Generac 005280, 005241, 005281, 005242, 005282 User Manual

...
C
LISTE
D
U
S
Installation and
Owner’s Manual
7, 10, 13 and 16kW Air-cooled,
Automatic Standby Generators
Models: 005240, 005280 (6 kW NG, 7 kW LP) 005241, 005281 (9 kW NG, 10 kW LP) 005242, 005282 (13 kW NG, 13 kW LP) 005243, 005244, (15 kW NG, 16 kW LP) 005283, 005284
Not intended for use as Primary Power in place of utility or in
life-support applications.
DANGER
DEADLY EXHAUST FUMES. OUTDOOR INSTALLATION ONLY!
INTRODUCTION
Thank you for purchasing this model of the Guardian product line by Generac Power Systems Inc. This model is a compact, high performance, air-cooled, engine-driven generator designed to automatically supply electrical power to operate critical loads dur­ing a utility power failure.
This unit is factory installed in an all-weather, metal enclosure that is intended exclusively for outdoor installation. This generator will operate using either vapor withdrawn liquid propane (LP) or natural gas (NG).
READ THIS MANUAL THOROUGHLY
If any portion of this manual is not understood, contact the nearest Authorized Dealer for starting, operating and servicing procedures.
Throughout this publication, and on tags and decals affixed to the generator, DANGER, WARNING, CAUTION and NOTE blocks are used to alert person­nel to special instructions about a particular opera­tion that may be hazardous if performed incorrectly or carelessly. Observe them carefully. Their defini­tions are as follows:
DANGER
After this heading, read instructions that, if not
strictly complied with, will result in serious person­al injury, including death, in addition to property damage.
After this heading, read instructions that, if not
strictly complied with, may result in serious person­al injury or property damage.
After this heading, read instructions that, if not
strictly complied with, could result in damage to equipment and/or property.
NOTE:
After this heading, read explanatory statements
that require special emphasis.
These safety warnings cannot eliminate the haz­ards that they indicate. Common sense and strict compliance with the special instructions while performing the service are essential to preventing accidents.
Four commonly used safety symbols accompany the DANGER, WARNING and CAUTION blocks. The type of information each indicates follows:
This symbol points out important safety infor-
mation that, if not followed, could endanger personal safety and/or property of others.
This symbol points out potential explosion haz-
ard.
This symbol points out potential fire hazard.
This symbol points out potential electrical shock
hazard.
The operator is responsible for proper and safe use of the equipment. The manufacturer strongly recom­mends that the operator read this Owner's Manual and thoroughly understand all instructions before using this equipment. The manufacturer also strong­ly recommends instructing other users to properly start and operate the unit. This prepares them if they need to operate the equipment in an emergency.
CONTENTS
This manual contains pertinent owner’s information, including warranty, electrical diagrams, exploded views and lists of repair parts, for these different models:
05240 & 05280 – 6 kW NG, 7 kW LP, single-cylin-
• der GH-410 Engine
05241 & 05281 – 9.0 kW NG, 10 kW LP, V-twin
• GT-530 Engine
05242 & 05282 – 13 kW NG, 13 kW LP, V-twin GT-
• 990 Engine
05243, 05244, 05283 & 05284 – 15 kW NG, 16 kW
• LP, V-twin GT-990 Engine
OPERATION AND MAINTENANCE
It is the operator's responsibility to perform all safety checks, to make sure that all maintenance for safe operation is performed promptly, and to have the equipment checked periodically by an Authorized Dealer. Normal maintenance service and replacement of parts are the responsibility of the owner/operator and, as such, are not considered defects in materials or workmanship within the terms of the warranty. Individual operating habits and usage contribute to the need for maintenance service.
Proper maintenance and care of the generator ensures a minimum number of problems and keep operating expenses at a minimum. See an Authorized Dealer for service aids and accessories.
HOW TO OBTAIN SERVICE
When the generator requires servicing or repairs, contact an Authorized Dealer for assistance. Service technicians are factory-trained and are capable of handling all service needs.
When contacting an Authorized Dealer about parts and service, always supply the complete model num­ber and serial number of the unit as given on its data decal, which is located on the generator. See section "The Generator" for decal location.
Model No. ____________ Serial No. ______________
AUTHORIZED
DEALER LOCATION
To locate the nearest AUTHORIZED
DEALER, please call this number:
1-800-333-1322
DEALER LOCATION INFORMATION
CAN BE OBTAINED AT THIS NUMBER or visit
www.guardiangenerators.com.
Table of Contents
Air-cooled Generators
Introduction ........................Inside Front Cover
Read This Manual Thoroughly ........................ IFC
Contents .......................................................... IFC
Operation and Maintenance ............................ IFC
How to Obtain Service ..................................... IFC
Authorized Dealer Locator Number ................... IFC
Safety Rules ........................................................2
Standards Index ..................................................3
Section 1 – General Information ...................4
1.1 Unpacking/Inspection .................................... 4
1.2 Protection Systems ........................................4
1.3 NEC Requirement for Arc Fault Circuit
Interruption Breaker for Bedrooms .............. 4
1.4 The Generator ...............................................5
1.5 Specifications ................................................ 6
1.6 System Set LED ............................................ 7
1.7 Fuel Requirements and Recommendations ...7
1.8 Fuel Consumption ......................................... 7
1.9 Reconfiguring the Fuel System ......................8
1.10 Location ........................................................9
1.11 Battery Requirements .................................. 10
1.12 Battery Installation ...................................... 10
1.13 The Battery .................................................11
Section 2 – Post Installation Start-up
and Adjustments .......................12
2.1 Before Initial Startup...................................12
2.2 Check Transfer Switch Operation ...............12
2.3 Electrical Checks ........................................13
2.4 Generator Tests Under Load .......................13
2.5 Checking Automatic Operation .................... 14
2.6 Adjusting the Fuel Regulator -
7kW (Natural Gas Only) ............................... 14
2.7 Engine Governor Adjustment ...................... 15
2.8 Voltage Regulator Adjustment ...................... 15
Section 3 – Operation ....................................16
3.1 Using the AUTO/OFF/MANUAL Switch ........ 16
3.2 Automatic Transfer Operation ..................... 16
3.3 Sequence of Automatic Operation ...............17
3.4 Manual Transfer Operation .........................17
3.5 Setting the Exercise Timer .......................... 18
3.6 Protection Systems ...................................... 18
Section 4 – Maintenance .............................. 20
4.1 Fuses ........................................................... 20
4.2 Checking the Engine Oil Level ..................... 20
4.3 Changing the Engine Oil .............................. 21
4.4 Changing the Engine Air Cleaner .................21
4.5 Spark Plug(s) .............................................. 22
4.6 Battery Maintenance .................................... 23
4.7 Adjusting GH-410/GT-530/990
Valve Clearance ............................................ 23
4.8 Cooling System ...........................................24
4.9 Attention After Submersion ......................... 24
4.10 Corrosion Protection ...................................25
4.11 Out of Service Procedure ............................. 25
4.12 Service Schedule .........................................26
Section 5 – Troubleshooting .........................27
5.1 Troubleshooting Guide ................................ 27
Section 6 – Notes ........................................... 28
Section 7 – Electrical Data ........................... 29
Section 8 – Exploded Views and
Parts Lists ................................... 40
Section 9 – Mounting Dimensions ............. 66
Section 10 – Warranty ................................... 68
1
IMPORTANT SAFETY INSTRUCTIONS
Air-cooled Generators
SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe operation
be copied and posted near the unit’s installation site. Safety should be stressed to all opera-
tors and potential operators of this equipment.
The engine exhaust from this product
• contains chemicals known to the state
defects or other reproductive harm.
This product contains or emits chemicals
• known to the state of California to cause
cancer, birth defects or other reproductive harm.
