Gemini GEM-RP1CAe2 Operating Manual

Page 1
1
OPERATING GUIDE for your
GEM-RP1CAe2 KEYPAD
© NAPCO 2000 DESIGN PATS. PENDING
ARMED
COMPUTERIZED SECURITY SYSTEM
STATUS
A 1 2 3
B 4 5 6
C 7 8 9 0
J
SYSTEM ARMEDSYSTEM ARMED 1122/01//01/0000 12:00 AM 12:00 AM
NEXT/YES
E
PRIOR/NO
F
AREA
G
Page 2
2
The GEM-RP1CAe2 is a “smart” user­friendly, menu-driven keypad designed for your Napco control panel. The keypad is interactive. Its alphanumeric screen will not only display the status of your system, but will also give you step-by-step instructions to guide you through all operations.
This booklet contains important information about the operation of your system with this GEM-RP1CAe2 Keypad. Read it carefully and keep it handy for future
reference. Check the Glossary for an explanation of terms that may be unfamiliar to you.
You'll probably find subjects mentioned in this booklet that do not apply to your system. Napco control panels have such a wide variety of features that few security systems, if any, will ever need them all. Your alarm professional has chosen appropriate features for your particular needs.
Regardless of how your system has been configured, rest assured that it has been carefully designed and engineered to the highest industry standards. To assure optimum safety and security, familiarize yourself with this equipment. Periodically check its condition and state of readiness by testing it at least once a week in both the ac/ battery and battery-only modes (ask your alarm professional how to make these tests).
INTRODUCTION
Test your sounding device and backup battery
(This test should only be performed on weekends or at a time designated by your alarm company.)
1. While disarmed, press A.
2. Answer NO (press F) until “ACTIVATE BELL TEST” appears in the
window. Press YES (E) to execute the test. The alarm will sound for about two
seconds.
If the alarm does not sound, call for service.
If the battery is low, “LOW BATTERY E02-00 SERVICE” will appear
in the display indicating a low battery condition. Allow 24 hours for the battery to recharge. If the trouble continues, call for service.
Test your central station communicator
1. Notify your Central Station of the impending test. While disarmed, enter
your User Code and press A.
2. Answer NO (press F) until “ACTIVATE DIALER TEST” appears in the window.
3. Press YES (E) to send a test code to the central station.
If the test is not successful, “COMM FAIL E03-00 SERVICE” will
display, indicating a communication failure. Call for service.
Note: Any subsequent successful transmission will clear a “Failure to Communicate” system trouble.
IMPORTANT - TEST YOUR SYSTEM WEEKLY
Page 3
3
TABLE OF CONTENTS
TABLE OF CONTENTS
Section Page
KEYPAD CONTROLS & INDICATORS ...........................................4
SETTING THE ALARM (ARMING) WHEN LEAVING ......................6
PROTECTING YOURSELF WHILE ON THE PREMISES ................8
TURNING OFF THE ALARM (DISARMING) WHEN RETURNING ...10
FIRE PROTECTION ......................................................................11
KEYPAD FUNCTIONS ...................................................................15
CENTRAL-STATION MONITORING ...............................................20
ADVANCED FEATURES ...............................................................21
PROGRAMMING USER CODES ....................................................22
SETTING THE DATE AND TIME ....................................................22
KEYPAD MESSAGES ....................................................................26
GLOSSARY ...................................................................................29
SYSTEM TROUBLE ERROR CODES ............................................32
TROUBLESHOOTING ...................................................................37
TO SILENCE AN ALARM, ENTER YOUR
CODE, AND PRESS J.
FOR SERVICE, CALL: _____________________ CENTRAL STATION: ______________________ EXIT DELAY:_____________________________ ENTRY DELAY:___________________________ FIRE ALARM SOUND*:_____________________ BURGLAR ALARM SOUND*:_________________
KEYPAD FIRE ENABLED? qYES qNO KEYPAD PANIC ENABLED? qYES qNO KEYPAD AUX. ENABLED? qYES qNO
*FIRE HAS PRIORITY OVER BURGLARY.
Page 4
4
KEYPAD CONTROLS & INDICATORS
1
2
3
4 5 6
7
12
8
9
10 11
ARMED
COMPUTERIZED SECURITY SYSTEM
STATUS
GEMINI
A 1 2 3
B 4 5 6
C 7 8 9 0
J
SYSTEM ARMEDSYSTEM ARMED 01/01/00 12:00 AM01/01/00 12:00 AM
NEXT/YES
E
PRIOR/NO
F
AREA
G
Page 5
5
KEYPAD CONTROLS & INDICATORS
Window. Displays system status
messages, zone descriptions, etc
STATUS Light. Lights (green) to indicate that the system is ready for arming. If a zone is not secured the light will be off and the zone will display in the window. If a zone has been bypassed, the STATUS light will blink while armed.
ARMED Light. Lights (red) to indicate that the system is armed. If an alarm has occurred, the ARMED LED will be flashing.
FUNCTION Button. Selects available system functions as displayed in the window. The selected function is executed by pressing the Jto button.
BYPASS Button. (1)Deactivates selected zones from the system.
(2)Unbypasses a bypassed zone.
RESET Button. (1) Resets various system troubles, displays, etc. (See text.) (2) Resets residential smoke detectors.
Numerical Keys (1-9, 0). Used to enter codes, zone numbers, etc.
ON/OFF Button. Entry key. Causes the entered code or selected function to be executed
INTERIOR Button. (1) Bypasses all Interior Zones simultaneously to allow free movement within the premises. (2) Scrolls the window display forward (NEXT). (3) Answers “YES” to questions in the window display.
INSTANT Button. (1) Cancels entry delay on Exit/Entry Zones, causing an instant alarm upon
violation. (2) Scrolls window display backward (PRIOR). (3) Answers “NO” to questions in the window display.
AREA Button (G). Selects other areas and is used with
emergency buttons. Emergency Buttons. Used with
the G button to signal an emergency, as follows:
Fire Emergency
Press the 7 and G buttons. Auxiliary Emergency
Press the 8 and G buttons Police Emergency
Press the 9 and G buttons.
1
2
3
4
5
6
7
8
9
10
11
12
Page 6
6
ZONES FAULTED
02 BACK DOOR
BYPASSED
BYPASSED
BYPASSED
02 BACK DOOR
Arming the System
1. Check the keypad. The green STATUS light must be on in order to arm. If the green light is off, “ZONES FAULTED” will display in the window followed by the number and description of each faulted zone. Note each problem zone and secure it by closing a window, door, etc. When all zones are secure, the green STATUS light will come on and the window will display “SYSTEM READY”.
