Generac 005308-0 User Manual

Owner’s Manual
• SAFETY
• ASSEMBLY
• OPERATION
• TROUBLESHOOTING
• ELECTRICAL DATA
• PARTS
1-800-333-1322
Portable Generator
COMMERCIAL • INDUSTRIAL • RESIDENTIAL
MODEL: 005308-0
17,500 Watt Portable Generator
and 60 amp manual transfer switch
with built-in load center
AUTHORIZED DEALER SUPPORT:
Table of Contents
Residential Portable Generator System
Safety Rules ..........................................1-3
Section 1 – General Information ....................4
1.1 Unpacking ....................................................................4
1.1.1 Accessory Box..................................................4
1.2 Assembly ......................................................................4
1.2.1 Assembling the Wheel Kit ................................4
1.2.2 Assembling the Handle ....................................5
1.2.3 Battery Connection ..........................................5
Section 2 – Operation ................................6
2.1 Know The Generator ....................................................6
2.2 Cord Sets and Connector Plugs....................................7
2.2.1 120V AC, 20 A, Duplex Receptacle ..................7
2.2.2 120V AC, 20 A, GFCI Receptacle ......................7
2.2.3 120V AC, 30 A Receptacle ............................7-8
2.2.4 120/240V AC, 30 A, Receptacle........................8
2.2.5 12 VDC, 10 Amp Receptacle ............................8
2.2.6 120/240V AC, 50 A, Receptacle........................8
2.3 How To Use The Generator ..........................................9
2.3.1 Grounding The Generator ................................9
2.3.2 Connecting Electric Loads ................................9
2.4 Don’t Overload The Generator ......................................9
2.5 Wattage Reference Chart ............................................10
2.6 Before Starting The Generator ....................................10
2.6.1 Adding Engine Oil ..........................................10
2.6.2 Adding Gasoline ............................................11
2.7 To Start The Engine ....................................................11
2.8 Stopping The Engine ..................................................12
2.9 Automatic Idle Control ................................................12
2.10 Cold Weather Operation/De-Icer ................................12
2.11 Low Oil Pressure Shutdown........................................12
2.11.1 Initial Start-up ................................................12
2.11.2 Sensing Low Oil Pressure ..............................12
2.11.3 Restarting ......................................................12
2.12 Charging a Battery ......................................................13
Section 3 – Maintenance ............................14
3.1 Maintenance Schedule ................................................14
3.2 Product Specifications ................................................14
3.2.1 Generator Specifications ................................14
3.2.2 Engine Specifications ....................................14
3.3 General Recommendations ........................................15
3.3.1 General Maintenance ......................................15
3.3.2 To Clean The Generator ..................................15
3.3.3 Engine Maintenance ......................................15
3.3.4 Checking Oil Level ..........................................15
3.3.5 Changing The Oil & Oil Filter ..........................15
3.3.6 Replacing The Spark Plug .............................16
3.4 Service Air Cleaner......................................................16
3.5 Clean Spark Arrestor Screen ......................................16
3.6 Adjusting Valve Clearance ..........................................17
3.7 General ......................................................................18
3.8 Long Term Storage ....................................................18
3.9 Other Storage Tips......................................................18
Section 4 – Troubleshooting ........................19
4.1 Troubleshooting Guide ................................................19
Section 5 – Installation Guide For
Manual Transfer Switch ........20-23
Section 6 – Operation Of Generator With
Manual Transfer Switch ........24-26
Section 7 – Notes ....................................27
Section 9 – Electrical Data......................28-31
Section 9 – Exploded Views and
Parts Lists ..........................32-43
Section 10 – Warranty ..........................44-46
INTRODUCTION
Thank you for purchasing this model of portable generator by Generac Power Systems, Inc. This model is a compact, high performance, air-cooled, engine driven generator designed to supply electrical power to operate electrical loads when utility power is unavailable due to a power outage.
READ THIS MANUAL THOROUGHLY
If you do not understand any portion of this manual, contact your nearest GENERAC®Authorized Dealer for starting, operating and servicing procedures.
Throughout this publication, and on tags and decals affixed to the generator, DANGER, WARNING, CAUTION and NOTE blocks are used to alert you to special instruction about a particular operation that may be hazardous if performed incorrectly or carelessly. Observe them carefully. Their definitions are as follows:
After this heading, you can read instructions that, if not strictly complied with, will result in serious personal injury, severe property damage and/or including without limitation, death.
After this heading, you can read instructions that, if not strictly complied with, may result in serious personal injury and/or property damage.
After this heading, you can read instructions that, if not strictly complied with, could result in damage to equipment and/or property.
NOTE: After this heading, you can read explanatory statements
that require special emphasis. These safety warnings cannot eliminate the hazards that they indicate. Common sense and strict compliance with the special instructions while performing the service are essential to preventing accidents.
Four commonly used safety symbols accompany the DANGER, WARNING and CAUTION blocks. The type of information each indicates follows:
This symbol points out important safety
information that, if not followed, could endanger personal safety and/or property of you and others.