Study these SAFETY RULES carefully before install­ing, operating or servicing this equipment. Become familiar with this Owner’s Manual and with the unit. The generator can operate safely, efficiently and reliably only if it is properly installed, operated and maintained. Many accidents are caused by failing to follow simple and fundamental rules or precautions.
The manufacturer cannot anticipate every possible circumstance that might involve a hazard. The warn­ings in this manual, and on tags and decals affixed to the unit are, therefore, not all-inclusive. If using a procedure, work method or operating technique the manufacturer does not specifically recommend, ensure that it is safe for others. Also make sure the procedure, work method or operating technique uti­lized does not render the generator unsafe.
WARNING:
of California to cause cancer, birth
WARNING:
DANGER
Despite the safe design of this generator,
operating this equipment imprudently, neglecting its maintenance or being careless can cause possible injury or death. Permit only responsible and capable persons to operate or maintain this equipment.
Potentially lethal voltages are generated by
these machines. Ensure all steps are taken to render the machine safe before attempting to work on the generator.
Parts of the generator are rotating and/or hot
during operation. Exercise care near running generators.
GENERAL HAZARDS
For safety reasons, the manufacturer recommends
• that the installation, initial start-up and main­tenance of this equipment is carried out by an Authorized Dealer.
The engine exhaust fumes contain carbon monox-
• ide, which can be DEADLY. This dangerous gas, if breathed in sufficient concentrations, can cause unconsciousness or even death. This exhaust system must be installed properly, in strict com­pliance with applicable codes and standards. Following installation, do nothing that might ren­der the system unsafe or in noncompliance with such codes and standards.
Keep hands, feet, clothing, etc., away from drive
• belts, fans, and other moving or hot parts. Never remove any drive belt or fan guard while the unit is operating.
Adequate, unobstructed flow of cooling and venti-
• lating air is critical to correct generator operation. Do not alter the installation or permit even partial blockage of ventilation provisions, as this can seri­ously affect safe operation of the generator. The generator MUST be installed outdoors.
When working on this equipment, remain alert
• at all times. Never work on the equipment when physically or mentally fatigued.
Inspect the generator regularly, and contact the
• nearest Authorized Dealer for parts needing repair or replacement.
Before performing any maintenance on the gen-
• erator, disconnect its battery cables to prevent accidental start up. Disconnect the cable from the battery post indicated by a NEGATIVE, NEG or (–) first, then remove the POSITIVE, POS or (+) cable. When reconnecting the cables, connect the POSITIVE cable first, the NEGATIVE cable last.
Never use the generator or any of its parts as a
• step. Stepping on the unit can stress and break parts, and may result in dangerous operating con­ditions from leaking exhaust gases, fuel leakage, oil leakage, etc.
2
ELECTRICAL HAZARDS
All generators covered by this manual produce
dangerous electrical voltages and can cause fatal electrical shock. Utility power delivers extremely high and dangerous voltages to the transfer switch as does the standby generator when it is in opera­tion. Avoid contact with bare wires, terminals, connections, etc., while the unit is running. Ensure all appropriate covers, guards and barriers are in place, secured and/or locked before operating the generator. If work must be done around an oper­ating unit, stand on an insulated, dry surface to reduce shock hazard.
Do not handle any kind of electrical device while
standing in water, while barefoot, or while hands or feet are wet. DANGEROUS ELECTRICAL SHOCK MAY RESULT.
The National Electrical Code (NEC) requires the
frame and external electrically conductive parts of the generator to be connected to an approved earth ground. Local electrical codes also may require proper grounding of the generator electrical system.
After installing this home standby electrical sys-
tem, the generator may crank and start at any time without warning. When this occurs, load cir­cuits are transferred to the STANDBY (generator) power source. To prevent possible injury if such a start and transfer occur, always set the generator’s AUTO/OFF/MANUAL switch to its OFF position before working on equipment and remove the 15A fuse from the generator control panel.
In case of accident caused by electric shock, imme-
diately shut down the source of electrical power. If this is not possible, attempt to free the victim from the live conductor. AVOID DIRECT CONTACT WITH THE VICTIM. Use a nonconducting implement, such as a dry rope or board, to free the victim from the live conductor. If the victim is unconscious, apply first aid and get immediate medical help.
Never wear jewelry when working on this equip-
ment. Jewelry can conduct electricity resulting in electric shock, or may get caught in moving com­ponents causing injury.
FIRE HAZARDS
For fire safety, the generator must be installed and
maintained properly. Installation must always
comply with applicable codes, standards, laws and regulations. Adhere strictly to local, state
and national electrical and building codes. Comply with regulations the Occupational Safety and Health Administration (OSHA) has established. Also, ensure that the generator is installed in accordance with the manufacturer’s instructions and recommendations. Following proper installa­tion, do nothing that might alter a safe installation and render the unit in noncompliance with the aforementioned codes, standards, laws and regu­lations.
IMPORTANT SAFETY INSTRUCTIONS
Air-cooled Generators
Keep a fire extinguisher near the generator at all
times. Extinguishers rated “ABC” by the National Fire Protection Association are appropriate for use on the standby electric system. Keep the extin­guisher properly charged and be familiar with its use. Consult the local fire department with any questions pertaining to fire extinguishers.
EXPLOSION HAZARDS
Do not smoke around the generator. Wipe up any
fuel or oil spills immediately. Ensure that no com­bustible materials are left in the generator com­partment, or on or near the generator, as FIRE or EXPLOSION may result. Keep the area surround­ing the generator clean and free from debris.
Gaseous fluids such as natural gas and liquid pro-
pane (LP) gas are extremely EXPLOSIVE. Install the fuel supply system according to applicable fuel-gas codes. Before placing the home standby electric system into service, fuel system lines must be properly purged and leak tested according to applicable code. After installation, inspect the fuel system periodically for leaks. No leakage is permit­ted.
STANDARDS INDEX
In the absence of pertinent standards, codes, regu­lations and laws, the published information listed below may be used as installation guide for this equipment.
1. NFPA No. 37, STATIONARY COMBUSTION
ENGINES AND GAS TURBINES, available from the National Fire Protection Association, 470 Atlantic Avenue, Boston, MA 02210.
2. NFPA No. 76A, ESSENTIAL ELECTRICAL
SYSTEMS FOR HEALTH CARE FACILITIES, available same as Item 1.
3. NFPA No. 54, NATIONAL FUEL GAS CODE,
available same as Item 1.
4. NFPA No. 58, AMERICAN NATIONAL STANDARD
FOR STORAGE AND HANDLING OF LIQUEFIED PETROLEUM GAS, available same as Item 1.
5. NFPA No. 70, NFPA HANDBOOK OF NATIONAL
ELECTRIC CODE, available same as Item 1.
6. Article X, NATIONAL BUILDING CODE, available
from the American Insurance Association, 85 John Street, New York, N.Y. 10038.
7. AGRICULTURAL WIRING HANDBOOK, avail-
able from the Food and Energy Council, 909 University Avenue, Columbia, MO 65201.
8. ASAE EP-3634, INSTALLATION AND
MAINTENANCE OF FARM STANDBY ELECTRICAL SYSTEMS, available from the American Society of Agricultural Engineers, 2950 Niles Road, St. Joseph, MI 49085.
9. NFPA No. 30, FLAMMABLE AND COMBUSTIBLE
LIQUIDS CODE, available same as Item 1.
3
Section 1 — General Information
Air-cooled Generators
DANGER
Only qualified electricians or contractors should
attempt such installations, which must comply strictly with applicable codes, standards and regu­lations.
1.1 UNPACKING/INSPECTION
After unpacking, carefully inspect the contents for damage.
This standby generator set is ready for installa-
tion with a factory supplied and pre-mounted base pad and has a weather protective enclosure that is intended for outdoor installation only.
