• Two Line LCD Tri-lingual
Digital Nexus™ Controller
• Isochronous Electronic Governor
• Sound Attenuated Enclosure
• Closed Coolant Recovery System
• Smart Battery Charger
• UV/Ozone Resistant Hoses
• ±1% Voltage Regulation
• Natural Gas or LP Operation
• 2 Year Limited Warranty
• UL 2200 Listed
Standby Power Rating
Model QT022 (Gray) - 22 kW 60Hz
Meets EPA Emission Regulations
CA/MA emissions Compliant
FEATURES
¡INNOVATIVE DESIGN & PROTOTYPE TESTING are key components of
GENERAC’S success in “IMPROVING POWER BY DESIGN.” But it
doesn’t stop there. Total commitment to component testing, reliability
testing, environmental testing, destruction and life testing, plus testing
to applicable CSA, NEMA, EGSA, and other standards, allows you to
choose GENERAC POWER SYSTEMS with the confidence that these
systems will provide superior performance.
¡TEST CRITERIA:
PROTOTYPE TESTED NEMA MG1-22 EVALUATION
SYSTEM TORSIONAL TESTED MOTOR STARTING ABILITY
¡SOLID-STATE, FREQUENCY COMPENSATED VOLTAGE REGULATION.
This state-of-the-art power maximizing regulation system is standard on
all Generac models. It provides optimized FAST RESPONSE to changing
load conditions and MAXIMUM MOTOR STARTING CAPABILITY
by electronically torque-matching the surge loads to the engine. An
unequalled ±1% voltage regulation.
¡SINGLE SOURCE SERVICE RESPONSE from Generac’s extensive dealer
network provides parts and service know-how for the entire unit, from the
engine to the smallest electronic component.
¡GENERAC TRANSFER SWITCHES. Long life and reliability are
synonymous with GENERAC POWER SYSTEMS. One reason for this
confidence is that the GENERAC product line includes its own transfer
systems and controls for total system compatibility.
Application & Engineering Data
QT022
GENERATOR SPECIFICATIONS
TYPESynchronous
ROTOR INSULATIONClass H
STATOR INSULATIONClass H
TELEPHONE INTERFERENCE FACTOR (TIF)<50
ALTERNATOR OUTPUT LEADS 3 PHASE4 wire
BEARINGSSealed Ball
COUPLINGFlexible Disc
LOAD CAPACITY (STANDBY RATING)22 kW
EXCITATION SYSTEMDirect
VOLTAGE REGULATION
TYPEElectronic
SENSINGSingle Phase
REGULATION± 1%
GENERATOR FEATURES
Revolving field heavy duty generator
Directly connected to the engine
Operating temperature rise 120 °C above a 40 °C ambient
Insulation is Class H rated at 150 °C rise
All models are fully prototyped tested
Ensures protection against mother nature.
Electrostatically applied textured epoxy paint for
added durability.
Quiet, critical grade muffler is mounted inside
the unit to prevent injuries.
Makes for an easy, eye appealing installation.
ENGINE SPECIFICATIONS
MAKEGenerac
MODELIn line
CYLINDERS4
DISPLACEMENT2.4 Liter
BORE3.41
STROKE3.94
COMPRESSION RATIO9.5:1
INTAKE AIR SYSTEMNaturally Aspirated
LIFTER TYPEHydraulic
GOVERNOR SPECIFICATIONS
TYPEElectronic
FREQUENCY REGULATIONIsochronous
STEADY STATE REGULATION± 0.25%
ENGINE LUBRICATION SYSTEM
OIL PUMPGear
OIL FILTERFull flow spin-on cartridge
CRANKCASE CAPACITY4 Quarts
ENGINE COOLING SYSTEM
TYPEClosed
WATER PUMPBelt driven
FAN SPEED1980
FAN DIAMETER18.1 inches
FAN MODEPusher
FUEL SYSTEM
FUEL TYPENatural gas, propane vapor
CARBURETORDown Draft
SECONDARY FUEL REGULATORStandard
FUEL SHUT OFF SOLENOIDStandard
OPERATING FUEL PRESSURE5” - 14” H
O
2
ELECTRICAL SYSTEM
BATTERY CHARGE ALTERNATOR12V 30 Amp
STATIC BATTERY CHARGER2 Amp
RECOMMENDED BATTERYGroup 26, 525CCA
SYSTEM VOLTAGE12 Volts
Rating definitions - Standby: Applicable for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. (All ratings in
accordance with BS5514, ISO3046 and DIN6271). (All ratings in accordance with BS5514, ISO3046, ISO8528, SAE J1349 and DIN6271).
Generac® QuietSource® Series Standby Generator - 22 kW
Exercise cycle
25% of rated load
50% of rated load
75% of rated load
100% of rated load*
For Btu content, multiply ft3/hr x 2520 (LP) or ft3/hr x 1000 (NG)
ENGINE COOLING
(inlet air including alternator and combustion air)ft
Air flow
System coolant capacity
Heat rejection to coolant
Max. operating air temp. on radiator
Max. ambient temperature
US gal.BTU/hr.
°C (°F)
°C (°F)
COMBUSTION AIR REQUIREMENTS
Flow at rated power 60 Hz
cfm68
SOUND EMISSIONS IN DBA
Exercising at 7 meters
Normal operation at 7 meters
3
/min.
22
22
22
Natural Gas
3
(ft
/hr.)