This symbol points out potential explosion hazard.This symbol points out potential fire hazard.This symbol points out potential electrical shock hazard.
The operator is responsible for proper and safe use of the equipment. We strongly recommend that the operator read this
“Owner’s Manual”
and thoroughly understand all instructions
before using this equipment.
We also strongly recommend instructing other users to properly start and operate the unit. This prepares them if they need to operate the equipment in an emergency.
CAUTION! Always disconnect spark plug wire and place the wire
where it cannot contact the spark plug to prevent accidental starting when setting up, transporting, adjusting or making repairs to your generator.
• The generator produces dangerously high voltage that can cause extremely hazardous electrical shock. Avoid contact with bare wires, terminals, etc. Never permit any unqualified person to operate or service the generator.
• Never handle any kind of electrical cord or device while standing in water, while barefoot or while hands or feet are wet. Dangerous electrical shock will result.
• The National Electric Code requires the frame and external electrically conductive parts of the generator be properly connected to an approved earth ground. Local electrical codes may also require proper grounding of the generator. Consult with a local electrician for grounding requirements in your area.
• Use a ground fault circuit interrupter in any damp or highly conductive area (such as metal decking or steel work).
• Do not use worn, bare, frayed or otherwise damaged electrical cord sets with the generator.
• Operate generator only on level surfaces and where it will not be exposed to excessive moisture, dirt, dust or corrosive vapors.
• Gasoline is highly FLAMMABLE and its vapors are EXPLOSIVE. Do not permit smoking, open flames, sparks or heat in the vicinity while handling gasoline. Avoid spilling gasoline on a hot engine. Comply with all laws regulating storage and handling of gasoline.
• Never add fuel while unit is running.
• Do not overfill the fuel tank. Always allow room for fuel expansion. If tank is over-filled, fuel can overflow onto a hot engine and cause FIRE or an EXPLOSION.
• Never store generator with fuel in tank where gasoline vapors might reach an open flame, spark or pilot light (as on a furnace, water heater or clothes dryer). FIRE or EXPLOSION may result.
• Generator exhaust gases contain DEADLY carbon monoxide gas.This dangerous gas, if breathed in sufficient concentrations, can cause unconsciousness or even death. Operate this equipment only in the open air where adequate ventilation is available.
• Allow at least 2 feet of clearance on all sides of generator or you could damage the unit. Never operate the unit inside any
room or enclosure where the free flow of cooling air into and out of the unit might be obstructed. Review “Cold Weather
Operation” on page 12.
NEVER operate your generator indoors, in an attached garage or near an open window.
1
-------------
DANGER
-------------
-------------
WARNING
-------------
-------------
CAUTION
-------------
-------------
DANGER
-------------
2
• Never start or stop the unit with electrical loads connected to receptacles AND with connected devices turned ON. Start the engine and let it stabilize before connecting electrical loads. Disconnect all electrical loads before shutting down the generator.
• Do not insert objects through unit's cooling slots.
• Never operate generator: in rain; indoors or in any enclosed compartment; if connected electrical devices overheat; if electrical output is lost; if engine or generator sparks; if flames or smoke are observed while unit is running; if unit vibrates excessively.
Note: Your generator is equipped with a spark arrestor muffler. The spark arrestor must be maintained in effective working order by the owner/ operator. In the State of California, a spark arrestor is required by law (Section 4442 of the California Public Resources Code). Other states may have similar laws. Federal laws apply on federal lands.
Study these SAFETY RULES carefully before installing, operating or servicing this equipment. Become familiar with this
Owner’s
Manual
and with the unit. The generator can operate safely, efficiently and reliably only if it is properly installed, operated and maintained. Many accidents are caused by failing to follow simple and fundamental rules or precautions.
GENERAC
®
cannot possibly anticipate every possible circumstance that might involve a hazard. The warnings in this manual, and on tags and decals affixed to the unit are, therefore, not all-inclusive. If you use a procedure, work method or operating technique GENERAC
®
does not specifically recommend, you must satisfy yourself that it is safe for you and others. You also must make sure the procedure, work method or operating technique that you choose does not render the generator unsafe.
Despite the safe design of this generator, operating this
equipment imprudently, neglecting its maintenance or being careless can cause possible injury or death. Permit only responsible and capable persons to operate or maintain this equipment.
Potentially lethal voltages are generated by these
machines. Ensure all steps are taken to render the machine safe before attempting to work on the generator.
Parts of the generator are rotating and/or hot during
operation. Exercise care near running generators.
GENERAL HAZARDS
Never operate in an enclosed area or indoors.
• For safety reasons, GENERAC®recommends that the maintenance of this equipment is carried out by a GENERAC
®
Authorized Dealer.
• The engine exhaust fumes contain carbon monoxide, which can be DEADLY. This dangerous gas, if breathed in sufficient concentrations, can cause unconsciousness or even death. This exhaust system must be properly maintained. You must do nothing that might render the exhaust system unsafe or in noncompliance with any local codes and/or standards.