2. Arm the system. Enter your code and press J. The green STATUS light will go off, the red ARMED light will come on and the window will display “EXIT TIME XXX”, “PLEASE
LEAVE NOW” (where “XXX” represents the exit time remaining, in 10-second steps). Note: If you enter a wrong code, the keypad will display “INVALID ENTRY, TRY AGAIN”. Re-enter your code immediately.
Leave the premises. Leave through the exit door before exit time expires.
Priority Arming
If you attempt to arm with a faulted Zone, a 3-second tone will sound at the keypad. “ZONES NOT NORMAL” and “CAN'T ARM SYSTEM”, will display in the window, indicating that the faulted zone(s) must be secured before the panel can be armed.
Selectively Bypassing Zones
If you cannot locate or repair the problem yourself, call for assistance. If you cannot get immediate help, bypass the problem zone(s) from the system by pressing B, then the
zone number (or vice versa). Note: Bypassed zones are unprotected. If armed with zones bypassed, be sure to have the system checked as soon as possible.
EXIT TIME 060 PLEASE LEAVE
ZONES NOT NORMAL CAN’T ARM SYSTEM
ZONES FAULTED
SYSTEM READY
02 BACK DOOR
BYPASSED
BYPASSED
BYPASSED
02 BACK DOOR
SETTING THE ALARM (ARMING) WHEN LEAVING
Page 7
7
SETTING THE ALARM (ARMING) WHEN LEAVING
System Trouble
If you attempt to arm with a “SYSTEM TROUBLE” display alternating with an indicated trouble code (e.g. “E02-00” (low battery); see SYSTEM TROUBLE ERROR CODES), a 3-second tone will sound at the keypad. The window will display “PRESS RESET KEY, CAN'T ARM SYSTEM”. If you cannot correct the problem immediately, pressing C will enable you to arm in this condition. Be sure to call for service as
soon as possible.
Area Arming (Optional)
Some systems may be divided, or partitioned, into smaller independent subsystems, which are referred to as Areas. In a system that has been partitioned into multiple areas, one or more area may be armed while others remain disarmed.
Manager's Mode (Optional)
The Manager's Mode allows the user to arm/disarm other areas in a partitioned system. To arm/disarm a
different area:
1 Press the numerical key representing the other area number. 2 Press G followed byJ. The keypad will now provide status and control of that area. 3 Enter your User Code followed by J to arm or disarm the area. 4 Press G followed byJ to return to the home area.
Global Arming (Optional)
To arm all areas simultaneously, press 9, G and enter your code followed byJ. To disarm all areas simultaneously, press 0, G and enter your code followed byJ.
The User Code must be valid in all area(s).
If any zone is not secured, the keypad will display “CAN’T ARM SYSTEM, AREA X IN TROUBLE”,
where X indicates the number of the Area in trouble. All faulted zones in the respective area(s) must be secured or bypassed. Note: If a system trouble is indicated, the system cannot be armed using this method.
SYS/TRBL
LOW BATTERY E02-00 SERVICE
SYS/TRBL
SYSTEM TROUBLE
SYS/TRBL
PRESS RESET KEY CAN’T ARM SYSTEM
EXIT TIME 060
PLEASE LEAVE NOW
CAN’T ARM SYSTEM
AREA X IN TROUBLE
Page 8
8
Bypassing Interior Zones
Interior Zones, when bypassed, allow free movement within the home while the protection of armed perimeter zones is maintained. To bypass Interior Zones, press E and enter your User Code followed byJ.
Your system may have provisions for two groups of Interior Zones. (Optional) (Interior Groups programmed? qYES qNO)
Press E, followed byJ to Bypass Interior Group 1: [ ____________________________________ ]
Press E twice followed byJ to Bypass Interior Group 2: [ ______________________________________ ]
Press E three times followed byJ to Bypass both Interior Groups 1 & 2.
Automatic Interior Bypass (Optional - Automatic Interior Bypass programmed? qYES qNO)
Your system may have been programmed for Automatic Interior Bypass, which allows it to recognize that you have armed the system and remained in the house, prompting it to automatically adjust the interior protection accordingly.
If you arm the system and remain in the house, all Interior Zones are automatically bypassed. The keypad will display
“BYPASSED” indicating that it is safe to move about.
If the system is armed and you leave, the Interior Zones will unbypass, providing complete interior protection.
Instant Protection
When retiring for the evening, after all family members are home, you can cancel the entry delay on the Entry Zone(s). To arm with instant protection, press F just prior to arming, or at any
time after the system is armed. When armed with Instant Protection opening the entry door will cause an immediate alarm.
When arming with Instant Protection, the exit delay will remain in effect, allowing exit of the house just after arming. While armed, the
window will display “SYSTEM ARMED I” and the red ARMED light will flicker rapidly to indicate instant protection.
PROTECTING YOURSELF WHILE ON THE PREMISES
SYSTEM ARMED I
Page 9
9
Easy Exit (Optional - Easy Exit programmed? qYES qNO)
Your system may have been programmed for Easy Exit, which allows a user to exit the premises while the system is armed. By activating Easy Exit while the system is armed, the Exit Delay countdown will take place, during which time you are permitted to leave through the exit door. The Easy Exit Delay time will be identical to the Exit Delay time the system gives you each time it is armed. This will allow, for example, an early morning commuter to exit the house, without having to disarm and rearm the system, awaking the family.
q Press E to activate Easy Exit on your system. (GEM-P3200/GEM-P9600 V11D or less, GEM-P1632 V8G or less) q Press J to activate Easy Exit on your system. (GEM-P3200/GEM-P9600 V20 or greater, GEM-P816/P1632 V9A or greater)
Emergency Buttons (Only available if programmed)
The Blue Emergency Buttons (77 88 & 99), if programmed, are always active, whether the system is armed or disarmed. The emergency signal will only be
transmitted when an Emergency Button and GG are pressed at the same time.
Fire Emergency Simultaneously press77 and GG to alert the central station of a Fire Emergency. * (Fire Emergency programmed? qYES qNO)
Auxiliary Emergency Simultaneously press88 andGG to alert the central station
of an Auxiliary Emergency.* (Auxiliary Emergency programmed? qYES qNO)
Police Emergency Simultaneously press99 andGG to alert the central station of a Police Emergency. * (Police Emergency programmed? qYES qNO)
PROTECTING YOURSELF WHILE ON THE PREMISES
Page 10
10
Disarming the System
1 Enter your premises through the Entry/Exit door. The keypad will sound a steady tone to
remind you to disarm the system before your Entry Delay time expires.
