Gems Sensors & Controls 67 Operating Manual

Page 1
Notes:
Form 670
Sheet P/N 100501-1
Rev. F
Warrick® Series 67
Intrinsically Safe Multi-Function Control
Installation and Operation Bulletin
Table of Contents
Page 3 Installation Instructions: Safe Sensing Circuits- General Information
- Wiring
Page 4 Installation Instructions: Intrinsically Safe Sensing Circuits
- Grounding
- Sensor Wiring
Page 5 Installation Instructions: Intrinsically Safe Sensing Circuits
Page 6 Installation Instructions: Intrinsically Safe Sensing Circuits
- Alarm Channel Wiring
- Alternation Circuitry
Page 7 Installation: High Voltage Circuits
- AC Supply
- Grounding
- Output Contacts
Page 8 Control Diagram
Page 9 Technical Information
- Specification
- Ordering Information
- Module Replacement
Page 10 Technical Information
- Module Replacement
Page 11 Operation Instructions
- Single Level Service: Contact Operation
- Single Level Service: Alarm Functions
Page 12 Operation Instructions
- Differential Level Service: Simplex
Page 13 Operation Instructions
- Differential Level Service: Duplex
Gems Sensors Inc. One Cowles Road Plainville, CT 06062-1198 Tel: 860-793-4579 Fax: 860-793-4580
Page 14 General Control Information
Page 15 Sample Wiring Diagram
Page 2
Notes:
Sample Wiring Diagram
L1
Ground
C
C
C
Ch 4
Ch 3
Alarm
NC
NC
NC
Figure 5
G L2 L1 NO C NC
Pump #2
Starter
Circuit
L1
High
Level
Low
Level
Bell
Pump #1
Starter Circuit
Non-Hazardous Area
Hazardous
Area
C NO NC
Channel 4 Channel 3 Channel 2 Channel 1
Ch 4 Ch 3 Ch 2 CH1
LED LED LED LED
S4 G S3 HS2 G LS2 HS1 G LS1 2-1 1-2 G SIL
C NO NC C NO NC C NO NC
DIP Switch
Alternate
2-1 1-2
Down Pump Up
Silence
Auto
1-2 2-1
Series
67C1C0A
Control
Note: For applications that do not require duplex alternation, a jumper must be placed from “G”
to “1-2 terminal
Non-Hazardous Area
Hazardous Area
High Level
Alarm
2
Standby
Pump Start
Duty Pump
Start
Pump(s)
Stop
Low Level
Alarm
15
Page 3
Control Diagram
Technical Information
Figure 2
AC Supply
G L2 L1 NO C NC
Load 4* Load 3* Load 2* Load 1*
C NO NC
C NO NC C NO NC C NO NC
CH 3/4 Alarm
* Form A & B contacts available
SPECIFICATIONS
Contact Design: Standard SPDT (1 form C): one normally open (N.O.) and one normally closed (N.C.),
non powered contacts Contact Ratings for each channel. Optional 1 Form A (N.O.) and 1 Form B (N.C.) isolated Load Contact Ratings: Standard Form C- 10A @ 120/240 VAC resistive and 30 VDC resistive, 1/3 Hp @ 120/ 240 VAC. Optional Form A & B - 5A @120/240 VAC and 30 VDC resistive, 1/8 Hp @ 120/240 VAC.
Bell Contacts: 1 Form C (N.O.), N.C., C) Bell Contact Ratings: 10A @ 120/240 VAC and 30 VDC resistive, 1/3 Hp @ 120/240 VAC Contact Life: Mechanical - 10 million operations. Electrical - 1,000,000 operations minimum at rated load. Primary Voltage: 120 or 240 VAC models + 10% - 15%, 50/60 Hz. Supply Current: Relays energized - 60ma @ 120 VAC, 30ma @ 240 VAC Secondary Circuit: 12 VAC RMS voltage on probes, 6ma current RMS. Sensitivity: Models operate from 4700-100,000 ohms maximum specific resistance
Temperature: -40° to 150° F Ambient Electronics Module: Solid state components enclosed in a black nylon housing Terminals: Standard Form C removable terminal strip containing a size 4 pan head screw with a clamping plate.