• Keep hands, feet, clothing, etc., away from drive belts, fans, and other moving or hot parts. Never remove any drive belt or fan guard while the unit is operating.
• Adequate, unobstructed flow of cooling and ventilating air is critical to correct generator operation. Do not alter the installation or permit even partial blockage of ventilation provisions, as this can seriously affect safe operation of the generator. The generator MUST be operated outdoors.
• When working on this equipment, remain alert at all times. Never work on the equipment when you are physically or mentally fatigued.
• Inspect the generator regularly, and contact your nearest GENERAC
®
Authorized Dealer for parts needing repair or
replacement.
• Before performing any maintenance on the generator, disconnect its battery cables to prevent accidental start up. Disconnect the cable from the battery post indicated by a NEGATIVE, NEG or (–) first. Reconnect that cable last.
• Never use the generator or any of its parts as a step. Stepping on the unit can stress and break parts, and may result in dangerous operating conditions from leaking exhaust gases, fuel leakage, oil leakage, etc.
IMPORTANT SAFETY INSTRUCTIONS
Residential Portable Generator System
SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe operation be copied and posted near the unit's installation site. Safety should be stressed to all operators and potential operators of this equipment.
The engine exhaust from this product
contains chemicals known to the state
of California to cause cancer, birth
defects or other reproductive harm.
WARNING:
This product contains or emits chemicals
known to the state of California to cause
cancer, birth defects or other reproductive harm.
WARNING:
-------------
DANGER
-------------
ELECTRICAL HAZARDS
• All generators covered by this manual produce dangerous electrical voltages and can cause fatal electrical shock. Utility power delivers extremely high and dangerous voltages as does the generator when it is in operation. Avoid contact with bare wires, terminals, connections, etc., while the unit is running. Ensure all appropriate covers, guards and barriers are in place before operating the generator. If you must work around an operating unit, stand on an insulated, dry surface to reduce shock hazard.
• Do not handle any kind of electrical device while standing in
water, while barefoot, or while hands or feet are wet.
DANGEROUS ELECTRICAL SHOCK MAY RESULT.
• The National Electrical Code (NEC) requires the frame and
external electrically conductive parts of the generator to be connected to an approved earth ground. Local electrical codes also may require proper grounding of the generator electrical system.
• In case of accident caused by electric shock, immediately shut
down the source of electrical power. If this is not possible, attempt to free the victim from the live conductor. AVOID DIRECT CONTACT WITH THE VICTIM. Use a non-conducting implement, such as a rope or board, to free the victim from the live conductor. If the victim is unconscious, apply first aid and get immediate medical help.
• Never wear jewelry when working on this equipment. Jewelry
can conduct electricity resulting in electric shock, or may get caught in moving components causing injury.
FIRE HAZARDS
• For fire safety, the generator must be operated and maintained
properly. Operation always must comply with applicable codes, standards, laws and regulations. Adhere strictly to local, state and national electrical and building codes. Comply with regulations the Occupational Safety and Health Administration (OSHA) has established. Also, ensure that the generator is operated in accordance with the manufacturer’s instructions and recommendations. Do not alter the construction of generator or change controls which might create an unsafe operating condition.
• Keep a fire extinguisher near the generator at all times.
Extinguishers rated “ABC” by the National Fire Protection Association are appropriate for use on the standby electric system. Keep the extinguisher properly charged and be familiar with its use. If you have any question pertaining to fire extinguishers, consult your local fire department.
EXPLOSION HAZARDS
• Do not smoke around the generator. Wipe up any fuel or oil spills immediately. Ensure that no combustible materials are left on or near the generator, as FIRE or EXPLOSION may result. Keep the area surrounding the generator clean and free from debris.
• Gasoline is extremely EXPLOSIVE.
STANDARDS INDEX
In the absence of pertinent standards, codes, regulations and laws, the published information listed below may be used as a guideline for operation of this equipment. Always reference the latest revision available for the standards listed.
1. NFPA No. 70, NFPA HANDBOOK OF NATIONAL ELECTRIC CODE.
2. Article X, NATIONAL BUILDING CODE, available from the American Insurance Association, 85 John Street, New York, N.Y. 10038.
3. AGRICULTURAL WIRING HANDBOOK, available from the Food and Energy Council, 909 University Avenue, Columbia, MO
65201.
4. ASAE EP-3634, INSTALLATION AND MAINTENANCE OF FARM STANDBY ELECTRICAL SYSTEMS, available from the American Society of Agricultural Engineers, 2950 Niles Road, St. Joseph, MI 49085.
5. NFPA No. 30, FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE.
3
IMPORTANT SAFETY INSTRUCTIONS
Residential Portable Generator System
1.1 UNPACKING
• Set the palleted carton on a rigid flat surface.
• Remove staples along bottom of carton that fasten carton to pallet. Open carton from top.
• Remove all packaging material.
• Remove separate accessory box.
• Lift carton off the generator.
