GE Industrial Solutions ZBTSCTH User Manual

OPERATION AND MAINTENANCE MANUAL ZBTSCTH SERIES POWER PANEL 100 - 4000 AMPS
46R-7000D Rev 8/97
INTRODUCTION
Zenith Bypass-Isolation Closed Transition Transfer Switches provide Zenith’s most comprehensive load power protection during standard operation, maintenance and testing procedures.
Closed Transition Transfer Switches parallel two available sources of power during test procedures to enable transfer without interrupting power to the load (make-before-break). Paralleling of the two sources occurs within a predefined window of synchronization and the initial source is then disconnected. If the primary source falls below preset voltage limits and the second source is available, the transfer switch defaults to open transition (break-before-make) mode. In this mode, the transfer switch uses the power from the available source to open the switch from the “dead source” first, before closing the switch into the second source. When in the Bypass­Isolation mode, the switch acts as a manual transfer switch, enabling testing, repair and even removal of the automatic transfer switch.
All Zenith transfer switches are designed for use on emergency or standby systems, and are rated for total system or motor loads. Transfer switches are UL Listed under Standard 1008 and CSA Certified under Standard C22.2 No. 178.
This manual provides information on the installation, operation, and maintenance of the switch. In addition, a complete information package is supplied with each transfer switch which details the features and accessories provided on that switch. The information package and the instruction manual should be kept in a readily accessible location to provide complete reference information on this critically important piece of equipment.
TABLE OF CONTENTS
Section I INSTALLATION
1. Requirements
2. Equipment Inspection and Storage
3. Mounting
4. Power Connections
5. Control Connections
6. Final Equipment Inspection
7. Functional Test
Section II OPERATION AND FEATURES
1. Sequence Of Operation
2. Bypass-Isolation Switch Operation
3. Zenith Standard Package
4. Zenith Optional Accessories
Section III MAINTENANCE AND TESTING
1. Inspection and Cleaning
2. Servicing
3. Testing
4. Troubleshooting
5. Emergency Service Procedure/Extended Parallel Time
2
2 2 2 3 4 5 5
6
6
8 11 11
12
12 12 12 13 14
Section IV ADJUSTMENTS AND SETTINGS
1. Paralleling Relay Settings
2. Solid State Timers
3. Voltage/Frequency Sensor (VFSM)
4. Solid State Phase Relay (ARSM)
5. Paralleling Window Under-Overvoltage Sensing Relay
6. Electronic Time Switch Z2000-2A
Appendix A TYPICAL SCHEMATIC DIAGRAMS
1. 100-400 Amps
2. 600-3000 Amps
3. Alarm Circuit Schematic
4. Three-Phase Control Sensing Schematic
5. Bypass Control Circuit
Appendix B REPLACEMENT PARTS
1. Power Panel — 100-400 Amps
2. Power Panel — 600-1200 Amps
3. Power Panel — 1600-3000 Amps
4. Bypass Subpanel
5. Control Panel Layout and Parts List
6. Cabinet Door Pilot Devices
16
16 16 16 17 17 17
19
19 20 21 21 22
23
23 23 24 24 28 31
SECTION I - INSTALLATION
!
!
!
DANGER
HAZARDOUS VOLTAGE
(Can Cause Severe Injury or Death)
Turn OFF all power before installation,
adjustment, or removal of transfer switch
or any of its components.
Each Zenith transfer switch is factory wired and tested. A complete information package is furnished with each switch which includes:
a. Sequence of operation. b. Description and operation of all
accessories supplied.
c. Power panel connection diagram and
schematic.
d. Description and identification of all
customer field connections.
Installation of Zenith transfer switches includes:
a. Mounting the transfer switch cabinet. b. Connection of all Normal, Emergency,
and Load cables or bus bars.
c. Connection of external control circuits
as required.
1. REQUIREMENTS
DANGER
Closed transition transfer switches typically require momentary paralleling of utility and generator sources. The customer should obtain approval from their utility before using a closed transition transfer switch.
Before installation, it is necessary to store the transfer switch in a clean dry place, protected from dirt and water. Provide ample air circulation and heat, if necessary, to prevent condensation.
Storage Temperature:
-30 C to + 65 C (-22 F to +149 F)
Operating Temperature (Ambient):
-20 C to +75 C (-4 F to +167 F) [40-260 Amps]
-20 C to +40 C (-4 F to +104 F)[400-3000 Amps]
Humidity:
5% to 95% (non-condensing)
3. MOUNTING
Adequate lifting means must be used to mount the transfer switch into place. The recommended method for moving the transfer switch using the lifting eyes and a spreader bar is illustrated in Figure 1. Enough room should be allowed to open the cabinet doors fully for inspection and servicing of the switch per NEC and local codes.
Before drilling conduit entry holes or any accessory mounting holes, cover and protect the switch and control panel to prevent dirt and metal fragments from entering the mechanical and electrical components. Failure to do so may result in damage and malfunction of the switch.
H
45°
SPREADER BAR
The following requirements must be met to use a closed transition transfer switch:
a. Isochronous governor with a frequency
range of 60 ± 0.2 Hz.
b. Shunt trip breaker on the genset with
a response time not exceeding 50 milliseconds.
2. EQUIPMENT INSPECTION AND
STORAGE
Immediately inspect the transfer switch when received to detect any damage which may have occurred during transit. If damage is found or suspected, file claims as soon as possible with the carrier and notify the nearest Zenith representative.
ZBTSCTH Operation and Maintenance Manual (46R-7000)2 Zenith Controls, Inc.
LIFTING EYES
CABINET
D
Figure 1
NOTICE
When lifting the switch using a spreader bar, height H must be equal to half of distance D.
SECTION I - INSTALLATION (Continued)
4. POWER CONNECTIONS
Zenith transfer switches are supplied with UL listed solderless screw type terminals as standard for the Normal, Emergency, and Load power connections. Table 1 lists the number and sizes of the cable lugs supplied as standard for each switch amp rating.
Connect the Normal, Emergency, and Load conductors to the clearly marked terminals on the transfer switch. Remove surface oxides from cables by cleaning with a wire brush. Verify that
all connections are correct before tightening the lugs. All cable lug connections must be tightened to the proper torque values as shown in Table 2.
Do not run cables or wiring behind front­connected transfer switches.
In cases where the Normal, Emergency, and Load connections are made to a rear connected bus bar, a compression washer, flat washer, and a minimum grade 5 bolt must be used and torqued to the values in Table 3.
Screw Type Terminals for External Power Connections
Switch Size
(Amps)
100 1 #14 to 1/0 AWG 3 #14 to 1/0 AWG 150 1 #8 to 3/0 AWG 3 #6 AWG to 300 MCM 225 1 #6 AWG to 250 MCM 3 #6 AWG to 300 MCM 260 1 #6 AWG to 350 MCM 3 #6 AWG to 300 MCM
Normal, Emergency & Load Terminals Fully Rated Neutral Bar (When Required) Cable Per Pole Range of Wire Sizes Number of Cables Number of Cables
400 1 #4 AWG to 600 MCM 4 #6 AWG to 300 MCM 600 2 #2 AWG to 600 MCM 8 #2 AWG to 600 MCM
800 1000 1200 1600 2000 3000 4000
Line and load terminals are located in rear and arranged for bus bar connection.
