The ATP1000 lets you control all programming and operation of compatible security systems
(see the “Specifications” section).
The large 2-line, 16-character display provides easy to read messages to indicate the current status of the system. The touchpad includes police, fire, and auxiliary panic buttons that can be activated anytime. A built-in speaker provides alarm, status, and button-press sounds. A swingdown door reveals a label with basic system operating commands. The door can be removed by
simply opening it past its stop point. The door can also be reattached later if desired.
Tools and Equipment Needed
•4-conductor, 22- or 18-gauge wire
•Screwdriver
•#6 screws and anchors (included)
•Panhead screws for gang box installation
•Saw or utility knife for cutting wallboard
,QVWDOODWLRQ,QVWUXFWLRQV
'RFXPHQW1XPEHU5HY$
2FWREHU
InstallationGuidelines
•Mount the touchpad in an environmentally controlled area (32°F to 120°F/0°C to 49°C).
•When mounting the touchpad, allow at least 3 inches below it for the swing-down cover.
•Do not exceed the maximum available power. See the panel installation instructions for maximum available power.
•Table 1 describes the power used by the touchpad.
•Table 2 describes the maximum wire lengths allowed between the touchpad and the panel.
Table 1: Touchpad Power Usage
Current (mA)Conditions
110Maximum alarm current with the
60Typical operation
12Power saving mode (no panel AC
Table 2: Maximum Touchpad Wire Lengths
Wire Gauge
(Unshielded or
Shielded)
18750 feet
22300 feet
buzzer sounding and the touchpad
illuminated from a button press
power)
Max. Touchpad Wire Length
Between Touchpad and Panel
1
Page 2
Installing the Mounting Plate
1. Separate the mounting plate from the touchpad by first loosening the screw, then lift the
touchpad away from the mounting plate (see Figure 1).
Note
Do not overtighten screws or
the mounting plate may bind
and prevent the touchpad
from mounting properly.
Loosen screw,
then lift touchpad.
Figure 1. Separating the Touchpad from the Mounting Plate
2. For wall mounting, place the mounting plate on the wall and mark the mounting holes
(see Figure 2). Be sure to leave a 3-inch clearance below for the touchpad door to open.
Mounting Holes
Mounting Holes
Figure 2. Mounting Hole Locations
3. Insert anchors into the wall at the marked locations where studs are not present.
4. Align the mounting plate holes with the wall or gang box screw holes and secure the
back plate using the screws provided.
5. For wall-mount installations, cut a hole in the wall in the wire access area of the mounting plate to pull the wiring cable through.
Wiring the Touchpad to the Panel
1. Remove panel AC and backup battery power.
2. Run a 4-conductor, 18- to 22-gauge wire from the panel to the touchpad location (see
Tabl e 2).
3. Connect the touchpad +12V, BUS A, BUS B, and GND terminals to the matching panel
terminals (see Figure 3 for touchpad terminal identification).
Attaching the Touchpad to the Mounting Plate
Align the tabs at the top of the mounting plate with the slots on the touchpad and swing the
touchpad bottom toward the mounting plate. Gently tighten the screw into the bottom of the
touchpad.
After making all wiring connections from the touchpad to the panel, you are ready to power up
the panel and verify correct communication between the touchpad and the panel. Upon power up,
the panel scans the bus for connected devices, assigns a unit number to each bus device, and automatically learns the device ID number of each bus device.
1. Verify that all wiring between the panel and touchpad is correct.
2. Connect the panel battery and restore AC power. Alphanumeric touchpads briefly show
SCANNING BUS DEVICES, then display date and time.
3. At the touchpad, enter program mode by pressing 8 + installer/dealer code (default =
4321) + 0 + 0. The touchpad should display SYSTEM PROGRAMMING.
4. Press
5. Press A or B until the display shows ACCESSORY MODULES, then press
ƒ and the display shows SECURITY.
ƒ. The display
should read BUS DEVICES.
6. Press
ƒ. The display shows the lowest device address and its ID. The following example
shows what a device address display may look like:
UNIT - ID
0—02110185**The 8-digit SuperBus ID number is also located on a label on back of the touchpad.
