Generac QT022 User Manual

GENERAC® QUIETSOURCE® SERIES
STANDBY GENERATORS
22 kW
Liquid-Cooled Engine Generator Sets
Includes:
• Generac Naturally Aspirated Gaseous Fueled 2.4L Engine
• Two Line LCD Tri-lingual Digital Nexus™ Controller
• Isochronous Electronic Governor
• Sound Attenuated Enclosure
• Closed Coolant Recovery System
• Smart Battery Charger
• UV/Ozone Resistant Hoses
• ±1% Voltage Regulation
• Natural Gas or LP Operation
• 2 Year Limited Warranty
• UL 2200 Listed
Standby Power Rating
Model QT022 (Gray) - 22 kW 60Hz
Meets EPA Emission Regulations
CA/MA emissions Compliant
FEATURES
¡ INNOVATIVE DESIGN & PROTOTYPE TESTING are key components of
GENERAC’S success in “IMPROVING POWER BY DESIGN.” But it doesn’t stop there. Total commitment to component testing, reliability testing, environmental testing, destruction and life testing, plus testing to applicable CSA, NEMA, EGSA, and other standards, allows you to choose GENERAC POWER SYSTEMS with the confidence that these systems will provide superior performance.
PROTOTYPE TESTED NEMA MG1-22 EVALUATION
SYSTEM TORSIONAL TESTED MOTOR STARTING ABILITY
¡ SOLID-STATE, FREQUENCY COMPENSATED VOLTAGE REGULATION.
This state-of-the-art power maximizing regulation system is standard on all Generac models. It provides optimized FAST RESPONSE to changing load conditions and MAXIMUM MOTOR STARTING CAPABILITY by electronically torque-matching the surge loads to the engine. An unequalled ±1% voltage regulation.
¡ SINGLE SOURCE SERVICE RESPONSE from Generac’s extensive dealer
network provides parts and service know-how for the entire unit, from the engine to the smallest electronic component.
¡ GENERAC TRANSFER SWITCHES. Long life and reliability are
synonymous with GENERAC POWER SYSTEMS. One reason for this confidence is that the GENERAC product line includes its own transfer systems and controls for total system compatibility.
Application & Engineering Data
QT022
GENERATOR SPECIFICATIONS
TYPE Synchronous
ROTOR INSULATION Class H
STATOR INSULATION Class H
TELEPHONE INTERFERENCE FACTOR (TIF) <50
ALTERNATOR OUTPUT LEADS 3 PHASE 4 wire
BEARINGS Sealed Ball
COUPLING Flexible Disc
LOAD CAPACITY (STANDBY RATING) 22 kW
EXCITATION SYSTEM Direct
VOLTAGE REGULATION
TYPE Electronic
SENSING Single Phase
REGULATION ± 1%
GENERATOR FEATURES
Revolving field heavy duty generator Directly connected to the engine Operating temperature rise 120 °C above a 40 °C ambient Insulation is Class H rated at 150 °C rise All models are fully prototyped tested
ENCLOSURE FEATURES
Aluminum weather
protective enclosure
Enclosed critical grade
muffler
Small, compact,
attractive
SAE Sound attenuated enclosure ensures quiet operation.
Ensures protection against mother nature. Electrostatically applied textured epoxy paint for added durability.
Quiet, critical grade muffler is mounted inside the unit to prevent injuries.
Makes for an easy, eye appealing installation.