2 Enter your User Code and pressJ. The red ARMED light will go out, indicating that the
system has been disarmed.
If you enter an invalid code, the keypad will beep 4 times, signifying an error. Re-enter your code immediately. 10 seconds before Entry Delay expires, the keypad will emit a pulsing warning tone.
Alarm Indication/Silencing an Alarm If the red ARMED light is flashing and “ALARM” is displayed, an alarm occurred while
you were out. Proceed with caution! If you suspect that an intruder may still be on the premises, leave immediately and call authorities from a neighbor's phone.
To silence an audible alarm:
Enter your code and press J. After the system is disarmed, the window will continue to display “ALARM” followed by the zone(s) violated. To reset the display, note the zones
violated, then press C.
TURNING OFF THE ALARM (DISARMING) WHEN RETURNING
ENTRY TIME XXX DISARM SYSTEM
INVALID ENTRY TRY AGAIN
**** ALARM ****
02 - BACK ALARM
03 - LIVING ROOM
Ambush (Optional - Ambush programmed? qYES qNO) (Your Ambush Code is __ __ )
The Ambush Code (optional) is a 2-digit code that is entered just prior to your Disarm Code. If an intruder forces you to disarm your system, (a) enter your Ambush Code; (b) enter your Disarm Code; (c) pressJ.
Example: If your User Code is 1234 and your Ambush Code is 99, press 9 9 1 2 34 1 2 34J.
This will send a silent alarm to the central station. The red ARMED light will go out and the window will display “SYSTEM
READY”, as if the system were merely disarmed. There will be no indication that an alarm has been sent.
Page 11
11
FIRE PROTECTION
(Applicable only where local ordinance permits use of this alarm control panel for fire protection.)
Fire-Zone Alarm
If a fire is detected, “FIRE ALARM” will be displayed and the keypad sounder will pulse. If a fire is in progress, evacuate the premises immediately! If necessary, call the Fire
Department from an outside phone.
FIRE
FIRE ALARM
FIRE
FIRE TROUBLE
Resetting a Fire-Zone Alarm
1 Press the C button to silence the keypad sounder. 2 If there is no evidence of a fire, enter your User Code and pressJ to turn off the alarm Check smoke detector(s). If a smoke
detector tripped, its red alarm indicator light will be on.
After the alarm condition is corrected (thermostat cooled down; smoke cleared from detector; etc.), pressing C again will reset the keypad within about 10 seconds.
Page 12
12
FIRE PROTECTION
Preparing a Fire Escape Plan
Even with the most advanced fire alarm system, adequate protection requires an escape plan.
To prepare your plan, draw floor plans of your building. (Space is provided on the next page.) Show two exits - a front or back door and a window from each room. (Make sure the window works. You may need a special fire­escape ladder if the window is high up.) Write down your outside meeting place.
Family Rehearsal.
Rehearse each of the following activities:
1 Everyone in his room with the doors
closed.
2 One person sounds the alarm. 3 Each person tests his door.
4 Pretend the door is hot and use the
alternate escape exit.
5 Everyone meets outdoors
at the assigned spot.
Important! - Read Carefully
1 Discuss these escape procedures
with all those who use the building: In a residence, sleep with the bedroom door closed. A closed door will hold back deadly smoke while you escape.
2 When the fire alarm signals, escape
quickly. Do not stop to pack.
3 Test the door. If it is hot, use your
alternate route through the window. If the door is cool, brace your shoulder against it and open it cautiously. Be ready to slam the door if smoke or heat rushes in. Crawl through smoke, holding your breath. Close the doors again on leaving to help prevent the fire from spreading.
4 Go to your specific outdoor meeting
place so you can see that everyone is safe.
5 Assign someone to make sure
nobody returns to the burning building.
6 Call the Fire Department from a
neighbor's telephone.
Would You Like More Safety Information?
For more information on home fire detection, burn safety, and home fire safety, write to the National Fire Protection Association, Public Affairs Dept. 05A, Batterymarch Plaza, Quincy, MA 02269.
Page 13
13
FIRE PROTECTION
Floorplan
Floorplan
Page 14
14
FIRE PROTECTION
Although a fire alarm system may be of a
reliable and state-of- the-art design, neither it nor its peripheral detection devices can offer guaranteed protection against fire. Any such equipment may fail to warn for a variety of reasons:
Control panels, communicators, dialers,
smoke detectors, and many other sensing devices will not work without power. Battery- operated devices will not work without batteries, with dead batteries, or with improperly-installed batteries. Devices powered solely by AC will not work if their power source is cut off for any reason.
Fires often cause a failure of electrical power.
If the system does not contain a working battery backup power supply, and if the electrical circuit feeding the devices is cut or is not providing power for any reason, the system will not detect heat or smoke or provide any warning of a possible fire.
Telephone lines needed to transmit alarm
signals to a central monitoring station may be out of service.
Smoke detectors, though highly effective in
reducing fire deaths, may not activate or
provide early-enough warning for a variety of reasons: (a) they may not sense fires that start where smoke cannot reach them, such as in chimneys, walls, roofs, behind closed doors, etc.; (b) they may not sense a fire on a different level of the residence or building; (c) they have sensing limitations; no smoke detector can sense every kind of fire every time.
Thermostatic heat detectors do not always
detect fires because the fire may be a slow smoldering low-heat type (producing smoke); because they may not be near the fire; or because the heat of the fire may bypass them. These detectors will not detect oxygen levels, smoke, toxic gases, or flames. Therefore, they may only be used as part of a comprehensive fire-detection system in conjunction with other devices. Under no circumstances should thermostatic heat detectors be relied upon as the sole measure to ensure fire safety.
Alarm warning devices such as sirens, bells,
or horns may not alert someone behind a closed or partially-opened door. Warning devices located on one level are less
likely to alert those on a different level. Even those who are awake may not hear the warning if the alarm is obscured by noise from a stereo, radio, air conditioner, or other appliance, or by passing traffic, etc. Alarm warning devices, however loud, may fail to warn the hearing impaired.
Alarm products, as all electrical devices, are
subject to component failure. Even though the equipment is designed for many years of trouble-free performance, electronic components could fail at any time.
Above are some of the reasons that fire
alarm equipment could fail. The most common cause of an alarm system not functioning when a fire occurs is inadequate testing and maintenance. The system should be tested at least weekly to ensure that all the equipment is working properly.