This UL listed standby generator set is packaged
with an automatic transfer switch with built in load center. The combination transfer switch and load center is pre-wired with a two foot and 30 foot conduit. Circuit breakers for emergency circuit connections are included (if equipped).
This UL listed, 2-pole switch is rated at 100 AC
amperes at 250 volts maximum. This transfer
switch is for indoor use only (if equipped).
If this generator is used to power electrical load
circuits normally powered by a utility power source, it is required by code to install a transfer switch. The transfer switch must effectively isolate the electrical system from the utility distribution system when the generator is operating (NEC 700, 701 & 702). Failure to isolate an electrical system by such means will result in damage to the gen­erator and also may result in injury or death to utility power workers due to backfeed of electrical energy.
If any loss or damage is noted at time of delivery, have the person(s) making the delivery note all damage on the freight bill or affix their signature under the consignor's memo of loss or damage.
If a loss or damage is noted after delivery, separate the damaged materials and contact the carrier for claim procedures.
“Concealed damage” is understood to mean damage to the contents of a package that is not in evidence at the time of delivery, but is discovered later.
1.2 PROTECTION SYSTEMS
Unlike an automobile engine, the generator may have to run for long periods of time with no operator pres­ent to monitor engine conditions. For that reason, the engine is equipped with the following systems that protect it against potentially damaging conditions:
1. Low Oil Pressure Sensor 4. Overspeed
2. High Temperature Sensor 5. RPM Sensor
3. Overcrank 6. Low Battery
4
There are LED readouts on the control panel to notify personnel that one of these faults has occurred. There is also a System Set LED that is lit when all of the conditions described in section "System Set LED" are true. (See the "Protection Systems" section for details.)
1.3 NEC REQUIREMENT FOR ARC
FAULT CIRCUIT INTERRUPTION BREAKER FOR BEDROOMS
In 2001, the National Electric Code (NEC) intro­duced a requirement for new construction. This new requirement indicates the need for Arc Fault Circuit Interrupters to be used to protect the complete branch circuit that feeds a dwelling bedroom. The actual NEC requirement is indicated below.
1.3.1 SECTION 210.12 ARC FAULT CIRCUIT
INTERRUPTER PROTECTION
1. Definition: An arc fault circuit interrupter is a
device intended to provide protection from the effects of arc faults by recognizing characteristics unique to arcing and by functioning to de-ener­gize the circuit when an arc fault is detected.
2. Dwelling Unit Bedrooms: All branch circuits that
supply 125 volt, single-phase, 15 and 20 ampere outlets installed in dwelling unit bedrooms shall be protected by an arc fault circuit interrupter listed to provide protection of the entire branch circuit.
Section 210.12 requires that AFCI protection be provided on branch circuits that supply outlets (receptacle, lighting, etc.) in dwelling bedrooms. The requirement is limited to 15 and 20 ampere, 125 volt circuits. There is no prohibition against provid­ing AFCI protection on other circuits or in locations other than bedrooms. Because circuits are often shared between a bedroom and other areas such as closets and hallways, providing AFCI protection on the complete circuit would comply with 210.12.
If during the installation of the home standby system the decision is made to provide back up power to a bedroom branch circuit, then the circuit breaker in the transfer switch should be replaced with an Arc Fault Circuit Interrupter.
It is most important that breakers only be switched like for like. For instance, if replacing a 15A breaker, it MUST be replaced with a 15A AFCI breaker. Likewise, a 20A breaker MUST be replaced with a 20A AFCI.
These AFCI breakers are available at the nearest hardware store.
Siemens Item # Description
Q115AF 15A Single Pole AFCI
Q120AF 20A Single Pole AFCI
1.4 THE GENERATOR
Section 1 — General Information
Air-cooled Generators
5
Section 1 — General Information
Air-cooled Generators
1.5 SPECIFICATIONS
1.5.1 GENERATOR
Model 05240 & 05280 05241 & 05281 05242 & 05282 05243 & 05244 05283 & 05284
Rated Max. Continuous 6,000 NG/7,000 LP 9,000 NG/10,000 LP 13,000 NG/13,000 LP 15,000 NG/16,000 LP Power Capacity (Watts*)
Rated Voltage 120/240 120/240 120/240 120/240 Rated Max. Continuous
Load Current (Amps)
120 Volts** 50.0 NG/58.3 LP 75.0 NG/83.3 LP 108.3 NG/108.3 LP 125 NG/133.3 LP
240 Volts 25.0 NG/29.2 LP 37.5 NG/41.7 LP 54.1 NG/54.1 LP 62.5 NG/66.6 LP Main Line Circuit Breaker 30 Amp 45 Amp 55 Amp 65 Amp Circuits***
50A, 240V - - - 1
40A, 240V - - 1 1
30A, 240V 1 1 1 -
20A, 240V - 1 - 1
20A, 120V 1 3 3 5
15A, 120V 5 3 5 5 Phase 1 1 1 1 Number of Rotor Poles 2 2 2 2 Rated AC Frequency 60 Hz 60 Hz 60 Hz 60 Hz Power Factor 1 1 1 1 Recommended Air Filter Part # 0C8127 Part # 0E9581 Part # 0C8127 Part # 0C8127 Battery Requirement Group 26 Group 26 Group 26 Group 26
12 Volts and 12 Volts and 12 Volts and 12 Volts and 350 Cold-cranking 525 Cold-cranking 525 Cold-cranking 525 Cold-cranking Amperes Minimum Amperes Minimum Amperes Minimum Amperes Minimum
Battery Warming Blanket 0F6148DSRV Weight (Unit Only) 336 Pounds 375 Pounds 425.5 Pounds 445 & 414 Pounds Enclosure Steel/Aluminum Normal Operating Range -20°F (-28.8°C) to 104°F (40°C)
* Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power and condition, etc. Maximum power
decreases about 3.5 percent for each 1,000 feet above sea level; and also will decrease about 1 percent for each 6° C (10° F) above 16° C (60° F) ambient temperature.
** Load current values shown for 120 volts are maximum TOTAL values for two separate circuits. The maximum current in each circuit must not exceed the value stated for 240
volts.
*** Circuits to be moved must be protected by same size breaker. For example, a 15 amp circuit in main panel must be a 15 amp circuit in transfer switch.
1.5.2 ENGINE
Model 05240 & 05280 05241 & 05281 05242 & 05282 05243 & 05244 05283 & 05284
Type of Engine GH-410 GT-530 GT-990 GT-990 Number of Cylinders 1 2 2 2 Rated Horsepower 14.5 @ 3,600 rpm 18 @ 3,600 rpm 30 @ 3,600 rpm 30 @ 3,600 rpm Displacement 410cc 530cc 992cc 992cc Cylinder Block Aluminum w/Cast Aluminum w/Cast Aluminum w/Cast Aluminum w/Cast Iron Sleeve Iron Sleeve Iron Sleeve Iron Sleeve Valve Arrangement Overhead Valves Overhead Valves Overhead Valves Overhead Valves Ignition System Solid-state w/Magneto Solid-state w/Magneto Solid-state w/Magneto Solid-state w/Magneto Recommended Spark Plug RC14YC BPR6HS RC14YC RC14YC Spark Plug Gap 0.76 mm (0.030 inch) 0.76 mm (0.030 inch) 1.02 mm (0.040 inch) 1.02 mm (0.040 inch) Compression Ratio 8.6:1 9.5:1 9.5:1 9.5:1 Starter 12 Vdc 12 Vdc 12 Vdc 12 Vdc Oil Capacity Including Filter Approx. 1.5 Qts Approx. 1.7 Qts Approx. 1.7 Qts Approx. 1.7 Qts Recommended Oil Filter Part # 070185F Part # 070185F Part # 070185F Part # 070185F Recommended Air Filter Part # 0C8127 Part # 0E9581 Part # 0C8127 Part # 0C8127 Operating RPM 3,600 3,600 3,600 3,600
6
Section 1 — General Information
Air-cooled Generators
1.6 SYSTEM SET LED
The “System Set” LED is lit when all of the following conditions are true:
1. The AUTO/OFF/MANUAL switch is set to the
AUTO position.
