Gems Sensors & Controls ELS-1150 Operating Manual

Instruction Bulletin No. 196361
ELS-1150 Series
Electro-Optic Level Switch
(Carbon Steel & St ainless Steel)
Rev B
Installation
1a. 3/4" Straight Thread Switch: Thread sensor into tank
wall and tighten by hand. Tighten to a maximum torque of 15 ft-lbs.
1b. 1/2" NPT Switch: Apply a curing type thread sealant (such
as Loctite #565 with primer "N"), which is compatible with the liquid media. We do not recommend pipe tape. For Carbon Steel units torque one to two turns (maximum) past the hand-tight engagement. For Stainless Steel units torque one turn (maximum) past the hand-tight engagement.Over
T orque of sensor can permanently damage sensor.
2. Sensor may be installed horizontally or up to 45° from horizontal, only . (See Figure 1)
3. Do not install sensor close to infrared sources.
4. Prism surface must be at least 2" from any reflective sur-
faces.
5. Connect appropriate voltage supply to red lead. For 12 VDC units, connect to 12 VDC ±5%. For 5 VDC units, connect to 5 VDC ±5%. For 24 VDC units, connect to 24 VDC ±5%.
6. Inductive loads must be diode-suppressed.
Mounting Attitude
These units must be mounted horizontally or up to 45° from horizontal, ONLY.
Specifications
Materials Housing Prism Operating Pressure Operating Temperature Current Consumption
Output
Electrical Termination
Repeatability Approvals
Note: Not for use in freezing liquids
Nickel-Plated Carbon Steel or 316SS Fused Glass 0 to 2500 psig, Max.
-40°F to 212°F (-40°C to 100°C) 5V ~22 mA No Load 12V ~34mA No Load 24V ~36mA No Load Open Collector Output,
18 mA Sink Max.
22 AWG, Polymeric, 12” to 14” Extended Lead Wires
±1 mm Units Labeled U.L. File E108913
C.E. EN 61326
Scale: Full
- Figure 1 -
Typical Wiring Diagram
R
LED
Output
+12 VDC or +5 VDC
Note
Inductive loads must be diode-suppressed.
Maintenance
Up to
45°
+5 VDC or +12 VDC or +24 VDC
Red White Black
Red
LOAD
18 mA
Max.
White Black
Sensor may require a periodic cleaning of prism surface. A mild detergent may be used to clean prism surface.
SENSOR
SENSOR
ELS-1150
(Mounting: 1/2” NPT Thread)
ELS-1150
(Mounting: 3/4” 16 UNJF-3A Fitting)
1.38” Ref.
1/2” NPT
7/8” HEX
Red = +12 or +5 VDC Input White = Output Black = Ground
Wire, #22 AWG, Polymeric (Unless otherwise specified, leads will be 12” to 14”
3/4” - 16UNJF-3A
O-Ring
1.38” Ref.
Red = +12 or +5 VDC Input White = Output Black = Ground
Wire, #22 AWG, Polymeric (Unless otherwise specified, leads will be 12” to 14”
Mounting Notes
1. Thread and O-Ring seal configu-
7/8”
HEX
ration per MS33656. Uses #3-908 size O-ring.
2. Mating tube fitting per MS-33649
3. Installation torque not to exceed 15 ft-lbs
This product complies with EN61326 Electrical Equipment for Measurement, Control and Laboratory use - EMC Requirements for Minimum Requirements and Industrial Locations. Special caution should be taken to meet EN61000-4-5 Surge Immunity if any of the following conditions apply to the installation: The product is installed outside; the cable is greater than 30 meters in length. In order to meet the Surge Immunity requirements, the following conditions must be followed during installation:
1. Shielded cable must be used, and the shield must be tied to earth ground (not power supply ground) on at least one end of the cable shield/drain wire. The shield must be maintained all the way from sensor to the power supply.
2. If unshielded cable is used, an earth grounded metal conduit can be used to replace the shielded cable.
3. For the sensor with metal body or enclosure the body/enclosure must be grounded to earth. If a protective metal housing is used, the metal housing should be grounded to earth.
4. If a protective plastic housing is used, the housing must be able to withstand at least 2 kV from the housing to earth ground.
Return Policy
Returns are accepted on stock items up to 30 days from date of order. You must contact our Returns Department for a Return Authoriza­tion (RA) number. Return the goods - freight prepaid - in the original container and include original packing slip. C. O. D. returns are not accepted. Gems reserves the right to apply restocking charges.
Tel: 860-793-4357 Fax: 860-793-4563
· Gems products must be maintained and installed in strict accordance with the National Electrical Code and the applicable Gems Product Instruction Bulletin that covers installation, operation and proper main­tenance. Failure to observe this information may result in serious injury or damages.
· For hazardous area applications involving such things as, but not limited to, ignitable mixtures, combustible dust and flammable materials, use an appropriate explosionproof enclosure or intrinsically safe interface device.
· Please adhere to the pressure and temperature limitations shown through­out this catalog for our level and flow sensors. These limitations must not be exceeded. These pressures and temperatures take into con­sideration possible system surge pressures, temperatures and their frequencies.
· Selection of materials for compatibility with the media is critical to the life and operation of Gems products. Take care in the proper selection of materials of construction, testing is required.
Important Points:
· NSF-approved sensors are made of materials approved for potable wa­ter applications according to Standard 61.
· Stainless steel is generally regarded as safe by NSF and FDA.
· Life expectancy of switch contacts varies with application. Contact Gems if life cycle testing is required.
· Ambient temperature changes do affect switch set points, since the gravity of a liquid can vary with temperature.
· Our sensors have been designed to resist shock and vibration. However, shock and vibration should be minimized.
· Filter liquid media containing particulate and/or debris to ensure the proper operation of our products.
· Electrical entries and mounting points in an enclosed tank may require liquid/vaporsealing.
· Our sensors must not be field-repaired.
· Physical damage sustained by product may render it unserviceable.