While an alarm system may make one
eligible for lower insurance rates, it is not a substitute for insurance. Homeowners, property owners, and renters are therefore urged to maintain adequate insurance coverage of life and property.
LIMITATIONS OF FIRE ALARM WARNING SYSTEM
Page 15
15
KEYPAD FUNCTIONS
The keypad can provide access to a wide assortment of utility functions. The functions are displayed in a prompting “YES/NO” format.
1 To enter the Function Menu, press A. In all UL-listed or high-security installations, a valid User Code must first be
entered followed by A.
2 To skip a function, answer NO (F) or A. 3 To select and execute a function, answer YES (E) or J.
Functions may be manually scrolled forward or backward using A and B, respectively.
To return to normal keypad operation, press the C button. The keypad will automatically return to its
normal operating mode if no activity is detected for longer than one minute.
Display Zone Faults? Displays the zone number of zones that are not secured. Press the NEXT and PRIOR Buttons (as displayed on-screen) to scroll faulted zones.
Display Zones Bypassed? Displays bypassed zones. Press NEXT(E) and PRIOR (F) to scroll bypassed zones.
Display Zone Directory? Displays a listing of all zones in the Area. Press NEXT(E) and PRIOR (F) to scroll zone directory.
DISPLAY ZN FAULTS Y/N
DISPLAY ZN BYPASSED Y/N
DISPLAY ZN DIRECTORY Y/N
Page 16
16
Activate Bell Test? Activates the alarm (while disarmed) for about 2 seconds and
performs a battery test. If the alarm does not sound, call for service.
If the battery is low, a “LOW BATTERY E02-00 SERVICE” will appear in the display
indicating a low battery condition. Allow 24 hours for the battery to recharge. If the trouble continues, call for service.
Display System Troubles? (Optional) Displays 1- or 2-digit error code along with a description of a problem detected in the system. (See SYSTEM TROUBLE ERROR CODES for a full description of these codes.) Use NEXT(E) and PRIOR (F)
to scroll system troubles. Display Fire Alarms? Displays alarms that have occurred on the Fire Zone(s). Press the NEXT and PRIOR Buttons to scroll zones. Display Fire Troubles? Displays trouble conditions that have been detected on the Fire Zone(s). Use NEXT(E) and PRIOR (F) to scroll zones.
Activate Chime? The Chime Mode will sound a tone at the keypad when the programmed zone is faulted while disarmed. To deactivate the Chime Mode, re­enter the Function Mode and when “DEACTIVATE CHIME“ is displayed, press YES (E). Note: The Chime Mode is disabled while armed.
Activate Watch Mode? (Optional - Watch Mode programmed? qYES qNO) This optional feature simultaneously turns on all zones designated as Day Zones, which will cause an indication at the keypad if a zone is opened while the system is disarmed. To deactivate the Watch Mode, arm, then disarm. All Day Zones will revert to regular Burglary Zones. Note: The Watch Mode is disabled while armed.
KEYPAD FUNCTIONS
ACTIVATE BELL TEST Y/N
DISPLAY SYS TRBL Y/N
DISPLAY FIRE ALARM Y/N
DISPLAY FIRE TRBL Y/N
ACTIVATE CHIME Y/N
ACTIVATE WATCH Y/N
Page 17
17
Reset System Trouble? System troubles display and sound at the keypad.
Correcting the trouble will clear most indications, however the following error codes will require manual reset: E13; E19; E20 and E22. (See SYSTEM TROUBLE ERROR CODES for a description of error codes.)
Reset Sensor Watch Failure? (Sensor Watch programmed? qYES qNO). Your system may have been programmed for Sensor Watch, a feature which supervises the motion sensors in the system. If a Sensor Watch failure occurs, a System Trouble E22-NN will result, where NN represents the zone number of the sensor in question. To reset, press C to clear the display, enter the Function
Menu, scroll to ”RESET SENSOR MSG“ and pressJ. If you cannot correct the problem, call for service
Start Exit Time? (Optional) (Start Exit Time programmed? qYES qNO) In Commercial Burglary systems, exit delay may have been programmed to start after a central-station “ringback” (verification) signal has been received. If the ringback tone has not been received within about 30 seconds after arming, a communication problem may exist. Use this function to start exit delay manually, then exit the premises immediately. Be sure to have your alarm specialist check communications with the central station as soon as possible.
RESET SYS TRBL Y/N
RESET SENSOR MSG Y/
START EXIT TIME Y/
KEYPAD FUNCTIONS
Page 18
18
KEYPAD FUNCTIONS
Activate Telephone Test? (Telephone Test programmed? qYES qNO). Sends a
communicator test to the central station. A communication failure will be indicated at the keypad by a system trouble “E03-FAIL TO COMM” display. Repeat the test to attempt to correct a communication failure, as any successful communication will clear this display.
Delay Arming 1-4 hours. (Not for UL-listed systems.) Your system may be set to arm automatically after a delay period of 1 to 4 hours.
To Delay Arm the system:
With the function “TO ARM IN 1-4 HRS“ displayed in the window, enter the desired
Delay Arming time in hours (1,2,3,or 4), followed by J.
At the end of this 1 - 4 hour Delay Arming period, the siren will sound a 2-second warning and the keypad will begin a 15-minute arming countdown with the sounder pulsing. The sounder may be silenced at this time by pressing C, but it will turn
back on with a steady warning tone 1 minute prior to arming, at which time the building must be exited.
The same steps can be used to delay a scheduled Auto Arming, if your system has been programmed as such.
ACTIVATE DIALER TEST Y/N
TO ARM IN 1-4 HRS PRESS 1-4 /N
Page 19
19
KEYPAD FUNCTIONS
Activate Program? Activates the Program Mode from Keypad No. 1. Note: This
feature is disabled while armed. (See PROGRAMMING USER CODES)
Activate Download? For installer's use only. If accidentally enabled, press C to exit.
Note: This feature is disabled while armed. Relay Control? (Relay Control programmed? qYES qNO).
Turns ON or OFF one or more programmed Relay Groups. PressJ to turn the displayed group on or off; press NEXT(E) to proceed to the next group, or
PRIOR (F) to scroll back to the previous group. Press C when done.