ENGINE SPECIFICATIONS
MAKE Generac
MODEL In line
CYLINDERS 4
DISPLACEMENT 2.4 Liter
BORE 3.41
STROKE 3.94
COMPRESSION RATIO 9.5:1
INTAKE AIR SYSTEM Naturally Aspirated
LIFTER TYPE Hydraulic
GOVERNOR SPECIFICATIONS
TYPE Electronic
FREQUENCY REGULATION Isochronous
STEADY STATE REGULATION ± 0.25%
ENGINE LUBRICATION SYSTEM
OIL PUMP Gear
OIL FILTER Full flow spin-on cartridge
CRANKCASE CAPACITY 4 Quarts
ENGINE COOLING SYSTEM
TYPE Closed
WATER PUMP Belt driven
FAN SPEED 1980
FAN DIAMETER 18.1 inches
FAN MODE Pusher
FUEL SYSTEM
FUEL TYPE Natural gas, propane vapor
CARBURETOR Down Draft
SECONDARY FUEL REGULATOR Standard
FUEL SHUT OFF SOLENOID Standard
OPERATING FUEL PRESSURE 5” - 14” H
O
2
ELECTRICAL SYSTEM
BATTERY CHARGE ALTERNATOR 12V 30 Amp
STATIC BATTERY CHARGER 2 Amp
RECOMMENDED BATTERY Group 26, 525CCA
SYSTEM VOLTAGE 12 Volts
Rating definitions - Standby: Applicable for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with BS5514, ISO3046 and DIN6271). (All ratings in accordance with BS5514, ISO3046, ISO8528, SAE J1349 and DIN6271).
Generac® QuietSource® Series Standby Generator - 22 kW
®
OPERATING DATA
KW RATING (LP/NG) 22/22
ENGINE SIZE 2.4 Liter Inline 4
GENERATOR OUTPUT VOLTAGE/KW - 60Hz KW AMP CB Size
120/240V, 1-phase, 1.0 pf 120/208V, 3-phase, 0.8 pf 120/240V, 3-phase, 0.8 pf
ENGINE FUEL CONSUMPTION
(Natural Gas) (Propane)
Exercise cycle 25% of rated load 50% of rated load 75% of rated load 100% of rated load*
For Btu content, multiply ft3/hr x 2520 (LP) or ft3/hr x 1000 (NG)
ENGINE COOLING
(inlet air including alternator and combustion air) ft
Air flow System coolant capacity Heat rejection to coolant Max. operating air temp. on radiator Max. ambient temperature
US gal. BTU/hr.
°C (°F)
°C (°F)
COMBUSTION AIR REQUIREMENTS
Flow at rated power 60 Hz
cfm 68
SOUND EMISSIONS IN DBA
Exercising at 7 meters Normal operation at 7 meters
3
/min.
22 22 22
Natural Gas
3
(ft
/hr.)
42 100 190 255 316
92 76 66
100
80 80
Propane
(gal/hr.) cu ft/hr
0.44 16
1.1 40
2.1 75
2.8 101
3.4 125
2,400
3
99,000 60 (150) 50 (140)
61 70
EXHAUST
Exhaust flow at rated output 60 Hz Exhaust temp. at muffler outlet
cfm
°F
165 900
ENGINE PARAMETERS
Rated synchronous RPM
60 Hz 1800
POWER ADJUSTMENT FOR AMBIENT CONDITIONS
Temperature Deration
3% for every 10 °C above - °C
1.65% for every 10 °F above - °F
25 77
Altitude Deration
1% for every 100 m above - m
3% for every 1000 ft. above - ft.
* Refer to "Emissions Data Sheets" for maximum fuel flow for EPA and SCAQMD permitting purposes.
RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without notice. KW rating is based on LPG Fuel and may derate with natural gas.