• Remove generator from shipping pallet by removing bolts through the shipping brackets.
Figure 1 - Bracket Removal
1.1.1 ACCESSORY BOX
Check all contents. If any parts are missing or damaged locate an authorized dealer at 1-800-333-1322.
Contents include:
• Wheel Axle Bolt-on tubular handle
• 2 – Washers 2 – Pneumatic Wheels
• 2 – Wheel Spacers 2 – Axle Bracket Assemblies
• 2 – Cotter Pins Bolt-on Foot
• Battery Charge Cable Spark Plug Wrench •
• Air Filter Oil Filter
• Pre-cleaner 2 – Quarts Oil
• 26 Wire Nuts 6 – Carriage Bolts, Washers,
Nuts
1.2 ASSEMBLY
The generator requires some assembly prior to using it. If problems arise when assembling the generator, please call the Generator Helpline at 1-800-333-1322.
1.2.1 ASSEMBLING THE WHEEL KIT
The wheel kit is designed to greatly improve the portability of the generator. A socket wrench with a 9/16” socket, a 1/2” socket, a 1/2” wrench and a pair of pliers are the tools that will be needed for assembly of the wheel kit.
Note: The wheel kit is not intended for over-the-road use.
• Refer to
Figure 2
shown on opposite page and install the wheel
kit as follows:
• Place the generator on a hard flat surface.
• Stand at the engine end of the unit and gently tilt the generator forward, high enough to place wooden blocks beneath the cradle. This will allow space to install the wheel assemblies.
• Attach an axle bracket assembly with attached sleeve to either side of the frame. Ensure the sleeve faces outward.
• Slide the axle through the sleeves on the axle brackets.
• Slide one wheel with flat washer to the outside and a spacer to the inside onto each end of the axle. Make sure the air inflation valve on the wheel is facing outward.
• Insert retaining pins and using pliers, bend out the ends to prevent the pins from falling out of the axle. Remove the wooden blocks.
1.2.2 ASSEMBLING THE HANDLE
• Attach the handle by aligning one side of the handle on the cradle, then spread the handle around the cradle and let it spring into place. Secure the handle to the frame using the 5/16’ hex head bolts provided. Check each fastener to ensure that it is secure.
• Using the handle, lift the unit high enough to place wooden blocks under the unit. Attach the front support foot to the underside of the cradle using the 3/8” carriage bolts provided.
• Remove the shipping brackets from the cradle, if you have not already done so.
4
Section 1 – General Information
Residential Portable Generator System
Shipping
Bracket (x4)
5
1.2.3 BATTERY CONNECTION
• The battery shipped with the generator has been provided fully charged. Caution must be taken when connecting the battery.
• Cut the tie wrap cable holding the RED and BLACK battery cables to the stator.
• Connect the RED battery cable to the battery Positive terminal (+). After making sure that the connection is tight, slip the rubber boot over the terminal connection.
• Connect the BLACK battery cable to the battery Negative terminal (–). Make sure the connection is tight.
• Double check all connections to ensure they are in the correct location and secure. See
Figure 3
at right.
Figure 3 - Battery Connections
Section 1 - General Information
Residential Portable Generator System
Negative
Cable
Positive
Cable
Figure 2 - Handle Assembly
6
Section 2 – Operation
Residential Portable Generator System
OPERATION
2.1 KNOW THE GENERATOR
Read the
Owner’s Manual
and
Safety Rules
before operating
this generator.
Compare the generator to this illustration to become familiarized with the locations of various controls and adjustments. Save this manual for future reference.
1) 12 Volt DC, 10 Amp Receptacle – This receptacle allows the
capability to recharge a 12 volt DC storage battery with provided battery charge cables.
2) 120 Volt AC, 20 Amp, Duplex Receptacle – Supplies
electrical power for the operation of 120 Volt AC, 20 Amp, single-phase, 60 Hz electrical lighting, appliance, tool and motor loads.
3) 120 Volt AC, 20A Duplex GFCI Receptacle
Supplies ground fault protected electrical power for operation of 120 volt AC 20 amp, single-phase, 60 Hz electric lighting, appliances, tools and motor loads.
4) 120 Volt AC, 30 Amp Locking Receptacle – Supplies
electrical power for the operation of 120 Volt AC, 30 Amp, single-phase, 60 Hz electrical lighting, appliance, tool and motor loads.
5) 120/240 Volt AC, 30 Amp Locking Receptacle – Supplies
electrical power for the operation of 120 and/or 240 Volt AC, 30 Amp, single-phase, 60 Hz, electrical lighting, appliance, tool and motor loads.
6) 120/240 Volt AC, 50 Amp Receptacle (Located on underside of control panel)– Supplies electrical power for
the operation of 120/240 Volt AC, 50 Amp, single-phase, 60 Hz, welder or motor loads.
7) Air Cleaner – Filters intake air as it is drawn into the engine.
8) Choke Knob – Used when starting a cold engine.
9) Winter / Summer Valve – See “Cold Weather Operation.”