4 #2 AWG to 600 MCM 12 #2 AWG to 600 MCM
12 3/0 AWG to 750 MCM
Table 1
Tightening Torque for Lugs
Socket Size Torque
Across Flats Lb.-In. Lb.-Ft.
1/8 45 4 5/32 100 8 3/16 120 10 7/32 150 12
1/4 200 17 5/16 275 23
3/8 375 31
1/2 500 42 9/16 600 50
Tightening Torque for Bus Bars
Bolt Size Torque Bolt (Grade 5)
Lb.-In. Lb.-Ft.
1/4-20 72 6
5/16-18 132 11
3/8-16 300 25 1/2-13 720 60
Table 3
Table 2
ZBTSCTH Operation and Maintenance Manual (46R-7000)Zenith Controls, Inc. 3
SECTION I - INSTALLATION (Continued)
5. CONTROL CONNECTIONS
A complete information package is furnished with each transfer switch including a complete connection diagram and schematic which details all necessary control circuit field connections.
The engine start control wires connect to the terminals specified in the upper right corner of the bypass cabinet. Terminals for field connections to the A3 Emergency auxiliary contacts and the A4 Normal auxiliary contacts are also provided. These terminals are clearly marked and appear on the left side of the ATS power panel. Figure 2 below shows the location of these terminals.
Make all other necessary external control connections to the appropriate terminal blocks located on the control panel. Insure that all connections are tightened to the torque specified in Table 4.
Control Wire Connections
Wire Size (AWG) Torque Lb.-In.
18-16 19
14-8 19
6-4 36
Table 4
Figure 2
ZBTSCTH Operation and Maintenance Manual (46R-7000)4 Zenith Controls, Inc.
SECTION I - INSTALLATION (Continued)
!
6. FINAL EQUIPMENT INSPECTION
Prior to energizing the transfer switch:
a. Remove any debris incurred due to
shipment or installation. DO NOT use a blower since debris may become lodged in the electrical and mechanical components and cause damage. Use of a vacuum is recommended.
b. Verify that all cabled connections are
correct and that phase rotation of both sources match.
c. Check engine start connections and verify
the correct connection of all control wires.
d. Check settings of all timers and adjust as
necessary. Also adjust any optional accessories as required. [See MX200 manual (50R-2000) for instructions on timer and option adjustments.]
e. Check the integrity of power connections
by verifying actual lug torque values as specified in this manual.
f. Make sure that all covers and barriers are
installed and properly fastened.
7. FUNCTIONAL TEST
pick up and the LED indicator will illuminate. Check the phase to phase voltages at the Emergency line terminals. Also, verify that the phase rotation of the Emergency source is the same as the phase rotation of the Normal source.
After the sources have been verified, shut down the engine generator, and put the starting control in the automatic position. Complete the visual inspection of the transfer switch, and close and lock the cabinet door.
Initiate the electrical transfer test by activating the test switch (TS). This de-energizes the engine start relay. The transfer switch closes into Emergency only after the sync-check relay ensures the proper phase relationship of both sources. After the transfer switch closes into Emergency, the SE limit switch becomes activated to de-energize the CCE relay and energize the CCNO relay. This opens the transfer switch out of Normal. When the transfer switch has opened out of Normal, the SNO-2 limit switch activates to de-energize the CCNO relay. The transfer switch has now closed into Emergency power without interrupting the load.
The functional testing of the transfer switch consists of electrical tests described in this section. Before proceeding, refer to the information package supplied with the transfer switch. Read and understand all instructions and review the operation of all accessories provided.
Before starting the operation test, check the equipment rating nameplate on the transfer switch to verify the correct system voltage. An example of the equipment rating nameplate is shown in Figure 3.
Figure 3
To begin the test, close the Normal source circuit breaker. Phase relays B1, B2, and B3 will pick up and the LED indicators will illuminate. Verify the phase to phase voltages at the Normal line terminals.
Next, close the Emergency source breaker and start the engine generator. The VFSM relay will
ZBTSCTH Operation and Maintenance Manual (46R-7000)Zenith Controls, Inc. 5
Turning the TS to AUTO initiates re-transfer to Normal. The transfer switch closes into Normal only after the sync-check relay ensures the proper phase relationship of both sources. After the transfer switch closes into Normal, the SN limit switch becomes activated (de-activated in 400 Amp units) to de-energize the CCN relay and energize the CCEO relay; the transfer switch opens out of Emergency. Then the SEO-2 limit switch activates to de-energize the CCEO relay. The transfer switch has now closed back into Normal power without interrupting the load.
The transfer switch defaults to an open transition transfer when the Normal source fails. Closed transition transfer is not possible with one source available. Open transition transfer for testing can be selected via the transition mode selector switch. (For a description of the Open Transition sequence of operation, refer to Section II ­Operation and Features, page 6.)
A 24 VDC circuit is supplied to control the alarm and warning indicators. To ensure continuous power to this circuit, a constant 24 VDC can be supplied by the customer from the engine start battery.
NOTICE
A periodic test of the transfer switch under load conditions is recommended to insure proper operation.
SECTION II - OPERATION AND FEATURES
1. SEQUENCE OF OPERATION
Figure 4 is a typical schematic diagram of a Zenith closed transition transfer switch. The information supplied with the transfer switch includes a schematic diagram and description of operation of all accessories provided.
Transfer of the load to the Emergency source begins automatically when any phase of the Normal source falls below the preset dropout point and this undervoltage failure condition is detected by solid state phase relays B1, B2, B3.
The phase relays drop out, de-energizing the Normal control relays CR & CR2, and engine start timer P1 begins its timing cycle. The P1 time delay is provided to override momentary outages and to prevent nuisance starting of the engine generator. If the Normal source voltage returns above the phase relays’ pickup setting, the P1 timing cycle is reset to zero by re-energizing the CR relay.
If the normal source voltage does not return before the P1 time delay is completed, the P1 timer drops out and sends a starting signal to the engine generator. An Emergency voltage and frequency sensing relay (VFSM) monitors the voltage and frequency of the Emergency source. When both the voltage and the frequency of the Emergency source reach the preset pickup points, the VFSM relay initiates transfer to the Emergency source and timer W begins it timing cycle. The W timer provides an adjustable transfer delay to the Emergency source as required.
When the W time is completed, the Emergency control relay RT energizes and picks up the CCNO relay. The CNO solenoid is then energized to open the transfer switch from normal position to neutral position. The switch remains in the neutral position for the duration of the DW time delay. After the DW time delay is completed, the CCE relay energizes the CE solenoid to close the transfer switch into the emergency source. The SE limit switch activates to de-energize the CCE relay.
The sequence for retransfer to the Normal source begins automatically when the voltage on all phases of the Normal source reach the preset pickup point and this condition is detected by the solid state phase relays, B1, B2, B3.
When the Normal source restores and if the transition mode selector switch is in CT (Closed Transition), the transfer switch will return to the Normal source in a make-before-break sequence (this is described in the Testing section of this manual).
If the transition mode selector switch is in OT (Open Transition), the transfer switch will return to the normal source in a break-before-make sequence. When the Normal source restores, the solid state phase relays, B1, B2, B3 pick up and switching to the Normal source is initiated by energizing timer T, beginning its timer cycle. The T timer provides an adjustable delay to insure that the Normal source has stabilized before reconnection to the load. If the Normal source fails before the T time delay completes, the phase relays drop out and the T timing cycle is reset to zero.