7. Press A or B to cycle through all bus device addresses until the touchpad appears.
8. After verifying the touchpad device ID, press
‚ repeatedly until the display shows SYSTEM
PROGRAMMING.
9. Press A or B until the display shows EXIT PROGRAMMING READY, then press
ƒ. The
touchpad should show the date and time display.
ProgrammingTo program options for the newly installed touchpad (such as key beeps) see the specific panel
installation instructions.
Connecting the
Touchpad for
System
Programming
Only
For installations that don’t include an alphanumeric touchpad as a permanent part of the system,
you can connect one for system programming to the Programming Touchpad Header on the
panel.
To do this you must first connect a Programming Touchpad Cable (60-791) to the touchpad wires
(see Programming Touchpad Cable Installation Instructions—466-1604, included with the
cable). Then, use the appropriate procedure for connecting the touchpad.
To connect a programming touchpad to a Concord Express, Concord, or Concord Ultra
panel with software version 2.0 or later:
1. With the panel powered up, connect the cable to the Programming Touchpad Header (see Figure 4).
When using the ATP1000 as a programming touchpad, be careful not to touch its cir-
!
Caution
.
cuit board which is exposed on the backside.
2. Activate the touchpad by pressing 8 + CODE + 0 + 2.
PROGRAMMING
TOUCHPAD
6
9
CABLE (60-791)
8642G29A.DS
TestSystemWeekly
A41
B
C
D
Stay
Away
Off
23
pressboth
Silent
Pager
NoDelay
5
pressboth
Features
System
Menu
8
7
pressboth
Status
Lights
Bypass
0#
*
Figure 4. Connecting a Programming Touchpad—Concord Express Shown, Concord Similar
3. Enter program mode by pressing 8 + installer/dealer CODE + 0 + 0 and program the
panel using the panel Installation Instructions.
4. When programming is completed, simply disconnect the programming touchpad.
To connect a programming touchpad to a Concord panel with software versions 1.0–1.6:
1. Disconnect AC and backup battery power.
2. Connect the cable plug onto the panel Programming Touchpad Header pins (see Figure 5).
3. Reconnect the AC and backup battery power. The touchpad briefly displays ***********,
SCANNING BUS DEVICES, then shows a time and date display.
Note
If the touchpad does not respond as described in step 3, there may be a bus conflict. To correct this,
change the touchpad unit number as described in the section “Changing the Touchpad Unit Number.”
Removing the programming touchpad from Concord panels with software versions 1.0–1.6:
To prevent a trouble condition, you must delete the programming touchpad unit number from
Concord panel memory before disconnecting it.
1. After programming is completed, return to the ACCESSORY MODULES menu, then press
The display should read BUS DEVICES.
2. Press
3. Press A or B until the display shows the programming touchpad unit number.
4. Press D to delete the device and its unit number from panel memory. The display shows:
5. Exit program mode and disconnect the programming cable from the panel header.
ƒ. The display shows the lowest unit number and its device name.
UNIT - TYPE
14-NONE
ƒ.
TestingNote
Contact the central monitoring station before activating alarms, to avoid dispatching local police and fire
departments.
Test the touchpad by arming/disarming the system, activating the touchpad panics, bypassing
sensors, and by turning chime and lights on/off to verify correct operation. Refer to the panel
User’s Manual
Adjusting
Display
Brightness and
Contrast
The touchpad display can be adjusted for easier viewing to help compensate for lighting conditions in the touchpad location.
The brightness adjustment lightens or darkens the background. The contrast adjustment lightens
or darkens the text.
To adjust display brightness:
1. Enter user programming mode by pressing 9 + user, partition, or system master CODE.
The display shows SYSTEM MENU, then TIME AND DATE
(Concord panels with software versions 1.0–1.6 display USER CODES.)
2. Press B until the display shows OPTIONS, then press
ING ON/OFF (current setting).
3. Press B twice and the display shows TOUCHPAD BRIGHTNESS 2 (default setting).
4. Enter a setting from 0 (darkest background) to 3 (brightest background), then press
5. The display flashes the entered selection, then stops after pressing
ting and brightness level.
6. Exit user programming mode.
To adjust display contrast:
for complete system operating instructions.
ƒ. The display shows DOWNLOAD-
ƒ.
