LS-2050/LS-52100 Series
Side-Mounted Level Switches
Instruction Bulletin No. 72950
Units are side-mounted in the tank at the point of high, low or intermediate level sensing. Ideal for tanks with "hard-to-get-at" tops or bottoms. Float and cam action is positive. Standard versions are U.L. Recognized - File No. E45168. Explosion-proof units are approved for Class I, Division I, Group D hazardous areas.
Electrical Connection . . .
Electrical connection is provided by wire leads with 1/2" NPT or junction box with 1/2" NPT.
Typical Wiring Diagrams . . .
Important Points!
Product must be maintained and installed in strict accordance
with the National Electrical Code and GEMS technical brochure and instruction bulletin. Failure to observe this warning could re­sult in serious injuries or damages. An appropriate explosion-proof enclosure or intrinsically safe interface device must be used for hazardous area appli­cations involving such things as (but not limited to) ignitable mixtures, combustible dust and flammable materials. *** Warning: To prevent ignition of flammable or combus­tible atmospheres, disconnect power before servicing. Pressure and temperature limitations shown on individual catalog pages and drawings for the specified level switches must not be exceeded. These pressures and temperatures take into consideration possible system surge pressures/tem­peratures and their frequencies. Selection of materials for compatibility with the media is critical to the life and operation of GEMS level switches. Take care in the proper selection of materials of construction; par­ticularly wetted materials.
P/N 72950
Rev. P
Life expectancy of switch contacts varies with applications. Contact GEMS if life cycle testing is required. Ambient temperature changes do affect switch set points, since the specific gravity of a liquid can vary with temperature. Level switches have been designed to resist shock and vibration; however, shock and vibration should be minimized. Liquid media containing particulate and/or debris should be filtered to ensure proper operation of GEMS products. Electrical entries and mounting points may require liq­uid/vapor sealing if located in an enclosed tank. Level switches must not be field repaired. Physical damage sustained by the product may ren­der it unserviceable.
Standard Versions
Explosion-Proof Versions
FM Approved
CSA Listed
LS-2050's
30288 30290 48068 48069
----
55690
----
----
----
55690
----
----
LS-52100's
52100 116971 116972
*
See "Electrical Data" on next page for more information
121753
----
----
121753
----
----
**100 VA switches are not UL recognized or CSA listed
Specifications . . .
Stem & Mtg Material Float Material
Other Wetted
Materials
Operating Temp °F
PSIG, Max. @ 70°F Mounting Attitude
Switch Differential (In Liquid)
Liquid Specific Gravity Lead Wires
Brass
Buna N
316 SS,
Beryllium Copper,
Teflon,
Ceramic
Water: To +180°F
Oil: -40° to +250°F
1/2" Min.
.8 Min.
LS-2050 LS-52100
150
Horizontal: ±15°
#18 AWG, 24" L., Polymeric
Switch*
SPDT, 20 VA SPDT, 20 VA
SPST, 100 VA, N.O. SPST, 100 VA, N.C.**
SPDT, 20 VA
SPST, 100 VA, N.O. SPST, 100 VA, N.C.**
316 SS 316 SS
316 SS 304 SS
SS,
Teflon,
Ceramic
Teflon,
Ceramic
-40°F to +300°F
900
500
Approx. 3/4"
.9 Min. .85 Min.
**
**
Dimensional Data . . .
LS-2050 Series (Brass/Buna N
1/2" NPT
3-7/16"
(87.3 mm)
LS-2050 Series (All Stainless Steel)
1"
NPT
LS-52100 Series
1"
NPT
5-9/32" Approx. (134.1 mm)
Approximate Actuation Level - Contacts Transfer
1"
NPT
7/8"
(22.2 mm)
1-3/8"
(34.8 mm)
Approximate Actuation Level ­Contacts Transfer on Ascending Level
5-1/16"
(128.6 mm)
on Ascending Level
1"
(25.4 mm)
4-1/8"
Approx.
(104.8 mm)
Approximate Actuation Level ­Contacts Transfer on Ascending Level
5-1/16"
(128.6 mm)
1"
(25.4 mm)
5/8"
2-3/8" ±1/8"
(60.3 mm)
3-5/8"
Approx.
(92.0 mm)
3-1/4"
Approx.
(82.5 mm)
To Install LS-52100 Series or LS-2050 Series Units with Buna N Float . . .
Insert unit from the outside through 1" NPT boss in the
Float In
Actuating
Position
tank side and tighten so that the arrow on the unit housing is pointing upward. Important: Units should be installed in environments free from excessive contamination and high shock.
Arrow Must
Point Upward
Float In
Dry Position
To Install LS-2050 Series Units with Stainless Steel Float . . . (Use either Method A or Method B shown below)
Arm
Arm
Float
2" NPT
Boss
Inside
of Tank
Lockwasher
Float
Method A: From outside of tank. Unscrew and remove float and lockwasher from unit arm. Thread a 2" to 1" NPT reducer (by others) onto unit and reassemble float and lockwasher. Insert unit and reducer in 2" NPT boss in tank side and tighten so that arrow on unit housing points upward.
Method B: When inside of tank is accessible. Unscrew and remove float
and lockwasher from unit arm. Insert unit in 1" NPT boss in tank and tighten so that arrow on housing points upward. Reas­semble float and lockwasher on unit arm from inside of tank.
2" to 1" NPT
Reducer
Arrow Must
Point Upward
Arrow
Must Point
Upward
Lockwasher
1" NPT
Boss
Electrical Data . . .
Switch Ratings - Max. Resistive Load
VA Amps DC
Volts
0-30
20
120 240
100*
This product is suitable for Class I and Class II applications only, per the requirements of standard EN60730 and any additional specific requirements for a particular application or medium being sensed. Class I compliance of metal bodied units requires a ground connection between the metal body and the earthing system of the installation. Class I compliance of plastic bodied units in contact with a conductive medium requires that the medium be effectively earthed so as to provide an earthed barrier between the unit and accessible areas. For Class III compliance, a supply at safety extra-low voltage (SELV) must be provided. Please consult the Factory for compliance information on specific part numbers.
The product is designed and manufactured in accordance with Sound Engineering Practice as defined by the Pressure Equipment Directive 97/23/EC. This product must not be used as a “safety accessory” as defined by the Pressure Equipment Directive, Article 1, Paragraph 2.1.3. The presence of a CE Mark on the unit does not relate to the Pressure Equipment Directive.
120 240
Amps A.C.
.4 .17 .08
.8**
.4
European Pressure Directive
.3 .13 .06
N.A. N.A.
* 100 VA switches are not U.L.
Recognized or CSA listed
**Limited to 50,000 operations.