2. The utility voltage being supplied to the unit is
being sensed by the PCB. If the utility sense volt­age is not connected to the unit or if it is below approximately 150-160 volts AC, then the system set light will flash rapidly. This indicates that if the AUTO/OFF/ MANUAL switch is placed in the Auto position, the generator will start.
3. No alarms are present, for example, low oil pres-
sure, high temperature, etc.
1.7 FUEL REQUIREMENTS
AND RECOMMENDATIONS
With LP gas, use only the vapor withdrawal sys­tem. This type of system uses the vapors formed
above the liquid fuel in the storage tank.
The engine has been fitted with a fuel carburetion system that meets the specifications of the 1997 California Air Resources Board for tamper-proof dual fuel systems. The unit will run on natural gas or LP gas, but it has been factory set to run on natural gas. Should the primary fuel need to be changed to LP gas, the fuel system needs to be reconfigured. See the Reconfiguring the Fuel System section for instruc­tions on reconfiguration of the fuel system.
Recommended fuels should have a Btu content of at least 1,000 Btus per cubic foot for natural gas; or at least 2,520 Btus per cubic foot for LP gas. Ask the fuel supplier for the Btu content of the fuel.
Required fuel pressure for natural gas is 5 inches
to 7 inches water column (0.18 to 0.25 psi); and for liquid propane, 10 inches to 12 inches of water column (0.36 to 0.43 psi).
NOTE:
All pipe sizing, construction and layout must com­ply with NFPA 54 for natural gas applications and NFPA 58 for liquid propane applications. Once the generator is installed, verify that the fuel pressure NEVER drops below four (4) inches water column for natural gas or 10 inches water column for liq­uid propane.
Prior to installation of the generator, the installer should consult local fuel suppliers or the fire mar­shall to check codes and regulations for proper installation. Local codes will mandate correct routing of gaseous fuel line piping around gardens, shrubs and other landscaping to prevent any damage.
Special considerations should be given when install­ing the unit where local conditions include flooding, tornados, hurricanes, earthquakes and unstable ground for the flexibility and strength of piping and their connections.
Use an approved pipe sealant or joint compound on all threaded fitting.
All installed gaseous fuel piping must be purged and leak tested prior to initial start-up in accordance with local codes, standards and regulations.
1.8 FUEL CONSUMPTION
Unit Nat. Gas (*) LP Vapor (**) 1/2 Load Full Load 1/2 Load Full Load
6/7 kW 66 119 0.82/30 1.47/54 9/10 kW 102 156 1.25/46 1.93/70 13/13 kW 156 220 1.55/57 2.18/80 15/16 kW 173 245 1.59/59 2.51/92
*Natural gas is in cubic feet per hour. **LP is in gallons per hour/cubic feet per hour. *** Values given are approximate.
1.8.1 BTU FLOW REQUIREMENTS -
NATURAL GAS
BTU flow required for each unit based on 1000 BTU per cubic foot.
6kW — 119,000 BTU/Hour
• 9kW — 156,000 BTU/Hour
• 13kW — 220,000 BTU/Hour
• 15kW — 245,000 BTU/Hour
DANGER
 Gaseous fuels such as natural gas and liquid
propane (LP) gas are highly explosive. Even the slightest spark can ignite such fuels and cause an explosion. No leakage of fuel is permitted. Natural gas, which is lighter than air, tends to collect in high areas. LP gas is heavier than air and tends to settle in low areas.
NOTE:
A minimum of one approved manual shut-off valve must be installed in the gaseous fuel supply line. The valve must be easily accessible. Local codes determine the proper location.
7
Section 1 — General Information
Air-cooled Generators
1.9 RECONFIGURING THE FUEL SYSTEM
1.9.1 7 KW, 410CC ENGINE
To reconfigure the fuel system from NG to LP, follow these steps (Figure 1.4):
NOTE:
The primary regulator for the propane supply is NOT INCLUDED with the generator. A fuel pres­sure of 10 to 12 inches of water column (0.36 to
0.43 psi) to the fuel inlet of the generator MUST
BE SUPPLIED.
1. Turn off the main gas supply (if connected).
2. Open the roof and remove the door.
3. Remove the battery (if installed).
4. Disconnect wire #0 and wire #14 from the gas
solenoid on top of the demand regulator.
5. Remove the carburetor fuel hose from the outlet
port of the demand regulator.
6. Remove the demand regulator by removing the
fastener that retains the regulator mounting bracket.
7. Remove the square headed steel pipe plug from
outlet port #1 and the brass hose barb fitting from outlet port #2.
8. Refit the brass hose barb fitting to outlet port #1
and the square headed steel pipe plug to outlet port #2.
Figure 1.4 – Demand Regulator
HOSE & PLUG SWITCHED SIDES
FUEL HOSE
FUEL HOSE
BRASS HOSE FITTING
OUTLET PORT
FUEL JET
BRASS HOSE
FITTING
ADJUSTMENT
SCREW
PIPE PLUG
NOTE:
Use an approved pipe sealant or joint compound on all threaded fittings to reduce the possibility of leakage.
9. Reverse procedure steps 1-6 to reinstall demand regulator.
10. Take the plastic plug supplied in the poly-bag with the generator and press it into the 3/4” hole on the bottom of the air cleaner base (Figure
4.6).
11. Reverse the procedure to convert back to natural gas.
12. Check for gas leakage at the pipe plug, hose con­nection and fittings.
1.9.2 10, 13 AND 16KW, V-TWIN ENGINES
To reconfigure the fuel system from NG to LP, follow these steps:
NOTE:
The primary regulator for the propane supply is NOT INCLUDED with the generator. A fuel pres­sure of 10 to 12 inches of water column (0.36 to
0.43 psi) to the fuel inlet of the generator MUST
BE SUPPLIED.
1. Open the roof.
2. For 10kW units: Loosen clamp and slide back the air inlet hose.
• Slide fuel selector on carburetor out towards the back of the enclosure (Figures 1.5 and 1.6).
• Return the inlet hose and tighten clamp secure­ly.
For 13 and 16kW units: remove the air cleaner
cover.
• Slide the selector lever out towards the back of the enclosure (Figures 1.7 and 1.8).
• Return the air cleaner cover and tighten the two thumb screws.
3. Close the roof.
4. Reverse the procedure to convert back to natural gas.
8
NG FUEL SYSTEM
RUNNING
PRESSURE
TAP
LP FUEL SYSTEM
STATIC PRESSURE TAP
Section 1 — General Information
Air-cooled Generators
Figure 1.5 - 10kW, GT-530 (Inlet Hose Slid Back)
Fuel Selection
Lever - "In" Position for Natural Gas
Fuel
Figure 1.6 - 10kW, GT-530 (Inlet Hose Slid Back)
Fuel Selection
Lever - "Out"
Position for
Liquid Propane
(Vapor) Fuel
Figure 1.7 - 13/16kW, GT-990 (Airbox Cover
Removed)
Fuel Selection Lever - "In" Position for Natural Gas Fuel
Figure 1.8 - 13/16kW, GT-990 (Airbox Cover
Removed)
Fuel Selection Lever - "Out" Position for Liquid Propane
(Vapor) Fuel
1.10 LOCATION
1.10.1 GENERATOR
Install the generator set, in its protective enclosure, outdoors, where adequate cooling and ventilating air is always available (Figure 1.9). Consider these fac­tors:
The installation of the generator must comply
strictly with NFPA 37, NFPA 54, NFPA 58, and NFPA 70 standards.
Install the unit where air inlet and outlet open-
• ings will not become obstructed by leaves, grass, snow, etc.. If prevailing winds will cause blowing or drifting, consider using a windbreak to protect the unit.