When the T time delay is completed, the Normal control relay CR energizes and picks up the power relay CCEO. This energizes the CEO solenoid opening the transfer switch out of the emergency source. The SEO-1 limit switch activates to energize the DT time delay and de-energize the CCEO relay. After the DT time delay is completed, the CCN relay energizes the CN solenoid to retransfer the switch into the normal source. The SN limit switch activates to de-energize the CCN relay. The SN limit switch also energizes the engine over-run timer U and begins its timing cycle. This timer provides a period of time for the engine generator to run without load and cool down before shutdown. After the U time delay is completed, the P1 timer isenergizedand the enginegeneratoris shutdown.
NOTES:
1. The transition mode selector switch on the front door enables the user to operate the unit in Open Transition mode, if so desired.
2. When in Closed Transition mode, if the transfer switch does not open the first source within 100 milliseconds, an alarm will sound, the transfer switch will open the last source it closed in to and will lock out the control circuit from any transfer operation. After the condition has been corrected the control circuit should be reset by turning the Failed to Open Lockout Reset switch to the right.
3. The controls will provide a signal to shunt trip the generator breaker if the transfer switch remains closed into both sources for more than 325 ms. The load will then be fed by the utility source. The maximum time that the two sources would be parallel, under these conditions, is less than 0.5 sec. Before operating the closed transition transfer switch the condition must be corrected and the shunt trip reset. Refer to the procedure for servicing the switch after shunt tripping occurs. The shunt trip reset switch is provided on the front door. Alarm and lights on the front door provide indication of failure conditions.
ZBTSCTH Operation and Maintenance Manual (46R-7000)6 Zenith Controls, Inc.
SECTION II - OPERATION AND FEATURES (Continued)
Figure 4
ZBTSCTH Operation and Maintenance Manual (46R-7000)Zenith Controls, Inc. 7
SECTION II - OPERATION AND FEATURES (Continued)
2. BYPASS-ISOLATION OPERATION - 100-400 AMP
a. Automatic
1) Manually operated bypass switch contacts (BN/BE) are open and ATS is supplying load.
2) Disconnect Switch (DS) is in Auto.
b. To Bypass ATS
1) Open bottom cabinet door and turn DS to Inhibit.
2) Position Manual Bypass Handle (MBH) to same power source as ATS.
c. To Test ATS
1) Bypass per above instructions.
2) Move ATS Location Handle (ALH) to Test location.
3) Turn DS to Auto.
4) Test Switch (TS) on bottom cabinet door will allow electrical operation of ATS.
d. To Isolate ATS
1) Bypass per above instructions.
2) Move ALH to Isolate location.
e. To Remove ATS
1) Bypass and isolate per above instructions.
2) Move ALH to Release location.
3) Disconnect multipin plugs.
4) Lift ATS out of drawer.
f. To Reconnect ATS
1) Place ATS into drawer slots (front rollers first).
2) Turn DS to Inhibit.
3) Manually position ATS into same source as bypass switch.
4) Reconnect multipin plugs and external connections to ATS.
5) Push ATS inward to engage carriage.
6) Move ALH to Test location (as indicated by light).
7) Turn DS to Auto and use TS to electrically operate ATS.
8) Turn DS to Inhibit.
9) Move ALH to Auto location.
10)Turn DS to Auto and open bypass with MBH.
11) ATS is now fully automatic.
Notes:
1. DS in Inhibit will prevent ATS electrical operation.
2. Do not use excessive force on mechanical handles.
3. Figures depict Bypass Normal. Sequence is the same for Bypass Emergency.
4. When ATS is in Test or Isolate, bypass switch is manual; transfer switch to either available source (indicated on light panel).
5. To operate bypass switch when ATS is in Test or Isolate, position MBH to available power source.
Legend:
1. BP - bypass switch (indicated by contacts BN/BE) is a three position switch.
2. ATS -Automatic Transfer Switch.
ZBTSCTH Operation and Maintenance Manual (46R-7000)8 Zenith Controls, Inc.
SECTION II - OPERATION AND FEATURES (Continued)
3. BYPASS-ISOLATION OPERATION - 600-1200 AMP
a. Automatic
1) Manually operated bypass switch contacts (BN/BE) are open and ATS is supplying load.
2) Disconnect Switch (DS) is in Auto.
b. To Bypass ATS
1) Open bottom cabinet door and turn DS to Inhibit.
2) Turn Bypass Selector Switch (BSS) to same power source as ATS.
3) Move the Manual Bypass Handle (MBH) upward.
c. To Test ATS
1) Bypass per above instructions.
2) Rotate crank mechanism counterclockwise until ATS Test light is illuminated.
3) Turn DS to Auto.
4) Test Switch (TS) on bottom cabinet door will allow electrical operation of ATS.
d. To Isolate ATS
1) Bypass per above instructions.
2) Rotate crank mechanism counterclockwise until ATS Isolated light is illuminated.
e. To Remove ATS
1) Bypass and isolate per above instructions.
2) Disconnect multipin plugs and external connections to ATS.
3) Rotate four power panel latches to vertical position, slide ATS forward and lock mechanism in place.
4) ATS can now be removed from cabinet.
f. To Reconnect ATS
1) Place ATS in slide mechanism.
2) Unlock slide mechanism. Slide ATS over power panel latches and rotate latches to horizontal position.
3) Turn DS to Inhibit.
4) Manually position ATS into same source as bypass switch.
5) Reconnect multipin plugs and external connections to ATS.
6) Rotate crank mechanismclockwiseuntilATS Test light is illuminated.
7) Turn DS to Auto and use TS to electrically operate ATS.
8) Turn DS to Inhibit.
9) Move ALH to Auto location.
10)Turn DS to Auto and open bypass with MBH.
11) ATS is now fully automatic.
Notes:
1. DS in Inhibit will prevent ATS electrical operation.
2. Do not use excessive force on mechanical handles.
3. Figures depict Bypass Normal. Sequence is the same for Bypass Emergency.
4. When ATS is in Test or Isolate, bypass switch is manual transfer switch to either available source (indicated on light panel).
5. To operate bypass switch when ATS is in Test or Isolate: a) Move MBH downward (to open
open Bypass Contacts BN/BE).
b) Turn BSS to opposite power
source.
c) Move MBH upward to close
into selected power source.
Legend:
1. BP - Bypass Switch (indicated by contacts BN/BE) is a three posi tion switch.
2. ATS - Automatic Transfer
Switch.
ZBTSCTH Operation and Maintenance Manual (46R-7000)Zenith Controls, Inc. 9
SECTION II - OPERATION AND FEATURES (Continued)
4. BYPASS-ISOLATION OPERATION - 1600-4000 AMP
a. Automatic
1) Manually operated bypass switch contacts (BN/BE) are open and ATS is supplying load.
2) Disconnect Switch (DS) is in Auto.
b. To Bypass ATS
1) Open bottom cabinet door and turn DS to Inhibit.
2) Turn Bypass Selector Switch (BSS) to same power source as ATS.
3) Move the Manual Bypass Handle (MBH) upward.
c. To Test ATS
1) Bypass per above instructions.
2) Rotate crank mechanism counterclockwise until ATS Test light is illuminated.
3) Turn DS to Auto.
4) Test Switch (TS) on bottom cabinet door will allow electrical operation of ATS.
d. To Isolate ATS
1) Bypass per above instructions.