183 600
INTERCONNECTIONS
QT022
NOTE:
MATCH WIRE NUMBERS TO TERMINAL NUMBERS
QT SERIES ENGINE GENERATOR
CONNECTION PANEL
N1N1
T1/LINE
N2
NEU
ON
T1
N2
23
194
178
194
183
23
E1
E2
NEUT
0
GROUND
UTILITY SUPPLY FROM
SERVICE DISCONNECT
CUSTOMER SUPPLIED NEUTRAL WIRE
LOAD SHED
MODULE
NEUTRAL BLOCK
GROUND
CUSTOMER CONNECTIONS
0
DC COMMON
194
23
TRANSFER
NEUTRAL BLOCK
RTS TRANSFER SWITCH
0 GROUND
15B +12V
T1
23 TRANSFER
NEUTRAL
AIR 1
CONTACTOR
1
AIR 2
CONTACTOR
2
PRIORITY 1
CONTACTOR
3
PRIORITY 2
PRIORITY 3
0
194
+12VDC
23
WARNING
NOTE WIRE ORIENTATION
CONTACTOR
4
PRIORITY 4
48850-T
(C1 & VR1)
(C2 & VR2)
T1N1 N2
UTILITY
STANDBY
0C4449A-T
N2
N1
N1
N2
E1
E2
T1
T2
T2
E1
E2
T1
NOTE: POWER LEADS AND TRANSFER SWITCH LEADS TO BE RUN IN TWO DIFFERENT CONDUITS.
CUSTOMER LOAD
(DISTRIBUTION PANEL)
LIQUID-COOLED INSTALLATION
NEXUS™ CONTROL FEATURES
2-Line Plain Text LCD Display Simple user interface for ease of operation Mode Switch
-Auto Automatic Start on Utility failure. 7 day exerciser
-Off Stops unit. Power is removed. Control and charger still operate.
-Manual/Test (start) Start with starter control, unit stays on. If utility fails, transfer to load takes place. Programmable start delay between 10-30 seconds Standard Engine Start Sequence Cyclic cranking: 16 sec. on, 7 rest (90 sec. maximum duration) Engine Warm-up 5 seconds Engine Cool-Down 1 minute Starter Lock-out Starter cannot re-engage until 5 sec. after engine has stopped. Smart Battery Charger Standard Automatic Voltage Regulation with Over and Under Voltage Protection Standard Automatic Low Oil Pressure Shutdown Standard Overspeed Shutdown Standard, 72Hz High Temperature Shutdown Standard Overcrank Protection Standard Safety Fused Standard Failure to Transfer Protection Standard Low Battery Protection Standard 50 Event Run Log Standard Future Set Capable Exerciser Standard Incorrect Wiring Protection Standard Internal Fault Protection Standard Common External Fault Capability Standard Governor Failure Protection Standard
*Single and three phase connections may vary, refer to the owner’s manual for specific connection information.
INSTALLATION LAYOUT QT022
AVAILABLE ACCESSORIES
®
Model # Product Description
If the temperature regularly falls below 32° F, install a cold weather kit to maintain
5630 Cold Weather Kit
optimal battery temperature. Kit consists of battery warmer with thermostat built into the wrap.
QT022
5621
5616 Extreme Cold Weather Kit
5651 Base Plug Kit Add base plugs to the base of the generator to keep out debris.
5704 Paint Kit Medium Grey Kit
5656 Scheduled Maintenance Kit
5928 Nexus Wireless Remote
5951
Auxiliary Transfer Switch Contact Kit
Advanced Nexus Wireless Remote
The auxiliary transfer switch contact kit allows the transfer switch to lock out a single large electrical load you may not need.
Recommended where the temperature regularly falls below 32° F for extended periods of time. For liquid cooled units only.
The Liquid-Cooled Scheduled Maintenance Kits offer all the hardware necessary to perform a complete maintenance on Generac liquidcooled generators.
Completely wireless and battery powered, Generac's Nexus wireless remote monitor provides you with instant status information without ever leaving the house.
Remotely control generator functions with the advanced model's LCD display. In addition to remote testing of the generator, set the excercise cycle and maintenance interval reminders.
5937
DLM Load Control Module (50 Amps)
Generac Power Systems, Inc. • S45 W29290 HWY. 59, Waukesha, WI 53189 • generac.com
©2012 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Bulletin 0187710SBY-H / Printed in U.S.A. 06/28/12
DLM Modules are used in conjunction with the Nexus Smart Switch to increase its load management capabilities. It gives the Nexus Smart Switch additional load management flexibility not found in any other transfer switch.
Loading...