Relay Group 01: [ ____________________________________ ]
Relay Group 02: [ ____________________________________ ]
Relay Group 03: [ ____________________________________ ]
Relay Group 04: [ ____________________________________ ]
Relay Group 05: [ ____________________________________ ]
Relay Group 06: [ ____________________________________ ]
Relay Group 07: [ ____________________________________ ]
Relay Group 08: [ ____________________________________ ]
ACTIVATE PROGRAM Y/N
ACTIVATE DOWNLOAD Y/N
RELAY CONTROL Y/N
Page 20
20
Your alarm specialist may have programmed your system to be monitored by a central station. The built-in digital communicator can transmit emergency signals and status reports to the central station 24 hours a day.
Communicator Features
Abort Delay. Ask your installer
which of your zones have abort delay, a delay that enables you to reset the system before it communicates to the central station. Regular Burglary (Non-24-Hour) Zone. Reports are aborted by disarming within the delay period.
24-Hour Zones and zones
programmed to report restores must be restored first, then the panel armed and disarmed, all within the delay period.
Opening and/or Closing
Reporting. Your system can notify
the central station every time it is disarmed or armed. Any or all of up to 96 different users can each be identified. If your system reports on
arming (Closing Report), the central station will acknowledge arming. This will signal at the keypad as a “ringback” beep. Note: If the ringback signal is not heard, call for service.
CENTRAL STATION MONITORING
Page 21
21
ADVANCED FEATURES
Security Bypass/Unbypass
(Security Bypass programmed? qYES qNO).
In high-security applications, zones may be bypassed (or unbypassed) only if a valid code is entered first, as follows: 1 Enter a User Code valid for bypass, then press BB .
2 Press BB then the zone number (or vice versa) to deactivate that zone.
Similarly, a bypassed zone may be unbypassed using the same procedure.
Start Exit Time After Ringback (for Commercial Burglary Systems only)
(Optional - Start Exit Time programmed? qYES qNO).
If your system reports to a central station, your panel may have been programmed to start exit delay after the central-station ringback (verification) signal. Then, after arming, your system will communicate to the central station. After the central station acknowledges receipt (ringback), exit delay will start. If ringback is not heard within about 30 seconds, a communication problem may exist; call for service. Function 11 (Start Exit Time) may then be used to manually start the exit delay, however reporting capability may be sacrificed. (If your system does not report or the ringback feature was not programmed, exit delay will start as soon as your code is entered. Also note that if an exception window is programmed, and the closing is within that window, no ringback is provided. Ask your alarm professional if this feature is enabled.)
Exit-Delay Restart
(Exit-Delay Restart programmed? qYES qNO).
On arming, the programmed exit delay will start. After the exit door has been opened and then closed, exit delay will change to 60 seconds. Thus, a long exit delay may be programmed, which will immediately be reduced to 60 seconds upon exiting. If re-entry occurs during that 60 seconds, exit delay will restart once again (and only once again) at 60 seconds. If so programmed, re-entry within 60 seconds after exit delay has expired, will cause the alarm to sound a 2-second warning (in addition to the entry sounder) to remind the user to disarm.
Page 22
22
PROGRAMMING (OPTIONAL)
Enter the User Program Mode
1 Enter your User Code, then press AA to enter the Function Mode. 2 Answer NO (FF) until “ACTIVATE PROGRAM Y/N” is displayed, then press YES
(EE)
“ENTER USER CODE” will display indicating that the system is ready for User Code programming.
Programming/Reprogramming a User Code
1 Enter the 2 digits of the user number to be programmed, followed by AA. ( Example: for User 4, enter 04 AA). 2 Enter the new User Code (up to 6 digits) 3 Press J to save the new User Code.
Repeat Steps 1 through 3 for each User Code to be programmed.
User Program Mode
Your Installer has programmed into your system a special User Program Code which can be used to not only Arm and Disarm the system, but also to enter the User Program Mode, where you can program other User Codes, Zone Descriptions and also set the system Time and Date. The following explains how you will use this code to program or erase additional User Codes:
ACTIVATE PROGRAM Y/N
ENTER USER CODE U01 123 - -
ENTER USER CODE U04 - -
Erasing a User Code
1 Enter the 2 digits of the user number to be erased followed by AA. 2 Press G0 to erase each digit of the User Code and then press J. 3 Example: Erase User 3’s 4-digit User Code:
4 Press 03 AA G0 G0 G0 G0 J.
ENTER USER CODE UO4 4567 - -
Page 23
23
PROGRAMMING (OPTIONAL)
Reviewing a Programmed User Code
To review an existing User Code, enter the 2-digit user number and the corresponding User Code will display.
Exiting the User Program Mode
When you have completed programming or erasing User Codes, press CC to exit the User Program Mode.
Programming Example Program the User 3 Code to “3784”: 1 Enter your User Code, followed by A.
2 Answer NO (press F ) repeatedly until “ACTIVATE PROGRAM Y/N” is displayed, then press YES (E).
3 The display will read “ENTER USER CODE”
4 Press 03 for User No. 3, then press A, A, followed by 3784. 5 Press J to save the code. 6 Press C to exit the Program Mode.
Notes:
If the system contains more than one keypad, only the keypad designated “No. 1” may be used for programming (if in doubt which is No. 1, ask your installer).
While in Program Mode, the ARMED and STATUS lights remain off and burglar and fire alarm functions are disabled.
In selecting your codes, do not program repetitive numbers (1111), consecutive numbers (1234), your birth date, address, or other obvious combinations. Choose a code of up to six digits (a minimum of four is recommended, and required in UL installations).If the keypad detects no Program Mode activity for more than 4 minutes, a tone will sound. Press CC to silence.
Page 24
24
PROGRAMMING (OPTIONAL)
Enter the User Program Mode
1 Enter your User Code, then press AA to enter the Function Mode.
Answer NO (press FF) until “ACTIVATE PROGRAM Y/N” is displayed, then press YES (EE).
2 “ENTER USER CODE” will display, press NEXT (EE) and the keypad will display the
Zone 1 Description.
Entering a new zone description
Use buttons 11 and 22 to position the cursor within the display.
Use buttons 33 and 66 to scroll through numbers, letters, punctuation marks and a
variety of symbols.
Use the above buttons to enter each character of the description and then press
J to save when the zone description is complete.
To advance to the next zone (or to any other zone):
Move the cursor to the displayed zone number (i.e., “01”) using 11 and 22.
Change the zone number using 33 and 66, then move the cursor to the first
character of the description and program a description for the new zone.
Always pressD to save each zone description
Programming Zone Descriptions
The zone descriptions which appear on the keypad display may be programmed in the User Program Mode.
