Standby Power Rating
Liquid Cooled
Gas Engine
30 kW 60 Hz
STANDARD EQUIPMENT
• All input connections in one single area
• High coolant temperature shutdown
• Low oil pressure shutdown
• Low coolant level automatic shutdown
• Overspeed automatic shutdown
• Crank timer
• Exercise timer
• Oil drain extension
• Cool flow radiator
• Closed coolant recovery system
Generator Sets
Whisper-Test™
Low Speed Exercise
62 dB(A) at 23 feet
GENERAC 1.6L ENGINE
Naturally Aspirated
Gaseous Fueled
UL 2200 Listed
Transfer Switch is sold separately
• UV/Ozone resistant hoses
• Watertight state of the art electrical connectors
• Mainline circuit breaker
• Radiator drain extension
• Battery charge alternator
• 2 Amp static battery charger
• Battery rack and battery cables
• Fan and belt guards
• Isochronous governor
• Flex fuel line pigtail
FEATURES
• Innovative design and fully prototype tested
• UL 2200 Listed
• Solid state frequency compensated
voltage regulator
• Dynamic and static battery charger
• Sound attenuated acoustically designed enclosure
Whisper-Test
•
• Acoustically designed engine cooling system
• State of the art digital control system with R-Series
digital control panel
™ for low noise level exercise
• High flow low noise factory engineered exhaust system
• Watertight electrical connectors
• Rodent proof construction
• High efficiency, low distortion Generac designed
alternator
• Vibration isolated from mounting base
• Matching Generac transfer switches engineered and
tested to work as a system
• All components easily accessible for maintenance
• Electrostatically applied powder paint
COMMERCIAL SERIES

APPLICATION & ENGINEERING DATA
COMMERCIAL 30 kW
GENERATOR SPECIFICATIONS
TYPE ...........................................................................................................Synchronous
ROTOR INSULATION .......................................................................................... Class F
STATOR INSULATION ......................................................................................... Class F
TOTAL HARMONIC DISTORTION ........................................................................... <5%
TELEPHONE INTERFERENCE FACTOR (TIF) ........................................................<50
ALTERNATOR OUTPUT LEADS 3 PHASE ........................................................... 4 wire
BEARINGS .................................................................................................... Sealed Ball
COUPLING .................................................................................................. Flexible Disc
LOAD CAPACITY (STANDBY RATING) ................................................................ 30 kW
EXCITATION SYSTEM ........................................................................................... Direct
NOTE: Generator rating and performance in accordance with
ISO8528-5, BS5514, SAE J1349, ISO3046, and DIN6271 standards.
VOLTAGE REGULATOR
TYPE ................................................................................................................Electronic
SENSING ................................................................................................... Single Phase
REGULATION .......................................................................................................... ± 1%
FEATURES ............................................................................................... V/F Adjustable
Adjustable Voltage and Gain
LED Indicators
ENGINE SPECIFICATIONS
MAKE ................................................................................................................ Generac
MODEL ................................................................................................................... In line
CYLINDERS ...................................................................................................................4
DISPLACEMENT .................................................................................................1.6 Liter
BORE ........................................................................................................................3.15
STROKE ....................................................................................................................3.13
COMPRESSION RATIO .........................................................................................9.75:1
INTAKE AIR SYSTEM ....................................................................... Naturally Aspirated
VALVE SEATS ..............................................................................................Replaceable
LIFTER TYPE .................................................................................................... Hydraulic
GOVERNOR SPECIFICATIONS
TYPE ................................................................................................................Electronic
FREQUENCY REGULATION ....................................................................... Isochronous
STEADY STATE REGULATION ..............................................................................± 0.25
ENGINE LUBRICATION SYSTEM
OIL PUMP ................................................................................................................Gear
OIL FILTER ............................................................................. Full flow spin-on cartridge
CRANKCASE CAPACITY ...................................................................................4 Quar ts
GENERATOR FEATURES
Revolving field heavy duty generator
Directly connected to the engine
Operating temperature rise 120 °C above a 40 °C ambient
Insulation is Class F rated at 130 °C rise
All models are fully prototyped tested
CONTROL PANEL FEATURES
SEVEN LED INDICATOR LIGHTS ADDITIONAL FUNCTIONS
• System ready • Utility sensing
• Low fuel pressure • Delay on utility failure for engine start
• Low battery • Engine warm-up before transfer
• Low oil pressure • Delay to retransfer to utility
• High coolant temp/low coolant temp • Engine cooldown timer
• Overspeed • Exerciser not set
• Overcrank
INTERNAL FUNCTIONS:
• 3 position switch (auto, off and manual)
• 2 wire start for any transfer switch
• Communicates with the Generac RTS transfer switch
• Built-in 7 day exerciser
• Selectable engine speed at exercise
• Governor controller is built into the master control board
• Temperature range -40 °C to 70 °C
Rating definitions - Standby: Applicable for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with
BS5514, ISO3046 and DIN6271). (All ratings in accordance with BS5514, ISO3046, ISO8528 and DIN6271).
ENGINE COOLING SYSTEM
TYPE .....................................................................................................................Closed
WATER PUMP .................................................................................................Belt driven
FAN SPEED ............................................................................................................. 2550
FAN DIAMETER ............................................................................................... 15 inches
FAN MODE ........................................................................................................... Pusher
FUEL SYSTEM
FUEL TYPE .......................................................................... Natural gas, propane vapor
CARBURETOR...............................................................................................Down Draft
SECONDARY FUEL REGULATOR ................................................................... Standard
FUEL SHUT OFF SOLENOID ..........................................................................Standard
OPERATING FUEL PRESSURE .................................................................. 5” - 14” H2O
ELECTRICAL SYSTEM
BATTERY CHARGE ALTERNATOR .............................................................12V 30 Amp
STATIC BATTERY CHARGER .............................................................................. 2 Amp
RECOMMENDED BATTERY ...........................................................Group 26, 525 CCA
SYSTEM VOLTAGE ............................................................................................. 12 Volts