2) Rotate crank mechanism counterclockwise until ATS Isolated light is illuminated.
e. To Remove ATS
1) Bypass and isolate per above instructions.
2) Disconnect multipin plugs and external connections to ATS.
3) Slide four corner latches of ATS to innermost position.
4) ATS can now be removed from cabinet.
f. To Reconnect ATS
1) Roll cart back into cabinet.
2) Slide four corner latches of ATS to outermost position.
3) Turn DS to Inhibit.
4) Manually position ATS into same source as bypass switch.
5) Reconnect multipin plugs and external connections to ATS.
6) Rotate crank mechanism clockwise until ATS Test light is illuminated.
7) Turn DS to Auto and use TS to electrically operate ATS.
8) Turn DS to Inhibit.
9) Rotate crank mechanism clockwise until ATS location pointer is aligned with Auto mark on location indicator (ATS must be in same source as bypass).
10) Turn DS to Auto and open bypass with MBH.
11) ATS is now fully automatic.
Notes:
1. DS in Inhibit will prevent ATS electrical operation.
2. DO NOT use excessive force on mechanical handles.
3. Figures depict Bypass Normal. Sequence is the same for Bypass Emergency.
4. When ATS is in Test or Isolate, bypass switch is a manual transfer switch to either available source (indicated on light panel).
5. To operate bypass switch when ATS is in Test or Isolate: a) Move MBH downward (to
open Bypass Contacts BN/BE)
b) Turn BSS to opposite power
source.
c) Move MBH upward to close
into selected power source.
Legend:
1. BP - Bypass Switch (indicated by contacts BN/BE) is a three position switch.
2. ATS - Automatic Transfer Switch.
ZBTSCTH Operation and Maintenance Manual (46R-7000)10 Zenith Controls, Inc.
SECTION II - OPERATION AND FEATURES (Continued)
5. ZENITH STANDARD PACKAGE
The Zenith Closed Transition Switch comes with the following standard features:
A3 Auxiliary contact closes when the switch is
in the Emergency position.
A4 Auxiliary contact closes when the switch is
in the Normal position.
DT Adjustable time delay before closing into
Normal source from open position (Open Transition Mode only).
DW Adjustable time delay before closing into
Emergency source from open position (Open Transition Mode only).
E Engine start contact closes to start the
engine generator when the Normal source fails. 1 N.O., 1 N.C. contact.
P1 Solid state adjustable timer with range from
0.5 to 6.0 seconds. The contact closes to start the engine generator.
T Adjustable time delay to transfer out of
Emergency source and into open position after Normal source is restored.
6. ZENITH OPTIONAL ACCESSORIES
Many control accessories are available to meet specific and special requirements. Your
drawings indicate which accessories were ordered with your switch.
U Adjustable time delay for engine cool down
after engine generator is signaled to shut down.
W Adjustable time delay to transfer out of
Normal source and into open position after Normal source failure.
ZBTSCTH Operation and Maintenance Manual (46R-7000)Zenith Controls, Inc. 11
SECTION III - MAINTENANCE AND TESTING
!
!
A preventive maintenance program will insure high reliability and long life for the transfer switch. The preventive maintenance program for the transfer switch should include the following items:
1. INSPECTION AND CLEANING
DANGER
HAZARDOUS VOLTAGE
(Can Cause Severe Injury or Death)
Turn OFF all power before installation, adjustment, or removal of transfer switch or
Before doing any work on the transfer switch, de-energize all sources of power. The switch should be inspected for any accumulation of dust, dirt, or moisture, and should be cleaned by vacuuming or wiping with a dry cloth or soft brush. DO NOT use a blower since debris may become lodged in the electrical and mechanical components and cause damage.
Remove the transfer switch barriers and check the condition of the contacts. Any surface deposits must be removed with a clean cloth (DO NOT USE EMERY CLOTH OR A FILE). If the contacts are pitted or worn excessively, they should be replaced. A general inspection of mechanical integrity should be made to include loose, broken or badly worn parts.
2. SERVICING
All worn or inoperative parts must be replaced using Zenith recommended replacement parts. Appendix B at the back of this manual includes replacement part information for typical power and control panel configurations. When ordering parts provide the model number or serial number from the transfer switch rating nameplate.
The operating mechanism of the transfer switch is lubricated with Lubriplate 105. The lubricant applied at the factory provides adequate lubrication for the lifetime of the switch. Should debris contaminate the mechanism, clean and apply additional Lubriplate.
3. TESTING
After completing the inspection, cleaning and servicing of the transfer switch, reinstall the switch cover, and close and lock the cabinet door. Reclose the circuit breakers feeding the utility and generator sources to the switch.
Initiate the electrical transfer test by activating the TS test switch. This de-energizes the engine start relay. The transfer switch closes into Emergency only after the sync-check relay ensures the proper phase relationship of both sources. After the transfer switch closes into Emergency, the SE limit switch becomes activated to de-energize the CCE relay and energize the CCNO relay. This opens the transfer switch out of Normal. When the transfer switch has opened out of Normal, the SNO-2 limit switch activates to de-energize the CCNO relay. The transfer switch has now closed into emergency power without interrupting the load.
Turning the TS to AUTO initiates re-transfer to Normal. The transfer switch closes into Normal, only after the sync-check relay ensures the proper phase relationship of both sources. After the transfer switch closes into Normal, the SN limit switch becomes activated to de-energize the CCN relay and energize the CCEO relay; the transfer switch opens out of Emergency. Then the SEO-2 limit switch activates to de-energize the CCEO relay. The transfer switch has now closed back into normal power without interrupting the load.
The transfer switch defaults to an open transition transfer when the Normal source fails. Closed transition transfer is not possible with one source available. Open transition transfer for testing can be selected via the transition mode selector switch.
A 24 VDC circuit is supplied to control the alarm and warning indicators. To insure continuous power to this circuit, a constant 24 VDC can be supplied by the customer from the engine start battery.
NOTICE
A periodic test of the transfer switch under load conditions is recommended to insure proper operation.
ZBTSCTH Operation and Maintenance Manual (46R-7000)12 Zenith Controls, Inc.
SECTION III - MAINTENANCE AND TESTING (Continued)
4. TROUBLESHOOTING
Before beginning any troubleshooting activity, refer to the information package supplied with the transfer switch and review the description and operation of all accessories supplied. Also refer to Section II of this manual, Operation and Features.
CONDITION ITEMS TO BE CHECKED
a. Engine-Generator Does Not Start
when Normal source fails or Test Switch (TS) is activated.
b. Does Not Transfer To Emergency
after generator starts.
c. Does Not Retransfer To Normal
when Normal source restores or Test Switch (TS) is deactivated.
d. Engine-Generator Does Not
Shutdown
Normal.
after retransfer to
1) Verify the setting of the time delay P1.
2) Make sure timer P1 drops out and the engine-start contact closes after time delay is completed.
3) Make sure the starting battery is charged and connected to the engine-generator.
4) Generator controls in Automatic mode.
5) Verify wiring of the engine-start contact If the generator does not start, contact the generator dealer.