ACTIVATE PROGRAM Y/N
01- FRONT DOOR
Page 25
25
PROGRAMMING (OPTIONAL)
Enter the User Program Mode
1 Enter your User Code, then press AA to enter the Function Mode. 2 Answer NO (press FF) until “ACTIVATE PROGRAM Y/N” is displayed, then press YES
(E).
3 “ENTER USER CODE” will display, press NEXT (E) until the keypad displays the “Enter
Date” screen.
Programming the Date
1 At the Enter Date screen, simply punch in the correct date using the numeric
keypad buttons. For example, for July 29, 2000, enter: 07 29 00
2 PressJto save the Date
Programming the system Date and Time.
The User Program Mode may also be used to set the system Date and Time which display on the
ACTIVATE PROGRAM Y/N
ENTER DATE
00/00/00
ENTER DATE
07/29/00
ENTER TIME
(12:00A)
ENTER TIME
(06:30P)
Programming the Time
1 After entering in the Date, press NEXT (E) for the Time Entry screen. 2 At the Enter Time screen, simply punch in the correct time using the numeric keypad
buttons and if necessary, press any numeric button to change the AM display to PM (or vice versa) For example, for 6:30 PM, enter: 06 30 06 30 (00 if necessary)
3 Press J to save the Time.
Page 26
26
KEYPAD MESSAGES
The keypad can display the following functional messages. Other diagnostic messages are available for the
installer or servicer. Should any unfamiliar message appear, call your dealer for service.
All zones operating; system can be armed. If displayed, “C” denotes Chime Mode on. (Note: This message may have been customized by your installer.)
Panel reporting to central station on arming. If necessary, wait for ringback signal before exiting.
Exit delay in progress. XXX denotes exit time remaining, in seconds. If displayed, “S” indicates Service Code active; I indicates arming with Instant protection.
Entry delay in progress. XXX shows entry time remaining, in seconds.
System armed. If displayed, “I” indicates arming with Instant protection.
Zones not secured (doors or windows may be open). Faulted zone(s) will scroll.
Arming attempted with faulted zone. The display will scroll the zone faults. Secure the zone(s) and arm system.
(With pulsing sounder.) Trouble condition on a Day Zone (followed by one or more zone descriptions). Press the C button to silence sounder.
SYSTEM READY C (DATE) (TIME)
EXIT TIME XXX SI PLEASE LEAVE
ENTRY TIME XXX DISARM SYSTEM
SYSTEM ARMED I (DATE) (TIME)
*ZONES FAULTED*
ZONES NOT NORMAL
*DAY ZONE TRBL*
PLEASE WAIT FOR RINGBACK
Page 27
27
KEYPAD MESSAGES
Alarm condition, followed by zone description(s). “ALARM” and zones will display after system is disarmed. Note zones, then press C to clear keypad.
(With pulsing sounder.) Trouble condition on a Fire Zone. Press C to silence sounder. Correct trouble or call for service.
(With pulsing sounder.) Alarm condition on a Fire Zone. Press C to silence sounder. Evacuate premises or correct cause of alarm.
(For partitioned systems only.) Code not valid for area.
Wrong code entered or “Easy Bypass” function not enabled.
(In Manager's Mode.) Arming prevented due to unsecured zone. “#” represents number of area with unsecured zone. Press area number, then the G button, then
J to view zones in that area. Correct problem, then arm as normal.
****ALARM****
***FIRE TRBL***
***FIRE ALARM***
CODE DENIED INCORRECT AREA
INVALID ENTRY TRY AGAIN
CAN’T ARM SYSTEM/ AREA # IN TROUBLE
Page 28
28
KEYPAD MESSAGES
The system is in the process of reporting a cancel signal to central station which will cancel the alarm which it has just reported.
The system has received an acknowledgment from central station of the cancellation of the alarm signal.
Indicates problem(s) detected on system. (See examples below and SYSTEM TROUBLE ERROR CODES for a complete list of system troubles and corrective actions.)
Check power transformer. Check for blown fuse or circuit breaker; general power outage.
Battery weak. If not recharged within 24 hours, replace battery.
Communication failure to central station.
ATTEMPTING TO CANCEL
ALARM CANCELED
**SYSTEM TRBL**
LOW BATTERY E02-00 SERVICE
COMM FAIL E03-00 SERVICE
AC POWER FAIL E01-00 SERVICE
Page 29
29
GLOSSARY
Following are brief descriptions of terms and features used herein that may be unfamiliar to you. Some of the features are programmable options that may or may not apply to your particular system.
Abort Delay: A delay period that
allows the control panel to be
reset, thus aborting a report to a
central station.
Access Code: A code (up to 6
digits) used to remotely unlock a
door.
Ambush Code: A 2-digit code
entered just prior to the User
Code when forced to disarm.
Sends a silent alarm to the
central station with no indication
at the keypad.
Area: Some systems may be
divided, or partitioned, into
smaller independent
subsystems, which are referred
to as Areas. Each Area may be
controlled by its own keypad or
by a keypad of a different Area
through Managers Mode.
Arming/Disarming - Turning the
system on/off by entering your code at the keypad, then
pressing J.
Battery - Backup power source in
the control-panel enclosure to provide protection in the event of a power failure.
BPASS Button - Enables you to
manually remove one or more protective zones from the system.
Central Station - Monitors incoming
reports and emergency messages from a digital communicator and notifies the proper authorities.
Chime: A keypad beep while
disarmed alerting that the programmed zone has been opened.
Closing Window: (Optional.) A
time interval within which closing (arming) is permitted without reporting to the central station.
Communicator: Reports
intrusions, emergencies, openings, closings, etc. directly to the central station over telephone lines.
Control Panel: The brain of the
system, it controls all system functions.
Directory: A listing of the
programmed zone descriptions stored in memory.
Easy Arming: Quick arming by
pressingJ (optional).
Page 30
30
GLOSSARY
Exit/Entry Delays: Separate
delays that let you exit and enter your premises without setting off an alarm when the system is armed.
INTERIOR Button: Bypasses
Interior Zones on arming (see Zones - Interior Zones).
Instant Protection: Arming
without entry delay using the
F button while remaining
on the premises.
Keypad: Puts control-panel
functions at your fingertips. It can be mounted anywhere in your premises.
Manager's Mode: In a partitioned
system, a low-security operating mode that allows arming by area.
Panic Buttons: Blue buttons on
the keypad (G and 7,
8 or 9). If enabled,
pressing G together with
7, 8 or 9 will alert
the central station of a fire, auxiliary, or police emergency.
Partitioned System: A system
that has been subdivided into two or more (up to eight) independent subsystems (areas).