Will accept up to two (2) #14 AWG wires per terminal. Optional Form A & B relay board will accept up to one (1) #14 AWG wire per terminal. Use copper (60-75° C) wire only. Torque to 20 inch pounds.
Listings: U.L. Intrinsically Safe (UL 913) File Number: E87112
ORDERING INFORMATION
67 X X X X X
Channel 4 Channel 3 Channel 2 Channel 1
Ch 4 Ch 3 Ch 2 CH1
LED LED LED LED
Non-Hazardous
Area
Hazardous Area
Note: For applications that do not require duplex alternation, a jumper wire must be placed from the “G” to “1-2” terminal.
S4 G S3 HS2 G LS2 HS1 G LS1
Ch 4 Ch 3 Ch 2 CH1
{
{
Sensors
DIP Switch
{
Alternate
2-1 1-2
2-1 1-2 G SIL
Down Pump Up
Silence
Auto
1-2 2-1
O N
A L A R M
O
4
F F
343 2
DIP Switch Blow Up
I
M O D E
D
1
4.7K
A
10K
B
26K
C
50K
D
100K
E
1
120 VAC
2
240 VAC
1 Form A & B (N.O.) & N.C. Isolated) for
A
each channel
1 Form C (N.O., N.C.)
C
for each channel
0
1
4
None
NEMA 1
NEMA 4
A
AC on Probe Circuit
D
DC on Probe Circuit
MODULE REPLACEMENT
If the electronic module needs to be replaced:
1. Turn off power to the control and load devices
2. Remove the metal partition located across the center of the module ( when required).
3. Remove all field wiring terminal blocks from the electronic module. The field wires do not need to be removed from the terminal blocks. The terminal blocks separate from the board as show in figure 8-1.
4. Remove the four (4) retaining screws from the base of the electronic module. The module can now be re­moved from the control panel.
5. Install a new module and reinstall all of the terminal blocks.
6. Reinstall the metal partition (when required).
7. Set all DIP switches according to previous instructions.
8
9
Page 4
Technical Information: Module Replacement
Installation: High Voltage Circuits
Terminal Strip
Removal
Diagram 3
A.C., Form C Load Contacts
and Sensor Terminals
A.C. SUPPLY:
Connect the incoming supply HOT lead to the L1 terminal, NEUTRAL lead to the L2 terminal and EARTH GROUND lead to the “G” Terminal. Note: the incoming power supply should have the same electrical characteris­tics as indicated on the control’s label.
GROUNDING
Terminal “G” on the supply line/load side terminal strip is a redundant system ground terminal and must be con­nected to the earth ground buss of the panel’s AC supply line feeder.
OUTPUT CONTACTS
Channels 1-4: Each channel has a dedicated non-powered contacts. These can be either Form C or Form A & B depending on the model. These contacts will change state when their respective channel activates. In DIRECT mode the relay will energize and the contacts will change state when the probe circuit sensor closes. In INVERSE mode the relay will energize and contacts will change state upon power up. The channel will then de-energize and return the contacts to their shelf state when the probe circuit sensor closes.
Form C- This contact configuration consists of one (1) Normally Open contact and one (1) Normally Closed contact. There are three terminals for electrical connections, N.O., N.C. and Common. Each terminal will accept up to two (2) #14 AWG wires
Form A & B: This contact configuration consists of one (1) Normally Open contact and one (1) Normally Closed contact which are electrically isolated from each other. There are two terminals for each contact. Each will accept one (1) # 14 AWG wire.
Form A & B Contacts
Separation
Point
Terminal Strip
Removal
Separation
Point
Field wiring
Field wiring
Alarm Bell: The alarm bell contacts are non-powered Form C construction. This contact configuration consist of consists of one (1) Normally Open contact and one (1) Normally Closed contact. There are three terminals for electrical connections, N.O., N.C. and Common. Each terminal will accept up to two (2) #14 AWG wires
When the output contacts are used to drive loads they should be wired in series with the load. This series branch circuit should then be connected across a power source compatible with the load. See figure 1.