(Section 2, page 12.)
10) Circuit Breakers (AC) – Each receptacle is provided with a push-to-reset circuit breaker to protect the generator against electrical overload. (50 amp uses toggle reset)
11) Fuel Tank – Tank holds 16 U.S. gallons of fuel.
12) Grounding Lug – Ground the generator to an approved earth
ground here. See page 9 for details.
13) Idle Control Switch – The idle control runs the engine at normal (high) speeds when there is an electrical load present and runs the engine at idle (low) speeds when a load is not present.
7
11
12
15
9
8
14
Figure 5 - Generator Controls
Figure 6 - Engine Control Panel
Figure 4 - Control Panel
14) Start/Run/Stop Switch – Controls the operation of the
generator.
15) Oil Fill – Use this point to add oil to engine.
16) Fuse - 10 Amp (Located at rear of control panel) – Protects
the DC control circuit from overload. If this fuse element has melted open the engine will not be able to crank and start.
2.2 CORD SETS AND CONNECTION PLUGS
2.2.1 AC, 20 AMP, DUPLEX RECEPTACLE
This is a 120 Volt outlet protected against overload by a 20 Amp push-to-reset circuit breaker. Use each socket to power 120 Volt AC, single phase, 60 Hz electrical loads requiring up to a combined 2400 watts (2.4 kW) or 20 Amps of current. Use only high quality, well­insulated, 3-wire grounded cord sets rated for 125 Volts at 20 Amps (or greater).
Keep extension cords as short as possible, preferably less than 15 feet long, to prevent voltage drop and possible overheating of wires.
Figure 7 - 120 Volt AC, 20 Amp, Duplex Receptacle
2.2.2 120V AC, 20 AMP, GFCI RECEPTACLE
This unit is equipped with a ground fault circuit interrupter (GFCI). This device meets applicable federal, state and local codes.
A GFCI receptacle is different from conventional receptacles. In the event of a ground fault, a GFCI will trip and quickly stop the flow of electricity to prevent serious injury.
Definition: Instead of following its normal safe path, electricity passes through a persons body to reach the ground. For example, a defective appliance can cause a ground fault.
A GFCI receptacle does NOT
protect against circuit overloads, short circuits, or shocks. For example, electric shock can still occur if a person touches charged electrical wires while standing on a non-conducting surface, such as a wood floor.
Figure 8 - 120 VAC, 20 Amp GFCI Receptacle
Testing the GFCI: Test the GFCI outlet every month as follows:
• Plug a test lamp into the receptacle.
• Start the generator, the test lamp should be on.
• Press the “Test” button located on the front of the receptacle
to trip the device.
• This should stop the flow of electricity making the lamp shut
off. The yellow trip indicator should now be on.
• To restore the flow of electricity, press the “Reset” button on
the front of the receptacle. If the GFCI does not perform in this manner, do not use the receptacle. Contact a local service dealer.
• This outlet is protected against overload by a 20A push-to-
reset circuit breaker. Use the outlet to power 120V AC, single­phase, 60 Hz, electrical loads requiring up to a combined 2400 watts (2.4 kW) or 20 amps of current.
2.2.3 120V AC, 30 AMP RECEPTACLE
Use a NEMA L5-30 plug with this receptacle. Connect a 3-wire cord set rated for 125 Volts AC at 30 Amps (or greater) to the plug.
7
Section 2 – Operation
Residential Portable Generator System
Figure 9 - 120 VAC, 30 Amp Receptacle
Use this receptacle to operate 120 Volt AC, 60 Hz, single phase loads requiring up to 3600 watts (3.6 kW) of power at 30 Amps. The outlet is protected by a 30 Amp push-to-reset circuit breaker.
2.2.4 120/240V AC, 30 AMP RECEPTACLE
Use a NEMA L14-30 plug with this receptacle. Connect a suitable 4-wire grounded cord set to the plug and to the desired load. The cord set should be rated for 250 Volts AC at 30 Amps (or greater).
Figure 10 - 120/240 VAC, 30 Amp Receptacle
Use this receptacle to operate 120 Volt AC, 60 Hz, single phase loads requiring up to 3600 watts (3.6 kW) of power at 30 Amps or 240 Volt AC, 60 Hz, single phase loads requiring up to 7200 watts (7.2 kW) of power at 30 Amps. The outlet is protected by two 30 Amp push-to-reset circuit breakers.
2.2.5 12 VOLT DC, 10 AMP RECEPTACLE
This receptacle allows you to recharge a 12 Volt automotive or utility style storage battery with the battery charge cables provided. This receptacle can not recharge 6 Volt batteries and can not be used to crank an engine having a discharged battery. See the section "Charging a Battery" (page 13) before attempting to recharge a battery.
Figure 11 - 12 Volt DC, 10 Amp Receptacle
2.2.6 120/240 VOLT AC, 50 AMP RECEPTACLE
Use the supplied NEMA 14-50 plug with this receptacle. Connect a 4-wire cord set rated for 250 Volts AC at 50 Amps to the plug.