Install the generator on high ground where water
• levels will not rise and endanger it.
Allow sufficient room on all sides of the generator
• for maintenance and servicing. This unit must be installed in accordance with current applicable NFPA 37 and NFPA 70 standards; as well as any other federal, state and local codes for minimum distances from other structures. DO NOT install under wooden decks or structures.
Install the unit where rain gutter down spouts,
• roof fun-off, landscape irrigation, water sprinklers or sump pump discharge does not flood the unit or spray the enclosure, including any air inlet or outlet openings.
Install the unit where services will not be affected
• or obstructed, including concealed, underground or covered services such as electrical, fuel, phone, air conditioning or irrigation.
Where strong prevailing winds blow from one
• direction, face the generator air inlet openings to the prevailing winds.
9
Section 1 — General Information
Air-cooled Generators
Install the generator as close as possible to the fuel
supply, to reduce the length of piping.
Install the generator as close as possible to the
transfer switch. REMEMBER THAT LAWS OR CODES MAY REGULATE THE DISTANCE AND LOCATION.
The genset must be installed on a level surface.
The base frame must be level within two (2) inches all around.
The generator is typically placed on pea gravel or
crushed stone. Check local codes if a concrete slab is required. If a concrete base slab is required, all federal, state and local codes should be followed. Special attention should be given to the concrete base slab which should exceed the length and width of the generator by a minimum of six (6) inches (0.152 meters) on all sides.
Figure 1.9 – Generator Clearances
Install the transfer switch indoors on a firm, sturdy
• supporting structure.
To prevent switch distortion, level the switch if
• necessary. This can be done by placing washers between the switch enclosure and mounting sur­face.
Never install the switch where water or any corro-
• sive substance might drip onto the enclosure.
Protect the switch at all times against excessive
• moisture, dust, dirt, lint, construction grit and corrosive vapors.
If the AUTO/OFF/MANUAL switch is not set to its
OFF position, the generator can crank and start as soon as the battery cables are connected. If the utility power supply is not turned off, spark­ing can occur at the battery posts and cause an explosion.
The engine exhaust fumes contain carbon mon-
oxide, which can be DEADLY. This dangerous gas, if breathed in sufficient concentrations, can cause unconsciousness or even death. This exhaust system must be installed properly, in strict compliance with applicable codes and stan­dards. Following installation, do nothing that might render the system unsafe or in noncompli­ance with such codes and standards.
• Operate the generator outdoors ONLY.
• Keep exhaust gases from entering a confined area through windows, doors, ventilation or other openings (Figure 1.9).
1.10.2 TRANSFER SWITCH
1.10.2.1 7, 10, 13, and 16 kW Units (if equipped)
The transfer switch shipped with this generator is enclosed in a NEMA 1 enclosure. This type of enclo- sure is intended for indoor use only. Follow these rules:
10
1.11 BATTERY REQUIREMENTS
See the Specifications section for correct battery size and rating.
1.12 BATTERY INSTALLATION
Fill the battery with the proper electrolyte fluid if necessary and have the battery fully charged before installing it.
Before installing and connecting the battery, complete the following steps:
1. Set the generator's AUTO/OFF/MANUAL switch to OFF.
2. Turn off utility power supply to the transfer switch.
3. Remove the 15A fuse from the generator control panel.
Battery cables were factory connected at the genera­tor (Figure 1.10). Connect cables to battery posts as follows:
4. Connect the red battery cable (from starter con­tactor) to the battery post indicated by a positive, POS or (+).
5. Connect the black battery cable (from frame ground) to the battery post indicated by a nega­tive, NEG or (—).
NOTE:
Dielectric grease should be used on battery posts to aid in the prevention of corrosion.
NOTE:
Damage will result if battery connections are made in reverse.
Figure 1.10 – Battery Cable Connections
NOTE: In areas where temperatures regularly fall below 10° F (-12° C) it is recommended that a pad type battery heater be installed to aid in cold climate starting (see Specifications).
NOTE:
The generator is equipped with a battery trickle charger that is active when the unit is set up for automatic operation. With the battery installed and utility power source voltage available to the transfer switch, the battery receives a trickle charge while the engine is not running, to prevent self-discharge. The trickle charger is designed to help extend the life of the battery by maintain­ing the battery when the unit is not running. The trickle charge feature cannot be used to recharge a discharged battery.
1.13 THE BATTERY
DANGER
Do not dispose of the battery in a fire. The
battery is capable of exploding.
A battery presents a risk of electrical shock
and high short circuit current. The following pre­cautions are to be observed when working on batteries:
• Remove the 15A fuse from the generator control
panel.
• Remove watches, rings or other metal objects;
• Use tools with insulated handles;
• Wear rubber gloves and boots;
• Do not lay tools or metal parts on top of the
battery; and
• Disconnect charging source prior to connecting or
disconnecting battery terminals.
Section 1 — General Information
Air-cooled Generators
Do not open or mutilate the battery. Released
electrolyte has been known to be harmful to the skin and eyes, and to be toxic.
The electrolyte is a dilute sulfuric acid that is
harmful to the skin and eyes. It is electrically conductive and corrosive.
The following procedures are to be observed:
• Wear full eye protection and protective clothing;
• Where electrolyte contacts the skin, wash it off immediately with water;
• Where electrolyte contacts the eyes, flush thor­oughly and immediately with water and seek medical attention; and
• Spilled electrolyte is to be washed down with an acid neutralizing agent. A common practice is to use a solution of 1 pound (500 grams) bicarbonate of soda to 1 gallon (4 liters) of water. The bicar­bonate of soda solution is to be added until the evidence of reaction (foaming) has ceased. The resulting liquid is to be flushed with water and the area dried.
Lead-acid batteries present a risk of fire because
they generate hydrogen gas. The following procedures are to be followed:
• DO NOT SMOKE when near the battery;
• DO NOT cause flame or spark in battery area; and
• Discharge static electricity from body before touch­ing the battery by first touching a grounded metal surface.
Be sure the AUTO/OFF/MANUAL switch is set to
the OFF position before connecting the battery cables. If the switch is set to AUTO or MANUAL, the generator can crank and start as soon as the battery cables are connected.
Be sure the utility power supply is turned off
and the 15A fuse is removed from the generator control panel, or sparking may occur at the bat­tery posts as the cables are attached and cause an explosion.
Servicing of the battery is to be performed or super­vised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized person­nel away from batteries.
See the Specifications section for the correct size and rating when replacing the battery. When using a maintenance-free battery, it is not necessary to check the specific gravity or electrolyte level. Have these procedures performed at the intervals specified in the “Service Schedule.” A negative ground system is used. Battery connections are shown on the wiring diagrams. Make sure the battery is correctly connect­ed and terminals are tight. Observe battery polarity when connecting the battery to the generator set.
11
Section 2 — Post Installation Start-up and Adjustments
Air-cooled Generators
2.1 BEFORE INITIAL START-UP
NOTE:
These units have been run and tested at the fac­tory prior to being shipped and do not require any type of break-in.
Before starting, complete the following:
1. Set the generator’s main circuit breaker to its OFF (or OPEN) position.
2. Set the generator's AUTO/OFF/MANUAL switch to the OFF position.
3. Turn OFF all breakers on the load center of the transfer box (T1 and T2).
4. Turn OFF all loads connected to the transfer switch terminals T1 and T2.
5. Check the engine crankcase oil level and, if neces­sary, fill to the dipstick FULL mark with the rec­ommended oil. Do not fill above the FULL mark.
6. Check the fuel supply. Gaseous fuel lines must have been properly purged and leak tested in accordance with applicable fuel-gas codes. All fuel shutoff valves in the fuel supply lines must be open.
During initial start up, after installation, it is normal for the generator to exceed the normal number of start attempts and experience an “over crank” fault. This is due to accumulated air in the fuel system dur­ing shipment.