Figure 1
Alarm Bell Contacts
See Output Board Options
N.C. N.O.CGL2L1
Close
on
Fault
VAC or 10 A @ 30 VDC
Open
on
Fault
Hot
Neutral
Channel 1
N.C.N.O. N.C.N.C.N.C. N.O.N.O.N.O.
Load Contacts
Series 67 - Option A
Contact Board
Channel 2
N.C.N.O.
Load
1/8 Hp 120, 240 VAC 5A @ 120/240
VAC or 5 A @ 30 VDC
Channel 4Channel 3
Load
Series 67 - Option C
Contact Board
Channel 1
N.C. N.O. N.C.N.C.N.C.C N.O.N.O.N.O. CCC
Channel 2
Load
1/3 Hp 120, 240 VAC 10A @ 120/240
VAC or 10 A @ 30 VDC
Channel 3
N.C. N.O. C
Load
Channel 4
Open & Close on Fault Contacts Rated
1/3 Hp 120, 240 VAC 10 A @ 120/240
Earth Ground
10 7
Page 5
Installation: Intrinsically Safe Sensing Circuits
Operation Instructions
ALARM CHANNEL WIRING:
SILENCE CIRCUITRY:
A normally open pushbutton is required for the Series 67’s alarm silence circuitry. The N.O. pushbutton must be connected to the “SIL” and “G” terminals. For more information about the operation of the silence circuitry consult the Alarm Operation section on page 11. NOTE: THE SILENCE PUSHBUTTON IS CONNECTED TO THE
INTRINSICALLY SAFE CIRCUITRY. THEREFORE THE PUSHBUTTON AND ITS ASSOCIATED WIRING SHOULD BE SEPARATED FROM THE NON-INTRINSICALLY SAFE WIRING AND DEVICES. CONSULT GENERAL WIRING INFORMATION FOR MORE INFORMATION.
ALARM DIP SWITCHES:
The alarm DIP switches for channels 3 and 4 can be set to enable the bell contacts for one or both alarm channels. However, this does not disable the alarm contact for that channel. Table 4 covers the DIP switch settings for various alarm conditions.
Table 4
DIP Switch Settings
3
Off - Down
4
Off - Down
3
On - Up
4
Off - Down
3
On - Up
4
On - Up
3
Off - Down
4
On - Up
Bell Contact Status
Channel 3 - Off - Disabled
Channel 4 - Off - Disabled
Channel 3 - On - Enabled
Channel 4 - Off - Disabled
Channel 3 - On - Enabled
Channel 4 - On - Enabled
Channel 3 - Off - Disabled
Channel 4 - On - Enabled
The Series 67 multi-function control can be used for many different applications including: pump control, solenoid valve control and alarm activation. The following instructions cover the most common applications. If your application is not included, contact Gems Sensors or our authorized representative in your area for assistance.
The operating instructions are broken up into two general categories: SINGLE and DIFFERENTIAL LEVEL SERVICE. The alarm functions are covered under the SINGLE LEVEL SERVICE heading while the pumping and solenoid valve functions are covered under the DIFFERENTIAL LEVEL SERVICE heading.
SINGLE LEVEL SERVICE: CONTACT OPERATION
LOAD CONTACTS: CHANNELS 1-4
The activation of these contacts is dependent upon the type of sensor (normally open or closed) and the mode of operation (direct or inverse). The table 6 gives the sensor activation condition, DIP switch settings, contact status and LED status for various applications and sensors.
Table 6
Application
High Level Alarm Normally Open Float
High Level Alarm Normally Closed Float
Low Level Alarm Normally Open Float
Low Level Alarm Normally Closed Float
Warrick Sensor
FE - Reed Switch Float for M Tilt Float
FE - Reed Switch Float for M Tilt Float
FE - Reed Switch Float for M Tilt Float
FE - Reed Switch Float for M Tilt Float
Sensor” Alarm
Activation Condition
Closes on Rising Level
Opens on Rising Level
Opens on Falling Level
Closes on Falling Level
DIP Switch
Setting
Inverse UP “I”
Direct DOWN “D”
Direct DOWN “D”
Inverse UP “I”
Relay Status
Upon Alarm
De-Energized
De-Energized
De-Energized
De-Energized
LED Status
Upon Alarm
ON
OFF
OFF
ON
ALTERNATION CIRCUITRY
AUTO OR MANUAL:
Series 67’s built-in alternator can be used to automatically alternate between two loads controlled by channels 1 and 2. However, the automatic alternation may be by-passed to become a manual operation. This can be accomplished with the use of jumper wires or a three position switch connected to the 2-1, 1-2 and “G” termi­nals. Table 5 covers the jumper connections for manual alternation. Refer to figure 1 for more wiring informa­tion on the wiring of the three position selector switch. NOTE: THE MANUAL ALTERNATION CIRCUITRY IS
CONSIDERED INTRINSICALLY SAFE. THEREFORE THE SELECTOR SWTICH, JUMPER WIRES AND THEIR ASSOCIATED WIRING SHOULD BE SEPARATED FROM NON-INTRINSICALLY SAFE WIRING DEVICES. CONSULT GENERAL WIRING INFORMATION FOR MORE INFORMATION ON INTRINSIC SAFETY.
Alternation
Status
Automatic*
Manual 1-2
Manual 2-1*
Required
Terminals 1-2 to “G”
Terminals 2-1 to “G”
* For non-alternation applications jumper 1-2 to “G”
** The position of the 1-2 and 2-1 indicating LED’s is dependent on the application. The position changes for pump-up or pump-down. Consult control diagram figure 6-1 for more information.
Jumper
None
Table 5
Notes
LED Status
Pump-Down*
Either
**
No. 1
No. 2**
LED Status
Pump-Up*
Either
**
No. 1
No. 2**
High Level Alarm Conductance Probes
Low Level Alarm Conductance Probes
UNKNOWN SENSOR Normally Open
UNKNOWN SENSOR Normally Closed
3R, 3T, 3W, 3Y, 3H or 3S
3R, 3T, 3W, 3Y, 3H or 3S
Probes in Contact with Conductive Liquid
Probes not in Contact with Conductive Liquid
Closes on Fault
Opens on Fault
Invers UP “I”
Direct DOWN “D”
Inverse UP “I”
Direct DOWN “D”
De-Energized
De-Energized
De-Energized
De-Energized
ON
OFF
ON
OFF
SINGLE LEVEL SERVICE: ALARM FUNCTIONS
BELL CONTACTS:
Under NORMAL operating conditions the alarm bell relay is held energized. The relay will de-energize to activate an alarm device when an abnormal condition exists on either channels 3 and/or 4. Either one or both alarm bell circuits can be disabled by adjusting the alarm DIP switches. Consult table 4 for more information on the bell DIP switch settings.
SILENCE CIRCUITRY:
Should an abnormal condition exist on either channels 3 and/or 4 the normally closed (N.C.) alarm bell relay contacts will close, activating an alarm device. The N.C. alarm bell contacts can be returned to their normal state (open) silencing the alarm, by depressing a normally open pushbutton connected to the “SIL” and “G” terminals. This will NOT affect the load contacts for channels 3 or 4 as they act independent from the alarm bell contacts.
6
11
Page 6
Operation Instructions
DIFFERENTIAL LEVEL SERVICE:
The following operating instructions are based on correct DIP switch settings and sensor types. Any deviation from these requirements may result in incorrect system operations. Consult table 7 for further instructions.
Table 7
LED
Status Sensor Closed
ON
OFF
ON
OFF
ON
OFF
Application
Simplex Pump-Down or Solenoid Valve Drain
Simplex Pump-Up or Solenoid Valve Fill
Duplex Pump-Down ­Common Pump Stop
Duplex Pump-Up ­Common Pump Stop
Duplex Pump-Down ­Separate Pump Stop
Duplex Pump-Up ­Separate Pump Stop
Warrick Sensor
Normally Open: F, M, FE, FOE 3R, 3T, 3W, 3Y, 3H or 3S
Normally Open: F, M, FE, FOE 3R, 3T, 3W, 3Y, 3H or 3S
Normally Open: F, M, FE, FOE 3R, 3T, 3W, 3Y, 3H or 3S
Normally Open: F, M, FE, FOE 3R, 3T, 3W, 3Y, 3H or 3S
Normally Open: F, M, FE, FOE 3R, 3T, 3W, 3Y, 3H or 3S
Normally Open: F, M, FE, FOE 3R, 3T, 3W, 3Y, 3H or 3S
DIP
Switch
Setting
Direct
“Down”
Inverse
“Up”
Direct
“Down”
Inverse
“Up”
Direct
“Down”
Inverse
“Up”
Activation
Condition
Sensor Closes on Rising Level
Sensor Closes on Rising Level
Sensor Closes on Rising Level
Sensor Closes on Rising Level
Sensor Closes on Rising Level
Sensor Closes on Rising Level
Contact
Status
N.O. - Closes N.C. - Opens
N.O. - Opens N.C. - Closes
N.O. - Closes N.C. - Opens
N.O. - Opens N.C. - Closes
N.O. - Closes N.C. - Opens
N.O. - Opens N.C. - Closes
Installation: Intrinsically Safe Sensing Circuits
DIFFERENTIAL LEVEL SERVICE:
Channels 1 and 2 are designed to provide differential on/off points to control pumps, solenoid valves or other equipment. These channels can also be used in single level service for alarms and cutoffs, however the control’s built-in silence circuitry and bell contacts cannot be used. Consult the Alarm section for more information.
When channels 1 and 2 are used for differential level service, the associated sensors must be normally open. The Inverse/Direct DIP switches must also be set to the proper mode for each channel to achieve the correct operation. Table 3 gives the correct sensor to terminal connections an DIP switch settings for vari­ous applications.
FOR APPLICATIONS THAT DO NOT REQUIRE DUPLEX ALTERNATION, A JUMPER WIRE MUST BE PLACED FROM THE “G” TO “1-2” TERMINAL.
Table 3
Application
Simplex Pump-Down or Solenoid Valve Drain**
Simplex Pump-Up or Solenoid Valve FillII
Duplex Pump-Down ­Common Pump Stop
Duplex Pump-Up ­Common Pump Stop
Sensor
Contact Style
Normally Open ­Closes on Rising Level
Normally Open ­Closes on Rising Level
Normally Open ­Closes on Rising Level
Normally Open ­Closes on Rising Level
Sensor
Terminal Connections
Start Pump / Open Valve - HS1 & G* Stop Pump / Close Valve - LS1 & G*
Start Pump / Open Valve - LS1 & G* Stop Pump / Close Valve - HS1 & G*
Duty Pump Start - HS1 & G* Standby Pump Start - HS2 & G* Duty and Standby Pump Stop - LS1 & G* Jumper - LS1 and LS2
Duty Pump Start - LS1 & G* Standby Pump Start - LS2 & G* Duty and Standby Pump Stop - HS1 & G* Jumper - HS1 and HS2
DIP Switch
Setting
Direct - Down Channels 1 or 2
Inverse - Up Channels 1 or 2
Direct - Down Channels 1 or 2
Inverse - Up Channels 1 or 2
DIFFERENTIAL LEVEL SERVICE: SIMPLEX
Simplex Pump Down- Should the level rise to the PUMP START sensor the N.O. load contacts will close
starting the pump. The pump will remain running until the level recedes below the PUMP STOP sensor and the load contacts open.
Simples Pump UP- Should the level recede below the PUMP START sensor the N.O. load contacts will close starting the pump. The pump will remain running until the level rises to the PUMP STOP sensor and the load contacts open.
Solenoid Valve Drain- Should the level rise to the VALVE OPEN sensor the N.O. load contacts will close energizing the normally closed valve to open. The valve will remain open until the level recedes below the VALVE CLOSE sensor and the load contacts open
Solenoid Valve Fill- Should the level recede below the VALVE OPEN sensor, the N.O. load contacts will close energizing the normally closed valve to open. The valve will remain open until the level rises to the VALVE CLOSE sensor and load contacts open.