42
100
190
255
316
92
76
66
100
80
80
Propane
(gal/hr.)cu ft/hr
0.4416
1.140
2.175
2.8101
3.4125
2,400
3
99,000
60 (150)
50 (140)
61
70
EXHAUST
Exhaust flow at rated output 60 Hz
Exhaust temp. at muffler outlet
cfm
°F
165
900
ENGINE PARAMETERS
Rated synchronous RPM
60 Hz1800
POWER ADJUSTMENT FOR AMBIENT CONDITIONS
Temperature Deration
3% for every 10 °C above - °C
1.65% for every 10 °F above - °F
25
77
Altitude Deration
1% for every 100 m above - m
3% for every 1000 ft. above - ft.
* Refer to "Emissions Data Sheets" for maximum fuel flow for EPA and SCAQMD permitting purposes.
RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a
reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with
ISO-3046-1. Design and specifications are subject to change without notice.
KW rating is based on LPG Fuel and may derate with natural gas.
183
600
INTERCONNECTIONS
QT022
NOTE:
MATCH WIRE
NUMBERS TO
TERMINAL NUMBERS
QT SERIES ENGINE GENERATOR
CONNECTION PANEL
N1N1
T1/LINE
N2
NEU
ON
T1
N2
23
194
178
194
183
23
E1
E2
NEUT
0
GROUND
UTILITY SUPPLY FROM
SERVICE DISCONNECT
CUSTOMER SUPPLIED
NEUTRAL WIRE
LOAD SHED
MODULE
NEUTRAL BLOCK
GROUND
CUSTOMER CONNECTIONS
0
DC COMMON
194
23
TRANSFER
NEUTRAL BLOCK
RTS TRANSFER SWITCH
0 GROUND
15B +12V
T1
23 TRANSFER
NEUTRAL
AIR 1
CONTACTOR
1
AIR 2
CONTACTOR
2
PRIORITY 1
CONTACTOR
3
PRIORITY 2
PRIORITY 3
0
194
+12VDC
23
WARNING
NOTE WIRE ORIENTATION
CONTACTOR
4
PRIORITY 4
48850-T
(C1 & VR1)
(C2 & VR2)
T1N1 N2
UTILITY
STANDBY
0C4449A-T
N2
N1
N1
N2
E1
E2
T1
T2
T2
E1
E2
T1
NOTE:
POWER LEADS AND TRANSFER SWITCH LEADS
TO BE RUN IN TWO DIFFERENT CONDUITS.
CUSTOMER LOAD
(DISTRIBUTION PANEL)
LIQUID-COOLED INSTALLATION
NEXUS™ CONTROL FEATURES
2-Line Plain Text LCD DisplaySimple user interface for ease of operation
Mode Switch
-Auto Automatic Start on Utility failure. 7 day exerciser
-OffStops unit. Power is removed. Control and charger still operate.
-Manual/Test (start)Start with starter control, unit stays on. If utility fails, transfer to load takes place.
Programmable start delay between 10-30 secondsStandard
Engine Start SequenceCyclic cranking: 16 sec. on, 7 rest (90 sec. maximum duration)
Engine Warm-up5 seconds
Engine Cool-Down1 minute
Starter Lock-outStarter cannot re-engage until 5 sec. after engine has stopped.
Smart Battery ChargerStandard
Automatic Voltage Regulation with Over and Under Voltage ProtectionStandard
Automatic Low Oil Pressure ShutdownStandard
Overspeed ShutdownStandard, 72Hz
High Temperature ShutdownStandard
Overcrank ProtectionStandard
Safety FusedStandard
Failure to Transfer ProtectionStandard
Low Battery ProtectionStandard
50 Event Run LogStandard
Future Set Capable ExerciserStandard
Incorrect Wiring ProtectionStandard
Internal Fault ProtectionStandard
Common External Fault CapabilityStandard
Governor Failure ProtectionStandard
*Single and three phase connections may vary, refer to the owner’s manual for specific connection information.
INSTALLATION LAYOUT QT022
AVAILABLE ACCESSORIES
®
Model #ProductDescription
If the temperature regularly falls below 32° F, install a cold weather kit to maintain
5630Cold Weather Kit
optimal battery temperature. Kit consists of battery warmer with thermostat built into
the wrap.
QT022
5621
5616Extreme Cold Weather Kit
5651Base Plug KitAdd base plugs to the base of the generator to keep out debris.
5704Paint KitMedium Grey Kit
5656Scheduled Maintenance Kit
5928Nexus Wireless Remote
5951
Auxiliary Transfer Switch
Contact Kit
Advanced Nexus Wireless
Remote
The auxiliary transfer switch contact kit allows the transfer switch to lock out a single
large electrical load you may not need.
Recommended where the temperature regularly falls below 32° F for extended periods
of time. For liquid cooled units only.
The Liquid-Cooled Scheduled Maintenance Kits offer all the hardware necessary to
perform a complete maintenance on Generac liquidcooled generators.
Completely wireless and battery powered, Generac's Nexus wireless remote monitor
provides you with instant status information without ever leaving the house.
Remotely control generator functions with the advanced model's LCD display. In
addition to remote testing of the generator, set the excercise cycle and maintenance
interval reminders.
5937
DLM Load Control Module
(50 Amps)
Generac Power Systems, Inc. • S45 W29290 HWY. 59, Waukesha, WI 53189 • generac.com
DLM Modules are used in conjunction with the Nexus Smart Switch to increase
its load management capabilities. It gives the Nexus Smart Switch additional load
management flexibility not found in any other transfer switch.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.