Pre-Alarm Warning: A keypad
sounder alert of an impending alarm. This option is programmable by zone for the same duration as that programmed for Abort Delay (see Abort Delay).
Report: A transmission to a
central station notifying of a change in the status of the system (alarm, trouble, low battery, etc.).
RF Low Battery: (Wireless sys-
tems only) Weak transmitter
battery.
F Check In: (Wireless systems
only) Periodic test report from transmitter (if a report is not received on time, a supervisory-failure system trouble will result).
Ringback: A beep after arming
verifying the central-station's receipt of a closing report.
Service Code: A code intended
for temporary use.
Sounder - A local warning device
at each keypad to alert that (a) entry delay has started; (b) an attempt was made to arm with a zone in trouble; (c) a Day­Zone condition exists (see Zones: Day Zone); (d) 10 seconds exit time remaining; (e) invalid code entered; or (f) central station acknowledged arming (see Ringback).
Page 31
31
GLOSSARY
System Trouble: A problem (low
battery, power failure, etc.) detected in the system.
Trouble: A zone fault; an open door,
window, or other problem that may prevent arming.
User Code: Your personalized code
for arming and disarming the system. It may contain up to six digitsZones: Independent circuits that protect specific areas of the premises:
Auto-Bypass Zone: A zone that will
be automatically bypassed from the protection system if it is in trouble (faulty) when the system is armed.
Burglary Zone: Detects intrusion. Day Zone: A zone that will cause a
visual and audible indication at the keypad if it is in trouble while disarmed.
Exit/Entry Follower Zone: Provides
exit and entry delay for interior
devices. Entry delay only occurs if re-entry takes place through the normal exit/entry door first.
Fire Zone: Detects fire alarms or
trouble conditions.
Interior Zones: Circuits within the
premises, usually including space­protection devices, interior doors, etc.; but not exterior doors or windows. These can all be bypassed simultaneously using the E button. (Two groups of
Interior Zones may be programmed for each area.)
Priority Zone: A zone that prevents
arming if in trouble.
Priority Zone with Bypass: A
Priority Zone that can be bypassed using the C button.
Selective-Bypassed Zone: A zone
that can be individually bypassed using the B button.
24-Hour Zone: A zone that is armed
and ready at all times to respond to an emergency situation.
Page 32
32
SYSTEM TROUBLE ERROR CODES
Your control panel is capable of detecting a variety of troubles that may affect system performance. In the unlikely event that a problem should occur, the SYS TBL (system trouble) icon will display on the left side of keypad window along with one or more of the following error codes. If the problem is related to a specific zone or device, the corresponding number will also be indicated. Below is a list of the most common troubles along with the necessary corrective action, if any. If a message appears that is not listed below, call your security professional for service. When a system trouble occurs, the keypad can be silenced and the display can be cleared by pressing C. The system can then be armed and disarmed as usual.
Note: If you cannot clear a system trouble yourself, call installing company for service as soon as possible.
Trouble
Indication
System Trouble
Condition
Action
E01-00
AC Power Failure This trouble will occur if AC power is not present. Make sure system transformer is plugged
into AC receptacle and check the circuit breaker, otherwise call installing company for
E02-00
Low Battery If there has been a recent power failure, the battery may be partially depleted and must be
recharged by the control panel. The control panel performs an automatic daily test of the battery, at which time the trouble will clear if the battery has been recharged.
If the trouble does not clear in 24 hours, call installing company for service.
E03-00
Communication Failure
The system was not able to report to central station. If this is due to a temporary interruption in the telephone service, the trouble can be cleared when the service is restored by performing a Communication Test:
1 While disarmed, enter your User Code followed by A.
1 Answer NO (F) until “ACTIVATE DIALER TEST” appears in the window.
Page 33
33
SYSTEM TROUBLE ERROR CODES
Trouble
Indication
System Trouble
Condition
Action
E04-NN
Wireless Transmitter Supervisory Failure
A problem has been detected with a wireless transmitter. Call installing company for service
E05-NN
Wireless Transmitter Low Battery
The battery in a wireless transmitter is low and should be replaced. This transmitter is on the zone corresponding to the number NN. The replacement battery for the GEM-TRANS2 door/ window transmitter, GEM-PIR motion detector and GEM-GB glass break detector is the Duracell DL123A 3 volt lithium. (2 required for the GEM-PIR and GEM-GB.) The replacement battery for the GEM-SMK is the Duracell MN1604 9 Volt Alkaline (2 required). The GEM-DT Dual Technology Sensor requires 4 C cell alkaline batteries.
Warning: Replace batteries only with the same type as specified above. Use of another battery may present a risk of fire or explosion. Do not recharge or disassemble battery, or dispose of in fire.
E06-NN
Receiver Response Failure
Call installing company for service.
E07-00
Download Failure Call installing company for service.
E08-00
Telephone Line Cut The telephone line has failed. If telephone service has been temporarily interrupted, the
trouble will clear automatically when it is restored. Otherwise, call installing company for
E09-00
System Cold Start
Page 34
34
SYSTEM TROUBLE ERROR CODES
Trouble
Indication
System Trouble
Condition
Action
E10-NN
Keypad Response Call installing company for service.
E11-NN
Keypad Tamper A keypad has been removed from the wall. Call installing company for service if problem
E12-NN
Expansion Zone Module Response
Call installing company for service.
E13-NN
Expansion Module The cover has been removed from a zone expansion module. A problem has been detected
E16-NN
Wireless Receiver A problem has been detected with the wireless receiver. Call installing company for service.
E17-NN
Receiver Tamper Condition
Call installing company for service.
E18-NN
KeyFob Transmitter Low Battery
The batteries in the wireless KeyFob transmitter indicated are low and should be replaced. The replacement battery is the Duracell 386 Lithium battery.
Warning: Replace batteries only with the same type as specified above. Use of another battery may present a risk of fire or explosion. Do not recharge or disassemble battery, or dispose of in fire.
Page 35
35
SYSTEM TROUBLE ERROR CODES
Trouble
Indication
System Trouble
Condition
Action
E19-00
User Program Memory
Call installing company for service.
E20-00
Dealer Program Memory
Call installing company for service.
E21-00
System Shutdown Call installing company for service.
E22-NN
Sensor Watch Activity Failure
A Motion Sensor on the zone indicated has failed the programmed Sensor Watch activity test. Insure that the sensor is able to detect activity in the area; clear any obstacles which may be blocking the sensor from detecting activity. Press C to clear the display, and
then use the Function Menu to Reset Sensor Watch Failure (see page 17). If you cannot correct the problem yourself, call installing company for service.
