens the circuit to Wire 14, and grounds Wire 18A. Fuel flow to the carburetor and igni­tion are terminated.
3. Wire 0B connects the Switch to frame ground.
Figure 5-6. – Start-Stop Switch
STARTER CONTACTOR RELAY
& STARTER MOTOR
The positive (+) battery cable attaches to the large lug on the STARTER CONTACTOR. Wire 13 then attaches to one side of the STARTER CONTACTOR RELAY contact, from this point Wire 13 attaches to the fuse F1 to supply battery voltage to the DC con­trol system. The opposite side of the starter contactor relay contact is connected to Wire 16.
Wire 16 will supply battery power to the starter con­tactor and to the engine controller board for field flash when the starter contactor relay is energized. Attached to the starter contactor relay coil is wire 56 (positive supply during cranking) and wire 0 (ground).
When the Start-Stop switch is set to “START”, the cir­cuit board delivers battery voltage to the Starter Contactor Relay via Wire 56.The Starter Contactor Relay energizes, its contacts close and the Starter Contactor is energized via wire 16. Its contacts close and battery voltage is available to the starter motor, and the engine cranks.
Figure 5-7. – Starter Motor
Figure 5-8. – Starter Contactor Relay
Page 26
Loading...
+ 64 hidden pages