Gems Sensors & Controls SERIES 35XX Instruction Bulletin

GEMS SENSORS & CONTROLS
OPERATING & INSTALLATION INSTRUCTIONS
SERIES 35XX
PLEASE READ CAREFULLY BEFORE INSTALLING
Part Number: 560550-0128 Issue: A
INTRODUCTION
Series 35XX high output pressure transducers and transmitters are fitted with an Asic providing various optional (at time of order) voltage outputs, and a 4-20mA current output capable of being used in control and indicating loops without further amplification.
Series 35XX with the CE Mark conform with the essential protection requirements of the EMC Directive 2004/108/EC by certified type testing to BS EN61326-1:2006 and EN61326-2-3:2006.
Series 35XX with the CE0086 mark also complies with the requirements of the Pressure Equipment Regulations 1999 and is classed as a safety accessory and can be used as a safety­related device on Category IV pressure equipment. No other product should be used as “Safety Accessories” as defined by the PED Article 1, Paragraph 2.1.3.
HAZARDOUS PRODUCTS
The Consumer Protection Act of 1987, Section 6 of the Health and Safety at Work Act 1974 and the Control of Substances Hazardous to Health Regulations 1988 require that we advise recipients and users of our products of any potential hazards associated with their storage, handling or use.
The products which our Company supplies may be classified as Electrical, Electro-Mechanical and Electronic equipment.
These products are tested and supplied in accordance with our published specifications or individual special requirements that are agreed in writing at time of order. They are constructed so as not to affect adversely the safety of persons and property when properly installed, maintained and used by qualified personnel, in the applications for which they were designed and manufactured.
Conformity with the requirements of the CE mark only applies when the installation conditions described in these instructions have been met. For units supplied without a cable assembly connection to the transducer must be accomplished using Gems Sensors approved cable. See APPROVED CABLE section.
GENERAL
* Transducer should not be subjected to greater than the maximum allowable pressure (P.S.)
/ Temperature (T.S) as defined on the transducer label.
* Transducer should not be subjected to mechanical impact.
* In the event of fire the end user must ensure that the system pressure is vented to a safe
area.
* The effects of decomposition of unstable fluids should be considered by the user when
560550-0128 Issue A Page 1 of 4
placing this device in service.
* The pressure transducer has no means of draining or venting, this must be performed by
another component in the end users system.
* Pressure range must be compatible with the maximum pressure being measured.
* Pressure media must be compatible with the transducer/transmitter wetted parts listed in
these instructions.
* Liquid must not be allowed to freeze in the pressure port.
* The gasket must be fitted under the electrical connector (mini-din only).
* Supply voltage must not exceed the value stated on the unit label.
MECHANICAL INSTALLATION Mounting: Pressure Transducer is designed to be attached by the coupling thread only. Omni-
directional, self supported directly into the pipework. Use a 22mm spanner on the hexagon provided to apply a maximum torque of 15Nm. The Customer must ensure that the pressure seal is suitable for the application. If in doubt contact Gems Sensors.
ELECTRICAL INSTALLATION
All types with the CE Mark include suppression devices providing EMC protection to EN 61000­4-2, EN 61000-4-3, EN 61000-4-4 and EN61000-4-6. Conformity with the requirements of the CE mark only applies when connection is made with Gems Sensors approved cable, see APPROVED CABLE section, and is connected as shown below:-
APPROVED CABLE
Gems sensors uses cables comprising 2, 3 or 4 colour-coded cores, enclosed by an aluminised polyester screen where the screen is in intimate contact with a separate drain wire. The outer sheath is chrome PVC and overall diameter is approximately 4 mm.
OPERATION
Having installed the transducers as instructed, they are ready for use. The transducer should not
be removed whilst the system is at pressure. Before applying power, check that the correct
polarity and excitation levels are being applied. See Table 1 for electrical connections.
CALIBRATION
Transducers are calibrated to the datum requested at time of order; this can be identified by the sixth letter of the identification code as follows:-
A - Absolute datum G - Gauge datum vented to atmosphere via the electrical connector or cable
LOAD CHARACTERISTICS (4-20mA Current Output)
The total resistive load in the loop (to include all the cable resistance) can be from 'zero to 50 x (supply volts -7.5) ohms' e.g. with a 24V d.c. supply the permissible load is from zero up to 825 ohms.
560550-0128 Issue A Page 2 of 4