1) If in Closed Transition Mode: a) Verify that the phase angle difference between
Normal and Emergency is < 5° (@ 0.1 Hz f).
b) Verify that the frequency difference between
Normal and Emergency is < 0.2 Hz (0.1 Hz is recommended). Also verify that the frequency difference is not 0 Hz.
c) Verify that the voltage difference between Normal
and Emergency is < ±5% of nominal.
d) Verify that the phase sequence is the same for
Normal and Emergency.
2) Emergency source breaker should be closed.
3) Emergency source voltage and frequency should meet the preset pickup values of the VFSM relay.
4) Make sure Emergency control relay RT picks up after time delay W.
1) If in Closed Transition Mode: a) Verify that the phase angle difference between
Normal and Emergency is < 5° (@ 0.1 Hz f).
b) Verify that the frequency difference between
Normal and Emergency is < 0.2 Hz (0.1 Hz is recommended). Also verify that the frequency difference is not 0 Hz.
c) Verify that the voltage difference between Normal
and Emergency is < ±5% of Nominal.
d) Verify that the phase sequence is the same for
Normal and Emergency.
2) Normal source voltage should meet the preset pickup value of the phase relays.
3) Make sure Normal control relay CR picks up after time delay T.
4) Verify the circuit connections from the power relay, CN1 or CCN, to the Normal switch operating circuit.
5) Verify the circuit connections from the power relay, CE1 or CCE, to the Emergency switch operating circuit.
1) Verify the setting of engine overrun time delay U.
2) Make sure timer P1 picks up and the engine-start contact has opened.
3) Generator controls in Automatic mode.
4) Verify wiring of the engine-start contact.
ZBTSCTH Operation and Maintenance Manual (46R-7000)Zenith Controls, Inc. 13
SECTION III - MAINTENANCE AND TESTING (Continued)
5. EMERGENCY SERVICE PROCEDURE FOR EXTENDED PARALLEL TIME
a. Auto Location:
Removal of closed transition transfer switch after Emergency breaker shunt trip.
1) Disconnect all power sources from bypass-isolation transfer switch.
2) Open the bottom cabinet door and turn the Disconnect Switch (DS) to the OFF position.
3) Remove the service access cover on the left hand side of the transfer switch.
4) The manual operator and the manual handle will now be exposed. Insert the handle into the Emergency side manual operator. Open the Emergency side contacts.
5) Close bottom cabinet door.
6) Energize Normal power.
7) Close the bypass contacts (BN) as described in Section II of this manual.
8) Isolate the transfer switch as described in Section II.
9) Remove the transfer switch from the bypass-isolation transfer switch as indicated on the bypass instruction label to inspect and repair.
10)Re-install the transfer switch after maintenance with contacts closed to the same source as the bypass switch. Re­install the manual handle in its holder and the service access cover on the left side of the transfer switch.
11)Re-connect the transfer switch to AUTO, as described in Section II.
b. Auto Location:
Removal of the closed transition transfer switch if Normal and Emergency contacts remain open.
1) Turn the BSS to an available source. Close the bypass switch into the
available source as described in
Section II of this manual.
2) Turn the DS to INHIBIT. Remove the transfer switch service access cover. Close the transfer switch into the same source as the bypass switch. (Incorrect sequencing is prevented by the interlocks while the transfer switch is in AUTO only.)
3) Remove the transfer switch from the bypass-isolation transfer switch as indicated in Section II to inspect and repair.
c. Test Location:
Removal of the closed transition transfer switch if both Normal and Emergency contacts remain open.
1) Close the bypass switch contacts (BN) as indicated on the bypass instruction label on the cabinet door.
2) Disconnect all power sources from bypass-isolation closed transition transfer switch.
3) Open bottom cabinet door. Turn the Disconnect Switch (DS) to the OFF position.
4) Remove the service access cover on the left side of the transfer switch.
5) The manual operator and the manual handle will not be exposed. Insert the handle into the Normal side and close the Normal contacts.
6) Close the bottom cabinet door.
7) Energize Normal power.
8) Remove the automatic transfer switch from the bypass-isolation transfer switch as indicated in Section II.
9) Re-install the transfer switch after maintenance with contacts closed to the same source as the bypass switch. Re­install the manual handle in its holder and the service ccess cover on the left side of the transfer switch.
10)Re-connect the transfer switch to AUTO, as indicated in Section II.
ZBTSCTH Operation and Maintenance Manual (46R-7000)14 Zenith Controls, Inc.
SECTION III - MAINTENANCE AND TESTING (Continued)
Model Number
Serial Number
Date Shipped
Start-Up Date
Drawings Supplied
FIELD NOTES
Test And Maintenance Notes
Date
Tested Observations Notes
ZBTSCTH Operation and Maintenance Manual (46R-7000)Zenith Controls, Inc. 15
SECTION IV - ADJUSTMENTS AND SETTINGS (Continued)
!
1. PARALLELING RELAY SETTINGS
25, 27/59N & 27/59E are factory set to allow paralleling of the sources only when these conditions have been met:
a. Phase Angle Differences < 5° (@ 0.1 Hz f) b. Frequency Difference < 0.2 Hz c. Voltage Difference < ±5% Nominal
NOTES:
1. This system requires an isochronous governor with an operating frequency of 60 ± 0.2 Hz.
2. Requires a shunt trip breaker on generator set with a response time not exceeding 50 ms.
2. SOLID STATE TIMERS
Solid state timers are adjustable from 0.1 second to 100 hours. The red timing indicator in the upper left corner flashes as the timer progresses through the timing cycle. When the timing cycle is completed, the indicator remains illuminated. A flathead screwdriver is required to change the setting, as shown in Figure 5 below.
CAUTION
Do NOT change the setting while the timer is energized. Timer malfunction or damage may
The factory setting of the solid state timers used in the Zenith standard package are shown in Table 5 below.
Timer Factory Setting
T U
W
DT
DW
ST
PART
OLC
ETT
Table 5
30 minutes
5 minutes
1 second 5 seconds 5 seconds
1 second
0.002 sec,
0.275 sec.
0.420 sec.
3. VOLTAGE/FREQUENCY SENSOR (VFSM)
Figure 5
The time unit is selected by turning the rotary switch at the lower right of the timer. Four selections are available: “Seconds”, “Minutes”, “Hours”, “10 Hours”. The time unit selected is displayed in the window below the time setting dial.
The time range is selected by turning the rotary switch at the lower left of the timer. Four ranges are available: “0-0.5”, “0-1.0”, “0-5.0”, “0-10.0”. The dial digits appear in the windows around the time setting knob.
The pickup point may be adjusted by rotating the adjustment screw as shown in Figure 6 below. Counter-clockwise rotation increases the pickup voltage.
Figure 6
Pickup Voltage (at 100% Frequency)
Adjustable: 80% to 95% Factory Set: 90%
Pickup Frequency
Adjustable: 80% to 100% Factory Set: 95%
ZBTSCTH Operation and Maintenance Manual (46R-7000)16 Zenith Controls, Inc.
SECTION IV - ADJUSTMENTS AND SETTINGS (Continued)
4. SOLID STATE PHASE RELAY (ARSM)
The pickup and dropout points may be adjusted by using the following procedure. Use of a variable voltage supply (Variac) is required. The relay is illustrated in Figure 7 below.