To reduce or eliminate this problem on initial start up, remove the air filter cover and partially cover the fuel mixer inlet while the engine is cranking (Figures
2.1 and 2.2). This will cause an abnormal vacuum
in the system and purge the air from the system. Once fuel reaches the engine, it will begin to run. Remove the blockage from the mixer inlet as soon as the engine begins to fire. The unit should then be run several minutes to insure that all air is removed from the fuel system. Once the engine is running, this procedure is not required as long as the fuel supply to the generator is not interrupted. This procedure will only be required if the generator becomes discon­nected from the fuel system for whatever reason.
NOTE:
This procedure applies to 13kW and 16kW units only and should be performed by trained person­nel.
Never operate the engine with the oil level
below the “Add” mark on the dipstick. Doing this could damage the engine.
Figure 2.1 – Remove Air Filter Cover
Figure 2.2 – Restrict Air Flow During
Inital Start Up
2.2 CHECK TRANSFER SWITCH OPERATION
Refer to the "Manual Transfer Operation" section, of the owner’s manual for procedures.
DANGER
Do not attempt manual transfer switch opera-
tion until all power voltage supplies to the transfer switch have been positively turned off. Failure to turn off all power voltage supplies will result in extremely hazardous and possibly fatal electrical shock.
12
Section 2 — Post Installation Start-up and Adjustments
Air-cooled Generators
2.3 ELECTRICAL CHECKS
Complete electrical checks as follows:
1. Set the generator's main circuit breaker to its OFF (or OPEN) position.
2. Set the generator's AUTO/OFF/MANUAL switch to the OFF position.
3. Turn OFF all breakers on the load center of the transfer box (T1 and T2).
4. Turn on the utility power supply to the transfer switch using the means provided (such as a utility main line circuit breaker).
DANGER
The transfer switch is now electrically “hot.”
Contact with “hot” parts will result in extremely hazardous and possibly fatal electrical shock. Proceed with caution.
5. Use an accurate AC voltmeter to check utility power source voltage across transfer switch ter­minals N1 and N2. Nominal line-to-line voltage should be 240 volts AC.
6. Check utility power source voltage across termi­nals N1 and the transfer switch neutral lug; then across terminal N2 and neutral. Nominal line-to­neutral voltage should be 120 volts AC.
7. When certain that utility supply voltage is compat­ible with transfer switch and load circuit ratings, turn OFF the utility power supply to the transfer switch.
8. On the generator panel, set the AUTO/OFF/ MANUAL switch to MANUAL. The engine should crank and start.
9. Let the engine warm up for about five minutes to allow internal temperatures to stabilize. Then, set the generator’s main circuit breaker to its ON (or CLOSED) position.
DANGER
Proceed with caution! Generator power voltage
is now supplied to the transfer switch. Contact with live transfer switch parts will result in dan­gerous and possibly fatal electrical shock.
10. Connect an accurate AC voltmeter and a frequen­cy meter across transfer switch terminal lugs E1 and E2. 7kW voltage should be 242-252 volts at a frequency of 61-63 Hertz. 10, 13, and 16kW voltage should be 247-249 volts at a frequency of
57.5-59.5 Hertz.
11. Connect the AC voltmeter test leads across ter­minal lugs E1 and neutral; then across E2 and neutral. In both cases, voltage reading should be 121-126 volts AC (7kW), and 125-126 volts AC (10, 13 and 16kW).
12. Set the generator’s main circuit breaker to its OFF (or OPEN) position. Let the engine run at no­load for a few minutes to stabilize internal engine generator temperatures.
13. Set the generator's AUTO/OFF/MANUAL switch to OFF. The engine should shut down.
NOTE:
It is important not to proceed until certain that generator AC voltage and frequency are correct and within the stated limits. Generally, if both AC frequency and voltage are high or low, the engine governor requires adjustment* (*GH410 only). If frequency is correct, but voltage is high or low, the generator’s voltage regulator requires adjustment.
2.4 GENERATOR TESTS UNDER LOAD
To test the generator set with electrical loads applied, proceed as follows:
1. Set generator’s main circuit breaker to its OFF (or OPEN) position.
2. Turn OFF all breakers on the load center of the transfer box (T1 and T2).
3. Set the generator's AUTO/OFF/MANUAL switch to OFF.
4. Turn OFF the utility power supply to the transfer switch, using the means provided (such as a util­ity main line circuit breaker).
Do not attempt manual transfer switch opera-
tion until all power voltage supplies to the transfer switch have been positively turned off. Failure to turn off all power voltage supplies will result in extremely hazardous and possibly fatal electrical shock.
5. Manually set the transfer switch to the STANDBY position, i.e., load terminals connected to the generator's E1/E2 terminals. The transfer switch operating lever should be down.
6. Set the generator's AUTO/OFF/MANUAL switch to MANUAL. The engine should crank and start immediately.
7. Let the engine stabilize and warm up for a few minutes.
8. Set the generator’s main circuit breaker to its ON (or closed) position. Loads are now powered by the standby generator.
9. Turn ON the load center of the transfer switch (T1 and T2).
10. Connect an accurate AC voltmeter and a frequen­cy meter across terminal lugs E1 and E2.
• 7kW voltage should be greater than 230 volts and frequency should be greater than 58 Hz.
13
Section 2 — Post Installation Start-up and Adjustments
• 10, 13 & 16kW voltage should be greater than 240 volts and frequency should be greater than 60 Hz.
11. Let the generator run at full rated load for 20-30 minutes. Listen for unusual noises, vibration or other indications of abnormal operation. Check for oil leaks, evidence of overheating, etc.
12. When testing under load is complete, turn OFF electrical loads.
13. Set the generator's main circuit breaker to its OFF (or OPEN) position.
14. Let the engine run at no-load for a few minutes.
15. Set the AUTO/OFF/MANUAL switch to OFF. The engine should shut down.
2.5 CHECKING AUTOMATIC
OPERATION
To check the system for proper automatic operation, proceed as follows:
1. Set generator’s main circuit breaker to its OFF (or OPEN) position.
2. Check that the AUTO/OFF/MANUAL switch is set to OFF.
3. Turn OFF the utility power supply to the transfer switch, using means provided (such as a utility main line circuit breaker).
4. Manually set the transfer switch to the UTILITY position, i.e., load terminals connected to the util­ity power source side.
5. Turn ON the utility power supply to the transfer switch, using the means provided (such as a util­ity main line circuit breaker).
6. Set the generator's main circuit breaker to its ON (or CLOSED)) position.
7. Set the AUTO/OFF/MANUAL switch to AUTO. The system is now ready for automatic operation.
8. Turn OFF the utility power supply to the transfer switch.
With the AUTO/OFF/MANUAL switch at AUTO, the engine should crank and start when the utility source power is turned OFF after a 10 second delay. After starting, the transfer switch should connect load cir­cuits to the standby side after a 15 second delay. Let the system go through its entire automatic sequence of operation.
With the generator running and loads powered by generator AC output, turn ON the utility power supply to the transfer switch. The following should occur:
After about 15 seconds, the switch should transfer
loads back to the utility power source.
About one minute after retransfer, the engine
should shut down.
2.6 ADJUSTING THE FUEL REGULATOR
- 7KW (NATURAL GAS ONLY)
NOTE:
All V-twin engine units DO NOT require a fuel reg­ulator adjustment due to the fuel system design.
Although the generator has been factory set to pro­vide maximum power, it may be necessary in some areas to adjust this setting. If experiencing engine problems at high or full load conditions, follow these steps. It will require a frequency meter to perform this procedure.
1. Turn off utility power to the main distribution panel in the house. This can be done by switching the service main breaker to the off or open posi­tion.
2. Allow the generator to start. Before loading the generator, confirm that the No Load Frequency, with the roof open and door off, is set to 63-63.5 Hz. Transfer load to emergency circuits.
3. Turn on appliances, lights, pumps, etc., that are on the emergency circuits in an attempt to fully load the generator. Be cautious not to overload the generator. Use the following chart as a guide:
Unit 120 Volts 240 Volts
7 kW 50.0 amps 25.0 amps
4. When 3/4 load has been achieved. Connect a fre­quency meter to the output lugs of the generator’s main line circuit breaker.
5. The fuel regulator is fitted with one adjustment screw. While watching the frequency meter, slowly turn the adjustment screw clockwise or counter­clockwise until the highest frequency is read on the meter. Only limited adjustment is available because of the set pin. Under no circumstances should any of the pins be removed (Figure 2.3).
Figure 2.3 — 7kW Fuel Regulator
ngine
Adjustment Screw
(One Side Only)
410cc Engine
Set Pin
14
Section 2 — Post Installation Start-up and Adjustments
Air-cooled Generators
6. When the highest frequency is reached maximum power has been set. From this point turn the adjustment screw 1/4 turn counterclockwise. The regulator is now set.
7. Turn utility power to the main distribution panel back on. This can be done by switching the ser­vice main breaker to the on or closed position. Allow the generator to shut down.
Do not make any unnecessary adjustments.
Factory settings are correct for most applica­tions. However, when making adjustments, be careful to avoid overspeeding the engine.
If this procedure or the test equipment is not avail­able, locate the nearest Dealer and they can perform the adjustments.
NOTE:
A service fee may be charged for this adjustment.
2.7 ENGINE GOVERNOR ADJUSTMENT
If both AC frequency and voltage are correspondingly high or low, adjust the engine governor as follows:
2.7.1 7 KW UNITS
2. Hold the governor lever at its wide open throttle position (clockwise), and rotate the governor shaft clockwise as far as it will go. Then, tighten the governor lever clamp bolt to 70 inch-pounds (8 N-m).
3. Start the generator; let it stabilize and warm up at no-load.
4. Connect a frequency meter across the generators AC output leads.
5. Turn the primary adjust screw to obtain a fre­quency reading of 61.5 Hertz. Turn the secondary adjust screw to obtain a frequency of 62.5 Hz.
6. When frequency is correct at no load, check the AC voltage reading. If voltage is incorrect, the volt­age regulator may require adjustment (See the Voltage Regulator Adjustment section).
2.7.2 13 KW AND 16 KW UNITS
NOTE:
All V-twin units DO NOT require an engine gover­nor adjustment due to their design.
2.7.3 ADDITIONAL CORROSION
PROTECTION
Periodically spray all engine linkage parts and brack­ets with corrosion inhibiting spray such as WD-40 or a comparable product.
The engine must be OFF to perform steps 1 and
2.
1. Loosen the governor clamp bolt (Figure 2.4).
Figure 2.4 — Engine Governor Adjustment
Single Cylinder Engines
SECONDARY
ADJUST SCREW
GOVERNOR
SHAFT
GOVERNOR
CLAMP
BOLT
PRIMARY
ADJUST SCREW
2.8 VOLTAGE REGULATOR
ADJUSTMENT
2.8.1 7KW UNITS
With the frequency between 62-63 Hertz at no-load, slowly turn the slotted potentiometer (Figure 2.5) until line voltage reads 248-252 volts.
2.8.2 10, 13, AND 16KW UNITS
With the frequency between 58-59 Hertz at no-load, slowly turn the slotted potentiometer (Figure 2.3) until line voltage reads 247-249 volts.
NOTE:
The access panel on top of the control panel must be removed to adjust the voltage regulator.
NOTE:
The voltage regulator is housed above the gen­erator's control panel. The regulator maintains a voltage in direct proportion to frequency at a 2-to­1 ratio. For example, at 62 Hertz, line-to-neutral voltage will be 124 volts.
15
Section 3 — Operation
Air-cooled Generators
Figure 2.5 – Voltage Adjustment Potentiometer
Tur n t o adjust voltage.
3.1 USING THE AUTO/OFF/MANUAL SWITCH (FIGURE 3.1)
3.1.1 “AUTO” POSITION
Selecting this switch position activates fully automatic system operation. It also allows the unit to automati­cally start and exercise the engine every seven days with the setting of the exercise timer (see the Setting the Exercise Timer section).
3.1.2 “OFF” POSITION
This switch position shuts down the engine. This position also prevents automatic operation.
Figure 3.1 – Generator Control Panel
CONTROL AND INFORMATION CENTER
SYSTEM SET
LOW BATTERY
AUTO. MAN.
OFF
SYSTEM FUSE
15A
ASSY: 0F8418/0F8419
SET
EXERCISE
TIME
LOW OIL
HIGH TEMP
OVER SPEED NO RPM SENSE IF FLASHING
OVER CRANK
FLASHING GREEN LED= NO UTILITY SENSE 5 FLASHING RED LEDS= EXERCISER NOT SET
3.1.3 “MANUAL” POSITION
Set the switch to MANUAL to crank and start the engine. Transfer to standby power will not occur unless there is a utility failure.
With the switch set to AUTO, the engine may
crank and start at any time without warning. Such automatic starting normally occurs when utility power source voltage drops below a pre­set level or during the normal exercise cycle. To prevent possible injury that might be caused by such sudden starts, always set the switch to OFF and remove the fuses before working on or around the generator or transfer switch. Then, place a “DO NOT OPERATE” tag on the genera­tor panel and on the transfer switch.
3.1.4 CHOKE OPERATION
1. 990 engines have an electric choke in the air box that is automatically controlled by the electronic control board.
2. 530 engines have an electric choke on the divider panel air inlet hose that is automatically con­trolled by the electronic control board.
3. 410 engines do not have a choke.
3.2 AUTOMATIC TRANSFER
OPERATION
To select automatic operation, do the following:
1. Make sure the transfer switch main contacts are set to their UTILITY position, i.e., loads con­nected to the utility power source (Figure 3.2).
2. Be sure that normal UTILITY power source volt­age is available to transfer switch terminal lugs N1 and N2 (Refer to the Electrical Data section).
3. Set the generator’s AUTO/OFF/MANUAL switch to AUTO.
4. Set the generator’s main circuit breaker to its ON (or CLOSED) position.
With the preceding steps complete, the generator will start automatically when utility source voltage drops below a preset level. After the unit starts, loads are transferred to the standby power source. Refer to the Sequence of Automatic Operation section.
16
Section 3 — Operation
Air-cooled Generators
3.3 SEQUENCE OF AUTOMATIC OPERATION
The generator’s control panel houses a control logic circuit board. This board constantly monitors util­ity power source voltage. Should that voltage drop below a preset level, circuit board action will signal the engine to crank and start. After the engine starts, the circuit board signals the transfer switch to acti­vate and connect load circuits to the standby power supply (load terminal lugs T1/T2 connect to terminal lugs E1/E2). Refer to the Electrical Data section.
The generator must run at 50 Hz or greater for the transfer output to be activated. Once activated, it will remain active even if the frequency dips below 50 Hz.
Upon restoration of utility source voltage above a preset level, generator circuit board action signals the transfer switch to transfer loads back to that power supply. After retransfer, the engine is signalled to shut down.
The actual sequence of operation is controlled by sensors and timers on a control logic circuit board, as follows:
A. Utility Voltage Dropout Sensor
• This sensor monitors utility source voltage.
• If utility source voltage drops below about 65 percent of the nominal supply voltage, the sensor energizes a 10 second timer.
• Once the timer has expired, the engine will crank and start if utility is still low.
B. Engine Warm-up Time Delay
• This mechanism lets the engine warm up for about five (5) seconds before the load is trans­ferred to the standby source.
C. Standby Voltage Sensor
• This sensor monitors generator AC output volt­age. When the voltage has reached 50 percent of the nominal rated voltage, transfer to standby can occur.
D. Utility Voltage Pickup Sensor
• This sensor monitors utility power supply volt­age. When that voltage is restored above 75 per­cent of the nominal source voltage, a retransfer time delay starts timing.
E. Retransfer Time Delay
• This timer runs for about 15 seconds.
• At end of a 15-second delay, circuit board action de-energizes transfer relay in the transfer switch if utility is still present.
• Retransfer to utility power source then occurs.
F. Engine Cool-down Timer
• When the load is transferred back to utility power source, the engine cool-down timer starts tim­ing.
• The timer will run for about one minute, and the generator will then shut down.
3.4 MANUAL TRANSFER OPERATION
3.4.1 TRANSFER TO GENERATOR
POWER SOURCE
To start the generator and activate the transfer switch manually, proceed as follows:
1. Set the generator’s AUTO/OFF/MANUAL switch to OFF.
2. Set the generator’s main circuit breaker to its OFF (or OPEN) position.
3. Turn OFF the utility power supply to the transfer switch using the means provided (such as a utility main line circuit breaker).
DANGER
Do not attempt to activate the transfer switch
manually until all power voltage supplies to the switch have been positively turned off. Failure to turn off all power voltage supplies may result in extremely hazardous and possibly fatal elec­trical shock.
4. Use the manual transfer handle inside the trans­fer switch to move the main contacts to their STANDBY position, i.e., loads connected to the standby power source (Figure 3.2).
5. To crank and start the engine, set the AUTO/OFF/ MANUAL switch to MANUAL.
6. Let the engine stabilize and warm up for a few minutes.
7. Set the generator’s main circuit breaker to its ON (or CLOSED) position. The standby power source now powers the loads.
Figure 3.2 – Manual Transfer Switch Operation
17
Section 3 — Operation
Air-cooled Generators
3.4.2 TRANSFER BACK TO UTILITY POWER
SOURCE
When utility power has been restored, transfer back to that source and shut down the generator. This can be accomplished as follows:
1. Set the generator’s main circuit breaker to its OFF (or OPEN) position.
2. Let the engine run for a minute or two at no-load to stabilize the internal temperatures.
3. Set the generator’s AUTO/OFF/MANUAL switch to its OFF (or OPEN) position. The engine should shut down.
4. Check that utility power supply to the transfer switch is turned OFF.
DANGER
Do not attempt to activate the transfer switch
manually until all power voltage supplies to the switch have been positively turned off. Failure to turn off all power voltage supplies may result in extremely hazardous and possibly fatal electrical shock.
5. Use the manual transfer handle inside the trans­fer switch to move the main contacts back to their UTILITY position, i.e., loads connected to the util­ity power source (Figure 3.2).
6. Turn ON the utility power supply to the transfer switch using the means provided.
7. Set the system to automatic operation as outlined in Automatic Transfer Operation section.
3.5 SETTING THE EXERCISE TIMER
This generator is equipped with an exercise timer. Once it is set, the generator will start and exercise once every seven days, on the day of the week and at the time of day the following sequence is completed. During this exercise period, the unit runs for approx­imately 12 minutes and then shuts down. Transfer of loads to the generator output does not occur during the exercise cycle unless utility power is lost.
A switch on the control panel (see Figure 3.1) per­mits selection of the day and time for the system to exercise. At the chosen time, perform the following sequence to select the desired day and time of day the system will exercise. Remember seasonal time changes affect the exercise time settings.
1. Verify that the AUTO/OFF/MANUAL switch is set to AUTO.
2. Press and hold the "Set Exercise Time" switch for several seconds, then release. All the red LED's will flash for approximately 10 seconds and then stop.
3. Once the red LED's stop flashing, the generator will start and run for approximately 12 minutes and then shut down. The exerciser is now set to run at this time of day each week.
Example: If the "Set Exercise Time" switch is
pressed on Saturday afternoon at 2:00 p.m., the generator will start and exercise for approximate­ly 12 minutes every Saturday at 2:00 p.m..
NOTE:
The exerciser will only work in the AUTO mode and will not work unless this procedure is per­formed. The exerciser will need to be reset every time the 12-volt battery is disconnected and then reconnected, and when the 15A fuse is removed.
The 16kW unit has a low speed exercise option. Dip switch 1 on the control board is factory set to OFF. This allows the engine to run at a slower speed dur­ing weekly exercise periods for quieter operation. If this Dip switch is set to ON, the generator will exer­cise at it's normal speed.
This DIP switch position is only read at board power up. If the DIP switch position is changed, power to the board must be cycled for the micro controller to recognize the new DIP switch position.
Low speed exercise will be handled as follows:
1. The standard start sequence will be initiated.
2. The unit will run at 2,400 RPM.
3. If utility is lost during exercise, the controller will do the following:
• Wait 10 seconds for utility to return.
• If utility returns within 10 seconds, continue to exercise at 2,400 RPM.
• If utility is still lost after 10 seconds, run the engine up to 3600 RPM and transfer the load. At this time the controller will exit the exercise routine and assume full automatic operation.
3.6 PROTECTION SYSTEMS
3.6.1 LOW OIL PRESSURE SWITCH
This switch (Figure 3.3) has normally closed con­tacts that are held open by engine oil pressure dur­ing cranking and operating. Should oil pressure drop below the 8 psi range, switch contacts close, and the engine shuts down. The unit should not be restarted until oil is added. The AUTO/OFF/MANUAL switch must then be turned to OFF and then back to AUTO.
18
3.6.2 HIGH TEMPERATURE SWITCH
This switch’s contacts (Figure 3.3) close if the tem­perature should exceed approximately 144º C (293º F), initiating an engine shutdown. The generator will automatically restart and the LED on the generator control panel will reset once the temperature has returned to a safe operating level.
Figure 3.3 – Low Oil Pressure and
High Temperature Switches
19
4.1 FUSES
The 15-amp fuse on the generator panel protects the DC control circuit against overload (Figure 4.1). This fuse is wired in series with the battery output lead to the panel. If this fuse element has melted open, the engine will not be able to crank or start. Replace this fuse using only an identical 15-amp replacement fuse. To replace the fuse, push the fuse holder cap down and rotate it counterclockwise. Whenever the fuse is removed or replaced, the exercise timer needs to be reset.
Figure 4.1 – Generator Control Panel
CONTROL AND INFORMATION CENTER
SYSTEM SET
LOW BATTERY
OFF
AUTO. MAN.
SYSTEM FUSE
15A
ASSY: 0F8418/0F8419
SET
EXERCISE
TIME
LOW OIL
HIGH TEMP
OVER SPEED NO RPM SENSE IF FLASHING
OVER CRANK
FLASHING GREEN LED= NO UTILITY SENSE 5 FLASHING RED LEDS= EXERCISER NOT SET
4.2 CHECKING THE ENGINE
Figure 4.2 — Oil Dipstick and Fill, 7kW
Oil Dipstick and Fill
Figure 4.3 — Oil Dipstick and Fill, 10kW
OIL LEVEL
For oil capacities, see the Specifications section. For engine oil recommendations, see the Engine Oil Recommendations section. To check the engine oil level, proceed as follows (Figures 4.2, 4.3 and 4.4):
1. Move the AUTO/OFF/ MANUAL switch to the OFF position.
2. Remove the dipstick and wipe it dry with a clean cloth.
3. Completely insert the dipstick; then, remove it again. The oil level should be at the dipstick “Full” mark. If necessary, add oil to the “Full” mark only. DO NOT FILL ABOVE THE “FULL” MARK.
Never operate the engine with the oil level
below the “Add” mark on the dipstick. Doing this could damage the engine.
4. Install the dipstick.
5. Reset the AUTO/OFF/MANUAL switch to its origi­nal position.
20
Loading...
+ 50 hidden pages