COMMERCIAL 30 kW
COMMERCIAL SERIES
OPERATING DATA
COMMERCIAL 30 kW
KW RATING 30 LP / 29 NG
ENGINE SIZE 1.6 Liter 4 cyl. inline
GENERATOR OUTPUT VOLTAGE/KW - 60Hz KW AMP CB Size
120/208V, three phase, 0.8 pf 30 LP / 29 NG 104.2 LP / 100.7 NG 125
120/240V, three phase, 0.8 pf 30 LP / 29 NG 90.3 LP / 87.3 NG 100
277/480V, three phase, 0.8 pf 30 LP / 29 NG 45.1 LP / 43.6 NG 50
GENERATOR LOCKED ROTOR KVA
AVAILABLE @ VOLTAGE DIP OF 35%
208 or 240V three phase 56
480V three phase 62
ENGINE FUEL CONSUMPTION
(ft
Exercise cycle 60 0.65 24
25% of rated load 193 2.1 76
50% of rated load 300 3.3 120
75% of rated load 415 4.5 165
100% of rated load 525 5.7 209
ENGINE COOLING
Air flow
(inlet air including alternator and combustion air) ft
System coolant capacity US gal. 2.0
Heat rejection to coolant BTU/hr. 131,000
Max. operating air temp. on radiator °C (°F) 60 (150)
Max. ambient temperature °C (°F) 50 (140)
(Natural Gas) (Propane) Natural Gas Propane
3
/min. 1,800
3
/hr.) (gal/hr.) cu ft/hr
COMBUSTION AIR REQUIREMENTS
Flow at rated power 60 Hz cfm 95
SOUND EMISSIONS IN DBA
db(A) @ 23 feet in exercise mode 62
db(A) @ 23 feet at normal operating load 75
EXHAUST
Exhaust flow at rated output 60 Hz cfm 260
Exhaust temp. at muffler outlet °F 1025
ENGINE PARAMETERS
Rated synchronous RPM 60 Hz 3600
HP at rated KW 60 Hz 48
POWER ADJUSTMENT FOR AMBIENT CONDITIONS
Temperature Deration 3% for every 10 °C above - °C 25
1.65% for every 10 °F above - °F 77
Altitude Deration 1% for every 100 m above - m 183
3% for every 1000 ft. above - ft. 600
RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a
reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance
with ISO-3046-1. Design and specifications are subject to change without notice. Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient
temperature, altitude, engine power and condition, etc.

INTERCONNECTIONS
COMMERCIAL 30 kW
INSTALLATION LAYOUT
CONTROL PANEL R TYPE
BATTERY CHARGER IS
ENCLOSED WITHIN
62.2
46
DOOR TYP
AUTO
OFF
OFF
ON
SET
MANUAL
EXERCISE
TIME
OVER CRANK
OVER SPEED
LOW COOLANT LEVEL
HI COOLANT TEMPERATURE
LOW OIL PRESSURE
LOW BATTERY
LOW FUEL PRESSURE
SYSTEM READY
DANGER
FUSES
High voltage.
LOCATED
Contact with terminals
may result in personal
INSIDE
injury or death.
0F3215
VISE ACTION LATCH,
ONE PER DOOR, ONE LIFT-OFF
DOOR PER SIDE OF GENERATOR
EXHAUST AND AIR DISCHARGE
LOUVERS - FRONT AND SIDES
27.4
DOOR
TYP
6
MIN.
33.5
30 240 1 ø 150 #1 to 300 mcm
30 208 3 ø 125 #2 to 1/0
30 240 3 ø 100 #4 to 1/0
30 480 3 ø 50 #6 to 300 mcm
COMMERCIAL SERIES
29
30.7
RIGHT SIDE VIEW
FUEL LINE CONNECTION
3/4" NPT FEMALE COUPLING
CONCRETE BASE
NOT INCLUDED
FRONT VIEW
EXHAUST MUFFLERS
ENCLOSED WITHIN,
UNIT WEIGHT: Steel 935 lbs.
GENERAC® POWER SYSTEMS, INC. • P.O. BOX 297 • WHITEWATER, WI 53190
Bulletin 0174550SBY / Printed in USA 05.07
WEBSITE: www.guardiangenerators.com
© 2007 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice.