Gems Sensors & Controls 26 Specifications

Series 26 Low Water Cutoff – Standoff Mount
Meets CSD1 Requirements Snap-Thru Standoff MountingNon Powered Contacts Compact SizeTime Delays Available Power Outage FeatureLED Monitoring U.L. “Limit Control” Test FeatureAC Current Minimizes Electrolysis
Series 26 – General Purpose Control
Designed for boiler low-water cutoff protection. A snap-through standoff mounting device is available for Series 26 units. Optional Power Outage feature resets after nuisance outages. Optional reset button is used when device has been deactivated because of low water condition. Reset is functional only if water has returned to normal level. Optional Test Feature available allows LLCO circuit to be tested without draining the water level in the boiler. Built-in 3 second time delay is standard. Up to 90 seconds available for increasing and decreasing levels.
Specifications
WARRICK CONDUCTIVITY SENSORS
Contact Design 1 N.O. & 1 N.C. (1 form C) Contact Rating 10 amp Resistive 1/3 hp at 120, 240 VAC Mode of Operation Direct Sensitivity 0-100K ohm, factory set Primary Voltage 120 VAC, 240 VAC1, 24 VAC, 208/240 VAC (+10%/-15%) 50/60 Hz Secondary Voltage 12 VAC, 1.5 mA Temperature -40°F to +150°F (-40°C to +65°C) Approvals1 U.L. 353, U.L. 508 File # MP1430 Terminal Style Spade connection Options Time Delays, Power Outage, Retrofit Plate, Test Feature,
See page E-11 for descriptions
Notes:
1. 240 VAC and 208/240 VAC are not U.L. recognized
LOW WATER CUTOFF
Applications
• Low-Water Cutoff • Single-Level Service
• Point Level • Alarms
• Valve Control • Pump Control
Dimensions
How to Order
Use the Bold characters from the chart below to construct a product code.
26 X X X X X XX XX
1. Series 26 General Purpose;
2. Sensitivity A 4.7K; B 10K; C 26K; D 50K; E 100K
3. Supply Voltage 1 120 VAC; 2 240 VAC; 3 24 VAC; 8 208/240 VAC
4. Standoff Style A 1/16˝ Panel; B 1/8˝ Panel; C Screw mount; D Retrofit
5. Enclosure 0 None; 1 NEMA 11; 4 NEMA 4
6. Option Package See page E-11, Chart B for code letter
7. Time Delay (decreasing level) Option 03-90 seconds; Blank 3 seconds
8. Time Delay (increasing level) Option 00-90 seconds; Blank 0 seconds
Notes:
1. Standoff Style D only.
Socket Details and Option Availability are located on web site.
1
1
Wiring
L1 L2
LLCO
RESET
A.C. SUPPLY
TRANSFORMER
G
NC
C
NO
RESET BUTTON OPTIONAL
LOW LEVEL CUTOFF PROBE
REFERENCE PROBE
TANK, IF METALLIC, MAY BE USED IN PLACE OF REFERENCE PROBE.
E-8
Visit www.GemsSensors.com for most current information.