ƒ and displays the new set-
1.Enter configuration mode by pressing the D and 6 buttons together for at least two seconds.
The display shows DA nnn.
2.Press and release the
displayed.
3.Press
4
1 and 2 buttons together repeatedly, until the desired contrast level is
‚ and the display briefly shows DONE, then shows the time and date.
TroubleshootingTable 3 describes what to do if the touchpad does not operate correctly.
Table 3: Troubleshooting
ProblemAction/Solution
Touchpad doesn’t
power up (no
display and no
beeps when
buttons are
pressed).
Touchpad display
appears blank, but
beeps sound when
buttons are
pressed.
Touchpad display
shows a flashing *,
indicating a trouble
condition and
system doesn’t
respond to
commands from
touchpad.
1. Check for correct wiring
connections at touchpad
and panel terminals.
2. Make sure panel battery
is connected correctly
and that the panel transformer is plugged in.
3. Make sure panel transformer is not plugged
into an electrical outlet
controlled by a switch.
Relocate transformer to
an unswitched outlet
location, if necessary.
1. Check the touchpad display contrast setting. It
may be set to 0 (no display).
1. Check for correct bus
wiring connections
(green and white wires)
at touchpad and panel
terminals.
2. Make sure touchpad unit
number is set to a different number than all other
bus devices. If necessary, change the touchpad unit number (see
procedure on this page).
(Concord panels with
software versions 1.0-
1.6 only.)
Changing the
Touchpad Unit
Number
Panels with Software
Version 1.0-1.6 Only)
(Concord
Use the following guidelines when changing device unit numbers to avoid communication conflicts between bus devices and the panel:
•All bus devices with DIP switches (LED Touchpads, ESMs, HIMs, etc.) must be set to the
desired unit number before applying power and entering program mode.
•Whenever possible, assign touchpad unit numbers before all other panel programming.
To change the touchpad unit number:
1. At the touchpad, press and hold the D and 6 buttons together for at least 2 seconds. The display should show DA n, where n is the current touchpad unit number (000 - 015).
Note
At this time, the touchpad is in configuration mode and no longer communicating to the panel. The system may immediately indicate a bus failure. Ignore the failure and continue with the procedure. The bus
failure will clear after successfully changing the touchpad unit number.
2. Press ƒ. The display shows ENTER _.
3. Enter the desired three digit unit number (000 - 015), then press
where n is the new touchpad unit number.
4. Do not use unit number 15 in Concord RF systems.
5. Press
Note
If the new touchpad unit number was previously learned by the panel, communication between the
touchpad and the panel begins immediately. However, if the new touchpad unit number has never been
6. Force the panel to scan bus devices as follows:
For systems where this is the only installed touchpad, remove panel AC and battery power,
then re-apply power.
For systems with more than one touchpad, go to another system touchpad and enter 8 +
installer/dealer
CODE (default = 4321) + 0 + 1. The display shows SCANNING BUS
DEVICES, then a time and date display.
The touchpad and all other bus devices should operate correctly and any bus failures should be
cleared.
Note
If the panel still indicates a bus failure the panel may have previously learned a unit number that is no
longer used by any bus device. See the specific panel Installation Instructions for more information on
deleting unused unit numbers.
Power Requirements: ................12 VDC nominal (See Table 1 for additional power requirements.)
Temperature Range: ..................32°F (0°C) to 120°F (49°C)
Maximum Humidity: ................95% relative, non-condensing
Dimensions: ..............................5.0” x 4.50” x 0.75” (L x W x D)
UL Listings (all applied for):.....UL 985 Household Fire Warning System Units
...................................................UL 1023 Household Burglar-Alarm System Units
...................................................UL 1610 Central Station Burglar-Alarm Units
Note
See specific panel Installation Instructions for complete UL installation requirements for the system you
are installing.
(Commercial Burglary)
NoticesFCC Part 15 Information to the User
Changes or modifications not expressly approved by GE Interlogix can void the user’s authority to operate the equipment.
FCC Part 15 Class B
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the
FCC Rules. These limits are designed to provide reasonable protection against interference in a residential installation.
This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with
the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation.
If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the
equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect the affected equipment and the panel receiver to separate outlets, on different branch circuits.
Consult the dealer or an experienced radio/TV technician for help.