Gelbau 462.4x User Manual

Operating instruction
br
br
A1
A2
Resistance evaluator 462.4x
Technical documentation
07.03.2007
Feature
The resistance evaluator 462.4x is a safety-switching unit designed for monitoring GELBAU Contact­Duo safety connecting blocks with a terminating resistance of 8,2 k. The series 462.4x is a dual­channel version including redundancy monitoring. The stop-outputs (13,14-23,24) include 2 forced safety relays and a reset-function. The additional two­way contact (31, 32, 34) is an alarm contact as well as an auxiliary contact.
The safety system corresponds to standards according to ZH1/494 as well as the European standard EN1760-2 for connecting blocks corresponding to output-equipment.
Construction
Z1 Z2
Z4Z3
Terminal view
Y2Y1
462.4x
stop break
ready
32
K1 K2
A2A1
K3
32313413 14 23 24
Y1 Y2 Z1 Z2
ws
Z4Z3
ws
AC
K1 K2
23 2413 14
34 31
13 14 23 24
+ DC -
Stop
8K2
8K2
Bridge Y1;Y2 = automatical reset
Function
The safety-switch unit is controlled by a closed circuit current. To start the device press reset-contact (Y1, Y2).When correctly connected in ready-mode the safety contacts (13, 14-23, 24) are connected and both green LED`s are on. If the Duo-contact-edge is activated (pressed) the relays K1 and K2 de­energise and the safety contacts (13, 14-23, 24) are open. The red LED is on (stop). If the closed­circuit current between Z1 and Z2 or Z3 and Z4 is interrupted the red (stop) LED is on and if in reset mode even the yellow LED (break) is on. Safety-switches 13, 14-23, 24 are open. The additional change-over contact 31, 32, 34 connects synchronous to STOP contact 13, 14. An automatic reset can be achieved by connecting terminals Y1 – Y2.
Important: The additional change-over contact 31, 32, 34 is an auxiliary contact and must not be used in safety-circuit.
Function table (status indication for sensor) Sensor-profile condition
Correct connected; not activated on closed Sensor 1 or2 activated (pressed) on open Sensor 1 or2 interrupted (disconnected or break) *1 = only by activated reset or automatic reset
LED red LED yellow LED green
Output 13,14,23.24
(2x)
on on *1 open
E452x.doc Gelbau GmbH & Co. KG D – 53859 Niederkassel – Ranzel Phone. 02208 / 9455-0 Fax 02208 /
Operating instruction
The installation and putting into operation of this device has to be
Resistance evaluator 462.4x
Technical documentation
07.03.2007
Assembly, Application
1. The switch-cabinet housing is ready for mounting on a 35 mm DIN rail (TS35) according to DIN
50022. For switchboard installation, a 26 mm rail-segment with 2 drillings is available.
2. The GELBAU contact-duo connecting-block(s) with an end-terminated resistor is connected to clamps Z1 Z2 and Z3 Z4. Please note that the brown wire is connected to terminal Z1 (Z3) and the white (blue) wire is connected to terminal Z2 (Z4). If you want to install one contact-duo connecting-block (Z1,Z2) the second input must be terminated with a 8,2k resistor.
3. The safety-relay outputs 13,14-23, 24 may be loaded with max. 4 A (AC). The additional change­over contact 31, 32, 34 can be loaded with 4 A.(Max. switching voltage 250 V AC)
4. Power supply must be connected to terminals A1 and A2. The phase-wire is connected to A1.
done by qualified staff only.
Trouble shooting problems
1. LED`s are out of operation Correct side voltage?
2. Constant glow of both red and yellow LED in manual or automatic-reset mode Is the contact edge connected correctly or is there an interruption in the contact wire? (Test switch shortly 8,2k resistance between Z1,Z2 and Z3,Z4),interrupt if function is o. k.
3. Constant glow of red LED Disconnect contact edge and examine it with an ohmmeter (value has to show approx. 8,2 k). Possibly short-circuit in lead-in wire?
4. Both channels show different status Send device to your dealer for control and repair.