12
Duty Pump Start - HS1 & G* Duplex Pump-Down ­Separate Pump Stops
Duplex Pump-Up ­Separate Pump Stops
*
Note 1: If conductance probes are being used, only one “G” connection is required. Terminal “G” must be
Normally Open ­Closes on Rising Level
Normally Open ­Closes on Rising Level
Standby Pump Start - HS2 & G*
Duty and Standby Pump Stop - LS1 & G*
Jumper - LS2 and G*
Duty Pump Start - LS1 & G*
Standby Pump Start - LS2 & G*
Duty and Standby Pump Stop - HS1 & G*
Jumper - HS2 & G*
Direct - Down Channels 1 or 2
Inverse - Up Channels 1 or 2
grounded to the vessel if metallic. If the electrode fitting being used has a metallic body and is supported directly upon a metallic vessel, the ground connection is facilitated by securing that end of the ground connector beneath the head of one of the screws which fasten the terminal housing to the body of the fitting. When the vessel is non-metallic, terminal “G” must be connected to an additional electrode of length equal to or longer than, the longest electrode. If wire suspension electrodes are being used, more than one Ground/ Reference probe may be required.
** Note 2: This setup is based on the use of a Normally Closed (N.C.) solenoid valve that energizes to open when power is applied to the coil circuit.
5
Page 7
Installation: Intrinsically Safe Sensing Circuits
Operation Instructions
GROUNDING:
The four mounting holes on the Series 67 provide an electrical connection for earth grounding between the control’s internal solid state circuitry and the enclosure chassis. To insure proper grounding, use only metal screws and lock washers when mounting this control. Terminal G on the supply line/load side terminal strip is a redundant system ground terminal and must be connected to earth ground buss of the control’s AC supply line feeder.
Note:
1. Intrinsically safe terminals can be connected to any non-energy generating or storing switch device such as a pushbutton, limit or float type switch or any Warrick electrode and fitting assembly.
2. To prevent electrical shock from supply line/load side powered connections, the Series 67 should be mounted in a tool accessible enclosure of proper NEMA rated integrity.
3. For U.L. 913 Listed panels, a metallic partition may be necessary to provide adequate spacing between non-intrinsically safe and intrinsically safe wiring and /or terminals.
4. For additional guidance on “Hazardous Location Installation” and “Intrinsically Safe Devices”, consult ANSI/ISA standard RP 12-6 or NEC articles 500-516 and local codes.
SENSOR WIRING
The Series 67 control has four independent intrinsically safe channels, which can be connected to different types of sensors including floats, conductance probes, pressure switches and other non-powered contacts or sensors. The connections of the sensors to the terminals will not vary with normally open or closed sensors. However, the Inverse/Direct DIP switches must be set to the proper mode for each channel to achieve the correct operation. Consult tables 2 and 3 for the proper DIP switch setting for various sensors and functions.
The following sections cover the intrinsically safe sensor connections for single and differential level service.
SINGLE LEVEL SERVICE:
All four channels can be used for single level service. Each channel is independent and can be used for its own single point function. However, only channels 3 and 4 have the alarm bell and silence capabilities. Consult the alarm sections for more information regarding the installation and operation of the alarm circuitry. Table 2 covers the sensor style to terminal connections for all four channels.
Table 2
Sensor Style
Normally Open: Closes on Alarm Condition
Normally Open: Opens on Alarm Condition
Terminal
Connections
Channel 1 - HS1 & G* Channel 2 - HS2 & G* Channel 3 - S3 & G Channel 4 - S4 & G
Channel 1 - HS1 & G* Channel 2 - HS2 & G* Channel 3 - S3 & G Channel 4 - S4 & G
DIP Switch Settings
Inverse Mode - Up Position
Direct Mode - Down Position
DIFFERENTIAL LEVEL SERVICE: DUPLEX PUMP DOWN WITH ALTERNATION
Common Pump Stop- The pumps will alternate each cycle with the duty pump starting when the level rises to the
DUTY PUMP START sensor and stops when the level recedes below the PUMP(S) STOP sensor.
If the duty pump fails or cannot meet the demand of the system and the level rises to the STANDBY PUMP START sensor, the standby pump will be started and will continue in operation until the level recedes below the PUMP(S) STOP sensor.
Separate Pump Stops- The pumps will alternate each cycle with the duty pump starting when the level rises to the DUTY PUMP START sensor and stops when the level recedes below the DUTY PUMP STOP sensor.
If the duty pump fails or cannot meet the demand on the system and the level rises to the STANDBY PUMP START sensor, the standby pump will be started and will continue in operation until the level recedes below the STANDBY PUMP STOP sensor.