Figure 8
a. Turn both DIFF adjustments fully counter-
clockwise.
b. Undervoltage sensing - Use lowest phase to
phase relationship on Variac to set the relay. Set Variac voltage to desired undervoltage setting. Turn undervoltage SET adjustment fully clockwise, then slowly counterclockwise
until the LED illuminates. c. Overvoltage sensing - Use the highest phase to phase voltage relationship on Variac to set
the relay. Set Variac voltage to desired
overvoltage. Turn overvoltage SET adjustment
fully clockwise, then counterclockwise until
LED illuminates.
Figure 7
a. Turn the pickup adjustment fully clockwise. b. Turn the dropout adjustment fully counter-
clockwise. c. Set Variac to the desired pickup voltage. d. Rotate the pickup adjustment counterclock-
wise very slowly until the relay picks up. The
LED will illuminate. e. Set Variac to the desired dropout voltage. f. Rotate the dropout adjustment clockwise very
slowly until the relay drops out. The LED will
go out. g. Verify the setting by raising the voltage until
the relay picks up and lowering the voltage
until the relay drops out. Pickup Voltage: 75% to 115% of Nominal
Factory Set: 90% of Nominal Dropout Voltage: 55% to 105% of Nominal Factory Set: 80% of Nominal
5. PARALLELING WINDOW UNDER-
OVERVOLTAGE SENSING RELAY
Undervoltage: 75-100% of 120V Factory Set: 95% Overvoltage: 100-125% of 120V Factory Set: 105%
6.ELECTRONIC TIME SWITCH Z2000-2A
This time switch is used for the C/D option. Time switch Z2000-1A is used for the C option.
a. Setting Time and Day:
Press and hold “ ” button during the Following adjustments:
1) Press “d” to set day pointer to correct day:
1 = Monday...7 = Sunday
2) Press “h” to set the hour. The time of day is
expressed in 24-hour military time:
04:00 = 4 a.m.....20:00 = 8 p.m.
3) Press “m” to set minutes
4) Release “ ” button. Clock is running
The pickup and dropout points may be adjusted by using the following procedure. Use of a variable voltage supply (Variac) is required. The relay is illustrated in Figure 8.
ZBTSCTH Operation and Maintenance Manual (46R-7000)Zenith Controls, Inc. 17
SECTION IV - ADJUSTMENTS AND SETTINGS (Continued)
c. Program Review and Change:
Press Prog button to recall and review the C1 and“C2 On/Off times. An E is displayed if all 24 positions are used or if the next available position is not filled.To change or clear a program, press Prog button to find the program to be changed or cleared. Change by pressing d, h or m buttons as required. Clear the entire program by simultaneously pressing “h” and “m”. Press “ ” to return to the clock run mode.
d. Program Override:
Figure 9
b. Programming:
Twenty-four total ON or OFF settings are available on one, several, or all days of the week.
1) Press Prog button. The blank program entry fieldwillappearwith twoflashingpoints: “__:__”
2) Press either C1 or C2 depending on which channel you wish to program.
3) Next, select either On or Off by pressing C1 or C2 which toggles the On/Off mode.
4) You will now see the pointer flashing above 1 for Monday. To lock in Monday, press Prog. If you want to enter further days, press d then Prog to lock them in. Solid pointers must be displayed over each day that the switching command is required.
5) Once the days are selected, press h button to enter the desired hour and press m to enter the desired minutes. To enter the program into the time switch, press Prog. When the programming is complete, press “ ” to return the clock run mode. If the “ ” button is not depressed, it will switch to the clock run mode after 60 seconds.
Each On/Off state can be manually changed by pressing C1 or C2. The next counteracting program cancels the manual override and resumes previous programming.
To continuously override automatic programming, press m and C1 or C2. The continuous override On/Off stat is preceded by a black dot on the display. To cancel, press m and C1 or C2 until the dot disappears.
The automatic program can be continuously overridden up to 47 days by pressing and holding h while pressing C1 or C2 until the display shows the number of days desired. Starting the following day at “0:00”, the display will show a “0:00”, both C1 and C2 off, and an H in the lower right hand corner.
ZBTSCTH Operation and Maintenance Manual (46R-7000)18 Zenith Controls, Inc.
APPENDIX A - TYPICAL SCHEMATIC DIAGRAMS
1. 100-400 AMPS
ZBTSCTH Operation and Maintenance Manual (46R-7000)Zenith Controls, Inc. 19
APPENDIX A - TYPICAL SCHEMATIC DIAGRAMS (Continued)
2. 600-3000 AMPS
ZBTSCTH Operation and Maintenance Manual (46R-7000)20 Zenith Controls, Inc.
APPENDIX A - TYPICAL SCHEMATIC DIAGRAMS (Continued)
3. ALARM CIRCUIT SCHEMATIC
4. 3φ CONTROL SENSING SCHEMATIC
ZBTSCTH Operation and Maintenance Manual (46R-7000)Zenith Controls, Inc. 21
APPENDIX A - TYPICAL SCHEMATIC DIAGRAMS (Continued)
5. BYPASS CONTROL CIRCUIT
a. 100-400 Amp
b. 600-3000 Amp
ZBTSCTH Operation and Maintenance Manual (46R-7000)22 Zenith Controls, Inc.
APPENDIX B - REPLACEMENT PARTS
!
NOTICE
Model number and serial number of switch must be included with all orders for replacement parts. Specify line voltages, drawing numbers and date of installation. When ordering parts not shown on the parts list, refer to this part by its legend description in the wiring diagrams.
1. POWER PANEL 100-400 AMPS
2. POWER PANEL 600-1200 AMPS
ZBTSCTH Operation and Maintenance Manual (46R-7000)Zenith Controls, Inc. 23
APPENDIX B - REPLACEMENT PARTS (Continued)
3. POWER PANEL 1600-3000 AMPS
5. BYPASS SUBPANEL4. POWER PANEL 4000 AMPS
ZBTSCTH Operation and Maintenance Manual (46R-7000)24 Zenith Controls, Inc.
APPENDIX B - REPLACEMENT PARTS (Continued)
Power Panel Replacement Parts List 100-400 Amps
Tag Description 100A 150A 225A 260A 400A
NL1,2,3 EL1,2,3 Cable Connection Lug, PS-4418 PS-4418 PS-4418 S-1422 S-1422 T1,2,3 CU Wire NLN, ELN, TN
Bypass Contact Assembly (Movable and Stationary)
N1,2,3 Normal 46P-1104A 46P-1104B 46P-1104C 46P-1104D 46P-1104E N (Sw. Neutral Normal) 46P-1105A 46P-1105B 46P-1105C 46P-1105D 46P-1105E E1,2,3 Emergency 46P-1106A 46P-1106B 46P-1106C 46P-1106D 46P-1106E E (Sw. Neutral Emergency) 46P-1107A 46P-1107B 46P-1107C 46P-1107D 46P-1107E
ATS Contact Assembly (Movable and Stationary)
NL1,2,3 Normal 46P-1100A 46P-1100B 46P-1100C 46P-1100D 46P-1100E N (Sw. Neutral Normal) 46P-1101A 46P-1101B 46P-1101C 46P-1101D 46P-1101E EL1,2,3 Emergency 46P-1102A 46P-1102B 46P-1102C 46P-1102D 46P-1102E N (Sw. Neutral Emergency) 46P-1103A 46P-1103B 46P-1103C 46P-1103D 46P-1103E Arc Grid Assy. 46P-1099
Voltage Part No.
