Gems Sensors & Controls 16M, 16 Installation Guide

Form 166Form 166
Form 166
Form 166Form 166
Sheet P/N 10021Sheet P/N 10021
Sheet P/N 10021
Sheet P/N 10021Sheet P/N 10021
RevRev
®®
®
®®
WW
arrickarrick
W
arrick
WW
arrickarrick
General Purpose ControlsGeneral Purpose Controls
General Purpose Controls
General Purpose ControlsGeneral Purpose Controls
Installation and Operation BulletinInstallation and Operation Bulletin
Installation and Operation Bulletin
Installation and Operation BulletinInstallation and Operation Bulletin
Series 16Series 16
Series 16
Series 16Series 16
Rev
RevRev
. F. F
. F
. F. F
This bulletin should be used by experienced personnel as a guide to the installation of Series 16 controls. Selection or installation of equipment should always be accompanied by competent technical assistance. We encourage you to contact Gems Sensors Inc. or its local representative if further information is required.
InstallationInstallation
Installation
SpecificationsSpecifications
Specifications
SpecificationsSpecifications
Control DesignControl Design
Control Design
Control DesignControl Design Contact DesignContact Design
Contact Design
Contact DesignContact Design
and one normally closed (N.C.), non-powered contacts.
Contact RatingsContact Ratings
Contact Ratings
Contact RatingsContact Ratings
@ 120, 240 VAC resistive (150°F), 1/3 H.P. @ 120, 240 VAC (120°F)
Contact LifeContact Life
Contact Life
Contact LifeContact Life
Electrical: 100,000 operations minimum at rated load.
Supply VSupply V
Supply V
Supply VSupply V
50/60 Hz. 2008/240 Model: 187 Vmin to 255 Vmax. VAC 50/ 60 Hz
Supply CurrentSupply Current
Supply Current
Supply CurrentSupply Current Secondary CircuitSecondary Circuit
Secondary Circuit
Secondary CircuitSecondary Circuit
amp current.
SensitivitySensitivity
Sensitivity
SensitivitySensitivity
mum specific resistance
TT
emperatureemperature
T
emperature
TT
emperatureemperature
TT
erminalserminals
T
erminals
TT
erminalserminals
connections 1/4” space
Time Delays:Time Delays:
Time Delays: Standard H probe, 0.5 seconds on rising level
Time Delays:Time Delays: ListingListing
Listing
ListingListing
: :
: U.L. recognized, Industrial Motor Control (508)
: :
::
::
::
: SPDT (1 form C): one normally open (N.O.)
::
: :
: 10A @ 120 or 240 VAC resistive (120°F), 1 A
: :
::
: Mechanical: 5 million operations.
::
oltageoltage
::
oltage
: 120, 240 or 24 VAC models: +10% - 15%,
oltageoltage
::
::
: Relay energized 4.4 VA.
::
::
: 12 VAC RMS voltage on probes, 1.5 milli-
::
::
: Models operate from 0 to 1,000,000 Ohm maxi-
::
::
: -40 to 150° F. ambient.
::
::
: Probe connections 3/16” spade: Line and power
::
1. Drill three .187 dia. holes in customer supplied backplate using stick on template supplied with control. Standard standoffs are designed for backplate thickness of .062 (1/ 16”). Standoffs are available for backplates of .125 (1/8”) nominal thickness. If retrofit plate standoffs are used, drill three .250 dia. holes in proper location.
2. Install three standoffs onto backplate. Install circuit board onto standoffs by pushing down on circuit board at outer edges of all four corners. Use both hands to slide board onto standoffs until standoffs lock. circuit board during installation. Do not push down on transformer or relays during installation. See sketch for proper installation. Install control in appropriate enclosure.
3. Wire control per diagram, following N.E.C. and local codes. Use appropriately sized spade terminals.
We have four different types of standoffs, designed to connect cirucit boards to panels
InstallationInstallation
CAUTION:CAUTION:
CAUTION: Do not overflex
CAUTION:CAUTION:
StandoffsStandoffs
Standoffs
StandoffsStandoffs
Top View
1-11-1
1-1
1-11-1
DimensionsDimensions
Dimensions
DimensionsDimensions
Backplate Supplied
à
à
à
2-1/2 (6.35 cm)
1-5/8 (4.13 cm)
à
2-3/16 (5.55 cm)
à
1-3/4 (4.45 cm)
3/16 (.48 cm) REF
Transformer
à
à
à
à
à
1-1/16
à
(2.70 cm) REF
by Others
à
1/2
(1.27 cm)
à
NotesNotes
Notes
NotesNotes
à
1 (2.54 cm)
à
Mounting template supplied with all open circuit board controls.
If panel mount stand-off is to be used, thru-holes to be drilled in back plate should be .187 Dia.
If retrofit stand-off is to be used, thru-holes to be drilled in back plate should be .250 Dia.