Figure 12 - 120/240 VAC, 50 Amp Receptacle
Use this receptacle to operate 120/240 Volt AC, 60 Hz electrical loads requiring up to 12,000 watts (12.0 kW) of power. This receptacle is protected by a 50 Amp 2-pole circuit breaker.
50 A
8
Section 2 – Operation
Residential Portable Generator System
2.3 HOW TO USE THE GENERATOR
If you have any problems operating your generator, please call the generator helpline at 1-800-333-1322.
2.3.1 GROUNDING THE GENERATOR
The National Electrical Code requires that the frame and external electrically conductive parts of this generator be properly connected to an approved earth ground. Local electrical
codes may also require proper grounding of the unit. For that purpose, generally, connecting a No. 10 AWG (American Wire Gauge) stranded copper wire to the grounding wing nut and to an earth-driven copper or brass grounding rod (electrode) provides adequate protection against electrical shock. However, local codes may vary widely. Consult with a local electrician for
grounding requirements in your area.
Figure 13 - Grounding the Generator
Proper grounding of the generator will help prevent electrical shock in the event of a ground fault condition in the generator or
in connected electrical devices. Proper grounding also helps dissipate static electricity, which often builds up in ungrounded devices.
2.3.2 CONNECTING ELECTRICAL LOADS
DO NOT connect 240 Volt loads to 120 Volt receptacles. DO NOT
connect 3-phase loads to the generator. DO NOT connect 50 Hz loads to the generator.
• Let engine stabilize and warm up for a few minutes after
starting.
• Plug in and turn on the desired 120 or 240 Volt AC, single
phase, 60 Hz electrical loads.
• Add up the rated watts (or amps) of all loads to be connected
at one time. This total should not be greater than (a) the rated wattage/amperage capacity of the generator or (b) circuit breaker rating of the receptacle supplying the power. See "Don't Overload the Generator" below.
2.4 DON’T OVERLOAD THE GENERATOR
Overloading a generator in excess of its rated wattage capacity can result in damage to the generator and to connected electrical devices. Observe the following to prevent overloading the unit:
• Add up the total wattage of all electrical devices to be
connected at one time. This total should NOT be greater than the generator's wattage capacity.
• The rated wattage of lights can be taken from light bulbs. The
rated wattage of tools, appliances and motors can usually be found on a data plate or decal affixed to the device.
• If the appliance, tool or motor does not give wattage, multiply
volts times ampere rating to determine watts (volts x amps = watts).
• Some electric motors, such as induction types, require about
three times more watts of power for starting than for running. This surge of power lasts only a few seconds when starting such motors. Make sure you allow for this high starting wattage when selecting electrical devices to connect to your generator:
1. Figure the watts needed to start the largest motor.
2. Add to that figure the running watts of all other connected
loads.
The Wattage Reference Guide on page 10 is provided to assist you in determining how many items your generator can operate at one time. (Note: All figures are approximate. See data plate on appliance for wattage requirements.)
Generator Ground Lug
9
Section 2 – Operation
Residential Portable Generator System
2.5 WATTAGE REFERENCE GUIDE
Device . . . . . . . . . . . . . . . . . . . . . . .Running Watts
*Air Conditioner (12,000 Btu) . . . . . . . . . . . . . . . . .1700
*Air Conditioner (24,000 Btu) . . . . . . . . . . . . . . . . .3800
*Air Conditioner (40,000 Btu) . . . . . . . . . . . . . . . . .6000
Battery Charger (20 Amp) . . . . . . . . . . . . . . . . . . . . .500
Belt Sander (3") . . . . . . . . . . . . . . . . . . . . . . . . . . . .1000
Chain Saw . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1200
Circular Saw (6-1/2") . . . . . . . . . . . . . . . . . . .800 to 1000
*Clothes Dryer (Electric) . . . . . . . . . . . . . . . . . . . . .5750
*Clothes Dryer (Gas) . . . . . . . . . . . . . . . . . . . . . . . . .700
*Clothes Washer . . . . . . . . . . . . . . . . . . . . . . . . . . .1150
Coffee Maker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1750
*Compressor (1 HP) . . . . . . . . . . . . . . . . . . . . . . . .2000
*Compressor (3/4 HP) . . . . . . . . . . . . . . . . . . . . . . .1800
*Compressor (1/2 HP) . . . . . . . . . . . . . . . . . . . . . . .1400
Curling Iron . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .700
*Dehumidifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .650
Disc Sander (9") . . . . . . . . . . . . . . . . . . . . . . . . . . . .1200
Edge Trimmer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .500
Electric Blanket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .400
Electric Nail Gun . . . . . . . . . . . . . . . . . . . . . . . . . . . .1200
Electric Range (per element) . . . . . . . . . . . . . . . . . .1500
Electric Skillet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1250
*Freezer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .700
*Furnace Fan (3/5 HP) . . . . . . . . . . . . . . . . . . . . . . . .875