120/240 K-3061
Bypass Step-Down 208/416 K-3063
XBN, XBE Transformer 220/440 K-3064
Secondary 24V 240/480 K-3062
380 K-3067 575 K-3065 600 K-3066
Main ATS Operating Coils
No. Volts Ph Wire Coil Volts Poles Part No.
-1 120 1 2 120 2 K-2178
-2 120/240 1 3 240 2, 3
-3 240 3 3 240 3 K-2189
-38 120/240 3 4 240 3, 4
CN/O & CE/O -4 120/208 3 4 208 3, 4 K-2177
-5 480 3 3 480 3 K-2176
-6 575/600 3 3 575/600 3 SPO
-7 277/480 3 4 480 3, 4 K-2176
-9 240/416 3 4 416 3, 4 SPO
-91 220/380 3 4 380 3, 4 K-2188
SN/SEO SE/SEO A3 A4
SCN/O & SCE/O CN/O & CE/O Limit Switches L-3079 AA AE1,2 PLS1,2
AI
AT1,2
AB3/ABE
AB4/ABN
NA4
EA3
BTE
BTN
TSE
BLL
ALL
DS ATS Solenoid Disconnect Switch:
BPS
TRS
Normal Position Limit Switch Emergency Position Limit Switch ATS Emergency Position Switch ATS Normal Position Switch
ATS Auto Location Switch ATS Isolate/Remove Location Switch Position Lever Switch ATS Isolate Location Switch ATS Test Location Switch Bypass Emergency Position Switch Bypass Normal Position Switch Normal TRS Limit Switch Emergency TRS Limit Switch Bypass Emergency Position Switch Bypass Normal Position Switch ATS Engaged Switch Bypass Lock Location Switch ATS Lock Location Switch
Operator 2-Position Maintain L-4018 Contact Block N.C. (3) L-1029 Contact Block N.O. (2) L-1028 Contact Block Mounting Plate PS-3473 Bypass Interlock Solenoid Transfer Release Solenoid
L-3002
L-3071
L-3070
L-5021
L-3054
K-2180
ZBTSCTH Operation and Maintenance Manual (46R-7000)Zenith Controls, Inc. 25
APPENDIX B - REPLACEMENT PARTS (Continued)
Power Panel Replacement Parts List 600-1200 Amps
Tag Description 600A 800A 1000A 1200A
N 1,2,3,N Normal Connections CU/AL Cable Lugs S-2119
(2) 600MCM-2
E 1,2,3,N Emergency Connections CU/AL Cable Lugs S-1393F
(2) 600MCM-2
T 1,2,3,N Load Connections CU/AL Cable Lugs S-1393F
(2) 600MCM-2 STAT (BP) Stationary Contact Assembly Bypass 26P-1144 26P-1126 26P-1126 26P-1126 STAT (ATS) Stationary Contact Assembly ATS 26P-1144 26P-1126 26P-1126 26P-1126 ARC Arc Grid Assembly Kit 23P-1366 MOV Movable Contact Assembly 23P-1157 23P-1125 26P-1125 26P-1125
Movable Contact (Switched Neutral) 23P-1157 26P-1231 26P-1231 26P-1231
Voltage Part No.
120/240 K-3061
Bypass Step-Down 208/416 K-3063
XBN, XBE Transformer 25VA, 220/440 K-3064
Secondary 24V 240/480 K-3062
380 K-3067 575 K-3065 600 K-3066
Main ATS Operating Coils
Voltage Systems
No. Volts Ph Wire Coil Volts Poles Part No.
-1 120 1 2 120 2 SPO
-2 120/2401 3 240 2 SPO
S-2131
(3) 600MCM-2
S-1391F
(3) 600MCM-2
S-1391F
(3) 600MCM-2
S-2132
(4) 600MCM-2
S-1392F
(4) 600MCM-2
S-1392F
(4) 600MCM-2
S-2132
(4) 600MCM-2
S-1392F
(4) 600MCM-2
S-1392F
(4) 600MCM-2
CN/CNO 3 CE/CEO -3 240 3 3 240 3 K-2146 K-2147
-4 120/2083 4 208 3, 4
-5 480 3 3 480 3 K-2158 K-2157
-7 277/4803 4 480 3, 4
-9 240/4163 4 416 3, 4 SPO
SN/SNO-1,2 SN/SNO-3,4 SE/SEO-1,2 SE/SEO-3,4 A3 ATS Emergency Position Switch L-5021 A4 ATS Normal Position Switch
AA AT ACU/ACD AI AE
AB3 AB4 ASE ASN DS
CBE CBN CBC Crank Mechanism Solenoid K-2159 RN/RNO RE/REO
ATS Normal Position Coil Cutout Switch DPDT ATS Emergency Position Coil Cutout Switch DPDT
Limit Switch, DPDT Roller Actuator
ATS Auto Location Switch ATS Test Location Switch Crank Limit Switches ATS Isolate Location Engine Start Transfer
Limit Switch, DPDT Lever Actuator
Bypass Emergency Position Switch Bypass Normal Position Switch BSS Emergency Position Switch BSS Normal Position Switch
ATS Solenoid Disconnect Switch
Operator 2-Position Maintain L-4009 Contact Block N.C. (3) L-1020 Contact Block N.O. (2) L-1024 Emergency Interlock Solenoid Normal Interlock Solenoid
Coil Rectifiers 23P-1473
23P-1533 23P-1535 23P-1534 23P-1536
L-3052
L-3054, L-3052
L-3054 L-3052 L-3052
L-5021
K-2192
ZBTSCTH Operation and Maintenance Manual (46R-7000)26 Zenith Controls, Inc.
APPENDIX B - REPLACEMENT PARTS (Continued)
Power Panel Replacement Parts List 1600-4000 Amps
Tag Description 1600/2000A 3000A 4000A
NL1,2,3 EL1,2,3
XBN, XBE Transformer 25VA, 220/440 K-3064
CN/O & CE/O -5 480 3 3 480 3 K-2160 K-2218
Cable Connection at Rear S-1302F(2)
Optional T1,2,3
(8) 600MCM-2 Stationary Contact Assembly Bypass and ATS S-2308 S-2343 23P-1655 Arc Grid Assembly Kit 23P-1171 Movable Contact Assembly 23P-1400 23P-1344 23P-1640 Movable Contact 23P-1399 23P-1338 SPO
Voltage Part No.
120/240 K-3061
Bypass Step-Down 208/416 K-3063
Secondary 24V 240/480 K-3062
380 K-3067 575 K-3065 600 K-3066
Main ATS Operating Coils
Voltage Systems
No. Volts Ph Wire Coil Volts Poles Part No.