DIFFERENTIAL LEVEL SERVICE: DUPLEX PUMP UP WITH ALTERNATION
Common Pump Stop- The pumps will alternate each cycle with the duty pump starting when the level recedes
below the DUTY PUMP START sensor and stops when the level rises to the PUMP(S) STOP sensor.
If the duty pump fails or cannot meet the demand of the system and the level recedes to the STANDBY PUMP START sensor, the standby pump will be started and will continue in operation until the level rises to the PUMP(S) STOP sensor.
Separate Pump Stops- The pumps will alternate each cycle with the duty pump starting when the level recedes to the DUTY PUMP START sensor and stops when the level rises to the DUTY PUMP STOP sensor.
If the duty pump fails or cannot meet the demand on the system and the level recedes to the STANDBY PUMP START sensor, the standby pump will be started and will continue in operation until the level rises to the STANDBY PUMP STOP sensor.
DIFFERENTIAL LEVEL SERVICE: DUPLEX PUMP DOWN WITHOUT ALTERNATION
Same operation as above disregarding the alternation sequence. Use appropriate jumper to determine manual pump start sequence. Refer to table 5 for the manual alternation jumper information.
DIFFERENTIAL LEVEL SERVICE: DUPLEX PUMP UP WITHOUT ALTERNATION
Same operation as above disregarding the alternation sequence. Use appropriate jumper to determine manual pump start sequence. Refer to table 5 for the manual alternation jumper information.
Normally Closed: Closes on Alarm Condition
Normally Closed: Opens on Alarm Condition
* Note: Channels 1 & 2 cannot activate the alarm bell contacts and do not have the silence/acknowledge capabilities
4
Channel 1 - HS1 & G* Channel 2 - HS2 & G* Channel 3 - S3 & G Channel 4 - S4 & G
Channel 1 - HS1 & G* Channel 2 - HS2 & G* Channel 3 - S3 & G Channel 4 - S4 & G
Inverse Mode - Up Position
Direct Mode - Down Position
13
Page 8
General Control Information
Figure 4
See notes 1, 3 & 5
See notes 1 & 3
Sensor 4
Sensor 3
Sensor 2
Sensor 1
Installation: Intrinsically Safe Sensing Circuits
This bulletin should be used by experienced personnel as a guide to the installation of the series 67. Selection or installation of equipment should always be accompanied by competent technical assis­tance. We encourage you to contact Gems Sensors or its local representative if further information is required.
IMPORTANT: BEFORE PROCEEDING TO INSTALL AND WIRE THE SERIES 67 CONTROL, READ AND THROUGHLY UNDERSTAND THESE INSTRUCTIONS.
Seal Off Fitting
Channel 1
N.C.N.O. N.C.N.C.N.C. N.O.N.O.N.O.
Series 67 - Option A
Contact Board
Channel 2
N.C.N.O.
Load
1/8 Hp 120, 240 VAC 5A @ 120/240
VAC or 5 A @ 30 VDC
Channel 4Channel 3
Load
Channel 1
N.C. N.O. N.C.N.C.N.C.C N.O.N.O.N.O. CCC
Series 67 - Option C
Contact Board
Channel 2
Load
1/3 Hp 120, 240 VAC 10A @ 120/240
VAC or 10 A @ 30 VDC
N.C.
Channel 3
N.O.
Load
Channel 4
C
SIL G 1-2 2-1 LS1 G HS1 LS2 G HS2 S3 G S4
N.C. N.O.CGL2L1
Close
on
Fault
Open & Close on Fault Contacts Rated
1/3 Hp 120, 240 VAC 10 A @ 120/240
Open
on
Fault
VAC or 10 A @ 30 VDC
Hot
Neutral
Notes:
1. All intrinsically safe wiring must be installed in accordance with article 504 of the National Electric Code, publication ANSI/NFPA 70 or CEC, Part 1 as applicable.
2. Grounding- The four mounting holes on the Series 67 provide an electrical connection for earth ground­ing between the controls internal solid state circuitry and the enclosure chassis. To insure proper grounding, use only metal screws and lock washers when mounting the control.