*Garage Door Opener . . . . . . . . . . . . . . . . . . .500 to 750
Hair Dryer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1200
Hand Drill . . . . . . . . . . . . . . . . . . . . . . . . . . .250 to 1100
Device . . . . . . . . . . . . . . . . . . . . . . .Running Watts
Hedge Trimmer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .450
Impact Wrench . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .500
Iron . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1200
*Jet Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .800
Lawn Mower . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1200
Light Bulb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .100
Microwave Oven . . . . . . . . . . . . . . . . . . . . . .700 to 1000
*Milk Cooler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1100
Oil Burner on Furnace . . . . . . . . . . . . . . . . . . . . . . . .300
Oil Fired Space Heater (140,000 Btu) . . . . . . . . . . . . .400
Oil Fired Space Heater (85,000 Btu) . . . . . . . . . . . . . .225
Oil Fired Space Heater (30,000 Btu) . . . . . . . . . . . . . .150
*Paint Sprayer, Airless (1/3 HP) . . . . . . . . . . . . . . . . .600
Paint Sprayer, Airless (handheld) . . . . . . . . . . . . . . . .150
Radio . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50 to 200
*Refrigerator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .700
Slow Cooker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .200
*Submersible Pump (1-1/2 HP) . . . . . . . . . . . . . . . .2800
*Submersible Pump (1 HP) . . . . . . . . . . . . . . . . . . .2000
*Submersible Pump (1/2 HP) . . . . . . . . . . . . . . . . .1500
*Sump Pump . . . . . . . . . . . . . . . . . . . . . . . .800 to 1050
*Table Saw (10") . . . . . . . . . . . . . . . . . . . . .1750 to 2000
Television . . . . . . . . . . . . . . . . . . . . . . . . . . . .200 to 500
Toaster . . . . . . . . . . . . . . . . . . . . . . . . . . . .1000 to 1650
Weed Trimmer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .500
*Allow 3 times the listed watts for starting these devices.
10
Section 2 – Operation
Residential Portable Generator System
2.6 BEFORE STARTING THE GENERATOR
Prior to operating the generator, engine oil and gasoline will need to be added, as follows:
2.6.1 ADDING ENGINE OIL
NOTE: When adding oil to the engine crankcase in the future, use only high quality detergent oil rated with API service classification SG, SH or SL SAE 30 weight. Use no special additives.
Select the oil’s viscosity grade according to the expected operating temperature. Do not use SAE 10W-40.
Above 40°F, use SAE 10W-30 or SAE 30.
Below 40°F, use synthetic 5W-20 or 5W-30.
Although multi-viscosity oils (5W-30, 10W-30, etc.) improve starting in cold weather, these multi-viscosity oils will result in increased oil consumption when used above 32°F. Check your engine oil level more frequently to avoid possible damage from running low on oil.
• Place generator on a level surface.
• Clean area around oil fill and remove oil fill cap and dipstick.
Wipe dipstick clean.
Slowly fill engine with oil through the oil fill opening until it
reaches the full mark on the dipstick. Stop filling occasionally to check oil level. DO NOT OVERFILL.
• Install dipstick. Install oil fill cap and finger tighten securely.
• Check engine oil level before starting each time thereafter.
2.6.2 ADDING GASOLINE
WARNING: Never fill fuel tank indoors. Never fill fuel tank
when engine is running or hot. DO NOT light a cigarette or smoke when filling the fuel tank.
Caution: Do not overfill the fuel tank. Always leave room
for fuel expansion.
• Use regular UNLEADED gasoline with the generator engine. Do not use premium gasoline. Do not mix oil with gasoline.
• Clean area around fuel fill cap, remove cap.
• Slowly add unleaded regular gasoline to fuel tank. Be careful not to overfill. Allow about 1/2" of tank space for fuel expansion, as shown here.
• Install fuel cap and wipe up any spilled gasoline.
Figure 14 - Fuel Tank
IMPORTANT: It is important to prevent gum deposits from
forming in fuel system parts such as the carburetor, fuel hose or tank during storage. Alcohol-blended fuels (called gasohol, ethanol or methanol) can attract moisture, which leads to separation and formation of acids during storage. Acidic gas can damage the fuel system of an engine while in storage. To avoid engine problems, the fuel system should be emptied before storage of 30 days or longer. See "Storage" on page 18. Never use engine or carburetor cleaner products in the fuel tank as permanent damage may occur.
2.7 TO START THE ENGINE
WARNING: Never start or stop engine with electrical devices plugged into the receptacles AND devices turned on.
• Unplug all electrical loads from the unit's receptacles before starting the engine.
• Make sure the unit is in a level position.
• Open the fuel shut-off valve.
Figure 15 - Fuel Shut-off Valve
• Locate the Idle Control ON/OFF switch on the control panel and
set it to the “OFF” position.
Figure 16 - Idle Control Switch
Section 2 – Operation
Residential Portable Generator System
11
-------------
WARNING
-------------
• Move engine CHOKE knob to “Full Choke” position.