-1 120 1 2 120 2 SPO 120/24
-2
-3 240 3 3 240 3 120/20
-4
-6 575 3 3 600 3 SPO 277/48
-7 120/24
-8 240/41
-9
1 3 240 2, 3
0
K-2151 K-2219
3 4 208 3, 4
8
3 4 480 3, 4 K-2160 K-2218
0
2 4 240 4 K-2151 K-2219
0
3 4 416 3, 4 Consult Zenith Factory K-2220
6
SN/SNO Limit Switch 23P-1540 SE/SEO Limit Switch 23P-1541 A3 ATS Emergency Position Switch 23P-1543 A4 ATS Normal Position Switch 23P-1542 AA AT AI
AE
AB3 AB4 DS ATS Solenoid Disconnect Switch:
CBE CBN CBC Crank Enable Solenoid K-2159R CH Crank Handle Limit Switch L-3052 RN/RNO RE/REO
ATS Auto Location Switch ATS Test Location Switch ATS Isolate Location Switch
Limit Switch DPDT, Roller Actuator
Engine Start Transfer L-3052
Limit Switch DPDT, Lever Actuator
Bypass Emergency Position Switch Bypass Normal Position Switch
Operator 2-Position Maintain Contact Block N.C. (1) Contact Block N.O. (2) Emergency Interlock Solenoid Normal Interlock Solenoid
Coil Rectifiers 23P-1473
L-3071
L-5021
L-4018
L-1020 L-1024 K-2192
23P-1582 (480VAC)
ZBTSCTH Operation and Maintenance Manual (46R-7000)Zenith Controls, Inc. 27
APPENDIX B - REPLACEMENT PARTS (Continued)
5. CONTROL PANEL LAYOUT AND PARTS LIST
28 Zenith Controls, Inc.ZBTSCTH Operation and Maintenance Manual (46R-7000)
APPENDIX B - REPLACEMENT PARTS (Continued)
Closed Transition Transfer Switch Control Panel Parts List
Tag Description Voltage Part No. CR2 Normal Control Relay 120 VAC K-1204 DT Transfer Delay Timer Neutral to Normal 120 VAC K-1230 DTR Normal Transfer Latch Relay 120 VAC K-1204 DW Transfer Delay Timer Neutral to Emergency 120 VAC K-1230 DWR Emergency Transfer Latch Relay 120 VAC K-1204 EFOAR Relay, Emergency Fail to Open Alarm 24 VDC K-1242 EFOR Emergency Fail to Open Latching Relay 120 VDC K-1240 ETT Emergency Trip Timer 120 VAC K-1230 LTCS Latch Test Cycle Start 120 VAC K-1204 NFOAR Relay, Normal Fail to Open Alarm 24 VDC K-1242 NFOR Normal Fail to Open Latching Relay 120 VDC K-1240 OLC Open Last Close 120 VAC K-1230 PAR Power Available Relay 120 VAC K-1204 PART Power Available Timer 120 VAC K-1249 PT1,2,3,4 Potential Transformers 120 /480 VAC K-3094
120/240 VAC K-3095
120/208 VAC K-3096 RAI Normal Available Relay 120 VAC K-1204 RAE Emergency Available Relay 120 VAC K-1204 RTCS Relay Test Cycle Start 240 VAC K-1256 SCL Sync Check Latch Relay 120 VAC K-1204 ST Sync Timer 120 VAC K-1230 STR Shunt Trip Relay 120 VDC K-1240 XNE Normal/Emergency Control Transformers 24/120 VAC K-3061
SSRCP Control Panel Standard Items Parts List
Tag Description Voltage Part No.
XN, XE Control Transformer 208 VAC K-3070
240/480 VAC K-3071
B1,2,3 Solid State Phase Relay 208/240 VAC K-1186
480 VAC K-1188 VFSM Voltage Frequency Sensor 120 VAC K-1192 CR Control Relay 120 VAC K-1204 RT Bypass T Relay 120 VAC K-1204 J1-J11 Jumpers - PS-5067 T Time Delay to Normal, Timer Solid State 120 VAC (Adjustable .1
second to 9990 hours)
U Engine Cool Down, Timer Solid State 120 VAC (Adjustable .1
second to 9990 hours)
W Time Delay to Emergency, Timer Solid State 120 VAC (Adjustable .1
second to 9990 hours)
P1 Time Delay Engine Start, Timer 120 VAC (Adjustable
.5 to 6 seconds)
ZBTSCTH Operation and Maintenance Manual (46R-7000)Zenith Controls, Inc. 29
K-1230
K-1230
K-1230
K-1201
APPENDIX B - REPLACEMENT PARTS (Continued)
Closed Transition Transfer Switch Control Panel (Standard Items)
Tag Description Voltage Part No. 25 Sync Check Relay 120 VAC K-1234 47N Phase Sequencing, Normal 120 VAC K-1246 47E Phase Sequencing, Emergency 120 VAC K-1246 27/59E Over/Undervoltage, Emergency 120 VAC K-1269 27/59N Over/Undervoltage, Normal 120 VAC K-1269 AS Alarm Silence Relays 24 VDC K-1242 CCN Power Relay for CN Solenoid 120 VAC K-1120 400-1200A
K-1257 1600-3000A CCNO Power Relay for CNO Solenoid 120 VAC K-1120 CCE Power Relay for CE Solenoid 120 VAC K-1120 400-1200A
K-1257 1600-3000A CCEO Power Relay for CEO Solenoid 120 VAC K-1120
Bypass Control Panel Parts List
Tag Description Part No. BR-1,2,3 Bridge Rectifier PS-5076 RNH Normal Voltage Relay K-1218 R1 Resistor, RNH, 30 ohm PS-4056 R2 Resistor, LDS, 120 ohm PS-4057 D1 Diode PS-4812 C Capacitor RNH PS-4058 ATR Auxiliary Test Relay K-1218
30 Zenith Controls, Inc.ZBTSCTH Operation and Maintenance Manual (46R-7000)
APPENDIX B - REPLACEMENT PARTS (Continued)
6. CABINET DOOR PILOT DEVICES
BYPASS-ISOLATION CLOSED TRANSITION
TRANSFER SWITCH CONTROLS
ZBTSCTH Operation and Maintenance Manual (46R-7000)Zenith Controls, Inc. 31
APPENDIX B - REPLACEMENT PARTS (Continued)
Controls and Indicating Lights Parts List
Controls Part No.
Description Operator Switch Mounting Base
Transition Mode Selector L-3081 L-1028 (4)
L-1029 (2) Test Switch L-3081 L-1029 Failed to Open Lock Out Reset L-4020 L-1028 PS-3473 Shunt Trip Reset L-4020 L-1028 Alarm Silence Push Button (ASPB) L-1025 L-1028
L-1029
Alarm Y780001
Indicating Lights (Upper Door) Part No.
Description Color Socket Bulb Lens
Normal Available Green PS-5048 Emergency Available Red PS-5047 Bypass Normal Location Green PS-5048 Bypass Emergency Location Red PS-5046 Y500005 PS-5047 ATS Test Position Amber PS-5049 ATS Isolate Position Amber PS-5049 ATS Inhibit Red PS-5047 ATS Disconnect Switch “Off” Red PS-5047
Indicating Lights (Lower Door) Part Numbers
Description Color Socket Bulb Lens
Normal Available Green PS-5048 Emergency Available Red PS-5046 PS-5105 PS-5047 Normal Closed Green PS-5048 Emergency Closed Red PS-5054 PS-5047 Sync Light White Y500005 PS-5051 Fail To Sync Light Red PS-5105 Normal Failed To Open Red PS-5046 Y500005 Emergency Failed To Open Red Y500005 PS-5047 Shunt Trip Light Red PS-1272 Alarm Silence (ASL) Red Y500005
32 Zenith Controls, Inc.ZBTSCTH Operation and Maintenance Manual (46R-7000)
830 West 40th Street
Chicago, IL 60609 USA
Phone: 773 247-6400
Fax: 773 247-7805
E-Mail: zenith@zenithcontrols.com
www.zenithcontrols.com
© 1997 Zenith Controls, Inc.
Loading...