à
1-7/8 (4.76 cm)
Side View
1/16
1/16
Standoff
à
Standoff
SensitivitySensitivity
Sensitivity
SensitivitySensitivity CharacterCharacter
Character
CharacterCharacter
à
**
* Based on type MTW or THHN wire, #14 or #16 AWG
**
1/8
Bottom View
1/8
Sensitivities vs MaximumSensitivities vs Maximum
Sensitivities vs Maximum
Sensitivities vs MaximumSensitivities vs Maximum
A or K
B or L C or M D or N
E or P
F or R G or S
Retrofit
Standoff
Probe Wire DistanceProbe Wire Distance
Probe Wire Distance
Probe Wire DistanceProbe Wire Distance
SensitivitySensitivity
Sensitivity
SensitivitySensitivity
(K Ohms)(K Ohms)
(K Ohms)
(K Ohms)(K Ohms)
4.7 10 26 50
100 470
1,000
Circuit Board
Standoff
*
DistanceDistance
Distance
DistanceDistance
(Ft)(Ft)
(Ft)
(Ft)(Ft)
10,000
5,700 2,200 1,075
Screw Mount
Standoff
570 270
38
WW
iring Diagramiring Diagram
W
iring Diagram
WW
iring Diagramiring Diagram
L1L1
L1
L1L1
GG
G
GG
Reference ProbeReference Probe
Reference Probe
Reference ProbeReference Probe
A. C. SupplyA. C. Supply
A. C. Supply
A. C. SupplyA. C. Supply
TT
ransformerransformer
T
ransformer
TT
ransformerransformer
L2L2
L2
L2L2
HH
H
HH
LL
L
LL
NC
C
NO
OperationOperation
Operation
OperationOperation
For single level service, use H and G connections.
High ProbeHigh Probe
High Probe
High ProbeHigh Probe
Low ProbeLow Probe
Low Probe
Low ProbeLow Probe
If metallic, the tank may be used in place of the reference probe.
Direct Mode- Single Level ServiceDirect Mode- Single Level Service
Direct Mode- Single Level Service
Direct Mode- Single Level ServiceDirect Mode- Single Level Service
::
: When the liquid rises to the electrode on terminal H, the control energizes, changing state of
::
the load contacts. (LED will be lit) The control remains energized until the liquid level recedes below electrode on terminal H. The control then de-energizes, (LED will not be lit) returning load to original state.
Inverse Mode- Single Level ServiceInverse Mode- Single Level Service
Inverse Mode- Single Level Service
Inverse Mode- Single Level ServiceInverse Mode- Single Level Service
::
: Control energizes with power, changing state of the load contacts. (LED will be lit) When the
::
liquid rises to the electrode on terminal H, the control de-energizes, returning the load contacts to shelf state. (LED will not be lit) The control remains de-energized until liquid level recedes below the electrode connected to terminal H. The control then energizes.
Direct Mode- Differential ServiceDirect Mode- Differential Service
Direct Mode- Differential Service
Direct Mode- Differential ServiceDirect Mode- Differential Service
::
: When the liquid rises to the electrode on terminal H, the control energizes, changing state of the
::
load contacts. (LED will be lit) The control remains energized until the liquid level recedes below electrode on terminal L. The control then de-energizes, (LED will not be lit) returning the load contacts to original state.
Inverse Mode- Differential ServiceInverse Mode- Differential Service
Inverse Mode- Differential Service
Inverse Mode- Differential ServiceInverse Mode- Differential Service
::
: Control energizes with power, (LED will be lit) changing state of the load contacts. When the
::
liquid rises to the electrode on terminal H, the control de-energizes, returning load contacts to shelf state. (LED will not be lit) The control remains de-energized until the liquid level recedes below the electrode on terminal L. The control then energizes.
OptionalOptional
Optional
OptionalOptional
Time DelaysTime Delays
Time Delays
Time DelaysTime Delays
::
: With time delay on increasing level, the liquid must be in contact with the short electrode for the full duration of the
::
time delay before control will operate. With delay on decreasing level, the liquid must be below long electrode for the full duration of the time delay before control will operate. In single level service, terminals H and L must be jumpered together to achieve time delays on both increasing and decreasing levels or just decreasing level.
16 X-X-X-X-XX-XX16 X-X-X-X-XX-XX
16 X-X-X-X-XX-XX
16 X-X-X-X-XX-XX16 X-X-X-X-XX-XX
Time Delay: Time Delay:
Time Delay: (decreasing level) 1-20 sec.
Time Delay: Time Delay: Time Delay:Time Delay:
Time Delay: (increasing level) 1-20 sec.
Time Delay:Time Delay: Enclosure:Enclosure:
Enclosure: 0-none, 1-NEMA 1, 4-NEMA 4, 7-NEMA 7, 12-NEMA 12
Enclosure:Enclosure: Standoff Style:Standoff Style:
Standoff Style: A- 1/16 panel, B- 1/8 panel,C-Screw mount, D- Retrofit plate
Standoff Style:Standoff Style: Supply VSupply V
Supply V
Supply VSupply V Mode/Sensitivity: Direct Mode/Sensitivity: Direct
Mode/Sensitivity: Direct A- 4.7K, B- 10K, C- 26K, D- 50K, E- 100K, F- 470K, G- 1M
Mode/Sensitivity: Direct Mode/Sensitivity: Direct
Inverse Inverse
Inverse K- 4.7K, L- 10K, M- 26K, N- 50K, P- 100K, R- 470K, S- 1M
Inverse Inverse
oltage:oltage:
oltage: 1- 120 VAC, 2- 240 VAC, 3- 24 VAC, 8- 208/240 VAC
oltage:oltage:
**
*
**
**
*187 Vmin to 255 Vmax VAC
**
Gems Sensors Inc. One Cowles Road Plainville, CT 06062-1198 Tel: 860-793-4579 Fax: 860-793-4580
Loading...