E23-00
Burglary Bus Failure Call installing company for service.
E24-00
Service Message The system is in need of a preventive maintenance service call. Call installing company for
service.
E39-00
Receiver Capacity Error
Call installing company for service.
E40-00
RF Self Test Failure A wireless motion sensor on the zone indicated has failed its automatic self test routine.
Call installing company for service.
Page 36
36
SYSTEM TROUBLE ERROR CODES
Trouble
Indication
System Trouble
Condition
Action
E41-NN
Fire Trouble A problem has been detected on the Fire zone indicated. Call installing company for service.
E51-00
Bell/Siren Trouble There is a problem with the Bell or Siren. Call installing company for service.
Page 37
37
TROUBLESHOOTING
What do I do if... For more info...
I try to arm my system but the keypad just displays “ZONES NOT NORMAL” and “CAN’T ARM SYSTEM” and beeps at me.
If the green STATUS light is off, a zone is open. Find and secure the open window or door. See Page 6
I try to arm my system but the keypad displays “SYSTEM TROUBLE” and beeps at me. The Error Codes numbers are displayed.
A System Trouble has been detected. Note the scrolling error codes, which represent the trouble. Press C and you will now be able arm to the system, but the trouble must be fixed as
soon as possible.
See Page 7 & 28
The Fire Alarm is sounding and I don’t know how to turn it off.
If a fire is in progress, evacuate the premises immediately! If necessary, call the Fire Department from an outside phone. If there is no evidence of a fire, enter your code and press J to silence the alarm. Note the
Zone Number displayed. Check the smoke detector(s). If a smoke detector tripped, its red alarm indicator light will be on. Press C to silence the keypad sounder.
See Page 11
Page 38
38
NOTES
Page 39
39
NOTES
Page 40
40
NAPCO LIMITED WARRANTY
NAPCO Security Systems, 333 Bayview Avenue, Amityville, NY 11701 OI234B
THE FOLLOWING STATEMENT IS REQUIRED BY THE FCC.
This equipment generates and uses radio-frequency energy and, if not installed and used properly, that is, in strict accordance with the manufacturer's instructions, may cause interference to radio and television
reception. It has been type tested and found to comply with the limits for a Class-B computing device in accordance with the specifications in Subpart J of Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference in a residential installation.
NAPCO SECURITY SYSTEMS, INC. (NAPCO) warrants its products to be free from manufacturing defects in materials and workmanship for thirty-six months following the date of manufacture. NAPCO will, within said period, at its option, repair or replace any product failing to operate correctly without charge to the original purchaser or user.
This warranty shall not apply to any equipment, or any part thereof, which has been repaired by others, improperly installed, improperly used, abused, altered, damaged, subjected to acts of God, or on which any serial numbers have been altered, defaced or removed. Seller will not be responsible for any dismantling or reinstallation charges.
THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF. THERE IS NO EXPRESS OR IMPLIED WARRANTY OF MERCHANTABILITY OR A WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE. ADDITIONALLY, THIS WARRANTY IS IN LIEU OF ALL OTHER OBLIGATIONS OR LIABILITIES ON THE PART OF NAPCO.
Any action for breach of warranty, including but not limited to any implied warranty of merchantability, must be brought within the six months following the end of the warranty period.
IN NO CASE SHALL NAPCO BE LIABLE TO ANYONE FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR BREACH OF THIS OR ANY OTHER WARRANTY, EXPRESS OR IMPLIED, EVEN IF THE LOSS OR DAMAGE IS CAUSED BY THE SELLER'S OWN NEGLIGENCE OR FAULT.
In case of defect, contact the security professional who installed and maintains your security system. In order to exercise the warranty, the product must be returned by the security professional, shipping costs prepaid and insured to NAPCO. After repair or replacement, NAPCO assumes the cost of returning products under warranty. NAPCO shall have no obligation under this warranty, or otherwise, if the product has been repaired by others, improperly installed, improperly used, abused, altered, damaged, subjected to accident, nuisance, flood, fire or acts of God, or on which any serial numbers have been altered, defaced or removed. NAPCO will not be responsible for any dismantling, reassembly or reinstallation charges.
This warranty contains the entire warranty. It is the sole warranty and any prior agreements or
representations, whether oral or written, are either merged herein or are expressly canceled. NAPCO neither assumes, nor authorizes any other person purporting to act on its behalf to modify, to change, or to assume for it, any other warranty or liability concerning its products.
In no event shall NAPCO be liable for an amount in excess of NAPCO's original selling price of the product, for any loss or damage, whether direct, indirect, incidental, consequential, or otherwise arising out of any failure of the product. Seller's warranty, as hereinabove set forth, shall not be enlarged, diminished or affected by and no obligation or liability shall arise or grow out of Seller's rendering of technical advice or service in connection with Buyer's order of the goods furnished hereunder.
NAPCO RECOMMENDS THAT THE ENTIRE SYSTEM BE COMPLETELY TESTED WEEKLY. Warning: Despite frequent testing, and due to, but not limited to, any or all of the following; criminal
tampering, electrical or communications disruption, it is possible for the system to fail to perform as expected. NAPCO does not represent that the product/system may not be compromised or circumvented; or that the product or system will prevent any personal injury or property loss by burglary, robbery, fire or otherwise; nor that the product or system will in all cases provide adequate warning or protection. A properly installed and maintained alarm may only reduce risk of burglary, robbery, fire or otherwise but it is not insurance or a guarantee that these events will not occur. CONSEQUENTLY, SELLER SHALL HAVE NO LIABILITY FOR ANY PERSONAL INJURY, PROPERTY DAMAGE, OR OTHER LOSS BASED ON A CLAIM THE PRODUCT FAILED TO GIVE WARNING. Therefore, the installer should in turn advise the consumer to take any and all precautions for his or her safety including, but not limited to, fleeing the premises and calling police or fire department, in order to mitigate the possibilities of harm and/or damage.
NAPCO is not an insurer of either the property or safety of the user's family or employees, and limits its liability for any loss or damage including incidental or consequential damages to NAPCO's original selling price of the product regardless of the cause of such loss or damage.
Some states do not allow limitations on how long an implied warranty lasts or do not allow the exclusion or limitation of incidental or consequential damages, or differentiate in their treatment of limitations of liability for ordinary or gross negligence, so the above limitations or exclusions may not apply to you. This Warranty gives you specific legal rights and you may also have other rights which vary from state to state.
Loading...