Terminal “G” on the supply line/load side terminal strip is a redundant system ground terminal and must be connected to the earth ground buss of the controls A.C. supply line feeder. The resistance between the system ground terminals and the earth ground buss must be less than 1 ohm.
To prevent electrical shock from supply line/load side powered connections, the Series 67 should be mounted in a metal enclosure of proper NEMA integrity.
3. The maximum total length of all of the intrinsically safe wiring (of each conductor) shall not exceed an accumulative value of 16,000 feet, excluding any ground wiring.
4. The intrinsically safe terminals of the Series 67 can be connected to any non-energy generating or storing switch device such as a push button, a limit or float type switch or any of Warrick’s electrode fitting assemblies.
5. When wiring alternation and bell silence switches, the switches and wiring must be separated from non­intrinsically safe circuits and wired in accordance with article 504 of the National Electric Code, publica­tion ANSI/NFPA 70 or CEC, Part 1 as applicable.
See note 4
Earth Ground
When installing according to these instructions, this device provides intrinsically safe sensing circuits for interface into Class I; Groups C & D, Class II; Groups E, F, & G and Class III; Hazardous Areas. Electrical equipment connected to associated apparatus should not exceed maximum ratings marked on product.
*** WARNING: To prevent ignition of flammable or combustible atmospheres, disconnect power before
servicing.
MOUNTING LOCATION
The control must be situated in a non-hazardous area where an explosive atmosphere will not exist at any time; otherwise, it must be mounted in a suitable U.L. approved explosion-proof enclosure with suitable U.L. approved explosion-proof seals.
WIRING: GENERAL INFORMATION
1. Intrinsically safe wiring must be kept separate from non-intrinsically safe wiring.
2. Intrinsically safe and non-intrinsically safe wiring may occupy the same enclosure or raceway if they are at least 2 inches (50mm) apart and separately tied down. Inside panels, field wiring terminals for intrinsically safe circuits must be separated by at least 2 inches (50 mm) from non-intrinsically safe wiring.
3. Wire the control device(s) to the Series 67 relay as shown in figure 1. A separate rigid metallic conduit should be used to enclose the conductors of the intrinsically safe control circuit.
4. An approved seal should be used at the point where the intrinsically safe control circuit wiring enters the hazardous area.
5. Capacitance and inductance of the field wiring from the intrinsically safe equipment to the associated apparatus shall be calculated and must be included in the system calculations as shown in Table 1. Cable capacitance, Ccable, plus intrinsically safe equipment capacitance, Ci must be less than the marked capacitance, Ca (or Co), shown on any associated apparatus used. The same applies for inductance (Lcable, Li and La or Lo, respectively).Where the cable capacitance and inductance per foot are not known, the folllowing values shall be used: Ccable = 60 pF/ft., Lcable = 0.2 µH/ft.
For intrinsically safe output wiring use #14 or #16 AWG type MTW or THHN wire. By using these wire types in conjunction with the following distance recommendations, you will not exceed the maximum capacitance for field wiring. Use Table 2 as a guide for maximum wire runs.
Table 1
I.S. Equipment V max (or Ui) I max (or Li) P max, Pi Ci + Ccable Li + Lcable
Terminals
SIL,G,1-2,2-1
LSI,G,HSI,LS2
S3,G,S4
> > > < <
Entity Parameters
Voc
12.82 Vdc
12.82 Vdc
12.82 Vdc
Associated Apparatus Voc or Vt (or Uo) Isc or It (or lo) Po Ca (or Co) La (or Lo)
Isc
7.2 mA
7.62 mA
2.54 mA
Po
24.5 mw
24.5 mw
8.2 mw
Ca
6.5 µF
6.5 µF
6.5 µF
La
100mH
100mH
100mH
Model
Number
67AXXXA
67BXXXA
67CXXXA
67DXXXA
67EXXXA
Table 2
Sensitivity Distance
4.7K Ohms
10K Ohms
26K Ohms
50K Ohms
100K Ohms
4,000 Feet
2,400 Feet
1,200 Feet
600 Feet
300 Feet
14
HS2,G
12.82 Vdc
5.08 mA
16.3 mw
6.5 µF
100mH
3
Loading...