Figure 17 - Full Choke Position
• To start engine, press and hold the Start/Run/Stop switch in the “Start” position. The engine will crank and attempt to start. When the engine starts, release the switch to the run position.
• When the engine starts, move choke knob to “1/2 Choke” position until the engine runs smoothly and then to “Run” position. If engine falters, move choke knob to “1/2 Choke” position until the engine runs smoothly and then to “Run” position.
Note: If engine fires, but does not continue to run, move choke lever to “Full Choke” and repeat starting instructions.
2.8 STOPPING THE ENGINE
• Shut off all loads, then unplug the electrical loads from generator panel receptacles. Never start or stop the engine with electrical devices plugged in and turned on.
• Turn “Off” the Idle Control switch (if on).
• Let engine run at no-load for several minutes to stabilize the internal temperatures of engine and generator.
• Move Start/Run/Stop switch to “Off” position.
• Close fuel valve.
IMPORTANT: Do not overload the generator. Also, do not overload individual panel receptacles. These outlets are protected against overload with push-to-reset-type circuit breakers. If amperage rating of any circuit breaker is exceeded, that breaker opens and electrical output to that receptacle is lost. Read “Don’t Overload the Generator” on page 9 carefully.
2.9 AUTOMATIC IDLE CONTROL
This feature is designed to greatly improve fuel economy. When this switch is turned “On,” the engine will only run at its normal fast governed engine speed when electrical load is connected. When the load is removed, the engine will run at a reduced speed of 2100 RPM. With the switch “Off,” the engine runs at the normal fast engine speed all the time. Always have the switch OFF when
starting and stopping the engine.
2.10 COLD WEATHER OPERATION/ DE-ICER
Under certain weather conditions (temperatures below 40° F (4° C) and a high dew point), the engine may experience icing of the carburetor and/or the crankcase breather system. To eliminate this problem, this generator engine is fitted with a winter/summer valve. this directs hot air into the carburetor during cold weather operation. Always make sure the winter/summer valve is in the correct location relative to the weather conditions.
2.11 LOW OIL PRESSURE SHUTDOWN SYSTEM
The engine is equipped with a low oil pressure sensor that shuts down the engine automatically when the oil pressure drops below 10 psi. If the engine shuts down by itself and the fuel tank has enough gasoline, check engine oil level.
2.11.1 INITIAL START-UP
A delay built into the low oil shutdown system allows oil pressure to build during starting. The delay allows the engine to run for about 10 seconds before sensing oil pressure.
2.11.2 SENSING LOW OIL PRESSURE
If the system senses low oil pressure during operation, the engine shuts down.
2.11.3 RESTARTING
If you try to restart the engine within 10 seconds after it shuts down, the engine may NOT start. The system needs 5 to 10 seconds to reset.
If you do restart the engine after such a shutdown and have not corrected the low oil pressure, the engine runs for about 10 seconds as described above and then stops.
Section 2 – Operation
Residential Portable Generator System
12
2.12 CHARGING A BATTERY
DANGER! Storage batteries give off explosive hydrogen gas
while recharging. An explosive mixture will remain around the battery for a long time after it has been charged. The slightest spark can ignite the hydrogen and cause an explosion. Such an explosion can shatter the battery and cause blindness or other serious injury.
DANGER! Do not permit smoking, open flame, sparks or
any other source of heat around a battery. Wear protective goggles, rubber apron and rubber gloves when working around a battery. Battery electrolyte fluid is an extremely caustic sulfuric acid solution that can cause severe burns. If spill occurs flush area with clear water immediately.
Your generator has the capability of recharging a discharged 12 Volt automotive or utility style storage battery. Do not use the unit
to charge any 6 Volt batteries. Do not use the unit to crank an engine having a discharged battery.
This battery charger is a pulse type designed to provide a quality charge current into the battery. The voltage measured at the outlet should be 8-12 VDC. This is normal and does not indicate a faulty charging system.
To recharge 12 Volt batteries, proceed as follows:
• Check fluid level in all battery cells. If necessary, add ONLY distilled water to cover separators in battery cells. Do not use tap water.
• If the battery is equipped with vent caps, make sure they are installed and are tight.
• If necessary, clean battery terminals.
• Connect battery charge cable connector plug to panel receptacle identified by the words "12-VOLT D.C."
• Connect battery charge cable clamp with red handle to the positive (+) battery terminal.
• Connect battery charge cable clamp with black handle to the negative (-) battery terminal.
• Start engine. Let the engine run while battery recharges. Engine idle control switch must
be in off position for battery
charging.
• When battery has charged, shut down engine.
Note: Use an automotive hydrometer to test battery state of charge and condition. Follow the hydrometer manufacturer's instructions carefully. Generally, a battery is considered to be at 100% state of charge when specific gravity of its fluid (as measured by hydrometer) is 1.260 or higher.
Section 2 – Operation
Residential Portable Generator System
13
Loading...
+ 33 hidden pages